Sect-7
-
Upload
sry-santos -
Category
Documents
-
view
221 -
download
7
description
Transcript of Sect-7
Section 7: UPS System Control
Chapter 1 - UPS System Control Principles
1.1 Introduction .............................................................................................. 7-1
Chapter 2 - High Voltage Interface Board
2.1 Chapter overview ..................................................................................... 7-5
2.2 General description ................................................................................... 7-5
2.3 Detailed description .................................................................................. 7-72.3.1 X1 Low voltage signals to/from the UPS Logic Board. .............. 7-72.3.2 X2 (Page 2) – DC bus (battery) voltage sense ............................. 7-72.3.3 X3 (Page 2) – Rectifier input voltage sense ................................. 7-72.3.4 X4 (Page 2) – UPS output voltage sense ..................................... 7-72.3.5 X5 (Page 2) – Inverter output voltage sense ................................ 7-72.3.6 X6 (Page 2) – Bypass voltage sense ............................................ 7-82.3.7 X7 (Page 1) – Power switch auxiliary contacts ........................... 7-82.3.8 X8 (Page 1) – Interface to external connection block .................. 7-82.3.9 X9 (Page 2) – Battery cabinet temperature .................................. 7-92.3.10 X10 (Page 2) – Input air temperature sensor ............................. 7-92.3.11 X11 (Page 2) – Inverter output air temperature sensor .............. 7-92.3.12 X12 (Page 2) – Transformer cubicle air temperature sensor ..... 7-92.3.13 X13 (Page 1) – Inverter assembly thermostats ........................ 7-102.3.14 X14 (Page 1) – Not in use ........................................................ 7-102.3.15 X15 (Page 1) – Battery fuse monitor ....................................... 7-102.3.16 X16 (Page 1) – Not in use (linked out) .................................... 7-102.3.17 X17 (Page 1) – Not in use (linked out) .................................... 7-102.3.18 X18 (Page 1) – Rectifier current sensing ................................. 7-102.3.19 X19 (Page 1) – Output current monitoring W-ph .................... 7-102.3.20 X20 (Page 1) – Output current monitoring V-ph ..................... 7-102.3.21 X21 (Page 1) – Output current monitoring U-ph ..................... 7-112.3.22 X22 (Page 1) – Battery current monitoring ............................. 7-112.3.23 X23 (Page 1) – Inverter current monitoring U-ph ................... 7-112.3.24 X24 (Page 1) – Inverter current monitoring V-ph ................... 7-112.3.25 X25 (Page 1) – Inverter current monitoring W-ph .................. 7-112.3.26 X26 (Page 1) – Not in use ........................................................ 7-112.3.27 X27 (Page 1) – Not in use ........................................................ 7-11
2.4 Summary information ............................................................................. 7-12
Chapter 3 - UPS Logic Board (4550007 H)
3.1 Chapter overview ................................................................................... 7-13
3.2 General description ................................................................................. 7-133.2.1 Circuit board functions .............................................................. 7-133.2.2 Input/Output connections ........................................................... 7-143.2.3 Block Diagram ........................................................................... 7-20
S-7.FM5 - Issue 2 Dated 21/08/97 i
SECTION 7 - UPS System Control 7200 Series UPS Service Manual
3.3 Detailed circuit description .................................................................... 7-233.3.1 Introduction ................................................................................ 7-233.3.2 Basic microcontroller system ..................................................... 7-243.3.3 Data bus, address bus and control bus buffers ........................... 7-263.3.4 Ni-Cad Battery back-up controller ............................................. 7-263.3.5 Reset generator ........................................................................... 7-273.3.6 System RAM and ROM memory addressing ............................ 7-283.3.7 Basic system control logic (D88) ............................................... 7-29
D88 Status signals to processor system ........................... 7-31D88 Reset circuit [RES_EXT> ........................................ 7-32Major control signal outputs ............................................ 7-32Load transfer control ........................................................ 7-34
3.3.8 CAN bus communications drivers and control logic ................. 7-353.3.9 Real-time clock (RTC) ............................................................... 7-353.3.10 Data bus buffers ‘chip select’ decoding ................................... 7-373.3.11 Data bus input buffers .............................................................. 7-383.3.12 Data bus output buffers ............................................................ 7-453.3.13 Frequency sensing and control signals .................................... 7-55
Frequency control principles ............................................ 7-55Frequency sync control and operation ............................. 7-56Non-Sync detection and alarm ......................................... 7-58External ‘sync inhibit’ ...................................................... 7-58
3.3.14 Analogue signal processing ..................................................... 7-59Bypass voltage signal processing ..................................... 7-59Inverter voltage sensing ................................................... 7-60Battery (bus) voltage sensing ........................................... 7-61Battery current sensing .................................................... 7-61Output voltage sensing ..................................................... 7-62Output current sensing ..................................................... 7-63Analogue signal monitoring multiplexers 7-64
3.3.15 Power supplies ......................................................................... 7-653.3.16 External communications ......................................................... 7-673.3.17 On board 7-segment indications summary .............................. 7-68
3.4 Summary information ............................................................................. 7-72
Chapter 4 - UPS Logic Board (4550004 E)
4.1 Chapter overview ................................................................................... 7-75
4.2 General description ................................................................................. 7-754.2.1 Circuit board functions .............................................................. 7-754.2.2 Input/Output connections ........................................................... 7-764.2.3 Block Diagram ........................................................................... 7-81
4.3 Detailed circuit description .................................................................... 7-844.3.1 Introduction ................................................................................ 7-844.3.2 Basic microcontroller system ..................................................... 7-854.3.3 Data bus, address bus and control bus buffers ........................... 7-884.3.4 Ni-Cad Battery back-up controller ............................................. 7-884.3.5 Reset generator ........................................................................... 7-894.3.6 System RAM and ROM memory addressing ............................ 7-90
ii S-7.FM5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System Control
4.3.7 Basic system control logic ......................................................... 7-92D22 Functional description .............................................. 7-92D23 Functional description .............................................. 7-94
4.3.8 CAN bus communications drivers and control logic ................. 7-964.3.9 Real-time clock (RTC) ............................................................... 7-964.3.10 Data bus buffers ‘chip select’ decoding ................................... 7-984.3.11 Data bus input buffers .............................................................. 7-994.3.12 Data bus output buffers .......................................................... 7-1054.3.13 Frequency sensing and control signals .................................. 7-113
Frequency control principles .......................................... 7-113Frequency sync control and operation ........................... 7-114Non-Sync detection and alarm ....................................... 7-116External ‘sync inhibit’ .................................................... 7-116
4.3.14 Analogue signal processing ................................................... 7-117Bypass voltage signal processing ................................... 7-117Inverter voltage sensing ................................................. 7-118Battery (bus) voltage sensing ......................................... 7-119Battery current sensing .................................................. 7-119Output voltage sensing ................................................... 7-120Output current sensing ................................................... 7-121Analogue signal monitoring multiplexers ...................... 7-122
4.3.15 Power supplies ....................................................................... 7-1234.3.16 External communications ....................................................... 7-1254.3.17 On board 7-segment indications summary ............................ 7-126
4.4 Summary information ........................................................................... 7-130
Chapter 5 - Operator Logic Board
5.1 Chapter overview ................................................................................. 7-133
5.2 General description ............................................................................... 7-1335.2.1 Circuit board functions ............................................................ 7-1335.2.2 Input/Output connections ......................................................... 7-1345.2.3 Block Diagram ......................................................................... 7-135
5.3 Detailed circuit description .................................................................. 7-1375.3.1 Introduction .............................................................................. 7-1375.3.2 Basic microcontroller system ................................................... 7-1385.3.3 Data bus, address bus and control bus buffers ......................... 7-1395.3.4 Reset generator ......................................................................... 7-1405.3.5 Alarm buzzer ............................................................................ 7-1405.3.6 Address decoding – D10 .......................................................... 7-1405.3.7 System RAM and ROM memory addressing .......................... 7-1415.3.8 Interface to the Operator Control Panel ................................... 7-1425.3.9 Interface to the CAN Bus ......................................................... 7-1435.3.10 Serial (modem) Interface ....................................................... 7-1445.3.11 RS232 & RS485 Interface ..................................................... 7-1445.3.12 Power Supply ......................................................................... 7-145
5.4 Summary information ........................................................................... 7-146
S-7.FM5 - Issue 2 Dated 21/08/97 iii
SECTION 7 - UPS System Control 7200 Series UPS Service Manual
Chapter 6 - Operator Control Panel
6.1 Section overview .................................................................................. 7-149
6.2 General description ............................................................................... 7-1496.2.1 Circuit board functions ............................................................ 7-1496.2.2 Input/Output connections ......................................................... 7-149
6.3 Detailed circuit description .................................................................. 7-1506.3.1 LED Display indication ........................................................... 7-1506.3.2 Operator input switches ........................................................... 7-1516.3.3 LCD Display Panel .................................................................. 7-151
Chapter 7 - System software
7.1 Introduction .......................................................................................... 7-153
7.2 Program structure and execution .......................................................... 7-1537.2.1 Initialisation/Reset ................................................................... 7-1567.2.2 Rectifier ON/OFF subroutine .................................................. 7-1587.2.3 Inverter OFF/ON Sub-routine .................................................. 7-1607.2.4 Frequency synchronisation control .......................................... 7-1627.2.5 Battery circuit breaker control ................................................. 7-1687.2.6 Low Battery Pre-alarm ............................................................. 7-1727.2.7 Battery undervoltage trip threshold ......................................... 7-1747.2.8 Battery Boost charge ................................................................ 7-1767.2.9 Battery Test .............................................................................. 7-1787.2.10 Load transfer control logic ..................................................... 7-180
iv S-7.FM5 - Issue 2 Dated 21/08/97
Section 7: UPS System Control
Chapter 1 - UPS System Control Principles
1.1 Introduction
Previous descriptions in this manual show that the UPS can broadly be dividedinto three major areas, each of which is largely independently controlled – i.e:
• the rectifier – (See section 4)• the inverter – (See section 5)• the static switch – (See section 6)
However, a study of these sections show that there is also a degree of commonal-ity concerning certain of their control functions; for example, the way in whichtheir required analogue sense signals are processed and applied, and their operat-ing parameters set from the Operator Control Panel.
The chapters in this section (7) describe those boards concerned with servicing thecontrol requirements of all three of the major power sections mentioned above,and as such are the boards that bring together the control functions of the entireUPS system – hence the section title UPS System Control. A block diagram show-ing the relationship between the System Control boards and the other UPS controlareas is shown in Figure 7-1.
High Voltage Interface Board
Analogue signal processing. The High Voltage Interface Board is responsiblefor processing the analogue sense signals obtained from various parts of the UPSpower sections – as illustrated in Figure 7-1. It attenuates, and where necessaryisolates, the sensed signals to levels acceptable to the low voltage operating envi-ronment of the other control boards, and in certain instances also provides ameans of signal calibration. The board’s output are then passed to the major con-trol logic boards via the UPS Logic Board, which is at the heart of the System Con-trol function.
Digital signal processing. This board also monitors various digital status sig-nals and passes them once again to the UPS Logic Board, where they are used bythe decision-making processes in its microcontroller’s software. For example,Figure 7-1 shows inputs from the power switch auxiliaries; but not shown are var-ious external inputs from circuits such as the Emergency Stop facility, batterycabinet thermostats etc.
Operator Control Panel & Operator Logic Board
These two boards provide the digital interface between the Operator and the UPSLogic Board and permit two-way data communication – i.e. metering data gener-ated on the UPS Logic Board are processed on the Operator Logic Board and thenpresented to the Operator Control Panel; conversely, parameter settings andmanual control inputs entered at the Operator Control Panel are passed throughthe Operator Logic Board processing circuits to the UPS Logic Board where theyimpinge on the microcontroller’s decision-making operation.
s7-c1.fm5 - Issue 2 Dated 21/08/97 7-1
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 1 - UPS System Control Principles
Figure 7-1: UPS Control system block diagram
Input mains
Inp
ut
Ch
oke
Ph
ase
C
on
tro
lled
Re
ctifi
er
DC
Bus
ba
rfil
ter
cap
aci
tors
Battery current sense
Input current sense
Inp
ut
Fu
ses
DC Bus voltage sense
Inp
ut
Iso
lato
rR
ecti
fie
r C
on
tro
l
Dri
ve (
Tri
gg
er)
Inte
rfa
ce B
d.
Re
ctifi
er
Lo
gic
B
oa
rd
UP
S L
og
ic B
oa
rd
Hig
h V
olt
ag
eIn
terf
ac
e B
oa
rd
Op
era
tor
Lo
gic
Bo
ard
Op
era
tor
Co
ntr
ol
Pa
ne
l
Ala
rm I
nte
rfa
ce B
oa
rd(I
/O O
ptio
n)
ON
GE
NE
RA
TO
R
Re
mo
te A
larm
s
Ou
tpu
tT
frm
r
3 P
ha
se
Po
we
rIn
vert
er
filte
r ca
pac
itors
Inv
ert
er C
on
tro
l
Inve
rte
r B
ase
D
rive
Bd
s.
Inve
rte
r L
og
icB
oa
rd
Inverter current sense
Inverter voltage sense
Critical Load
Inve
rte
r-si
de
Co
nta
cto
r
Bypass Mains
Q1 Aux
CBbat Aux
Output voltage sense
Output current sense
Byp
ass
-sid
eS
tatic
Sw
itch
Sta
tic
Sw
itch
Co
ntr
ol
Out
pu
tIs
olat
or
Q4 Aux
Byp
ass
Iso
lato
r
Q2 Aux
Mai
nte
na
nce
Byp
ass
Iso
lato
r
Q3 Aux
Sta
tic S
witc
h
Dri
ver
Bo
ard
Inpu
t vo
ltag
e s
ens
e
Bat
tery
cu
rren
t se
nse
Inp
ut c
urr
ent
sens
eD
C B
us
volta
ge
se
nse
Inve
rte
r cu
rre
nt
sen
seIn
vert
er
volta
ge s
en
se
Q1
Au
xC
Bb
at A
ux
Byp
ass
vol
tag
e s
ense
Out
pu
t cu
rre
nt s
en
seQ
4 A
ux
Q2
Au
xQ
3 A
ux
Ba
tter
y B
rea
ker
Tri
p
Input voltage sense
Inverter voltage sense
Sy
ste
m C
on
tro
l
Bypass voltage sense
Dri
ve (
Tri
gg
er)
Inte
rfa
ce B
d.
Ou
tpu
t vo
ltag
e s
ens
e
Pa
ralle
l Co
ntr
ol B
us
Pa
ralle
l Lo
gic
Bo
ard
(1
+1
on
ly)
7-2 s7-c1.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 1 - UPS System Control Principles
Alarm Interface Board
Several forms of Alarm Interface Board are available to allow remote indicationof the alarms generated on the UPS Logic Board (refer to the Options Section ofthis manual). These boards also permit the connection of certain basic externalcontrols; such as on-generator, sync inhibit, second stage current limit etc.
UPS Logic Board
As is evident from reading the earlier part of this chapter, the UPS Logic Boardis central to the whole System Control function.
This board, which is micro-controller driven, accepts various analogue and digitalinputs from the High Voltage Interface Board, Operator Control Board and AlarmInterface Board (optional) and provides the necessary control and alarms signalsused by the remainder of the UPS control areas. It also monitors various alarm andstatus signals from the rectifier, inverter and static switch control sections andproduces appropriate alarms and control logic signals.
The board is software-driven and a description of the software functions and flow-charts are provided at the end of this section (see Chapter 7).
In a 1+1 configured system the UPS Logic Board is also fed with various controland status signals from the Parallel Logic Board pertaining to the parallel-controlfunctions (See section 8).
s7-c1.fm5 - Issue 2 Dated 21/08/97 7-3
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 1 - UPS System Control Principles
7-4 s7-c1.fm5 - Issue 2 Dated 21/08/97
Section 7:
Chapter 2 - High Voltage Interface Board
2.1 Chapter overview
This chapter contains a circuit description of the High Voltage Interface Boardused across the whole model 7200 Series UPS range and should be read in con-junction with circuit diagram SE-4590054-O (2 pages).
Signal annotations shown on the circuit diagrams are shown in italics in the fol-lowing text – e.g. VINV_A.
2.2 General description
The purpose of this board is to provide an interface between the high voltage en-vironments of the UPS power circuitry and the low voltage environment of thesystem control boards. The high voltage sense signals taken from various parts ofthe power circuitry are therefore attenuated on this board before being applied totheir appropriate control circuits.
In addition to providing signal attenuation the board also contains calibration fa-cilitates for those signals which are power-related. This allows the board to beused across the entire model range providing the calibration links are set appro-priately.
All the low-voltage signals are connected to the UPS Logic Board via socket X1and ribbon cable W8: the remaining IDC connectors (X2 to X27) carry the highvoltage signals.
Table 7-1on the following page provides an overview of each connectors’ func-tion and this is followed by a more detailed circuit description.
Power supplies
The ±12V control power rails required by the board’s op-amps are obtained fromthe UPS Logic Board and connected via X1 pins 1-12 as shown on the circuit di-agram page 2.
s7-c2.fm5 - Issue 2 Dated 21/08/97 7-5
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 2 - High Voltage Interface Board
.
Table 7-1: Connector summary
X1 Low voltage signals to/from the UPS Logic Board.
X2 DC bus (battery) voltage sense inputs.
X3 Rectifier input voltage sensing inputs
X4 UPS output voltage sensing inputs
X5 Inverter output voltage sensing inputs
X6 Bypass voltage sensing inputs
X7 Power switch auxiliary contacts
X8 Interface to customer connection block X8
X9 Battery cabinet temperature
X10 Input air temperature sensor inputs
X11 inverter output air temperature sensor inputs
X12 Transformer cabinet air temperature sensor inputs
X13 Inverter assembly thermostats (n/c)
X14 Not in use
X15 Battery fuse monitor
X16 Not in use (linked out) – inverter fuse fail
X17 Not in use (linked out) – rectifier fuse fail
X18 Rectifier input current monitor
X19 Output current monitoring W-ph
X20 Output current monitoring V-ph
X21 Output current monitoring U-ph
X22 Battery current monitoring
X23 Inverter current monitoring U-ph (12 pulse inverter only)
X24 Inverter current monitoring V-ph (6 pulse & 12 pulse inverter)
X25 Inverter current monitoring W-ph (6 pulse & 12 pulse inverter)
X26 Not in use – 12 pulse rectifier DC current ½ bridge
X27 Not in use – 12 pulse rectifier DC current ½ bridge
7-6 s7-c2.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 2 - High Voltage Interface Board
2.3 Detailed description
The remainder of this chapter contains a detailed description of the circuits asso-ciated with each of the above connectors.
2.3.1 X1 Low voltage signals to/from the UPS Logic Board.
X1 carries various signals between the High Voltage Interface Board and the UPSLogic Board, each of which is described in detail below. It also carries ±12Vpower supplies from the UPS Logic Board to the High Voltage Interface Board toprovide it with general control power supply rails and also power the DCCT de-vices used to monitor the battery current and inverter output current.
2.3.2 X2 (Page 2) – DC bus (battery) voltage sense
The DC Bus (battery) voltage is monitored at connector X2, attenuated by N4dand connected to the UPS Logic Board via X1-27. The attenuation factor is ap-proximately 136:1 – i.e. V_B has a sensitivity of approximately 7.3mV per V(bat-tery) and is therefore approximately 3.255Vdc. at a nominal float charge of 446V.
2.3.3 X3 (Page 2) – Rectifier input voltage sense
The input mains line voltage is connected to connector X3, attenuated by threesections of N4 and connected to the UPS Logic Board via X1 terminals 24,25,26.
Each section of N4 monitors the input voltage on a line-to-line basis; for exampleN4a inputs are connected to the input U (Vrec-A) and V (Vrec-B) phases. The at-tenuation factor is approximately 75:1 – i.e. VREC_AB has a sensitivity of ap-proximately 13.3mV per Vl-l (input volts) and therefore equals 5.8Vrms (15Vp-p)when the input mains voltage is at a nominal 400Vac.
Note: the input voltage is applied to X3 only when the input power switch Q1 isclosed and the main input power fuses are healthy.
2.3.4 X4 (Page 2) – UPS output voltage sense
The UPS output voltage is connected to connector X4, attenuated by three sec-tions of N3 and connected to the UPS Logic Board via X1 terminals 21,22,23.
Each section of N3 monitors the output voltage on a line-to-neutral basis; for ex-ample N3a inputs are connected to the output neutral (Vout-0) and U phase(Vout-A). The attenuation factor is approximately 100:1 – i.e. VO_A has a sensi-tivity of approximately 10mV per Vl-n (output) and therefore equals 2.2Vrms(8Vp-p) when the UPS output voltage is at a nominal 220Vac.
Note: the output voltage is connected to X4 from the ‘live’ side of the outputpower switch Q4 and is present when the inverter output contactor is closed (loadon inverter) OR the bypass static switch is closed (load on bypass) but not whenthe load is running on the maintenance bypass and the UPS is shut down.
2.3.5 X5 (Page 2) – Inverter output voltage sense
The inverter output voltage is connected to connector X5, attenuated by three sec-tions of N2 and connected to the UPS Logic Board via X1 terminals 18,19,20.
Each section of N2 monitors the inverter voltage on a line-to-neutral basis; for ex-ample N2a inputs are connected to the inverter neutral (Vinv-0) and U phase(Vinv-A). The attenuation factor is approximately 100:1 – i.e. VINV_A has a sen-sitivity of approximately 10mV per Vl-n (inverter) and therefore equals 2.2Vrms(8Vp-p) when the inverter voltage is at a nominal 220Vac.
s7-c2.fm5 - Issue 2 Dated 21/08/97 7-7
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 2 - High Voltage Interface Board
Note: the inverter voltage is connected to X5 from the junction of the output trans-former and inverter output contactor and is present only when the inverter is op-erating. When the inverter output contactor is closed (load on inverter) the voltageapplied to X5 is identical to the output voltage sense signals applied to X4 (seeabove) – these two signal groups can therefore be considered as monitoring eitherside of the inverter output contactor.
2.3.6 X6 (Page 2) – Bypass voltage sense
The UPS bypass voltage is connected to connector X6, attenuated by three sec-tions of N1 and connected to the UPS Logic Board via X1 terminals 15,16,17.
Each section of N1 monitors the bypass voltage on a line-to-neutral basis; for ex-ample N1a inputs are connected to the bypass neutral (Vin-0) and U phase (Vin-A).The attenuation factor is approximately 100:1 – i.e. VI_A has a sensitivity of ap-proximately 10mV per Vl-n (bypass) and therefore equals 2.2Vrms (8Vp-p) whenthe UPS output voltage is at a nominal 220Vac.
Note: the bypass voltage is connected to X4 from the ‘switched’ side of the bypasspower switch Q2 and is present when the switch is closed (normal).
2.3.7 X7 (Page 1) – Power switch auxiliary contacts
Each of the UPS power switches has an auxiliary contact which signals the switchstatus to the UPS Logic Board via the High Voltage Interface Board Q7. In eachcase the auxiliary contact is open when the main switch is open, and one side isconnected to 0V which is available at X7-5. When the power switches are closedthey therefore pull their respective status signals at X1 terminals 43-46 to 0Vwhich is interpreted as logic low by the switch monitoring circuits on the UPSLogic Board. Conversely, when the power switches are open the outputs to X1terminals 43-46 are pulled up to +4.7V and interpreted as logic high.
2.3.8 X8 (Page 1) – Interface to external connection block
X8 is connected to the customer terminal block (X3) by means of the wires iden-tified in Figure 7-1 below:
Figure 7-2: Connection between X8 and customer T.B
Battery circuit breaker “enable”
A +5V battery circuit breaker “enable” signal is generated on the UPS LogicBoard and connected to the High Voltage Interface Board X1-54 from where itpasses directly through X8-2 to the customer T.B. X3-6. From here, the signal istaken via external wiring to the trip circuit on the Battery Circuit Breaker Control-ler Board. The battery circuit breaker will “trip” if this “enable” supply is re-moved (note that X8-5 provides the enable signal 0V return path).
1234567
X8
HVI Board
123456789101112
X3
Customer T.B
7776
8182
79
7-8 s7-c2.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 2 - High Voltage Interface Board
Battery circuit breaker auxiliary
Auxiliary contacts of the battery circuit breaker ‘make’ the circuit between X8terminals 4 and 5 (0V) when the breaker is closed. This is fed as a logic low ‘cir-cuit breaker closed’ status signal (SW_BAT) to the UPS Logic Board via X1-53.When the circuit breaker is open SW_BAT is pulled up to 4.7V due to V11.
Emergency Stop
The emergency stop circuit is connected in a ‘normally-closed’ fashion betweenthe customer T.B. terminals 10 and 11. This is connected via wires 76 and 77 toX8 terminals 6 and 7 and then passed to the UPS Logic Board via X1-52 in theform of a logic low ESD signal. When the emergency stop circuit is open, ESD ispulled up to 4.7V due to V10.
If the emergency stop facility is not used then a link must be fitted between ter-minals 10 and 11 on the customer T.B. in order for the UPS to operate.
Note: when the emergency stop circuit is activated it shuts down the UPS powersections and isolates the load but does not disconnect the UPS input power source(unless an optional external mains circuit breaker is used) therefore the UPS con-trol logic will maintain its operating control power from the input mains supply ifit is still available.
2.3.9 X9 (Page 2) – Battery cabinet temperature
The battery cabinet temperature is monitored by an LM355A temperature sensorwhich produces a temperature-proportional voltage of 10mV/°C. This is bufferedon the High Voltage Interface Board and the resulting T4 signal is connected tothe UPS Logic Board via X1-60 and is ultimately used by the Rectifier LogicBoard to reduce the regulated battery float charge voltage by 1V per degree cen-tigrade of increase in battery temperature.
2.3.10 X10 (Page 2) – Input air temperature sensor
The input air temperature is monitored by an LM355A temperature sensor whichproduces a temperature-proportional voltage of 10mV/°C. This is buffered on theHigh Voltage Interface Board and the resulting T3 signal is connected to the UPSLogic Board via X1-59. The UPS Logic Board uses this signal to present theactual input cooling air-flow temperature on the appropriate Operator ControlPanel metering display window.
2.3.11 X11 (Page 2) – Inverter output air temperature sensor
The inverter output air temperature is monitored by an LM355A temperaturesensor which produces a temperature-proportional voltage of 10mV/°C. This isbuffered on the High Voltage Interface Board and the resulting T2 signal is con-nected to the UPS Logic Board cooling air-flow temperature on the appropriateOperator Control Panel metering display window.
2.3.12 X12 (Page 2) – Transformer cubicle air temperature sensor
The transformer cubicle air temperature is monitored by an LM355A temperaturesensor which produces a temperature-proportional voltage of 10mV/°C. This isbuffered on the High Voltage Interface Board and the resulting T1 signal is con-nected to the UPS Logic Board via X1-57. This signal is ultimately used by theRectifier Logic Board to reduce the regulated battery float charge voltage by 1Vper degree centigrade of increase in transformer temperature (between 25°C and35°C).
s7-c2.fm5 - Issue 2 Dated 21/08/97 7-9
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 2 - High Voltage Interface Board
2.3.13 X13 (Page 1) – Inverter assembly thermostats (normally closed)
The thermostats fitted to the inverter heatsink provide a normally closed circuitbetween X13 pins 1 and 2, and open only if the temperature rises above 90°C. TheTH status signal to the UPS Logic Board via X1-51 is therefore normally low, andrises to 4.7V (due to V9) following an inverter overtemperature event.
If an overtemperature condition occurs an “inverter overtemperature” alarm isimmediately activated (alarm #34) and the inverter is shut down after one minuteif the condition is still present – “overtemp shutdown” (alarm #62) annunciated.The shut-down condition is latched, and the reset button must be pressed to restartthe inverter and cancel the alarm.
2.3.14 X14 (Page 1) – Not in use
2.3.15 X15 (Page 1) – Battery fuse monitor
The battery fuse contains a micro-switch failure detection device which providesa normally closed circuit between X15 pins 1 and 2. The FUS_BAT status signalto the UPS Logic Board via X1-50 is therefore normally low, and rises to 4.7V(due to V8) following a fuse failure. Alarm #54 annunciates a fuse failure event.
2.3.16 X16 (Page 1) – Not in use (linked out)
2.3.17 X17 (Page 1) – Not in use (linked out)
2.3.18 X18 (Page 1) – Rectifier current sensing
Two CTs mounted on the U and V phases of the rectifier assembly provide inputcurrent sense signals to X18 pins 1-3. These signals are rectified by V12-V17 andthe resulting dc voltage (IREC_I) is developed across a selectable burden resistorand fed to the UPS Logic Board via X1-35. The appropriate resistance is selectedby a three-position jumper identified as X40 which should be set to position 0-3in all cases of 30kVA, 40kVA and 60kVA models. This signal is used by the Rec-tifier Logic Board to limit the maximum input current allowed through the recti-fier in order to protect the rectifier SCRs.
2.3.19 X19 (Page 1) – Output current monitoring W-ph
A CT mounted on the UPS output W phase provides a current sense signal to X19pins 1-3. The resulting voltage (IO_C) is developed across a selectable burden re-sistor and fed to the UPS Logic Board via X1-34. The appropriate resistance isselected by a three-position jumper identified as X39 which should be set to po-sition 0-3 in all cases of 30kVA, 40kVA and 60kVA models. This signal is usedby the UPS Logic Board to initiate an overload warning (alarm #66) and overloadlatches (alarm #62), and also to initiate the overload timer.
2.3.20 X20 (Page 1) – Output current monitoring V-ph
A CT mounted on the UPS output V phase provides a current sense signal to X20pins 1-3. The resulting voltage (IO_B) is developed across a selectable burden re-sistor and fed to the UPS Logic Board via X1-33. The appropriate resistance isselected by a three-position jumper identified as X38 which should be set to po-sition 0-3 in all cases of 30kVA, 40kVA and 60kVA models. This signal is usedby the UPS Logic Board to initiate an overload warning (alarm #66) and overloadlatches (alarm #62), and also to initiate the overload timer.
7-10 s7-c2.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 2 - High Voltage Interface Board
2.3.21 X21 (Page 1) – Output current monitoring U-ph
A CT mounted on the UPS output U phase provides a current sense signal to X21pins 1-3. The resulting voltage (IO_A) is developed across a selectable burden re-sistor and fed to the UPS Logic Board via X1-32. The appropriate resistance isselected by a three-position jumper identified as X37 which should be set to po-sition 0-3 in all cases of 30kVA, 40kVA and 60kVA models. This signal is usedby the UPS Logic Board to initiate an overload warning (alarm #66) and overloadlatches (alarm #62), and also to initiate the overload timer.
2.3.22 X22 (Page 1) – Battery current monitoring
A DCCT mounted in the battery positive line provides a current sense signal toX22 pin 2 (pins 1 and 3 carry the ±12V operating power supply to the DCCT de-vice). The signal voltage (IO_A) is developed across a selectable burden resistorand fed to the UPS Logic Board via X1-31. The appropriate resistance is selectedby a three-position jumper identified as X31 which should be set to position 0-2in standard 30kVA, 40kVA and 60kVA models and 0-3 in a 60kVA model. Thesense signal is used by the Rectifier Logic Board to limit the maximum batterycharge current (to protect the battery), and also by the UPS Logic Board to calcu-late the percentage capacity and remaining autonomy time.
2.3.23 X23 (Page 1) – Inverter current monitoring U-ph
Not used – the inverter U-phase current is not monitored in a standard 7200 SeriesUPS model.
2.3.24 X24 (Page 1) – Inverter current monitoring V-ph
A DCCT mounted in the inverter output V-phase line provides a current sensesignal to X24 pin 2 (pins 1 and 3 carry the ±12V operating power supply to theDCCT device). The signal voltage (IINV_B) is developed across a selectableburden resistor and fed to the UPS Logic Board via X1-29. The appropriate resist-ance is selected by a three-position jumper identified as X33 which should be setto 0-2 in standard 40kVA models and 0-3 in a 30kVA and 60kVA models.
This signal is used by the Inverter Logic Board to:
• regulate the PWM drives in order to sustain the inverter output during loadchanges (i.e. act as a feed-forward control).
• introduce a 150% inverter current limit (achieved by blocking the PWMsignal and reducing the inverter voltage) in order to limit the maximumcurrent drawn through the inverter and protect the inverter IGBT devices.
2.3.25 X25 (Page 1) – Inverter current monitoring W-ph
A DCCT mounted in the inverter output W-phase line provides a current sensesignal to X25 pin 2 (pins 1 and 3 carry the ±12V power supply to the DCCT de-vice). The signal voltage (IINV_C) is developed across a selectable burden resistorand fed to the UPS Logic Board via X1-30. The appropriate resistance is selectedby a three-position jumper identified as X34 which should be set to position 0-2in standard 40kVA models and 0-3 in a 30kVA and 60kVA models.
This signal is used in the same way as the V-phase signal described above.
2.3.26 X26 (Page 1) – Not in use
2.3.27 X27 (Page 1) – Not in use
s7-c2.fm5 - Issue 2 Dated 21/08/97 7-11
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 2 - High Voltage Interface Board
2.4 Summary information
Table 7-2: High Voltage Interface Board configuration links
JumperLink
PositionFunction
— 0 - 1
30 kVA CT burden selectionX31 0 - 2
X31 : X32 : X33 : X34 : X35 : X37 : X38 : X39 : X40
0 - 3
— 0 - 1
40 kVA CT burden selectionX31 : X32 : X33 : X34 0 - 2
X35 : X36 : X37 : X38 : X39 : X40 0 - 3
— 0 - 1
60 kVA CT burden selection— 0 - 2
X31 :X32 : X33 : X34 : X35 : X36 : X37 : X38 : X39 : X40
0 - 3
7-12 s7-c2.fm5 - Issue 2 Dated 21/08/97
Section 7: UPS System Control
Chapter 3 - UPS Logic Board (4550007 H)
3.1 Chapter overview
This chapter contains a circuit description of the current UPS Logic Board usedacross the whole 7200 Series UPS model range, and should be read in conjunctionwith circuit diagram SE-4550007-H (7 pages).
Part Nº SE-4550007-H is a direct replacement for Part Nº SE-4550004-E whichmay be fitted to units manufactured prior to February 1997. Though their are onlyminor differences in the two PCBs a full explanation of the UPS Logic Board PartNº SE-4550004-E can be found in Section 20 Chapter 4.
Signal annotations shown on the circuit diagrams are shown in italics in the fol-lowing text – e.g. [CLKOUT>.
3.2 General description
3.2.1 Circuit board functions
Figure 7-3: UPS Logic Board connections
The position of the UPS Logic Board with respect to the other control boardsplaces it at the heart of the UPS control operation and its functional responsibili-ties can be broadly summarised as follows:
• Motherboard –One of the most basic functions provided by the UPS Logic Board is to actas a ‘motherboard’ for signals travelling directly between any of the othercircuit boards connected to it: e.g. the input voltage sense signals passesdirectly from the High Voltage Interface Board to the Rectifier Logic
UPS Logic Board
RectifierLogic Board
InverterLogic Board
Static SwitchDriver Board
I/face BoardHigh Voltage
ParallelControlLogic
X1
X2
X3
X4
X5
X6
X7
X8
Logic BoardOperator
Alarm OptionsExternal
X1
X2 X4 X13
X2 X9X1 OperatorControlPanel
X2
X3
s7-c3a.fm5 - Issue 2 Dated 21/08/97 7-13
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
Board.• System control –
The UPS Logic Board contains a microprocessor-based control systemwhich reads various status signals derived on the other circuit boards andproduces several ‘system’ control logic signals: e.g. ‘stop/start’ signals tothe Rectifier/Inverter Logic Boards, and ‘transfer command’ signals to theStatic Switch Interface Board.
• Alarms control –The UPS Logic Board acts as an assembly point for alarm signals gener-ated on the various other boards, together with those generated on the UPSLogic Board itself, and controls their distribution to the Operator ControlPanel and External Alarms Options under microprocessor supervision.
• Operator programming interface –The UPS Logic Board microprocessor enforces the programmable systemoperating parameters selected by the operator, via the Operator LogicBoard, onto the ‘system’ control logic
• Static Switch transfer control –The UPS Logic Board contains decision-making logic which controls theload transfer events between the inverter and static bypass supplies.
3.2.2 Input/Output connections
The UPS Logic Board has eight connectors (See Figure 7-3) whose connectionsare summarised below.
• X1 – System control and monitoring signals to/from the Rectifier Board4520074-A (See Table 7-3).
• X2 – System control and monitoring signals to/from the High VoltageInterface Board 4590054-O (See Table 7-4).
• X3 – System control and monitoring signals to/from the Inverter LogicBoard 4530025-T (See Table 7-5).
• X4 – Power supply to Operator Logic Board 4550005-F (see circuit dia-gram sheet 7).
• X5 – System control and monitoring signals to/from the Static SwitchDriver Board 4542043-Z (See Table 7-6).
• X6 – Data/logic to/from Operator Logic Board 4550005-F (see circuit dia-gram sheet 7).
• X7 – System control and monitoring signals to/from the Parallel LogicBoard 4520075-B. (See Table 7-1)
• X8 – Alarm outputs to optional external (remote) alarm display boards(see relevant external alarm interface board in the Options section of thismanual).
7-14 s7-c3a.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
Table 7-3: Connector X1 (To Rectifier Logic Board)
PIN I/O Function
1-4 I 0V – ground reference for digital electronics
5-8 I +12V power supply derived from AC-DC Power Supply Board
9-12 I -12V power supply derived from AC-DC Power Supply Board
13-14 I/O Common – ground reference for analogue sense signals
15 O VREC_AC: Input mains voltage sense signal (phases U-W) – through connection from HVI Board – (15Vp-p)
16 O VREC_BA: Input mains voltage sense signal (phases V-U) – through connection from HVI Board – (15Vp-p)
17 O VREC_CB:Input mains voltage sense signal (phases W-V) – through connection from HVI Board – (15Vp-p)
18 O IB: Battery current sense signal – through connection from HVI Board – battery current limit control
19 – Not used in standard modules
20 O IREC: Rectifier input current sense signal – through connection from HVI Board – input current limit control
21-23 – Not used in standard modules
24 I IREC_T: Used in parallel systems only (not available)
25 O VB: DC Bus (battery) voltage feedback – through connection from HVI Board (-3.225Vdc @446V DC Bus)
26 O T_BAT: Battery cabinet temperature sensor – through connection from HVI Board (2.98V @ 25°C)
27 O IDC_1: Not used in standard model (12 pulse rectifier only)
28 O IDC_2: Not used in standard model (12 pulse rectifier only)
29 O DB: Used in parallel systems only (input current sharing)
30 O DB_0: Used in parallel systems only (input current sharing)
31 – Not used in standard modules
32 I OVLREC: Rectifier overload error status (Overload = 1)
33 I BLKREC: Rectifier OFF/ON status (OFF = 1, ON = 0)
34 I SEQREC: Input mains phase sequence error status (Error = 1)
35 I IN_LOW: Low input volts 20% error status (Error = 1)
36 O ON_REC: Rectifier Run(1)/Stop(0) command from UPSLB micro
37 O XRADD_1: Reduced current limit from UPSLB micro (On Gen = 1)
38 O REC_A: Charge mode selection from UPSLB micro
39 O REC_B: Charge mode selection from UPSLB micro
40 – Not used in standard modules
s7-c3a.fm5 - Issue 2 Dated 21/08/97 7-15
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
Table 7-4: Connector X2 (To High Voltage Interface Board)
PIN I/O Function
1-4 – 0V – ground reference for digital electronics
5-8 O +12V supply to HVI Board
9-12 O -12V supply to HVI Board
13-14 – Common – ground reference for analogue sense signals
15-17 I VI-A, VI-B, VI-C: Bypass sense voltages for U-V-W phases respectively. Approximately 1% of bypass L-N voltage
18-20 I VINV-A, VINV-B, VINV-C: Inverter sense voltages for U-V-W phases. Approximately 1% of inverter L-N voltage (8Vp-p)
21-23 I VO-A, VO-B, VO-C: UPS output sense voltages for U-V-W phases respectively. Approximately 1% of UPS output L-N voltage (8Vp-p)
24-26 I VREC-AC, VREC-BA, VREC-CB: Input mains sense voltages. Approximately 1.3% of input L-L voltage – e.g. approx. range 5V - 5.5V (15Vp-p) for 380-415V nominal input
27 I V-B: DC Bus (Battery) volts sense signal. Approximately 0.7% of the DC Bus voltage (+3.225Vdc @446V DC Bus)
28-30 I IINV-A, IINV-A, IINV-C: Inverter current sense (150% phaseback)
31 I I-B: Battery current sense signal (Batt I limit and current display)
32-34 I IO-A, IO-B, IO-C: Output current – O/load alarm/timer/display
35 I IREC-1: Input current sense signal (dc)
36-42 – Not used in standard modules
43 I SW-REC: Rectifier Input Switch auxiliary contact status
44 I SW-IN: Static Bypass Switch auxiliary contact status
45 I SW-BYP: Maintenance Bypass Switch auxiliary contact status
46 I SW-OUT: Output Switch auxiliary contact status
47 – Not used in standard modules
48 I FUSINV: Inverter fuse monitor (not used in standard module)
49 I FUSREC: Rectifier fuse monitor (not used in standard module)
50 I FUSBAT: Battery fuse monitor
51 I TH: Inverter thermostat contact status
52 I ESD: Emergency shutdown
53 I SW-BAT: Battery isolator auxiliary contact status
54 O BATTRP: Battery isolator trip signal
55-56 – Not used in standard modules
57-60 I T1, T2, T3, T4: Temperature sensing monitoring signals
7-16 s7-c3a.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
Table 7-5: Connector X3 (Inverter Logic Board)
PIN I/O Function
1 - 4 I 0V power supply rail
5 - 8 I +12V power supply derived from DC-DC Power Supply Board
9 - 12 I -12V power supply derived from DC-DC Power Supply Board
13 – Common
14 – Common
15-17 O [VI-A>, [VI-B>, [VI-C>: Bypass volts sense signals – through connection from HVI Board
18-20 O [VIN-A>, [VIN-B>, [VIN-C>: Inverter volts sense signals – through connection from HVI Board
21-23 O [IINV_A>, [IINV_B>, [IINV_C>: Inverter current sense signals – through connection from HVI Board
24 O [XINVOI>: Mains error – load transfer to inverter (H)
25 O [DREF>: Output voltage adjustment - used in parallel modules
26 O [DREF0>: Output voltage adjustment - used in parallel modules
27-30 O [DV-A>, [DV-B>, [DV-C>, [DV-0>: Load sharing signals used for parallel modules only
31 O [INV-L>: Transfer load to inverter command from processor system
32 I [OVL-INV>: Inverter overload status to processor system (OVL = L)
33 I [BLK-INV>: Inverter On/Off status to processor system (Off = H)
34 I [BACK>: Inv. frequency back to processor system from Inverter Logic Board
35 O [SYNC>: Produced by processor system to Inverter Logic Board
36 O [ON-INV>: Inverter On/Off control from processor system (Off = L)
37 O [INV-F>: from processor system (Inv Freq)
38-39 O [INV_A>, [INV_B>: from processor system - used in output volts selection
40 I Inverter thermostat status signals (optional)
s7-c3a.fm5 - Issue 2 Dated 21/08/97 7-17
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
Table 7-6: Connector X5 (Static Switch Driver Board)
PIN I/O Function
1 - 4 O 0V power supply rail
5 - 8 O +12V power supply rail
9 - 12 O -12V power supply rail
13 I XSTAI1: Not used in standard module. Details required as to what is connected to SSDB connector X7
14 I XSTAI2: Output contactor (inverter output) auxiliary contact status– low = contactor closed
15-16 O INV-L: Transfer load to inverter command from processor system
17-18 O MNS-L: Transfer load to bypass command from processor system
19 – XSTAD1: Not used in standard module.
20 – XSTAD2: Not used in standard module.
Table 7-1: Connector X7 (See Table 8-2)
PIN I/O Function
1-4 – 0V – ground reference for digital electronics
5-8 O +12V supply to HVI Board
9-10 O -12V supply to HVI Board
11-13 – VO-A, VO-B, VO-C: UPS output sense voltages for U-V-W phases respectively. Approximately 1% of UPS output L-N voltage (8Vp-p)
14 I Common – ground reference for analogue sense signalsVI-A, VI-B, VI-C: Bypass sense voltages for U-V-W phases respectively. Approximately 1% of bypass L-N voltage
15-17 I IO-A, IO-B, IO-C: Output current – O/load alarm/timer/display
18 I I_B_P:
19 COMM_P:
20-22 DV-A, DV-B, DV-C:
23 DV-0:
24 IREC-T:
25 DB:
26 DB-0:
27-28 0V – ground reference
29-30 +5V – Supply to
31 PAOU10:
7-18 s7-c3a.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
32 INV_DIS:
33 SW-OUT:
34 SWBYP:
35 I_BST_BAT:
36 I_TST_BAT:
37 MNS_DIS:
38 BLK_SEL:
39 OFF_INV:
40 C_L_INV:
41 RES_EXT:
42 V-AUX:
43 O_BLK_SW:
44 O_MNS_L_SS:
45 O_MNS_D_SS:
46 TST_BAT:
47 BST_BAT:
48 MNS_SYN_KO:
49 O_MNS_DIS:
50 SYN_INV_OK:
51 PAR_REC:
52 INV-L:
53 FRQ_SYN:
54 FRQ_PAR:
55 FRQ_MNS:
56 BACK:
57 INV_OK:
58 CON_SEL:
59 I_SW_BYP:
60 XSTAIZ:
Table 7-1: Connector X7 (See Table 8-2)
PIN I/O Function
s7-c3a.fm5 - Issue 2 Dated 21/08/97 7-19
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
3.2.3 Block Diagram
Figure 7-4: UPS Logic Board basic block diagram
Re
set
Po
we
rX
28
20
MH
zC
lock
RA
M
Ana
logu
e S
igna
l
Ou
tpu
tB
uff
er
P5
P1
P4
P0
An
alo
gu
eB
uff
eri
ng
MU
XD
43
D4
8D
49
EP
RO
MC
S
Add
ress
X
Inp
ut
Bu
ffe
r
Dat
a X
P2
CA
NIn
terf
ace
P3
Con
trol
Dat
a
Ou
tpu
tD
isp
lay
X1
X2
X3
X5
X7
X8
Re
ctifi
er
Lo
gic
Bd
H.V
.I B
oa
rd
Inve
rte
rL
og
ic B
d
SB
S B
oa
rd
Pa
ralle
lL
og
ic
Ala
rmB
oa
rd
D2
2
D2
3In
vert
er R
un
Rec
tifie
r R
un
S1O
n Inve
rter
Inve
rter
conta
ctor
contr
ol
S2
S3
S5
Rese
tB
ypass
On/O
ffIn
vert
er
On/O
ffR
ect
ifier
On/O
ff
On B
ypass
Byp
ass
SC
R c
ontr
ol
ON
OF
F
ON
OF
F
A/D
Conve
rters
ON
OF
F
ON
OF
F
7-20 s7-c3a.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
3.2.3.1 System overview
Processor system
The UPS Logic Board control system is based on a type 80C166 microcontroller,as shown in Figure 7-4. This device contains six ports through which it commu-nicates with peripheral circuits/devices, together with several ‘system controllines’. It also contains an internal A/D converter, four programmable timers andinternal ROM & RAM.
