APPLICATIONNOTE GENERATORSETDESIGNPARAMETERS

Shri Karve

November 2012

ECI Publication No Cu0158

Available from www.leonardo-energy.org/node/156613

Page 2: Set Design Parameters

7/25/2019 Set Design Parameters

http://slidepdf.com/reader/full/set-design-parameters 2/12

Publication No Cu0158

Issue Date: November 2012

Page i

Document Issue Control Sheet

Document Title: Application Note – Generator Set Design Parameters

Publication No: Cu0158

Issue: 01

Release: November 2012

Author(s): Shri Karve

Reviewer(s): Bruno De Wachter

Document History

Issue Date Purpose

1 November2012

Initial publication, in the framework of the Good Practice Guide

2

3

Disclaimer

While this publication has been prepared with care, European Copper Institute and other contributors provideno warranty with regards to the content and shall not be liable for any direct, incidental or consequentialdamages that may result from the use of the information or the data contained.

Copyright© European Copper Institute.

Reproduction is authorised providing the material is unabridged and the source is acknowledged.

Page 3: Set Design Parameters

7/25/2019 Set Design Parameters

http://slidepdf.com/reader/full/set-design-parameters 3/12

Publication No Cu0158

Issue Date: November 2012

Page ii

CONTENTS Summary ........................................................................................................................................................ 1

Introduction .................................................................................................................................................... 2

Basic functions of Generator sets ................................................................................................................... 2

Different types of generator sets .................................................................................................................... 2

Main components of generator sets ............................................................................................................... 3

The Diesel Engine.................................................................................................................................................... 3

The Engine exhaust pipes and silencers .......................................................... ....................................................... 3

Acoustic Noise abatement ......................................................... ................................................................. ............ 4

The Alternator ........................................................................................................................................................ 4 Generator set frame ................................................................. ............................................................... ............... 4

AMF Panel .................................................................................................................. ............................................. 4

Typical components on control panels and generating units .......................................................... ....................... 5

Generator set sizing ........................................................................................................................................ 6

Generator set maintenance ............................................................................................................................ 8

Conclusion ...................................................................................................................................................... 9

References ...................................................................................................................................................... 9

Page 4: Set Design Parameters

7/25/2019 Set Design Parameters

http://slidepdf.com/reader/full/set-design-parameters 4/12

Publication No Cu0158

Issue Date: November 2012

Page 1

SUMMARY The intention of this paper is to look at various aspects of generator sets (gensets) utilised globally to providemedium to long term backup power, and to improve system availability and reliability. Critical locations andapplications depend on generators for back-up power. Examples of such critical locations are hospitals,

airports, government buildings, telecommunications facilities, data centres, and nuclear power plants. Withinthis paper we intend to cover the main components of gensets, general applications, different fuels utilised,size selection, environmental issues, maintenance and noise pollution. The main emphasis of this documentwill be towards selection of gensets for critical loads and system availability.

Page 5: Set Design Parameters

7/25/2019 Set Design Parameters

http://slidepdf.com/reader/full/set-design-parameters 5/12

Publication No Cu0158

Issue Date: November 2012

Page 2

INTRODUCTION Although the public utilities are fairly reliable in developed countries, even the best utility systems areinadequate to meet the demands of critical loads. In the event of utility failure, the UPSs and/or generator setscan provide the necessary backup.

As the time and length of blackouts are unpredictable, critical applications require backup for the worst casescenario. Applications can be labeled critical because of the risk of a high financial loss, or because there is ahealth and safety risk involved, or both. The nature of criticality is different for each application:

Some applications, such as continuous production lines, incorporate high financial losses in case offrequent short interruptions, but can be subject to the occasional longer black out.

Other applications, such as the air-conditioning systems of a hospital or a data centre, can besubjected to short interruptions, but require backup for any longer black out.

For a third category of applications, such as operating theatre or a data centre server farm, any shortor long interruption should be avoided at any cost.

While UPS systems deal with short term power disturbances, gensets take over in case of any longer blackouts.

