P O R TA B L E M E T H A N E D E T E C T O R
SENSIT® PMD
I N S T R U C T I O N M A N UA LR E A D A N D U N D E R S T A N D I N S T R U C T I O N S B E F O R E U S E
851 Transport DriveValparaiso, IN 46383-8432
Phone: 888 473 6748 219 465 2700Fax: 219 465 2701
Email: [email protected]: www.gasleaksensors.com
Warnings:
• Topreventignitionofflammableorcombustible atmospheresdisconnectpowerbeforeservicing.
• Removeandchargebatterypackinanareaknowntobe freeofcombustiblegases.
• UseonlySensitTechnologiesbatterypack.
• Servicemayonlybeperformedbyfactoryauthorized servicetechnicians
• Notforuseinenvironmentsgreaterthan21%oxygen.
Safety Precautions:
• Readandunderstandinstructionspriortouse.
• AlwaysstartthePMDinanareaknowntobegasfree.
• Tamperingwiththisproductmayvoidthewarranty.
• UseonlySensitTechnologiesapprovedparts andaccessories.
• Neveruseaninstrumentknowntobedamaged, operatingunusually,oroutofcalibration.
For further information contact Sensit Technologies.
SensitTechnologies851TransportDriveValparaiso,Indiana46383USA
Tel:219/465-2700Fax:219/465-2701
Email:[email protected]:www.gasleaksensors.com
TABLE OF CONTENTS Section Title Page
GeneralDescription......................................................4
PartsandAccessories..................................................5
ProductSpecifications..................................................6
ProductFeatures..........................................................6
ElectronicFeatures......................................................7
DisplayFeatures...........................................................8
HousingFeatures.........................................................9-10
Filters............................................................................11
FieldOperations...........................................................12
QuickMenu..................................................................13
UserMenu....................................................................14
Calibration....................................................................15
AdjustableFeatures......................................................16-17
Warranty.......................................................................20
4
TELESCOPICSURVEY BOOTand PROBE ROD
GRAPHIC DISPLAY INFRAREDCOMMUNICATIONS
ALARM LEDSOUNDER
FILTER
OPERATIONBUTTONS
BACKLIGHTSENSOR
“D”RING
General Description
TheSensit®PMD,referredtoasthe“PMD”,isdesignedtodetectmethanegasfrom1ppmupto100%volume.ThePMDmaybeusedforwalkingsurveysandvehiclesurveys(whenproperlyinstalled)forundergroundnaturalgaspipingsystems.Otherapplicationsincludelandfillmonitoringandcheckingpipingsystemswhereotherinterferinggasesmayprovideinaccuratereadings.
ThePMDsensesgasusingInfrared(IR)AbsorptionSpectroscopyincombinationwithanelectronicnarrowbandpassfilter.Thistechnologyutilizesaninfraredlightsourcewithanoutputthatischangedwhen certain gasesabsorb the light output. The filter only allows specific lightwavelengths to bemonitoredandmeasured.TheconcentrationofgasisproportionaltotheamountofspecificIRlightabsorbedandisdisplayedinPPM,%LELand/or%Vol.
ThePMDhasalargedisplayindicatingconcentrationandotherinstrumentfunctionssuchasbatterychargeandperformance.Aninternalpumpprovidesrapidsamplingintothedetectionchamber.Audibleandvisualalarmsindicatewhenpresetalarmsareexceeded.Bluetoothdatatransmissionprovidescommunicationofrealtimeandstoreddata.OptionalGPSandDataLoggingallowforfurtherrecordingoftime,dateandlocationdata.