The ports are configured by an initialisation routine performed by the system soft-ware on power-up and can be summarised as follows.
• Port 0This port is configured as a 16-bit bi-directional data bus <D0...D15>
• Port 1This port is configured as the first 16-bits of an 18-bit address bus<A0...A15> the other two address lines are provided by port 4.
• Port 2The lower half of this port <P2-0...P2-7> carries various synchronising/tim-ing signals and the upper half <P2-8...P2-15> comprises the CAN data bus,which carries the data to/from the Operator Logic Board
• Port 3This 16-bit port is configured as a mixture of inputs and outputs generallyconcerned with controlling the CAN Bus data exchange.
• Port 4The lower two lines only are utilised on port 4. These form the upper twoaddress lines <A16...A17> the lower address lines <A0...A15> are providedby port 1.
• Port 5The lower ten lines of this port <P5-0...P5-9> are configured to act as inputsto the internal A/D converter.
• System control linesIn addition to the I/O ports the microcontroller also has the general controlI/O lines normally associated with a microprocessor-based system; suchas a system clock, reset, and Read/Write control.
Memory
The microcontroller uses both internal and external memory. 2 X 126k of battery-backed RAM and 2 X 516k of EPROM are fitted to the board as standard whichholds the system operating software. Facilities are included on the board to allowalternative memory configurations to be used as described later.
Data buffers
The 16-bit data bus is connected to various control circuit boards via input andoutput data buffers, as shown in Figure 7-4, which are controlled by individual‘chip select’ enable lines to direct the data flow to/from the appropriate source, asrequired by the system control software.
Analogue signal processing
The microcontroller monitors various analogue signals which are connected tothe UPS Logic Board from the peripheral boards. These signals are processed bysuitable analogue circuitry, buffered where necessary, and applied to the micro-controller’s A/D inputs via a series of multiplexer devices.
s7-c3a.fm5 - Issue 2 Dated 21/08/97 7-21
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
Primary output control signals
Although the micro-controller produces numerous control logic signals, its pri-mary outputs can be considered to be:
• Inverter Start/Stop Signal to the Inverter Logic Board which determines whether or not theinverter section is ‘enabled’ or ‘inhibited’.
• Rectifier Start/Stop Signal to the Rectifier Logic Board which determines whether or not therectifier section is ‘enabled’ or ‘inhibited’.
• Load on inverter Signal which controls the ‘inverter-side’ contactor (K1) and connects theinverter output to the load.
• Load on bypass Signal which controls the static switch and connects the load to the staticbypass supply.Note: the ‘load on inverter’ and ‘load on bypass’ signals are interlockedsuch that they cannot be activated simultaneously.
As shown on the block diagram, these signals are produced by a dedicated logicblock which is controlled by the data bus together with individual switches whichallow each of the above functions to be manually overridden.
Operator Interface
The microcontroller is connected to the Operator Logic Board via the CAN Bus,which is a bi-directional serial communications link that enables the operator toprogram several operational parameters into the micro-controller and also enablesvarious alarms and indications to be displayed on the Operator Control Panel.
7-22 s7-c3a.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
3.3 Detailed circuit description
3.3.1 Introduction
The UPS Logic Board circuit diagram (SE-4540007-H) comprises 7 sheets. Withreference to the block diagram description (See Figure 7-4), the drawings canbroadly be described as follows:
• Sheet 1 contains a ‘signal map’ identifying the functions covered on theremaining pages. It also contains a summary chart detailing the variousconfiguration jumpers.
• Sheet 2 contains the– basic microcontroller system– data bus, address bus and control line buffers– Ni-Cad battery back-up controller– reset generator
• Sheet 3 contains the– system RAM and ROM memory and its associated configuration links– Inverter/Rectifier Start/Stop control logic– load transfer control logic– CAN bus communications drivers and control logic– Real-time clock (RTC)
• Sheet 4 contains the– data bus input buffers– data bus output buffers– on-board 7-segment indication circuit
• Sheet 5 contains analogue signal processing circuits for the– input voltage sense signals– inverter voltage sense signals– DC (battery) bus voltage sense signal– Battery current sense signalit also contains reference voltage generators; power supply monitors; andinverter overvoltage and input overvoltage fault detection circuits.
• Sheet 6 contains analogue signal processing circuits for the– output voltage sense signals– output current sense signalsit also contains the analogue signal multiplexers (for the A/D inputs), out-put overvoltage and overcurrent fault detection circuits.
• Sheet 7 contains the– input/output signal identifications details– serial communications (RS485) driver and port
Note: On the diagrams, a ‘negative’ symbol at the end of a signal’s annotation in-dicates that the signal is ‘active low’ – e.g. [RD> = [RD->.
As with all micro-based system, the microcontroller’s operation is determined bythe program held in the system’s memory: and as this is hidden to the service en-gineer there is very little that can be done to ascertain that the board is workingcorrectly apart from checking the validity of its input and output signals, and othersignals generated on the board which are required by the central processor system.The following description deals with the board on this basis, and should providesufficient information to determine whether or not the board is functioning cor-rectly when it comes to troubleshooting. A full software description is beyond thescope of this manual.
s7-c3a.fm5 - Issue 2 Dated 21/08/97 7-23
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
3.3.2 Basic microcontroller system
(circuit diagram sheet 2)
Figure 7-5: Micro system control signals
Caution When monitoring the signals described in this section it is best done with controlpower only – i.e. with the UPS power sections shut down and the circuit boardslive via the control power supply. The signals entering the left of the above dia-gram are constant and can be monitored with a meter/oscilloscope; those shownon the right of the diagram are not constant and best monitored with a logic probe.The logic sequence/timing of these signals depend upon various circuit conditionsand cannot therefore be accurately defined; however, for field test purposes, thepresence of a ‘variable switching’ logic signal at these points would generally in-dicate that the basic processor control bus is serviceable and the system softwareis running.
Power supply
The microcontroller is powered from the general +5V rail which is provided by athree-terminal 5V regulator (N1) shown on diagram sheet 7.
System clock (XTAL1)
A dedicated crystal-controlled clock generator (E2) provides a system clocksignal which is connected to the microcontroller (D12) pin 20. This signal is a20MHz squarewave switching between +5V and 0V.
System reset (RSTIN)
On power-up, a 1 second logic low reset pulse, [RSTIN->, is applied to D42 pin 27from the ‘reset generator’ circuit. This can also be manually applied for trouble-shooting purposes by temporarily bridging jumper X28 (See paragraph 3.3.5).The [RSTIN-> pulse forces the processor to restart its operation from the beginningof its operating program which forces it to run through its initialisation routine.
Non-Maskable Interrupt (NMI)
When the input to D42 pin 29 (NMI) goes low it instructs the system software tointerrupt its present operation and execute a power-down routine to save criticaldata.
The source of this input is determined by X17 which is normally ‘made’ 2-3 andselects the power failure detection circuit output [PFO> as the controlling signal –this circuit is shown on diagram sheet 5 (See paragraph 3.3.15.4).
20
27
29
54
Power Supply
Clock
Reset
Power
Vref (+5V)
XTAL1
RSTIN
NMI
VAREF
96
97
25
92
READY
CLKOUT
ALE
BHE
Ready
Clock out
Address latch enable
Bus high enable
96
26
95
RSTOUT
RD
WR
Reset out
Read
Write
Fail
Co
ntro
l Bu
s
D42
7-24 s7-c3a.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
Reference voltage (VAREF)
The input to D42 pin 54 (VAREF) is a +5V reference voltage used by the internalA/D converters to compute the digital values for all analogue signals – e.g volts/current/VA etc. An adjustable reference voltage generator (N45 pin 8) (See par-agraph 3.3.15.2), shown on diagram sheet 5, provides this input ([VREF>) via X20which is normally ‘made’ 1-2.
Clock out (CLKOUT)
This output is a 20MHz squarewave synchronised to the processor clock input andis used by the RAM/ROM memory address decoding logic D33 (See paragraph3.3.6) shown on the diagram sheet 3. This is to ensure that when the processorwishes to read from/write to memory the memory access is synchronised to theinternal microprocessor action – i.e. it ensures that the accessed memory addressis relevant to the current processor’s requirements.
Address latch enable (ALE)
This output goes high to enable the address bus to be latched into the RAM/ROMmemory address decoding logic D33 shown on the diagram sheet 3 – (See para-graph 3.3.6).
Bus high enable (BHE)
The logic state of this output indicates whether the processor is internally enablingits ‘high’ or ‘low’ byte data bus – i.e. it indicates if the micro wishes to read from(or write to) the lower byte (D0....D7) or the higher byte (D8....D15). [BHE-> islow when the high byte is being accessed, and vice versa, and is used by the RAM/ROM memory address decoding logic shown on the diagram sheet 3 – (See par-agraph 3.3.6).
Reset out (RSTOUT)
[RSTO-> is controlled by the reset input signal, [RSTIN->, and goes high while theinput rest signal is applied. This signal is synchronised to the system clock andreturns high an integral number of clock pulses after the input reset signal is re-moved. The [RSTO-> signal is used by the RAM/ROM memory address decodinglogic shown on the diagram sheet 3 (See paragraph 3.3.6); and a buffered version,[RSTOX->, is connected to the data bus output buffers as shown on diagram sheet4 via jumper X25 (2-3) – (See paragraph 3.3.12).
Ready (Ready)
This input, when low, inserts wait states in the processor’s operation; thus slowingit down. It is driven by the RAM/ROM memory address decoding logic shown onthe diagram sheet 3 – (See paragraph 3.3.6) – and holds off the processor’s oper-ation until the appropriate address latching has taken place, thus effectively ex-tending the read/write times when slower memory elements are being used.
Read (RD)
This output goes low when the processor wishes to read the data from the deviceor memory location currently addressed by the address bus.
Write (WR)
This output goes low when the processor wishes to write data to the device ormemory location currently addressed by the address bus.
s7-c3a.fm5 - Issue 2 Dated 21/08/97 7-25
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
3.3.3 Data bus, address bus and control bus buffers
(circuit diagram sheet 2).
Data bus buffer
Two type ACT245 octal bus transceivers (D32 & D36) are employed as bi-direc-tional protection buffers between the microcontroller (D0....D15) and the data bus(DX0....DX15). D32 buffers the ‘low’ byte (D0....D7) and D36 the ‘high’ byte;however both are controlled by a common data direction signal – i.e. the micro-controller’s [RD-> output – therefore the data direction of all 16 data bus lines arecontrolled by a single signal.
These devices are described in appendix A (See paragraph A.1).
When the microcontroller drives its [RD-> output low it sets the data directionthrough the buffers from B-to-A, which allows the data bus contents through tothe microcontroller’s data inputs. At other times, when [RD-> is high, data flowsthrough the buffers from A-to-B, allowing the micro to place data onto the databus, which can then be written to a peripheral circuit as required.
Address bus buffer
The address bus is also buffered by two ACT245 devices (D38 & D41) but, unlikethe data bus described above, in this case the data direction is fixed by connectingpin 1 of each device to a permanent +5V supply. Thus the address bus data alwaysflows through the devices in the A-to-B direction and used to select a memory lo-cation – the buffered address bus is annotated (AX0....AX17).Note: AX16 & AX17 are buffered by the control bus buffer described below.
Control bus buffer
The control bus signals [RD->, [WR->, [BHE->, [RSTO-> are all buffered by D47.This device is configured with fixed data direction A-to-B, in the same manner asthe address bus buffer described above, by the application of a fixed +5V supplyat D47 pin 1. The buffered control signals [RDX->, [WRX->, [BHEX->, [RSTOX-> areused by various circuits distributed throughout the circuit diagrams.
In all cases the above mentioned buffers have pull-up resistors connected to theirinput and output pins – e.g. resistor packs R307, R309 etc.
3.3.4 Ni-Cad Battery back-up controller
(circuit diagram sheet 2).
A 3.6V 280mAh Ni-Cad battery is fitted to the UPS Logic Board to back-up theRAM contents and maintain the RTC time-keeping operation when the UPS isturned OFF; when fully charged the battery offers a back-up period of up to 4 to5 months.
The charger circuit is activated by the [OUTBAT> signal which is produced by theprocessor via D25 pin 19 (diagram sheet 4). When [OUTBAT> goes high it turnson V152 which then turns on V151 to supply the battery charge current via ledH8, R32 and V73. The charge voltage is limited to 4.7V by zener V14.
Note: the battery can be disabled for shipping/storage by opening jumper X31.
The battery is connected to the RAM memory devices and Real Time Clockdevice – shown on diagram sheet 3 – via V32 and the battery supply annotated[VRAM>. Thus, if the board’s power supply is turned off (i.e. UPS fully powereddown) the programmable parameters held in RAM (e.g. kVA, working voltage
7-26 s7-c3a.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
and frequency, battery charging parameters and display language) are main-tained; and the real-time clock keeps running. It is not therefore necessary to re-program these parameters following every start-up.
Note: Jumper X31 must be made in order to enable this function.
The [VBATT> output is not connected to other parts of the circuit, but it is moni-tored by the microcontroller’s analogue input [AN9> via D44, which is a quad an-alogue switch. [VBATT> is switched through D44 pin 2, by [FL-12> when it goeshigh; this is controlled by a ±12V supply rail monitor circuit (diagram sheet 5)which inhibits the [VBATT> sense signal if the ±12V power rails are invalid, thuspreventing an erroneous battery voltage fault being detected by the micro underthese conditions.
Note: the other three gates within D44 are not used and their inputs are tied to 0V.
[OUTBAT> signal details
The micro-controller monitors the NiCad battery voltage (3.6V nom) via AN9and its internal A/D converter (as described above) and turns on the Ni-Cadcharger, by driving the [OUTBAT> signal high, if the Ni-Cad voltage falls below2.8V. When the charger is active, the [INTERNAL BATTERY LOW] message isdisplayed on the Operator Control Panel (alarm #76) and led H8 illuminates.Once the battery is recharged to 3.6V the charger is turned off by the [OUTBAT>
signal returning low and the alarm message is cancelled. Thus the Ni-Cad batteryis charged only when necessary and is not permanently trickle-charged.
Note: the NiCad charger may be active for several hours when the UPS is firstcommissioned (depending on the initial battery charge state) – jumper X31 mustbe fitted to ‘enable’ the battery back-up facility.
3.3.5 Reset generator
(circuit diagram sheet 2).
A purpose-designed Supply Voltage Supervisor (N24) provides the micro with a1 second sec logic low [RSTIN-> reset signal on power-up. This signal, which isapplied to the micro pin 27, can also be initiated manually by temporarily makingjumper X28 (1-2). The [RSTIN> signal also resets the RAM chip select signals pro-duced by D19a/d (shown on circuit diagram sheet 3) and points the micro to itsinitialisation routines.
Caution Using X28 to activate the reset circuit during normal UPS operation will crash theunit, because the ‘run’ signals to the rectifier, inverter and static switch will be dis-abled for the 1 second reset period.
On power-up (reset) the micro-controller receives initialisation data from D20which is an EEPROM used to store the Emerson/Liebert/SICE software passportidentification. Amongst other things this configures the micro’s programmableports P0-P5 to the parameters required to operate in this application. Without thissecurity interlock the micro-controller will be inactive. An inverse output, [V-
AUX>, goes high on reset and is connected to D22 and D23 in the ‘Inverter/Recti-fier Start/Stop control logic’ and ‘Load transfer control logic’ (circuit diagramsheet 3). This resets the logic latches (Emergency Stop, DC Overvolts, etc.) andre-applies the ‘run’ signals to the rectifier, inverter and static switch.
Note: the reset time is determined by R157/C97, and begins when the +5V supplyrail reaches 3.6V on initial power-up.
s7-c3a.fm5 - Issue 2 Dated 21/08/97 7-27
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
3.3.6 System RAM and ROM memory addressing
(circuit diagram sheet 3).
The system memory comprises 2 x 512k EPROMs (D35 & D46) and 2 x 128kRAM chips (D28 & D40). All these devices have an 8-bit data bus output; how-ever, the EPROMs have a 16-bit address input while the RAM chips have a 17-bit address facility.
Random Access memory (RAM)
This is the read/write memory store; sometimes referred to as the temporarystore. Any data fed in from the peripheral devices or produced during the execu-tion of the main program will be temporarily held in RAM – e.g. UPS setup pa-rameters such as kVA, nominal voltages/frequency, serial number, passwords,etc. This is a ‘volatile’ location, meaning that when power is lost to the componentall data is also lost; thus the need for the on-board back-up Ni-Cad battery.
Read Only Memory (ROM)
This memory contains the ‘operating system program’, or firmware, which is ba-sically a sequence of instructions to be carried out by the micro-controller in orderto make it perform the actions required of it. Upon power-up the micro is pointedto the first instruction as part of its reset initialisation, and from then on it stepsthrough the programmed instructions in a sequence dictated by various events andmonitored conditions.
ROM is ‘non-volatile’, which means that it does not lose its memory contents inthe event of a loss of power.
Address decoding – D33 / D19
The ‘output enable’ pins of all four memory devices are controlled by the controlbus [RD-> line, therefore when this line goes low the processor can read the dataheld at the current address from any of the devices. The purpose of the ‘addressdecoding’ circuit is to enable the microcontroller to select which of the EPROMor RAM devices it wishes to communicate with at any given time. The memorydevices’ ‘chip select’ inputs are controlled by a circuit comprising an ASIC i.c.(D33) and two gates of D19.
D33’s inputs are connected to A0, A14....A17, and several control bus signals –as described in paragraph 3.3.2. – which are all controlled by the microcontroller.The output signals, [CSEP1L->, [CSEP1H->, [CSRA1L->, and [CSRA1H->, adopt logicstates determined directly by these processor-controlled inputs and are synchro-nised to the processor operation by the 20MHz [CLKOUT> signal.
When low, [CSEP1L-> and [CSEP1H-> enable the EPROM devices via their ‘chipenable’ inputs (pin 20), while [CSRA1L-> and [CSRA1H-> perform a similar func-tion on the RAM chips.
The [READY> output from D33 is fed back to the micro to inform it that the appro-priate addresses have been loaded into D33’s internal latches (See paragraph3.3.2).
As D19 provides the ‘chip select’ inputs to the RAM devices it is powered fromthe battery-backed RAM supply to prevent RAM data corruption on UPS powerdown.
Note: jumper X14 provides a test facility for bench testing only and all linksshould be open during normal operation.
7-28 s7-c3a.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
AX15 & AX16 configuration links
The UPS Logic Board has been designed to facilitate future software upgrades byincluding configuration links to permit the addressing of alternative memory de-vices. These links affect the routing of the AX15 and AX16 address lines, and thestandard configuration is shown below in Figure 7-6.
In the standard configuration the signals annotated [PIN29EP> and [PIN3EP> areconnected to the EPROMs’ A14 and A15 inputs and are therefore driven by theAX15 and AX16 address lines respectively. The [PIN31RAM> signal (AX16) isconnected to the A15 input of both RAM devices and the [PIN3RAM> signal(AX15) is connected to the RAM ‘write enable’ inputs.
Figure 7-6: AX15 & AX16 decoding configuration links
3.3.7 Basic system control logic (D88)
The term ‘Basic System Control Logic’ is used here to described the signals gen-erated by the UPS Logic Board which control the rectifier and inverter ‘start/stop’commands; battery circuit breaker ‘trip’, and the ‘load transfer’ control betweeninverter and static bypass.
These functions are controlled by a single ASIC device annotated D88 which isshown on sheet 3 of the diagram and also in greater detail in Figure 7-7. D88 alsoprovides the processor system with various status signals, as illustrated in theblock diagram.
The following description begins by identifying D88’s input logic signals, andcontinues by explaining their influences on the individual output control signals.
1
2
3
1
2
3
1
2
3
1
2
3
5
4
3
5
4
3
2
1
2
1
X19 X13
X22 X21
X23 X24
[AX16>
[AX15>
[PIN29EP>
[PIN3EP>
[PIN31RAM>
[PIN3RAM>
[PIN29RAM>
[WRX–>
s7-c3a.fm5 - Issue 2 Dated 21/08/97 7-29
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
Figure 7-7: Basic system control logic (internal detail)
43
D88
44
16
13
01
11
12
02
17
05
06
14
07
18
31
41
04
40
32
20
26
2724
39
37
38
36
33
34
28
29
09
08
N15-14
N15-8
0V
Z39
R97
D26-5
0V
R1
13
R1
11
R1
12
C6
3
65
2
C64
25
D26-4
D26-6
ON_REC
MNS_L
INV_L
BAT_TRP
ON_INVBLK_INV_M
M_BAT_MA
RES_EXT
M_ESD
REC_ON
BLK_REC_M
L_MAINS
BLK_MNS
L_INV
M_SCR_OP
BAT_MA_DSCR_OP_D
ESD_D
ESD_I
SCR_OPN
BAT_MA
MRESET
V-AUX
ALM_RES
SEQ_MNS
BLK_BYP_M
MNS_KO
IBOPEN
INV_ON
OFF_INV
C_L_INV
INV_DIS
SYN_KO
B-INV
0V+5V
Q3
Q2
S1
Q1
R320
R320
R320
R320Block
Rectifier
BlockInverter
ManualRESET
BlockBypass
R86
X7=41
D26-3
X2-54
X3-36
D51-8
D51-6
X1-36
N24-6
D26-7
D21-2
D55-9
D21-16
D21-5
X7-39
X7-40
D21-9
X7-32
D54-6
D1-4D21-12
D21-15
D34-12
X2-52
7-30 s7-c3a.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
3.3.7.1 D88 Status signals to processor system
Emergency shutdown [M_ESD>
The ‘emergency shutdown’ signal [ESD_I> to D88-9 is driven by external circuitryand connected via X2-52 (sheet 7) as a logic high when the emergency shutdownis applied.
This drives pin 29 ([M_ESD>) high which is connected to the processor system viaD26-5 where it initiates alarm #63 [CUT-OFF: EMERGENCY] (See paragraph3.3.11.4) and also provides a latching input back to D88 pin 24 ([ESD_D>) whichholds pin 29 in its high state until the reset circuit is activated – the latching signalis debounced by R112/C63.
The high [ESD_D> input to D88 pin 24:
• turns off the ‘bypass enable’ signal ([BLK_MNS> = 0) D88 pin 25.• trips the battery circuit breaker ([BAT_TRP> = 0) D88-34• turns OFF (stops) the rectifier ([ON_INV> = 0) D88-33• turns OFF (stops) the inverter ([ON_REC> = 0) D88-37
Static switch SCR open [M_SCR_OP>
The ‘static switch SCR open’ signal [SCR_OPN> to D88-28 is produced by N15-8 or N5-14 (sheet 6) as a logic high when the detection circuits ‘sees’ a voltagedrop across one of the static bypass SCRs.
This drives pin 32 ([M_SCR_OP>) high (provided the ‘load on mains’ ([MNS_L>)output to D88-38 is also high) which is connected to the processor system viaD26-4 where it annunciates alarm #15 [BYP: SCR FAILURE] (See paragraph3.3.11.4) and also provides a latching input back to D88 pin 27 ([SCR_OP_D>)which holds pin 32 in its high state until the reset circuit is activated – the latchingsignal is debounced by R111/C62.
In addition to latching the output on pin 32, the logic high [SCR_OP_D> input alsoblocks the static switch by forcing high the [BLK_MNS> output at D88-25 (see de-tails of [BLK_MNS> below).
DC Overvoltage – fast
The ‘DC Fast Overvoltage’ signal ([BAT_MA>) to D88-8 is produced by N13-8(sheet 5) and is logic high when a DC busbar (battery) overvoltage condition(>620V) is present.
This drives pin 20 ([M_BAT_MA>) high which is connected to the processor systemvia U26-6 where it initiates alarm #58 [DC BUS: FAST OVERVOL.] (See para-graph 3.3.11.4) and also provides a latching input back to D88 pin 26([BAT_MA_D>) which holds pin 20 in its high state until the reset circuit is activat-ed – the latching signal is debounced by R113/C64.
The logic high latching signal to pin 20 ([M_BAT_MA>) also:
• trips the battery circuit breaker ([BAT_TRP> = 0) D88-34• turns OFF (stops) the rectifier ([ON_INV> = 0) D88-33• turns OFF (stops) the inverter ([ON_REC> = 0) D88-37
s7-c3a.fm5 - Issue 2 Dated 21/08/97 7-31
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
3.3.7.2 D88 Reset circuit [RES_EXT>
There are three sources of reset signal applied to D88:
• D88-16 receives a logic high reset signal from the microcontroller via thedata bus output buffer D21-2 (See paragraph 3.3.12.5). This is a softwarereset programmable via the Operator Control Board
• D88-44 receives a logic high reset pulse when the board is powered up(See paragraph 3.3.5)
• D88-43 is driven high when the manual reset button (S1) is pressed
Common functions
In each case, a logic high activation on any of the above inputs:
• resets the ‘Emergency shutdown’, ‘Bypass SCR open’ and ‘DC overvolt-age’ latches described above.
• provides a [RES_EXT> reset signal at D88-39 which is applied via X7-41to the Parallel Logic Board in a ‘1+1’ configured system.
[V_AUX> signal functions
In addition to the common functions described above the [V_AUX> signal also:
• applies a reset signal directly to the Parallel Logic Board – via X7-42.• resets (turns off) the static bypass – ([BLK_MNS> = 1) D88-25.• resets (opens) the battery circuit breaker– ([BAT_TRP> = 0) D88-34.• resets (turns off) the inverter – ([ON_INV> = 0) D88-33.• resets (turns off) the rectifier – ([ON_REC> = 0) D88-37.
The [V_AUX> ‘power-up’ reset signal to D88-44 also resets the [BLK_MNS> outputfrom D88-25, described immediately above.
3.3.7.3 Major control signal outputs
Static bypass inhibit [BLK_MNS>
The [BLK_MNS> output from D88 pin 25 goes high when D88 detects any condi-tion which requires the load to be prevented from being connected to the staticbypass supply. This output is fed to the microcontroller via the data bus bufferU26-3 where it initiates alarm #16 [BYP:HARDWARE BLOCK.] (See paragraph3.3.11.4) and is also connected to the ‘load-on-bypass’ control logic within D88where it inhibits the ‘load-on-bypass’ command [MNS_L> output from D88 pin 38.
The [BLK_MNS> signal can be driven high, disabling the static bypass, by any oneof the following conditions:
• ‘Emergency shutdown’ latch set – ([ESD_D> = 1) D88-24 (see above).• ‘Bypass SCR open’ latch set – ([M_SCR_OP> = 1) D88-27 (see above).• 1 second Power-up reset pulse ([V_AUX> =1) D88-44 (see above).• Static bypass mains phase sequence error ([SEQ_MNS> = 1) D88-13. This
is derived from D27a on diagram sheet 5 (see paragraph 3.3.13.2 on page7-56).
• ‘Manual block’ applied from switch Q1 – ([BLK_MNS_M>) = 1) D88-1.• ‘Mains error’ signal – ([MNS_KO>) = 1) D88-11. This is produced by the
processor system under software control and applied via data bus bufferD55 (see paragraph 3.3.12.7 on page 7-50).
7-32 s7-c3a.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
Battery circuit breaker trip [BAT_TRP>
A logic low [BAT_TRP> output from D88-34 trips the battery circuit breaker viaX2-54 (sheet 7), which is connected to the High Voltage Interface Board (See sec-tion 7 paragraph 2.3.8).
The [BAT_TRP> signal can be driven low by any one of the following inputs:
• ‘DC Fast Overvoltage’ latch set ([BAT_MA_D> = 1) D88-26 (see above).• ‘Emergency shutdown’ latch set – ([ESD_D> = 1) D88-24 (see above).• 1 second Power-up reset pulse ([V_AUX> =1) D88-44 (see above).• ‘Software trip’ – ([IBOPEN> = 1) D88-12. This is produced by the processor
system under software control and applied via data bus buffer D21-16(See paragraph 3.3.12.5).Note: This signal trips the battery breaker on low DC voltage as follows:– UPS on greater than 15% load = 330V– UPS on less than 15% load = 360VThe low voltage trip level is programmable via the Operator Control PanelSET-UP screen, and is adjustable between 1.6V/cell and 1.69V/cell; how-ever the 30V window between the <>15% levels is not adjustable.
Inverter Start/Stop (On/Off)
The [ON-INV> output from D88-33 is connected to the Inverter Logic Board viaX3-36 (sheet 7) where it controls the inverter ‘Start/Stop’ status (see paragraph2.3.8 on page 5-51). A logic low [ON-INV> signal commands the inverter to‘STOP’ and can be effected by any one of the following D88 inputs (conversely,all the following inputs must be in their ‘healthy’ low state in order for the inverterto run):
• ‘DC Fast Overvoltage’ latch set ([BAT_MA_D> = 1) D88-26 (see above).• ‘Emergency shutdown’ latch set – ([ESD_D> = 1) D88-24 (see above).• 1 second Power-up reset pulse ([V_AUX> =1) D88-44 (see above).• ‘Software control’ – ([INV-ON> = 0) D88-17. This is produced by the proc-
essor system under software control and applied via data bus buffer D21-6(See paragraph 3.3.12.5). This signal is ‘low’ to inhibit the inverter and‘high’ to enable it. When this signal is actively blocking the inverter (i.e.low) it initiates alarm #30 [INV:SOFTWARE BLOCK.].
• ‘Manual inverter block’ – ([BLK_INV_M> = 1) D88-2 – logic high from themanual inverter inhibit switch Q2. If the [ON-INV> signal at D88 pin 33 is active (low), blocking the inverter,alarm #32 [INV: HARDWARE BLOCK] will be active. Note that alarm #32will be disabled if alarm #31 is active. Alarm #31 can be interpreted thatthe inverter has been selected off, while alarm #32 suggests that theinverter has been turned off for some other reason.
• Parallel Logic ‘Inverter OFF’ request – ([OFF_INV> = 1) D88-5. This inputallows the Parallel Logic Board to enable/inhibit the inverter in a ‘1+1’configured system (see paragraph 2.3.1 on page 8-12). [OFF_INV> is highto inhibit the inverter and vice-versa.
Rectifier Start/Stop (ON/OFF) [ON_REC>
The [ON_REC> output from D88-37 is connected to the Rectifier Logic Board viaX1-36 (sheet 7) where it controls the rectifier ‘Start/Stop’ status (see paragraph2.3.6 on page 4-35). A logic low [ON_REC> signal turns OFF the rectifier and canbe effected by any one of the following D88 inputs:
• ‘DC Fast Overvoltage’ latch set ([BAT_MA_D> = 1) D88-26 (see above).
s7-c3a.fm5 - Issue 2 Dated 21/08/97 7-33
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
• ‘Emergency shutdown’ latch set – ([ESD_D> = 1) D88-24 (see above).• 1 second Power-up reset pulse ([V_AUX> =1) D88-44 (see above).• ‘Software control’ – ([REC-ON> = 0) D88-40 – [REC-ON>. This is produced
by the processor system under software control and applied via the databus output buffer D21-15 (See paragraph 3.3.12.5). [REC-ON> is ‘low’ toinhibit the rectifier and ‘high’ to enable it. When this signal is activelyblocking the rectifier (i.e. low) it initiates alarm #20 [RECT:SOFTWAREBLOCK].
• ‘Manual rectifier block’ – ([BLK_REC_M> = 1) D88-4. This input isobtained from the manual rectifier inhibit switch Q3. If the [ON-REC> signal at D88 pin 37 is active (low), blocking the rectifier,alarm #22 [RECT:HARDWARE BLOCK] will be active. Note that this willbe disabled if alarm #21 is active. Alarm #21 can be interpreted that therectifier has been selected off via the Operator Control Panel, while alarm#22 suggests that the rectifier has been turned off for some other reason
3.3.7.4 Load transfer control
The transfer control logic within D88 is interlocked such that the ‘load on invert-er’ [INV_L> and ‘load-on-bypass’ [MNS_L> commands are mutually exclusive.
‘Load on inverter’ command [INV_L>:
The Load on inverter’ command ([INV_L>) output from D88-36 goes high to trans-fer the load to the inverter; and is connected to the Static Switch Driver Board viaX5-15 (sheet 7), where it turns OFF the static switch (disconnecting the load fromthe bypass supply) and energises the ‘inverter-side’ contactor (K1) driver circuit.
It is also connected to the Inverter Logic Board, via X3-31, where it triggers thelatches within D11 which makes the inverter voltage track the bypass supply volt-age for 100ms (See section 5 paragraph 2.3.3). This is done to provide a smoothtransfer from bypass to inverter and reduce the wear on the ‘inverter-side’ contac-tor (K1).
In order for D88 pin 36 ([INV_L>) to go high, all of the following conditions mustbe satisfied:
• ‘Inverter Logic Board OK’ – ([B-INV> = 0) D88-31. This input is driven bythe fault detection circuit on the Inverter Logic Board and applies a 1 sec-ond logic high hold-off command to X3-33 ([BLKINV> diagram sheet 7)when any of its internal faults are active (e.g. Vsat) (see paragraph 2.3.7on page 5-50). This is connected to D88-31 in the form of [B-INV>, andmust therefore be logic low, indicating “no fault” in order to permit theload to be connected to the inverter.
• ‘Software request’ – ([L_INV> = 1) D88-14. This is produced by the proces-sor system and applied via the data bus output buffer D21-9 when all itssoftware-monitored parameters have been verified (e.g. Inverter voltageOK, Sync OK etc.)(See paragraph 3.3.12.5).
• Parallel Logic ‘Inverter on inverter’ request – ([C_L_INV> =0) D88-6. Thisinput is generated by the Parallel Logic Board in a ‘1+1’ configured sys-tem and goes low when the parallel system control conditions request con-necting the load on inverter. In a single-module application this input,which is applied via X7-40, is tied to logic low and has no affect.
‘Load on bypass’ command [MNS_L>:
The ‘load on bypass’ command output from D88-38 goes high to transfer the loadto the bypass; and is connected to the Static Switch Driver Board via X5-17 (sheet
7-34 s7-c3a.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
7), where it turns on the static switch driver circuit, connecting the load to thebypass supply. It is also connected internally (within D88) to disable the ‘bypassSCR open’ annunciation circuit when ‘load on bypass’ is not being commanded– i.e. the ‘Open Circuit SCR’ fault is discounted while the load is ‘on-inverter’.
In order for D88 pin 38 ([MNS_L>) to go high, all of the following conditions mustbe satisfied:
1. The static bypass must be ‘enabled’ – i.e. the [BLK_MNS> output on D88 pin25 must be low (see above).
2. Parallel Logic ‘Inverter on bypass’ request – ([INV-DIS> =0) D88-6. This inputis generated by the Parallel Logic Board in a ‘1+1’ configured system andgoes low when the parallel system control conditions request connecting theload on bypass. In a single-module application this input, which is applied viaX7-32, is tied to logic low and has no affect. Note: on the Parallel Logic Board the signal at X1-32 is identified as[I_BUS_INV_L>.
3. In addition to conditions (1) and (2) above, one of the following conditionsmust also be valid:
a) ‘Software request’ – ([L_MNS> = 1) D88-41. This is produced by the proc-essor system when all software-monitored parameters are correct (e.g.Critical bus volts not OK, overload, bypass volts OK etc.) and applied viathe data bus output buffer D21-12 (See paragraph 3.3.12.5).
b) No ‘Load-on-inverter’ is being requested – i.e. D88-6 [C_L_INV> ANDD88-14 [L_INV> are both logic high (see above). This means that neitherthe Parallel Logic Board nor the microprocessor system are calling for theload to be connected to the inverter
c) Inverter is blocked, but still in-sync – i.e. D88-31 [BLK_INV> is high (seeabove) AND the [SYN_KO> input to D88-18 is low. Note that [SYN_KO> isderived via the processor system and D54, and is logic high when theinverter and bypass are not in sync (see paragraph 3.3.12.8 on page 7-52).
3.3.8 CAN bus communications drivers and control logic
(circuit diagram sheet 3).
The CAN bus communications system is described in paragraph 5.3.9. (OperatorLogic Board).
3.3.9 Real-time clock (RTC)
(circuit diagram sheet 3)
The MC68698 (D18) is a peripheral device which contains a real-time clock/cal-endar, a 32 x 8 bit static RAM, and a synchronous, serial, three-wire interface forcommunicating with the micro-controller. As it’s title suggests, the real timeclock accurately counts seconds, minutes, hours (AM/PM), Day-of-the week,date, month and year (including auto-incrementing leap-year). In the UPS LogicBoard application it provides ‘date stamping’ for the Operator Control Panel mes-sages and ‘service data’ entered via the Maintenance Menu Screen (see para-graph 2.4.6.3 on page 2-40). The device operates from the Ni-Cad back-upbattery to maintain its time-keeping function and prevent data loss when the gen-eral +5V control power is turned off. It also contains many other circuit functions,
s7-c3a.fm5 - Issue 2 Dated 21/08/97 7-35
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
such as an alarm facility, watchdog timer etc. which are not used in this applica-tion but may be mentioned briefly in the following description.
Power supply details
D18 is powered from the +5 volt power supply, which is connected to pin 16(Vcc) and available at all times provided the unit is powered up.
When jumper X33 is made 1-2 the battery-backed RAM supply [VRAM] (See par-agraph 3.3.4) is connected to pin 13 [Vbatt> and also, via an R-C delay circuit(R108/C54), to pin 10 [POR>.
The delayed input to pin 10 is seen as a ‘Power On Reset’ [POR> and resets thedevice by briefly holding pin 10 low while the device is powered-up. However,as the battery-backed supply is present at all times, this is effectively a ‘once-only’ reset that takes place when X33 is initially made 1-2 (i.e. battery connected)and is not affected by subsequent application/removal of the UPS Logic Board’s+5V control power supply.
The board’s +5V supply rail is monitored at D18 pin 12; and when the voltage atthis pin is less than 0.7V above the Ni-Cad voltage (pin 13) the device switchesto a low-power stand-by mode whereby it maintains its time-keeping function butinternally inhibits serial communication facilities with the micro-controller. Thisprevents the passage of invalid or spurious data while the micro-controller is pow-ering-down and so prevents RTC data corruption.
Clock control
The RTC’s internal timer operation can be controlled from one of two sources;either from an external crystal-controlled clock reference or a 50/60Hz mains-de-rived sinusoidal signal. In this particular application an external crystal is usedand the 50/60Hz input to pin 11 (LINE) is grounded via R107.
For crystal operation pins 14 and 15 are connected to a 32.768kHz, 1.048576kHz,2.097152kHz or 4.194304kHz crystal, as shown on the circuit diagram. A pro-grammable internal divider circuit enables the particular external clock frequencyto be scaled down to that used by the internal logic. The internal clock signal ismade available at pin 1 (CLKO) but in this particular application is not used, andremains unterminated.
Serial communications interface
Four lines, connected to pins 4 to 7, implement a bi-directional communicationsinterface with the micro-controller, and allow the micro to write configuration andcontrol data to the RTC and read the ‘time’ and register data. As described above,such communication is inhibited if the UPS Logic Board’s +5V power rail is un-available.
The [ORCS> input to pin 7 (SS) is seen as a ‘chip select’ input in this applicationand must be held high while either a read or write event is taking place. Data isinput (written) to the RTC by [ORDI> to pin 5; and output (read) from the deviceby [ORDO> from pin 7. In each case the data takes the form of a serial data streamclocked in/out by the ‘serial clock’ signal [ORSK> applied to pin 4. Note that allfour of these signals are under direct control of the micro-controller and appliedto the data bus via the buffers shown on diagram sheet 4.
Other connections
The functions connected to pin 2, pin 3 and pin 9 are not used in this particularapplication and these pins are tied to their default logic levels as shown.
7-36 s7-c3a.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
Section 7:
3.3.10 Data bus buffers ‘chip select’ decoding
The data bus communicates with the peripheral circuits and devices via 16 octalbuffers which are selected in ‘pairs’ to provide a 16 bit data bus transfer. Themicro-controller selects a particular buffer-pair by appropriately addressing the‘chip select’ decoding circuit (D52) which then ‘enables’ the required buffers.Details of the digital signals handled by each buffer are provided in the followingparagraphs.
Figure 7-8: Data bus buffer control (block diagram)
D8
D2
D1
D26
D51
D60
D17
D25
D9
D21
D50
D55
D7
D10
D54
D56
OE
OE[CSIN1->
OE
OE[CSIN2->
OE
OE[CSIN3->
CP
CP[CSDIS->
<CSOU1-]
<CSOU2-]
<CSOU3-]
<CSOU4-]
Microcontroller
DATABUS
[CSIN1->[CSIN2->[CSIN3->
[CSDIS->
[CSOU1->[CSOU2->[CSOU3->[CSOU4->
1213141516171819
123456789
AX11AX12AX13AX14AX15AX16AX17
[RDX->[WRX->
D52
Address Bus
Control Bus
CP
CP
CP
CP
CP
CP
CP
CP
s7-c3b.fm5 - Issue 2 Dated 21/08/97 7-37
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
3.3.11 Data bus input buffers
(diagram sheet 4).
Digital signals which are read by the microcontroller as part of its control functionare connected to the data bus via six type HCT 245 octal bus transceivers (See Ap-pendix A.1) which are accessed in pairs to provide a 16-bit data transfer (SeeFigure 7-8). The buffers ‘data direction’ pins are held permanently high, thereforethe data flow is fixed from ‘A-to-B’ in each device. ‘Chip select’ signals fromD52 are connected to the buffers ‘output enable’ pins which provides the meansfor the micro to select each pair of devices as required.
The remainder of this sub-section lists the digital signals connected to the data busthrough the bus input buffers, and provides signal details where appropriate.
Note: The alarms shown are for version 4 software. These may vary from earliersoftware versions, which will have different screen descriptions, the alarmnumber and definition however remains the same.
3.3.11.1 Buffer D8 – activated by CSIN1
XRADT1
Source: Sheet 7 X1-31
Description: From the Power Rectifier overtemperature sensing device – thisinput is not normally used and is held permanently low by jumper X10 (1-2) onthe Rectifier Logic Board. If used, in an overtemperature situation this input ini-tiates alarm #24 [RECT: OVERTEMPERAT.] and the rectifier and inverter areshut-down 1 minute later accompanied by alarm #62 [CUT-OFF: OVERTEM-PER]. This alarm must be reset by pressing the manual reset push-button.
OVLREC
Source: Sheet 7 X1-32
Description: Rectifier Overload – this input goes high when the rectifier is op-erating in input current limit mode (H6 illuminated on the Rectifier Logic Board)– (See section 4 paragraph 2.3.4.2). This initiates alarm #23 [RECTIFIER: I/P LIMIT].
BLKREC
Source: Sheet 7 X1-33
Description: Rectifier Blocked – this input goes high when the Rectifier Logicboard is in its ‘stop’ mode (See section 4 paragraph 2.3.6). This can be due to theRectifier Logic Board detecting an internal fault or a ‘stop’ (block) commandissued by the UPS Logic Board (See paragraph 3.3.7).
The internal fault channel is triggered by either: incorrect phase rotation; Rectifi-er Logic Board power supply failure; or low input voltage (-20%). The externalfault channel initiated by the UPS Logic Board will be accompanied by alarm #21[RECT: OFF VIA DISPL.] or alarm #22 [RECT: HARDWARE BLOCK] (See par-agraph 3.3.7).
7-38 s7-c3b.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
SEQREC
Source: Sheet 7 X1-34
Description: Rectifier input phase sequence error – this input goes high whenthe Rectifier Logic board phase sequence monitor detects an error on the incom-ing 3 phase mains supply (H8 illuminated on the Rectifier Logic Board) (See sec-tion 4 paragraph 2.3.6.1).
IN-LOW
Source: Sheet 7 X1-35
Description: Rectifier input undervoltage – this input goes high when the Rec-tifier Logic board input voltage monitor detects a -20% undervoltage condition onthe incoming 3 phase mains supply (H9 illuminated on the Rectifier Logic Board)(See section 4 paragraph 2.3.6.2).
XATI1 / XATI2 / XATI3
Source: Sheet 7 X2-40 / 41 / 42
Description: Not used – no connection on High Voltage Interface Board.
3.3.11.2 Buffer D2 – activated by CSIN1
SW-REC
Source: Sheet 7 X2-43
Description: Rectifier input switch monitor – this input goes low when the rec-tifier input mains power switch is closed. This signal passes through the HighVoltage Interface Board (See section 7 paragraph 2.3.7). When the input switchis open, this signal initiates alarm #04 [RECTIF. SWITCHOPEN].
SW-IN
Source: Sheet 7 X2-44
Description: Static Bypass switch monitor – this input goes low when the StaticBypass mains power switch is closed. This signal passes through the High Volt-age Interface Board (See section 7 paragraph 2.3.7). When the bypass switch isopen, this signal initiates alarm #02 [BYPASS SWITCH OPEN].
SW-BYP
Source: Sheet 7 X2-45
Description: Maintenance Bypass switch monitor – this input goes low whenthe Maintenance Bypass switch is closed. This signal passes through the HighVoltage Interface Board (See section 7 paragraph 2.3.7). When the maintenancebypass switch is closed, this signal initiates alarm #06 [MANUAL BYPASSCLOSED].
s7-c3b.fm5 - Issue 2 Dated 21/08/97 7-39
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
SW-OUT
Source: Sheet 7 X2-46
Description: Output switch monitor – this input goes low when the Outputswitch is closed. This signal passes through the High Voltage Interface Board(See section 7 paragraph 2.3.7). When the output switch is open, this signal ini-tiates alarm #03 [OUTPUT SWITCH OPEN].
FUSINV
Source: Sheet 7 X2-48
Description: Not used - held permanently low due to link fitted to connectorX16 on the High Voltage Interface Board (see main equipment wiring diagrams).If used, this input monitors the inverter fuse and on fuse failure initiates alarm #38[INV: FUSE FAIL].
FUSREC
Source: Sheet 7 X2-49
Description: Not used - held permanently low due to link fitted to connectorX17 on the High Voltage Interface Board (see main equipment wiring diagrams).If used, this input monitors the rectifier (input) fuses and on fuse failure initiatesalarm #25 [RECT: FUSE FAIL].
FUSBAT
Source: Sheet 7 X2-50
Description: Battery fuse monitor – this input goes high if the battery fuse rup-tures (See section 7 paragraph 2.3.15). The fuse is detected by a micro-switch located on the fuse which, when activated,initiates alarm #57 [BATTERY: FUSE FAIL].
TH
Source: Sheet 7 X2-51
Description: Inverter thermostat monitor – this input goes high if an inverterthermostat opens (overtemperature > 90°C) (See section 7 paragraph 2.3.13). Inthe event of an overtemperature situation occurring, this input initiates alarm #34[INV: OVERTEMPERATURE.] and the rectifier and inverter are shut-down 1minute later accompanied by alarm #62 [CUT-OFF: OVERTEMPER.]. This alarmmust be reset by pressing the manual reset push-button (S1).
