Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance...

19
1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com Rev. C Serv-A-Pure 1447 DI System Operation & Maintenance Manual

Transcript of Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance...

Page 1: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com Rev. C

Serv-A-Pure 1447 DI System

Operation & Maintenance Manual

Page 2: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 2 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

Table of Contents Section       Description    1.0       Glossary  of  Terms    2.0         General  Description  

2.1     Principles  of  Purifying  Water  2.2       Laboratory  Grade  Water  System  Specifications  2.3       pH  In  Ultra  Pure  Water    

3.0       Product  Specification     3.1     System  Drawings  and  Layout    4.0       Installing  the  System    5.0         Maintenance    6.0       Consumable  and  Spare  Parts    7.0       Requesting  Service    8.0         Troubleshooting  Guide    9.0       Tank  Sizes  and  Capacities    10.0       Warranty  

Page 3: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 3 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

1.0 Glossary of Terms

The  following  terms  are  used  throughout  this  text.  Please  take  a  few  moments  to  familiarize  yourself  with  them  so  that  the  information  and  instructions  within  are  clear.    TERM         DESCRIPTION    DI   “Deionization”  is  the  process  used  in  this  system  to  purify  the  water.  

Deionization  removes  almost  all  minerals  from  the  water    GPM     “Gallons  Per  Minute”  tells  the  flow  rate  of  the  system.    TDS   “Total  Dissolved  Solids”  is  a  measure  of  the  combined  content  of  all  inorganic  

and  organic  substances.  Typically  measured  in  PPM  or  Microsiemens.    TOC   “Total  Organic  Carbon”  is  the  amount  of  carbon    bound  in  an  organic  compound  

and  is  often  used  as  a  measure  of  water  quality  or  cleanliness.    RO   “Reverse  Osmosis”  is  a  water  purification  technology  that  may  be  used  to  greatly  

extend  the  life  of  DI  cartridges.                                        

Page 4: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 4 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

2.0 General Description    •  This  deionized  water  system  has  been  engineered  to  consistently  produce  Type  II  ultrapure  water.  This  system  is  user-­‐friendly,  does  not  require  any  pretreatment  options,  and  lowers  the  cost  per  gallon  to  purify  the  water    •  Adding  a  pre-­‐treatment  reverse  osmosis  system  will  greatly  increase  the  lifespan  of  each  deionizer  tank.  However  one  is  not  required  and  this  system  can  run  directly  off  of  city  water.  The  feed  water  quality  will  determine  the  necessary  pretreatment,  if  any.  Optional  pretreatment  systems  are  available  to  operate  from  tap  water  that  does  not  meet  feed  water  specifications.    •  Serv-­‐A-­‐Pure’s  1447  DI  water  system  does  not  use  any  reservoir  which  allows  bacteria  to  build  up.  All  water  produced  is  purified  as  it  is  drawn  off  to  reduce  any  possibility  of  bacteria  contamination.  The  1447  DI  system  can  provide  you  with  up  to  8.0  gallons  per  minute  (depending  on  tank  size)  of  deionized  water.  Whether  you  use  1  gallon  per  day  or  1000  gallons  per  day,  the  1447  DI  system  is  a  perfect  fit  for  nearly  every  application.    •  The  1447  DI  system  is  designed  to  provide  water  that  has  high  resistivity  and  low  TOC  (>  1.0  MΩ*cm  and  ≤  500  ppb).  The  1447  DI  system  is  ideally  suited  for  higher  water  use  applications  such  as,  closed  loop  systems,  industrial  applications  and  solar  panel  rinsing.    •  Every  1447  DI  system  comes  with  free  technical  phone  support.  Your  1447  DI  cartridges  can  be  changed  out  by  a  member  of  Serv-­‐A-­‐Pure’s  courteous  and  friendly  staff.  Alternatively,  all  cartridges  can  be  sent  to  you  via  common  carrier  to  allow  for  more  economical  change  outs.    •  All  filters  on  the  1447  DI  system  are  recommended  to  be  changed  at  a  minimum  of  every  6  months,  depending  on  feed  water  quality.  This  allows  maintenance  to  take  place  as  little  as  two  times  per  year.                      