5
Accessories
Standard Accessories
TelescopicSurveyProbe Part#883-00029Shoulder(Carrying)Strap Part#360-00238LithiumRechargeableBatteryPack Part#871-00017UniversalWallCharger Part#871-00025BatteryDoorRemovalTool Part#360-00249InstructionManual Part#750-00045HydrophobicFilterRingAssembly(10Pack) Part#873-00033SurveyProbeFilter(Blue)(1Filter) Part#360-00064
Optional Accessories
FiberglassBarHoleProbe Part#883-00019BrassBarHoleProbe Part#883-00018HDFiberglassBarHoleProbe Part#883-00021PMDManualCalibrationKit Part#881-00070BumpGasCylinder(50ppmCH4) Part#315-030004DeluxHardCarryingCase Part#872-00010CompactCarryingCase Part#872-00013ShippingBoxandFoam Part#872-00017HotSwapVehicleBattery Part#871-00030RemovableMemoryCard Part#360-00243PMDHarness Part#870-00046
Replacement Parts
Shoulder(Carrying)Strap Part#360-00238FilterCapAssembly“O”Rings Part#870-00034SurveyProbeFilter(Blue)(1Filter) Part#360-00064
6
Product Specifications
Operational Specifications
Temperature: -4to122FDutyCycle: ~7hoursResponsetime: T50<3secondsAlarms: Audible-95db@15inches Visual–Redbacklightondisplay Visual–Displayinfo Visual–Failureindicators Settings–PPMandLELPower: LithiumIonRechargeablebatterypack OptionalVehiclepoweradapterPumpFlow: 1lpmDetectionRange: 0-5000ppm 10–100%LEL 5-100%V/V
Physical Specifications
Size: 11”x4.5”x6.5”(Approximate)Weight: 6.1LbsConstruction: CastAluminum/ABSPlastic
Sensor Specifications
IRSensor: Wavelength–3.4m DetectionRange1ppm–100%v/v Warmup<10min Calibrationrequired-3months
Product Features• ThePMDisconstructedofdurableABSplastic• ThehousingisdesignedtomeetIP54protection• ThePMDisdesignedtomeetCat3IntrinsicSafetyrequirements• Batterypackisdesignedforeasyfieldreplacement• FieldorSmartCalcalibrationiseasilyperformed• Externalfiltersareinexpensiveeasytochange• TheLCDdisplayiseasytoread• ThePMDusesasimple“SensitStyle”userinterface• CommunicationwithotherdevicesiseasywithBluetoothinterface• RealtimeGPSisoptional• RealtimeDataloggingwithremovablestorageoption
7
Electronic Features
User Interface
Theuserinterfaceincludesthefollowingfeatures:• Threebuttonoperation• LEDStatusindicators• Sounder• Photocell(automaticbacklighting)• IRcommunicationport• LCD
Button Operation
TheSensitPMDisoperatedwiththeuseofthreebuttonsbelowthedisplay.
TheyarelabeledA,B,C.
The“A”button:• activates/deactivatestheinstrument• mutestheaudiblealarms• accessSmart-Calcommunication
The“B”button:• Accessesthequickmenuandusermenu• DigitallyadjuststheTICKsoundforleaklocating
The“C”button:• Savesdisplayedreadingstotheinternalmemory• Performsamanualzero.
8
Display Features
Thedisplayprovidesallinformationincluding:• GasconcentrationinPPM,LELAND%Vol• Batteryvoltagestatus• PumpStatus• GPSactivationandcoordinates• Bluetoothoperation• Dataloggingoperation• Warningindication• Tickoperation
Iconsonthedisplayindicatethestatusofvariousfunctions.
-FlowOK -Flowblocked
-Alarmnotmuted -PPMalarmmuted
-%LELalarmmuted -%GASalarmmuted
-Warning/trouble/failuresymbol
-BluetoothOnandConnected -Bluetoothonbutnotconnected
-TickON
-Dataloggingon–flashoncefordatasave
-DataSaved–flashonceformanualdatasave
-GPSConnected -GPSenabled-notconnected
9
Alarm settings
Thereare3adjustablealarmsettings.
1. PPM a. Default:10ppm b. LowLimit:0 c. Highlimit=500 d. DisablePPMalarm:SetthePPMalarmto0 e. Alarm:Audible,LED,Redbacklightifunitindark
2. %LEL a. Default:50%LEL b. LowLimit:10%LEL c. Highlimit=90%LEL(Ifnoautorangeto%gas) d. DisableLELalarm:Cannotdisablethisalarm(muteonly) e. Alarm:Audible,LED,Redbacklightifunitindark
3. %GAS a. Default17%Vol b. LowLimit:5%Vol c. HighLimit:50%Vol d. Disable%GASalarm:Cannotdisablethisalarm c. Alarm:LED,Redbacklightifunitindark
AdjustmentoftheppmalarmiscoveredintheUserMenuportionofthismanual.