3.3.11.3 Buffer D1 – activated by CSIN2
SW-BAT
Source: Sheet 7 X2-53
Description: Battery circuit breaker monitor – this input goes low when the Bat-tery switch (or contactor) is closed. This signal passes through the High VoltageInterface Board (See section 7 paragraph 2.3.7). When the battery switch is open,this signal initiates alarm #05 [BATTERY SWITCH OPEN].
7-40 s7-c3b.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
OVLINV
Source: Sheet 7 X3-32
Description: Inverter Overload – this input goes high when the inverter is oper-ating in current limit mode (H14 illuminated on the Inverter Logic Board) – (Seesection 5 paragraph 2.3.7). In an Overload condition, this signal initiates alarm#33 [INV: CURRENT LIMIT].
BLKINV
Source: Sheet 7 X3-33
Description: Inverter Blocked – this input goes high when the Inverter LogicBoard is in its ‘stop’ mode (See section 5 paragraph 2.3.8). This can be due to theInverter Logic Board detecting an internal fault or a ‘stop’ (block) commandissued by the UPS Logic Board (See paragraph 3.3.7). The internal fault channelis triggered by either: IGBT desaturation, ribbon cable disconnected, InverterLogic Board power failure. The external fault channel initiated by the UPS LogicBoard will be accompanied by alarm [#30], [#31] or [#32].
XINVI1
Source: Sheet 7 X3-40
Description: Not used – held permanently low due to X13 (2-3) on the InverterLogic Board which disables this alternative temperature sensor route. The activethermostat route is via [TH> described earlier.
XSTAI1
Source: Sheet 7 X5-13
Description: Not used – held permanently low due to X11 (1-2) on the StaticSwitch Driver Board. No thermostat is fitted on the heatsink.
XSTAT2
Source: Sheet 7 X5-14
Description: Inverter output contactor monitor – goes low when the inverteroutput contactor is closed (load on inverter) and is used by the transfer controllogic software routine.
LINK X12
Source: On-board jumper X12
Description: The normal position is open – link is closed to disable Initialisa-tion
3.3.11.4 Buffer D26 – activated by CSIN2
MRESET
Source: Sheet 3 – switch S1
Description: RESET switch – goes high when the on-board manual reset switch(S1) is pressed and is used by the micro to unlatch “block commands” issued bysome of its software routines.
s7-c3b.fm5 - Issue 2 Dated 21/08/97 7-41
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
BLK-MNS
Source: Sheet 3 – D88 pin 25
Description: ‘Static Switch blocked’ monitor – this input goes high to informthe micro that the static switch control logic (on this Board) is inhibiting the staticswitch (alarm #16 [BYP: HARDWARE BLOCK). This can be invoked by any ofthe following signals applied to D88 (See paragraph 3.3.7.1).
– static switch manual inhibit switch (Q1) closed– bypass phase sequence error detected– emergency shutdown operated (latched)– open circuit SCR (latched)– UPS Logic Board power supply failure
M-SCR-OP
Source: Sheet 3 – D88 pin 32
Description: ‘Static Switch SCR open circuit’ monitor – this input goes high toinform the micro that an open circuit static switch SCR has been detected (on thisBoard) (alarm #15 BYP: SCR FAILURE]). This signal is latched within D88 andmust be reset using S1 to return to normal conditions.
M-ESD
Source: Sheet 3 – D88 pin 29
Description: ‘Emergency shutdown’ monitor – this input goes high to informthe micro that an emergency shutdown (Emergency Stop) has been applied (Seeparagraph 3.3.7.1) (alarm [#63] [CUT-OFF: EMERGENCY]). This signal islatched within D88 and must be reset using S1 to return to normal conditions.
M-BAT-MA
Source: Sheet 3 – D88 pin 20
Description: DC Overvoltage – this input goes high to inform the micro that a‘DC Overvoltage’ has been detected (See paragraph 3.3.7) (alarm [#58] [DC BUS: FAST OVERVOL.]). This signal is latched within D88 and must bereset by S1 to return to normal conditions.
SEQMNS
Source: Sheet 5 – D34 pin 10
Description: Bypass phase sequence error – this input goes high to inform themicro that a ‘Bypass phase sequence error’ has been detected (See paragraph3.3.14.1). Note that the Rectifier Logic Board detects a phase sequence error onthe UPS (rectifier) input mains supply (See section 4 paragraph 2.3.6.1). A phasesequence error initiates alarm [#14] [BYP: PHASE ROT.ERROR] and also ena-bles alarm [#16] [BYP: HARDWARE BLOCK] via the micro.
EEDO
Source: Sheet 2 – D20 pin 4
Description: Output from the security EPROM to initiate the micro-controller.
7-42 s7-c3b.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
DRDO
Source: Sheet 3 – D18 pin 6
Description: Real Time Clock output (See paragraph 3.3.9).
3.3.11.5 Buffer D51 – activated by CSIN3
I-BST-BAT
Source: Sheet 7 – X7-35
Description: The signal to this input is generated on the Parallel Logic Boardwhen the modules in a 1+1-configured system are connected in ‘common battery’mode; and is logic high when ‘battery boost’ is requested by either module (seeparagraph 2.6.2 on page 8-37). This informs the processor system to commandthe Rectifier Logic Board to enter Boost Mode (see D17 [REC_A> [REC_B> out-puts).
I-TST-BAT
Source: Sheet 7 – X7-36
Description: The signal to this input is generated on the Parallel Logic Boardwhen the modules in a 1+1-configured system are connected in ‘common battery’mode; and is logic high when ‘battery test’ is selected in either module (see par-agraph 2.6.3 on page 8-37). This informs the processor system to command theRectifier Logic Board to enter Battery Test Mode (see D17 [REC_A> [REC_B> out-puts).
MNS-DIS
Source: Sheet 7 – X7-37
Description: The signal to this input is generated on the Parallel Logic Board,and is applicable only in a 1+1-configured system. It is logic high if the[D_MNS_DIS> output from D50-16 (via X1-49) is driven high in either module.
BLK-SEL
Source: Sheet 7 – X7-38
Description: The signal to this input is generated on the Parallel Logic Boardwhen the modules in a 1+1-configured system; and is logic high if the ParallelLogic Board’s selective shutdown circuit is active (LED H1 illuminated on Par-allel Logic Board) (see paragraph 2.3.1.1 on page 8-13).
MNS-L
Source: Sheet 3 D88-38
Description: This input goes high when the control logic requests ‘load-on-by-pass’. This signal is also fed to the Static Switch Driver Board (X5-17)
I-SW-BYP
Source: Sheet 7 – X7-59
Description: The signal to this input is generated on the Parallel Logic Boardand is logic low when the Maintenance Bypass Switch is closed is either moduleconnected to a 1+1-configured system.
s7-c3b.fm5 - Issue 2 Dated 21/08/97 7-43
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
INV-L
Source: Sheet 3 – D88-36
Description: This input goes high when the control logic requests ‘load-on-in-verter’. This signal is fed to the Static Switch Driver Board X5-15 where it initi-ates the output contactor closure; and it is also connected to the Parallel LogicBoard where it enables the current sharing function in a 1+1-configured system(see paragraph 2.5 on page 8-31).
INV-DIS
Source: Sheet 7 – X7-32
Description: This input signal is produced by the Parallel Logic Board in a 1+1-configured system and is logic when the Parallel Logic Board requests ‘load-on-bypass’ (see paragraph 2.3.2 on page 8-15). The signal is also applied to thetransfer control logic within D88 (See paragraph 3.3.7.4).
3.3.11.6 Buffer D60 – activated by CSIN3
BLK-EXT
Source: Sheet 7 – X8 pin 11
Description: From external alarms (AS400 interface board). This input pro-vides a means of allowing the inverter to be turned OFF/ON from an externalsignal via the Remote Alarms Board. The ‘Block’ (OFF) signal is applied as aclosed contact across the Remote Alarms Board terminal block X5 pins 1-2.
Note: Jumper X6 on the Remote Alarms Board must be selected 2-3 in order toenable this function.
BLK-SYN
Source: Sheet 7 – X8 pin 12
Description: Sync disable – this is an input from the optional ‘remote alarm’sboard’ (AS400 interface board) which goes high (+5V) when the UPS is “ON-
GENERATOR” – and is normally used to prevent the inverter synchronising to afrequency-wild standby generator. The On Generator status signal is applied as aclosed contact across the Remote Alarms Board terminal block X5 pins 3-4.
Note: The response to the “ON-GENERATOR” event is programmable via the Op-erator Control Panel FUNCTION software screen which allows three separatefunctions to enabled/disabled:
• Synchro Block – is concerned with the [BLK-SYN> signal mentioned hereand, when enabled, prevents the inverter from tracking the bypass fre-quency when it is being provided by the standby generator.
• Charge Inhibit – is concerned with the battery recharge current limitfunction which, when enabled, reduces the RECTIFIER current limit by15%.
• Current Limit – is concerned with the rectifier input current limit[XRADD1> function which, when enabled, reduces the input current limitby 35%.The reduced current limit functions are employed to lower the potentialmaximum current demand if the standby generator is undersized.
7-44 s7-c3b.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
BLK-01
Source: Sheet 7 – X8 pin 9
Description: From external alarms (AS400 interface board) Not used.
BLK-CHG
Source: Sheet 7 – X8 pin 10
Description: Rectifier Disable – This input provides a means of allowing therectifier to be turned OFF/ON from an external signal via the Remote AlarmsBoard. The ‘Block’ (OFF) signal is applied as a closed contact across the RemoteAlarms Board terminal block X5 pins 1-2.
Note: Jumper X6 on the Remote Alarms Board must be selected 1-2 in order toenable this function.
Links X26
Source: Sheet 4 jumper X26
Description: The four sections of jumper X26 are detailed in a Table on the cir-cuit diagram sheet 1 and summarized below:
Table 7-7: X26 Jumper details
3.3.12 Data bus output buffers
(circuit diagram sheet 4).
Digital signals generated by the microcontroller as part of its control function arefed to the peripheral circuits via 10 type-74C273 octal latches (See Appendix A.2)which are accessed in pairs to provide a 16-bit data transfer (See Figure 7-8). The
LINK 1-2
Open(Standard)
Auto-transfer mode enabled (“on-line” operation).Automatic load transfer from bypass to inverter when the inverter is available – i.e. the inverter is the preferred sup-ply source
Closed
Manual-transfer mode enabled (“off-line” operation).Automatic load transfer from bypass to inverter only when the bypass is unavailable – i.e. the bypass is the preferred supply source. Note: there will be a 3-cycle break on trans-fer to inverter,
LINK 3-4
Open “Inverter voltage fail lockout monitor” disabled
Closed(Standard)
“Inverter voltage fail lockout monitor” enabled. i.e. The inverter is given 5 seconds to reach nominal voltage other-wise it is latched OFF.
LINK 5-6
Open(Standard)
Enables the “Event History” monitor to store up to a maxi-mum of 10 alarms.
Closed
Resets the “Event History” monitor. Note: After the 10th “event”, the monitor buffer is full an cannot store any further “events”. The buffer should be reset to 0 after each mainte-nance or commissioning to enable new “events” to be cap-tured.
LINK 7-8
Open(Standard)
Password protection enabled.
Closed Password protection disabled
s7-c3b.fm5 - Issue 2 Dated 21/08/97 7-45
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
‘chip select’ signals from D52 provide the latch clock signals and data is thereforetransferred through the latches when the appropriate ‘chip select’ signal switchesfrom low to high. A logic low [RSTDX-> reset signal is connected to all the databus output buffers via jumper X25 (3-2) and drives all their outputs low when ap-plied. [RSTDX-> is produced by the microcontroller (See paragraph 3.3.3) andshown on the circuit diagram sheet 2.
The remainder of this sub-section lists the digital signals connected through thelatches, and provides signal details where appropriate.
3.3.12.1 Buffers D7 and D10– activated by CSDIS
These two devices connect the data bus output to the two on-board 7-segment di-agnostic displays (H11 & H12). For a detailed description of the displayed param-eters (see paragraph 3.3.17 on page 7-68).
3.3.12.2 Buffer D17 – activated by CSOUT1
XRADD1
Destination: Sheet 7 – X1 pin 37
Description: Reduced current limit – when this output goes high it reduces theRectifier Logic Board’s input current limit threshold by 35% (See section 4 par-agraph 2.3.4.2).
Conditions: This software-selectable output is activated when the UPS is run-ning on ‘standby generator’ as described on page 7-44 ([BLK_SYN>).
REC-B & REC-A
Destination: Sheet 7 – X1 pin 38 / 39
Description: Charge mode selection – these two outputs are connected to a de-coder on the Rectifier Logic Board where they invoke one of four permissiblecharge modes (see section 4 table 4-3).
Conditions: These outputs select Test, Boost, Float and Manual charge modesin response to selections made on the Operator Control Panel. The automaticBoost mode parameters, i.e. duration and threshold, are also operator-defined –(see paragraph 2.5.6 on page 2-53). LEDs on the Rectifier Logic Board illumi-nate to indicate the active charge mode.
XAT01 & XATO2
Destination: Sheet 7 – X2 pin 55 / 56
Description: Not used
INV-F
Destination: Sheet 7 – X3 pin 37
Description: Base frequency selection – informs the Inverter Logic Board’s‘staircase pattern generator’ of the UPS system’s base frequency (i.e. 50/60Hz).(See section 5 paragraph 2.3.2).
Conditions: This output is high for 50Hz and low for 60Hz as selected on theOperator Control Panel – see ‘Selecting the UPS SETUP parameters’ in the com-missioning procedure (see paragraph 2.4.5.3 on page 2-35).
7-46 s7-c3b.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
INV-B & INV-A
Destination: Sheet 7 – X3 pin 38 / 39
Description: Inverter working voltage selection – these two outputs are con-nected to a decoder on the Inverter Logic Board where they select one of four per-missible charge modes (see section 5 table 5-3).
Conditions: The logic states of these outputs are determined by the workingvoltage selected by the operator – see commissioning procedure (see paragraph2.4.5.2 on page 2-34). LEDs on the Inverter Logic Board illuminate to indicatethe active selection.
3.3.12.3 Buffer D25 – activated by CSOUT1
XSTAO1 & XSTAO2
Destination: Sheet 7 – X5 pin 19 / 20
Description: Not used
RE485-
Destination: Sheet 7 – D58 pin 2
Description: This output selects the ‘Read Enable’ pin of D58, which is anRS485 communications driver connected to the parallel interface connector X7pins 59/60 – not used.
OE485
Destination: Sheet 7 – D58 pin 3
Description: This output selects the ‘Output Enable’ pin of D58, which is anRS485 communications driver connected to the parallel interface connector X7pins 59/60 – not used.
TP5
Destination: Sheet 7 – X18 pin 5
Description: Not used (test point for system software).
OUTBAT
Destination: Sheet 2 – V152
Description: This output, when high, ‘enables’ the on-board Ni-Cad batterycharger.
Conditions: This output enables the Ni Cad battery charger if its voltage fallsto 2.8Vdc and disables it again once the battery voltage rises to 3.6V.
Note: when the charger is enabled the [INTERNAL BATTERY LOW] warning isannunciated (alarm [#76] active).
3.3.12.4 Buffer D9 – activated by CSOUT2
EECS / EESK / EEDI
Destination: Sheet 3 – D18 pin 7
Description: These outputs control the data acquisition of EEPROM D20
s7-c3b.fm5 - Issue 2 Dated 21/08/97 7-47
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
ORCS
Destination: Sheet 3 – D18 pin 7
Description: Real Time Clock (RTC) ‘chip select’ (See paragraph 3.3.9).
ORSK
Destination: Sheet 3 – D18 pin 4
Description: Real Time Clock (RTC) ‘serial communications clock input’ (Seeparagraph 3.3.9).
ORDI
Destination: Sheet 3 – D18 pin 5
Description: Real Time Clock (RTC) ‘serial data input’ (See paragraph 3.3.9).
SELANA / SELANB
Destination: Sheet 6
Description: These two outputs are connected to the address inputs of three 2-pole multiplexers which select the analogue signals for the microcontroller’s A/Dinputs – e.g. selecting the analogue signals for display purposes (kVA values arecalculated in software using V x I).
3.3.12.5 Buffer D21 – activated by CSOUT2
ALMRES
Destination: Sheet 3 – D22 pin 1
Description: Software controlled RESET – This output, when high, resets theEmergency Shutdown, DC Overvoltage and Open SCR fault latches within D22.
Conditions: This facility is not programmed into the current software and it istherefore not used.
INV-ON
Destination: Sheet 3 – D88 pin 17
Description: ‘Inverter ON’ request – This output, when high, requests D88 toissue an [ON_INV> command signal which is connected to the Inverter LogicBoard and turns ON the inverter – provided other D88 inputs are correct (See par-agraph 3.3.7).
Conditions: (see paragraph 7.2.3 on page 7-160)
L-INV
Destination: Sheet 3 – D88 pin 14
Description: ‘Load-on-inverter’ request – This output is connected to the loadtransfer control logic within D88 where it is interlocked with the [BLK_INV> and[C_L_INV> signals within D88 (See paragraph 3.3.7.4). This signal is high whenthe processor system requests ‘load-on-inverter’.
Conditions: (see paragraph 7.2.10 on page 7-180)
7-48 s7-c3b.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
L_MAINS
Destination: Sheet 3 – D88 pin 41
Description: ‘Load-on-bypass (mains)’ request – This output is connected tothe load transfer control logic within D88 where it is interlocked with severalother signals within D88 (See paragraph 3.3.7.4). This signal goes high when theprocessor system requests ‘load-on-bypass’.
Conditions: (see paragraph 7.2.10 on page 7-180)
REC-ON
Destination: Sheet 3 – D88 pin 40
Description: ‘Rectifier ON’ request – This output, when high, requests D88 toissue an [ON_REC> command signal, which is connected to the Rectifier LogicBoard and turns ON the rectifier (provided other D88 inputs are correct (See par-agraph 3.3.7)).
Conditions: (see paragraph 7.2.2 on page 7-158).
IBOPEN
Destination: Sheet 3 – D88 pin 12
Description: Trip battery circuit breaker– This output, when high, requests D88to issue a [BAT_TRP> command signal which is connected to the High Voltage In-terface Board and turns OFF the battery circuit breaker driver transistor.
Conditions: This signal is software driven via a programmable parameter set-ting entered from the Operator Control Panel to trip the battery circuit breakerwhen the battery is fully discharged (see page 2-37). The Emergency Shutdownand DC Overvoltage inputs to D88 pins 9 and 8 also trigger the battery trip signalwhen active (See paragraph 3.3.7).
TP6
Destination: Sheet 7 – X18 pin 6
Description: Not used (test point for system software).
3.3.12.6 Buffer D50 – activated by CSOUT3
O_BLK_SW
Destination: Sheet 7 – X1-43
Description: This output is used in a multi-module system only and has noaffect in a single-module or 1+1 system. In a multi-module system the output isconnected to the Parallel Logic Board where, when high, it turns off the invertersin all the modules connected to the system.
O_MNS_L_SS
Destination: Sheet 7 – X1-44
Description: This output is used in a multi-module system only and has noaffect in a single-module or 1+1 system. In a multi-module system the output isconnected to the Parallel Logic Board where, when high, it opens the output con-tactor in every module when a transfer to bypass is commanded.
s7-c3b.fm5 - Issue 2 Dated 21/08/97 7-49
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
O_MNS_D_SS
Destination: Sheet 7 – X1-45
Description: This output goes high when the bypass supply parameters aredeemed valid by the processor system. This is connected to the ‘bypass frequencyvalidation circuit on the Parallel Logic Board where it determines if the GVCO isallowed to synchronise to the bypass (see paragraph 2.4.4.1 on page 8-27).
TST_BAT
Destination: Sheet 7 – X1-46
Description: This output goes high when the processor system requests a ‘bat-tery test’ function and is connected to the Parallel Logic Board. If the UPS is con-figured as a 1+1 system with common battery, the Parallel Logic Board passesthis signal along the parallel control bus where it switches both modules to thebattery test mode – i.e. ensures both modules operate at the same charge voltage(see paragraph 2.6.3 on page 8-37).
BST_BAT
Destination: Sheet 7 – X1-47
Description: This output goes high when the processor system requests a ‘bat-tery boost’ function and is connected to the Parallel Logic Board. If the UPS isconfigured as a 1+1 system with common battery, the Parallel Logic Board passesthis signal along the parallel control bus where it switches both modules to thebattery boost mode – i.e. ensures both modules operate at the same charge voltage(see paragraph 2.6.2 on page 8-37).
MNS_SYN_KO
Destination: Sheet 7 – X1-48
Description: This output goes high when the processor system senses that theInverter Logic Board has achieved internal synchronism and is connected to theParallel Logic Board. If the UPS is configured as a 1+1 system this is used by theGVCO synchronisation control system as part of its inter-module synchronisationfunction (see paragraph 2.4 on page 8-19).
O_MNS_DIS
Destination: Sheet 7 – X1-49
Description: This high signal is connected to the Parallel Logic Board via X1-49 which, via the parallel control bus, immediately returns a logic low [MNS_DIS>
signal back to X1-37 in both modules of a 1+1 configured system. This is inputto the processor system via D51-4.
3.3.12.7 Buffer D55 – activated by CSOUT3
PAR_REC
Destination: Sheet 7 – X7-51
Description: This signal is driven high by the processor system when it requests‘parallel rectifier’ operation. It is connected to the Parallel Logic Board where itenergises relay K5, whose contacts complete the rectifier current sharing controlcircuit.
7-50 s7-c3b.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
OUT-03
Destination: Sheet 7 – X8 pin 31
Description: Output to Parallel Logic Board
Conditions: Not used in a 1+1-configured system.
OUT-03
Destination: Sheet 7 – X8 pin 25
Description: Output to I/O interface (remote alarms, AS400 interface etc.).
Conditions: Not used
MNS-KO
Destination: Sheet 7 – X8 pin 26
Description: Output to I/O interface (remote alarms, AS400 interface etc.).
Conditions: Logic high if mains (bypass) supply error – i.e. overvoltage [#11],undervoltage [#12], absent [#10] or bypass blocked [#17].
BATED
Destination: Sheet 7 – X8 pin 27
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Logic high if the battery voltage falls to its end-of-discharge level[#56] – as set by operator through Operator Control Panel (see page 2-37). It isalso active if the battery breaker is open [#05] or the battery fuse is open [#57].
CHG-INH
Destination: Sheet 7 – X8 pin 28
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Logic high if the battery charger is inhibited (driven by the[BLK-CHG> signal described on page 7-45). Jumper X4 pins 1-2 must be linked onthe Alarm Board.
SWBYP
Destination: Sheet 7 – X8 pin 29
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Logic high if maintenance bypass isolator is closed – accompaniedby alarm #06 [MANUAL BYPASS CLOSED].
OUT-01
Destination: Sheet 7 – X8 pin 23
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Not used in the present software implementation
s7-c3b.fm5 - Issue 2 Dated 21/08/97 7-51
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
3.3.12.8 Buffer D54 – activated by CSOUT4
OUT-02
Destination: Sheet 7 – X8 pin 24
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Not used in the present software implementation
OVT-BAT
Destination: Sheet 7 – X8 pin 18
Description: Output to I/O interface (remote alarms, AS400 interface, RemoteAlarms Monitor etc).
Conditions: Logic high in the event of battery overtemperature – Not used inthe present software implementation.
SYN-KO
Destination: Sheet 7 – X8 pin 16
Description: Output to I/O interface (remote alarms, AS400 interface, RemoteAlarms Monitor etc).
Conditions: Logic high if the inverter is unsynchronised to the bypass supply– i.e. if the phase displacement is more than ±9°. This condition will initiate alarm#35 [INV: UNSYNCHRONISED].
ALL-GEN
Destination: Sheet 7 – X8 pin 17
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: This is the “Common Alarm” output to the Alarm Board and isactive if any of the following alarms are present: [#05], [#06], [#10], [#11], [#12],[#16], [#17], [#24], [#33], [#34], [#52], [#56], [#57], [#66].
A400ON
Destination: Sheet 7 – X8 pin 31
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: This alarm is active when the load is on the UPS (inverter or by-pass) and is interlocked with the Maintenance Bypass being closed.
A400UF
Destination: Sheet 7 – X8 pin 32
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Condition: Mains Failure alarm; enabled by alarm [#01] and active when [#22] is energised.
A400BL
Destination: Sheet 7 – X8 pin 33
Description: Output to I/O interface (remote alarms, AS400 interface etc).
7-52 s7-c3b.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
Conditions: Low Battery warning; enabled by alarm [#01] and active when[#56] is energised.
A400BY
Destination: Sheet 7 – X8 pin 34
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Load on Bypass; active when alarm [#18] is energised.
3.3.12.9 Buffer D56 – activated by CSOUT4
MNSREC
Destination: Sheet 7 – X8 pin 20
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Rectifier input voltage failure – active when H9 is illuminated onthe Rectifier Logic Board.
CS-KO
Destination: Sheet 7 – X8 pin 19
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Bypass-side Static Switch blocked – goes high if a fault is detectedon the static switch (alarm [#16] present).
BAT-DSC
Destination: Sheet 7 – X8 pin 13
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Battery discharging – active when alarm [#22] is present.
OVL
Destination: Sheet 7 – X8 pin 14
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Overload – active when alarm [#33] or [#66] is present.
OVT-DIS
Destination: Sheet 7 – X8 pin 15
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Overtemperature – active when alarm [#24] or [#34] is present.
OVT-AMB
Destination: Sheet 7 – X8 pin 30
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Output Air overtemperature – not used.
XINV01
Destination: Sheet 7 – X3 pin 24
s7-c3b.fm5 - Issue 2 Dated 21/08/97 7-53
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
Description: Mains error inhibit to Inverter Logic Board transfer control.
Conditions: On the Inverter Logic Board a circuit within D11 provides a con-trol signal [RIF> which briefly transfers the voltage reference signal to the bypasssupply just before the ‘inverter-side’ contactor is closed; (see paragraph 2.3.3 onpage 5-45). This signal, [XIN01>, goes high to inform the Inverter Logic Board ofa mains (bypass) voltage error and prevents the switch-over to the bypass supplyreference from taking place; and so prevents the inverter locking to an out-of-specvoltage.
TP7
Destination: Sheet 7 – X18 pin 7
Description: Not used (test point for system software).
7-54 s7-c3b.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
Section 7:
3.3.13 Frequency sensing and control signals
Figure 7-9: Frequency synchronisation control
Important Note: This section describes the frequency control operation for a ‘single-module’ instal-lation – i.e. where the module is operating as a single, stand-alone UPS system.
Where the module is part of a ‘1+1 System’, the control operation is very similarexcept that the “bypass R_phase supply” signal to which the unit attempts to syn-chronise is obtained from the Parallel Logic Board, and is subject to a complexinter-module synchronisation regime.
To understand to synchronisation principles of a ‘1+1’ system, you are advised toread section 8 paragraph 2.4 prior to this section.
3.3.13.1 Frequency control principles
The inverter frequency is determined by the VCO section of a phase locked loopi.c. (D6) on the Inverter Logic Board which provides a 288kHz (nominal) clocksignal to a frequency-divider (within D1) which then clocks the multiplexers inthe ‘reference voltage generator’ circuit section 5 paragraph 2.3.2.
D1
FrequencyDivider
INV-F 44
D6
43
VCO
PhaseComparator
4CL
K
SYNC14
35
0/6
0H
z
D42
MIC
RO
CO
NT
RO
LLE
R
D53
BACKBACKM
416
63
15F-INF-INM
515
62
D17 15
D59
INV-F
SYNCM 564
34
37
35
34
37
35
UPS Logic Board Inverter Logic Board
X2
X3 X4
Bypass supply R-phase voltage sensing
50 /60 Hzselection
Master Freqreference forInverter Osc
PhaseLocked
Loop13
9
50/60Hz signalsynchronised tobypass (when present)
D54 6
DATABUS
SYNC-KO
Sync errordetection
VI-A
D60 2 BLK-SYN
Sync Inhibit
X18-2
X18-3
Clocksignalsto tri-wavegenerator
(correction)
28
8kH
z
8Vp-p
54
Parallel logic
27
[O_BACK>
15
14
2
2-3 = SingleX34:1-2 = Parallel
1
3
align
R247phase
SYNC
5V(M:S variations )
20
21
D1
X72
s7-c3c.fm5 - Issue 2 Dated 21/08/97 7-55
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
Base frequency selection
The inverter base frequency is selected via the Operator Control Panel duringcommissioning and is read by the microcontroller through the CAN bus. Themicro responds by appropriately setting the [INV-F> output from D17-15 – Low =50Hz and High = 60Hz. This is connected to the ‘frequency divider’ on the Invert-er Logic Board where it determines the division factor – i.e. when [INV-F> is lowthe 288kHz VCO output is divided by 5760 to produce a 50Hz output at D1-27;when [INV-F> is high the division is 4800 and produces a 60Hz output.
Frequency synchronisation
It is desirable that the inverter output is synchronised to the bypass supply undernormal operating conditions as this enables a ‘closed’ load transfer to be carriedout in the event of a UPS fault – where-by the static switch SCRs are turned on atthe same time as the inverter contactor is opened, and the load does not experiencea supply break.
If the inverter is not synchronised to the bypass supply there could be a large volt-age difference across the static switch SCRs while the load is ‘on-inverter’ (i.e.SCRs OFF) which might damage the UPS/load equipment during a subsequent‘closed’ transfer: in such circumstances an ‘open’ transfer takes place if the UPSdevelops a fault, where-by the inverter contactor is opened prior to turning ONthe static switch SCRs. This causes a load supply break of up to 1 second, whichis an inbuilt feature designed to avoid load damage.
The frequency synchronisation control mechanism is quite complex and effec-tively based on two nested phase locked loops. The inner loop comprises D6 onthe Inverter Logic Board and the outer loop is functionally provided by the micro-controller, under software control.
3.3.13.2 Frequency sync control and operation
Inverter Logic Board phase-locked-loop (assuming 50Hz operation.)
The ‘phase comparator’ section of D6 compares the 50Hz output from D1-27,connected to D6-3, with a frequency reference signal annotated [SYNC> which isproduced by the microcontroller and connected to D6-14 (available at test pointX18-4). If the ‘phase comparator’ detects any phase difference between these twosignals its output at D6-13 will modify the VCO’s frequency in such a way as tomake the ‘frequency divider’ output at D1-27 match the [SYNC> signal frequency– i.e. the VCO frequency will be modified until the ‘phase comparator’ within D6sees no error between these signals, whereupon the circuit can be considered tobe phase-locked. Thus the inverter frequency tracks the [SYNC> signal ‘reference’frequency.
[SYNC> signal generation (assuming 50Hz)
The microcomputer monitors the bypass supply R-phase waveform [VI-A> via acomparator which extracts its frequency information, [F-INM>. This signal can beseen at X18-2 as a squarewave coinciding with the bypass supply R-phase zero-crossing points. The Inverter Logic Board frequency divider’s 50Hz output (D1-27) is also monitored and is available at X18-3, annotated [BACKM>.
Under software control, the micro operates on these two signals in the same wayas described above for the Inverter Logic Board’s phase-locked-loop. That is, itperforms the ‘phase comparator’ and ‘VCO’ functions described above and pro-duces a 50Hz output, [SYNC>, whose absolute frequency is controlled by the de-
7-56 s7-c3c.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
tected phase difference between [F-INM> and [BACKM> – i.e. the width of the pulseis directly proportional to the amount of phase difference.
Example of sync control
The overall operation of the synchronisation control circuits can best be explainedby example. Consider the case where the bypass frequency suddenly jumps from50Hz to 50.5Hz:
1. The micro will sense the jump in bypass frequency through a rise in [F-INM>
to 50.5Hz.
2. The micro will sense a phase error between [F-INM> and [BACKM> due to theirfrequency difference and will ramp-up the [SYNC> signal frequency becauseit senses that the bypass frequency is higher than that of the inverter.Note: ramp-up speed is controlled under a slew rate software program factoryset at 0.1Hz /Second.
3. The ‘phase comparator’ in the Inverter Logic Board’s phase-locked-loop willsee the ramping [SYNC> frequency and detect that it is now higher than thefrequency divider’s ‘50Hz’ output.
4. The phase comparator error output (pin 13) will call for an increase in VCOfrequency, which will thus increase the ‘frequency divider’ clock rate andthereby demand an increased inverter frequency.
5. The ‘50Hz’ outputs from the frequency divider also ramp-up in line with theinverter frequency and have two affects:
a) The increasing output at D1-27 is fed back to the phase-locked-loop(D6-3) where it maintains phase-lock – i.e. it ties the clock frequency tothe [SYNC> signal and maintains close tracking of this signal.
b) The same increasing output from D1-27 is fed back to the microcontrollervia R247 where it allows the phase error function to maintain a closecheck on the ‘bypass/inverter’ frequency and phase relationship.
6. When the inverter frequency has risen to match the 50.5Hz bypass frequency,and the [F-INM> and [BACKM> signals are in phase:
a) The [SYNC> frequency will stop ramping up and remain at 50.5Hz, syn-chronised to the bypass supply due to the action of the micro.
b) The VCO clock frequency will remain constant – i.e. 290.88kHz (5760 x 50.5 – as 5760 is the divider factor for 50Hz systems).
c) The output from D1 pin 27 will be steady at 50.5Hz and synchronised tothe [SYNC> signal.
7. If [SYNC> is synchronised to the bypass supply (6a) and the frequency divideroutputs/inverter are synchronised to the [SYNC> signal (6c) then this results inthe inverter being effectively synchronised to the bypass supply, are required.
Important notes: The above description requires qualification by the follow-ing notes.
a) The internal mechanism of the frequency divider chip ties its ‘50Hz’ out-puts to the zero-crossing points of the R-phase inverter voltage. Thus, asthe micro uses the bypass R-phase supply as its frequency sensing source,this effectively ensures that the inverter and bypass supplies are synchro-nised correctly from a phase alignment viewpoint.
s7-c3c.fm5 - Issue 2 Dated 21/08/97 7-57
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
b) To aid description the above example assumed that the bypass frequencyunderwent a stepped change; however, in practice any change in bypassfrequency is likely to occur gradually: in which case the circuit dynamicsare usually able to maintain a phase-locked condition during the period ofchange, resulting in the inverter frequency tracking the bypass frequencyat all times without incurring a detectable phase error.
c) The synchronising ‘window’ and ‘slew-rate’ are adjustable and selectedfrom the Operator Control Panel setup menus. The ‘window’ defines thelimits to which the inverter is allowed to track the bypass frequency andnormally set to ±2%; while the ‘slew-rate’ defines the maximum permit-ted rate-of-change of inverter frequency and is usually set to 0.1Hz/s.– i.e.this determines the fastest rate of change of bypass frequency tolerated bythe synchronisation circuit whilst maintaining sync.If the bypass frequency goes outside the permitted window for longer than1 minute, the inverter frequency will return to its base frequency and awaitthe mains return within the sync window, where-upon it will re-synchro-nise. An [INV:UNSYNCHRONIZED] (alarm #35) warning will be dis-played while this situation is in effect.
d) In the event of a bypass supply failure the microcontroller will drive its[SYNC> output to the ‘centre’ frequency – i.e. 50Hz.
Sync phase adjustment
R247 is connected to a ‘phase-shift’ circuit on the Inverter Logic Board and pro-vides the means for trimming any error in the phase relationship between the in-verter [BACKM> and bypass [F-INM> sense signals once the sync control circuit isphase-locked – due mainly to component tolerances. Therefore, once the inverteris synchronised this resistor can be adjusted to reduce the residual phase differ-ence between the inverter R-phase output and the bypass R-phase supply.
3.3.13.3 Non-Sync detection and alarm
An alarm condition [SYN-KO> is flagged by the microcontroller when it detectsthat the [BACKM> and [F-INM> signals are more than 11° out-of-phase. This is com-municated to the Operator Logic Board via the CAN bus and also, via D54-6, tothe I/O interface connector X8-16 where it can be used to provide a remote alarmsindication (sheet 7). [SYN-KO> is ‘high’ when a non-sync condition is present.
3.3.13.4 External ‘sync inhibit’
In certain circumstances it may be necessary to inhibit the synchronisation loop –for example when supplying the UPS from a stand-by generator whose frequencyregulation is poor. This can be achieved by an external input via the I/O connectorX8-11 [BLK-SYN> which is connected to the microcontroller via D60-2. This inputmust be taken ‘high’ to inhibit the synchronisation function (See paragraph3.3.11.6).
Note: The control can be activated only after being ‘enabled’ in the ‘Function’ pa-rameter software setup screen (see paragraph 2.4.7.3 on page 2-43).
7-58 s7-c3c.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
3.3.14 Analogue signal processing
The UPS Logic Board monitors the UPS input voltage, output voltage, invertervoltage, battery voltage, output current and battery current. These inputs are proc-essed by analogue circuits (sheets 6 & 7) which provide appropriate signals forthe microcomputers A/D input port. In some cases the inputs are also convertedto digital alarm/status signals which are connected to the micro via the data bus.
3.3.14.1 Bypass voltage signal processing
Figure 7-10: Bypass voltage sensing block diagram
Voltage sensing
The bypass voltage sense signals ([VI-A> - [VI-C>) are developed on the High Volt-age Interface Board (See paragraph 2.3.6) and connected via X2 pins 15, 16, 17to N6b/c/d which are unity-gain buffers (sheet 5). The signals at N6 outputs there-fore equate to approximately 1% of the bypass supply line-neutral voltage (e.g.2.4Vrms at 240V working) and are connected to several blocks as shown inFigure 7-10.
Voltage monitoring
N29a-c take the line-to-neutral sense voltages produced by N6 and converts theminto line-to-line sense voltages suitable for connecting to the microcontroller A/Dinputs. Taking N29a as an example; this amplifier differentially sums the [VI-A>
and [VI-B> signals from N6 and produces the [VIABM> L-L signal. However theamplifier attenuates the resultant signal to about 30% (e.g. 1.38V for 240V work-ing) due to its feedback resistance ratios: also, the non-inverting input is connect-ed to VREF-2 (2.5V reference voltage) rather than to the 0V rail, which thereforeapplies a 2.5V offset to [VIABM>. Thus in a 240V system working at nominal volt-age [VIABM> is approximately 3.9Vp-p centred on a 2.5V reference. This signalsits well within the microcontroller’s A/D 0-5V input level, and is shown connect-ed to the A/D multiplexer circuit (sheet 6).Note: if the bypass voltage is missing [VIABM> will be 2.5Vdc due to the absenceof any ac signal.
A-Ph
N6Buffer
N29Sum-Amp
N29dRectifier
N14Filter
N14Filter
B-Ph
3-PhaseBypass
VoltsSense
D27Ph-Seq
VIABM
VIBCM
VICAM
[SVI>
[SVIM>
[F-IN>
[SEQMNS>
To A/DMultiplexers
To SCR OPEN det.
To A/D Multiplexers
To Micro(sync control - bypass R-ph)
To Micro(Phase Sequence
Line-Neut Line-Line
REF-2 (2.5V)
8Vp-p
+5V+2.5V
0V
(Display uses)
(Bypass volts monitor)
error detector)
s7-c3c.fm5 - Issue 2 Dated 21/08/97 7-59
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
Bypass frequency and phase sequence monitors
The bypass R-phase signal [VI-A> from N6-14 is connected to a zero-crossing cir-cuit comprising N14a/d which produces a squarewave output [F-IN> at D34-6which coincides with the R-phase zero-crossing points. This signal is used by themicrocontroller in its frequency synchronisation control (See paragraph3.3.13.1).
A similar squarewave coinciding with the S-phase is obtained via N14b/c andbuffered by D34-8. These two squarewave signals are connected to a D-type flip-flop (D27) which detects their phase relationship. Under normal circumstancesthe R-phase signal should lead that of the S-phase; therefore when the rising-edgeR-phase signal clocks D27, its data (D) input should be ‘low’, producing a perma-nent ‘high’ on its Q output which inverted to a ‘low’ [SEQMNS> signal at D34-10.
In the event of a phase sequence error, D27 will have a permanent ‘low’ clockedthrough to its Q output and produce a ‘high’ [SEQMNS> signal.
[SEQMNS> is connected to the microcontroller via the data bus buffer D28-7where it flags a phase rotation error – [BYP: PHASE ROT.ERROR] alarm #14(See paragraph 3.3.11.4).
3-phase voltage monitor
A full-wave, three-phase diode bridge comprising V34-V36 & V40-V42, produc-es a dc voltage proportional to the full three-phase supply which is fed to N29d.This amplifier attenuates the signal by 55% due to the values of the feedback re-sistors; therefore the output at N2-14 is approximately 2.5Vdc at nominal workingvoltage. Note that this is a ripple voltage since there is very little capacitancearound the amplifier. Thus if any bypass phase voltage goes out of tolerance (e.g.±10% window) the detector will sense the error. It does not require all threephases to go outside the error window.
N2-14 provides signals to two other areas: [SVIM> is connected to the microcon-troller A/D input via the multiplexer circuit shown on sheet 6 and used by themicro to monitor the bypass voltage for a each individual phase (e.g. ±10% volt-age error); and [SVI> is connected to the circuit (also on sheet 6) which detects anopen circuit static switch SCR.
3.3.14.2 Inverter voltage sensing
Figure 7-11: Inverter voltage sensing block diagram
Voltage sensing
The inverter voltage sense signals ([VINV-A> - [VINV-C>) are developed on the HighVoltage Interface Board (See paragraph 2.3.5) and connected via X2 pins 18, 19,20 to N3a-c which are unity-gain buffers (sheet 5). The signals at N3 outputstherefore equate to approximately 1% of the inverter line-neutral voltage. A full-wave, three-phase diode bridge produces a dc voltage proportional to the fullthree-phase output which is then fed to N3d. This amplifier attenuates the signal
N3dRectifier
3-PhaseInverter
VoltsSense
[SVINVM>To A/D Multiplexers
Line-Neut
N3a-cBuffer
8Vp-p2.2Vdc
error detected on individual phase
7-60 s7-c3c.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
by 55% due to the values of the feedback resistors; therefore the output at N3-14is approximately 2.5Vdc at nominal voltage, and connected to the microcontrollerA/D input via the multiplexer circuit shown on sheet 6. This is a ripple voltage asdescribed previously, and is monitored by the inverter voltage error softwarefunction (i.e. ±10%).
3.3.14.3 Battery (bus) voltage sensing
Figure 7-12: Battery voltage sensing block diagram
Battery volts monitor
The DC busbar (battery) voltage sense signal [V-B> is developed on the High Volt-age Interface Board (See paragraph 2.3.3) and connected via X2 pin 27 to N13awhich is a unity-gain buffer (sheet 5). The signal sensitivity is set on the HighVoltage Interface Board to approximately 7.3mV per Volt(bat) therefore [VBM> isabout 3.255V at nominal 446V float charge voltage. This signal is connected tothe microcontroller A/D input, via the multiplexer circuit shown on sheet 6, whereit is used by several software functions, such as: display metering; slow DC over-voltage (max 2.4V/cell window); Low Battery warning (1.82V/cell window); Endof Discharge (1.67V/cell window); and % Charge/autonomy Time algorithms.
DC Overvolts detection (Fast)
[VBM> is also monitored by N13c, which is configured as a comparator and usedto detect a DC Bus overvoltage condition. N13c has a fixed threshold which op-erates ([BAT-MA> goes high) when [VBM> reaches approximately 4.45V, whichequates to a DC Bus voltage of around 620Vdc.
[BAT-MA> is connected to the ‘Basic System Control Logic’ where it trips the bat-tery circuit breaker, turns off the rectifier and inverter, and trips a latch (See par-agraph 3.3.7.1). In an overvoltage situation – [DC BUS: FAST OVERVOL.] alarm#58 – the ‘Basic System Control Logic’ responds by issuing a ‘high’ [MBATMA>
signal which flags the micro-controller via data bus buffer D26 (See paragraph3.3.11.4).
3.3.14.4 Battery current sensing
Figure 7-13: Battery current sensing block diagram
N13cComparator
[VBM>To A/D Multiplexers
N13aBuffer[V-B> [BAT-MA>
DC Overvoltage (Fast)
3.25Vdc@ 446V(bat)
(set to 620V(bat))
[IBM>To A/D Multiplexers
N13bBuffer
[I_B>
REF-2 (2.5V)
[I_B_P>
X36: 1-2 = Separate battery2-3 = Common battery
s7-c3c.fm5 - Issue 2 Dated 21/08/97 7-61
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
Battery current monitor
The battery current sense signal [I_B> is developed on the High Voltage InterfaceBoard (See paragraph 2.3.22) and connected via X2 pin 31 to N13b which has again of approximately1.5 (sheet 5). The signal sensitivity is set on the High Volt-age Interface Board by jumper X38 and the output [IBM> is connected to themicro-controller A/D input via the multiplexer circuit shown on sheet 6 where itis used for display purposes, and % Charge and Autonomy Time algorithms.
I_B_P is used in a 1+1 installation when the rectifier is paralleled in order to sharecurrent in a common battery system (see paragraph 2.6.1 on page 8-36)
3.3.14.5 Output voltage sensing
Figure 7-14: Output voltage sensing block diagram
Voltage sensing
The bypass voltage sense signals ([VO-A> - [VO-C>) are developed on the HighVoltage Interface Board (See paragraph 2.3.6) and connected via X2 pins 21, 22,23 to N5a-c which are unity-gain buffers (sheet 6). The signals at N5 outputstherefore equate to approximately 1% of the output line-neutral voltage (e.g. 2.4V(8Vp-p) at 240V) and connected to several blocks as shown in Figure 7-14.
Voltage monitoring
The signals from N5a-c are connected to two sets of buffers which provide line-to-neutral and line-to-line monitoring voltages which are connected to the micro-controller A/D inputs via the multiplexer circuit shown on sheet 6 and used formetering & display purposes.
L-N voltage monitoring. is provided by N38a-c which attenuate the voltagesense signals by approximately 55% and also applies a 2.5Vdc offset due to thenon-inverting connection being terminated at VREF-2 (2.5V reference voltage). At240V nominal voltage the monitor output signals [VOAM>, [VOBM>, VOCM> aretherefore 1Vrms (2.8Vp-p) centred about a +2.5V reference which sits well withinthe microcontroller’s A/D 0-5V input level.
N5Buffer
N31Sum-Amp
N15aRectifier
3-PhaseOutput
VoltsSense
N15b-dCompar-
VOABM
VOBCM
VOCAM
[SVOM>
[SCROPN>
To A/DMultiplexers
To A/D Multiplexers
To Micro(SCR open cct.)
Line-Line
REF-2 (2.5V)
N30Buffer
VOAM
VOBM
VOCM
To A/DMultiplexers
Line-Neut
REF-2 (2.5V)
[SVI> ator
8Vp-p
+5V+2.5V
0V
(Critical bus monitor)
(monitoring & display)
(Monitoring &display)
7-62 s7-c3c.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
Note: if the output voltage is missing [VOAM> etc. will be 2.5Vdc due to the ab-sence of any ac signal.