Page 5: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 5 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

2.1 Principles of Purifying Water

The  Serv-­‐A-­‐Pure  1447  DI  system  uses  deionization  as  the  process  to  purify  water.  The  deionization  process  removes  all  ions  from  a  solution.  The  1447  DI  system  uses  mixed  bed  resins  combined  with  both  cation  and  anion  resins.  Cation  resins  remove  all  cations  (positively  charged  ions  such  as  Sodium,  Calcium,  and  Magnesium)  and  anion  resins  remove  all  anions  (negatively  charged  ions  such  as  sulfate,  bicarbonate  and  chlorides).  

 Deionization  systems  can  be  either  continuous  or  batch  mode  operations.  In  a  continuous  system,  the  water  is  purified  as  quickly  as  it  is  used,  whereas  in  batch  operations  the  water  will  be  purified  slower  than  the  end  usage  and  stored  in  a  tank  so  it  may  be  used  at  faster  flow  rates.  

 Sizing  a  system  is  based  upon  your  water  usage.  There  are  three  basic  requirements  used  to  determine  the  design  of  a  water  purification  system:  

 1.  Maximum  demand  (gpm  peak)  2.  Average  demand  (gpm  average  per  day)  3  Water  purity  level  required.    

The  first  governs  the  amount  of  flow  rate  and  the  second  sizes  the  storage  required  (if  any).    1447  Deionization  Operation    Water  enters  the  1447  DI  system  and  passes  first  through  a  5.0  micron  pre  filter.  This  filter  removes  particulate  and  sediment  from  the  raw  water.  Next  it  passes  through  a  carbon  absorption  cartridge,  which  removes  chlorine  and  other  organics  from  the  feed  water.  The  water  then  passes  through  one  or  more  deionization  tanks  that  exchange  the  ions  in  the  water  stream  for  hydrogen  ion  and  the  hydroxyl  ion,  which  leaves  us  with  only  H2O  left  in  the  water.  Finally,  the  water  passes  though  a  1.0  micron  post  filter  to  ensure  no  resin  fines  are  passed  into  the  purified  water  stream.  Red/Green  purity  lights  monitor  the  quality  of  the  water  to  ensure  you  are  still  receiving  Type  II  lab  water.                  

Page 6: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 6 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

2.2 Laboratory Grade Water System Specifications

Different  published  norms  define  the  quality  required  for  specific  laboratory  water  applications:  ASTM  and  ISO  3696  for  laboratory  applications,  CLSI  guidelines  for  clinical  laboratories.      The  table  below  outlines  the  different  water  specifications  based  on  different  water  type  per  ASTM  guidelines:    

Contaminant   Parameter  and  Unit   Type  1   Type  2   Type  3  Ions   Resistivity  (MΩ*cm  @  25  C)   >  18.0   >  1.0   >  0.05  Organics   TOC  (ppb)   <  10   <  50   <  200  Pyrogens   (Eu/ML)   <  0.03   NA   NA  

Particulates  Particulates  >  0.2  μm  (units/mL)   <  1   NA   NA  

Colloids   Silica  (ppb)   <  10   <  100   <  1000  Bacteria   Bacteria  (cfu/mL)   <  1   <  100   <  1000  

These values are only guidelines, as some specific laboratory applications may require a quality superior to the quality indicated by the norms. TYPE  1   Type  1  water  is  the  grade  required  for  critical  laboratory  applications  such  as  HPLC  

mobile  phase  preparation,  blanks  and  sample  dilution  in  GC,  HPLC,  AA,  ICP-­‐MS  and  other  advanced  analytical  techniques;  preparation  of  buffers  and  culture  media  for  mammalian  cell  culture  and  IVF;  production  of  reagents  for  molecular  biology  applications  (DNA  sequencing,  PCR);  and  preparation  of  solutions  for  electrophoresis  and  blotting.  

TYPE  2   Type  2  water  is  the  grade  used  in  general  laboratory  applications  such  as  buffers,  pH  solutions  and  microbiological  culture  media  preparation,  as  feed  to  Type  1  water  systems,  clinical  analyzers,  cell  culture  incubators  and  weatherometers;  and  for  the  preparation  of  reagents  for  chemical  analysis  or  synthesis.  

TYPE  3   Type  3  water  is  the  lowest  laboratory  water  grade,  recommended  for  glassware  rinsing,  heating  baths  and  filling  autoclaves,  or  to  feed  Type  1  lab  water  systems.  

These  standards  can  be  used  in  conjunction  with  the  Type  of  water.  

