SERIES 5335 - 5335H PRESSURE REDUCING VALVE Control Valves... · A pressure gauge can be fitted...
Transcript of SERIES 5335 - 5335H PRESSURE REDUCING VALVE Control Valves... · A pressure gauge can be fitted...
SERIES 5335 - 5335H
SAFEGUARDS WATER HEATERS AND DOMESTIC SYSTEMS
FUNCTION AND FEATURES
� Compact design � Makes pressure limiting valves redundant
� Easily adjustable 100 - 600kPa � Gauge port standard (inline model)
� Superior flow rate � Inbuilt Strainer
� Available in high temperature version � Replaceable cartridge
� Factory set at 500kPa � ‘H’ version rated to 80ºC and 2,000kpa
AS 1357.2
C OF C 02467
PRESSUREREDUCING VALVE 15MM - 25MM
)
CODE CONN.
533545 15mm
533555 20mm
533545H 15mm
533555H 20mm
533565H 25mm
STANDARD DUAL OUTLET
CODE CONN.
533551H 20mm
RIGHT ANGLE
CODE CONN.
533550 20mm
533550H 20mm
All Valve industries Pty ltd. · Unit 2, 18-28 Sir Joseph Banks Drive
Kurnell NSW 2231 - Ph: +61 2 8543 9811 · Fax: +61 2 8543 9822
www.allvalve.com.au · [email protected] · © Copyright 2013
WE RESERVE THE RIGHT TO CHANGE OUR PRODUCTS AND THEIR RELEVANT
TECHNICAL DATA, CONTAINED IN THIS PUBLICATION, AT ANY TIME AND
WITHOUT PRIOR NOTICE.
PRODUCT SPECIFICATIONS
0,5 1 2 50,2
∆p (kPa)
50
100
20
150
30
40
60
80
120
90
70
∆p (m w.g.)
5
10
2
1
15
3
4
6
8
12
9
7
5
10
20
50 Flo
wra
te
(l/m
in)
(m3/
h)
1/ 2” 3/ 4” 1”
170913-0
0PRESSURE RANGE 100 - 600kPa (500kPa - 533551H)
FACTORY SET 500kPa
MAX. INLET PRESSURE 1600kPa (standard) / 2000kPa (‘H’)
MAX. TEMPERATURE 60ºC (standard) / 80ºC (‘H’)
MEDIA Water / Air
OPTIONAL PRESSURE GAUGE 0 - 1000kPa
GAUGE PORT SIZE 8mm
TECHNICAL SPECIFICATIONS
Pressure reducing valves are a valuable asset to any piping system. Many people are under the misapprehension that more pressure is better
when, in fact, it is often the reverse. Too much pressure in a system puts unnecessary strain on water heaters, plumbing joints, taps, washers, etc,
increasing the chance of leaks, burst hoses on washing machines and other appliances and adding greatly to water hammer problems.
The Caleffi 5335 series pressure reducing valve is fully adjustable between 100 - 600kPa and allows for easy adjustment to an optimum pressure.
A pressure gauge can be fitted into the gauge port for accurate setting. The valve comes factory set at 500kPa, the most common pressure
setting required for domestic systems. With all the advantages of the Caleffi 5335 series adjustable pressure reducing valves, using pressure
limiting valves will soon become outdated.
The Caleffi 5335/H is available in both standard and high temperature versions. Alternatively, the Caleffi 535 series “dial-up” pressure reducing
valve range is available from 15mm to 50mm.