L-L voltage monitoring. is provided by N31a-c. Taking N31a as an example;this amplifier differentially sums the A and B phase signals from N5 and producesthe [VOABM> L-L signal. However, the amplifier attenuates the resultant signal byabout 70% (e.g. 1.38V for 240V working) due to its feedback resistance ratios:also, as with the L-N circuit described above, the non-inverting input is connectedto VREF-2 (2.5V reference voltage) rather than to the 0V rail, which applies a 2.5Voffset to [VOABM>. Thus in a 240V system working at nominal voltage [VOABM>
is approximately 3.9Vp-p centred on a 2.5V reference.
3-phase voltage monitor
A full-wave, three-phase diode bridge comprising V29-V31 etc, produces a dcvoltage proportional to the full output three-phase supply which is fed to N15a.This amplifier attenuates the signal by 55% due to the values of the feedback re-sistors; therefore the [SVOM> output at N15-1 will be approximately 2.5Vdc atnominal working voltage. Note that this is a ripple voltage since there is very littlecapacitance around the amplifier. [SVOM> is connected to the microcontroller A-to-D inputs via the multiplexer circuit shown on sheet 6. This is used by themicro-controller as a critical bus voltage error monitor (factory set to ±10%) fortransfer functions.
Open Circuit Static Switch SCR detection
As shown in Figure 7-14, the output voltage (3-phase) sense signal [SVOM> andbypass voltage (3-phase) sense signal [SVI> are both connected to the StaticSwitch ‘SCR open circuit’ detector.
3.3.14.6 Output current sensing
Figure 7-15: Output sensing block diagram
Output current monitor
The UPS output current sense signals ([IO-A> - [IO-C>) are developed on the HighVoltage Interface Board (See paragraph 2.3.19) and connected via X2 pins 32,33, 34 to N4a-c which attenuate the sense signals by approximately 75% and alsoapplies a 2.5Vdc offset due to the non-inverting connection being terminated atVREF-2 (2.5V reference voltage). The output signals [IOAM> etc. are connected tothe microcontroller A/D inputs via the multiplexer circuit, and the 2.5V offset issufficient to make the a.c. current signal sit within the 0-5V A/D input voltagerange. These signals are by the micro’s ‘overload’ algorithm (i.e. 150% for 1
N4dSum-amp
3-PhaseOutput
CurrentSense
[IONM>To A/D Multiplexers
N4a-cBuffer
REF-2 (2.5V)
[IOAM>[IOBM>[IOCM>
(Overload & Timers)
(Display Metering)
s7-c3c.fm5 - Issue 2 Dated 21/08/97 7-63
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
minute, 125% for 10 minutes, 110% for 1 hour, 101% for 9 hours). They also rep-resent the values shown on the Operator Control Panel ‘Measurements’ displayscreen.
N4d calculates the neutral current by differentially summing the three line cur-rents – in a balanced three phase system the algebraic sum of the currents shouldequal zero, thus if the system is unbalanced then the amount of imbalance repre-sent the current flowing in the neutral path. The neutral current signal [IONM> isalso subject to the 2.5V offset and applied to the microcontroller A/D inputs viathe multiplexers in the same way as the line current signals.
3.3.14.7 Analogue signal monitoring multiplexers
The microcontroller has ten A/D inputs ([AN0> to [AN9>).
[AN6> to [AN9> are fed by fixed inputs signal sources; however, [AN0> to [AN5>are fed via a series of multiplexers which allow the micro to select from varioussignal sources. Three type 4052 multiplexers are used for this purpose, each ad-dressed by two signals ([SELANA> and [SELANB>) produced by the microcontrol-ler via data bus buffer D9 (See paragraph 3.3.12.4). Sheet 6 contains themultiplexer circuit and illustrates the various monitored signals connected to theirdata pins (See Appendix A.3). The multiplexers are inhibited if the -12V powersupply monitor detects an undervoltage by applying a logic high [FL-12-> to themultiplexer inhibit inputs (pin 6) (See paragraph 3.3.15.3).
Note: the inputs annotated [T1> - [T4> are temperature sensing inputs – refer to theHigh Voltage Interface Board description (See paragraph 2.3.12).
Note: the micro can access the A/D signals in parallel and where necessary cancalculate values for the display – e.g. kW = V x I.
7-64 s7-c3c.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
Section 7:
3.3.15 Power supplies
3.3.15.1 General description and voltage regulators
The UPS Logic Board ±12V power supply rails are provided from two parallelsources and will be available if either source is live. The first source is from theRectifier Logic Board, which is itself powered from the AC-DC Power Supplyand available whenever the UPS input (rectifier) supply is live (see paragraph 2.1on page 3-5); the second if from the Inverter Logic Board, which is powered fromthe DC-DC Power Supply and is available whenever the rectifier is working orthe batteries are connected to the DC Busbar (see paragraph 3.1 on page 3-7).
From the UPS Logic Board the ±12V supplies are passed directly to all the re-maining circuit boards and the communications port etc.
3.3.15.2 Reference voltage generators
Several devices require a stable +5V power supply which is provided by a simple3-terminal +5V regulator (N1), shown on sheet 7.
In addition to the +5V power supply rail, there are also two reference voltage gen-erators on the circuit board. One generates a regulated +5V, [VREF>, from the+12V line and the other generates a regulated 2.5V output, [VREF-2>, from the+5V supply rail. These reference voltages are used in conjunction with the micro-controller’s A/D analogue inputs and are shown on sheet 5 of the circuit diagram.
+5V reference voltage [VREF>
This provides a stable power supply for the A/D converters within the microwhich is necessary for them to maintain their conversion accuracy.
2.5V reference voltage [VREF-2>
The micro-controller’s internal A/D converters operate on stable 0V and +5Vpower rails, as described above. Therefore if an AC signal is to be monitored (e.g.bypass voltage), or a positive-and-negative going DC signal (e.g. battery current),then a 2.5V offset is required shift the 0V point of the monitored signal into thecentre of the A/D converters’ input working range. This enables the A/D circuitto convert both halves of an AC waveform and both positive and negative transi-tions of a dc signal voltage.
3.3.15.3 -12V undervoltage detector
Comparator N45a (sheet 5) serves as a -12V supply rail monitor and detects whenthe -12V is less than approximately -9.8V. The operating threshold for this circuitis set by V70 which applies a zener referenced voltage across R242/243 from the+12V rail and under normal conditions sets N45-3 at about 1.86V. The -12V railis monitored via a resistor divider (R240/241) which is fixed at +3V at one end byV70.
Due to the chosen resistor ratios, the voltage at N45-2 rises above 1.86V when the-12V rail is less than -9.8V, at which point N45-1 switches low and produces alogic high [FL-12-> signal and low [FL-12>.
When [FL-12> goes low it inhibits the back-up battery voltage sense signal to themicrocontroller via D44, as shown on diagram sheet 2 (See paragraph 3.3.4).When [FL-12-> goes high is disables the microcontroller’s A/D input multiplexers,as shown on sheet 6 (See paragraph 3.3.14.7).
s7-c3d.fm5 - Issue 2 Dated 21/08/97 7-65
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
3.3.15.4 +12V undervoltage detector
Comparator N45b (sheet 5) serves as a +12V supply monitor. The operatingthreshold for this circuit is set by [VREF-2> which applies a stabilised +2.5V toN45-6, at about 1.86V. The +12V rail is monitored via a resistor divider (R246/245/R244) which pulls the input to N45-5 below the 2.5V threshold when the+12V rail fall below the 9.8V level. When this occurs the output at N45-7 switch-es from high to low which is reflected at D57-8 and the resulting ‘low’ [PFO> flagresets the microcontroller via its non-maskable interrupt (NMI) (See paragraph3.3.2). The micro jumps to a ‘save data’ subroutine as the supply rails are crash-ing.
7-66 s7-c3d.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
3.3.16 External communications
RS232 communications
In addition to the bi-directional communication facility with the Operator LogicBoard via the CAN Bus, the microcontroller can also be accessed externally viaa standard RS232 communications connection (X9). This is designed to be usedwith a portable computer for diagnostic, calibration and configuration purposes.Communication takes place through D16 which is a standard RS232 line driver/receiver connected to the micro via [TXO0> and [RXO0>, as shown on sheet 7 (SeeAppendix A.6).
RS-485 Parallel control communications
An RS485 communications facility is also shown on sheet 7, based around D58(See Appendix A.5). The differential I/O bus of this device (pins 6 & 7) is connect-ed to the Parallel Logic Board via X7 ([TXRX+>, [TXRX->).
Transmit mode. the transmit mode is enabled when [DE485> is high, whereup-on the [TXDI> data from the microcontroller, applied to D58 pin 4, passes throughthe device and drives its differential outputs as described in appendix A.5. Notethat X32 should be made in order to connect the bus termination resistor (R250)across the transmission line to present the correct impedance to the differentialoutputs.
Receive mode. the receive mode is enabled when [RE485-> is taken low, where-upon the data on the differential I/O bus is converted into a data-stream and con-nected to the microcontroller via [RXDI>.
s7-c3d.fm5 - Issue 2 Dated 21/08/97 7-67
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
3.3.17 On board 7-segment indications summary
The following table provides a summary of the alarm codes indicated on the two7-segment LEDs together with their alarm interpretations and associated OperatorPanel audible and visible alarm annunciations. Note that there is no on-screenalarm history facility, but where two (or more) alarms are active simultaneouslythe associated codes will be displayed in a cyclic fashion at 1 second intervalsNote: Where the fault LED state is annotated (*) this indicates that the alarm islatched and must be reset using S1 on the UPS Logic Board
Note: The following table has been updated for version 4.0 software alarm de-scriptions. Earlier software versions may differ slightly though the alarm functionremains the same.
CODEDisplay Alarm Messages
(Correct Meaning)Audible Alarm
(Operator Panel)FAULT LED (red)(Operator Panel)
01 [ NORMAL OPERATION ] OFF OFF
02 [ BYPASS SWITCH OPEN ] Continuous ON
03 [ OUTPUT SWITCH OPEN ] Continuous ON
04 [ RECTIF. SWITCH OPEN ] Continuous ON
05 [ BATTERY SWITCH OPEN ] Continuous ON
06 [ MANUAL BYPASS CLOSED]Manual bypass breaker closed
Pulsed Flashing
10 [BYP: ABSENT ]Bypass supply absent – i.e. <50V
Intermittent Flashing
11 [ BYP: OVERVOLTAGE ]Bypass supply over voltage –upper limit set via mimic menu
Intermittent Flashing
12 [ BYP: UNDERVOLTAGE ]Bypass supply under voltage –lower limit set via mimic menu
Intermittent Flashing
13 [ BYP: FREQUENCY ERROR]Bypass supply over/under freq –window limit set via mimic menu
Intermittent Flashing
14 [ BYP: PHASE ROT. ERROR ]Bypass phase rotation error
Continuous ON
15 [ BYP: SCR FAILURE ]Bypass SCR open circuit
Continuous ON *
16 [ BYP:HARDWARE BLOCK ]Bypass supply blocked –
hardware block on UPS Logic Board
Pulsed Flashing
17 [ BYP: OFF VIA DISPLAY]Bypass blocked via operator menu
Pulsed Flashing
18 [ LOAD ON BYPASS ] Intermittent Flashing
19 [ BYP: OVERTEMPERATURE ]Static bypass overtemperature
warning
Continuous ON
7-68 s7-c3d.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
20 [ RECT:SOFTWARE BLOCK]Software block via micro
Intermittent Flashing
21 [ RECT: OFF VIA DISPL. ]Rectifier blocked via operator menu
Pulsed Flashing
22 [ RECT: HARDWARE BLOCK ]Hardware block via UPS Logic Board
Continuous ON
23 [ RECT: CURRENT LIMIT ]Rectifier input current limit
Intermittent Flashing
24 [ RECT: OVERTEMPERAT. ]Rectifier overtemperature
Continuous ON
25 [ RECT: FUSE FAIL ]Input fuse failure (F10,F11,F12)
Continuous ON
30 [ INV: SOFTWARE BLOCK ]Software block via micro
Intermittent Flashing
31 [ INV: OFF VIA DISPLAY ]Inverter blocked via operator menu
Intermittent Flashing
32 [ INV: HARDWARE BLOCK ]Hardware block via UPS Logic Board
Continuous ON
33 [ INV: CURRENT LIMIT ]Inverter 150% current limit active
Continuous ON
34 [ INV: OVERTEMPERATURE ]Inverter overtemperature
Continuous ON
35 [ INV: UNSYNCHRONIZED ]Inverter unsynchronised to bypass
warning
Intermittent Flashing
36 [ INV: OVERVOLTAGE ]Inverter overvolts warning
Continuous ON
37 [ INV: UNDERVOLTAGE ]Inverter undervolts warning
Continuous ON
38 [ INV: FUSE FAIL ]Inverter fuse failure
Continuous ON
39 [ OUTPUT: OVERVOLTAGE ]Inverter overvoltage trip –
critical bus overvoltage trip to bypass
Continuous ON
40 [ OUTPUT: UNDERVOLTAGE ]Critical bus undervoltage trip to
bypass – level set via mimic menu
Continuous ON
41 [ OUTPUT: NO VOLTAGE ]UPS in off-line mode
Continuous ON
42 [ OUTPUT: WAVEFORM ERR. ]Critical bus peak voltage error
Continuous ON
CODEDisplay Alarm Messages
(Correct Meaning)Audible Alarm
(Operator Panel)FAULT LED (red)(Operator Panel)
s7-c3d.fm5 - Issue 2 Dated 21/08/97 7-69
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
43 [ INV: FREQUENCY ERROR ]lnverter frequency error –
inverter frequency window is twice the bypass window
Continuous ON
44 [ INV: PARALLEL ERROR ]Paralleling current error
Continuous ON *
45 [ CONTACTOR FAILURE ]
50 [ BATTERY: UNDER TEST ]Battery test in operation
Pulsed OFF
51 [ BATTERY: TEST FAILED ]Battery test has failed
Intermittent Flashing *
52 [ BATTERY: DISCHARGING ]Battery is discharging
Intermittent Flashing
53 [ BATTERY: E.O.D. ]Battery end_of_discharge trip –
level set via mimic menu
Continuous ON
54 [ BOOST: TIME EXPIRED]Boost charge period expired
Pulsed Flashing
55 [ DC BUS: SLOW OVERVOL. ]DC slow overvolts warning –
level set via mimic menu
Continuous ON *
56 [ DC BUS: UNDERVOLTAGE ]Low battery warning –
level set via mimic menu
Continuous ON
57 [ BATTERY: FUSE FAIL ]Battery fuse (F13) failure
Continuous ON
58 [ DC BUS: FAST OVERVOL. ]Fast dc overvoltage –
fixed at 620V
Continuous ON *
60 [ BYP: XFER COUNT BLOCK ]Transfer counter exceeded
– i.e. >8 transfers in 1 minute
Continuous ON *
61 [ CUT-OFF: OVERLOAD ]Overload timer expired
Continuous ON *
62 [ CUT-OFF: OVERTEMPER. ]Overtemperature timer expired
Continuous ON *
63 [ CUT-OFF: EMERGENCY ]“Emergency power-off” activated
Continuous ON *
66 [ OVERLOAD PRESENT ]Overload present (warning)
Continuous ON
67 [ CUT-OFF: OVERLOAD ]Overload timer expired
Continuous ON *
CODEDisplay Alarm Messages
(Correct Meaning)Audible Alarm
(Operator Panel)FAULT LED (red)(Operator Panel)
7-70 s7-c3d.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
70 [ BAD EEPROM PROGRAM. ]Start-up error – use mimic reset
Pulsed ON
71 [ ERR. LRC PAR. PAG 1 ]Incorrect display variable
Pulsed ON
72 [ ERR. LRC PAR. PAG 2 ]Incorrect display variable
Pulsed ON
73 [ ERR. LRC PAR. PAG 3 ]Incorrect display variable
Pulsed ON
74 [ ERR LRC ALARM HIS. ]Alarm History buffer error
Pulsed ON
75 [ ERR LRC EVENT HIS. ]Alarm History buffer error
Pulsed ON
76 [ INTERNAL BATTERY LOW ]Internal PCB ni-cad battery Low
Pulsed ON
80 [ ERROR LRC TABLE ]
81 [ ERROR LRC PANEL ]
82 [ MODEM WRONG CONFIG. ]
83 [ ERROR LRC ALARM MEM. ]
84 [ MODEM NO RESPONSE ]Modem incorrectly connected
85 [ MODEM FALSE COMMAND ]Modem incorrectly configured
86 [ MODEM TIMEOUT TRASM. ]Modem baud-rate error
87 [ CAN BUS NO RESPONSE ]UPS-to-display not connected
88 [ AUTONOMY XXXX min ]Battery autonomy time
CODEDisplay Alarm Messages
(Correct Meaning)Audible Alarm
(Operator Panel)FAULT LED (red)(Operator Panel)
s7-c3d.fm5 - Issue 2 Dated 21/08/97 7-71
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
3.4 Summary information
Table 7-8: UPS Logic Board configuration jumpers
JumperLink
Position Function
X12
OPEN (standard)
1 - 2 Not Required
3 - 4 Not Required
X13 1 - 2 EPROM Enable
2 - 3 RAM Enable (standard)
X14
1 - 2 Not Required
Testing onlynormally open
3 - 4 Not Required
5 - 6 Not Required
7 - 8 Not Required
X151 - 2 PLL option with
2 - 3 PLL option with (standard)
X16OPEN CAN Bus to display disabled
1 - 2 CAN Bus to display enabled (standard)
X171 - 2 ALE enable data save
2 - 3 Power supply fail enable data save (standard)
X191 - 2 EPROM II enable (not required)
2 - 3 RAM II enable (not required)
X201 - 2
+5V PCB enables microprocessor ref. For VA calculations (standard)
2 - 3 V ref. enables microprocessor ref. For VA calculations
X211 - 2 Not Required
2 - 3 RAM enable (standard)
X221 - 2 EPROM enable (standard)
2 - 3 Not Required
X23
1 - 2 Not Required
2 - 3 EPROM enable (standard)
3 - 4 Not Required
4 - 5 Not Required
X24
1 - 2 RAM enable (standard)
2 - 3 EPROM enable (not required)
3 - 4 RAM enable (standard)
4 - 5 EPROM enable (not required)
CAP IN
FIN AUX
7-72 s7-c3d.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 3 - UPS Logic Board (4550007 H)
X251 - 2 Manual reset of output buffers
2 - 3 Microprocessor reset of output buffers (standard)
X26
1 - 2
Open (Standard)Auto-transfer mode enabled (“on-line” operation).Automatic load transfer from bypass to inverter when the inverter is available – i.e. the inverter is the preferred supply source.ClosedManual-transfer mode enabled (“off-line” operation).Automatic load transfer from bypass to inverter only when the bypass is unavailable – i.e. the bypass is the preferred supply source. Note: there will be a 3-cycle break on trans-fer to inverter.
3 - 4
Open“Inverter voltage fail lockout monitor” disabled.Closed (Standard)“Inverter voltage fail lockout monitor” enabled. i.e. The inverter is given 5 seconds to reach nominal voltage other-wise it is latched OFF.
5 - 6
Open (Standard)Enables the “Event History” monitor to store up to a maxi-mum of 10 alarms.ClosedResets the “Event History” monitor. Note: After the 10th “event”, the monitor buffer is full an cannot store any further “events”. The buffer should be reset to 0 after each mainte-nance or commissioning to enable new “events” to be cap-tured.
7 - 8
Open (Standard)Password protection enabledClosedPassword protection disabled
X28OPEN Power up reset enabled (standard)
CLOSED Power up reset disabled
X29OPEN 2.5V power supply monitor enabled (standard)
1 - 2 2.5V power supply monitor disabled
X31OPEN Internal battery disabled
1 - 2 Internal battery installed and charger enabled (standard)
X32OPEN RS485 port disabled
1 - 2 RS485 port enabled (standard)
X331 - 2 Calendar IC supply from VRAM (Standard)
2 - 3 Calendar IC supply from internal battery
X341 - 2 G.V.C.O. to inverter logic = parallel module
2 - 3 Micro V.C.O. to inverter logic = single module
JumperLink
Position Function
s7-c3d.fm5 - Issue 2 Dated 21/08/97 7-73
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 3 - UPS Logic Board (4550007 H)
Table 7-9: UPS Logic Board potentiometer adjustment
Table 7-10: UPS Logic Board LED indication
X351 - 2 Separate battery per module (parallel system)
2 - 3 Common battery (parallel system)
X361 - 2 Separate battery per module (parallel system)
2 - 3 Common battery (parallel system)
Potentiometer Function
R209 5 volt reference adjustment. Check at X20 pin 1
R212 2.5 volt reference adjustment. Check at anode of V45
LED Colour Function
H1 Red Internal battery charger operating
JumperLink
Position Function
7-74 s7-c3d.fm5 - Issue 2 Dated 21/08/97
Section 20: UPS System Control
Chapter 4 - UPS Logic Board (4550004 E)
4.1 Chapter overview
This chapter contains a circuit description of the UPS Logic Board used across thewhole 7200 Series UPS model range, and should be read in conjunction with cir-cuit diagram SE-4550004-E (7 pages).
Signal annotations shown on the circuit diagrams are shown in italics in the fol-lowing text – e.g. [CLKOUT>.
4.2 General description
4.2.1 Circuit board functions
Figure 20-16: UPS Logic Board connections
The position of the UPS Logic Board with respect to the other control boardsplaces it at the heart of the UPS control operation and its functional responsibili-ties can be broadly summarised as follows:
• Motherboard –One of the most basic functions provided by the UPS Logic Board is to actas a ‘motherboard’ for signals travelling directly between any of the othercircuit boards connected to it: e.g. the input voltage sense signals passesdirectly from the High Voltage Interface Board to the Rectifier LogicBoard.
• System control –The UPS Logic Board contains a microprocessor-based control systemwhich reads various status signals derived on the other circuit boards and
UPS Logic Board
RectifierLogic Board
InverterLogic Board
Static SwitchDriver Board
I/face BoardHigh Voltage
ParallelControlLogic
X1
X2
X3
X4
X5
X6
X7
X8
Logic BoardOperator
Alarm OptionsExternal
X1
X2 X4 X13
X2 X9X1 OperatorControlPanel
s7c3aOLD.fm - Issue 2 Dated 21/08/97 20-371
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
produces several ‘system’ control logic signals: e.g. ‘stop/start’ signals tothe Rectifier/Inverter Logic Boards, and ‘transfer command’ signals to theStatic Switch Interface Board.
• Alarms control –The UPS Logic Board acts as an assembly point for alarm signals gener-ated on the various other boards, together with those generated on the UPSLogic Board itself, and controls their distribution to the Operator ControlPanel and External Alarms Options under microprocessor supervision.
• Operator programming interface –The UPS Logic Board microprocessor enforces the programmable systemoperating parameters selected by the operator, via the Operator LogicBoard, onto the ‘system’ control logic
• Static Switch transfer control –The UPS Logic Board contains decision-making logic which controls theload transfer events between the inverter and static bypass supplies.
4.2.2 Input/Output connections
The UPS Logic Board has eight connectors (See Figure 20-16) whose connec-tions are summarised below.
• X1 – System control and monitoring signals to/from the Rectifier Board4520074-A (See Table 20-11).
• X2 – System control and monitoring signals to/from the High VoltageInterface Board 4590054-O (See Table 20-12).
• X3 – System control and monitoring signals to/from the Inverter LogicBoard 4530024-S (See Table 20-13).
• X4 – Power supply to Operator Logic Board 4550005-F (see circuit dia-gram sheet 7).
• X5 – System control and monitoring signals to/from the Static SwitchDriver Board 4542041-X (See Table 20-14).
• X6 – Data/logic to/from Operator Logic Board 4550005-F (see circuit dia-gram sheet 7).
• X7 – Used in multi-module parallel operating systems only.• X8 – Alarm outputs to optional external (remote) alarm display boards
(see relevant external alarm interface board in the Options section of thismanual).
20-372 s7c3aOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
Table 20-11: Connector X1 (To Rectifier Logic Board)
PIN I/O Function
1-4 I 0V – ground reference for digital electronics
5-8 I +12V power supply derived from AC-DC Power Supply Board
9-12 I -12V power supply derived from AC-DC Power Supply Board
13-14 I/O Common – ground reference for analogue sense signals
15 O VREC_AC: Input mains voltage sense signal (phases U-W) – through connection from HVI Board – (15Vp-p)
16 O VREC_BA: Input mains voltage sense signal (phases V-U) – through connection from HVI Board – (15Vp-p)
17 O VREC_CB:Input mains voltage sense signal (phases W-V) – through connection from HVI Board – (15Vp-p)
18 O IB: Battery current sense signal – through connection from HVI Board – battery current limit control
19 – Not used in standard modules
20 O IREC: Rectifier input current sense signal – through connection from HVI Board – input current limit control
21-23 – Not used in standard modules
24 I IREC_T: Used in parallel systems only (not available)
25 O VB: DC Bus (battery) voltage feedback – through connection from HVI Board (-3.225Vdc @446V DC Bus)
26 O T_BAT: Battery cabinet temperature sensor – through connection from HVI Board (2.98V @ 25°C)
27 O IDC_1: Not used in standard model (12 pulse rectifier only)
28 O IDC_2: Not used in standard model (12 pulse rectifier only)
29 O DB: Used in parallel systems only (input current sharing)
30 O DB_0: Used in parallel systems only (input current sharing)
31 – Not used in standard modules
32 I OVLREC: Rectifier overload error status (Overload = 1)
33 I BLKREC: Rectifier OFF/ON status (OFF = 1, ON = 0)
34 I SEQREC: Input mains phase sequence error status (Error = 1)
35 I IN_LOW: Low input volts 20% error status (Error = 1)
36 O ON_REC: Rectifier Run(1)/Stop(0) command from UPSLB micro
37 O XRADD_1: Reduced current limit from UPSLB micro (On Gen = 1)
38 O REC_A: Charge mode selection from UPSLB micro
39 O REC_B: Charge mode selection from UPSLB micro
40 – Not used in standard modules
s7c3aOLD.fm - Issue 2 Dated 21/08/97 20-373
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
Table 20-12: Connector X2 (To High Voltage Interface Board)
PIN I/O Function
1-4 – 0V – ground reference for digital electronics
5-8 O +12V supply to HVI Board
9-12 O -12V supply to HVI Board
13-14 – Common – ground reference for analogue sense signals
15-17 I VI-A, VI-B, VI-C: Bypass sense voltages for U-V-W phases respectively. Approximately 1% of bypass L-N voltage
18-20 I VINV-A, VINV-B, VINV-C: Inverter sense voltages for U-V-W phases. Approximately 1% of inverter L-N voltage (8Vp-p)
21-23 I VO-A, VO-B, VO-C: UPS output sense voltages for U-V-W phases respectively. Approximately 1% of UPS output L-N voltage (8Vp-p)
24-26 I VREC-AC, VREC-BA, VREC-CB: Input mains sense voltages. Approximately 1.3% of input L-L voltage – e.g. approx. range 5V - 5.5V (15Vp-p) for 380-415V nominal input
27 I V-B: DC Bus (Battery) volts sense signal. Approximately 0.7% of the DC Bus voltage (+3.225Vdc @446V DC Bus)
28-30 I IINV-A, IINV-A, IINV-C: Inverter current sense (150% phaseback)
31 I I-B: Battery current sense signal (Batt I limit and current display)
32-34 I IO-A, IO-B, IO-C: Output current – O/load alarm/timer/display
35 I IREC-1: Input current sense signal (dc)
36-42 – Not used in standard modules
43 I SW-REC: Rectifier Input Switch auxiliary contact status
44 I SW-IN: Static Bypass Switch auxiliary contact status
45 I SW-BYP: Maintenance Bypass Switch auxiliary contact status
46 I SW-OUT: Output Switch auxiliary contact status
47 – Not used in standard modules
48 I FUSINV: Inverter fuse monitor (not used in standard module)
49 I FUSREC: Rectifier fuse monitor (not used in standard module)
50 I FUSBAT: Battery fuse monitor
51 I TH: Inverter thermostat contact status
52 I ESD: Emergency shutdown
53 I SW-BAT: Battery isolator auxiliary contact status
54 O BATTRP: Battery isolator trip signal
55-56 – Not used in standard modules
57-60 I T1, T2, T3, T4: Temperature sensing monitoring signals
20-374 s7c3aOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
Table 20-13: Connector X3 (Inverter Logic Board)
PIN I/O Function
1 - 4 I 0V power supply rail
5 - 8 I +12V power supply derived from DC-DC Power Supply Board
9 - 12 I -12V power supply derived from DC-DC Power Supply Board
13 – Common
14 – Common
15-17 O [VI-A>, [VI-B>, [VI-C>: Bypass volts sense signals – through connection from HVI Board
18-20 O [VIN-A>, [VIN-B>, [VIN-C>: Inverter volts sense signals – through connection from HVI Board
21-23 O [IINV_A>, [IINV_B>, [IINV_C>: Inverter current sense signals – through connection from HVI Board
24 O [XINVOI>: Mains error – load transfer to inverter (H)
25 O [DREF>: Output voltage adjustment - used in parallel modules
26 O [DREF0>: Output voltage adjustment - used in parallel modules
27-30 O [DV-A>, [DV-B>, [DV-C>, [DV-0>: Load sharing signals used for parallel modules only
31 O [INV-L>: Transfer load to inverter command from processor system
32 I [OVL-INV>: Inverter overload status to processor system (OVL = L)
33 I [BLK-INV>: Inverter On/Off status to processor system (Off = H)
34 I [BACK>: Sync signal back to processor system (Sync pulse train)
35 O [SYNC>: Produced by processor system (Sync pulse train)
36 O [ON-INV>: Inverter On/Off control from processor system (Off = L)
37 O [INV-F>: from processor system (Inv Freq)
38-39 O [INV_A>, [INV_B>: from processor system - used in output volts selection
40 I Inverter thermostat status signals (optional)
s7c3aOLD.fm - Issue 2 Dated 21/08/97 20-375
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
Table 20-14: Connector X5 (Static Switch Driver Board)
PIN I/O Function
1 - 4 O 0V power supply rail
5 - 8 O +12V power supply rail
9 - 12 O -12V power supply rail
13 I XSTAI1: Not used in standard module. Details required as to what is connected to SSDB connector X7
14 I XSTAI2: Output contactor (inverter output) auxiliary contact status– low = contactor closed
15-16 O INV-L: Transfer load to inverter command from processor system
17-18 O MNS-L: Transfer load to bypass command from processor system
19 – XSTAD1: Not used in standard module.
20 – XSTAD2: Not used in standard module.
20-376 s7c3aOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
4.2.3 Block Diagram
Figure 20-17: UPS Logic Board basic block diagram
Re
set
Pow
erX
28
20
MH
zC
lock
RA
M
An
alo
gu
e S
ign
al
Ou
tpu
tB
uff
er
P5
P1
P4
P0
An
alo
gu
eB
uff
erin
g
MU
XD
43
D4
8D
49
EP
RO
MC
S
Addre
ss X
Inp
ut
Bu
ffe
r
Dat
a X
P2
CA
NIn
terf
ace
P3
Con
trol
Dat
a
Ou
tpu
tD
isp
lay
X1
X2
X3
X5
X7
X8
Re
ctifi
er
Lo
gic
Bd
H.V
.I B
oa
rd
Inve
rte
rL
og
ic B
d
SB
S B
oa
rd
Pa
ralle
lL
og
ic
Ala
rmB
oa
rd
D2
2
D2
3In
vert
er
Ru
n
Re
ctifi
er
Ru
n
S1O
n I
nve
rte
rIn
vert
er
con
tact
or
con
tro
l
S2
S3
S5
Re
set
Byp
ass
On
/Off
Inve
rte
r O
n/O
ffR
ect
ifie
r O
n/O
ff
On
Byp
ass
Byp
ass
SC
R c
on
tro
lO
N
OF
F
ON
OF
F
A/D
Co
nve
rte
rs
ON
OF
F
ON
OF
F
s7c3aOLD.fm - Issue 2 Dated 21/08/97 20-377
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
4.2.3.1 System overview
Processor system
The UPS Logic Board control system is based on a type 80C166 microcontroller,as shown in Figure 20-17. This device contains six ports through which it com-municates with peripheral circuits/devices, together with several ‘system controllines’. It also contains an internal A/D converter, four programmable timers andinternal ROM & RAM.
The ports are configured by an initialisation routine performed by the system soft-ware on power-up and can be summarised as follows.
• Port 0This port is configured as a 16-bit bi-directional data bus <D0...D15>
• Port 1This port is configured as the first 16-bits of an 18-bit address bus<A0...A15> the other two address lines are provided by port 4.
• Port 2The lower half of this port <P2-0...P2-7> carries various synchronising/tim-ing signals and the upper half <P2-8...P2-15> comprises the CAN data bus,which carries the data to/from the Operator Logic Board
• Port 3This 16-bit port is configured as a mixture of inputs and outputs generallyconcerned with controlling the CAN Bus data exchange.
• Port 4The lower two lines only are utilised on port 4. These form the upper twoaddress lines <A16...A17> the lower address lines <A0...A15> are providedby port 1.
• Port 5The lower ten lines of this port <P5-0...P5-9> are configured to act as inputsto the internal A/D converter.
• System control linesIn addition to the I/O ports the microcontroller also has the general controlI/O lines normally associated with a microprocessor-based system; suchas a system clock, reset, and Read/Write control.
Memory
The microcontroller uses both internal and external memory. 2 X 126k of battery-backed RAM and 2 X 516k of EPROM are fitted to the board as standard whichholds the system operating software. Facilities are included on the board to allowalternative memory configurations to be used as described later.
Data buffers
The 16-bit data bus is connected to various control circuit boards via input andoutput data buffers, as shown in Figure 20-17, which are controlled by individual‘chip select’ enable lines to direct the data flow to/from the appropriate source, asrequired by the system control software.
Analogue signal processing
The microcontroller monitors various analogue signals which are connected tothe UPS Logic Board from the peripheral boards. These signals are processed bysuitable analogue circuitry, buffered where necessary, and applied to the micro-controller’s A/D inputs via a series of multiplexer devices.
20-378 s7c3aOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
Primary output control signals
Although the micro-controller produces numerous control logic signals, its pri-mary outputs can be considered to be:
• Inverter Start/Stop Signal to the Inverter Logic Board which determines whether or not theinverter section is ‘enabled’ or ‘inhibited’.
• Rectifier Start/Stop Signal to the Rectifier Logic Board which determines whether or not therectifier section is ‘enabled’ or ‘inhibited’.
• Load on inverter Signal which controls the ‘inverter-side’ contactor (K1) and connects theinverter output to the load.
• Load on bypass Signal which controls the static switch and connects the load to the staticbypass supply.Note: the ‘load on inverter’ and ‘load on bypass’ signals are interlockedsuch that they cannot be activated simultaneously.
As shown on the block diagram, these signals are produced by a dedicated logicblock which is controlled by the data bus together with individual switches whichallow each of the above functions to be manually overridden.
Operator Interface
The microcontroller is connected to the Operator Logic Board via the CAN Bus,which is a bi-directional serial communications link that enables the operator toprogram several operational parameters into the micro-controller and also enablesvarious alarms and indications to be displayed on the Operator Control Panel.
s7c3aOLD.fm - Issue 2 Dated 21/08/97 20-379
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
4.3 Detailed circuit description
4.3.1 Introduction
The UPS Logic Board circuit diagram (SE-4540004-E) comprises 7 sheets. Withreference to the block diagram description (See Figure 20-17), the drawings canbroadly be described as follows:
• Sheet 1 contains a ‘signal map’ identifying the functions covered on theremaining pages. It also contains a summary chart detailing the variousconfiguration jumpers.
• Sheet 2 contains the– basic microcontroller system– data bus, address bus and control line buffers– Ni-Cad battery back-up controller– reset generator
• Sheet 3 contains the– system RAM and ROM memory and its associated configuration links– Inverter/Rectifier Start/Stop control logic– load transfer control logic– CAN bus communications drivers and control logic– Real-time clock (RTC)
• Sheet 4 contains the– data bus input buffers– data bus output buffers– on-board 7-segment indication circuit
• Sheet 5 contains analogue signal processing circuits for the– input voltage sense signals– inverter voltage sense signals– DC (battery) bus voltage sense signal– Battery current sense signalit also contains reference voltage generators; power supply monitors; andinverter overvoltage and input overvoltage fault detection circuits.
• Sheet 6 contains analogue signal processing circuits for the– output voltage sense signals– output current sense signalsit also contains the analogue signal multiplexers (for the A/D inputs), out-put overvoltage and overcurrent fault detection circuits.
• Sheet 7 contains the– input/output signal identifications details– serial communications (RS485) driver and port
Note: On the diagrams, a ‘negative’ symbol at the end of a signal’s annotation in-dicates that the signal is ‘active low’ – e.g. [RD> = [RD->.
As with all micro-based system, the microcontroller’s operation is determined bythe program held in the system’s memory: and as this is hidden to the service en-gineer there is very little that can be done to ascertain that the board is workingcorrectly apart from checking the validity of its input and output signals, and othersignals generated on the board which are required by the central processor system.The following description deals with the board on this basis, and should providesufficient information to determine whether or not the board is functioning cor-rectly when it comes to troubleshooting. A full software description is beyond thescope of this manual.
20-380 s7c3aOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
4.3.2 Basic microcontroller system
(circuit diagram sheet 2)
Figure 20-18: Micro system control signals
Caution When monitoring the signals described in this section it is best done with controlpower only – i.e. with the UPS power sections shut down and the circuit boardslive via the control power supply. The signals entering the left of the above dia-gram are constant and can be monitored with a meter/oscilloscope; those shownon the right of the diagram are not constant and best monitored with a logic probe.The logic sequence/timing of these signals depend upon various circuit conditionsand cannot therefore be accurately defined; however, for field test purposes, thepresence of a ‘variable switching’ logic signal at these points would generally in-dicate that the basic processor control bus is serviceable and the system softwareis running.
Power supply
The microcontroller is powered from the general +5V rail which is provided by athree-terminal 5V regulator (N1) shown on diagram sheet 7.
System clock (XTAL1)
A dedicated crystal-controlled clock generator (E2) provides a system clocksignal which is connected to the microcontroller (D12) pin 20. This signal is a20MHz squarewave switching between +5V and 0V.
System reset (RSTIN)
On power-up, a 1 second logic low reset pulse, [RSTIN->, is applied to D42 pin 27from the ‘reset generator’ circuit. This can also be manually applied for trouble-shooting purposes by temporarily bridging jumper X28 (See paragraph 4.3.5).The [RSTIN-> pulse forces the processor to restart its operation from the beginningof its operating program which forces it to run through its initialisation routine.
Non-Maskable Interrupt (NMI)
When the input to D42 pin 29 (NMI) goes low it instructs the system software tointerrupt its present operation and execute a power-down routine to save criticaldata.
20
27
29
54
Power Supply
Clock
Reset
Power
Vref (+5V)
XTAL1
RSTIN
NMI
VAREF
96
97
25
92
READY
CLKOUT
ALE
BHE
Ready
Clock out
Address latch enable
Bus high enable
96
26
95
RSTOUT
RD
WR
Reset out
Read
Write
Fail
Co
ntro
l Bu
s
D42
s7c3aOLD.fm - Issue 2 Dated 21/08/97 20-381
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
The source of this input is determined by X17 which is normally ‘made’ 2-3 andselects the power failure detection circuit output [PFO> as the controlling signal –this circuit is shown on diagram sheet 5 (See paragraph 4.3.15.4).
Reference voltage (VAREF)
The input to D42 pin 54 (VAREF) is a +5V reference voltage used by the internalA/D converters to compute the digital values for all analogue signals – e.g volts/current/VA etc. An adjustable reference voltage generator (N45 pin 8) (See par-agraph 4.3.15.2), shown on diagram sheet 5, provides this input ([VREF>) via X20which is normally ‘made’ 1-2.
Clock out (CLKOUT)
This output is a 20MHz squarewave synchronised to the processor clock input andis used by the RAM/ROM memory address decoding logic D33 (See paragraph4.3.6) shown on the diagram sheet 3. This is to ensure that when the processorwishes to read from/write to memory the memory access is synchronised to theinternal microprocessor action – i.e. it ensures that the accessed memory addressis relevant to the current processor’s requirements.
Address latch enable (ALE)
This output goes high to enable the address bus to be latched into the RAM/ROMmemory address decoding logic D33 shown on the diagram sheet 3 – (See para-graph 4.3.6).
Bus high enable (BHE)
The logic state of this output indicates whether the processor is internally enablingits ‘high’ or ‘low’ byte data bus – i.e. it indicates if the micro wishes to read from(or write to) the lower byte (D0....D7) or the higher byte (D8....D15). [BHE-> islow when the high byte is being accessed, and vice versa, and is used by the RAM/ROM memory address decoding logic shown on the diagram sheet 3 – (See par-agraph 4.3.6).
Reset out (RSTOUT)
[RSTO-> is controlled by the reset input signal, [RSTIN->, and goes high while theinput rest signal is applied. This signal is synchronised to the system clock andreturns high an integral number of clock pulses after the input reset signal is re-moved. The [RSTO-> signal is used by the RAM/ROM memory address decodinglogic shown on the diagram sheet 3 (See paragraph 4.3.6); and a buffered version,[RSTOX->, is connected to the data bus output buffers as shown on diagram sheet4 via jumper X25 (2-3) – (See paragraph 4.3.12).
Ready (Ready)
This input, when low, inserts wait states in the processor’s operation; thus slowingit down. It is driven by the RAM/ROM memory address decoding logic shown onthe diagram sheet 3 – (See paragraph 4.3.6) – and holds off the processor’s oper-ation until the appropriate address latching has taken place, thus effectively ex-tending the read/write times when slower memory elements are being used.
Read (RD)
This output goes low when the processor wishes to read the data from the deviceor memory location currently addressed by the address bus.
20-382 s7c3aOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
Write (WR)
This output goes low when the processor wishes to write data to the device ormemory location currently addressed by the address bus.
s7c3aOLD.fm - Issue 2 Dated 21/08/97 20-383
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
4.3.3 Data bus, address bus and control bus buffers
(circuit diagram sheet 2).
Data bus buffer
Two type ACT245 octal bus transceivers (D32 & D36) are employed as bi-direc-tional protection buffers between the microcontroller (D0....D15) and the data bus(DX0....DX15). D32 buffers the ‘low’ byte (D0....D7) and D36 the ‘high’ byte;however both are controlled by a common data direction signal – i.e. the micro-controller’s [RD-> output – therefore the data direction of all 16 data bus lines arecontrolled by a single signal.
These devices are described in appendix A (See paragraph A.1).
When the microcontroller drives its [RD-> output low it sets the data directionthrough the buffers from B-to-A, which allows the data bus contents through tothe microcontroller’s data inputs. At other times, when [RD-> is high, data flowsthrough the buffers from A-to-B, allowing the micro to place data onto the databus, which can then be written to a peripheral circuit as required.
Address bus buffer
The address bus is also buffered by two ACT245 devices (D38 & D41) but, unlikethe data bus described above, in this case the data direction is fixed by connectingpin 1 of each device to a permanent +5V supply. Thus the address bus data alwaysflows through the devices in the A-to-B direction and used to select a memory lo-cation – the buffered address bus is annotated (AX0....AX17).Note: AX16 & AX17 are buffered by the control bus buffer described below.
Control bus buffer
The control bus signals [RD->, [WR->, [BHE->, [RSTO-> are all buffered by D47.This device is configured with fixed data direction A-to-B, in the same manner asthe address bus buffer described above, by the application of a fixed +5V supplyat D47 pin 1. The buffered control signals [RDX->, [WRX->, [BHEX->, [RSTOX-> areused by various circuits distributed throughout the circuit diagrams.
In all cases the above mentioned buffers have pull-up resistors connected to theirinput and output pins – e.g. resistor packs R307, R309 etc.
4.3.4 Ni-Cad Battery back-up controller
(circuit diagram sheet 2).
A 3.6V 280mAh Ni-Cad battery is fitted to the UPS Logic Board to back-up theRAM contents and maintain the RTC time-keeping operation when the UPS isturned OFF; when fully charged the battery offers a back-up period of up to 4 to5 months.
The charger circuit is activated by the [OUTBAT> signal which is produced by theprocessor via D25 pin 19 (diagram sheet 4). When [OUTBAT> goes high it turnson V152 which then turns on V151 to supply the battery charge current via ledH8, R32 and V73. The charge voltage is limited to 4.7V by zener V14.
Note: the battery can be disabled for shipping/storage by opening jumper X31.
The battery is connected to the RAM memory devices and Real Time Clockdevice – shown on diagram sheet 3 – via V32 and the battery supply annotated[VRAM>. Thus, if the board’s power supply is turned off (i.e. UPS fully powereddown) the programmable parameters held in RAM (e.g. kVA, working voltage
20-384 s7c3aOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
and frequency, battery charging parameters and display language) are main-tained; and the real-time clock keeps running. It is not therefore necessary to re-program these parameters following every start-up.
Note: Jumper X31 must be made in order to enable this function.
The [VBATT> output is not connected to other parts of the circuit, but it is moni-tored by the microcontroller’s analogue input [AN9> via D44, which is a quad an-alogue switch. [VBATT> is switched through D44 pin 2, by [FL-12> when it goeshigh; this is controlled by a ±12V supply rail monitor circuit (diagram sheet 5)which inhibits the [VBATT> sense signal if the ±12V power rails are invalid, thuspreventing an erroneous battery voltage fault being detected by the micro underthese conditions.
Note: the other three gates within D44 are not used and their inputs are tied to 0V.
[OUTBAT> signal details
The micro-controller monitors the NiCad battery voltage (3.6V nom) via AN9and its internal A/D converter (as described above) and turns on the Ni-Cadcharger, by driving the [OUTBAT> signal high, if the Ni-Cad voltage falls below2.8V. When the charger is active, the [BACK-UP BATTERY LOW] message is dis-played on the Operator Control Panel (alarm #76) and led H8 illuminates. Oncethe battery is recharged to 3.6V the charger is turned off by the [OUTBAT> signalreturning low and the alarm message is cancelled. Thus the Ni-Cad battery ischarged only when necessary and is not permanently trickle-charged.
Note: the NiCad charger may be active for several hours when the UPS is firstcommissioned (depending on the initial battery charge state) – jumper X31 mustbe fitted to ‘enable’ the battery back-up facility.
4.3.5 Reset generator
(circuit diagram sheet 2).
A purpose-designed Supply Voltage Supervisor (N24) provides the micro with a1 second sec logic low [RSTIN-> reset signal on power-up. This signal, which isapplied to the micro pin 27, can also be initiated manually by temporarily makingjumper X28 (1-2). The [RSTIN> signal also resets the RAM chip select signals pro-duced by D19a/d (shown on circuit diagram sheet 3) and points the micro to itsinitialisation routines.