Housing Features
Battery Pack
Thebatterypackislocatedonthebacksideoftheinstrumenthousing.ThebatteriesareLithiumIonrechargeable.ThebatteriesareonlyavailablefromSensitTechnologies.
Toremovethebatterypackturntheretainingscrews¼turn.Pullthebottomofthepackawayfromthemainhousing.Rechargingofthebatterypackrequiresremovalfromthemainhousing.
Toreplaceslidethetoptabsofthebatterypackintotheretainersatthetopofthemainhousing.Pushthebottomintoplaceandturnandlocktheretainingscrews.
10
ChargeComplete
(Green)
Charging
(Red)
Status
(Yellow)
ChargerConnection
Gas Inlet and Outlet
Locatedonthefrontofthemainhousingisthegasinletandoutlet.Botharefittedwithluer-styleconnectionsforeasyconnectiontoprobeaccessories.
Thecenterconnectionisthegasinlet.Totherightistheoutlet.Donotblockgasoutlet.
Shoulder Strap attachment
“D”ringsarelocatedoneachsideofthemainhousingforshoulderstrapattachment.Clipsonthestrapwillattachsecurely.
ThebatterypackhasLED’stoindicatechargestatus.Chargingshouldonlybeperformedinanareaknowtobefreeofcombustiblegases.
11
Hydrophobic Filter Assembly
WARNING:Donotoperatewithoutproperfilter.Damagemayoccurtothepumpandotherinternalparts.Onlychangefilterwithpumporinstrumentoff.
Thegasinletisprotectedbyahydrophobicfilter.
Itisaccessedby:1. Detachanyprobeassembly2. Twistandremovefiltercap3. Removeandreplacefilterdisc4. Check“O”ringinsidecap5. Replacefiltercap6. Performedflowblocktest
Additionalfiltersarelocatedineachoftheaccessoryprobeassemblies.
12
Operation and Field Use
ToactivateinstrumentpushPOWERbutton.Thefollowingwarm-upsequencewilloccur:
1. Warm-upsequence(a-i)withinfobelow.
a. Logo b.SerialNumber c.Revision d. SystemCheck i. LEDcheck ii. Backlightcheck iii. Date/Time e. Caldue(upcoming)orCalPastDue f. ActivationAcknowledgments i. Pump ii. Dataglog iii. GPS g. Sensorwarm-up(7-10Min)and“PleaseWait” h. Autozero i. Workingdisplay 2. Attachtheappropriateprobeassemblyandperformaflowblockcheck.An alarmsound,displayindicationandflowiconwillindicateafailedtest. 3. Followcompanyproceduresforperformingleaksurvey/investigation
4. Ifthealarmsettinghasbeenexceededpressandreleasethe“A”buttonto disablethealarm.Thealarmsoundwillautomaticallyresetwhenthe concentrationhasgonebelowthethresholdvalue.Secondaryalarmsathigher concentrationwillactivatewhenvaluesareexceeded.Pressandreleasethe“A” buttonagaintomutesecondaryalarms.Duringanyalarm,thedisplaybacklight willbeREDincolor.
5. Checkfiltersdailyforbestresults.
6. Batterypowerisdisplayedusingabatteryvoltageicon.Fullbatteryis12.0v. BATLOWVOLTwillbedisplayedat8vwheninsufficientbatterypowerisavailable.
7. Toturnofforputintostandbymodepushandholdthe“A”button.Itwill display“SHUTDOWN”onleftsideand“STANDBY”onrightsideofthedisplay. Pressthe‘A’buttontoturntheinstrumentoff.Press‘C’toputunitinstandby modewhichwillreducepowerconsumptionandwillallowyoutoreducethe warmuptimetoapproximatelytwominutes.Werecommendusingstandby modeforlessthan1hour.
13
QUICK MENU
Pressandrelease‘B’button.Thiswillprovideaccesstothefollowingfunctions.Pressthe“C”buttontoscrollthroughtheoptions.Use‘B’buttontoselect.Use‘B’buttonagaintoturnitOFFor‘C’buttontoturnON.Press‘A’buttontoselectyourchoiceandexitmenu.