Standby power systems used to be specified merely on technical requirements, international standards, andlocal electrical codes. However, with growing dependence on virtually perpetual source of electric power, inrecent times, sizing and specifying has become a business decision. Such a decision also incorporates thoroughfinancial evaluation and an economic risk assessment process.

BASIC FUNCTIONS OFGENERATOR SETS In simple terms, the generator converts the stored fuel source into electrical energy to provide back up to theload. Popular fuels are gas or diesel depending on load characteristics. As stated previously, generator sets aremainly utilized to provide necessary backup for extended utility failure. Automatic mains failure (AMF)detection is normally included within the critical power system design. As soon as mains supply fails, AMFhelps to start the generator automatically to provide support for the load. The unit is expected to start upwithin few seconds to protect the load in a stable and sustained manner. Output from the generator set will becompatible with the needs of the application, and with a minimum voltage harmonic distortion (THDU).Output frequency stability and Slew Rate (rate of change of frequency -Hz/Sec) of the gensets need to becompatible with the load.

DIFFERENT TYPES OF GENERATOR SETS Diesel generators are normally used for standby and base load (continuous) applications. Gas powered unitsare mainly utilized for Combined Heat and Power (CHP) type applications. There are some generators that usevegetable oil to achieve a low carbon footprint. Utility failures are unpredictable and hence the generator setmust always be ready to start and pick up the load without prior warning. For this reason, such generators arerefer red to as ‘Standby Generators’. Smaller and medium size generators have low voltage (400Volts) output.Larger machines with ratings of 1600 KVA or higher, may have high voltage (10k volts) output. This paper willfocus mainly on low voltage standby diesel generators, since they project major share of the generator market.

Page 6: Set Design Parameters

7/25/2019 Set Design Parameters

http://slidepdf.com/reader/full/set-design-parameters 6/12

Publication No Cu0158

Issue Date: November 2012

Page 3

MAIN COMPONENTS OF GENERATOR SETS

THE DIESELENGINE

Internal combustion diesel engines comprise the vast majority of prime movers for standby power generators,due to their reliability, durability and performance under load.

The diesel engine drives the alternator via a suitable coupling. The engine’s fuel supply is normally provided bya day tank, and installed very close to the engine (see Figure 1). The bulk fuel tank is typically kept outside thegenerator plant room with adequate capacity to meet the design specification. Trace heating of the fueltransfer pipes and the bulk fuel tank is recommended for locations with low ambient temperature. The localPollution Control Regulation may require that the bulk fuel storage tank has a secondary containmentstructure i.e. a bund. If Biodiesel blends of fuel are utilised then it is worth noting issues concerningsedimentation and gum formation due to long term storage. During engine operation, sediments can causeblockage of fuel filter and can foul the fuel intake system. The gum accumulation may also lead to sticking ofengine moving parts e.g. fuel injectors and valves. In some EU countries the Biodiesel will include additives toensure compliance with local standards for oxidation stability and to make it suitable for storing for aminimum period of six months. In order to achieve a quick engine start, it is recommended that the enginecoolant and lubrication systems are continuously preheated in line with manufacturers recommendations. It isalso important to make sure that the engine battery is continuously monitored, and kept in a fully chargedstate. In order to keep the noise emission level down, a four stroke engine is to be preferred to a two strokeengine.

In order to maintain a stable engine speed at different loads, the governors are used to control the supply offuel to the injectors. There are two different types of governors that can be fitted to the engine: an electronicone or a mechanical one. Electronic governors are to be preferred, as they provide a faster and finer responseto any load changes when compared to mechanical types of governors. A stable crank shaft speed results in astable alternator output frequency.

When selecting the type of engine- turbo charged or naturally aspirated achieving a fast recovery during stepload operation is an important selection criterion. The naturally aspirated engines can accept a 100% loadstep; however such engines tend to be much bigger than the turbo charged units. A higher number of cylinderswill offer shorter starting time and better engine reliability.

An adequate provision of lubrication oil should be available within the plant room, as this can becomeessential during longer blackouts. The lubrication oil drum should be fitted with a suitable hand pump to easetransfer of oil to the engine.