Caution Using X28 to activate the reset circuit during normal UPS operation will crash theunit, because the ‘run’ signals to the rectifier, inverter and static switch will be dis-abled for the 1 second reset period.
On power-up (reset) the micro-controller receives initialisation data from D20which is an EEPROM used to store the Emerson/Liebert/SICE software passportidentification. Amongst other things this configures the micro’s programmableports P0-P5 to the parameters required to operate in this application. Without thissecurity interlock the micro-controller will be inactive. An inverse output, [V-
AUX>, goes high on reset and is connected to D22 and D23 in the ‘Inverter/Recti-fier Start/Stop control logic’ and ‘Load transfer control logic’ (circuit diagramsheet 3). This resets the logic latches (Emergency Stop, DC Overvolts, etc.) andre-applies the ‘run’ signals to the rectifier, inverter and static switch.
Note: the reset time is determined by R157/C97, and begins when the +5V supplyrail reaches 3.6V on initial power-up.
s7c3aOLD.fm - Issue 2 Dated 21/08/97 20-385
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
4.3.6 System RAM and ROM memory addressing
(circuit diagram sheet 3).
The system memory comprises 2 x 512k EPROMs (D35 & D46) and 2 x 128kRAM chips (D28 & D40). All these devices have an 8-bit data bus output; how-ever, the EPROMs have a 16-bit address input while the RAM chips have a 17-bit address facility.
Random Access memory (RAM)
This is the read/write memory store; sometimes referred to as the temporarystore. Any data fed in from the peripheral devices or produced during the execu-tion of the main program will be temporarily held in RAM – e.g. UPS setup pa-rameters such as kVA, nominal voltages/frequency, serial number, passwords,etc. This is a ‘volatile’ location, meaning that when power is lost to the componentall data is also lost; thus the need for the on-board back-up Ni-Cad battery.
Read Only Memory (ROM)
This memory contains the ‘operating system program’, or firmware, which is ba-sically a sequence of instructions to be carried out by the micro-controller in orderto make it perform the actions required of it. Upon power-up the micro is pointedto the first instruction as part of its reset initialisation, and from then on it stepsthrough the programmed instructions in a sequence dictated by various events andmonitored conditions.
ROM is ‘non-volatile’, which means that it does not lose its memory contents inthe event of a loss of power.
Address decoding – D33 / D19
The ‘output enable’ pins of all four memory devices are controlled by the controlbus [RD-> line, therefore when this line goes low the processor can read the dataheld at the current address from any of the devices. The purpose of the ‘addressdecoding’ circuit is to enable the microcontroller to select which of the EPROMor RAM devices it wishes to communicate with at any given time. The memorydevices’ ‘chip select’ inputs are controlled by a circuit comprising an ASIC i.c.(D33) and two gates of D19.
D33’s inputs are connected to A0, A14....A17, and several control bus signals –as described in paragraph 4.3.2. – which are all controlled by the microcontroller.The output signals, [CSEP1L->, [CSEP1H->, [CSRA1L->, and [CSRA1H->, adopt logicstates determined directly by these processor-controlled inputs and are synchro-nised to the processor operation by the 20MHz [CLKOUT> signal.
When low, [CSEP1L-> and [CSEP1H-> enable the EPROM devices via their ‘chipenable’ inputs (pin 20), while [CSRA1L-> and [CSRA1H-> perform a similar func-tion on the RAM chips.
The [READY> output from D33 is fed back to the micro to inform it that the appro-priate addresses have been loaded into D33’s internal latches (See paragraph4.3.2).
As D19 provides the ‘chip select’ inputs to the RAM devices it is powered fromthe battery-backed RAM supply to prevent RAM data corruption on UPS powerdown.
Note: jumper X14 provides a test facility for bench testing only and all linksshould be open during normal operation.
20-386 s7c3aOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
AX15 & AX16 configuration links
The UPS Logic Board has been designed to facilitate future software upgrades byincluding configuration links to permit the addressing of alternative memory de-vices. These links affect the routing of the AX15 and AX16 address lines, and thestandard configuration is shown below in Figure 20-19.
In the standard configuration the signals annotated [PIN29EP> and [PIN3EP> areconnected to the EPROMs’ A14 and A15 inputs and are therefore driven by theAX15 and AX16 address lines respectively. The [PIN31RAM> signal (AX16) isconnected to the A15 input of both RAM devices and the [PIN3RAM> signal(AX15) is connected to the RAM ‘write enable’ inputs.
Figure 20-19: AX15 & AX16 decoding configuration links
1
2
3
1
2
3
1
2
3
1
2
3
5
4
3
5
4
3
2
1
2
1
X19 X13
X22 X21
X23 X24
[AX16>
[AX15>
[PIN29EP>
[PIN3EP>
[PIN31RAM>
[PIN3RAM>
[PIN29RAM>
[WRX–>
s7c3aOLD.fm - Issue 2 Dated 21/08/97 20-387
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
0
+
N1
N1
4.3.7 Basic system control logic
The term ‘Basic System Control Logic’ is used here to described the signals gen-erated by the UPS Logic Board which control the ‘start/stop’ commands to therectifier and inverter, the battery circuit breaker ‘trip’ control, and the ‘load trans-fer’ control between inverter and static bypass.
These functions are controlled by two ASICs annotated D22 and D23 which areshown on sheet 3 of the diagram and also in greater detail in Figure 20-20 below.
Figure 20-20: Basic system control logic (internal detail)
4.3.7.1 D22 Functional description
D22 provides four status signals which are used by D23 and are also monitoredby the microcontroller via the data bus input buffers.
123
4
56
7
8
9
11
13
14
1234
8
9
11
5
6
7
1314
17
16
15
12
D22
M_ESD
MSCROP
M_BAT_MA
BLK_MAINS
ALARMS_RESV-AUX
M_RESET
ESD
M-ESDSCR_OPN
MNS_L
MSCROP
BAT_MA
M_BAT_MA
SEQ_MAINS
BLK_BYP
12
15
16
17
19
D23
D21-2
M_BAT_MA
IB_OPEN
V-AUX
M_ESD
RST_OUT
L_INV
L_MAINS
BLK_INV_M
INV_ON
BLK_MAINS
BLK_REC_M
REC_ON
BAT_TRP
ON_INV
INV_L
MNS_L
ON_REC
0V
V
5V
N24-6
5-14
5-8
0V
Z39
R86
R97
D34-12
D26-7
D21-16
D21-5
D21-6
D21-9
D21-12
D21-15
X2-54
X3-36
X5-31
X5-17
X1-36
X5-16
D26-3
D26-6
D26-4
D26-5
Q3Q2S1Q1
R1
10
R1
06
R1
54
R1
09
BlockRectifier
BlockInverter
ManualRESET
BlockBypass
R1
13
R1
11
R1
12
C6
3
C6
2
C64
20-388 s7c3aOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
Emergency shutdown [ESD>
The ‘emergency shutdown’ signal [ESD> to D22-4 is driven by external circuitryand connected via X2-52 (sheet 7) as a logic high when the emergency shutdownis applied. When D22 pin 4 goes high it drives pin 17 high which then provides alatching input back to D22 pin 5 which holds pin 17 high until the reset circuit isactivated – the latching signal is debounced by R112/C63. D22 pin 5 also turnsoff the bypass enable signal via D22 pin 12 – i.e. turns off the bypass SCRs.
In addition to providing the latching function, the ‘high’ output from D22-17,[M_ESD>, is fed to the microcontroller via data bus buffer D26-5 to initiate alarm#63 [CUT-OFF: EMERGENCY] (See paragraph 4.3.11.4) and it is also connectedto D23-4 where it:
• Trips the battery circuit breaker ([BAT_TRP> = 0)• Turns Off (stops) the rectifier ([ON_INV> = 0)• Turns Off (stops) the inverter ([REC> = 0)
Static switch SCR open
The ‘static switch SCR open’ signal [SCROPN> to D22-6 is produced by N15-8 orN5-14 (sheet 6) as a logic high when the detection circuits ‘sees’ a voltage dropacross one of the static bypass SCRs. When D22 pin 6 goes high it drives pin 16high (provided the ‘load on mains’ input to D22-7 is also high) which then pro-vides a latching input back to D22 pin 8. This inhibits the output on pin 12 andholds pin 16 high until the reset circuit is activated – the latching signal is de-bounced by R111/C62. Thus [SCROPN> will block the bypass only when the loadis ‘on-bypass’.
In addition to providing the latching function, the ‘high’ output from D22-16,[MSCROP>, is fed to the microcontroller via the data bus buffer D26-4 (See para-graph 4.3.11.4) where it annunciates alarm #15 [I/P: SCR CUT OFF].
DC Overvoltage – fast
The ‘DC Fast Overvoltage’ signal [BAT_MA> to D22-9 is driven by N13-8 (sheet5) and is logic high when a DC busbar (battery) overvoltage condition (>620V) ispresent. When D22 pin 9 goes high it drives pin 15 high which then provides alatching input back to D22 pin 11 which holds pin 15 high until the reset circuitis activated – the latching signal is debounced by R113/C64.
In addition to providing the latching function the ‘high’ output from D22-15,[MBATMA>, is fed to the microcontroller via the data bus buffer U26-6 to initiatealarm #58 [DC BUS: FAST OVERV.] (See paragraph 4.3.11.4) and it is also con-nected to D23-1 where it:
• Trips the battery circuit breaker ([BAT_TRP> = 0)• Turns Off (stops) the rectifier ([ON_INV> = 0)• Turns Off (stops) the inverter ([REC> = 0)
Static bypass inhibit
The [BLKMNS> output from D22 pin 12 goes high when D22 detects any conditionwhich requires the load to be prevented from being connected to the static bypasssupply. This output is fed to the microcontroller via the data bus buffer U26-3 toinitiate alarm #17 [BYPASS INHIBIT REM.] (See paragraph 4.3.11.4) and is alsoconnected to D23-7 where, when ‘high’, it inhibits the ‘load-on-bypass’ com-mand [MNS_L> output from D23 pin 17.
The [BLKMNS> signal can be driven high by any of the following conditions:
s7c3aOLD.fm - Issue 2 Dated 21/08/97 20-389
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
• ‘Emergency shutdown’ latch set (D22-5 = high)• ‘Bypass SCR open’ latch set (D22-8 = high)• 1 second Power-up reset pulse (D22-5 = positive-going pulse)• Static bypass mains phase sequence error (D22-13 = high) from D27 on
diagram sheet 5 • ‘Manual block’ applied from switch Q1 (D22-14 = high)
RESET
There are three reset signal sources applied to D22:
• D22-1 receives a logic high reset signal from the microcontroller via thedata bus output buffer D21-2 (See paragraph 4.3.12.5). This is a softwarereset programmable via the Operator Control Board
• D22-2 receives a logic high reset pulse when the board is powered up (Seeparagraph 4.3.5)
• D22-3 is driven high when the manual reset button (S1) is pressed
The ‘Emergency shutdown’, ‘Bypass SCR open’ and ‘DC overvoltage’ latchesdescribed above are all reset when any one of the three reset inputs are active.
Note: the ‘power-up’ reset signal to D22-2 also resets the [BLKMNS> output fromD22-12, described immediately above.
4.3.7.2 D23 Functional description
D23 provides five major control signals, as detailed below:
Battery circuit breaker trip
A logic low [BATTRP> output from D23-12 trips the battery circuit breaker viaX2-54 (sheet 7), which is connected to the High Voltage Interface Board (See sec-tion 7 paragraph 2.3.8). This signal can be driven low by any of the followingD23 inputs:
• ‘DC Fast Overvoltage’ to D23-1 ([MBATMA> = 1) from D22-15 (see above)• ‘Emergency shutdown’ to D23-4 ([MSDD> = 1) from D22-17 (see above)• ‘Power-up reset’ to D23-3 (see above)• ‘Software trip’ to D23-2 – [IBOPEN> generated by the microcontroller and
connected via the data bus output buffer D21-16 (See paragraph 4.3.12.5).Note: This signal trips the battery breaker on low DC voltage as follows:– UPS on less than 15% load = 330V– UPS on greater than 15% load = 360VThe low voltage trip is programmable via the Operator Control Panel Set-Up parameters, and is adjustable between 1.6V/cell and 1.69V/cell. The30Volt window at the 15% level is not adjustable.
Inverter Start/Stop (On/Off)
The [ON-INV> output from D23-15 is connected to the Inverter Logic Board viaX3-36 (sheet 7) where it controls the inverter ‘Start/Stop’ status. A logic low[ON-INV> signal commands the inverter to ‘Stop’ and can be effected by any oneof the following D23 inputs (conversely, all the following inputs must be in their‘healthy’ low state in order for the inverter to run):
• ‘DC fast overvoltage’ (>620V) to D23-1 – ([MBATMA> = 1) from D22-15(see above)
• ‘Emergency shutdown’ to D23-4 – ([MSDD> = 1) from D22-17 (see above)• ‘Power-up reset’ to D23-3 (see above)
20-390 s7c3aOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
• ‘Software control’ to D23-6 – [INV-ON> generated by the microcontrollerand connected via the data bus output buffer D21-6 (See paragraph4.3.12.5). This signal is ‘low’ to inhibit the inverter and ‘high’ to enable it.When this signal is actively blocking the inverter (i.e. low) it initiatesalarm #31 [INVERTER: OFF REM.].
• ‘Manual inverter block’ to D23-5 – logic high from the manual inverterinhibit switch Q2. If the [ON-INV> signal at D23 pin 5 is active (low),blocking the inverter, alarm #30 [INVERTER: OFF] will be active. Notethat alarm #31 will be disabled if alarm #30 is active. Alarm #31 can beinterpreted that the inverter has been selected off, while alarm #30 sug-gests that the inverter has been turned off for some other reason.
Rectifier Start/Stop (On/Off)
The [ON-REC> output from D23-19 is connected to the Rectifier Logic Board viaX1-36 (sheet 7) where it controls the rectifier ‘Start/Stop’ status. A logic low[ON-REC> signal turns OFF the rectifier and can be effected by any one of the fol-lowing D23 inputs (conversely, all the following inputs must be in their “healthy”state in order for the rectifier to run):
• ‘DC Fast Overvoltage’ (>620V) to D23-1 – ([MBATMA> = 1) from D22-15(see above)
• ‘Emergency shutdown’ to D23-4 – ([MSDD> = 1) from D22-17 (see above)• ‘Power-up reset’ to D23-3 (see above)• ‘Software control’ to D23-14 – [REC-ON> generated by the microcontrol-
ler and connected via the data bus output buffer D21-12 (See paragraph4.3.12.5) this signal is ‘low’ to inhibit the rectifier and ‘high’ to enable it.When this signal is actively blocking the rectifier (i.e. low) it initiatesalarm #20 [RECTIFIER: OFF].
• ‘Manual rectifier block’ to D23-13 – logic high from the manual rectifierinhibit switch S2. If the [ON-REC> signal at D23 pin 19 is active (low),blocking the rectifier, alarm #22 [RECTIFIER: BLOCK] will be active.Note that this will be disabled if alarm #21 is active. Alarm #21 can beinterpreted that the rectifier has been selected off via the Operator ControlPanel, while alarm #22 suggests that the rectifier has been turned off forsome other reason
Load transfer control
The transfer control logic within D23 is interlocked such that the ‘load on invert-er’ [INV_L> and ‘load-on-bypass’ [MNS_L> commands are mutually exclusive.
[INV-L>: This output, from D23-16, goes high to transfer the load to the invert-er and is connected to the Static Switch Driver Board via X5-15 (sheet 7), whereit turns off the static switch (disconnecting the load from the bypass supply) andenergises the ‘inverter-side’ contactor (K1) driver circuit.
It is also connected to the Inverter Logic Board, via X3-31 where it triggers thelatches within D11 which makes the inverter voltage track the bypass supply volt-age for 100ms (See section 18 paragraph 3.3.3). This is done to provide a smoothtransfer from bypass to inverter and reduce the wear on the ‘inverter-side’ contac-tor (K1).
In order for D23 pin 16 to go high, D23 requires pin 8 ([RSTOUT>) to be low andpin 9 ([L-INV>) high. Both these signals are produced by the microcontroller andconnected to D23 via the data bus output buffer D21 (See paragraph 4.3.12.5).
s7c3aOLD.fm - Issue 2 Dated 21/08/97 20-391
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
[RSTOUT> is a 1 second hold-off command issued by the microcontroller when itis performing its initialisation checks during power-up; and [L-INV> is the ‘trans-fer-load-to-inverter’ command issued when all its software-controlled parametershave been verified (e.g. Inverter voltage OK, Sync OK etc.).
[MNS-L>: This output, from D23-17, goes high to transfer the load to thebypass and is connected to the Static Switch Driver Board via X5-17 (sheet 7),where it turns on the static switch driver circuit, connecting the load to the bypasssupply. It is also connected to D22-7 where (when low) it disables the ‘bypassSCR open’ input to D22-6 when the load is not connected to the bypass supply.
In order for D23 pin 17 to go high D23 requires:
• pin 7 to be low (i.e. no [BLKMNS> from D22)
AND• either pin 8 [RSTOUT> to be high – not requesting ‘load-on-inverter’
ORpin 11 ([L-MNS>) high – requesting ‘load-on-bypass’.
The signals to pins 8 and 11 are produced by the microcontroller and connectedto D23 via the data bus output buffer D21 (See paragraph 4.3.12.5). [RSTOUT> isa 1 second hold-off command issued by the microcontroller when it is performingits initialisation checks during power-up; and [L-MAINS> is the “transfer-load-to-bypass” command issued when all its software-controlled parameters have beenverified for appropriate action (e.g. Critical bus volts not OK, overload, bypassvolts OK etc.).
4.3.8 CAN bus communications drivers and control logic
(circuit diagram sheet 3).
The CAN bus communications system is described in paragraph 5.3.9. (OperatorLogic Board).
4.3.9 Real-time clock (RTC)
(circuit diagram sheet 3)
The MC68698 (D18) is a peripheral device which contains a real-time clock/cal-endar, a 32 x 8 bit static RAM, and a synchronous, serial, three-wire interface forcommunicating with the micro-controller. As it’s title suggests, the real timeclock accurately counts seconds, minutes, hours (AM/PM), Day-of-the week,date, month and year (including auto-incrementing leap-year). In the UPS LogicBoard application it provides ‘date stamping’ to the Operator Control Panel mes-sages and ‘service data’ as entered via the Maintenance Menu Screen (see para-graph 2.4.6.3 on page 2-40). The device operates from the Ni-Cad back-upbattery to maintain its time-keeping function and prevent data loss when the gen-eral +5V control power is turned off. It also contains many other circuit functions,such as an alarm facility, watchdog timer etc. which are not used in this applica-tion but may be mentioned briefly in the following description.
Power supply details
D18 is powered from the Ni-Cad-backed [VRAM> supply which is available at alltimes provided jumper X31 is made 1-2 (See paragraph 4.3.4). This supply isconnected to pin 16 (Vcc), pin 13 (Vbatt) and also, via an R-C delay circuit(R1087/C54), to pin 10 (POR). The general +5V control power rail is also moni-tored by the device at pin 12 (VSYS).
20-392 s7c3aOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
The delayed input to pin 10 is seen as a Power On Reset (POR) and resets thedevice by briefly holding pin 10 low while the device is powered-up. Note that asthe battery-backed supply is present at all times, this is effectively a ‘once-only’reset that takes place when X13 is initially made (i.e. battery connected) and is notaffected by subsequent application/removal of the UPS Logic Board’s +5V con-trol power supply.
The board’s +5V supply rail is monitored at D18 pin 12; and when the voltage atthis pin is less than 0.7V above the Ni-Cad voltage (pin 16) the device switchesto a low-power standby mode whereby it maintains its time-keeping function butinternally inhibits the serial communication facilities with the micro-controller.This prevents the passage of invalid or spurious data while the micro-controller ispowering-down and so prevents RTC data corruption.
Clock control
The RTC’s internal timer operation can be controlled from one of two sources;i.e. either from an external crystal-controlled clock reference or a 50/60Hz mains-derived sinusoidal signal. In this particular application an external crystal is usedand the 50/60Hz input to pin 11 (LINE) is grounded via R107.
For crystal operation pins 14 and 15 are connected to a 32.768kHz, 1.048576kHz,2.097152kHz or 4.194304kHz crystal, as shown on the circuit diagram. A pro-grammable internal divider circuit enables the particular external clock frequencyto be scaled down to that used by the internal logic. The internal clock signal ismade available at pin 1 (CLKO) but in this particular application is not used, andremains unterminated.
Serial communications interface
Four lines, connected to pins 4 to 7, implement a bi-directional communicationsinterface with the micro-controller, and allow the micro to write configuration andcontrol data to the RTC and read the ‘time’ and register data. As described above,such communication is inhibited if the UPS Logic Board’s +5V power rail is un-available.
The [ORCS> input to pin 7 (SS) is seen as a ‘chip select’ input in this applicationand must be held high while either a read or write event is taking place. Data isinput (written) to the RTC by [ORDI> to pin 5; and output (read) from the deviceby [ORDO> from pin 7. In each case the data takes the form of a serial data streamclocked in/out by the ‘serial clock’ signal [ORSK> applied to pin 4. Note that allfour of these signals are under direct control of the micro-controller and appliedto the data bus via the buffers shown on diagram sheet 4.
Other connections
The functions connected to pin 2, pin 3 and pin 9 are not used in this particularapplication and these pins are tied to their default logic levels as shown.
s7c3aOLD.fm - Issue 2 Dated 21/08/97 20-393
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
Section 20:
4.3.10 Data bus buffers ‘chip select’ decoding
The data bus communicates with the peripheral circuits and devices via 16 octalbuffers which are selected in ‘pairs’ to provide a 16 bit data bus transfer. The mi-crocontroller selects a particular buffer-pair by appropriately addressing the ‘chipselect’ decoding circuit (D52) which then ‘enables’ the required buffers. Detailsof the digital signals handled by each buffer are provided in the following para-graphs.
Figure 20-21: Data bus buffer control (block diagram)
D8
D2
D1
D26
D51
D60
D17
D25
D9
D21
D50
D55
D7
D10
D54
D56
OE
OE[CSIN1->
OE
OE[CSIN2->
OE
OE[CSIN3->
CP
CP[CSDIS->
<CSOU1-]
<CSOU2-]
<CSOU3-]
<CSOU4-]
Microcontroller
DATABUS
[CSIN1->[CSIN2->[CSIN3->
[CSDIS->
[CSOU1->[CSOU2->[CSOU3->[CSOU4->
1213141516171819
123456789
AX11AX12AX13AX14AX15AX16AX17
[RDX->[WRX->
D52
Address Bus
Control Bus
CP
CP
CP
CP
CP
CP
CP
CP
20-394 s7c3bOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
4.3.11 Data bus input buffers
(diagram sheet 4).
Digital signals which are read by the microcontroller as part of its control functionare connected to the data bus via six type HCT 245 octal bus transceivers (See Ap-pendix A.1) which are accessed in pairs to provide a 16-bit data transfer (SeeFigure 20-21). The buffers ‘data direction’ pins are held permanently high, there-fore the data flow is fixed from ‘A-to-B’ in each device. ‘Chip select’ signals fromD52 are connected to the buffers ‘output enable’ pins which provides the meansfor the micro to select each pair of devices as required.
The remainder of this sub-section lists the digital signals connected to the data busthrough the bus input buffers, and provides signal details where appropriate.
4.3.11.1 Buffer D8 – activated by CSIN1
XRADT1
Source: Sheet 7 X1-31
Description: From the Power Rectifier overtemperature sensing device – thisinput is not normally used and is held permanently low by jumper X10 (1-2) onthe Rectifier Logic Board. If used, in an overtemperature situation this input ini-tiates alarm #24 [RECTIFIER: OVERTEMP.] and the rectifier and inverter areshut-down 1 minute later accompanied by alarm #62 [CUT-OFF: OVERTEMP].This alarm must be reset by pressing the manual reset push-button.
OVLREC
Source: Sheet 7 X1-32
Description: Rectifier Overload – this input goes high when the rectifier is op-erating in input current limit mode (H6 illuminated on the Rectifier Logic Board)– (See section 4 paragraph 2.3.4.2). This initiates alarm #23 [RECTIFIER: I/P LIMIT].
BLKREC
Source: Sheet 7 X1-33
Description: Rectifier Blocked – this input goes high when the Rectifier Logicboard is in its ‘stop’ mode (See section 4 paragraph 2.3.6). This can be due to theRectifier Logic Board detecting an internal fault or a ‘stop’ (block) commandissued by the UPS Logic Board (See paragraph 4.3.7.2).
The internal fault channel is triggered by either: incorrect phase rotation; Rectifi-er Logic Board power supply failure; or low input voltage (-20%). The externalfault channel initiated by the UPS Logic Board will be accompanied by alarm #21[RECTIFIER: OFF REM.] or alarm #22 [RECTIFIER: BLOCK] (See paragraph4.3.7.2).
SEQREC
Source: Sheet 7 X1-34
Description: Rectifier input phase sequence error – this input goes high whenthe Rectifier Logic board phase sequence monitor detects an error on the incom-ing 3 phase mains supply (H8 illuminated on the Rectifier Logic Board) (See sec-tion 4 paragraph 2.3.6.1).
s7c3bOLD.fm - Issue 2 Dated 21/08/97 20-395
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
IN-LOW
Source: Sheet 7 X1-35
Description: Rectifier input undervoltage – this input goes high when the Rec-tifier Logic board input voltage monitor detects a -20% undervoltage condition onthe incoming 3 phase mains supply (H9 illuminated on the Rectifier Logic Board)(See section 4 paragraph 2.3.6.2).
XATI1 / XATI2 / XATI3
Source: Sheet 7 X2-40 / 41 / 42
Description: Not used – no connection on High Voltage Interface Board.
4.3.11.2 Buffer D2 – activated by CSIN1
SW-REC
Source: Sheet 7 X2-43
Description: Rectifier input switch monitor – this input goes low when the rec-tifier input mains power switch is closed. This signal passes through the HighVoltage Interface Board (See section 7 paragraph 2.3.7). When the input switchis open, this signal initiates alarm #04 [RECTIF. BREAKER OPEN].
SW-IN
Source: Sheet 7 X2-44
Description: Static Bypass switch monitor – this input goes low when the StaticBypass mains power switch is closed. This signal passes through the High Volt-age Interface Board (See section 7 paragraph 2.3.7). When the bypass switch isopen, this signal initiates alarm #02 [BYPASS BREAKER OPEN].
SW-BYP
Source: Sheet 7 X2-45
Description: Maintenance Bypass switch monitor – this input goes low whenthe Maintenance Bypass switch is closed. This signal passes through the HighVoltage Interface Board (See section 7 paragraph 2.3.7). When the maintenancebypass switch is closed, this signal initiates alarm #06 [ON MANUAL BYPASS].
SW-OUT
Source: Sheet 7 X2-46
Description: Output switch monitor – this input goes low when the Outputswitch is closed. This signal passes through the High Voltage Interface Board(See section 7 paragraph 2.3.7). When the output switch is open, this signal ini-tiates alarm #03 [OUTPUT BREAKER OPEN].
FUSINV
Source: Sheet 7 X2-48
Description: Not used - held permanently low due to link fitted to connectorX16 on the High Voltage Interface Board (see main equipment wiring diagrams).If used, this input monitors the inverter fuse and on fuse failure initiates alarm #38[INVERTER: FUSE FAIL].
20-396 s7c3bOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
FUSREC
Source: Sheet 7 X2-49
Description: Not used - held permanently low due to link fitted to connectorX17 on the High Voltage Interface Board (see main equipment wiring diagrams).If used, this input monitors the rectifier (input) fuses and on fuse failure initiatesalarm #25 [RECTIFIER: FUSE FAIL].
FUSBAT
Source: Sheet 7 X2-50
Description: Battery fuse monitor – this input goes high if the battery fuse rup-tures (See section 7 paragraph 2.3.15). The fuse is detected by a micro-switch located on the fuse which, when activated,initiates alarm #57 [BATTERY: FUSE FAIL].
TH
Source: Sheet 7 X2-51
Description: Inverter thermostat monitor – this input goes high if an inverterthermostat opens (overtemperature > 90°C) (See section 7 paragraph 2.3.13). Inthe event of an overtemperature situation occurring, this input initiates alarm #34[INVERTER: OVERTEMP.] and the rectifier and inverter are shut-down 1 minutelater accompanied by alarm #62 [CUT-OFF: OVERTEMPER]. This alarm must bereset by pressing the manual reset push-button (S1).
4.3.11.3 Buffer D1 – activated by CSIN2
SW-BAT
Source: Sheet 7 X2-53
Description: Battery circuit breaker monitor – this input goes low when the Bat-tery switch (or contactor) is closed. This signal passes through the High VoltageInterface Board (See section 7 paragraph 2.3.7). When the battery switch is open,this signal initiates alarm #05 [BATTERY BREAKER OPEN].
OVLINV
Source: Sheet 7 X3-32
Description: Inverter Overload – this input goes high when the inverter is oper-ating in current limit mode (H14 illuminated on the Inverter Logic Board) – (Seesection 18 paragraph 3.3.7). In an Overload condition, this signal initiates alarm#33 [INVERTER: CURR.LIMIT].
BLKINV
Source: Sheet 7 X3-33
Description: Inverter Blocked – this input goes high when the Inverter LogicBoard is in its ‘stop’ mode (See section 18 paragraph 3.3.8). This can be due tothe Inverter Logic Board detecting an internal fault or a ‘stop’ (block) commandissued by the UPS Logic Board (See paragraph 4.3.7.2). The internal fault chan-nel is triggered by either: IGBT desaturation, ribbon cable disconnected, InverterLogic Board power failure. The external fault channel initiated by the UPS LogicBoard will be accompanied by alarm [#30], [#31] or [#32].
s7c3bOLD.fm - Issue 2 Dated 21/08/97 20-397
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
XINVI1
Source: Sheet 7 X3-40
Description: Not used – held permanently low due to X13 (2-3) on the InverterLogic Board which disables this alternative temperature sensor route. The activethermostat route is via [TH> described earlier.
XSTAI1
Source: Sheet 7 X5-13
Description: Not used – held permanently low due to X11 (1-2) on the StaticSwitch Driver Board. No thermostat is fitted on the heatsink.
XSTAT2
Source: Sheet 7 X5-14
Description: Inverter output contactor monitor – goes low when the inverteroutput contactor is closed (load on inverter) and is used by the transfer controllogic software routine.
LINK X12
Source: On-board jumper X12
Description: Not used.
4.3.11.4 Buffer D26 – activated by CSIN2
MRESET
Source: Sheet 3 – switch S1
Description: RESET switch – goes high when the on-board manual reset switch(S1) is pressed and is used by the micro to unlatch “block commands” issued bysome of its software routines.
BLKMNS
Source: Sheet 3 – D22 pin 12
Description: ‘Static Switch blocked’ monitor – this input goes high to informthe micro that the static switch control logic (on this Board) is inhibiting the staticswitch (alarm #16 [BYPASS INHIBIT]). This can be invoked by any of the follow-ing signals applied to D22 (See paragraph 4.3.7.1).
– static switch manual inhibit switch (Q1) closed– bypass phase sequence error detected– emergency shutdown operated (latched)– open circuit SCR (latched)– UPS Logic Board power supply failure
MSCROP
Source: Sheet 3 – D22 pin 16
Description: ‘Static Switch SCR open circuit’ monitor – this input goes high toinform the micro that an open circuit static switch SCR has been detected (on thisBoard) (alarm #15 [I/P: SCR CUT-OFF]). This signal is latched within D22 andmust be reset using S1 to return to normal conditions.
20-398 s7c3bOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
M-ESD
Source: Sheet 3 – D22 pin 17
Description: ‘Emergency shutdown’ monitor – this input goes high to informthe micro that an emergency shutdown (Emergency Stop) has been applied (Seeparagraph 4.3.7.1) (alarm [#63] [CUT-OFF: EMERGENCY]). This signal islatched within D22 and must be reset using S1 to return to normal conditions.
MBATMA
Source: Sheet 3 – D22 pin 15
Description: DC Overvoltage – this input goes high to inform the micro that a‘DC Overvoltage’ has been detected (See paragraph 4.3.7.2) (alarm [#58] [DC BUS: FAST OVERV.]). This signal is latched within D22 and must be resetby S1 to return to normal conditions.
SEQMNS
Source: Sheet 5 – D34 pin 10
Description: Bypass phase sequence error – this input goes high to inform themicro that a ‘Bypass phase sequence error’ has been detected (See paragraph4.3.14.1). Note that the Rectifier Logic Board detects a phase sequence error onthe UPS (rectifier) input mains supply (See section 4 paragraph 2.3.6.1). A phasesequence error initiates alarm [#14] [I/P: PHASE ROT.ERROR] and also enablesalarm [#16] [BYPASS INHIBIT] via the micro.
EEDO
Source: Sheet 2 – D20 pin 4
Description: Output from the security EPROM to initiate the micro-controller.
DRDO
Source: Sheet 3 – D18 pin 6
Description: Real Time Clock output (See paragraph 4.3.9).
4.3.11.5 Buffer D51 – activated by CSIN3
PAIN1 to PAIN8
Source: Sheet 7 – X7
Description: Data from parallel control bus – not used in a ‘single-module’ in-stallation. The Parallel Logic board interfaces with the micro via this buffer andis active only in the “1+1” and “multi-module” system configurations
4.3.11.6 Buffer D60 – activated by CSIN3
BLK-SYN
Source: Sheet 7 – X8 pin 11
Description: Sync disable – this is an input from the optional ‘remote alarm’sboard’ (AS400 interface board) which goes high (+5V) when the UPS is “ON-
GENERATOR” – and is normally used to prevent the inverter synchronising to afrequency-wild standby generator. The On Generator status signal is applied as aclosed contact across the Remote Alarms Board terminal block X5 pins 3-4.
s7c3bOLD.fm - Issue 2 Dated 21/08/97 20-399
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
Note: The response to the “ON-GENERATOR” event is programmable via the Op-erator Control Panel FUNCTION software screen which allows three separatefunctions to enabled/disabled:
• Synchro Block – is concerned with the [BLK-SYN> signal mentioned hereand, when enabled, prevents the inverter from tracking the bypass fre-quency when it is being provided by the standby generator.
• Charge Inhibit – is concerned with the battery recharge current limitfunction which, when enabled, reduces the RECTIFIER current limit by15%.
• Current Limit – is concerned with the rectifier input current limit[XRADD1> function which, when enabled, reduces the input current limitby 35%.The reduced current limit functions are employed to lower the potentialmaximum current demand if the standby generator is undersized.
BLK-EXT
Source: Sheet 7 – X8 pin 12
Description: From external alarms (AS400 interface board). This input pro-vides a means of allowing the inverter to be turned OFF/ON from an externalsignal via the Remote Alarms Board. The ‘Block’ (OFF) signal is applied as aclosed contact across the Remote Alarms Board terminal block X5 pins 1-2.
Note: Jumper X6 on the Remote Alarms Board must be selected 2-3 in order toenable this function.
BLK-01
Source: Sheet 7 – X8 pin 9
Description: From external alarms (AS400 interface board) Not used.
BLK-CHG
Source: Sheet 7 – X8 pin 10
Description: Rectifier Disable – This input provides a means of allowing therectifier to be turned OFF/ON from an external signal via the Remote AlarmsBoard. The ‘Block’ (OFF) signal is applied as a closed contact across the RemoteAlarms Board terminal block X5 pins 1-2.
Note: Jumper X6 on the Remote Alarms Board must be selected 1-2 in order toenable this function.
Links X26
Source: Sheet 4 jumper X26
Description: The four sections of jumper X26 are detailed in a Table on the cir-cuit diagram sheet 1 and summarized below:
20-400 s7c3bOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
Table 20-15: X26 Jumper details
4.3.12 Data bus output buffers
(circuit diagram sheet 4).
Digital signals generated by the microcontroller as part of its control function arefed to the peripheral circuits via 10 type-74C273 octal latches (See Appendix A.2)which are accessed in pairs to provide a 16-bit data transfer (See Figure 20-21).The ‘chip select’ signals from D52 provide the latch clock signals and data istherefore transferred through the latches when the appropriate ‘chip select’ signalswitches from low to high. A logic low [RSTDX-> reset signal is connected to allthe data bus output buffers via jumper X25 (3-2) and drives all their outputs lowwhen applied. [RSTDX-> is produced by the microcontroller (See paragraph 4.3.3)and shown on the circuit diagram sheet 2.
The remainder of this sub-section lists the digital signals connected through thelatches, and provides signal details where appropriate.
4.3.12.1 Buffers D7 and D10– activated by CSDIS
These two devices connect the data bus output to the two on-board 7-segment di-agnostic displays (H11 & H12). For a detailed description of the displayed param-eters (see paragraph 4.3.17 on page 20-422).
4.3.12.2 Buffer D17 – activated by CSOUT1
XRADD1
Destination: Sheet 7 – X1 pin 37
LINK 1-2 Open(Standard)
Auto-transfer mode enabled (“on-line” operation).Automatic load transfer from bypass to inverter when the inverter is available – i.e. the inverter is the pre-ferred supply source
Closed Manual-transfer mode enabled (“off-line” operation).Automatic load transfer from bypass to inverter only when the bypass is unavailable – i.e. the bypass is the preferred supply source. Note: there will be a 3-cycle break on transfer to inverter,
LINK 3-4 Open “Inverter voltage fail lockout monitor” disabled
Closed(Standard)
“Inverter voltage fail lockout monitor” enabled. i.e. The inverter is given 5 seconds to reach nominal voltage otherwise it is latched OFF.
LINK 5-6 Open(Standard)
Enables the “Event History” monitor to store up to a maximum of 10 alarms.
Closed Resets the “Event History” monitor. Note: After the 10th “event”, the monitor buffer is full an cannot store any further “events”. The buffer should be reset to 0 after each maintenance or commissioning to enable new “events” to be captured.
LINK 7-8 Open(Standard)
Password protection enabled.
Closed Password protection disabled
s7c3bOLD.fm - Issue 2 Dated 21/08/97 20-401
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
Description: Reduced current limit – when this output goes high it reduces theRectifier Logic Board’s input current limit threshold by 35% (See section 4 par-agraph 2.3.4.2).
Conditions: This software-selectable output is activated when the UPS is run-ning on ‘standby generator’ as described on page 20-399 ([BLK-SIN>).
REC-B & REC-A
Destination: Sheet 7 – X1 pin 38 / 39
Description: Charge mode selection – these two outputs are connected to a de-coder on the Rectifier Logic Board where they invoke one of four permissiblecharge modes (see section 4 table 4-3).
Conditions: These outputs select Test, Boost, Float and Manual charge modesin response to selections made on the Operator Control Panel. The automaticBoost mode parameters, i.e. duration and threshold, are also operator-defined –(see paragraph 2.5.6 on page 2-53). LEDs on the Rectifier Logic Board illumi-nate to indicate the active charge mode.
XAT01 & XATO2
Destination: Sheet 7 – X2 pin 55 / 56
Description: Not used
INV-F
Destination: Sheet 7 – X3 pin 37
Description: Base frequency selection – informs the Inverter Logic Board’s‘staircase pattern generator’ of the UPS system’s base frequency (i.e. 50/60Hz).(See section 18 paragraph 3.3.2).
Conditions: This output is high for 50Hz and low for 60Hz as selected on theOperator Control Panel – see ‘Selecting the UPS SETUP parameters’ in the com-missioning procedure (see paragraph 2.4.5.3 on page 2-35).
INV-B & INV-A
Destination: Sheet 7 – X3 pin 38 / 39
Description: Inverter working voltage selection – these two outputs are con-nected to a decoder on the Inverter Logic Board where they select one of four per-missible charge modes (see section 18 table 18-10).
Conditions: The logic states of these outputs are determined by the workingvoltage selected by the operator – see commissioning procedure (see paragraph2.4.5.2 on page 2-34). LEDs on the Inverter Logic Board illuminate to indicatethe active selection.
4.3.12.3 Buffer D25 – activated by CSOUT1
XSTAO1 & XSTAO2
Destination: Sheet 7 – X5 pin 19 / 20
Description: Not used
20-402 s7c3bOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
RE485-
Destination: Sheet 7 – D58 pin 2
Description: This output selects the ‘Read Enable’ pin of D58, which is anRS485 communications driver connected to the parallel interface connector X7pins 59/60 – not used.
OE485
Destination: Sheet 7 – D58 pin 3
Description: This output selects the ‘Output Enable’ pin of D58, which is anRS485 communications driver connected to the parallel interface connector X7pins 59/60 – not used.
TP5
Destination: Sheet 7 – X18 pin 5
Description: Not used (test point for system software).
OUTBAT
Destination: Sheet 2 – V152
Description: This output, when high, ‘enables’ the on-board Ni-Cad batterycharger.
Conditions: This output enables the Ni Cad battery charger if its voltage fallsto 2.8Vdc and disables it again once the battery voltage rises to 3.6V.
Note: when the charger is enabled the [BACK-UP BATTERY LOW] warning is an-nunciated (alarm [#76] active).
4.3.12.4 Buffer D9 – activated by CSOUT2
EECS / EESK / EEDI
Destination: Sheet 3 – D18 pin 7
Description: These outputs control the data acquisition of EEPROM D20
ORCS
Destination: Sheet 3 – D18 pin 7
Description: Real Time Clock (RTC) ‘chip select’ (See paragraph 4.3.9).
ORSK
Destination: Sheet 3 – D18 pin 4
Description: Real Time Clock (RTC) ‘serial communications clock input’ (Seeparagraph 4.3.9).
ORDI
Destination: Sheet 3 – D18 pin 5
Description: Real Time Clock (RTC) ‘serial data input’ (See paragraph 4.3.9).
s7c3bOLD.fm - Issue 2 Dated 21/08/97 20-403
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
SELANA / SELANB
Destination: Sheet 6
Description: These two outputs are connected to the address inputs of three 2-pole multiplexers which select the analogue signals for the microcontroller’s A/Dinputs – e.g. selecting the analogue signals for display purposes (kVA values arecalculated in software using V x I).
4.3.12.5 Buffer D21 – activated by CSOUT2
ALMRES
Destination: Sheet 3 – D22 pin 1
Description: Software controlled RESET – This output, when high, resets theEmergency Shutdown, DC Overvoltage and Open SCR fault latches within D22.
Conditions: This facility is not programmed into the current software and it istherefore not used.
INV-ON
Destination: Sheet 3 – D23 pin 6
Description: ‘Inverter ON’ request – This output, when high, requests D23 toissue an [ON_INV> command signal which is connected to the Inverter LogicBoard and turns ON the inverter – provided other D23 inputs are correct (See par-agraph 4.3.7.2).
Conditions: (see paragraph 7.2.3 on page 7-160)
RSTOUT
Destination: Sheet 3 – D23 pin 8
Description: Software controlled “reset” – When low, this output resets the“load-on-inverter” signal the [L_INV> and “load-on-mains” signal [L_MAINS>.
Conditions: The signal deactivates the above signals while the micro is reload-ing the default parameters, which can be activated using the RELOAD UPS DATAselection on the Operator Control Panel menu screens. Note: the load shouldalways be on the “Maintenance Bypass” before performing a “system reload”.
L-INV
Destination: Sheet 3 – D23 pin 9
Description: ‘Load-on-inverter’ request – This output is interlocked with the[RSTOUT> signal within D23 (See paragraph 4.3.7.2). In order to command the‘load-on-inverter’ this signal must be high and the [RSTOUT> signal low.
Conditions: (see paragraph 7.2.10 on page 7-180)
LMAINS
Destination: Sheet 3 – D23 pin 11
Description: ‘Load-on-bypass (mains)’ request – In order to command the‘load-on-bypass’ this signal and the [RSTOUT> signal must be high– see also[RSTOUT>, above.
Conditions: (see paragraph 7.2.10 on page 7-180)
20-404 s7c3bOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
REC-ON
Destination: Sheet 3 – D23 pin 14
Description: ‘Rectifier ON’ request – This output, when high, requests D23 toissue an [ON_REC> command signal which is connected to the Rectifier LogicBoard and turns ON the rectifier (provided other D23 inputs are correct (See par-agraph 4.3.7.2)).
Conditions: (see paragraph 7.2.2 on page 7-158).
IBOPEN
Destination: Sheet 3 – D23 pin 2
Description: Trip battery circuit breaker– This output, when high, requests D23to issue a [BAT_TRP> command signal which is connected to the High Voltage In-terface Board and turns OFF the battery circuit breaker driver transistor.
Conditions: This signal is software driven via a programmable parameter set-ting entered from the Operator Control Panel to trip the battery circuit breakerwhen the battery is fully discharged (see page 2-37). The Emergency Shutdownand DC Overvoltage inputs to D23 pins 4 and 1 also trigger the battery trip signalwhen active (See paragraph 4.3.7.2).
TP6
Destination: Sheet 7 – X18 pin 6
Description: Not used (test point for system software).
4.3.12.6 Buffer D50 – activated by CSOUT3
PAOUT1....PAOUT8
Destination: Sheet 7 – X7
Description: Data to parallel control bus – used in ‘parallel’ installations only.
4.3.12.7 Buffer D55 – activated by CSOUT3
PAOUT9 / PAOUT10
Destination: Sheet 7 – X7
Description: Data to parallel control bus – not used in a ‘single-module’ instal-lation.
OUT-03
Destination: Sheet 7 – X8 pin 25
Description: Output to I/O interface (remote alarms, AS400 interface etc.).
Conditions: Not used
MNS-KO
Destination: Sheet 7 – X8 pin 26
Description: Output to I/O interface (remote alarms, AS400 interface etc.).
s7c3bOLD.fm - Issue 2 Dated 21/08/97 20-405
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
Conditions: Logic high if mains (bypass) supply error – i.e. overvoltage [#11],undervoltage [#12], absent [#10] or bypass blocked [#17].
BATED
Destination: Sheet 7 – X8 pin 27
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Logic high if the battery voltage falls to its end-of-discharge level[#56] – as set by operator through Operator Control Panel (see page 2-37). It isalso active if the battery breaker is open [#05] or the battery fuse is open [#57].
CHG-INH
Destination: Sheet 7 – X8 pin 28
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Logic high if the battery charger is inhibited (driven by the[BLK-CHG> signal described on page 20-400). Jumper X4 pins 1-2 must be linkedon the Alarm Board.
SWBYP
Destination: Sheet 7 – X8 pin 29
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Logic high if maintenance bypass isolator is closed – accompaniedby alarm #06 [ON MANUAL BYPASS].
OUT-01
Destination: Sheet 7 – X8 pin 23
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Not used in the present software implementation
4.3.12.8 Buffer D54 – activated by CSOUT4
OUT-02
Destination: Sheet 7 – X8 pin 24
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Not used in the present software implementation
OVT-BAT
Destination: Sheet 7 – X8 pin 18
Description: Output to I/O interface (remote alarms, AS400 interface, RemoteAlarms Monitor etc).
Conditions: Logic high in the event of battery overtemperature – Not used inthe present software implementation.