Measurement  (Unit)   A   B   C  Heterotrophic  Bacteria  Count  (CFU/ml)   10/1000   10/100   1000/10  

Endotoxin  (units  per  ml)   0.03   0.25   n/a      

Page 7: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 7 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

2.3 pH In Ultra Pure Water

In  discussing  pH  and  pH  as  applied  to  corrosion  most  people  forget  that  the  total  salt  content  is  also  important  in  corrosion.  The  pH  measurement  of  Ultra  Pure  water  is  practically  meaningless.  The  classic  story  is  the  technician  who  drew  a  sample  of  18  MegOhm  water,  carried  it  40  feet  to  the  pH  meter  and  found  he  had  a  pH  of  6.5.  He  knew  this  could  not  be  correct  so  he  swirled  the  water  to  get  a  better  reading.  To  his  amazement,  the  pH  dropped  to  4.5.  He,  of  course,  felt  the  water  was  not  pure,  however,  what  he  did  not  realize  until  later  was  that  he  had  added  CO2  to  the  water.  He  had  formed  carbonic  acid  during  his  swirling  and  this  had  lowered  the  pH.   The  question  is,  was  the  pH  of  4.5  on  Ultra  Pure  water  more  corrosive  than  pH  7.0  Ultra  Pure  water?  The  answer  is  no,  because  one  mg/l  of  Sodium  Bicarbonate  would  immediately  raise  the  pH  to  over  7.0.  A  pH  of  4.5  in  water  of  500  mg/L  Total  Dissolved  Solids  (TDS)  would  be  quite  corrosive  and  would  require  well  over  500  mg/L  of  Sodium  Bicarbonate  to  raise  the  pH  over  7.0.  What  this  tells  you  is  that  pH  alone  without  knowledge  of  the  other  components  in  the  water  is  not  sufficient  to  base  a  decision  on.   It  should  be  remembered  that  Ultra  Pure  water  will  always  tend  to  be  slightly  acidic,  i.e.  pH  less  than  7.0,  because  of  the  tendency  for  CO2  to  dissolve  in  water.  Without  other  salts  to  buffer  the  weak  carbonic  acid  the  pH  value  will  be  reduced.  The  pH  of  water  with  less  than  10  mg/l  TDS  has  questionable  validity.  The  pH  of  water  with  between  10  and  50  mg/L  TDS  becomes  more  important,  but  not  the  major  indicator  of  corrosion.  The  pH  is  the  major  indicator  of  corrosion  with  water  with  over  50  mg/l  TDS.                                    

Page 8: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 8 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

3.0 Product Specification Specifications   1447-­‐2-­‐3BB  Feed  Water   Potable  tap  water  with  conductivity  <  2000µS/cm  @  25°C,    

At  a  pressure  of  15-­‐90*  psi    Flow  Rate   Up  to  8.0  GPM    Resistivity   >  1.0  MΩ•cm  @  25°C  (Type  II)  Typically  Operating  Temperature  Range   35  –  100°F  (2-­‐38°C)  TOC   <  500  ppb  Wall  Plate  Weight,  Approx:   65  pounds  Floor  Space  Dimensions  (H  x  W  x  D)   72”  x  48”  x  24”  *Pressures  exceeding  90  psi  may  require  an  optional  inlet  pressure  regulator  

               

Page 9: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 9 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

   

Legend

Valve! N/O = Normally Open! N/C = Normally Closed

Install Dr / 1447 DI 2 Tank Install

Typical Two Tank Mixed Bed Deionization Installation To Provide ≥ 1.0 MegOhm Water

Raw Water IN

Note:!Water Enters The D. I. Tanks Thru!The Female Fitting & Exits Out The !Male Fitting.

Connect Inlet!Plumbing Here

WP5-BB!WP5-BB20P!

5.0 Micron Filter!20” BB Cartridge!

#355223

Pure Water Out !Connect to outlet with !only Plastic or Stainless!Steel Pipe

!When Light on Tank #2 Goes Out!If Light on DI-2 goes Out With Water Flowing Change DI-1 and DI-2 with New Full DI Tanks.!!When Light on Tank #1 Goes Out!Remove DI-1 and return for reprocessing!Move DI-2 to the DI-1 position and install New Full tank in DI-2 position.

Purity Light!