Each generator set must have suitable fire protection equipment fitted within the plant room. Typically afusible link mounted over the unit with automatic shutting off of bulk fuel tank supply pump/fire valve etc.

The following basic engine instruments are considered necessary:

Lubrication oil pressure gauge with trip contact or a sensor.

Lubricating oil temperature gauge

Service hour run counter

Coolant temperature gauge with trip contactor or a sensor

Engine speed indicator

THE ENGINE EXHAUST PIPES AND SILENCERS

Page 7: Set Design Parameters

7/25/2019 Set Design Parameters

http://slidepdf.com/reader/full/set-design-parameters 7/12

Publication No Cu0158

Issue Date: November 2012

Page 4

All the engines must be fitted with exhaust gas silencers to limit noise pollution generated by the dieselengine. It is imperative that all exhaust pipe work and silencers are suitably insulated with lagging to avoidburns. The exhaust system length should be kept as short as possible with minimum number of bends. Asuitable drain valve should be installed in the lower section of the exhaust system to drain any accumulatedcondensate from the exhaust system. Bellow type expansion joints are generally used as pipes will expand in

length as the temperature rises (as a rule of thumb, 1mm per 500 degrees centigrade). The level of noiseabatement depends on local by-laws and customer requirements. The main gaseous exhaust pollutants fromdiesel engine are oxides of sulphur, nitrogen and carbon. The particulate pollutants will be mainly carbon oroxides. Even small engines can produce significant amount of pollutants, and hence care must be taken torelease such pollution in a safe manner. In some cases, the local authorities may also demand inclusion of asuitable catalytic converter to limit pollution. Depending on location of the generator, some of the silencersmay have to be installed with a snow flap to avoid damage from severe snow fall.

ACOUSTICNOISE ABATEMENT Adequate acoustic housing needs to be allowed for any generator set installation. Since a typical diesel engine

will emit 130 dB A of noise at one meter distance from the engine. The local regulations and surroundingenvironment may dictate the level of required noise attenuation. It is worth noting that noise abatement canbe rather expensive. In some cases the generator may have to be installed within an ISO container, customisedenclosure or in a separate building with suitable noise reduction. Containerised generator sets are gettingpopular, and have several benefits as listed below:

minimal site work

robust construction with protection against the weather

self-contained noise abatement

ease of transportation

THE ALTERNATOR The alternator converts the engine ’s mechanical power into AC electrical power. The brushless alternator isnow generally utilized for all generator sets. In Europe, typical output voltage from the alternator would be400V 3 Phase at 50 Hz output frequency. Each alternator is fitted with an Automatic Voltage Regulator (AVR),which controls the stability and amplitude of the alternator output voltage. The alternator output frequency of50 Hz is determined by the engine speed, and based on alternator winding and number of Poles. The loadprofile is a dominant factor is sizing the alternator. Some loads may be rich in harmonic currents, whilst othersmay impose a leading power factor on the alternator. If these loads are to be protected, permanent magnetexcitation or alternator oversizing should be considered. On the other hand, if an active harmonic filter is usedto block the leading power factor and the load harmonics, oversizing the alternator is unnecessary.

GENERATOR SET FRAME A rigid steel chassis is used for mounting the main components of the generator set. Such a frame needs to bedesigned to handle the weights and the torsional stresses of all the rotating members of the system. The baseof the frame would be fitted with anti-vibration mounts (AVMs), to avoid engine vibrations being transferredto the building structure. Some buildings have stringent specifications regarding vibrations, imposing specialrequirements to the AVMs. The AVM count can be increased in order to reduce the point loadings, and tocomply with the floor loading design parameters.

AMF PANEL

Page 8: Set Design Parameters

7/25/2019 Set Design Parameters

http://slidepdf.com/reader/full/set-design-parameters 8/12

Publication No Cu0158

Issue Date: November 2012

Page 5

In case the generator is used for a secure power supply installation, it is necessary to install a suitable controlpanel. If the utility fails, the AMF panel enables automatic start of the genset and connects/transfers thegenerator output to the load. All the AMF controlled gensets continue to provide power for a minimum periodof two minutes even after the mains supply is restored. This provides additional cover in the event the utilityfault has not been resolved and the supply gets disconnected again.

