Sequence Impedance in Different Power Equipments

7
4.9.2 Sequence Networks of a loaded Synchronous Gener ator: A three-pahse synchronous generator, having a synchronous impedance of  ¯ Z s  per phase, with its neutral grounded through a impedance  ¯ Z n  is shown in Fi g. 4. 44. The genera tor is supplyi ng a balanced thre e phase load. The generator voltages  ¯ E a ,  ¯ E b  and  ¯ E c  are balanced and hence treated Figure 4.44:  Three phase synchronous generator supplying a balanced load as positive sequence set of voltage phasors and can be expressed as: ¯ E abc = 1 a 2 a  ¯ Ea  (4.87) As the generator is supplying a three-phase balanced load, the following KVL equations can be written for each phase : ¯ V  a  =  ¯ E a  ¯ Z s ¯ I a  ¯ Z n ¯ I n ¯ V  b  =  ¯ E b  ¯ Z s ¯ I b  ¯ Z n ¯ I n  (4.88) ¯ V  c  =  ¯ E c  ¯ Z s ¯ I c  ¯ Z n ¯ I n 155

Transcript of Sequence Impedance in Different Power Equipments

Page 1: Sequence Impedance in Different Power Equipments

8/13/2019 Sequence Impedance in Different Power Equipments

http://slidepdf.com/reader/full/sequence-impedance-in-different-power-equipments 1/7

Page 2: Sequence Impedance in Different Power Equipments

8/13/2019 Sequence Impedance in Different Power Equipments

http://slidepdf.com/reader/full/sequence-impedance-in-different-power-equipments 2/7

Page 3: Sequence Impedance in Different Power Equipments

8/13/2019 Sequence Impedance in Different Power Equipments

http://slidepdf.com/reader/full/sequence-impedance-in-different-power-equipments 3/7

Page 4: Sequence Impedance in Different Power Equipments

8/13/2019 Sequence Impedance in Different Power Equipments

http://slidepdf.com/reader/full/sequence-impedance-in-different-power-equipments 4/7

Figure 4.46: The sequence networks of a transmission line

transmission line, the series leakage impedance will not change if the phase sequence of applied volt-

age is reversed. Therefore, the positive and negative sequence impedances offered by a transformerare equal. The zero sequece current ows through a transformer if paths for it to ow exist on theprimary as well the secondary sides. For such transformers the zero sequence impedance is equal tothe leakage impedance, as a consequence Z 0

= Z 1

= Z 2 . The positive and negative sequence networks

of a transformer are identical to the positive and negative sequence networks of a transmission lineas shown in Fig. 4.46 (a) and (b). The sequence networks for zero sequence depends on the windingconnections and whether or not the neutrals are grounded. To derive these circuits for differenttransformer connections, one has to keep in mind that an open circuit will exist on the primary(secondary) side if there is no ground return for primary (secondary) currents or if there is no corre-sponding path for secondary(primary) zero-sequence currents. The different three-phase transformerconnections and their equivalent zero-sequence networks are discussed next. It is assumed that theneutrals, if grounded, are solidly grounded.

Figure 4.47: The zero-sequence equivalent circuit of a Star-Star transformer with both neutralsgrounded

(a) Star-Star connections with both neutrals grounded: Since both the neutrals are grounded,thephasor sum of three unbalanced phase currents is equal to three times the zero sequence currentI a 0 (equation (4.82)). Hence, the zero sequence currents can ow in the primary and secondary

158

Page 5: Sequence Impedance in Different Power Equipments

8/13/2019 Sequence Impedance in Different Power Equipments

http://slidepdf.com/reader/full/sequence-impedance-in-different-power-equipments 5/7

windings and the transhomer, therefore, can be represented by the equivalent zero-sequenceleakage impedance. The equivalent circuit is shown in Fig. 4.47.

(b) Star-Star connections with only one neutral grounded: When the neutral of only one winding isgrounded, the phase currents of the ungrounded winding must add up to zero. This implies that

the zero sequence currents can not exist in the ungrounded winding and hence the zero sequencecurrents can not exist even in the transformer side with neutral grounded. The transformer inthis case, is represented as an open circuit between primary and secondary windings and theequivalent circuit is shown in Fig. 4.48.

Figure 4.48: The zero-sequence equivalent circuit of a Star-Star transformer with only one neutralgrounded

(c) Star-Star connections with only no neutral grounded: In this case also the phasor sum of thephase curents of both the windings is zero and hence the zero sequence currents can not exist onany winding in this case also. The zero sequence equivalent network is represented as an opencircuit between the two windings and is shown in Fig. 4.49.

Figure 4.49: The zero-sequence equivalent circuit of a Star-Star transformer with both neutralsungrounded

159

Page 6: Sequence Impedance in Different Power Equipments

8/13/2019 Sequence Impedance in Different Power Equipments

http://slidepdf.com/reader/full/sequence-impedance-in-different-power-equipments 6/7

Page 7: Sequence Impedance in Different Power Equipments

8/13/2019 Sequence Impedance in Different Power Equipments

http://slidepdf.com/reader/full/sequence-impedance-in-different-power-equipments 7/7

the windings. Hence, an open circuit exists between the two windings as far as zero-sequence cur-rents are concerned. To permit the circulating zero-sequence current to exist, the zero-sequenceleakage impedance is represented as a closed path with the ground. The equivalent circuit isshown in Fig. 4.52.

Figure 4.52: The zero-sequence equivalent circuit of a Delta-Delta transformer

Figure 4.53: The zero-sequence equivalent circuit of a Star-Delta transformer with neutral groundedthrough impedance

Point to remember: If the neutral of a transformer is grounded through a grounding impedanceZ n , as shown in Fig. 4.53, then, the total zero-sequence equivalent impdance to be used in theequivalent circuit is

Z 0 total = Z 0 + 3 Z n (4.95)

This is due to the fact that the neutral current is 3 times the zero-sequence current per phase.Next, the concepts of unsymmetrical fault analysis are developed with help of Thevenin’s equiv-

alent circuit of sequence networks and symmetrical components in the next lecture.

161