1. TICK–Audibleleakdetectionmode.NOTE:Activatingthetickwilldisable soundalarm.
a. Whenactivatedatickwillbeheardeverysecond.Frequencyoftickwill increaseasgasconcentrationincrease. b. Pressandrelease‘B’buttonwillresetthetickfrequencyto1tickper second. Thetickfrequencywillincreaseifgasconcentrationincreasefrom thatconcentration. c. Toturnthetickoff,pressandrelease‘A’button.Pressandrelease‘A’button againtoactivatethealarmsound.
WhenviewingthefollowingselectionsUse‘B’buttontoselect.Use‘B’button againtoturnitOFFor‘C’buttontoturnON.Press‘A’buttontoselectyourchoice andexitmenu. 2. BHTest–Barholetestfunction 3. PUMP-Use‘B’buttontoselect.Use‘B’buttonagaintoturnitOFFor‘C’ buttontoturnON.Press‘A’buttontoselectyourchoiceandexitmenu. 4. GPS–RealtimeGPSX/Ycoordinates 5. SmartLink-UseBluetoothtodownloadlogs(Calibration,QuickCal,Session,Barhole,Autologs) 6.Warning-Usethisfeaturetolistcurrentfailuremode.
Bluetooth Activation
WhentheBluetoothisactivatedthedisplayreadingscanbetransmittedtoanydevicecapableofreceivingBluetoothdata.Thedatamayalsobeviewedbyusing“HyperTerminal”.Thewebsiteiswww.lgraeve.com
BluetoothPasskey:5DigitSerialNumber
SerialCommunicationsSettings:BitsPerSecond:57600Databits:8Parity:NoneStopbits:1Flowcontrol:None
DataStreamcanbeadjustedtosenddataevery1-10sec.youcanfindsettingstochangethisinExpertMenu->DataStream.YouneedtoturnDataStreamONinUserMenu.
OnceconnectedtotheBluetoothdevice,PMDsendsthe7digitPPMreading.
14
USER MENU
Toaccesstheusermenupushandholdthe“B”buttonuntilUSERMENUisdisplayed.Fromthismenuthefollowingfeaturescanbeviewedbypressingthe“C”buttontoscrollthroughtheoptions.Entertheselectionbypressingthe“B”buttonandadjustingbyusingthe“C”buttonortheonscreenprompts.Pressingthe“A”buttonrepeatedwillreturnyoutotheworkingdisplay.
Date and Time Viewthedateandtime. Timeisin24hourformat.Dateismm/dd/yyformat.
Print Menu Allowsaccesstoprintmenuforcalibrationandoperationalsessions.
Bump Test Performtimedtestforgasresponseinppmrange.Pumpmaybe selectedONorOFFforthisfunction.
Calib Menu CalibrationtoZeroAir,1000ppm,2.5%and100%methanegasconcentrations. ForinstructionrefertoCALIBRATIONsectionofthismanual. •ZeroAir-ToSetZeroPoint PumpOn/Off OnscreenInstruction •1000PPM-Tocalibrate1000ppmlevelonly (ZeroAircalibrationrequiredfirst-automatic) •2.5%V/V-toCal2.5%(50LEL)CH4 Only (ZeroAircalibrationrequiredfirst-automatic) •100%V/V-toCal100%(100LEL)CH4 Only (ZeroAircalibrationrequiredfirst-automatic) •FullCalib-Automaticallysequencezero,1000,2.5%V/V,100%V/V (ThisupdatesCalDue)
Datalog Activatesthedataloggingsystem.(IfActivatedw/memorycard)
Data Stream Activatesrealtimedatastreamingofdisplayreadingseverysecondto anotherrecordingdeviceusingBluetooth.Settingsonpage13.
Alarm PPM AdjustmentforPPMalarmvalue. Settingat0disablesalarm. Rangeis0-500ppm
Set Clock Adjustdateandtime.View Sess Log Viewmanuallysaveddata.View BHLOG Viewthebarholetestlogs(IfActivated).View Auto ViewAutologdataofoperationalpeakvalues.View Cal Log Viewcalibrationlog.QCal Log Viewrecordingofindividualcalibration(NotFullCalib)
15
Calibration Check
Toverifytheproperoperationofthisinstrumentapplyaknownconcentrationof50-1000ppmmethanetothesamplesystempriortouse.