There are two changeover contactors within the AMF panel. One of them is for the mains, and the other one isfor the generator. These contactors must be interlocked appropriately to avoid that both contactors wouldclose at the same time.

The AMF panel should be provided with a suitable bypass switch, complete with necessary interlocks, in orderto enable a safe execution of the necessary maintenance actions on the panel.

TYPICAL COMPONENTS ON CONTROL PANELS AND GENERATING UNITS Generator instrument panels are either mounted on the generator frame or as a free standing panel. Theinstallation of components listed below will be subject to set ratings and project specification. LCD displays andkey pads are now also becoming a common place for the following 15, 16 and 17 listed items.

1. Time delay mains failure relay for engine start and auto-changeover2. Interlock auto-changeover switch3. Voltage/frequency sensitive relay for generator circuit breaker4. Generator overcurrent relay5. Time delay relay for automatic normal supply reinstatements6. Time delay relay for engine cooling7. Bypass switch to auto-changeover switch for test and maintenance8. Push button – manual start engine9. Push button – emergency stop (red with yellow back plate)10. Auto start sequence switch11. Mains failure simulation switch12. Fail to start relay with audible/visual alarm13. Lubrication oil pressure gauge with engine low pressure alarm14. Engine high temperature relay with audible/visual alarm15. Generator voltmeter with phase selection rotary switch16. Generator amp meter with phase selection rotary switch17. Frequency meter18. Battery charger and batteries for start control, alarm and indication;19. Battery and battery charger isolation and visual indicator

20. Battery voltmeter21. Battery amp meter

Page 9: Set Design Parameters

7/25/2019 Set Design Parameters

http://slidepdf.com/reader/full/set-design-parameters 9/12

Publication No Cu0158

Issue Date: November 2012

Page 6

GENERATOR SET SIZING It is important to understand the factors that affect the operation of a generator set, as this can help inselecting the right components for a generator set to suit the application.

As a good starting point, it is worth adding up all the loads that need to be supported by the generator.However, it is important to be aware of the minimum load the unit will have to face for a considerable timeduring its operation. This is critical, as light load running can cause engine damage. Hence, one may need toconsider use of a dummy load to avoid running at loads below 30% of nameplate rating. Any future loadexpansion of the project needs to be considered too. A single, large diesel standby generator may havesufficient capacity to supply all your critical loads. However, it is often advisable to divide the load amongsmaller, multiple standby generators to maximize reliability and operational flexibility. In the unlikely eventthat one standby generator does not start when needed, the others will start and share the load by drawing ontheir built-in reserve capacities. Another advantage of multiple generator systems is that one unit can beoffline for maintenance without affecting the availability of standby power for emergencies.

It is worth considering the Tier Classification Standard (I, II, III & IV Levels) as defined by Uptime Institute

(www.uptimeinstitute.com ) to attain specific availability/reliability. This Standard combines the impact of

site management with that of the infrastructure choice and provides adequate guidance when planning for aparticular number of nines (99.999% i.e. Five Nines) for the availability of the critical load.

The following parameters also need to be considered during the sizing of the genset, and consequently needto be mentioned in the specifications for the genset supplier:

The choice of fuel can affect the size of the engine. For example, gas or LPG fed engines have to beoversized.

The geographical location. If the unit has to operate at high altitude or in a high temperature

environment then the engine size may have to be increased. The duty cycle the unit. If the generator set supports standby application, no overload capacity is

required. However, if it is for prime power (continuous long term operation) or for paralleling with theutility, the genset needs to have a 10% overload capacity.

The load profile. If the unit is expected to support a very unbalanced three phase load, the genset hasto be oversized. The size of step loads needs to be considered, since this can affect the output voltageand frequency dip. The maximum allowable voltage and frequency dip also needs to be specified, sothat the genset can be sized accordingly. Loads with leading power factor and/or non-linear currents(e.g. from UPSs and variable speed drives) can also affect the choice of the alternator. Loadsconsisting of electric motors with a high inrush current demand a larger than normal generator set.