TANKS

(989) 892-7745 (800) 338-4905

LOCATION

DATE

SCALE

DRAWN

DRG NONA

2 Tank Deionization Exchange System - AH2

RCH

For 5.0 gpm Maximum Flow Rate

11-30-09

091020

Serv-A-Pure Company !1101 Columbus. Ave. Bay City, MI. 48708

#1447 DI Tanks, 3.75 cu. ft.

Note:!Water is good while lights!remain lit. When light on #2!tank goes Out, exchange tanks.

RFC-1!RFC20-BB!

Carbon Cartridge!20” BB Cartridge!

#155247

WP1-BB!WP1-BB20P!

1.0 Micron Filter!20” BB Cartridge!

#355222

DI-1!Mixed Bed DI Tank!

14" x 47"!3.75 cu. ft. Resin

DI-2!Mixed Bed DI Tank!

14" x 47"!3.75 cu. ft. Resin

Page 10: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 10 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

4.0 Installing the System

This  section  includes  instructions  for  initial  installation  and  start-­‐up  of  the  unit.  Described  herein  are  selection  of  unit  location,  unit  unpackaging,  and  connection  of  the  unit  to  the  water  and  electrical  supplies.  Also  described  are  cartridge  installation  and  the  purging  of  trapped  air.    5.1  Setup  

•  Select  a  location  for  the  unit,  which  is  in  close  proximity  to  the  water  supply  and  electrical  supply  connection.  Select  a  wall  that  will  support  a  70-­‐pound  load  on  16-­‐inch  stud  centers  or  provide  wall-­‐backing  material.    •  Carefully  remove  all  of  the  packaging  material  and  tape  used  for  shipping  purposes,  and  position  the  unit  in  its  operating  location.  The  top  of  the  wall  plate  should  be  mounted  72”  off  of  the  ground.  

 •  Connect  the  inlet  plumbing  to  the  supplied  MPT  ball  valve.  Inlet  plumbing  can  be  made  from  any  material  such  as  copper,  cast  iron,  pvc  etc.    •  Connect  the  outlet  plumbing  to  the  supplied  MPT  ball  valve.  Outlet  plumbing  needs  to  be  constructed  from  PVC,  CPVC,  SS  or  some  other  inert  material  to  reduce  leaching  of  contaminants  into  the  DI  water.  

 5.2  Installing  the  Cartridges  

•  Install  the  pre-­‐sediment,  pre-­‐carbon  and  post-­‐sediment  filters.  These  may  come  installed  in  the  housings  for  shipping  purposes.  If  so,  open  the  housings  and  remove  the  packaging  material  from  the  filters  and  re-­‐install.  Hand  tight  is  ok,  no  need  to  tighten  down  with  the  provided  spanner  wrench.  Only  use  the  wrench  if  you  have  a  small  leak  and  for  help  in  removing  the  housings.  

 •  Arrange  the  DI  cylinders  below  the  wall  plate.  Make  all  connections  from  the  wall  plate  to  the  DI  cylinders  by  following  the  attached  labels.  Such  as  connect  “DI  Tank  #1  Inlet  to  DI  Tank  #1  Inlet”.  

 5.3  Start  Up  Procedure  

•  Plug  in  the  2  supplied  resistivity  lights.  The  electrical  outlet  should  be  properly  grounded  and  fused.  The  lights  will  be  red  with  no  water  flowing  through  them.    •  Open  Test  Valve  #1  and  place  an  open  container  underneath  valve.    •  Slowly  turn  on  the  water  supply  to  the  unit  and  correct  any  leaks  at  the  supply  

Page 11: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 11 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

connections.    •Allow  the  air  to  bleed  from  the  system  through  the  outlet  valve  into  the  open  container.  When  all  air  has  been  purged  from  the  first  2  filter  housings  close  valve.    •  Open  Test  Valve  #2  and  placed  open  container  underneath  the  valve.    •  Allow  all  of  the  air  to  bleed  from  the  deionization  tanks.  Verify  that  the  purity  lights  turn  “Green”  with  the  water  flowing.  Once  the  purity  lights  turn  “Green”  and  the  air  is  completely  purged,  close  the  outlet  valve.    •  The  system  is  now  ready  to  be  used.    

   

Page 12: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 12 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

5.0 Maintenance

The  1447  DI  system  was  designed  and  manufactured  to  have  the  ability  to  produce  Type  II  lab  water  for  many  uses.  It  purifies  water  that  meets  or  exceeds  the  specifications  recommended  by  ASTM  and  CAP  for  Type  II  Lab  Water  when  it  is  operated  and  maintained  according  to  these  instructions.  