Thisisnotarequiredprocessbutisrecommendediftheproducthasnotbeenusedformorethan30days.
Calibration
ThePMDrequirescalibrationevery3months.Anautomaticreminderwillnotifytheuserthatcalibrationisdueatstartup.
Calibrationcanonlybeperformediftheinstrumenthasbeenoperationalfor30minutes.
Tocalibratetheareamustbeknowntobegasfree.Ifthereismethaneintheareaabottleofzeroairwillbenecessary.Othergasesrequiredinclude1000ppm,2.5%and100%methane(pipelinegasisalsoacceptable).Somegasescanbecalibratedindividually.ContactSENSITTechnologiesServiceDepartmentformoreinformation.
Calibrationisperformedwiththepumpoffifthereisnoaccesstodemandflowregulatorsforthecalibrationbottles.Turn-offisselectedpriortocalibration.
CalibrationisperformedthroughtheUserMenu.Usingthe“B”buttonaccesstheUserMenu.Usethe“C”buttontoscrollto“CalibMenu”.
Tobeginpressthe“B”button.Iftheinstrumenthasnotoperatedfor30minutesacountdowntimerinsecondswillbedisplayed.Whentheproperamountoftimehasbeenmetthedisplaywillshow“Proceed”.Pressanybutton.Abeepwillbeheard.
SelectCalTypeandfollowon-screenprompts.FullCalibisreccomended.
Applyzeroppmmethaneorcleanair.Press“C”buttontobeginzeroaircalibration.Displaywillshow“waitingforstability”followedby“success”whencompleted.Pressanybuttontocontinue.
Displaywillread“pleaseapply1000ppmmethane”.Attachandapply1000ppmmethane.Theprocessrequires1-5minutes.SearchingOPTTEMPwillbedisplayed,thendisplaywillshow“waitingforstability”followedby“success”whencompleted.
Displaywillread“pleaseapply2.5%methane”.Attachandapply2.5%methane.Theprocessrequires1-5minutes.Displaywillshow“waitingforstability”followedby“success”whencompleted.
Displaywillread“pleaseapply100%methane”.Attachandapply100%methane.Theprocessrequires1-5minutes.Displaywillshow“waitingforstability”followedby“success”whencompleted.
Uponcompletionpressanykeytoexittoworkingdisplay.Activatethepumpandallowtoclearpriortoturningoff.Thecalibrationreminderwillautomaticallyupdateaftersuccessfulcalibration.
16
Adjustable Features (passwordprotected)ContactSensitTechnologiestogainaccesstothefollowingadjustablefeaturesnotintheusermenu.
Service Contrast: Adjustthedisplaycontrastasneeded.
Quick Scan: OptimumTempAdjust(1000ppmrequired) Orientation Cal: Calibrationoflampoutputindifferentpositions. Cal Flow: Settingflowalarm
Tick SENS Lo,Med,orHigh
Alarm %LEL AdjusttheLELalarmvalue.Defaultis50%.
Alarm %V/V Adjustthepointwhenthealarmdeactivates.Defaultis17%.
Show SESS Allowdisplayofmanuallysaveddata.Defaultisoff.
Show BHLOG AllowdisplayofBHtests.Defaultisoff
Show AUTO AllowdisplayofAutologdata.Displayisoff.
BH Time Setthetimeinsecondsfordurationofthebarholetest. Defaultis15seconds.
Purge Time Setpurgetimeforinstrumentpriortoshutdown. Defaultis10seconds.
Standby Timeofinactivityorlackofmotioninminutesthatwillcausethe instrumenttoautomaticallygointolowpowermode.Defaultisoff.
Shutdown Timeinminutesthatshutdownwilloccurwheninstandbymode. Defaultis60.
Bump Limit Concentrationofgastobeacceptablewhenperformingabumptest. Rangeis5–1000ppm.Defaultis800.SetLowerandUpperLimit.
Bump Time Timerequiredinsecondsforunittopassabumptest. Rangeis10-60.Defaultis45.
Log Period TimebetweenDatalogpointsinseconds.Range1-60.Defaultis1.
Data Stream Timeinsecondsfordatatobestreamedthrough Bluetoothcommunication.Defaultif1second.