CODE 533545/H 533555/H 533565H 533550/H 53351H
A 15mm 20mm 25mm 20mm 20mm
B 74.5 74.5 74.5 74.5 67
C 22 22 23 50 46
D Ø 46 Ø 46 Ø 46 Ø 46 Ø 46
E 79 84.5 95 82.5 43
Weight(kg) 0.45 0.46 0.54 0.49 0.49
DIAGRAM PRESSURE LOSS CHART
AS 1357.2
C OF C 02467
* ‘H’ denotes high temp &
high pressure version
E
A A
BC
D
E
A A
BC
D
5 3 3 5Ser ie
s
Pressure range:
100÷600 kPa
Max inletpressu
re 1600 kPa
Flow rate:30 @ 100 kPa
130 @ 600 kPa
Max temperatur
e:60°
AS 1357.2
WMKA 02467
5 3 3 5Ser ie
s
Pressure range:
100÷600 kPa
Max inletpressu
re 1600 kPa
Flow rate:30 @ 100 kPa
130 @ 600 kPa
Max temperatu
re:60°
AS 1357.2
WMKA 02467
E
A
BC
D
5 3 3 5 Ser ies
Pressure range: 100÷600 kPaMax inlet pressure 1600 kPaFlow rate: 30 @ 100 kPa
130 @ 600 kPaMax temperature: 60°
AS 1357.2
WMKA 02467
533
5335
5335
* ‘H’ denotes high temp &
high pressure version
* ‘H’ denotes high temp &
high pressure version
!*
SERIES 535
� Compact design � Max 2,500kPa inlet pressure
� Easily adjustable 100 - 600kPa � Gauge port standard (optional gauge)
� High (ow rate � Inbuilt Strainer
� Dial-up adjustment � Replaceable cartridge
� Union ends standard
AS 1357.2
C OF C 02467
PRESSURE
REDUCING VALVE 15MM - 50MM
SAFEGUARDS COMMERCIAL AND HIGH RISE BUILDINGS
FUNCTION AND FEATURES
!!
All Valve industries Pty ltd. · Unit 2, 18-28 Sir Joseph Banks Drive
Kurnell NSW 2231 - Ph: +61 2 8543 9811 · Fax: +61 2 8543 9822
www.allvalve.com.au · [email protected] · © Copyright 2013
WE RESERVE THE RIGHT TO CHANGE OUR PRODUCTS AND THEIR RELEVANT
TECHNICAL DATA, CONTAINED IN THIS PUBLICATION, AT ANY TIME AND
WITHOUT PRIOR NOTICE.
PRODUCT SPECIFICATIONS
∆p (kPa)
50
100
20
10
150
30
40
60
80
120
90
70
∆p (mw.g.)
5
10
2
1
15
3
4
6
8
12
9
7
1/2"
3/4"
1"
11/4"
11/2"
2"
11/4"
(535074/5)
0,5 1 2 50,2
10
20
20
50
100
Flowrate
(l/min)(m
3/h)
2005
10
220713-00
PRESSURE RANGE 100 - 600kPa
FACTORY SET 300kPa
MAX. INLET PRESSURE 2500kPa
MAX. TEMPERATURE 60ºC
MEDIA Water / Air
OPTIONAL PRESSURE GAUGE - RANGE 0 - 1000kPa
GAUGE PORT SIZE 8mm
TECHNICAL SPECIFICATIONS
Pressure reducing valves are a valuable asset to any piping system. Many people are under the misapprehension that more pressure is better
when, in fact, it is often the reverse. Too much pressure in a system puts unnecessary strain on water heaters, plumbing joints, taps, washers,
etc, increasing the chance of leaks, burst hoses on washing machines, etc, and adding greatly to water hammer problems.
The 535 has a maximum inlet pressure of 2500kPa and is adjustable between 100 and 600kPa. The valve comes pre-set at 300kPa but is easily
changed to your desired pressure setting by turning the adjustment knob on the top of the valve. Once the required pressure is ‘dialled-up’, the
adjustment knob can be locked by tightening the screw located in the centre of the knob. A gauge port is standard on the body of the valve so
that a gauge can be <tted to monitor the downstream pressure.
For ease of inspection and maintenance, a removable internal cartridge and strainer, containing all the regulating components, can be accessed
through the top of the valve.
WARNING
If it is critical to maintain a precise pressure
to protect equipment downstream of the
Calef< 5335 series pressure reducing valve,
we recommend the installation of a pressure
relief valve.