 •  The  pre-­‐sediment,  pre-­‐carbon  and  post-­‐sediment  filters  should  be  changed  every  6  months,  or  more  often  if  necessary.    •  The  DI  resin  cylinders  must  be  replaced  when  the  purity  light  indicates  the  water  purity  is  below  your  requirements  or  every  6  months.    •  The  exterior  surfaces  may  be  cleaned  with  a  mild  detergent  and  a  soft  cloth  to  keep  the  unit  looking  new  and  clean.  

 Replacing  the  Cartridges    The  pre-­‐sediment,  pre-­‐carbon  and  post-­‐sediment  cartridges  are  expendable  items  that  have  a  limited  capacity  to  filter  the  water.  Monitor  the  pressure  using  the  installed  pressure  gauges  and  change  if  the  pressure  drop  becomes  too  great  (15-­‐20  PSI  drop).  The  cartridges  should  be  replaced  every  6  months  as  a  matter  of  routine  maintenance  or  every  time  the  DI  cylinders  are  replaced.     •  Turn  off  the  inlet  and  outlet  ball  valves.    

•  Place  an  open  container  under  one  of  the  blue  handled  test  valves.  Open  the  valve  and  bleed  the  pressure  off  of  the  system.  Verify  both  pressure  gauges  read  0  psi  before  continuing.    •  Using  the  supplied  spanner  wrench,  remove  the  filter  housing  sumps  from  the  wall  plate.  Remove  the  installed  cartridges  and  dispose  properly,  according  to  local  codes.    •  Install  new  cartridges  and  screw  the  sumps  back  onto  the  wall  plate.    •If  needed,  exchange  the  DI  cylinders  at  this  time  (see  below).    •  Ensure  open  container  is  still  under  test  valve  and  slowly  open  the  inlet  ball  valve.  Bleed  all  air  out  of  system.  Close  the  test  valve  and  open  the  outlet  valve.    •  Inspect  the  housings  for  leaks  at  this  time.  

Page 13: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 13 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

Replacing  the  DI  Cylinders    The  DI  cylinders  can  only  remove  a  certain  amount  of  contaminants  from  the  water  before  they  need  to  be  replaced.  When  the  purity  light  turns  red,  with  water  flowing,  it  is  time  to  change  out  the  DI  cylinders.  

•  Turn  off  the  inlet  and  outlet  ball  valves.    

•  Place  an  open  container  under  one  of  the  blue  handled  test  valves.  Open  the  valve  and  bleed  the  pressure  off  of  the  system.  Verify  both  pressure  gauges  read  0  psi  before  continuing.  

 •  Unscrew  the  connections  on  top  of  the  DI  tanks  

    •  Install  new  DI  cylinders  and  firmly  cam  down  each  connection.    

•  Reconnect  the  connection  on  top  of  the  DI  tanks.  Ensure  open  container  is  still  under  test  valve  and  slowly  open  the  inlet  ball  valve.  Bleed  all  air  out  of  system.  Confirm  purity  lights  turn  green  (make  take  a  few  gallons).    •  Inspect  each  fitting  for  leaks.      

   

Page 14: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 14 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

 

6.0 Consumables and Spare Parts

Pre-­‐sediment  5.0  Micron  Filter  Part  Number:  5M-­‐WP-­‐20BB    Pre-­‐sediment  20”  Carbon  Filter:  Part  Number:  155247-­‐43    Post-­‐Sediment  1.0  Micron  Filter  Part  Number:  1M-­‐WP-­‐20BB    14”  x  47”  DI  Tank  Part  Number:  SAP-­‐1447-­‐MB    O-­‐Ring  for  Filter  Housings  Part  Number:  151122    Spanner  Wrench  for  Filter  Housings  Part  Number:  144368              

Page 15: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 15 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

7.0 Requesting Service

Before  calling  the  factory  to  request  service,  search  the  troubleshooting  guide  on  the  next  page  for  symptoms,  which  your  unit  exhibits,  and  verify  the  cause  and  possible  remedies  listed.  If  your  symptom  is  not  listed,  or  the  remedy  does  not  provide  a  cure,  contact:      

   

 1101  Columbus  Ave  Bay  City,  MI  48611  

Phone:  (989)  892-­‐7745  Fax:  (989)  989-­‐1092  www.ServAPure.com  

Email:  [email protected]        