17
Adjustable Features (Continued)Rest UCal Resetcaldatatofactorysettings(PasswordProtected)
Set Cal Due TimeInterval(90Default)
Cal Due Ack RequiresbuttonpushafterCalDuereminder(defaultoff)
DISP Callog Last5calibrationrecords PPM Option: PPMAutorangetoLEL.Defaultison.
PPM Handoff: HandofffromPPMtoLELor%V/Vsetting.(default5000)
% LEL Option: LELfrom0.1-100%.DefaultisOn 100% LEL Equiv: SetLELlimitsfrom4.0–5.0%gasvolume.Defaultis5%. PPM+%LEL: DisplaybothPPMand%LEL.DefaultisOff NG Factor: Automaticcalculationforlowmethanepipelinegas.(default100)
UCal Date Dateoflastfullusercalibration Erase Auto EraseAutolog
Erase Sess ErasemanuallysaveddataLog Erase BHLog Erasebarholetestlog
SCal Pump On/OffDuringCal(foreachgastype)whencalibratingonthecal-station
Rezero REQD DowndriftAlert,On/Off,Value5Default
Language Selectlanguagefordisplay
Auto Bump Requirebumptestbeforeuse(defaultoff,adjustable1-30days)
Erase Bump EraseAutoBumpLog
Saving SD Card Data Log Information
RemoveSDMemoryCardfrominsidethebatterycompartment.InstallSDMemoryCardincomputer.SaveFileindesiredformatandlocation.Preferredformatis.kml
GPS Data Conversion & Coordinate Mapping
GPSDataconversionandmappingcanbeaccomplishedusingSmart-LinkDataViewerSoftwareandGoogleEarthorgpsvisualizer.com
1.UsingSmartLinkselectthedesiredreports.(See“Howtouse”and“Reports”sectionofSmartLinkHelpfileformoreinformation.)
2.Click“SaveReport”button.Savereportasformat.kmlformat.ThisformatwillonlysaveloginformationforwhichvalidGPScoordinateinformationisavailable.
3.GoogleEarthmustbeinstalled(FreeDownload).Doubleclickthe.kmlfile.ItwillopenGoogleEarthandloadthemap.
Note:IfGoogleEarthisnotinstalled,proceedtonumber4.
4.Goto:http://www.gpsvisualizer.com/Select“Google Maps”.
18
Import your .kml file:
1.Usingbrowsebutton,selectthefileyouwishtoview.
2.Selectthemaptype.
Way-points: To display coordinates, gas concentrationdetectedandtimeatspecificlocations.ItisbesttousewithSession-log,Bar-holelogandAuto-log.
Route points: The “route” would represent the road,trail, path, etc. that you have taken. It also display gasconcentrationdetectedandtimeatspecificlocations.It isbesttousewithData-logtoviewareasurveyed.
3.Click“Drawthemap”button.
19
GPS Data Conversion & Coordinate MappingSampleofthedatalogreportisdisplayedbelow.
Warranty
YourSensitPMDiswarrantedtobefreefromdefectsinmaterialsandworkmanshipforaperiodoftwoyearsafterpurchase(excludingcalibration).Ifwithinthewarrantyperiodtheinstrumentshouldbecomeinoperativefromsuchdefectstheinstrumentwillberepairedorreplacedatouroption.Thiswarrantycoversnormaluseanddoesnotcoverdamagewhichoccursinshipmentorfailurewhichresultsfromalteration,tampering,accident,misuse,abuse,neglectorimpropermaintenance.Proofofpurchasemayberequiredsbeforewarrantyisrendered.Unitsoutofwarrantywillberepairedforaservicecharge.InternalrepairormaintenancemustbeperformedbyaSensitTechnologiesauthorizedtechnician.Violationwillvoidthewarranty.Unitsmustbereturnedpostpaid,insuredandtotheattentionoftheservicedepartmentforwarrantyorrepair.
Thiswarrantygivesyouspecificlegalrightsandyoumayhaveotherrightswhichvaryfromstatetostate.
SensitTechnologies851TransportDriveValparaiso,Indiana46383USA
Tel:219/465-2700Fax:219/465-2701
Email:[email protected]:www.gasleaksensors.com
SENSIT PMD INSTRUCTION MANUALPart # 750-00045 Revision12-15-17