Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

59
Second Revision No. 1040-NFPA 13-2017 [ Global Comment ] PRI-AAA Update metric conversions in NFPA 13 to match that as shown on the attached list and pdf of NFPA 13. Supplemental Information File Name Description Approved 13-PRI_metrics.pdf Metric conversions for PRI-AAA Metric_values_used_in_NFPA_13..docx Submitter Information Verification Submitter Full Name: AUT-PRI Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Fri Oct 06 13:33:12 EDT 2017 Committee Statement and Meeting Notes Committee Statement: The metric conversions in the attached list are considered to be “soft” or approximate conversions and are intended to consider trade sizes for pipe and other materials and have been appropriately rounded with the number of significant digits taken into account. The intent of this list is to provide for consistent use of metric conversions throughout the standard with the understanding that it is acceptable for an engineer, authority having jurisdiction, designer or, installer to use an exact conversion rather than an approximate conversion as used in the standard when necessary. The attached list has been reviewed by the NFPA 13 Metric Task Group. Response Message: National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C... 1 of 1 10/27/2017, 8:34 AM

Transcript of Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Page 1: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

PRI-AAA

Update metric conversions in NFPA 13 to match that as shown on the attached list and pdf ofNFPA 13.

Supplemental Information

File Name Description Approved

13-PRI_metrics.pdf Metric conversions for PRI-AAA ✓Metric_values_used_in_NFPA_13..docx ✓

Submitter Information Verification

Submitter Full Name: AUT-PRI

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Oct 06 13:33:12 EDT 2017

Committee Statement and Meeting Notes

CommitteeStatement:

The metric conversions in the attached list are considered to be “soft” or approximateconversions and are intended to consider trade sizes for pipe and other materials and havebeen appropriately rounded with the number of significant digits taken into account. Theintent of this list is to provide for consistent use of metric conversions throughout thestandard with the understanding that it is acceptable for an engineer, authority havingjurisdiction, designer or, installer to use an exact conversion rather than an approximateconversion as used in the standard when necessary.

The attached list has been reviewed by the NFPA 13 Metric Task Group.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 1 10/27/2017, 8:34 AM

Page 2: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Pressure tanks shall be provided with an approved means for automatically maintaining the required air pressure.

5.2.4.1.3 Where a pressure tank is the sole water supply, an approved trouble alarm shall also be provided to indicate low air pressure and low water level with the alarm supplied from an electrical branch circuit independent of the air compressor.

5.2.4.1.4 Pressure tanks shall not be used to supply other than sprinklers and hand hose attached to sprinkler piping.

5.2.4.2 Capacity. 5.2.4.2.1 In addition to the requirements of 5.1.2, the water capacity of a pressure tank shall include the extra capacity needed to fill dry pipe or preaction systems where installed.

5.2.4.2.2 The total volume shall be based on the water capacity plus the air capacity required by 5.2.4.3.

5.2.4.3* Water Level and Air Pressure. 5.2.4.3.1 Pressure tanks shall be kept with a sufficient supply of water to meet the demand of the fire protection system as calculated in Chapter 23 for the duration required by Chapter 11, Chapter 12, or Chapter 22.

5.2.4.3.2 The pressure shall be sufficient to push all of the water out of the tank while maintaining the necessary residual pressure (required by Chapter 23) at the top of the system.

5.2.5 Gravity Tanks. An elevated tank installed in accordance with NFPA 22 shall be an acceptable water supply source.

5.2.6 Penstocks, Flumes, Rivers, or Lakes. Water supply connections from penstocks, flumes, rivers, lakes, or reservoirs shall be arranged to avoid mud and sediment and shall be provided with approved double removable screens or approved strainers installed in an approved manner.