   

Page 16: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 16 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

8.0 Troubleshooting Guide

Symptom   Cause   Remedy  No  Water  Flow   Inlet/Outlet  Valve  Is  

Closed    No  Feed  Water  Pressure  

Open  the  inlet/outlet  valve  and  check  for  flow    Check  feed  line  and  correct  condition  

Slow  Water  Flow   Feed  Pressure  Low    Plugged  pre/post  filters  

Feed  Pressure  needs  to  be  between  30-­‐80  psi    Change  filter  that  is  plugged.  Use  pressure  gauges  to  determine  which    on  is  plugged.  

Purity  Light  Red   No  Flow      Tanks  Exhausted  

Water  needs  to  be  flowing  for  light  to  read  properly    If  water  is  flowing  and  light  is  red,  change  DI  Tanks  

Tanks  Exhaust  Quickly  

High  Feed  Water  TDS    High  Water  Usage  

Install  pretreatment  option  such  as  RO  system    Upgrade  to  larger  DI  tanks  

DI  Tank  Leaking   Resin  under  o-­‐ring  on  fitting  

Remove  seal  and  ensure  no  resin  beads  or  other  debris  are  there      

Filter  Housing  Leaking  

Sump  Not  Tight      O-­‐Ring  damaged  

Tighten  the  sump  with  spanner  wrench  (Do  not  over  tighten)    Replace  o-­‐ring  

             

Page 17: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 17 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

9.0 Tank Sizes and DI Capacities

The  following  chart  shows  the  estimated  amount  of  gallons  each  DI  tank  will  produce.  For  example,  if  you  have  a  635  DI  tank  and  your  feed  water  is  200  ppm,  you  can  expect  your  DI  tank  to  produce  504  gallons.

Feed  Water  TDS  (ppm  or  

mg/l)  

618  (0.27  ft3)  

818  (0.44  ft3)  

635  (0.57  ft3)  

835  (0.92  ft3)  

844  (1.25  ft3)  

1447  (3.75  ft3)  

10   4,934   8,041   10,417   16,814   21,017   67,255  50   954   1,555   2,014   3,251   4,063   13,003  100   477   777   1,007   1,625   2,032   6,501  200   239   389   504   813   1,016   3,251  300   159   259   336   542   677   2,164  400   119   194   252   406   508   1,625  500   95   155   201   325   406   1,300  

               

Page 18: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Page 18 of 19 Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com

10.0 Warranty

Serv-­‐A-­‐Pure’s  1447  DI  system  has  a  one-­‐year  warranty  from  the  date  of  purchase.  If  any  component  fails  to  function  normally  within  the  first  year,  return  the  unit  to  the  factory  prepaid.  If  in  the  opinion  of  the  factory,  failure  was  due  to  defects  in  materials  or  workmanship,  repair  or  replacement  will  be  made  without  charge.  A  reasonable  service  charge  will  be  made  for  diagnosis  or  repairs  not  covered  by  this  warranty.  Serv-­‐A-­‐Pure  Company  assumes  no  other  responsibility  or  liability.    This  warranty  does  not  cover  filters  or  DI  cylinders,  as  their  lifespan  is  completely  dependent  on  the  feed  water  quality.  Also  any  products  which  has  been  subject  to  misuse,  neglect,  accident  or  used  in  violation  of  operating  instructions  nor  does  it  extend  to  any  units  altered  or  repaired  by  anyone  other  than  Serv-­‐A-­‐Pure  Company  or  Serv-­‐A-­‐Pure  authorized  technicians.    In  no  event  shall  Serv-­‐A-­‐Pure  Company  be  liable  for  any  incidental,  consequential,  special,  indirect,  punitive  or  exemplary  damages  or  lost  profits  from  any  breach  of  this  warranty  or  otherwise.    Serv-­‐A-­‐Pure  Company  reserves  the  right  to  make  changes  in  design,  specifications  and  prices  without  notice.  

Page 19: Serv-A-Pure 1447 DI System Operation & Maintenance Manual · 1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708 Page 2 of

1447 DI System Operation & Maintenance Manual Serv-A-Pure Company • 1101 Columbus Ave. Bay City, MI 48708

Phone: (800) 338-4905 • Fax: (989) 892-1092 • www.servapure.com Rev. C