SYN-KO
Destination: Sheet 7 – X8 pin 16
20-406 s7c3bOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
Description: Output to I/O interface (remote alarms, AS400 interface, RemoteAlarms Monitor etc).
Conditions: Logic high if the inverter is unsynchronised to the bypass supply– i.e. if the phase displacement is more than ±9°. This condition will initiate alarm#35 [INVERTER: OUT OF SYNC].
ALL-GEN
Destination: Sheet 7 – X8 pin 17
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: This is the “Common Alarm” output to the Alarm Board and isactive if any of the following alarms are present: [#05], [#06], [#10], [#11], [#12],[#16], [#17], [#24], [#33], [#34], [#52], [#56], [#57], [#66].
A400ON
Destination: Sheet 7 – X8 pin 31
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: This alarm is active when the load is on the UPS (inverter or by-pass) and is interlocked with the Maintenance Bypass being closed.
A400UF
Destination: Sheet 7 – X8 pin 32
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Condition: Mains Failure alarm; enabled by alarm [#01] and active when [#22] is energised.
A400BL
Destination: Sheet 7 – X8 pin 33
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Low Battery warning; enabled by alarm [#01] and active when[#56] is energised.
A400BY
Destination: Sheet 7 – X8 pin 34
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Load on Bypass; active when alarm [#18] is energised.
4.3.12.9 Buffer D56 – activated by CSOUT4
MNSREC
Destination: Sheet 7 – X8 pin 20
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Rectifier input voltage failure – active when H9 is illuminated onthe Rectifier Logic Board.
s7c3bOLD.fm - Issue 2 Dated 21/08/97 20-407
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
CS-KO
Destination: Sheet 7 – X8 pin 19
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Bypass-side Static Switch blocked – goes high if a fault is detectedon the static switch (alarm [#16] present).
BAT-DSC
Destination: Sheet 7 – X8 pin 13
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Battery discharging – active when alarm [#22] is present.
OVL
Destination: Sheet 7 – X8 pin 14
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Overload – active when alarm [#33] or [#66] is present.
OVT-DIS
Destination: Sheet 7 – X8 pin 15
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Overtemperature – active when alarm [#24] or [#34] is present.
OVT-AMB
Destination: Sheet 7 – X8 pin 30
Description: Output to I/O interface (remote alarms, AS400 interface etc).
Conditions: Output Air overtemperature – not used.
XINV01
Destination: Sheet 7 – X3 pin 24
Description: Mains error inhibit to Inverter Logic Board transfer control.
Conditions: On the Inverter Logic Board a circuit within D11 provides a con-trol signal [RIF> which briefly transfers the voltage reference signal to the bypasssupply just before the ‘inverter-side’ contactor is closed; (see paragraph 3.3.3 onpage 18-251). This signal, [XIN01>, goes high to inform the Inverter Logic Boardof a mains (bypass) voltage error and prevents the switch-over to the bypasssupply reference from taking place; and so prevents the inverter locking to an out-of-spec voltage.
TP7
Destination: Sheet 7 – X18 pin 7
Description: Not used (test point for system software).
20-408 s7c3bOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
Section 20:
4.3.13 Frequency sensing and control signals
Figure 20-22: Frequency synchronisation control
4.3.13.1 Frequency control principles
The inverter frequency is determined by the VCO section of a phase locked loopi.c. (D6) on the Inverter Logic Board which provides a 288kHz (nominal) clocksignal to a frequency-divider (within D1) which then clocks the multiplexers inthe ‘reference voltage generator’ circuit (See section 18 paragraph 3.3.2).
Base frequency selection
The inverter base frequency is selected via the Operator Control Panel duringcommissioning and is read by the microcontroller through the CAN bus. Themicro responds by appropriately setting the [INV-F> output from D17-15 – Low =50Hz and High = 60Hz. This is connected to the ‘frequency divider’ on the Invert-er Logic Board where it determines the division factor – i.e. when [INV-F> is lowthe 288kHz VCO output is divided by 5760 to produce a 50Hz output at D1-26/27; when [INV-F> is high the division is 4800 and produces a 60Hz output.
Frequency synchronisation
It is desirable that the inverter output is synchronised to the bypass supply undernormal operating conditions as this enables a ‘closed’ load transfer to be carried
D1
FrequencyDivider
INV-F 44
D6
43
VCO
PhaseComparator
4CL
KSYNC
14
26
3
50
/60
Hz
27
FRFB
R247
D42
MIC
RO
CO
NT
RO
LL
ER
D53
BACKBACKM
416
63
15F-INF-INM
515
62
D17 15
D59
INV-F
SYNCSYNCM15564
34
37
35
34
37
35
UPS Logic Board Inverter Logic Board
X2
X3 X4
Bypass supply R-phase voltage sensing
50 /60 Hzselection
Master Freqreference forInverter Osc
PhaseLocked
Loop
phasealign
13
9
50/60Hz signalsynchronised tobypass (when present)
D54 6
DATABUS
SYNC-KO
Sync errordetection
VI-A
D60 2 BLK-SYN
Sync Inhibit
X18-2
X18-3
X18-4
Clocksignalsto tri-wavegenerator
(correction)
28
8kH
z
8Vp-p
s7c3cOLD.fm - Issue 2 Dated 21/08/97 20-409
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
out in the event of a UPS fault – where-by the static switch SCRs are turned on atthe same time as the inverter contactor is opened, and the load does not experiencea supply break.
If the inverter is not synchronised to the bypass supply there could be a large volt-age difference across the static switch SCRs while the load is ‘on-inverter’ (i.e.SCRs OFF) which might damage the UPS/load equipment during a subsequent‘closed’ transfer: in such circumstances an ‘open’ transfer takes place if the UPSdevelops a fault, where-by the inverter contactor is opened prior to turning ONthe static switch SCRs. This causes a load supply break of up to 1 second, whichis an inbuilt feature designed to avoid load damage.
The frequency synchronisation control mechanism is quite complex and effec-tively based on two nested phase locked loops. The inner loop comprises D6 onthe Inverter Logic Board and the outer loop is functionally provided by the micro-controller, under software control.
4.3.13.2 Frequency sync control and operation
Inverter Logic Board phase-locked-loop (assuming 50Hz operation.)
The ‘phase comparator’ section of D6 compares the 50Hz output from D1-26,connected to D6-3, with a frequency reference signal annotated [SYNC> which isproduced by the microcontroller and connected to D6-14 (available at test pointX18-4). If the ‘phase comparator’ detects any phase difference between these twosignals its output at D6-13 will modify the VCO’s frequency in such a way as tomake the ‘frequency divider’ output at D1-26 match the [SYNC> signal frequency– i.e. the VCO frequency will be modified until the ‘phase comparator’ within D6sees no error between these signals, whereupon the circuit can be considered tobe phase-locked. Thus the inverter frequency tracks the [SYNC> signal ‘reference’frequency.
[SYNC> signal generation (assuming 50Hz)
The microcomputer monitors the bypass supply R-phase waveform [VI-A> via acomparator which extracts its frequency information, [F-INM>. This signal can beseen at X18-2 as a squarewave coinciding with the bypass supply R-phase zero-crossing points. The Inverter Logic Board frequency divider’s 50Hz output (D1-27) is also monitored and is available at X18-3, annotated [BACKM>.
Under software control, the micro operates on these two signals in the same wayas described above for the Inverter Logic Board’s phase-locked-loop. That is, itperforms the ‘phase comparator’ and ‘VCO’ functions described above and pro-duces a 50Hz output, [SYNC>, whose absolute frequency is controlled by the de-tected phase difference between [F-INM> and [BACKM> – i.e. the width of the pulseis directly proportional to the amount of phase difference.
Example of sync control
The overall operation of the synchronisation control circuits can best be explainedby example. Consider the case where the bypass frequency suddenly jumps from50Hz to 50.5Hz:
1. The micro will sense the jump in bypass frequency through a rise in [F-INM>
to 50.5Hz.
2. The micro will sense a phase error between [F-INM> and [BACKM> due to theirfrequency difference and will ramp-up the [SYNC> signal frequency becauseit senses that the bypass frequency is higher than that of the inverter.
20-410 s7c3cOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
3. The ‘phase comparator’ in the Inverter Logic Board’s phase-locked-loop willsee the ramping [SYNC> frequency and detect that it is now higher than thefrequency divider’s ‘50Hz’ output.
4. The phase comparator error output (pin 13) will call for an increase in VCOfrequency, which will thus increase the ‘frequency divider’ clock rate andthereby demand an increased inverter frequency.
5. The two ‘50Hz’ outputs from the frequency divider also ramp-up in line withthe inverter frequency and have two affects:
a) The increasing output at D1-26 is fed back to the phase-locked-loop(D6-3) where it maintains phase-lock – i.e. it ties the clock frequency tothe [SYNC> signal and maintains close tracking of this signal.
b) The increasing output from D1-27 is fed back to the microcontroller viaR247 where it allows the phase error function to maintain a close check onthe ‘bypass/inverter’ frequency and phase relationship.
6. When the inverter frequency has risen to match the 50.5Hz bypass frequency,and the [F-INM> and [BACKM> signals are in phase:
a) The [SYNC> frequency will stop ramping up and remain at 50.5Hz, syn-chronised to the bypass supply due to the action of the micro.
b) The VCO clock frequency will remain constant – i.e. 290.88kHz (5760 x 50.5 – as 5760 is the divider factor for 50Hz systems).
c) The outputs from D1 pins 26 and 27 will be steady at 50.5Hz and synchro-nised to the [SYNC> signal.
7. If [SYNC> is synchronised to the bypass supply (6a) and the frequency divideroutputs/inverter are synchronised to the [SYNC> signal (6c) then this results inthe inverter being effectively synchronised to the bypass supply, are required.
Important notes: The above description requires qualification by the follow-ing notes.
a) The internal mechanism of the frequency divider chip ties its ‘50Hz’ out-puts to the zero-crossing points of the R-phase inverter voltage. Thus, asthe micro uses the bypass R-phase supply as its frequency sensing source,this effectively ensures that the inverter and bypass supplies are synchro-nised correctly from a phase alignment viewpoint.
b) To aid description the above example assumed that the bypass frequencyunderwent a stepped change; however, in practice any change in bypassfrequency is likely to occur gradually: in which case the circuit dynamicsare usually able to maintain a phase-locked condition during the period ofchange, resulting in the inverter frequency tracking the bypass frequencyat all times without incurring a detectable phase error.
c) The synchronising ‘window’ and ‘slew-rate’ are adjustable and selectedfrom the Operator Control Panel setup menus. The ‘window’ defines thelimits to which the inverter is allowed to track the bypass frequency andnormally set to ±2%; while the ‘slew-rate’ defines the maximum permit-ted rate-of-change of inverter frequency and is usually set to 0.1Hz/s.– i.e.this determines the fastest rate of change of bypass frequency tolerated bythe synchronisation circuit whilst maintaining sync.If the bypass frequency goes outside the permitted window the inverterfrequency will return to its base frequency and await the mains return
s7c3cOLD.fm - Issue 2 Dated 21/08/97 20-411
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
within the sync window, where-upon it will re-synchronise. An[INVERTER: OUT OF SYNC] (alarm #35) warning will be displayedwhile this situation is in effect.
d) In the event of a bypass supply failure the microcontroller will drive its[SYNC> output to the ‘centre’ frequency – i.e. 50Hz.
Sync phase adjustment
R247 is connected to a ‘phase-shift’ circuit on the Inverter Logic Board and pro-vides the means for trimming any error in the phase relationship between the in-verter [BACKM> and bypass [F-INM> sense signals once the sync control circuit isphase-locked – due mainly to component tolerances. Therefore, once the inverteris synchronised this resistor can be adjusted to reduce the residual phase differ-ence between the inverter R-phase output and the bypass R-phase supply.
4.3.13.3 Non-Sync detection and alarm
An alarm condition [SYN-KO> is flagged by the microcontroller when it detectsthat the [BACKM> and [F-INM> signals are more than 11° out-of-phase. This is com-municated to the Operator Logic Board via the CAN bus and also, via D54-6, tothe I/O interface connector X8-16 where it can be used to provide a remote alarmsindication (sheet 7). [SYN-KO> is ‘high’ when a non-sync condition is present.
4.3.13.4 External ‘sync inhibit’
In certain circumstances it may be necessary to inhibit the synchronisation loop –for example when supplying the UPS from a stand-by generator whose frequencyregulation is poor. This can be achieved by an external input via the I/O connectorX8-11 [BLK-SYN> which is connected to the microcontroller via D60-2. This inputmust be taken ‘high’ to inhibit the synchronisation function (See paragraph4.3.11.6).
Note: The control can be activated only after being ‘enabled’ in the Function pa-rameter software setup screen (see paragraph 2.4.7.3 on page 2-43).
20-412 s7c3cOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
4.3.14 Analogue signal processing
The UPS Logic Board monitors the UPS input voltage, output voltage, invertervoltage, battery voltage, output current and battery current. These inputs are proc-essed by analogue circuits (sheets 6 & 7) which provide appropriate signals forthe microcomputers A/D input port. In some cases the inputs are also convertedto digital alarm/status signals which are connected to the micro via the data bus.
4.3.14.1 Bypass voltage signal processing
Figure 20-23: Bypass voltage sensing block diagram
Voltage sensing
The bypass voltage sense signals ([VI-A> - [VI-C>) are developed on the High Volt-age Interface Board (See paragraph 2.3.6) and connected via X2 pins 15, 16, 17to N6b/c/d which are unity-gain buffers (sheet 5). The signals at N6 outputs there-fore equate to approximately 1% of the bypass supply line-neutral voltage (e.g.2.4Vrms at 240V working) and are connected to several blocks as shown inFigure 20-23.
Voltage monitoring
N29a-c take the line-to-neutral sense voltages produced by N6 and converts theminto line-to-line sense voltages suitable for connecting to the microcontroller A/Dinputs. Taking N29a as an example; this amplifier differentially sums the [VI-A>
and [VI-B> signals from N6 and produces the [VIABM> L-L signal. However theamplifier attenuates the resultant signal to about 30% (e.g. 1.38V for 240V work-ing) due to its feedback resistance ratios: also, the non-inverting input is connect-ed to VREF-2 (2.5V reference voltage) rather than to the 0V rail, which thereforeapplies a 2.5V offset to [VIABM>. Thus in a 240V system working at nominal volt-age [VIABM> is approximately 3.9Vp-p centred on a 2.5V reference. This signalsits well within the microcontroller’s A/D 0-5V input level, and is shown connect-ed to the A/D multiplexer circuit (sheet 6).Note: if the bypass voltage is missing [VIABM> will be 2.5Vdc due to the absenceof any ac signal.
A-Ph
N6Buffer
N29Sum-Amp
N29dRectifier
N14Filter
N14Filter
B-Ph
3-PhaseBypass
VoltsSense
D27Ph-Seq
VIABM
VIBCM
VICAM
[SVI>
[SVIM>
[F-IN>
[SEQMNS>
To A/DMultiplexers
To SCR OPEN det.
To A/D Multiplexers
To Micro(sync control - bypass R-ph)
To Micro(Phase Sequence
Line-Neut Line-Line
REF-2 (2.5V)
8Vp-p
+5V+2.5V
0V
(Display uses)
(Bypass volts monitor)
error detector)
s7c3cOLD.fm - Issue 2 Dated 21/08/97 20-413
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
Bypass frequency and phase sequence monitors
The bypass R-phase signal [VI-A> from N6-14 is connected to a zero-crossing cir-cuit comprising N14a/d which produces a squarewave output [F-IN> at D34-6which coincides with the R-phase zero-crossing points. This signal is used by themicrocontroller in its frequency synchronisation control (See paragraph4.3.13.1).
A similar squarewave coinciding with the S-phase is obtained via N14b/c andbuffered by D34-8. These two squarewave signals are connected to a D-type flip-flop (D27) which detects their phase relationship. Under normal circumstancesthe R-phase signal should lead that of the S-phase; therefore when the rising-edgeR-phase signal clocks D27, its data (D) input should be ‘low’, producing a perma-nent ‘high’ on its Q output which inverted to a ‘low’ [SEQMNS> signal at D34-10.
In the event of a phase sequence error, D27 will have a permanent ‘low’ clockedthrough to its Q output and produce a ‘high’ [SEQMNS> signal.
[SEQMNS> is connected to the microcontroller via the data bus buffer D28-7where it flags a phase rotation error – [I/P: PHASE ROT.ERROR] alarm #14 (Seeparagraph 4.3.11.4).
3-phase voltage monitor
A full-wave, three-phase diode bridge comprising V34-V36 & V40-V42, produc-es a dc voltage proportional to the full three-phase supply which is fed to N29d.This amplifier attenuates the signal by 55% due to the values of the feedback re-sistors; therefore the output at N2-14 is approximately 2.5Vdc at nominal workingvoltage. Note that this is a ripple voltage since there is very little capacitancearound the amplifier. Thus if any bypass phase voltage goes out of tolerance (e.g.±10% window) the detector will sense the error. It does not require all threephases to go outside the error window.
N2-14 provides signals to two other areas: [SVIM> is connected to the microcon-troller A/D input via the multiplexer circuit shown on sheet 6 and used by themicro to monitor the bypass voltage for a each individual phase (e.g. ±10% volt-age error); and [SVI> is connected to the circuit (also on sheet 6) which detects anopen circuit static switch SCR.
4.3.14.2 Inverter voltage sensing
Figure 20-24: Inverter voltage sensing block diagram
Voltage sensing
The inverter voltage sense signals ([VINV-A> - [VINV-C>) are developed on the HighVoltage Interface Board (See paragraph 2.3.5) and connected via X2 pins 18, 19,20 to N3a-c which are unity-gain buffers (sheet 5). The signals at N3 outputstherefore equate to approximately 1% of the inverter line-neutral voltage. A full-wave, three-phase diode bridge produces a dc voltage proportional to the fullthree-phase output which is then fed to N3d. This amplifier attenuates the signal
N3dRectifier
3-PhaseInverter
VoltsSense
[SVINVM>To A/D Multiplexers
Line-Neut
N3a-cBuffer
8Vp-p2.2Vdc
error detected on individual phase
20-414 s7c3cOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
by 55% due to the values of the feedback resistors; therefore the output at N3-14is approximately 2.5Vdc at nominal voltage, and connected to the microcontrollerA/D input via the multiplexer circuit shown on sheet 6. This is a ripple voltage asdescribed previously, and is monitored by the inverter voltage error softwarefunction (i.e. ±10%).
4.3.14.3 Battery (bus) voltage sensing
Figure 20-25: Battery voltage sensing block diagram
Battery volts monitor
The DC busbar (battery) voltage sense signal [V-B> is developed on the High Volt-age Interface Board (See paragraph 2.3.3) and connected via X2 pin 27 to N13awhich is a unity-gain buffer (sheet 5). The signal sensitivity is set on the HighVoltage Interface Board to approximately 7.3mV per Volt(bat) therefore [VBM> isabout 3.255V at nominal 446V float charge voltage. This signal is connected tothe microcontroller A/D input, via the multiplexer circuit shown on sheet 6, whereit is used by several software functions, such as: display metering; slow DC over-voltage (max 2.4V/cell window); Low Battery warning (1.82V/cell window); Endof Discharge (1.67V/cell window); and % charge/autonomy time algorithms.
DC Overvolts detection (Fast)
[VBM> is also monitored by N13c, which is configured as a comparator and usedto detect a DC Bus overvoltage condition. N13c has a fixed threshold which op-erates ([BAT-MA> goes high) when [VBM> reaches approximately 4.45V, whichequates to a DC Bus voltage of around 620Vdc.
[BAT-MA> is connected to the ‘Basic System Control Logic’ where it trips the bat-tery circuit breaker, turns off the rectifier and inverter, and trips a latch (See par-agraph 4.3.7.1). In an overvoltage situation – [DC BUS: FAST OVERV.] alarm#58 – the ‘Basic System Control Logic’ responds by issuing a ‘high’ [MBATMA>
signal which flags the micro-controller via data bus buffer D26 (See paragraph4.3.11.4).
4.3.14.4 Battery current sensing
Figure 20-26: Battery current sensing block diagram
N13cComparator
[VBM>To A/D Multiplexers
N13aBuffer[V-B> [BAT-MA>
DC Overvoltage (Fast)
3.25Vdc@ 446V(bat)
(set to 620V(bat))
[IBM>To A/D Multiplexers
N13bBuffer[I-B>
REF-2 (2.5V)
s7c3cOLD.fm - Issue 2 Dated 21/08/97 20-415
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
Battery current monitor
The battery current sense signal [I-B> is developed on the High Voltage InterfaceBoard (See paragraph 2.3.22) and connected via X2 pin 31 to N13b which has again of approximately1.5 (sheet 5). The signal sensitivity is set on the High Volt-age Interface Board by jumper X38 and the output [IBM> is connected to themicro-controller A/D input via the multiplexer circuit shown on sheet 6 where itis used for display purposes, and % charge and Autonomy Time algorithms.
4.3.14.5 Output voltage sensing
Figure 20-27: Output voltage sensing block diagram
Voltage sensing
The bypass voltage sense signals ([VO-A> - [VO-C>) are developed on the HighVoltage Interface Board (See paragraph 2.3.6) and connected via X2 pins 21, 22,23 to N5a-c which are unity-gain buffers (sheet 6). The signals at N5 outputstherefore equate to approximately 1% of the output line-neutral voltage (e.g. 2.4V(8Vp-p) at 240V) and connected to several blocks as shown in Figure 20-27.
Voltage monitoring
The signals from N5a-c are connected to two sets of buffers which provide line-to-neutral and line-to-line monitoring voltages which are connected to the micro-controller A/D inputs via the multiplexer circuit shown on sheet 6 and used formetering & display purposes.
L-N voltage monitoring. is provided by N38a-c which attenuate the voltagesense signals by approximately 55% and also applies a 2.5Vdc offset due to thenon-inverting connection being terminated at VREF-2 (2.5V reference voltage). At240V nominal voltage the monitor output signals [VOAM>, [VOBM>, VOCM> aretherefore 1Vrms (2.8Vp-p) centred about a +2.5V reference which sits well withinthe microcontroller’s A/D 0-5V input level.Note: if the output voltage is missing [VOAM> etc. will be 2.5Vdc due to the ab-sence of any ac signal.
N5Buffer
N31Sum-Amp
N15aRectifier
3-PhaseOutput
VoltsSense
N15b-dCompar-
VOABM
VOBCM
VOCAM
[SVOM>
[SCROPN>
To A/DMultiplexers
To A/D Multiplexers
To Micro(SCR open cct.)
Line-Line
REF-2 (2.5V)
N30Buffer
VOAM
VOBM
VOCM
To A/DMultiplexers
Line-Neut
REF-2 (2.5V)
[SVI> ator
8Vp-p
+5V+2.5V
0V
(Critical bus monitor)
(monitoring & display)
(Monitoring &display)
20-416 s7c3cOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
L-L voltage monitoring. is provided by N31a-c. Taking N31a as an example;this amplifier differentially sums the A and B phase signals from N5 and producesthe [VOABM> L-L signal. However, the amplifier attenuates the resultant signal byabout 70% (e.g. 1.38V for 240V working) due to its feedback resistance ratios:also, as with the L-N circuit described above, the non-inverting input is connectedto VREF-2 (2.5V reference voltage) rather than to the 0V rail, which applies a 2.5Voffset to [VOABM>. Thus in a 240V system working at nominal voltage [VOABM>
is approximately 3.9Vp-p centred on a 2.5V reference.
3-phase voltage monitor
A full-wave, three-phase diode bridge comprising V29-V31 etc, produces a dcvoltage proportional to the full output three-phase supply which is fed to N15a.This amplifier attenuates the signal by 55% due to the values of the feedback re-sistors; therefore the [SVOM> output at N15-1 will be approximately 2.5Vdc atnominal working voltage. Note that this is a ripple voltage since there is very littlecapacitance around the amplifier. [SVOM> is connected to the microcontroller A-to-D inputs via the multiplexer circuit shown on sheet 6. This is used by themicro-controller as a critical bus voltage error monitor (factory set to ±10%) fortransfer functions.
Open Circuit Static Switch SCR detection
As shown in Figure 20-27, the output voltage (3-phase) sense signal [SVOM> andbypass voltage (3-phase) sense signal [SVI> are both connected to the StaticSwitch ‘SCR open circuit’ detector.
4.3.14.6 Output current sensing
Figure 20-28: Output sensing block diagram
Output current monitor
The UPS output current sense signals ([IO-A> - [IO-C>) are developed on the HighVoltage Interface Board (See paragraph 2.3.19) and connected via X2 pins 32,33, 34 to N4a-c which attenuate the sense signals by approximately 75% and alsoapplies a 2.5Vdc offset due to the non-inverting connection being terminated atVREF-2 (2.5V reference voltage). The output signals [IOAM> etc. are connected tothe microcontroller A/D inputs via the multiplexer circuit, and the 2.5V offset issufficient to make the a.c. current signal sit within the 0-5V A/D input voltagerange. These signals are by the micro’s ‘overload’ algorithm (i.e. 150% for 1minute, 125% for 10 minutes, 110% for 1 hour, 101% for 9 hours. They also rep-resent the values shown on the Operator Control Panel ‘Measurements’ displayscreen.
N4dSum-amp
3-PhaseOutput
CurrentSense
[IONM>To A/D Multiplexers
N4a-cBuffer
REF-2 (2.5V)
[IOAM>[IOBM>[IOCM>
(Overload & Timers)
(Display Metering)
s7c3cOLD.fm - Issue 2 Dated 21/08/97 20-417
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
N4d calculates the neutral current by differentially summing the three line cur-rents – in a balanced three phase system the algebraic sum of the currents shouldequal zero, thus if the system is unbalanced then the amount of imbalance repre-sent the current flowing in the neutral path. The neutral current signal [IONM> isalso subject to the 2.5V offset and applied to the microcontroller A/D inputs viathe multiplexers in the same way as the line current signals.
4.3.14.7 Analogue signal monitoring multiplexers
The microcontroller has ten A/D inputs ([AN0> to [AN9>).
[AN6> to [AN9> are fed by fixed inputs signal sources; however, [AN0> to [AN5>are fed via a series of multiplexers which allow the micro to select from varioussignal sources. Three type 4052 multiplexers are used for this purpose, each ad-dressed by two signals ([SELANA> and [SELANB>) produced by the microcontrol-ler via data bus buffer D9 (See paragraph 4.3.12.4). Sheet 6 contains themultiplexer circuit and illustrates the various monitored signals connected to theirdata pins (See Appendix A.3). The multiplexers are inhibited if the -12V powersupply monitor detects an undervoltage by applying a logic high [FL-12-> to themultiplexer inhibit inputs (pin 6) (See paragraph 4.3.15.3).
Note: the inputs annotated [T1> - [T4> are temperature sensing inputs – refer to theHigh Voltage Interface Board description (See paragraph 2.3.12).
Note: the micro can access the A/D signals in parallel and where necessary cancalculate values for the display – e.g. kW = V x I.
20-418 s7c3cOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
Section 20:
4.3.15 Power supplies
4.3.15.1 General description and voltage regulators
The UPS Logic Board ±12V power supply rails are provided from two parallelsources and will be available if either source is live. The first source is from theRectifier Logic Board, which is itself powered from the AC-DC Power Supplyand available whenever the UPS input (rectifier) supply is live (see paragraph 2.1on page 3-5); the second if from the Inverter Logic Board, which is powered fromthe DC-DC Power Supply and is available whenever the rectifier is working orthe batteries are connected to the DC Busbar (see paragraph 3.1 on page 3-7).
From the UPS Logic Board the ±12V supplies are passed directly to all the re-maining circuit boards and the communications port etc.
4.3.15.2 Reference voltage generators
Several devices require a stable +5V power supply which is provided by a simple3-terminal +5V regulator (N1), shown on sheet 7.
In addition to the +5V power supply rail, there are also two reference voltage gen-erators on the circuit board. One generates a regulated +5V, [VREF>, from the+12V line and the other generates a regulated 2.5V output, [VREF-2>, from the+5V supply rail. These reference voltages are used in conjunction with the micro-controller’s A/D analogue inputs and are shown on sheet 5 of the circuit diagram.
+5V reference voltage [VREF>
This provides a stable power supply for the A/D converters within the microwhich is necessary for them to maintain their conversion accuracy.
2.5V reference voltage [VREF-2>
The micro-controller’s internal A/D converters operate on stable 0V and +5Vpower rails, as described above. Therefore if an AC signal is to be monitored (e.g.bypass voltage), or a positive-and-negative going DC signal (e.g. battery current),then a 2.5V offset is required shift the 0V point of the monitored signal into thecentre of the A/D converters’ input working range. This enables the A/D circuitto convert both halves of an AC waveform and both positive and negative transi-tions of a dc signal voltage.
4.3.15.3 -12V undervoltage detector
Comparator N45a (sheet 5) serves as a -12V supply rail monitor and detects whenthe -12V is less than approximately -9.8V. The operating threshold for this circuitis set by V70 which applies a zener referenced voltage across R242/243 from the+12V rail and under normal conditions sets N45-3 at about 1.86V. The -12V railis monitored via a resistor divider (R240/241) which is fixed at +3V at one end byV70.
Due to the chosen resistor ratios, the voltage at N45-2 rises above 1.86V when the-12V rail is less than -9.8V, at which point N45-1 switches low and produces alogic high [FL-12-> signal and low [FL-12>.
When [FL-12> goes low it inhibits the back-up battery voltage sense signal to themicrocontroller via D44, as shown on diagram sheet 2 (See paragraph 4.3.4).When [FL-12-> goes high is disables the microcontroller’s A/D input multiplexers,as shown on sheet 6 (See paragraph 4.3.14.7).
s7c3dOLD.fm - Issue 2 Dated 21/08/97 20-419
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
4.3.15.4 +12V undervoltage detector
Comparator N45b (sheet 5) serves as a +12V supply monitor. The operatingthreshold for this circuit is set by [VREF-2> which applies a stabilised +2.5V toN45-6, at about 1.86V. The +12V rail is monitored via a resistor divider (R246/245/R244) which pulls the input to N45-5 below the 2.5V threshold when the+12V rail fall below the 9.8V level. When this occurs the output at N45-7 switch-es from high to low which is reflected at D57-8 and the resulting ‘low’ [PFO> flagresets the microcontroller via its non-maskable interrupt (NMI) (See paragraph4.3.2). The micro jumps to a ‘save data’ subroutine as the supply rails are crash-ing.
20-420 s7c3dOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
4.3.16 External communications
RS232 communications
In addition to the bi-directional communication facility with the Operator LogicBoard via the CAN Bus, the microcontroller can also be accessed externally viaa standard RS232 communications connection (X9). This is designed to be usedwith a portable computer for diagnostic, calibration and configuration purposes.Communication takes place through D16 which is a standard RS232 line driver/receiver connected to the micro via [TXO0> and [RXO0>, as shown on sheet 7 (SeeAppendix A.6).
RS-485 Parallel control communications
An RS485 communications facility is also shown on sheet 7, based around D58(See Appendix A.5). The differential I/O bus of this device (pins 6 & 7) is connect-ed to the Parallel Logic Board via X7 ([TXRX+>, [TXRX->).
Transmit mode. the transmit mode is enabled when [DE485> is high, whereup-on the [TXDI> data from the microcontroller, applied to D58 pin 4, passes throughthe device and drives its differential outputs as described in appendix A.5. Notethat X32 should be made in order to connect the bus termination resistor (R250)across the transmission line to present the correct impedance to the differentialoutputs.
Receive mode. the receive mode is enabled when [RE485-> is taken low, where-upon the data on the differential I/O bus is converted into a data-stream and con-nected to the microcontroller via [RXDI>.
s7c3dOLD.fm - Issue 2 Dated 21/08/97 20-421
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
4.3.17 On board 7-segment indications summary
The following table provides a summary of the alarm codes indicated on the two7-segment LEDs together with their alarm interpretations and associated OperatorPanel audible and visible alarm annunciations. Note that there is no on-screenalarm history facility, but where two (or more) alarms are active simultaneouslythe associated codes will be displayed in a cyclic fashion at 1 second intervalsNote: Where the fault LED state is annotated (*) this indicates that the alarm islatched and must be reset using S1 on the UPS Logic Board
CODEDisplay Alarm Messages
(Correct Meaning)Audible Alarm
(Operator Panel)FAULT LED (red)(Operator Panel)
01 [ NORMAL OPERATION ] OFF OFF
02 [ BYPASS BREAKER OPEN ] Continuous ON
03 [ OUTPUT BREAKER OPEN ] Continuous ON
04 [ RECTIF. BREAKER OPEN ] Continuous ON
05 [ BATTERY BREAKER OPEN ] Continuous ON
06 [ ON MANUAL BYPASS ]Manual bypass breaker closed
Pulsed Flashing
10 [ I/P: ABSENT ]Bypass supply absent – i.e. <50V
Intermittent Flashing
11 [ I/P: OVER LIMITS ]Bypass supply over voltage –upper limit set via mimic menu
Intermittent Flashing
12 [ I/P: UNDER LIMITS ]Bypass supply under voltage –lower limit set via mimic menu
Intermittent Flashing
13 [ I/P: FREQUENCY ERROR]Bypass supply over/under freq –window limit set via mimic menu
Intermittent Flashing
14 [ I/P: PHASE ROT. ERROR ]Bypass phase rotation error
Continuous ON
15 [ I/P: SCR CUTOFF ]Bypass SCR open circuit
Continuous ON *
16 [ BYPASS INHIBIT ]Bypass supply blocked –
hardware block on UPS Logic Board
Pulsed Flashing
17 [ BYPASS INHIBIT REM. ]Bypass blocked via operator menu
Pulsed Flashing
18 [ LOAD ON BYPASS ] Intermittent Flashing
19 [ BYPASS OVERTEMPERAT. ]Static bypass overtemperature
warning
Continuous ON
20 [ RECTIFIER: OFF ]Software block via micro
Intermittent Flashing
20-422 s7c3dOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
21 [ RECTIFIER: OFF REM. ]Rectifier blocked via operator menu
Pulsed Flashing
22 [ RECTIFIER: BLOCK ]Hardware block via UPS Logic Board
Continuous ON
23 [ RECTIFIER: I/P LIMIT ]Rectifier input current limit
Intermittent Flashing
24 [ RECTIFIER: OVERTEMP. ]Rectifier overtemperature
Continuous ON
25 [ RECTIFIER: FUSE FAIL ]Input fuse failure (F10,F11,F12)
Continuous ON
30 [ INVERTER: OFF ]Software block via micro
Intermittent Flashing
31 [ INVERTER: OFF REM. ]Inverter blocked via operator menu
Intermittent Flashing
32 [ INVERTER: BLOCK ]Hardware block via UPS Logic Board
Continuous ON
33 [ INVERTER: CURR. LIMIT ]Inverter 150% current limit active
Continuous ON
34 [ INVERTER: OVERTEMP. ]Inverter overtemperature
Continuous ON
35 [ INVERTER:OUT OF SYNC ]Inverter unsynchronised to bypass
warning
Intermittent Flashing
36 [ INVERTER: OVERVOLTA. ]Inverter overvolts warning
Continuous ON
37 [ INVERTER: UNDERVOLTA. ]Inverter undervolts warning
Continuous ON
38 [ INVERTER: FUSE FAIL ]Inverter fuse failure
Continuous ON
39 [ OUTPUT: OVERVOLTAGE ]Inverter overvoltage trip –
critical bus overvoltage trip to bypass
Continuous ON
40 [ OUTPUT: UNDERVOLTAGE ]Critical bus undervoltage trip to
bypass – level set via mimic menu
Continuous ON
41 [ OUTPUT: NO VOLTAGE ]UPS in off-line mode
Continuous ON
42 [ OUTPUT: WRONG W.FORM ]Critical bus peak voltage error
Continuous ON
43 [ INVERTER: WRONG FREQ ]lnverter frequency error –
inverter frequency window is twice the bypass window
Continuous ON
CODEDisplay Alarm Messages
(Correct Meaning)Audible Alarm
(Operator Panel)FAULT LED (red)(Operator Panel)
s7c3dOLD.fm - Issue 2 Dated 21/08/97 20-423
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
44 [ INVERTER: SEL. BLOCK ]Paralleling current error
Continuous ON *
50 [ BATTERY: UNDER TEST ]Battery test in operation
Pulsed OFF
51 [ BATTERY: TEST FAILED ]Battery test has failed
Intermittent Flashing *
52 [ BATTERY: DISCHARGING ]Battery is discharging
Intermittent Flashing
53 [ BATTERY: E.O.D. ]Battery end_of_discharge trip –
level set via mimic menu
Continuous ON
54 [ MAX.DUR.BOOST CHARGE ]Boost charge period expired
Pulsed Flashing
55 [ DC BUS: OVERVOLTAGE ]DC slow overvolts warning –
level set via mimic menu
Continuous ON *
56 [ DC BUS: UNDERVOLTAGE ]Low battery warning –
level set via mimic menu
Continuous ON
57 [ BATTERY: FUSE FAIL ]Battery fuse (F13) failure
Continuous ON
58 [ DC BUS: FAST OVERVOLT. ]Fast dc overvoltage –
fixed at 620V
Continuous ON *
60 [ BYPASS OVERUSE ]Transfer counter exceeded
– i.e. >8 transfers in 1 minute
Continuous ON *
61 [ CUT-OFF: OVERLOAD ]Overload timer expired
Continuous ON *
62 [ CUT-OFF: OVERTEMPER. ]Overtemperature timer expired
Continuous ON *
63 [ CUT-OFF: EMERGENCY ]“Emergency power-off” activated
Continuous ON *
66 [ OVERLOAD ]Overload present (warning)
Continuous ON
67 [ CUT-OFF: OVERLOAD ]Overload timer expired
Continuous ON *
70 [ BAD EEPROM PROGRAM. ]Start-up error – use mimic reset
Pulsed ON
CODEDisplay Alarm Messages
(Correct Meaning)Audible Alarm
(Operator Panel)FAULT LED (red)(Operator Panel)
20-424 s7c3dOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
71 [ ERR. LRC PARAM.PAG1 ]Incorrect display variable
Pulsed ON
72 [ ERR. LRC PARAM.PAG2 ]Incorrect display variable
Pulsed ON
73 [ ERR. LRC PARAM.PAG3 ]Incorrect display variable
Pulsed ON
74 [ ERR LRC ALARM HIST. ]Alarm History buffer error
Pulsed ON
75 [ ERR LRC EVENT HIST. ]Alarm History buffer error
Pulsed ON
76 [ BACK-UP BATTERY LOW ]Internal PCB ni-cad battery Low
Pulsed ON
80 [ ERROR LRC TABLE ]
81 [ ERROR LRC PANEL ]
82 [ MODEM WRONG CONFIG. ]
83 [ ERROR LRC ALARM MEM. ]
84 [ MODEM NO RESPONSE ]Modem incorrectly connected
85 [ MODEM FALSE COMMAND ]Modem incorrectly configured
86 [ MODEM TIMEOUT TRASM. ]Modem baud-rate error
87 [ CAN BUS NO RESPONSE ]UPS-to-display not connected
88 [ AUTONOMY XXXX min ]Battery autonomy time
CODEDisplay Alarm Messages
(Correct Meaning)Audible Alarm
(Operator Panel)FAULT LED (red)(Operator Panel)
s7c3dOLD.fm - Issue 2 Dated 21/08/97 20-425
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
4.4 Summary information
Table 20-16: UPS Logic Board configuration jumpers
JumperLink
Position Function
X11 NO LINK Disable RS232 port (standard)
1 - 2 Enable RS232 port
X12 OPEN (standard)
1 - 2 Not Required
3 - 4 Not Required
X13 1 - 2 EPROM Enable
2 - 3 RAM Enable (standard)
X14 1 - 2 Not Required
Testing onlynormally open
3 - 4 Not Required
5 - 6 Not Required
7 - 8 Not Required
X15 1 - 2 PLL option with
2 - 3 PLL option with (standard)
X16 OPEN CAN Bus to display disabled
1 - 2 CAN Bus to display enabled (standard)
X17 1 - 2 ALE enable data save
2 - 3 Power supply fail enable data save (standard)
X19 1 - 2 EPROM II enable (not required)
2 - 3 RAM II enable (not required)
X20 1 - 2 +5V PCB enables microprocessor ref. For VA calculations (standard)
2 - 3 V ref. enables microprocessor ref. For VA calculations
X21 1 - 2 Not Required
2 - 3 RAM enable (standard)
X22 1 - 2 EPROM enable (standard)
2 - 3 Not Required
X23 1 - 2 Not Required
2 - 3 EPROM enable (standard)
3 - 4 Not Required
4 - 5 Not Required
CAP IN
FIN AUX
20-426 s7c3dOLD.fm - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 4 - UPS Logic Board (4550004 E)
X24 1 - 2 RAM enable (standard)
2 - 3 EPROM enable (not required)
3 - 4 RAM enable (standard)
4 - 5 EPROM enable (not required)
X25 1 - 2 Manual reset of output buffers
2 - 3 Microprocessor reset of output buffers (standard)
X26 1 - 2 Open (Standard)Auto-transfer mode enabled (“on-line” operation).Automatic load transfer from bypass to inverter when the inverter is available – i.e. the inverter is the preferred supply source.ClosedManual-transfer mode enabled (“off-line” operation).Automatic load transfer from bypass to inverter only when the bypass is unavailable – i.e. the bypass is the preferred supply source. Note: there will be a 3-cycle break on trans-fer to inverter.
3 - 4 Open“Inverter voltage fail lockout monitor” disabled.Closed (Standard)“Inverter voltage fail lockout monitor” enabled. i.e. The inverter is given 5 seconds to reach nominal voltage other-wise it is latched OFF.
5 - 6 Open (Standard)Enables the “Event History” monitor to store up to a maxi-mum of 10 alarms.ClosedResets the “Event History” monitor. Note: After the 10th “event”, the monitor buffer is full an cannot store any further “events”. The buffer should be reset to 0 after each mainte-nance or commissioning to enable new “events” to be cap-tured.
7 - 8 Open (Standard)Password protection enabledClosedPassword protection disabled
X28 OPEN Power up reset enabled (standard)
CLOSED Power up reset disabled
X29 OPEN 2.5V power supply monitor enabled (standard)
1 - 2 2.5V power supply monitor disabled
X31 OPEN Internal battery disabled
1 - 2 Internal battery installed and charger enabled (standard)
X32 OPEN RS485 port disabled
1 - 2 RS485 port enabled (standard)
JumperLink
Position Function
s7c3dOLD.fm - Issue 2 Dated 21/08/97 20-427
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 4 - UPS Logic Board (4550004 E)
Table 20-17: UPS Logic Board potentiometer adjustment
Table 20-18: UPS Logic Board LED indication
Potentiometer Function
R209 5 volt reference adjustment. Check at X20 pin 1
R212 2.5 volt reference adjustment. Check at anode of V45
LED Colour Function
H1 Red Internal battery charger operating
20-428 s7c3dOLD.fm - Issue 2 Dated 21/08/97
Section 7:
Chapter 5 - Operator Logic Board
5.1 Chapter overview
This chapter contains a circuit description of the Operator Logic Board usedacross the entire 7200 Series UPS model range, and should be read in conjunctionwith circuit diagram SE-4550005-F (4 pages).
Signal annotations shown on the circuit diagrams are shown in italics in the fol-lowing text – e.g. [CLKOUT>. Where a signal is ‘active low’ it is followed by a ne-gating symbol – e.g. [RSTD->
5.2 General description
5.2.1 Circuit board functions
The Operator Logic Board provides a microprocessor-controlled interface be-tween the Operator Control Panel and the microcontroller-based UPS controlsystem on the UPS Logic Board. Its primary functions can be summarised as fol-lows:
• Display indication–The UPS Logic Board provides the Operator Logic Board with data per-taining to various system operating parameters which are converted to aformat suitable for driving the Operator Control Panel LCD display.
• Operator input–The Operator Control Panel switches are monitored by the Operator LogicBoard which converts any switch operation into a format understood bythe UPS Logic Board.
• External communications options –The Operator Logic Board provides several external communicationsfacilities for use with remote alarm/control stations. Connector X8 – provides a two-way RS232 read/write control port.Connector X5 – provides a one-way RS232 read only control port.Connector X5 – provides a one-way RS485 read only control port.The board also contains an RS232/modem interface which can be used fordiagnostic purposes.
• Isolated power supply –An isolated power supply is contained on the Operator Logic Board whichis used by the circuits associated with the communications facilities. Inter-nal communications between the Operator Logic Board and the UPSLogic Board is by means of a CAN bus (Controller Area Networking).Power supply isolation increases noise immunity and helps avoid spuriousdata transfer between the micro-computer systems contained on eachboard.
s7-c4.fm5 - Issue 2 Dated 21/08/97 7-133
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 5 - Operator Logic Board
5.2.2 Input/Output connections
Figure 7-29: Operator Logic Board connections
The Operator Logic Board has six connectors (See Figure 7-29) whose connec-tions are summarised below.
• X1 – Connection to the Operator Control Panel• X2 – System control and monitoring signals to/from the UPS Logic
Board. This connection takes the form of a serial data link (CAN Bus).• X4 – Standard RS485 comms port (read only)• X5 – Standard RS232 comms port (read only)• X8 – Standard RS232 comms port/modem interface available for external
control/monitoring/diagnostics facilities (read/write)• X9 – Control power supplies (±12V) from the system control power rails
via the UPS Logic Board.
Operator Logic Board
����������������������������������������
������������������������������������
X8 X5
X2
X4
X9X1
UPS Logic BoardPanel
OperatorX4 X6
RS485CommsFacility
RS232Comms
(Reserved)
RS232ModemFacility
(read/write) (read only) (read only)
Isolatedpower supplyfeed
CAN Bus
7-134 s7-c4.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 5 - Operator Logic Board
5.2.3 Block Diagram
Figure 7-30: Operator Logic Board basic block diagram
LED
s
S
witc
hes
Re
set
Pow
erX
26
20
MH
zC
lock
RA
M
Se
ria
lD
eco
de
D1
1
LE
DS
Sw
itches
Latch
Ad
dre
ss B
us
or
Da
ta B
us
RO
M
CA
N
D1
2D
eco
de
Dis
pla
yL
atc
hData
D19
D2
0
X23
R2
1C
on
tra
stA
dju
stm
en
t
P5
P1
P4
P0
P3
D2
= 8
0C
16
6
AX
DX
RS
23
2R
ea
dO
nly
RS
48
5R
ea
dO
nly
CA
N B
us
RS
23
2P
ort
X8
Re
ad
/W
rite
LE
Ds
Ba
r G
rS
witc
hC
ha
rac
X1
Ho
rn
s7-c4.fm5 - Issue 2 Dated 21/08/97 7-135
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 5 - Operator Logic Board
5.2.3.1 System overview
Processor system
The Operator Logic Board control system is based on a type 80C166 microcon-troller, as shown in Figure 7-30. This device, which is identical to that used on theUPS Logic Board, contains six configureable ports through which it communi-cates with peripheral circuits/devices, together with several ‘system controllines’. It also contains several internal A/D converters, four programmable timersand internal ROM (32k) and RAM (1k).