Chapter 6 Installation Underground Piping 6.1* Piping. [24:10.1]

6.1.1* All piping used in private fire service mains shall be in accordance with 6.1.1.1, 6.1.1.2 or 6.1.1.3. [24:10.1.1]

6.1.1.1 Listing. Piping manufactured in accordance with Table 6.1.1.1 shall be permitted to be used. [24:10.1.1.1]

Table 6.1.1.1 Manufacturing Standards for Underground Pipe

Materials and Dimensions Standard

Ductile Iron

Page 3: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Materials and Dimensions Standard

Cement Mortar Lining for Ductile Iron Pipe and Fittings for Water AWWA C104

Polyethylene Encasement for Ductile Iron Pipe Systems AWWA C105

Rubber-Gasket Joints for Ductile Iron Pressure Pipe and Fittings AWWA C111

Flanged Ductile Iron Pipe with Ductile Iron or Gray Iron Threaded Flanges AWWA C115

Thickness Design of Ductile Iron Pipe AWWA C150

Ductile Iron Pipe, Centrifugally Cast for Water AWWA C151

Standard for the Installation of Ductile Iron Water Mains and Their Appurtenances AWWA C600

Concrete

Reinforced Concrete Pressure Pipe, Steel-Cylinder Type AWWA C300

Prestressed Concrete Pressure Pipe, Steel-Cylinder Type AWWA C301

Reinforced Concrete Pressure Pipe, Non-Cylinder Type AWWA C302

Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, Pretensioned AWWA C303

Standard for Asbestos-Cement Distribution Pipe, 4 in. Through 16 in., for Water Distribution Systems

AWWA C400

Cement-Mortar Lining of Water Pipe Lines 4 in. and Larger — in Place AWWA C602

Plastic

Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in., for Water Distribution AWWA C900

Polyvinyl Chloride (PVC) Pressure Pipe, 14 in. Through 48 in., for Water Distribution AWWA C905

Polyethylene (PE) Pressure Pipe and Fittings, 4 in. (100 mm) Through 63 in. (1575 mm) for Water Distribution

AWWA C906

Molecularly Oriented Polyvinyl Chloride (PVCO) 4-24 in. AWWA C909

Brass

Specification for Seamless Red Brass Pipe ASTM B43

Page 4: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Materials and Dimensions Standard

Copper

Specification for Seamless Copper Tube ASTM B75

Specification for Seamless Copper Water Tube ASTM B88

Requirements for Wrought Seamless Copper and Copper-Alloy Tube ASTM B251

[24:Table 10.1.1.1]

6.1.1.2 Piping specifically listed for use in private fire service mains shall be permitted to be used. [24:10.1.1.2]

6.1.1.2.1 Where listed pipe is used, it shall be installed in accordance with the listing limitations including installation instructions. [24:10.1.1.2.1]

6.1.1.2.2 Where listing limitations or installation instructions differ from the requirements of this standard, the listing limitations and installation instructions shall apply. [24:10.1.1.2.2]

6.1.1.3 Steel piping manufactured in accordance with Table 6.1.1.3 that is externally coated and wrapped and internally galvanized shall be permitted to be used between the hose coupling(s) on the fire department connection and the check valve installed in the fire department connection piping. [24:10.1.1.3]

Table 6.1.1.3 Steel Piping for Fire Department Connections

Materials and Dimensions Standard

Specification for Black and Hot-Dipped Zinc-Coated (Galvanized) Welded and Seamless Steel Pipe for Fire Protection Use

ASTM A795

Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless

ASTM A53

Standard Specification for Electric-Resistance Welded Steel Pipe ASTM A135

[24:Table 10.1.1.3]

6.1.1.3.1 External coating and wrapping as required by 6.1.1.3 shall be approved. [24:10.1.1.3.1]

6.1.1.4 Dry Pipe Underground. 6.1.1.4.1 Where necessary to place pipe that will be under air pressure underground, the pipe shall be protected against corrosion.

6.1.1.4.2 Unprotected cast-iron or ductile-iron pipe shall be permitted where joined with a gasketed joint listed for air service underground.

