SELECTABLE-RANGE AC CURRENT TRANSDUCER Model CTS-150 · selectable-range ac current transducer...

2
Single unit offers: Inputs from 0 to 50, 100 & 150 Amps Outputs from 0 to 1, 5 or 10 Volts Field selectable Switch-Selectable Input and Output Ranges n One model serves a variety of applications n Accommodates changes in load conditions without replacement n Minimizes spare parts inventory Faster, Simpler Installation n Clamped, split-core design for fast, non-interrupting installation n Flying leads to minimize wiring and installation time n Compact size to fit in tight spaces n Self-powered to minimize installation complexity Building Automation Data Loggers Panel Meters Remote Monitoring Load Monitoring Branch Monitoring Process Automation Control Systems Potential Applications Accuracy and Durability n 1.0% of full scale accuracy on any range n Average measurement with RMS calibration n 4X over-range capability n 600 volt isolation, tested to 3,500 volts SELECTABLE-RANGE AC CURRENT TRANSDUCER Model CTS-150 4242 REYNOLDS DRIVE HILLIARD, OHIO 43026 -1264 PHONE: (614) 777-1005 FAX: (614) 777- 4511 WWW.OHIOSEMITRONICS.COM 1-800-537-6732 08/2016

Transcript of SELECTABLE-RANGE AC CURRENT TRANSDUCER Model CTS-150 · selectable-range ac current transducer...

Page 1: SELECTABLE-RANGE AC CURRENT TRANSDUCER Model CTS-150 · selectable-range ac current transducer model cts-150 4242 reynolds drive • hilliard, ohio • 43026-1264 phone: (614) 777-1005

Single unit offers:

Inputs from 0 to 50, 100 & 150 Amps

Outputs from 0 to 1, 5 or 10 Volts

Field selectable

Switch-Selectable Input and Output Ranges n One model serves a variety of applications

n Accommodates changes in load conditions without replacement

n Minimizes spare parts inventory

Faster, Simpler Installation n Clamped, split-core design for fast, non-interrupting installation

n Flying leads to minimize wiring and installation time

n Compact size to fit in tight spaces

n Self-powered to minimize installation complexity

Building Automation

Data Loggers

Panel Meters

Remote Monitoring

Load Monitoring

Branch Monitoring

Process Automation

Control Systems

Potential Applications

Accuracy and Durability n 1.0% of full scale accuracy on any range

n Average measurement with RMS calibration

n 4X over-range capability

n 600 volt isolation, tested to 3,500 volts

SELECTABLE-RANGE AC CURRENT TRANSDUCER Model CTS-150

4242 REYNOLDS DRIVE • HILLIARD, OHIO • 43026-1264 PHONE: (614) 777-1005 • FAX: (614) 777-4511 WWW.OHIOSEMITRONICS.COM • 1-800-537-6732

08/2016

Page 2: SELECTABLE-RANGE AC CURRENT TRANSDUCER Model CTS-150 · selectable-range ac current transducer model cts-150 4242 reynolds drive • hilliard, ohio • 43026-1264 phone: (614) 777-1005

Input Range (selectable)

Over-range (10 seconds)

Frequency Range

Output Signal (selectable)

Response Time (to 90% of FS)

Ripple (Vpp)

Output Loading

Accuracy

Temp Effect (-40 to 70 ˚C)

Operating RH

Insulation Class

Withstand Voltage

Sensing Aperture

Storage Range

Case

Compliance

Weight

50, 100, or 150 amps

4 X

50-60 Hertz

0 to 1, 5 or 10 volts

<200 mSec

<1.0% FS

>1 Megohm, min

1.0% of Full Scale (FS)

0.006% / ˚C typical

0-95%, non-condensing

600 VAC

3500 VAC for 1 minute

1.00 X 0.91 inches

-40 to 85 ˚C

UL94 V-0

RoHS

0.5 lbs

SPECIFICATIONS TABLECONNECTIONS & DIMENSIONS

1.66 [42.16]

0.88 [22.35]

1.84 [46.74]

1.44 [36.58]APPROXIMATELY 72”

(-) BLK(+)WHT

(-) BLK(+)WHT

OUTPUT

0.44 [11.18]

0.91 [23.10]

3.12 [79.32]

1.87 [47.45]

0.49 [12.45]

1.00 [25.40]

SELECTABLE-RANGE AC CURRENT TRANSDUCER

INPUT & OUTPUT RANGE SELECTION

0-50Aac Input

0-100Aac Input

0-150Aac Input

0-1Vdc Output 0-5Vdc Output 0-10Vdc Output

DIP-SWITCH SETTINGS

1 2 3 4 5 6

OPEN

1 2 3 4 5 6

OPEN

1 2 3 4 5 6

OPEN

1 2 3 4 5 6

OPEN

1 2 3 4 5 6

OPEN

1 2 3 4 5 6

OPEN

1 2 3 4 5 6

OPEN

1 2 3 4 5 6

OPEN

N/A

4242 REYNOLDS DRIVE • HILLIARD, OHIO • 43026-1264 PHONE: (614) 777-1005 • FAX: (614) 777-4511 WWW.OHIOSEMITRONICS.COM • 1-800-537-6732

Bottom view withDip-Switch identification

Model CTS-150

08/2016