Series SV Specification Sheet
Transcript of Series SV Specification Sheet
8/8/2019 Series SV Specification Sheet
http://slidepdf.com/reader/full/series-sv-specification-sheet 1/2
For Steam Heating ApplicationsES-SV
Job Name ––––––––––––––––––––––––––––––––––––––––––– Contractor ––––––––––––––––––––––––––––––––––––––––––––
Job Location –––––––––––––––––––––––––––––––––––––––––– Approval ––––––––––––––––––––––––––––––––––––––––––––––
Engineer –––––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. –––––––––––––––––––––––––––––––––––
Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative –––––––––––––––––––––––––––––––––––––––––
Series SV Non-Vacuum Float Type,Steam Air VentsSeries SV Non-Vacuum Float Type Steam Air Vents are
designed to vent air on non-vacuum steam heating systems.
Used on radiators, convectors and steam mains.
Model SV For ordinary one-pipe steam systems not requiring proportionalventing, (Non-Adjustable).
1 ⁄ 8" (3mm) angle connection
Model SVA Adjustable air vent for proportional venting to steam heatingsystems.
1 ⁄ 8" (3mm) angle connection
Models SVS-1, SVS-2Non-adjustable air vents for steam system.1 ⁄ 8" and 1 ⁄ 4" (3 and 8mm) straight connections
Model SVS-3Straight connection, non-adjustable vent for mains.
1 ⁄ 2", 3 ⁄ 4" (15, 20mm)
SVA
SVS-2
Typical Installations
Watts AirVent
*See Note
3 ⁄ 4" (20mm) Nipple
Supply Main1-Pipe ordry return
2-Pipe15" (381mm) Min.
Boiler Water Line
ReducerWet
Return
18" (457mm) Min.
Nipple 6" to 10"(150 to 250mm)
*See Note
Main Vent
WattsRadiator
Valve
Supply Main
pitch piping down from here
*Add additionalvents as required.
One-Pipe Radiator System
" Fitting3 ⁄ 4
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contactWatts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incur-ring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
8/8/2019 Series SV Specification Sheet
http://slidepdf.com/reader/full/series-sv-specification-sheet 2/2
ES-SV 0334 © Watts Regulator Co., 2003 Printed in U.S.A.
USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.wattsreg.com
Canada: 5435 North Service Rd., Burlington, ONT. L7L 5H7; www.wattscanada.ca
Materials of constructionFloat: Brass
Body: Brass
Pressure
Model SVA
Maximum operating pressure 1.5psi (10.3 kPa).
Maximum pressure 10psi (68.0 kPa).
Model SV, SVS-1, SVS-2, and SVS-3
Maximum operating pressure 6psi (41.3 kPa).
Maximum pressure 10psi (68.9 kPa).
Model SVA Adjustable Features
Top View Setting
Actual Port Opening
• Fast Venting
Full open or 7 ⁄ 8 port for the radiation farthest from the boiler or
hard to heat radiation (coldest rooms).
• Medium Venting1 ⁄ 2 or 3 ⁄ 4 port for radiation located between middle and end of
main (warm rooms).
• Slow Venting1 ⁄ 8 or 1 ⁄ 4 port for radiation located closest to boiler (hot rooms).
Dimensions
31 ⁄ 8"(81mm)
13 ⁄ 4"(43mm)
37 ⁄ 16"(89mm)
11 ⁄ 4(32mm)
37 ⁄ 16"(89mm)
11 ⁄ 4"(32mm)
SV, SVA SVS-1, SVS-2 SVS-3