The ports are configured by an initialisation routine performed by the system soft-ware on power-up and can be summarised as follows.
• Port 0Port 0 is configured as a multiplexed Data/Address bus and is connectedto both the Address and Data bus ports of the peripheral devices through aseries of controlled latches, providing an 8-bit data bus <DX0...DX7> or 16-bit address bus <AX0...AX15>.
• Port 1This is configured as a 16-bit output port. Its primary outputs, [LD1> to[LD9> drive the Operator Control Panel LEDs. Other outputs provide theLCD display ‘read’ and ‘write’ control signals and ‘chip select’ signals forthe RS485 communications port device.
• Port 2Three lines of this port are used in conjunction with the CAN serial datacontroller. For reasons of clarity this port is not shown in Figure 7-30.
• Port 3This port is configured to work with the internal timers and is used to con-trol the RS232 and RS485 access, and also the audible warning sounderassociated with the UPS Alarms annunciation.
• Port 4The lower two lines only are utilised on port 4. These provide the uppertwo address lines <A16...A17> – the lower address lines <A0...A15> are pro-vided by port 0. These lines, which do not pass through the selectablebuffers used by the lower 16 address lines, are always available and usedas inputs by the ‘address decoding’ which produce the ‘chip select’ signalsused by the various peripheral devices.
• Port 5The lower five lines of this port <P5-0...P5-4> monitor the Operator Con-trol Panel switches and detects their operation.
• System control linesIn addition to the I/O ports, the microcontroller also has a control bus withI/O lines generally associated with a microprocessor-based system; suchas a system clock, reset, address latch enable, power reset and Read/Writecontrol. These are connected to the peripheral devices where required.
Memory
The microcontroller uses both internal and external memory; 256k of RAM and256k of EPROM are fitted to the board as standard and holds the system operatingsoftware. Facilities are included on the board to allow alternative memory config-urations to be used as described later.
7-136 s7-c4.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 5 - Operator Logic Board
Data/Address latch & buffers
The 16-bit data/address bus is connected to the various peripheral devices andboards via input and output data latches/buffers, as shown in Figure 7-30. Thesebuffers are controlled by individual ‘chip select’ select lines to direct the data flowto/from the appropriate source, as required by the system control software.
5.3 Detailed circuit description
5.3.1 Introduction
The Operator Logic Board circuit diagram (SE-4550005-F) comprises 4 sheets.With reference to the block diagram description, the drawings can broadly be de-scribed as follows:
• Sheet 1 contains a ‘signal map’ identifying the functions covered on theremaining pages. It also contains a summary chart detailing the variousconfiguration jumpers (X11 – X25).
• Sheet 2 contains the switched-mode isolated power supply circuit.• Sheet 3 contains the
– basic microcontroller system.– data bus, address bus and control bus buffers.– address decoding.– system RAM and ROM memory and its associated configuration links.– power-up reset generator.
• Sheet 4 contains the– CAN bus communications drivers and control logic.– RS232 (modem) communications interface.– RS485 communications interface.– Operator Control Panel interface.
As with all micro-based system, the microcontroller’s operation is determined bythe program held in the system’s memory and, as this is hidden to the service en-gineer, there is very little that can be done to ascertain that the board is workingcorrectly apart from checking the validity of its input and output signals, and othersignals generated on the board which are required by the central processor system.The following description deals with the board on this basis, and should providesufficient information to allow a troubleshooting engineer to determine whetheror not the board is functioning correctly. A detailed software description isbeyond the scope of this manual.
s7-c4.fm5 - Issue 2 Dated 21/08/97 7-137
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 5 - Operator Logic Board
5.3.2 Basic microcontroller system
(circuit diagram sheet 2)
Figure 7-31: Micro system control signals
Caution When monitoring the signals described in this section it is best done with controlpower only – i.e. with the UPS power sections shut down and the circuit boardslive via the control power supply. Some signals are irregular, or have very largemark:space ratios, and are best monitored with a logic probe. The logic se-quence/timing of these signals depend upon various circuit conditions and cannottherefore be accurately defined; however, for field test purposes, the presence ofa ‘variable switching’ logic signal at these points would generally indicate that thebasic processor control bus is serviceable and the system software is running.
Power supply
The microcontroller is powered from the isolated +5V rail which is provided bya switched-mode power supply circuit shown on diagram sheet 2 (See paragraph5.3.12).
System clock (XTAL1)
A dedicated crystal-controlled clock generator (E2) provides a system clocksignal which is connected to the microcontroller pin 20. This signal is a 20MHzsquarewave switching between +5V and 0V.
System reset (RSTIN)
A one second logic low reset pulse, [RSTIN->, is applied to D42 pin 27 on power-up from the ‘reset generator’ circuit. This can also be manually applied for trou-bleshooting purposes by bridging and un-bridging jumper X26.
Reset out (RSTOUT)
[RSTO-> is controlled by the reset input signal, [RSTIN->, and goes high while theinput rest signal is applied. This signal is synchronised to the system clock andreturns high an integral number of clock pulses after the input reset signal is re-moved. The [RSTO-> signal is connected to the ‘address decoder’ circuit fromwhere it resets the peripheral devices.
That is, upon receipt of the “wake-up” request ([RSTIN->) the microprocessorissues a “wake-up” call ([RSTO->) to all the other relevant devices.
20
27
54
Power Supply
Clock
Reset
+5V Vref
XTAL1
RSTIN
VAREF
25ALE Address latch enable
26
95
RD
WR
Read
Write
Co
ntro
l Bu
s
D2
28RSTOUT Reset Out
7-138 s7-c4.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 5 - Operator Logic Board
Reference voltage (VAREF)
The input to D2 pin 54 (VAREF) is a reference voltage used by the internal A/Dconverters; however, in this application the A/D circuits are not used and thisinput is connected directly to the general +5V supply rail.
Address latch enable (ALE)
When the multiplexed Address/Data bus (port 0) carries Address information thisoutput goes ‘high’. This is used to control the address bus buffers as describedbelow.
Read (RD)
This output goes low when the processor wishes to read the data from the deviceor memory location currently addressed by the address bus.
Write (WR)
This output goes low when the processor wishes to write data to the device ormemory location currently addressed by the address bus
5.3.3 Data bus, address bus and control bus buffers
(circuit diagram sheet 3.)
Overview
As described above, the microcontroller’s Port 0 acts as a multiplexed 16-bit Ad-dress/Data bus. When this bus carries Address information the [ALE> output goes‘high’ to enable the address bus latches (D5 and D6) whose buffered outputs arethen treated as a 16-bit address bus [AX0...AX15>. Conversely, when [ALE> is ‘low’the bus information is interpreted as Data and connected to the peripheral devicesvia an 8-bit data bus latch (D7) in conjunction with the ‘read’ [RD-> control line.
Address bus buffer
Two 74HCT573 devices serve as the address buffers (D5 & D6) – these are de-scribed in Appendix A (See appendix A.4).
In this application the Output Enable pins are connected to a permanent logic low(0V) and the devices are therefore permanently enabled. The Address/Data buscontents are thus transferred to the buffers’ output when the Address Latch Enable[ALE> signal, connected to D5/D6 pin 11, goes high.
The buffered address bus is annotated (AX0....AX15) and is shown connected tothe ROM (D8) and RAM (D9) memory. It is also connected to the peripheral de-vices shown on the circuit diagram sheet 4.
Data bus buffer
A type 74HCT245 octal bus transceiver (D7) is employed as bi-directional bufferbetween the microcontroller (D0....D7) and the data bus (DX0....DX7).
The data direction through D7 is controlled by the microcontroller’s [RD-> output.Thus, when the microcontroller drives its [RD-> output low it sets the data direc-tion from B to A through the buffers (See appendix A.1), which allows the databus contents through to the microcontroller’s data inputs. At other times, when[RD-> is high, data flows through the buffers from A to B, allowing the micro toplace data onto the data bus which can then be written to a peripheral circuit asrequired.
s7-c4.fm5 - Issue 2 Dated 21/08/97 7-139
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 5 - Operator Logic Board
Control bus buffer (diagram sheet 4)
Two 74HCT245 devices serve as the control bus buffers (D18 & D17). These areidentical to the data bus buffer but have a fixed data direction (A-to-B) as pin 1 ispermanently connected to +5V in each case. D17 interfaces the tactile switches(ENTER, UP, DOWN) and the three mimic LEDs on the Operator Control Panel.D18 deals with the 6-segment bargraphs (%load & autonomy time) and the con-trol bus [RD> and [WR-> signals. The buffered control signals [RDX-> and [WRX->,
are used by various devices distributed throughout the circuit diagrams.
In all cases the above mentioned buffers have pull-up resistors connected to theirinput and output pins to protect their internal logic – e.g. resistor packs R52 - R54.
5.3.4 Reset generator
(circuit diagram sheet 3.)
A purpose-designed Supply Voltage Supervisor (N4) provides the micro with aone second logic low [RSTIN-> reset signal on power-up. This logic low pulse,which is applied to the micro pin 27, can also be initiated manually by ‘making’jumper X26 (1-2). It also sends a logic high reset signal [RSTO-> to the ‘addressdecoding’ circuit (D10) from where it resets the peripheral devices via their ap-propriate ‘chip select’ or ‘chip enable’ inputs (See paragraph 5.3.6).
Note: the reset time is determined by R4/C1, and begins when the +5V supply railreaches 3.6V on initial power-up.
5.3.5 Alarm buzzer
(circuit diagram sheet 3.)
The alarm buzzer is driven by the processor’s port 3.0 output via driver transistorV11. Various alarm sound sequences are used to annunciate different types ofalarm warning and responses. These are obtained by the processor producing var-ious mark:space drive waveforms and are therefore strictly processor dependant.
During troubleshooting the alarm sounder can be inhibited by fitting a jumper toX23 (1-2) which clamps the base of V11 to 0V and prevents it from turning on.
5.3.6 Address decoding – D10
(circuit diagram sheet 3.)
The microcontroller communicates with
• the system memory – RAM and ROM (D8 and D9).• the Operator Control Panel – via connector X1.• the UPS Logic Board – via D12 and the CAN Bus.• the Serial Line Controller (D11) – which interfaces with the RS232 and
RS485 communications facilities.Under the control of the micro, the ‘address decoding’ circuit (D10) produces in-dividual ‘enable’ signals for each of the above mentioned devices which allowsthe micro to select a particular device with which it wishes to communicate at anypoint in time.
D10 is a purpose-designed ASIC chip which decodes address lines AX11...AX17
together with the control bus [RD->, [WR-> and [RSTO-> lines, and from theseinputs it provides the following controlled signals:
• [CSEPR-> – logic low selects the EPROM memory chip (D8).
• [CSRAM-> – logic low selects the RAM memory chip (D9).
7-140 s7-c4.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 5 - Operator Logic Board
• [CSCAN-> – logic low selects the CAN bus interface (D12 on sheet 4).• [CSER-> – logic low selects the Serial Line Controller (D11 on sheet 4).• [CSDISP-> – logic low selects the Operator Control Panel (X1 on sheet 4).• Buffered AX16 and AX17 address bus lines.
5.3.7 System RAM and ROM memory addressing
(Refer to diagram sheet 3.)
Figure 7-32: AX14 & AX15 decoding configuration links
The system memory comprises a 256k EPROM (D8) and 256k of RAM (D9).
AX14 & AX15 configuration links
The Operator Logic Board has been designed to ease future software upgrades byincluding configuration links to permit the addressing of alternative memory de-vices. These links affect the routing of the AX15 and AX16 address lines, and thestandard configuration is shown in Figure 7-32.
EPROM (D8) Configuration. In the standard configuration the signals anno-tated [PIN29EP> and [PIN3EP> are connected to EPROM D8’s A14 and A15 inputsand are therefore driven by the AX14 and AX15 address lines respectively. The[PIN31EP> input to D8 is concerned with selecting the “program” mode, and is leftopen circuit due to the lack of jumper on X14. [PIN30EP> is held at a permanent+5V (due to the jumper 2-3) on X12.
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
4
5
4
5
X14 X19
X15 X18
X16 X17
[AX15>
[AX14>
[PIN29EP>
[PIN3EP>
[PIN31RAM>
[PIN3RAM>
[WRX->
[PIN31EP>
[RDX->
+5V
[PIN29RAM>
3
2
3
2
1
X12 X13
[PIN3EP> D9 pin 281
[AX17>
s7-c4.fm5 - Issue 2 Dated 21/08/97 7-141
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 5 - Operator Logic Board
Two conditions must be satisfied to connect the device’s D0....D7 outputs to thedata bus. First, the EPROM’s ‘output enable’ pin (pin 24), which is controlled bythe control bus [RDX->, must be low. Second, the ‘chip select’ (CS) input to pin22, which is connected to the buffered [AX16> address line obtained from D10,must also be low. Note that [AX16> is not subject to the [ALE> signal switchingthrough D5/D6 and is therefore permanently accessible by the processor.
RAM (D9) Configuration. In the standard configuration the signals annotated[PIN29RAM> and [PIN3RAM> are connected to the RAM’s A14 and A15 inputs.
[PIN29RAM> is not used and is open-circuit due to the lack of jumper fitted to X17pin 2. [PIN3RAM> is connected to the buffered Address line [AX14> due to thejumpers on X18 and X17
Once again, two conditions must be satisfied to connect the device’s D0....D7 out-puts to the data bus. First, the RAM’s ‘output enable’ pin (pin 22), which is con-trolled by the control bus [RDX->, must be low. Second, the ‘chip select’ (CS)input to pin 20, which is connected to the [CSRAM-> output from D10, must alsobe low.
5.3.8 Interface to the Operator Control Panel
(circuit diagram sheet 4 – see also drawing SM-0360803-B sheets 2/3.)
The Operator Control Panel is connected to X1 and its interface signals can besegregated into three areas; namely LED Driver; LCD Driver; and Push-buttonDetection – each of which is described below.
LED Driver
Multiplexed power supplies. The operator control panel contains 17 leds ar-ranged in three ‘banks’ – two banks of 6 led and one bank of 5 leds. The anodesof all the leds forming a particular bank are connected, via current limiting resis-tors, to a common +5V power supply; therefore three supplies are required intotal. Referring to the diagram sheet 4, these supplies are obtained by three mul-tiplexed signals ([LD7>, [LD8>, [LD9>) which are produced by the microcontrollerand then buffered by D17 and transistors V12-V14 to provide [LC0>, [LC1>, [LC2>.These transistors are thus switched sequentially (i.e. “strobed”) to provide thepositive power feed to each ‘bank’ of leds in turn.
LED Control. Each ‘bank’ of leds are controlled by a common control bus pro-duced by the microcontroller annotated [LD1> to [LD6>. These signals are bufferedby D18 and connected X1 as [LD0> to [LD5>. As the micro strobes the positivesupply to each ‘bank’ of leds it drives its control bus lines ‘low’ to illuminate aparticular led within the ‘bank’. By driving the leds in this manner the micro hasfull control over which leds are illuminated.
Note: the positive supply is strobed at a rate of 83.3Hz and therefore the leds donot appear to flicker when illuminated.
LCD Driver
The LCD Display device on the Operator Control Panel displays 4 lines of twentycharacters and is used to indicate status information, alarm warning messages andalso provides the messaging system used by the operator to select various opera-tional parameters.
The textual message information is stored in the Operator Logic Board’s ROMand output to the Operator Control Panel by the microcontroller, via the data bus
7-142 s7-c4.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 5 - Operator Logic Board
[DX0> to [DX7>, at convenient intervals in a suitable form which can be interpretedby LCD display device.
As the microcontroller “sees” the LCD device as just another device on the databus it must also provide a means of addressing it when required. This is achievedthrough a combination of the [CSDISP> ‘chip select’ signal from the address de-coding circuit of D10 (See paragraph 5.3.6) and a ‘Write’ signal [RWDISP> pro-duced directly by the processor port 1. To access the LCD display [CSDISP> mustbe taken ‘high’ and [RWDISP> ‘low’.
Note: A reset signal [RSDISP> is also produced by the micro port 1 which can to-tally reset the LCD display device.
Other lines connected to the LCD device are concerned with its power supply re-quirements. The device requires +5V at X1-32; 0V at X1-30 and X1-2; and a var-iable “contrast” supply in the range 0V to +5V at X1-4.
Push-button Detection
The five push-button on the Operator Control Panel are connected to a common0V supply presented to X1 pin 31 and, when pressed, they route this 0V back to:
• X1 pin 21 (UP)• X1 pin 23 (DOWN)• X1 pin 25 (ENTER)• X1 pin 27 (ESCAPE)• X1 pin 29 (ALARM CANCEL)
These signals, annotated [P-0> to [P-4>, are buffered by D17 and the resulting[TST1> to [TST5> signals are polled by the microcontroller at regular intervals toenable it to detect when a particular push-button is pressed.
5.3.9 Interface to the CAN Bus
(circuit diagram sheet 4.)
The Operator Logic Board uses the CAN bus to communicate with the UPS LogicBoard. This bus carries bi-directional data between these two boards; e.g. opera-tional status and alarm parameters are passed from the UPS Logic Board to theOperator Logic Board for processing and display on the Operator Control Panel.Selections made by the operator at the Operator Control Panel are passed via theOperator Logic Board to the UPS Logic Board to set the system operating param-eters.
The CAN bus (see appendix B) utilises an 82C200 controller and 82C250 inter-face chip, both of which are described in appendix A.
82C200 control signals. The CAN bus controller is connected to the micro-controller’s 8-bit data bus (DX0....DX7) in the same way as the other peripheraldevices. The microcontroller must therefore provide a means of addressing itwhen required. This is achieved through a combination of the [CSCAN> ‘chip se-lect’ signal from the address decoding circuit of D10 (See paragraph 5.3.6) andbuffered read/write signals ([RDX-> and [WRX->).
Note: an initialising reset signal [RSCAN> is also produced by the micro port 3which starts communications.
82C250 control signals. This device is described in detail in appendix A (Seeappendix A.10). Jumper X24 should be made 1-2 to connect the 120 Ohm line ter-mination resistor across its I/O line terminals. “High speed” mode is permanentlyselected due to pin 8 being grounded.
s7-c4.fm5 - Issue 2 Dated 21/08/97 7-143
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 5 - Operator Logic Board
5.3.10 Serial (modem) Interface
(circuit diagram sheet 4.)
Serial (modem) communications is afforded by D11, which is a type 8521A Uni-versal Synchronous/Asynchronous Receiver/Transmitter (USART) working inconjunction with D13, which is a bi-directional line driver device type LT1133.
8521A operation. This device (D11) converts the parallel data into a serial dataformat for transmission, and vice-versa for data reception. This device is de-scribed in detail in appendix A (See appendix A.8).
D11 is connected to the 8-bit data bus (DX0....DX7) and selected by a logic low[CSSER-> signal produced by the address decoding circuit. Read/Write control isafforded by the buffered [RDX-> and [WRX->, both of which are active ‘low’.
The microcontroller port 3 provides the 8521 with its general clock signal, [CLK-
SER> at approximately 1.25MHz, and also a reset signal [RESSER> which isactive ‘high’.
The Data/Control input (D11 pin 12) is controlled by the buffered address line[AX0>, which is ‘high’ for data transfer and ‘low’ for control word transfer.
The serial I/O data and control lines are interfaced to the modem port (X8) via theLT1133 driver circuit which converts the 8521A outputs to RS232C levels.
5.3.11 RS232 & RS485 Interface
(Refer to diagram sheet 4.)
Two of the controlled timers within the microcontroller (D2) are configured to op-erate as further communication interfaces. Data I/O transfer is processed via port3 with one port annotated [TXD0> & [RXD0>, and the other [TXD1> & [RXD1>. TheseI/O data lines are raised to RS232 levels by D19 (MAX232) and RS485 levels byD20 (75176) – D20 is controlled by the [RE485-> & [OE485> outputs from port 1.
RS232 communications via D19 and X5
The RS232 interface (D19) is provided by a standard MAX232 device (See ap-pendix A.7).
This is a dual channel device: channel 1 interfaces [TXD0> & [RXD0> which is per-manently connected to the RS232 I/O port at X5. Channel 2 interfaces [TXD1> &
[RXD1> and is connected to X4 via jumpers X20 (1-2), X21 (2-3), X22 (2-3). Thisis the “standard” configuration for these jumpers.
RS485 communications via D20 and X4
The RS485 interface (D20) is provided by a SN75176A differential bus transceiv-er (See appendix A.5).
This is a single channel device which interfaces [TXD1> & [RXD1> only, via jump-ers X20 (2-3), and is connected to X4 via jumpers X21 (1-2), X22 (1-2). Whenthe jumpers are configured in the above positions they effectively route the RS485communications through to X4 whilst still enabling RS232 communications atX5.
The transmit data and receive data flow is controlled through D20 by means ofthe [RE485-> & [OE485> inputs to pins 2 and 3. A truth table showing the full af-fects of these inputs is provided in appendix A (See appendix A.5).
7-144 s7-c4.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 5 - Operator Logic Board
5.3.12 Power Supply
(circuit diagram sheet 1.)
As many of the circuits on the Operator Logic Board are connected to external(possibly remote) devices, such as a modem, they are all powered from an isolated+5V power rail which is derived from an on-board dc-dc power converter basedon a purpose-designed current-mode PWM controller (UC3845). This controlleris fully described in appendix A (See appendix A.9).
Power circuit operation
The dc-dc converter’s input power is obtained from the UPS Logic Board’s ±12Vwhich is connected to X9 pins 1 and 3. This is filtered by C41 and L1/L2 to pro-vide an unregulated power rail of approximately 24V; although the -12V rail istaken as the 0V reference by the control electronics.
The converter operation is based on FET V10. When this device is turned ON itdraws current through the transformer primary (1-10) which induces opposingcurrents into the secondary windings – note the winding polarities.
In practice, V10 is driven by a variable PWM output from N1 (at a basic rate of40kHz) and the net result is an alternating current induced in winding 5-6 whichis full-wave rectified by V9 to provide a d.c. voltage smoothed by L3/C52/C53.This “smoothed” voltage is regulated at +5V by appropriately controlling V10’sPWM gate drive signal.
PWM control operation
The PWM controller (N1) is powered from a 16V zener-regulated supply ob-tained from the unregulated 24V rail – note that N1 requires a minimum of8.4Vdc to function correctly (See appendix A.9). The base PWM frequency is setto approximately 40kHz by R35/C44 (i.e. the PWM pulse repetition rate is ap-proximately 25µs.).
Current feedback signal. A current feedback signal is obtained from R40(0.33R) which is connected in series with the transformer primary currentswitched by V10. The voltage across this resistor will thus be proportional to thecurrent drawn through the primary winding when V10 is turned on. This currentfeedback signal is fed to N1 pin 1 which internally regulates the mark-to-spaceratio of the PWM output at pin 6 for load stepping and overloads.
Voltage feedback signal. A voltage feedback signal is obtained via an opto-coupled circuit which monitors the voltage across the isolated +5V rail. N3 is areference voltage generator which aims at maintaining 2.5V at its reference input(N3 pin 1 – i.e. at the junction of R47/R48). This means that it therefore attemptsto maintain +5V at the top of R47 – which is connected directly to the output +5Vrail.
If the +5V rail therefore rises above or falls below its nominal +5V level then N3will reduce/increase (respectively) the conduction through the opto-isolator,which is thus sensed by N1.
The feedback voltage is source via the +5V reference voltage produced by N1 atpin 8 and superimposed on the junction of R33 and R34 according to the amountof conduction of V21, as shown in Figure 7-33.
Indications. An led (H1 is connected across the isolated +5V rail and illumi-nates when this supply is correct.
s7-c4.fm5 - Issue 2 Dated 21/08/97 7-145
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 5 - Operator Logic Board
Figure 7-33: Voltage feedback signal
5.4 Summary information
Table 7-19: Operator Logic Board configuration jumpers
R3310k
R344k7
V21
VCC
VCC
ISENSE3
RT/CT4
O/P6
COMP1
VFB2
VREF8
75
N1
UC3842
R32
22k
5V(ref)
Outputvoltagesensing
JumperLink
Position Function
X11 OPEN +5v enable main CPU (Standard)
CLOSED ALE enable main CPU
X12 1 - 2 Main CPU enable EPROM
2 - 3 +5v enable EPROM (Standard)
X13 1 - 2 Main CPU enable RAM
2 - 3 +5v enable RAM (Standard)
X14 1 - 2 Not Required Testing OnlyOpen = Standard2 - 3 Not Required
X15 1 - 2 Main CPU enable EPROM (Standard)
2 - 3 Not Required
X16 1 - 2 Not Required
2 - 3 Main CPU enable EPROM (Standard)
3 - 4 Not Required
4 - 5 Not Required
X17 1 - 2 Write to RAM enable
2 - 3 Not Required
3 - 4 Main CPU enable RAM (Standard)
4 - 5 Not Required
X18 1 - 2 Not Required
2 - 3 Main CPU enable RAM (Standard)
7-146 s7-c4.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 5 - Operator Logic Board
Table 7-20: Operator Logic Board potentiometer adjustment
Table 7-21: Operator Logic Board LED indication
X19 1 - 2 Not Required RAM extensionNormally open2 - 3 Not Required
X20 1 - 2 Read/Write RS232 enable (Standard)
2 - 3 Read/Write RS485enable
X21 1 - 2 Enable port x4 for RS485
2 - 3 Enable port x4 for RS232 (Standard)
X22 1 - 2 Enable port x4 for RS485
2 - 3 Enable port x4 for RS232 (Standard)
X23 1 - 2 Inhibit buzzer
2 - 3 Enable buzzer (Standard)
X24 1 - 2 Enable CAN bus to UPS logic (Standard)
2 - 3 Disable CAN bus to UPS logic
X25 1 - 2 Enable RS485 bus to port x4 (Standard)
2 - 3 Disable RS485 bus to port x4
X26 OPEN +5v power supply reset enabled (Standard)
CLOSED +5v power supply reset disabled
Potentiometer Function
R21 Display contrast adjustment
LED Colour Function
H1 Green Internal power supply operating
JumperLink
Position Function
s7-c4.fm5 - Issue 2 Dated 21/08/97 7-147
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 5 - Operator Logic Board
7-148 s7-c4.fm5 - Issue 2 Dated 21/08/97
Section 7:
Chapter 6 - Operator Control Panel
6.1 Section overview
This section contains a circuit description of the Operator Control Panel usedacross the entire 7200 Series UPS model range, and should be read inconjunction with circuit diagram SE-0360803-B.
Signal annotations shown on the circuit diagrams are shown in italics in thefollowing text – e.g. [CLC2>.
6.2 General description
6.2.1 Circuit board functions
The Operator Control Panel functions can be summarised as follows:
• LED Display indication–This board contains LED which provides the operator with various statusindications – i.e. UPS module mimic; load bargraph; battery charge/auton-omy time bargraph; alarm warning indication.
• Operator input switches–The Operator Control Panel switches provide the means for the operator toeffect system control through a menu/messaging system.
• LCD Display Panel–The LCD display panel provides status and alarm messages for the opera-tor together with the menus used by the operator in setting up and interro-gating the UPS control system.
6.2.2 Input/Output connections
All input/output signals are connected to the Operator Logic Board via a single34-way ribbon connector.
s7-c5.fm5 - Issue 2 Dated 21/08/97 7-149
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 6 - Operator Control Panel
6.3 Detailed circuit description
6.3.1 LED Display indication
Figure 7-34: LED Display indication
The operator control panel contains 17 leds arranged in three ‘banks’ as shown inFigure 7-34 – two banks of 6 led and one bank of 5 leds.
• LEDs 1-5 provide module mimic indication, alarm active and battery CB• LEDs 6-11 provide the load bargraph indication and overload• LEDs 12-17 provide the battery charge bargraph indication and autonomy
The anodes of all the leds forming each of the above ‘banks’ are connected, viacurrent limiting resistors, to a +5V power supply. These +5V supplies are provid-ed by three multiplexed signals ([LC0>, [LC1>, [LC2>) which are provided by theOperator Logic Board – i.e. these supplies are “strobed” to provide the positivepower feed to each ‘bank’ of leds in turn (See paragraph 5.3.8) .
Each ‘bank’ of leds are controlled by a common control bus produced by theOperator Logic Board annotated [LD1> to [LD6>. As the positive supply is strobedto each ‘bank’ of leds, the leds illuminate according to which of the control buslines are ‘low’. By driving the leds in this manner the microcontroller on theOperator Logic Board has full control over which individual leds are illuminatedat any particular time.
Note: the positive supply is strobed at a high frequency and therefore the leds donot appear to flicker when illuminated
R1
2
R2
3
R3
4
R4
5
R5
6
R6
7
R7
8
R8
9
C1
R3
D17
D16
D15
D14
D13
D12
R1
2
R2
3
R3
4
R4
5
R5
6
R6
7
R7
8
R8
9
C1
R2
D11
D10
D9
D8
D7
D6
R1
2
R2
3
R3
4
R4
5
R5
6
R6
7
R7
8
R8
9
C1
R1
D4
D3
D2
D1D5
X7-5
X7-3
X7-1
X7-7
X7-9
X7-11
X7-13
X7-15
X7-17
LC0
LC1
LC2
LD5
LD4
LD3
LD2
LD1
LD0
7-150 s7-c5.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 6 - Operator Control Panel
6.3.2 Operator input switches
Figure 7-35: Operator switches
The five push-button on the Operator Control Panel are connected to a common0V supply presented to X7 pin 31 from the Operator Logic Board; when pressed,they route a 0V signal (annotated [P-0> to [P-4>) back to the microcontroller onthe Operator Logic Board via the connections shown in Figure 7-35.
6.3.3 LCD Display Panel
Figure 7-36: LCD Display module
S1
UP
S2
DOWN
S3
ENTER
S4
ESCAPE
S5
ALARM CANCEL
X7-31
X7-21
X7-23
X7-25
X7-27
X7-29
0V
P4
P3
P2
P1
P0
D07
D18
D310
D411
D512
D613
D714
VDD2
VL3
R/WR5
RS4
E6
+5VK
0VA
D29
VSS1
LCD_MODULE
X7-14
X7-16
X7-18
X7-20
X7-22
X7-24
X7-26
X7-28
X7-4
X7-6
X7-2
X7-10
X7-8
X7-12
X7-32
X7-304 x 20
s7-c5.fm5 - Issue 2 Dated 21/08/97 7-151
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 6 - Operator Control Panel
7-152 s7-c5.fm5 - Issue 2 Dated 21/08/97
Section 7: UPS System Control
Chapter 7 - System software
7.1 Introduction
The general UPS control operation is based on the microcontroller system con-tained on the UPS Logic Board, as described in chapter 3 of this section (see par-agraph 3.3.2 on page 7-24). The following description explains in basic termshow the microcontroller system is programmed to operate and provides details ofthe conditional flowcharts applicable to the major UPS control signals (e.g. recti-fier OFF/ON, inverter OFF/ON, load transfer control).
Despite the fact that the software is not generally accessible to the service engi-neer, an understanding of some of the sub-routines described later can be an in-valuable troubleshooting aid to differentiate between the ‘cause and effects’ ofcertain conditions.
The “C” programming language used to write the system software is closely re-lated to the actual digital processing, and comprises a sequence of instructionswhich determines the microcontroller operation. The program is held in two 512kRead-Only Memory chips (EEPROM) D35 & D46 which are accessed by the mi-crocontroller via the system address and data busses. D20 is also a ROM device,and contains initialisation data.
Although it does not contain the “system software” itself, the Random AccessMemory (RAM) holds important data concerning the system’s operation, such asthat programmed by the operator from the Operator Control Panel, which is re-quired by the main program. Battery back-up is provided to maintain such datawhen the UPS is powered down. RAM also provides a temporary store for dataproduced by the main program during its routine execution.
7.2 Program structure and execution
Initialisation
When the UPS is first powered up the microcontroller receives a 1 second resetpulse from the reset generator (see paragraph 3.3.5 on page 7-27) which forcesthe micro to read the instruction contained in a particular memory location (usu-ally 0000). This is the start point of an initialisation routine which sets up the com-plete microcontroller system in readiness for entry into the main program. Theinitialisation routine performs functions such as configuring the microcontrollerI/O ports, peripheral communication ports and protocols, internal timers and A/Dconverters; and reading system data (such as UPS module rating and configura-tion) from the non-volatile RAM. Some of these functions are performed onceonly during the initial set-up whilst others are also revisited during the main pro-gram execution – e.g. if the module kVA rating or single/parallel configurationdata is changed whilst the module is running it will not affect the main programuntil the microcontroller is reset.
Note: the reset generator can also be triggered manually through the selection ofjumper X28; however, if a reset is applied whilst the UPS is running it will crashdue to the rectifier, inverter and static switch all being turned off during the resetperiod. USE WITH CAUTION!
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-153
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
Main program
The system software will enter its main program once the initialisation routineshave been completed. The main program comprises a series of instructions whichare executed sequentially in a continuous loop (See Figure 7-37).
Figure 7-37 shows that the main program operates on two levels; identified in theillustration as the ‘foreground’ and ‘background’ routines. Notice that both the‘foreground’ and ‘background’ routines call various ‘sub-routines’ whilst work-ing through the main program loop. A sub-routine is a self-contained “mini-pro-gram” that can be called from various points in the main program loop.
The ‘foreground’ routine services vital functions which are required to be per-formed at regular intervals, or at a particular time, in order to secure proper systemcontrol: while the ‘background’ routine is of secondary importance and executedon an opportunity basis when the ‘foreground’ routine is idle. For example, thesub-routine that checks that the inverter output voltage is within limits is consid-ered ‘critical’ and is called every 250µs; while the sub-routine that checks thestate of the inverter ON/OFF menu selection is less-critical and perhaps executedonce per second. All program timing functions are tied to the microcontrollersystem clock (20MHz), which also synchronises the address/data bus transfer op-erations, and the microcontroller’s internal programmable timers.
A successful ‘real-time’ program requires that the main program loop is complet-ed as fast as possible and it is therefore good practice to return to the main pro-gram from a sub-routine as quickly as possible.
‘Background routine’
The background routine is responsible for managing the calculation of the voltageand current signals produced by the A/D converters and storing the results in theappropriate RAM memory locations from where they are read at regular intervalsby the foreground routine. It also reads the condition of the Operator ControlPanel buttons and sets status flags in the RAM memory.
‘Foreground routine’
The foreground routine calls a series of sub-routines to carry out a check of themany variables and status flags held in memory and perform various functions de-pending on the results – i.e. the sub-routines make decisions based on the state ofthe memory contents that they read.
For example: a sub-routine that controls the state of the [REC_ON> signal is calledevery 500msecs. This signal determines whether or not the rectifier is requestedto turn ON (see page 7-33) and in making the decision, the sub-routine looks atthe following status flags stored in memory:
• the manual ‘rectifier inhibit’ switch status (UPS Logic Board).
• the rectifier fuse fail status.
• the selected rectifier ON/OFF status (from Operator Control Panel menuscreen).
If all three of the above conditions are conducive to starting the rectifier, the soft-ware will drive the [REC_ON> signal high which turns on the rectifier, and alsosends a status signal via the CAN bus to inform the display system of the new rec-tifier status. Several other sub-routines which control similar signals to[REC_ON>, and are therefore of prime interest to the service engineer, are illustrat-ed in detail later in this chapter.
7-154 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Figure 7-37: Main program “Foreground” and “Background” routines
:
:
:
:: : : :
: :Low BattWarning
flag_2INV_ON
: :DC Overvoltage
flag_3
: :In. VoltsWindow
flag_4
Vb=432 Ib :Inv. VoltsWindow
flag_1REC_ON
Vout
Vinv
Vin
START
Set Initial flags
If clock=0001 ExecSUB: INV-ON
If clock=0010 ExecSUB: REC_ON
If clock=0150 ExecSUB: SYNC_OK
If clock=0200 ExecSUB: IB_OPEN
:::
If clock=nnnnExecute SUB: nnnn
:
Return to START
Fo
reg
rou
nd
Ro
utin
e
SUB: INV-ONSee Flow-chart 1
SUB: REC-ONSee Flow-chart 2
SUB: SYNC_OKSee Flow-chart 3
SUB: IB_OPENSee Flow-chart 4
Page 1
Page 2
RAMMEMORY
CPUClock
START
Calculate Vb
Calculate Vinv
Calculate Ib
:::
Set Flags
Check DisplayButtons
:::
Return to START
Backg
round R
outin
e
SUB: Look-up A/Dinput (Vb)
Running inbackground
Start
CHK Vb
CHK Vin
..........
..........
..........
..........
..........
..........
..........
End(Return to start)
Bac
kgro
un
d R
ou
tin
es
Begin SUB:
Question 1? No
End SUB:
Process A
Question 2
Process D
NoProcess B
Process C
Yes
Sub-Routine 1
Sub-Routine 2
Start
Execute Chk1 if t=0.5µs
Execute Chk2 if t=100µs
..........
..........
..........
..........
..........
..........
..........
..........
..........
End(Return to start)
Ma
in P
rog
ram
me
Question a condition(e.g. Is Vb < undervoltage trip level)
Perform a function(e.g. Set BatU/V Flag - Trip battery etc.)
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-155
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
7.2.1 Initialisation/Reset
The system reset routine is activated when the UPS is first powered up or follow-ing the application of the hardware reset (see paragraph 3.3.5 on page 7-27). Note: the reset pulse is applied for approximately 10/20ms in order to allow the+5V power rail to stabilise.
The Initialise/Reset routine:
• resets the micro’s peripheral devices by forcing the output digital signalsto logic low (with the exception of the [SYNC>, [PWM1>, [PWM2>,
[PLLOU1> signals, whose states remain undefined).
• verifies no-reversal of the output digital connectors.
• initialises the software application into the working RAM
• starts the ‘watch-dog’ timer
• verifies that the EEPROM holds valid system parameters (See Chart 7-1).
• checks the nominal sync frequency
• checks the visual display and 7-segment led (for 5 seconds)
• returns a Pass/Fail status.
Checking the system parameter data
The initialisation/reset routine checks that the programmed system parameters areacceptable for the correct operation of the UPS equipment. The parameters areheld in three pages of the EEPROM. Page 1 holds the parameters set by the Op-erator Control Panel and pages 2 & 3 contain the internal parameters. A Longitu-dinal Redundancy Counter (LRC) is associated with each page to allow errorchecking.
Default values for the system parameters are held in fixed memory addresses inthe system EPROMS. The EEPROMs’ data can thus be reinitialised with theEPROM default values by following the “RELOAD DATA” procedure on theOperator Control Panel (see paragraph 2.4.7.5 on page 2-46). This should be car-ried out if an LRC error is found with the page associated with the Operator Panelentered data.
7-156 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-1: Initialisation/Reset
Return to main program
Does memorypage 2 initialse
correctly?
Begin SUB: [RESET>
Does memorypage 1 initialse
correctly?
Does memorypage 3 initialse
correctly?
Initialisation passed Initialisation failed
End SUB
Yes
Yes
Yes
Failed LRC P2set error 72
[ERROR LRC PAR PAG 2]No
Failed LRC P3set error 73
[ERROR LRC PAR PAG 3]No
Failed LRC P1set error 71
[ERROR LRC PAR PAG 1]No
Does UPSPower rating
parameter exist?
set error 70[BAD EEPROM PROGRAMM]
No
Is link X12 made 1-2?
Yes
Yes
No
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-157
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
7.2.2 Rectifier ON/OFF subroutine
This subroutine enables the software to control the rectifier ON/OFF function.
The sub-routine is affected by the following inputs:
• Rectifier fuse-fail monitor ([FUSREC>) –connected to X2 pin 49 from the fuse’s fault detection micro-switch. Afuse failure event activates alarm #25.
• ‘Rectifier Block’ (BLK_RAD>) –derived from the fault detection logic on the Rectifier Logic Board whichshuts down the rectifier if that board detects an internal fault (applied toX3 pin 33).
• Operator Control Panel ON/OFF selection ([TLC_REC>) –Applied via the CAN Bus from the Operator Logic Board. An OFF statusevent activates alarm #21.
The sub-routine produces the following output:
• Rectifier ON/OFF command signal [REC_ON>–connected as an input to D88 where it affects the logic state of the ultimaterectifier control signal [ON_REC> (see paragraph 3.3.7 on page 7-29).
This signal is applied via the CAN Bus from the Operator Logic Boardand activates alarm #20 [RECT: SOFTWARE BLOCK] when in its OFFstatus.
7-158 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-2: Rectifier RUN control [REC_ON>
Is theRectifier Block signalactive on the Rectifier
Logic Board?
Begin SUB: [REC_ON>(every 500ms)
Is theRectifier selected ON
at the Operator ControlPanel?
Is the RectifierFuse Failactive?
Set [REC_ON>output to ON(Logic high)
[Turn OFF Alarm #20]
Set [REC_ON>output to OFF(Logic Low)
[Turn ON alarm #20]
End SUB(return to main prog.)
Yes
Yes
No
No
No
Yes
D88
REC_ON
EPO
DC O/volts
Man Inhibit (Q3)
PS FAIL [ON_REC>To RectifierLogic Board
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-159
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
7.2.3 Inverter OFF/ON Sub-routine
This subroutine enables the software to control the inverter ON/OFF function
The sub-routine is affected by the following inputs:
• Battery voltage validation ([ST_BAT>) –as determined by the battery voltage monitor sub-routine (See Chart 7-7).
• Inverter block (BLK_INV>) –derived from the fault detection logic on the Inverter Logic Board whichshuts down the inverter if that board detects an internal fault (applied toX3 pin 33).
• Output Isolator status ([SW_OUT>) –connected to X2 pin 46 from Isolator’s auxiliary contact. When open, itinitiates alarm #03.
• Maintenance Bypass Isolator status ([SW_BYP>) –connected to X2 pin 45 from Isolator’s auxiliary contact. When Closed, itinitiates alarm #06.
• External ‘Inverter Block’ command ([BLK_EXT>) –connected to X8 pin 11 and applied via the optional Alarms InterfaceBoard.
• Operator Control Panel ON/OFF selection ([TLC_INV>) –applied from the Operator Logic Board via the CAN bus. When OFF, itinitiates alarm #31.
• Load status ([ST_CA>) – signifies load on inverter/bypass/open as determined by the load transfercontrol sub-routine (See Figure 7-39).
The sub-routine produces the following output:
• Inverter ON/OFF command signal [INV_ON>–connected as an input to D88 where it affects the logic state of the ultimateinverter control signal [ON_INV> (see paragraph 3.3.7 on page 7-29).This signal is applied via the CAN Bus from the Operator Logic Boardand activates alarm #30 [INV: SOFTWARE BLOCK] when in its OFF sta-tus.
7-160 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-3: Inverter RUN control [INV_ON>
Is the batteryvoltage within permissible
range?
Begin SUB: [INV_ON>(every 500ms)
Is anExternal Blockbeing applied?
Is theInverter Block signalactive on the Inverter
Logic Board?
Set [INV_ON>output to ON(Logic high)
[Remove alarm #30]
Set [INV_ON>output to OFF
(Logic low)[Activate alarm #30]
End SUB(return to main prog.)
No
Yes
Yes
D88
INV_ON
EPO
DC O/volts
Man Inhibit (Q2)
PS FAIL [ON_INV>
Are the OutputIsolator and Maint. Isolator
closed together?
Is theInverter selected ON
at the Operator ControlPanel?
Yes
No
No
No
Yes
Yes
No
To InverterLogic Board
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-161
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
7.2.4 Frequency synchronisation control
The Inverter synchronisation control is complex and, for the purpose of this de-scription, is divided into three flow charts.
Figure 7-38: Frequency synchronisation software block diagram
“Mains OK” routine. This routine is responsible for verifying that the bypasssupply is fully available and the bypass frequency is within the selected voltageand frequency window limits. The major output from this routine is monitored bythe Sync Source Selector routine which determines whether the inverter is to:
1. Synchronise to the bypass supply (if the bypass is valid).
2. Synchronise to the last available valid frequency – i.e. if the frequency goesoutside the sync-window the selected frequency will remain at the windowedge frequency for 1 minute (debounce) then revert to the internally gener-ated base frequency reference clock (50/60Hz). Note: when the bypass frequency returns to within the window the PLL willrevert to synchronising to the bypass after 1 second.
3. Synchronise to the internal reference clock if the bypass supply disappears.
The sub-routine is affected by the following inputs:
• Bypass R-phase frequency ([F-IN>) –Manufactured from X2 pin 15 via the High Voltage Interface Board.
• Nominal frequency (50/60Hz) –Selected via the Operator Control Panel and applied via the CAN bus.
• Acceptable sync window (±1Hz) –Programmed via the Operator Control Panel through the “set-up” menu,and applied via the CAN bus.
• Bypass voltage status (SVI) –This flag is set by another subroutine depending on the bypass voltage sta-tus – i.e:0 = OK (bypass voltage within the mimic-programmed limits [±10%])1 = LOW (bypass undervoltage [below -10%]) alarm #12 active.2 = HIGH (bypass voltage high [above +10%]) alarm #11 active.3 = ABSENT (bypass voltage less than 50V) alarm #10 active.
Mains OKRoutine
SyncSourceSelector
PLLCalculate
PhaseDisplacement
PLLSlewRate
Control
[F_IN>
[SVI>
Window LimitsSync
Source
[FOK>(alarm #13)
[PLL>
[BACK>
Error
[BLK_SYN>
[SYNC_OK>(alarm #35)
External Sync InhibitInverter Freq F/Back
[SYNC>
7-162 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
The sub-routine affects the following outputs:
• Frequency status flag ([FOK>) –OFF = FAULTON = OK.Disables/enables alarm #13
• PLL enable flag –Enables/disabled frequency slew-rate control (See Chart 7-5)
• Reference frequency status ([Sync Source>) –Selects the frequency value to which the PLL will lock – i.e. to the “Lastfrequency” or “internal clock.”
. Flow Chart 7-4: “Mains OK” Routine
Begin SUB: FrequencyCalculation
End SUB:Return to main program
YesHas the 1Secstability timer
expired?
Is the bypassfrequency within theselected window?
(±1Hz)
Is the bypassvoltage present?
(SVI = Not 3)Yes
NoNo
Yes
Set FOK = ON(bypass frequency is OK)
Sync Source = MAINS (1)
No
Set FOK = OFF(bypass frequency is not OK)
Annunciate alarm #13[BYP: FREQUENCY ERROR]
Reset delay counter = 0
Yes
Start the "re-enable" timer(1minute)
Set [PLL> flag = OFFDisable the PLL slew-ratre control
Sync Source = PREVIOUS (2)frequency (Use last available
frequency as reference)
Has the"1 min re-enable" counter
timed-out?
No
Yes
No
Has the 1Secstability timer
expired?
Increment the 1 sec "PLLre-enable" counter
Set PLL> flag = ONEnable the PLL slew rate
control
Sync Source = BASE FREQ (3)
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-163
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
Sync Source Selector. This subroutine enables the software to control the PLLfrequency selection (see paragraph 3.3.13 on page 7-55).
The sub-routine is affected by the following inputs:
• External sync inhibit ([BLK-SYN>) –connected to X8 pin 12 from External Alarms Interface option.