The load transfer. If the load transfer to the genset system is carried out in a planned sequential

manner, this can avoid oversizing of the gensets in a system with several gensets running in parallel. The generator output frequency 50 or 60 Hz.

The anticipated fault clearing capacity.

Page 10: Set Design Parameters

7/25/2019 Set Design Parameters

http://slidepdf.com/reader/full/set-design-parameters 10/12

Publication No Cu0158

Issue Date: November 2012

Page 7

Figure 1 – Typical lay-out for two 400 kVA generator sets

Page 11: Set Design Parameters

7/25/2019 Set Design Parameters

http://slidepdf.com/reader/full/set-design-parameters 11/12

Publication No Cu0158

Issue Date: November 2012

Page 8

GENERATOR SET MAINTENANCE Since the diesel engine has hundreds of moving components, it is important to carry out routine maintenance.Maintenance is one of the key factors for diesel generator set ’s reliability. The generator room must haveadequate access to ease routine maintenance. As the diesel engine has high durability, most of the

maintenance is mainly of preventative nature.

Regular inspection and m aintenance in accordance with manufacturer’s recommendations can play a critical

role in maximizing set reliability and minimize repairs.

Following operations should form part of preventative maintenance:

• General inspection• Lubrication service• Cooling system service• Fuel system service including a check on fuel contaminants• Servicing and testing starting batteries• Regular engine testing

It is important to make sure that the regular engine testing is not carried out under light load condition. Whena diesel engine is operating on light load or no load, it will not attain the required optimal operationaltemperature. When the diesel engine is allowed to run for extended periods below its designed operatingtemperature, unburned fuel is exhausted and noticed as wetness in the exhaust system. This is termed as“Wet Stacking” .

The unburned fuel starts to build up in the exhaust side of the engine, resulting in a black oily fluid leakingfrom the exhaust manifold joints. Wet Stacking can cause serious damage to various components of theengine.

Page 12: Set Design Parameters

7/25/2019 Set Design Parameters

http://slidepdf.com/reader/full/set-design-parameters 12/12

Publication No Cu0158

Issue Date: November 2012

Page 9

CONCLUSION Statistically, 95% of all utility disturbances last for less than five minutes. The remaining 5% of longerinterruptions are likely to last for many hours. As all natural disasters, human errors and equipment failuresand black outs are not predictable. Consequently, if the application is so critical that no power interruption can

be tolerated, a standby generator must be installed as part of the protected power supply system.

The selection of the genset size should take a potential future growth of the load into account. Consultingavailability/reliability architecture guidelines, such as th e Uptime Institute’s tier level standard can help withtaking power system architecture decisions.

The specification and installation of a diesel generator is a complex matter covering many electrical andmechanical disciplines. All aspects need to be fully considered if an installation is to be successfully executed.

The cornerstone of a successful installation is ensuring that the genset is correctly rated against the criticalload; this includes capacity, duty, as well as dynamic performance characteristics. Over sizing of standbygenerators is common place; the penalty for oversizing is not just the capital cost of the genset itself, it alsorequires more attenuation, and larger fuel and flue systems.

It is likely that in future the exhaust gas pollution levels will be reduced dramatically due to further tighteningof such standards. In view of this, the engine designs will need to be improved substantially.

Once installed, the on-going reliability should be assured by having a proactive maintenance regime inaccordance with the manufacturer’s recommendations . Such a maintenance regime is also required tomaintain warranty cover.

REFERENCES • Cummins Power Generation Inc.• Power Electrics (Bristol) Ltd.• Worldwide Independent Power, June ‘06. Impact of Blade Servers on Data Centres- S.Karve• Uptime Institute – Availability, Tier Standard• ISO 3046 parts 1/6 - Internal combustion engine performance• ISO 8528 Generator set performance classification• IEC947-6-1 Low voltage switch gear