CODE 535040 535050 535060 535070 535080 535090
A 15mm 20mm 25mm 32mm 40mm 50mm
B 140 160 180 200 220 250
C 20.5 20.5 20.5 40 40 40
D 112 112 112 178 178 178
E Ø 54 Ø 54 Ø 54 Ø 73 Ø 73 Ø 73
Weight(kg) 0.92 1.06 1.38 2.6 3.4 4.3
CODE SIZE
535040 15mm
535050 20mm
535060 25mm
535070 32mm
535080 40mm
535090 50mm
PRESSURE REDUCING VALVE
SPECIFICATIONS PRESSURE LOSS CHART
AS 1357.2
C OF C 02467
DIAGRAM
!"
SERIES 536
� Compact design � Max 2,500kPa inlet pressure
� Adjustable 50 - 600kPa � Rated to 80ºC
� High &ow rate � Inbuilt Strainer
� Suitable at low &ows � Replaceable cartridge
� Union ends standard � Quiet operation
PRESSURE
REDUCING VALVE 15MM - 40MM
SAFEGUARDS COMMERCIAL AND INDUSTRIAL SYSTEMS
FUNCTION AND FEATURES
* Optional Gauge Shown
!#
All Valve industries Pty ltd. · Unit 2, 18-28 Sir Joseph Banks Drive
Kurnell NSW 2231 - Ph: +61 2 8543 9811 · Fax: +61 2 8543 9822
www.allvalve.com.au · [email protected] · © Copyright 2013
WE RESERVE THE RIGHT TO CHANGE OUR PRODUCTS AND THEIR RELEVANT
TECHNICAL DATA, CONTAINED IN THIS PUBLICATION, AT ANY TIME AND
WITHOUT PRIOR NOTICE.
PRODUCT SPECIFICATIONS
220713-00
PRESSURE RANGE 100 - 600kPa
FACTORY SET 300kPa
MAX. INLET PRESSURE 2500kPa
MAX. TEMPERATURE 80ºC
MEDIA Water / Air
OPTIONAL PRESSURE GAUGE - RANGE 0 - 1000kPa
GAUGE PORT SIZE 8mm
TECHNICAL SPECIFICATIONS
Pressure reducing valves are a valuable asset to any piping system. Many people are under the misapprehension that more pressure is better
when, in fact, it is often the reverse. Too much pressure in a system puts unnecessary strain on water heaters, plumbing joints, taps, washers,
etc, increasing the chance of leaks, burst hoses on washing machines, etc, and adding greatly to water hammer problems.
The 536 has a maximum inlet pressure of 2500kPa and is adjustable between 100 and 600kPa. For ease of inspection and maintenance, a
removable internal cartridge and strainer, containing all the regulating components, can be accessed through the top of the valve.
CODE 536040 536050 536060 536070 536080
A 15mm 20mm 25mm 32mm 40mm
B 140 160 180 200 220
C 76 90 95 110 120
D Ø 51 Ø 60 Ø 60 Ø 72 Ø 72
E 53.5 54 54 63 63
F 89.5 111.5 111.5 126 126
A A
EF
BC
D
FLOW SELECTION AND PRESSURE LOSS CHART DIAGRAM
0,5
1
2
5
0,2
V (m/s)
0,1
10
20
50
100
200
500
4
3
0,4
0,3
∆p (bar)
0,5
1
0,2
0,1
1,5
0,3
0,4
0,6
0,8
1,2
0,9
0,7
∆p (m w.g.)
5
10
2
1
15
3
4
6
8
12
9
7
0,5
1 2 5
10
20
Flow
rate
(l/min) (m3 /h)
40
5
0,2
1/2”
3/4” 1” 1 1/4” 1 1/2” 2” DN 65
1/2” 3/4” 1” 1 1/4” 1 1/2” 2” DN 65
10
20
50
100
200
500
0,5
1 2 5
10
20
Flow
rate
(l/min) (m3 /h)
40
5
0,2
!$