• External sync inhibit ([ON_GEN>) –One of the functions of the “On-Generator” input is to disable the invertersynchronisation (selected via the Operator control Panel SET-UP menu).
• Permission to enable sync inhibit operation ([GREL_BLK_SINC>) –this is a programmable parameter (see paragraph 2.4.7.3 on page 2-43).
• PLL Phase Locked ([PLL_ON>) –A software routine which determines if the inverter and bypass are within±9° of each other.PLL_ON = within ±9° of each otherPLL_OFF = not within ±9° of each other
• Timeout value for bypass frequency monitor ([FOK>) –this is a programmable parameter associated with the timeout of the“Bypass Frequency Not OK” status.
The sub-routine produces the following outputs:
• Sync Source –master frequency reference to the phase displacement calculation routine.
• PLL locked ([SYNC_OK>)Enables/Disables alarm #35
7-164 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-5: Sync Source Selector Routine
Is anexternal Block synch inhibit
signal being applied(BLK_SYN)?
Is theexternal block facilityenabled (ON_GEN) &(GREL_BLK_SINC)
Begin SUB: PLL Sync
End SUB:Return to main program
Sync Source = PresentPLL held to present frequency
Sync Source = BASE FREQPLL locked to internal clock
50/60Hz frequency
No No
Yes
Yes
No
SYNC_OK = OFF
Active alarm 35[INV: UNSYNCHRONIZED]
No
No
Is the mainsfrequency within theselected window?
(FOK=ON)?
Is the PLLphase locked within ±9°?
(PPL Flag=ON)
Has the mainsbeen out of limits for
> 10Secs?
Has the PLLbeen locked for at least
1 Sec?No
Yes
Sync Source = PREVIOUSPLL held to previous
frequency
No
SYNC_OK = ON
De-active alarm 35[INV: UNSYNCHRONIZED]
Yes
SYNC_OK = OFFActive alarm 35
[INV: UNSYNCHRONIZED]
From Mains frequency validation chart
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-165
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
Phase displacement calculation. This routine controls the rate of change ofthe inverter frequency in order to track the bypass supply frequency. The “target”slew rate is programmable via the Operator Control Panel – i.e. the amount of dis-placement error is multiplied the gain factor entered under the “Speed” menu onthe Operator Control Panel.
The sub-routine is affected by the following inputs:
• Sync Source –The is the master frequency reference as selected by the Sync SourceSelector and Mains OK routines. This reference may be:
a) Present frequency –Holds the inverter frequency constant at the present value when an exter-nal inhibit is applied (e.g. via the optional Alarm Board).
b) Previous frequency –If the mains frequency goes outside its window limits, this holds theinverter frequency constant at the last valid mains frequency (e.g. at thewindow edge frequency).
c) Base frequency–Reverts the inverter back to the Base Frequency if no mains reference fre-quency is available.
d) Mains frequency –Forces the inverter to track the bypass frequency as long as it remainsavailable and within the window limits.
• Inverter Frequency [BACK> –Actual inverter frequency as presented to the Inverter Logic Board.
The sub-routine produces the following outputs:
• Inverter Sync ([SYNC>) –Master frequency reference to the Inverter Logic Board.
• Error –A phase displacement is calculated depending on the relationship betweenthe two inputs (Sync Source & [BACK>). The detected error is then multi-plied by a programmed “gain” parameter, which is entered via the“Speed” display menu. This either speeds-up or slows-down the inverterclock (nominal 288kHz) on the Inverter Logic Board in order to make theinverter track the “Sync source” reference frequency.The “Gain” figure obviously affects the rate at which the inverter fre-quency is allowed to change while undertaking its tracking function, andis put into effect in the PLL Slew Rate Control Routine.
7-166 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-6: PLL Slew rate control (phase displacement calculation).
Begin SUB: PLL PhaseDetector
Is the "Out-of-phase"flag ON?
Calculate phase displacementbetween inverter [BACK> and
[Sync Source]No Yes
End SUB:Return to main program
Calculate phase displacementbetween inverter [BACK> and
[Sync Source]
Is the error greaterthan ±8°?
No
Calculate phase error direction(lead/lag)
Set "Out-of-phase" flag= ON
Add calculated "error" toinverter clock.
(Slew-rate control routine)
Calculated error w.r.t. slewrate gain (set via "Speed")
Yes
Is the error greaterthan ±9°?
Calculate phase error direction(lead/lag)
Set "Out-of-phase" flag= OFF
Add calculated "error" toinverter clock.
(Slew-rate control routine)
Calculated error w.r.t. slewrate gain (set via "Speed")
No
Set "Out-of-phase" flag= ON
Yes
Set "Out-of-phase" flag= OFF
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-167
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
7.2.5 Battery circuit breaker control
This subroutine enables software control of the battery circuit breaker via the[IB_OPEN> signal applied to U23 (see paragraph 3.3.7 on page 7-29).
This subroutine reacts to changes in the battery status flag (ST_BAT) which indi-cates whether the battery voltage is above the ‘slow overvoltage’ level, below the‘undervoltage trip’ level, or positioned satisfactorily between the two. Changes instatus affect the state of [IB_OPEN> after a suitable debounce period, which is ap-plied to prevent spurious operation. The debounce period of all three status chang-es are factory programmed independently.
The sub-routine is affected by the following inputs:
• Battery voltage ([VB>) –connected to X2 pin 27 via High Voltage Interface board
• Battery maximum threshold ([Vs_sup_bat>) –programmed via the Display menu system.
• Battery undervoltage trip threshold ([Vs_inf_bat>) –software calculated depending on discharge current (Ib) and programmedvia the Display menu system.
• Rectifier in Manual Mode status –command input from Operator Control Panel.
• Battery Test Mode status –enabled & programmed from Operator Control Panel.
• Battery Boost Charge Mode status –enabled & programmed via the Display menu system
• On-Generator status –when enabled (from Operator Panel) reduces the battery charge when theUPS is running On-Generator (see paragraph 2.4.7.3 on page 2-43) –requires Alarm Interface Board input.
The sub-routine affects the following outputs:
• Battery status flag ([ST_BAT>) –depending on the measured battery voltage, [ST_BAT> can have one ofthree possible values; – [ST_BAT> = BAT_BAS (battery undervoltage alarm [53])– [ST_BAT> = BAT_ALT (battery overvoltage alarm [55])– [ST_BAT> = BAT_OK (battery voltage within acceptable range).
• Battery circuit breaker control ([IB_OPEN>) –connected as an input to D88 where it affects the logic state of the ultimateBattery Trip signal [BAT_TRP> (see paragraph 3.3.7 on page 7-29) – logichigh trips the battery breaker and low ‘enables’ it.
7-168 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-7: Battery Control
To Next PageIs the battery
voltage (VB) below theset low volts level?
(Vs_inf_bat)
Begin SUB: Battery circuitbreaker control
Is ST_BATalready flagging an
undervolts trip status?(BAT_BAS)
Yes
Yes
End SUB:Return to main program
No
Has the LowDC condition been
present for longer than1Sec?
No
Set ST_BAT to BAT_BAS to flag Low Voltage Trip
-activate alarm [53]
Yes
Set IB_OPEN high to open thebattery circuit breaker
No
D88
[IB_OPEN>
M_BAT_MA
M_ESD
RESET BAT_TRIP
HIGH
(See Chart 7-9)
(Executed every 500ms)
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-169
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
Flow Chart 7-7: Continued......
End SUB:Return to main program
Is the batteryvoltage above the setslow overvolts level?
(Vs_sup_bat)
Is ST_BATalready flagging a
slow overvoltage status?(BAT_ALT)
Yes No
Yes
Is the battery inTEST; MANUAL or
BOOST mode?Yes
No
No
No
Is theON GENERATOR block
applied?Yes
No
D88
[IB_OPEN>
M_BAT_MA
M_ESD
RESET BAT_TRIP
HIGH
Has the LowDC condition been
present for longer than1Sec?
Set ST_BAT to BAT_ALT to flag High Voltage Trip
-activate alarm [55]
Yes
Set IB_OPEN high to open thebattery circuit breaker
From Previous Page
To Next Page
7-170 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-7: Continued......
End SUB:Return to main program
Is ST_BATalready flagging an
OK status?(BAT_OK)
Yes
Has the DC Busbeen stable for longer
than 5 secs?
Set ST_BAT to BAT_OKto flag Battery OK
- for Alarm Interface board
Set IB_OPEN low to enablethe battery circuit breaker
Yes
No
No
No
D88
[IB_OPEN>
M_BAT_MA
M_ESD
RESET BAT_TRIP
LOW
From Previous Page
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-171
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
7.2.6 Low Battery Pre-alarm
This sub-routine controls the annunciation of the [DC BUS: UNDERVOLTAGE]warning (alarm # 56) when the battery voltage falls to a value just above the un-dervoltage trip voltage.
A delay counter provides a 1 second delay between a change in alarm status andthe alarm indication to prevent spurious operation.
The sub-routine is affected by the following inputs:
• Battery voltage ([VB>) –connected to X2 pin 27 via the High Voltage Interface board.
• Battery Pre-alarm operating threshold ([Vs_pre_al_bat>) –programmed via the Operator Logic board and applied via the CAN bus.
The sub-routine affects the following outputs:
• Battery Pre-alarm status flag ([sta_pre_bat>) –enables/disables [ DC BUS UNDERVOLTAGE ] alarm [#56].
7-172 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-8: Low battery pre-alarm
Is the batteryvoltage (VB) below the
pre-alarm voltslevel?
Begin SUB: Battery LowVoltage Pre-Alarm
Is alarm #56[DC BUS: UNDER-VOLTAGE] active
at present?
Yes
No
End SUB:Return to main program
Yes
Has VB beenbelow pre-alarm level for
longer than 1Sec?No
Display alarm #56[DC BUS: UNDERVOLTAGE]
Yes
Is alarm #56[DC BUS: UNDER-VOLTAGE] active
at present?
No
No
Has VB beenabove pre-alarm level for
longer than 1Sec?
Remove alarm #56[DC BUS: UNDERVOLTAGE]
Yes
Yes
No
(Executed every 500ms)
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-173
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
7.2.7 Battery undervoltage trip threshold
This sub-routine calculates the battery undervoltage trip (End-of Discharge) ref-erence level ([Vs_inf_bat>) used in the battery circuit breaker control sub-routine(See Chart 7-7).
The operating threshold value depends on the percentage battery current beingdrawn; basically, the undervoltage trip voltage is raised by 10% if the battery dis-charge current is less than 10% of its fully-rated current. This is to prevent the bat-tery from undergoing a prolonged low-level discharge and thus enhances theoverall battery performance and working life.
The sub-routine is affected by the following inputs:
• Battery current ([IB>) –from X2 pin 31 via the High Voltage Interface board.
• Battery circuit breaker status ([SW_BAT>) –from X2 pin 53 via the High Voltage Interface board.
• Number of battery elements –entered via Operator Control Panel and applied via the CAN bus.
• Nominal ‘End-of-discharge’ voltage (V/Cell) –entered via Operator Control Panel and applied via the CAN bus.
• Background task results –2 flags are set in RAM by a background sub-routine, calculated as follows:NOMINAL = N. BATT. EL x END DIS.110% NOMINAL = NOMINAL + 10%
N. BATT. EL. = Number of battery cells connected in the string, as enteredvia the “SET UP” Display menu.END DIS. = Minimum discharge voltage per battery cell, also entered viathe “SET UP” Display menu.
Example: if 198 cells & end of discharge = 1.67V/Cell then:NOMINAL = 330.6V and 110 NOMINAL = 363.76V
The sub-routine affects the following outputs:
• Battery undervoltage trip reference ([Vs_inf_bat>) –(See Chart 7-7)
7-174 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-9: Battery undervoltage trip threshold
Is the battery circuitbreaker open?
Begin SUB: Battery undervoltagethreshold selection
No
No
End SUB:Return to main program
Is the battery current less than 10% ?
Yes
Use the upper level
Vs_inf_bat = 110% NOMINAL
Yes
Use the lower level
Vs_inf_bat = NOMINAL
(Executed every 500ms)
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-175
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
7.2.8 Battery Boost charge
This sub-routine determines when the Rectifier Logic Board is requested to oper-ate in the Boost Charge mode (see paragraph 2.3.2 on page 4-26).
Boost charge is enabled from the Operator Control Panel and can be invokedManually or Automatically.
• Manual selection puts the charger in an immediate Boost mode.
• Automatic Boost mode is invoked if the charge current is greater than aprogrammed threshold level for 1 minute following the return of the mainssupply after an outage. The system remains in the boost mode until eitherthe battery current falls below the threshold for 5 seconds, or the boostcharge timer (up to ten hours) expires (in which case an error is flagged –alarm #54 – and further Boost charge operation is locked out.
The sub-routine is affected by the following inputs:
• Battery current ([IB>) –from X2 pin 31 via the High Voltage Interface board.
• Automatic Boost charge enable/inhibit –selected from Operator Control Panel and applied via the CAN bus.
• Manual Boost charge requested–selected from Operator Control Panel and applied via the CAN bus.
• Battery in Test mode –flag set by another sub-routine (See Chart 7-11).
• Rectifier in Manual mode –flag set by another sub-routine.
• On-Generator mode –flag set by another sub-routine.
• Automatic changeover threshold –programmable from Operator Control Panel (default = 10% of battery cur-rent limit threshold) and applied via the CAN bus.
• 1 minute timer –to determine when to enter Auto Boost Mode – factory default setting.
• 5 second timer –to determine when to exit Auto Boost under normal conditions (i.e. batteryregains its charge) – factory default setting.
• Boost Mode timer (to 10 hours) –to determine when to exit Boost Mode under fault conditions (i.e. batteryfails to regain its charge and charge current remains high). Programmablefrom Operator Control Panel and applied via the CAN bus.
The sub-routine affects the following outputs:
• Charge Mode selection signals ([REC_A> and [REC_B>) –selects charge mode on Rectifier Logic Board.
• Boost charge status flag –signalling boost active/inactive/timeout
• Alarm #54 driver [BOOST: TIME EXPIRED]signalling boost charger timer expired.
7-176 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-10: Battery Boost
Is BATTERY TESTrequest active?
Begin SUB: Boost charge
End SUB:Return to main program
Reset "Batt-in-BOOST" flag to OFF(i.e. Stop Boost charge even if it is
already in progress)
No
Increment 1 minute delaytimer
Is the batterycurrent > 10% of therated Batt. current
limit?
Has BOOSTmode been manually
selected?
Has delaytimer reached its
terminal count(1min)?
Is the Automatic BOOST function
enabled?
Is anON GENERATORcondition active?
Is rectifier inMANUAL mode?
No No
No
Yes
No
Yes
No
Start BOOST charge timer
Yes
Set the "Battery In BoostCharge" flag = ON.
Request "BOOST ChargeMode" to Rectifier Logic Bd
(REC_A=0 / REC_B=1)
Is the batterycurrent > 10% of the rated
current limit?Increment 5 second timer
Has timerreached its
terminal count(5 sec)?
No
Yes
Yes
Increment BOOST Chargetimer
HasBOOST charge
timer reached its terminalcount (10Hrs
max)?
Activate alarm #54 (latched)[BOOST: TIME EXPIRED]
Request "FLOAT Charge Mode" toRectifier Logic Bd (REC_A=1 /
REC_B=0)Yes
No
Is alarm #54already active (latched)
[BOOST: TIMEREXPIRED]?
No
No
No
Yes
Request "FLOAT Charge Mode"to Rectifier Logic Bd (REC_A=1
/ REC_B=0)
Reset 5 second timer
Reset 5 second timer
Yes Yes Yes
(Executed every 500ms)
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-177
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
7.2.9 Battery Test
A “Battery Test” routine is enabled from the Operator Control Panel and can beinvoked Manually or Automatically at a set date and time (see paragraph 2.4.7.2on page 2-42). When the TEST is invoked the rectifier is turned off and the bat-teries are discharged for a predefined period (nominally 5 minutes). A check ismade during the TEST period to ensure that the battery voltage does not fallbelow a predefined minimum value (nominally 1.9V/Cell). If the battery fails thischeck an alarm is annunciated and the rectifier is turned back on to take over thesupply to the inverter.
The battery test subroutine handles the management of the Test process.
The sub-routine is affected by the following inputs:
• Battery voltage ([VB>) –connected to X2 pin 27 via High Voltage Interface BOard
• Automatic Test date/time start details –programmed via the Operator Control Panel and applied via the CAN bus.
• Final test voltage threshold (1.9V/cell) –programmed via the Operator Control Panel and applied via the CAN bus.
• End-of-test (FAIL) debounce delay(1.5s) – factory-fixed delay time to prevent spurious detections
• Automatic Test duration period –programmed via the Operator Control Panel and applied via the CAN bus.
• Battery Test request (manual) –programmed via the Operator Control Panel and applied via the CAN bus.
• Battery Test request (auto) –programmed via the Operator Control Panel and applied via the CAN bus.
• ‘Rectifier in Manual’ status flag ([st_rad_man>) –flag set by another sub-routine.
• ‘On Generator’ status flag ([st_grel_blk_car>) –flag set by another sub-routine.
The sub-routine affects the following outputs:
• Charge Mode selection signals ([REC_A> and [REC_B>) –selects charge mode on the Rectifier Logic Board (see paragraph 2.3.2 onpage 4-26).
• State of test result on exit ([TST_BAT>) –OFF = OK and ON = FAIL.enables alarm #51 driver [BATTERY: TEST FAILED]
• ‘Battery in test’ mode status flag ([abil_tst_bat>) –ON = Test in progressenables alarm #50 driver [BATTERY: UNDER TEST ]
•
7-178 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-11: Battery Test
(Executed every 500ms)Begin SUB: Battery TEST(Initialisation request)
End SUB:Return to main program
Set TST_BAT to OFF (Stopthe Battery Test even if it is
already in progress)
NoIs a Manual
OR Automatic Testrequest active?
Is anON GENERATORcondition active?
Is rectifier inMANUAL mode?
No
YesYes
Is theprogrammed testduration >0mins?
Increment test duration counter
Set [abil_tst_bat> flag=ON.Annunciate alarm #50
[BATTERY: UNDER TEST]
Request "TEST Mode" toRectifier Logic Bd
(REC_A=1 / REC_B=1)
set [TST_BAT> = ON(enable the TEST flag)
No
Yes
Is [tst_bat> = ON(test enabled)?
Yes
Has the TESTduration counter
reached its final count?(5 mins)
Yes
Is the batteryvoltage below the
test threshold?(1.9V/cell)
No
Yes
Set [TST_BAT> = OFF(Stop the battery test))
Remove alarm #50[BATTERY: UNDER TEST]
Increment delay counter
Yes
Has the delay counter reached its
terminal count?(1.5s)
Reset delaycounter to 0
Yes
Reset delaycounter to 0
Activate alarm #51[BATTERY: TEST FAILED]
Request "FLOAT Mode" toRectifier Logic Bd
(REC_A=1 / REC_B=0)
Reset the test durationcounter to 0
No
No
No
No
No
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-179
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
7.2.10 Load transfer control logic
7.2.10.1 Transfer control system overview
The Transfer Control Logic consists of four sub-routines, each of which is asso-ciated with a particular transfer control logic state. During each cycle of the mainprogram (100µs), only one of these four routines is executed, as determined bythe state of the “Load Status Flag” (ST_CA): namely –
• “initialisation” mode (ST_CA = 0).
• “load-on-bypass” mode (ST_CA = 1).
• “load-on-inverter” mode (ST_CA = 2).
• “out-of-sync transfer” mode (ST_CA = 3).
That is, the four routines comprising the Load Transfer Control Logic themselvesform a closed loop which is accessed every 100µs, whereby the selected routineto be executed is determined by the condition of the “Load Status Flag” (ST_CA)set on the previous pass. This is illustrated in Figure 7-39.
Example
Assuming that ST_CA is currently set to “1” (load-on-bypass mode).
The load-on-bypass sub-routine’s preferred action is to transfer the load to the in-verter, after first examining the inverter output voltage status and confirming thatit’s OK.
If the inverter voltage status is found acceptable, this sub-routine grants the outputcontactor (K1) “permission to close” and sets ST_CA =2 – which means that on thenext entry to the Transfer Control Logic (100µs later) the load-on-inverter sub-routine will be selected for execution. On the other hand, if the inverter voltage status indicates an error condition thenthe subroutine will not grant permission to close K1 and ST_CA will remain set to“1” – which means that the load-on-bypass routine will be executed again the nexttime the Transfer Control Logic is called (in 100µs).
Due to its complexity, the four Transfer Control Logic subroutines are describedindividually on the following pages.
7-180 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Figure 7-39: Transfer Control Logic sub-routines
7.2.10.2 ST_CA=0 (Load status = Initialisation mode)(See Chart 7-12)
This is the Load Transfer Control Logic subroutine entered during initial power-up, or when commanded by one of the other sub-routines (See Figure 7-39).
When in this routine, the software examines various flags in order to undertakeany actions appropriate to the “initialisation” mode of operation. For example; ifthe bypass voltage status is OK it will lead to closing the bypass SCRs, and if theinverter output voltage is OK it will lead to closing the output contactor (K1).Once the appropriate action is determined, the load status flag (ST_CA) is reas-signed (ST_CA=1 or ST_CA=2) which calls the appropriate sub-routine the nexttime the Transfer Control Logic subroutine is executed (in 100µs).
If no appropriate flags are set, the program returns to the main program withoutchanging ST_CA, –i.e. leaving the load disconnected and ST_CA=0. Thus the nexttime the Load Transfer Control Logic subroutine is called (in 100µs) this sameinitialisation routine will be repeated.
Monitored flags
The initialisation mode sub-routine monitors the following flags:
1. Bypass voltage monitor status – ST_SVI The bypass voltage is monitored by the UPS Logic Board micro via the HighVoltage Interface Board. The ripple voltage to the A/D allows the individualmonitoring of each phase, and a software routine compares the actual valuesagainst the programmed limit values to set the flag status:
0 = OK (bypass voltage within the mimic-programmed limits [±10%])1 = LOW (bypass undervoltage [below -10%])2 = HIGH (bypass voltage high [above +10%])3 = ABSENT (bypass voltage less than 50V)
ST_CA=0Initialisation Mode
ST_CA=3Out-Of-Sync Transfer
Mode
ST_CA=2Load-On-Inverter Mode
ST_CA=1Load-On-Bypass Mode
Power-up
ST_CA=0
ST_CA=2
ST_CA=1
ST_CA=1
ST_CA=0
ST_CA=3
ST_CA=0
ST_CA=1
ST_CA=2
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-181
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
2. Bypass Blocked Status – BL_RETE
This flag is generated by a software routine which monitors the condition of:
• [BLK_MNS> signal (alarm #16) –which is activated by emergency power off; open bypass SCRs; phaserotation error; open bypass breaker; PCB power supply failure.
• [TLC_RETE> signal (alarm #17) –bypass inhibit selection made by operator.
BL_RETE = ON – if either alarm #16 or #17 is active.BL_RETE = OFF – if alarm #16 or #17 are both inactive.
3. Inverter Voltage Monitor Status – ST_SVINVThe inverter voltage is monitored by the UPS Logic Board micro via the HighVoltage Interface Board. The ripple voltage to the A/D allows the individualmonitoring of each phase, and a software routine compares the actual valuesagainst the programmed limit values to set the flag status:
0 = OK (inverter voltage within the mimic-programmed limits [±10%])1 = LOW (inverter undervoltage [below -10%]) Activates alarm #37.2 = HIGH (inverter voltage high [above +10%]) Activates alarm #36.3 = ABSENT (inverter voltage less than 50V)
4. Operator-selected Inverter ON/OFF – TLC_INV
The Inverter ON/OFF selection from the Operator Control Panel is monitoredby the UPS Logic Board micro via the CAN Bus.
TLC_INV = ON (Start inverter)TLC_INV = OFF (Stop inverter) Activates alarm #31.
5. Inverter Logic Board Run Status – BL_INV
The Inverter Logic Board’s Stop/Run status is monitored by the UPS LogicBoard micro. When in the inverter Stop mode, alarm #32 will be active.
BL_INV = ON – if Inverter Logic Board Run/Stop control is in its Stop mode.BL_INV = OFF – if Inverter Logic Board Run/Stop control is in its Run mode.
6. Overload Latch Status – BLK_INV_OVL
Presented to the UPS Logic Board micro from the 150% inverter current limitdetection circuit on the Inverter Logic Board. A software delay allows 5 sec-onds of inverter operation before alarm #61 is latched.
BLK_INV_OVL = ON – if overcurrent latch is activated –contactor K1 tripped.BLK_INV_OVL = OFF – if the overcurrent latch is not activated.
7. 10 second stability timer status – BLK_INV_DP
The inverter is given 10 seconds to reach nominal voltage (i.e. within themimic-programmed limits).
BLK_INV_DP = ON – block closure of the output contactor (K1).BLK_INV_DP = OFF – permit closure of the output contactor (K1).
7-182 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-12: Transfer Control - (ST_CA=0)
Begin SUB: Load transfercontrol
YesIs the "bypass
block" status active?(BL_RETE = OFF)
Is theBypass Voltage OK?
(ST_SVI = OK)
Is the loadstatus flag in its
initialisation state?(ST_CA=0)
Yes
No
No
Yes
Set [L_MAINS> = 1Turn ON bypass SCRs
Set ST_CA = 1annunciate alarm #18[LOAD ON BYPASS]
Set [L_INV> = 0Open inverter contactor (K1)
LOAD ON BYPASS
Is the inverterselected ON from the
Operator Panel?TLC_INV = ON
Is theInverter Voltage OK?
(ST_SVINV = OK)
No
Yes
No
NoIs the "Inverter
Run" status OK?[INV_BLK>=OFF
Yes
Is the "InverterOverload Block" active?
[BLK_INV_OVL>=ON
Yes
Isthe "10s Stability
Timer" latch active?[BLK_INV_DP>
= ON
Yes
No
Set [L_MAINS> = 0Turn OFF bypass SCRs
Set ST_CA=2remove alarm #18
[LOAD ON BYPASS]
Set [L_INV> = 1Close inverter contactor (K1)
LOAD ON INVERTER
No1
End SUB:Return to Main Program
Yes
No
To Next Chart
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-183
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
7.2.10.3 ST_CA=1 (Load status = Load-on-bypass mode) (See Chart 7-13)
This is the Load Transfer Control Logic subroutine entered when the load is con-nected to the bypass supply; as commanded by ST_CA=0 during the initialisationroutine, or ST_CA=2 while the load is “on-inverter” (See Figure 7-39).
When in this routine, the software examines various flags in order to undertakeany actions appropriate to the “load-on-bypass” mode of operation. For example;if the inverter voltage status is OK it will lead to the closure of the output contac-tor (K1), if the bypass voltage fails it will lead to the opening of the bypass SCRs.Once the appropriate action is determined the load status flag (ST_CA) is reas-signed (i.e. ST_CA=2 or ST_CA=0) which calls the appropriate sub-routine the nexttime the Transfer Control Logic subroutine is executed (in 100µs).
If no appropriate flags are set, the program returns to the main program withoutchanging ST_CA, – i.e. leaving the load “on-bypass” and ST_CA=1. Thus the nexttime the Load Transfer Control Logic subroutine is called (in 100µs) this same“load-on-bypass” routine will be repeated.
Monitored flags
The “load-on-bypass” mode sub-routine monitors the following flags:
1. Bypass Blocked Status – BL_RETE
This flag is generated by a software routine which monitors the condition of:
• [BLK_MNS> signal (alarm #16) –which is activated by emergency power off; open bypass SCRs; phaserotation error; open bypass breaker; PCB power supply failure.
• [TLC_RETE> signal (alarm #17) –bypass inhibit selection made by operator.
BL_RETE = ON – if either alarm #16 or #17 is active.BL_RETE = OFF – if alarm #16 or #17 are both inactive.
2. Auto-retransfer Mode Selection – X26:1-2
If jumper X26 pins 1-2 are “made” it allows the examination of the “once-only” transfer flag (BLK_COM_DP) which is set (ON) if the load has previ-ously been transferred to the inverter. If X2 pins 1-2 are open this flag isignored.
3. Inverter block Latch Status – TMP
Before the load is transferred to the inverter, a temporary flag is enabledwhich monitors the status of:
• Overload timeout flag (alarm #61)
• Inverter run flag (alarm #32) – see BL_INV below
• “One-transfer” flag (enabled by X26:1-2 see above)
• 10 second “Stability” flag (enabled by X26:3-4)
• Transfer counter flag (>8 transfers)
If any of the above flags are active, the TMP flag is set to ON and preventsthe inverter output contactor (K1) being closed. Note that if the TMP flag isON it can be reset only by selecting the inverter OFF/ON at the OperatorControl Panel.
7-184 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
4. Inverter Voltage Monitor Status – ST_SVINV
The inverter voltage is monitored by the UPS Logic Board micro via the HighVoltage Interface Board. The ripple voltage to the A/D allows the individualmonitoring of each phase, and a software routine compares the actual valuesagainst the programmed limit values to set the flag status:
0 = OK (inverter voltage within the mimic-programmed limits [±10%])1 = LOW (inverter undervoltage [below -10%]) Activates alarm #37.2 = HIGH (inverter voltage high [above +10%]) Activates alarm #36.3 = ABSENT (inverter voltage less than 50V)
5. Operator-selected Inverter ON/OFF – TLC_INV
The Inverter ON/OFF selection from the Operator Control Panel is monitoredby the UPS Logic Board micro via the CAN Bus.
TLC_INV = ON (Start inverter)TLC_INV = OFF (Stop inverter) Activates alarm #31.
6. Synchronisation Status – SYNK_OK
A software routine within the PLL sub-routine verifies that the inverter andbypass voltages are within ±9° of each other. The inverter output contactor(K1) is inhibited for 5 seconds after this condition is satisfied in order to vali-date the circuit’s stability and allow time for the PLL to bring the phase dis-placement error to zero.
SYNK_OK = ON (OK to transfer)SYNK_OK = OFF (not OK to transfer)
7. Transfer Counter Status – CTR_ATT_RETE
The transfer counter is incremented each time the load is transferred from theinverter to bypass, and flags an error if more than eight transfers take placeover a one minute period. In such an occurrence the counter locks out the out-put contactor to prevent further transfers from taking place.
a) Before the load is transferred to the inverter (ST_CA=2), the transfercounter is checked to see if this is the first transfer-to-inverter event. If itis, a one minute timer started; if it is not, then the timer is already running.
b) Next, the transfer counter is examined. If the counter contents is less thaneight, the output contactor (K1) is permitted to close. If the counter equals8 (or more) the one minute timer is examined to see if it has timed-out;and if so, the temporary flag TMP is enabled (see above) which preventsthe output contactor (K1) closing.
c) The transfer counter is reset to zero if the inverter voltage falls below itsnominal range, thus it is active only as long as the inverter voltage is OK.
8. Inverter Logic Board Run Status – BL_INV
The Inverter Logic Board’s Stop/Run status is monitored by the UPS LogicBoard micro. When in the inverter Stop mode, alarm #32 will be active.
BL_INV = ON – if Inverter Logic Board Run/Stop control is in its Stop mode.BL_INV = OFF – if Inverter Logic Board Run/Stop control is in its Run mode.
9. 10s stability counter enable status – X26:3-4The inverter is allowed 10 seconds to reach its nominal voltage (i.e. within itsselected working voltage range [±10% default]). If the inverter fails to satisfy
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-185
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
this condition it is turned OFF and alarm #32 annunciated. This feature can beenabled/disabled via jumper X26 pins 3-4 (closed = enabled); the status ofwhich is read by this subroutine.
10.Bypass voltage monitor status – ST_SVI The bypass voltage is monitored by the UPS Logic Board micro via the HighVoltage Interface Board. The ripple voltage to the A/D allows the individualmonitoring of each phase, and a software routine compares the actual valuesagainst the programmed limit values to set the flag status:
0 = OK (bypass voltage within the mimic-programmed limits [±10%])1 = LOW (bypass undervoltage [below -10%]) Activates alarm #12.2 = HIGH (bypass voltage high [above +10%]) Activates alarm #11.3 = ABSENT (bypass voltage less than 50V) Activates alarm #10.
11.150% Current Limit Status – OVL_INV
The 150% overload condition is detected on the Inverter Logic Board andpassed to the UPS Logic Board micro. Alarm #33 annunciates the overloadfault condition.The ST_CA=1 sub-routine monitors this signal to enable it to hold the load“on-bypass”, even if the bypass voltage is outside its programmed voltagelimits, once the inverter is feeding a short-circuit present between the inverterpower blocks and the output contactor (K1).
7-186 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-13: Transfer Control - (ST_CA=1)
Is the "bypassblock" status active?
(BL_RETE = ON)
Is the loadstatus flag in its
Load-on-bypass mode?(ST_CA=1)
Yes
NoNo
Is the "once onlytransfer" flag activated?
(i.e. load on inverteronce before)
Is X26:1-2 Closed?(only one transfer to
inverter allowed)
Yes
Yes
No
No
Is the inverterselected ON at the
mimic panel?(TLC_INV=ON)
YesIs the invertervoltage OK?
(ST_SVINV=OK)Yes
Isthe "inverter OffLatch" active?
(TMP=ON)
Yes
NoNo
Yes
No
1
2
Set [L_MAINS> = 0Turn OFF bypass SCRs
Set ST_CA = 0(return to intialise mode)
Set [L_INV> = 0Open inverter contactor (K1)
Set Transfer counter = 0
Reset "Once Only Transfer "flag to OFF
Enable Inverter OFF latch(TMP=ON)
To monitor:
1. Overload timeout flag2. Inverter block flag3. Transfer counter >84. Once only transfer flag5. 10s Stability flag
(If any of the above is activatedthen TMP=ON, else TMP=OFF)
Disable Inverter OFF latch(TMP=ON)
(Use the mimic display to rest thelatch trigger source from 1 -5 in
above dialog box)
A B C
End SUB:Return to Main Program
To Next Chart To Next ChartTo Next Chart
From Previous Chart
To Chart 7-14
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-187
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
Flow Chart 7-13: Continued
From Previous Chart From Previous Chart
Is "Inverter Run"signal present?(BL_INV=OFF)
Are the bypassvolts OK?
(ST_SVI = 0)
No
Yes
Yes
Is the transfercounter at zero?
IsX26:3-4 Closed?
(10s inverter stabilitycheck enabled)
No
No
Yes
Is the invertervoltage not OK?(ST_SVINV=KO)
Yes
No
Yes
Set [L_MAINS> = 0Turn OFF bypass SCRs
Set ST_CA = 2(Load on inverter mode)
Set [L_INV> = 1Close inverter contactor (K1)
A B C
Has 10s delayexpired?
Yes
Turn Inverter OFFSet BLK_INV = ON(trigger Alarm #32)
Activate 10Sec Stability flag(i.e. TMP = ON)
End SUB:Return to Main Program
No
NoIs the inverter in
sync with bypass?SNYK_OK=ON
No
Yes
Start the 1 minute timer
Is the transfercounter >8?
Has 1 minutetimer expired?
Yes
No
Set Counter >8 flag ON(CTR_ATT_RETE = ON)
(trigger Alarm #60)This will also set (TMP=ON)
Reset 1 minute counter = 0
Yes
Is the 5 seconds"wait in bypass"delay expired?
No
No
Set "Once only transfer" flag(i.e. TMP = ON)
Yes
Is the invertercurrent limit active?
OVL_INV=ONYes
Set [L_MAINS> = 0Turn OFF bypass SCRs
Set ST_CA = 0(return to initialise mode)
Set [L_INV> = 0Open inverter contactor (K1)
No
7-188 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
7.2.10.4 ST_CA=2 (Load status = Load-on-inverter mode)
This is the Load Transfer Control Logic subroutine entered when the load is con-nected to the inverter supply; as commanded by ST_CA=0 during the initialisa-tion routine, or ST_CA=1 while the load is “on-bypass” (See Figure 7-39).
When in this routine, the software examines various flags in order to undertakeany actions appropriate to the “load-on-inverter” mode of operation. For example;if the inverter voltage status is not OK (KO) it will lead to the closure of the bypassSCRs and the opening of the output contactor (K1). Once the appropriate actionis determined the load status flag (ST_CA) is reassigned (i.e. ST_CA=1 or ST_CA=3)and the next time the Load Transfer Control Logic subroutine is called (in 100µs)then the appropriate sub-routine will be executed.
If no appropriate flags are set, the program returns to the main program withoutchanging ST_CA, – i.e. leaving the load “on-inverter” and ST_CA=2. Thus thenext time the Load Transfer Control Logic subroutine is executed (in 100µs) thissame “load-on-inverter” routine will be called.
Monitored flags
The “load-on-inverter” mode sub-routine monitors the following flags:
1. Output Voltage Monitor Status – ST_SVO
The output voltage is monitored by the UPS Logic Board micro via the HighVoltage Interface Board. The ripple voltage to the A/D allows the individualmonitoring of each phase, and a software routine compares the actual valuesagainst the programmed limit values to set the flag status:
0 = OK (output voltage within the mimic-programmed limits [±10%])1 = LOW (output undervoltage [below -10%]) Activates alarm #40.2 = HIGH (output voltage high [above +10%]) Activates alarm #39.3 = ABSENT (output voltage less than 50V) Activates alarm #41.
2. Inverter Logic Board Run Status – BL_INV
The Inverter Logic Board’s Stop/Run status is monitored by the UPS LogicBoard micro. When in the inverter Stop mode, alarm #32 will be active.
BL_INV = ON – if Inverter Logic Board Run/Stop control is in its Stop mode.BL_INV = OFF – if Inverter Logic Board Run/Stop control is in its Run mode.
3. Operator-selected Inverter ON/OFF – TLC_INV
The Inverter ON/OFF selection from the Operator Control Panel is monitoredby the UPS Logic Board micro via the CAN Bus.
TLC_INV = ON (Start inverter)TLC_INV = OFF (Stop inverter) Activates alarm #31.
4. Bypass voltage monitor status – ST_SVI The bypass voltage is monitored by the UPS Logic Board micro via the HighVoltage Interface Board. The ripple voltage to the A/D allows the individualmonitoring of each phase, and a software routine compares the actual valuesagainst the programmed limit values to set the flag status:
0 = OK (bypass voltage within the mimic-programmed limits [±10%])1 = LOW (bypass undervoltage [below -10%]) Activates alarm #12.2 = HIGH (bypass voltage high [above +10%]) Activates alarm #11.3 = ABSENT (bypass voltage less than 50V) Activates alarm #10.
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-189
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
5. Bypass Blocked Status – BL_RETE
This flag is generated by a software routine which monitors the condition of:
• [BLK_MNS> signal (alarm #16) –which is activated by emergency power off; open bypass SCRs; phaserotation error; open bypass breaker; PCB power supply failure.
• [TLC_RETE> signal (alarm #17) –bypass inhibit selection made by operator.
BL_RETE = ON – if either alarm #16 or #17 is active.BL_RETE = OFF – if alarm #16 or #17 are both inactive.
6. Synchronisation Status – SYNK_OK
A software routine within the PLL sub-routine verifies that the inverter andbypass voltages are within ±9° of each other. The inverter output contactor(K1) is inhibited for 5 seconds after this condition is satisfied in order to vali-date the circuit’s stability and allow time for the PLL to bring the phase dis-placement error to zero.
SYNK_OK = ON (OK to transfer)SYNK_OK = OFF (not OK to transfer)
7. Transfer Counter Status – CTR_ATT_RETE
The transfer counter is incremented each time the load is transferred from theinverter to bypass, and flags an error if more than eight transfers take placeover a one minute period. In such an occurrence the counter locks out the out-put contactor to prevent further transfers from taking place.
a) Before the load is transferred to the inverter (ST_CA=2), the transfercounter is checked to see if this is the first transfer-to-inverter event. If itis, a one minute timer started; if it is not, then the timer is already running.
b) Next, the transfer counter is examined. If the counter contents is less thaneight, the output contactor (K1) is permitted to close. If the counter equals8 (or more) the one minute timer is examined to see if it has timed-out;and if so, the temporary flag TMP is enabled (see above) which preventsthe output contactor (K1) closing.
c) The transfer counter is reset to zero if the inverter voltage falls below itsnominal range, thus it is active only as long as the inverter voltage is OK.
8. 150% Current Limit Status – OVL_INV
The 150% overload condition is detected on the Inverter Logic Board andpassed to the UPS Logic Board micro. Alarm #33 annunciates the overloadfault condition. The purpose of monitoring the flag in this instance is to forcethe inverter to feed a short circuit for 5 seconds if the bypass is absent.
9. 10s stability counter enable status – X26:3-4If this function is enabled, and the bypass voltage is unavailable, the inverteris allowed 10 seconds to reach its nominal voltage (i.e. within its selectedworking voltage range [±10% default]). If the inverter fails to satisfy this con-dition it is turned OFF and alarm #32 annunciated. This feature can be ena-bled/disabled via jumper X26 pins 3-4 (closed = enabled); the status of whichis read by this subroutine. If this function is disabled, the critical bus statushas no influence on the inverter run signal.
7-190 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
Flow Chart 7-14: Transfer Control - (ST_CA=2)
Is the"critical bus volts
monitor" status OK?(ST_SVO = 0)
Is the loadstatus flag in its
Load-on-inverter mode?(ST_CA=2)
Yes
No Yes
Is theInverter selected
OFF at the Mimic Panel?(TLC_INV=OFF)
Is the "inverterRun" status OFF?
BL-INV=OFF
No
No Yes
No
2
3
E F
Is thebypass voltage OK?
(ST_SVI=0)Yes
Is the "inverterRun" status OFF?
BL-INV=OFF
No
Is theInverter selected
OFF at the Mimic Panel?(TLC_INV=OFF)
No
Set [L_MAINS> = 0Turn OFF bypass SCRs
Set ST_CA = 0
Set [L_INV> = 0Open inverter contactor (K1)
Yes
Yes
Reset Transfer Counter
Is thebypass block active?
(BL_RETE=ON)
Yes
Yes
Is the inverter insync with the bypass?
(SNYK_OK=ON)
No
D
No
No
Yes
End SUB:Return to Main Program
From Chart 7-13
To Chart 7-15
To next chart To next chart To next chart
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-191
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
Flow Chart 7-14: Continued
Is the 150%current limit flag active?
(OVL_INV=ON)Yes
No
Is X26:3-4closed?
E F
YesHas the 10s
delay expired?
D
End SUB:Return to Main Program
No
Set [L_MAINS> = 0Turn OFF bypass SCRs
Set ST_CA = 3
Set [L_INV> = 0Open inverter contactor (K1)
Set [L_MAINS> = 1Turn ON bypass SCRs
Set ST_CA = 1
Set [L_INV> = 0Open inverter contactor (K1)
Increment transfer counter
Start 5 second "wait inbypass" delay timer
Is theInverter selected
OFF at the Mimic Panel?(TLC_INV=OFF)
Turn Inverter OFF for 1 sec.
Yes
End SUB:Return to Main Program
No
Has 5 secondtimer expired?
No
Set [L_MAINS> = 0Turn OFFbypass SCRs
Set ST_CA = 0
Set [L_INV> = 0Open inverter contactor (K1)
Reset transfer counterSet Blk_INV=ON
Alarm #32
Activiate Overload Alarm #61
Yes
Yes
No
Set [L_MAINS> = 0Turn OFFbypass SCRs
Set ST_CA = 0
Set [L_INV> = 0Open inverter contactor (K1)
Reset transfer counter
Set Blk_INV=ONAlarm #32
Set 10s Stability flag=ON(i.e. TMP=ON)
From previous chart From previous chartFrom previous chart
7-192 s7-c6.fm5 - Issue 2 Dated 21/08/97
7200 Series UPS Service Manual SECTION 7 - UPS System ControlCHAPTER 7 - System software
7.2.10.5 ST_CA=3 (Load status = Out-of-Sync transfer mode)
This is the Load Transfer Control Logic subroutine entered when commanded byST_CA=2 while the load is “on-inverter” (See Figure 7-39).
When in this routine, the software examines various flags in order to undertakeany actions appropriate to the “out-of-sync” mode of operation. For example;once an out-of-sync transfer has occurred, a three second break is introducedbefore the bypass SCRs are closed.
Once the appropriate actions are taken, the load status flag is re-assigned to eitherST_CA = 1 or ST_CA = 0, which calls for one of the routines described earlier tobe executed on the next pass of the main program.
If no appropriate flags are set, the program returns to the main program withoutchanging the load status flag (ST_CA still = 3). Thus the next time the LoadTransfer Control Logic subroutine is executed (in 100µs) this same “out-of-sync”subroutine will be called.
Monitored flags
The “out-of-sync” transfer mode sub-routine monitors the following flags:
1. Output contactor (K1) status flag – XSTAI2
This flag is initially set (OFF) as K1 is closed while the load is “on-inverter”(ST_CA=2). When undertaking an “out-of-sync” transfer, contactor K1should open, then after a delay of 3 seconds the bypass SCRs should beturned ON. The 3 second delay is controlled by the system software and isinitiated when XSTAI2 indicates that K1 is open. Note that XSTAI2 is con-nected to K1 auxiliary contacts and sensed via the High Voltage InterfaceBoard.
XSTAI2 = ON (K1 contactor is closed)XSTAI2 = OFF (K1 contactor is open)
2. Bypass Blocked Status – BL_RETE
This flag is generated by a software routine which monitors the condition of:
• [BLK_MNS> signal (alarm #16) –which activated by emergency power off; open bypass SCRs; phase rota-tion error; open bypass breaker; PCB power supply failure.
• [TLC_RETE> signal (alarm #17) –bypass inhibit selection made by operator.
BL_RETE = ON – if either alarm #16 or #17 is active.BL_RETE = OFF – if alarm #16 or #17 are both inactive.
s7-c6.fm5 - Issue 2 Dated 21/08/97 7-193
SECTION 7 - UPS System Control 7200 Series UPS Service ManualCHAPTER 7 - System software
Flow Chart 7-15: Transfer Control - Initialisation mode (ST_CA=3)
Is K1 StatusMonitor Disabled?
(XSTAI=ON)
Isthe load
status flag in its "Out-of-sync transfer" mode?
(ST_CA=3)
Yes
No
Yes
Has the 3 sec timedelay expired?
No
3
Is K1 Open yet(XSTAI2=ON)
Is the BypassBlock status active?
(BL_RETE=ON)
Set [L_MAINS> = 0Turn OFF bypass SCRs
Set ST_CA = 0
Set [L_INV> = 0Open inverter contactor (K1)
Reset Transfer Counter
End SUB:Return to Main Program
disable K1 Status MonitorSet XSTAI2 = ON)
Start 3 second time delay
Set [L_MAINS> = 1Turn ON bypass SCRs
Set ST_CA = 1(annunciate Alarm #16)
Set [L_INV> = 0Open inverter contactor (K1)
Increment Transfer Counter
No
Yes
Yes
No Yes
No
From chart 7-14
7-194 s7-c6.fm5 - Issue 2 Dated 21/08/97