6.1.2* All piping used in private fire service mains shall be rated for the maximum system working pressure to which the piping is exposed to but shall not be rated at less than 150 psi (10 bar). [24:10.1.2]

6.1.3* When lined piping is used, the manufacturer’s literature for internal diameter shall be used for all hydraulic calculations. [24:10.1.3]

Page 5: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.1.4 Where piping installed in a private fire service main must be installed above grade, the piping materials shall conform to NFPA 13. [24:10.1.4]

6.1.4.1* Underground piping shall be permitted to extend into the building through the slab or wall not more than 24 in. (600 mm). [24:10.1.4.1]

6.2 Fittings. [24:10.2]

6.2.1 All fittings used in private fire service mains shall be in accordance with 6.2.1.1 or 6.2.1.2. [24:10.2.1]

6.2.1.1 Fittings manufactured in accordance with Table 6.2.1.1 shall be permitted to be used. [24:Table 10.2.1.1]

Table 6.2.1.1 Fittings Materials and Dimensions

Materials and Dimensions Standard

Cast Iron

Gray Iron Threaded Fittings, Classes 125 and 250 ASME B16.4

Gray Iron Pipe Flanges and Flanged Fittings, Classes 25, 125, and 250 ASME B16.1

Ductile Iron

Ductile Iron and Gray Iron Fittings, 3 in. Through 48 in., for Water and other Liquids AWWA C110

Ductile Iron Compact Fittings, 3 in. Through 24 in. and 54 in. through 64 in. for Water Service

AWWA C153

Malleable Iron

Malleable Iron Threaded Fittings, Class 150 and 300 ASME B16.3

Steel

Factory-Made Wrought Steel Buttweld Fittings ASME B16.9

Buttwelding Ends ASME B16.25

Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and Elevated Temperatures

ASTM A234

Pipe Flanges and Flanged Fittings, NPS 1⁄2 Through 24 ASME B16.5

Forged Steel Fittings, Socket Welded and Threaded ASME B16.11

Steel Pipe Flanges for Waterworks Service — Sizes 4 in. Through 144 in. AWWA C207

Dimensions for Fabricated Steel Water Pipe Fittings AWWA C208

Page 6: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Materials and Dimensions Standard

Copper

Wrought Copper and Bronze Solder Joint Pressure Fittings ASME B16.22

Cast Cast Bronze Solder Joint Pressure Fittings ASME B16.18

Bronze Fittings

Cast Bronze Threaded Fittings ASTM B16.15

[24:Table 10.2.2.1]

6.2.1.2 Fittings specifically listed for use in private fire service mains shall be permitted to be used. [24:10.2.1.2]

6.2.1.2.1 Where listed fittings are used, they shall be installed in accordance with their listing limitations including installation instructions. [24:10.2.1.2.1]

6.2.1.2.2 Where listing limitations or installation instructions differ from the requirements of this standard, the listing limitations and installation instructions shall apply. [24:10.2.1.2.2]

6.2.2 All fittings used in private fire service mains shall be rated for the maximum system working pressure to which the fittings are exposed, but shall not be rated at less than 150 psi (10 bar). [24:10.2.2]

6.2.3 Where fittings installed in a private fire service main must be installed above grade, the fittings shall conform to NFPA 13. [24:10.2.3]

6.2.3.1 Fittings in accordance with 6.2.1 shall be permitted for the transition to the above ground piping or fittings. [24:10.2.3.1]

6.3 Connection of Pipe Fittings and Appurtenances. [24:10.3]

6.3.1* Connection of all fittings and appurtenances to piping shall be in accordance with Section 6.3. [24:10.3.1]

6.3.2 Connections of pipe and fittings indicated in Table 6.1.1.1 and Table 6.2.1.1 shall be in accordance with the referenced standard in the Table. [24:10.3.2]

6.3.3 Listed Connections. Connections utilizing listed products shall be in accordance with the listing limitations and the manufacturer’s installation instructions. [24:10.3.3]

6.3.3.1 Where listing limitations or installation instructions differ from the requirements of this standard, the listing limitations and installation instructions shall apply. [24:10.3.3.1]

6.3.4 Where pipe, fittings or appurtenances are connected using threads, all threads shall be in accordance with ANSI/ASME B1.20.1. [24:10.3.4]

6.3.5 Grooved Connections.

Page 7: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Where pipe, fittings or appurtenances are connected using grooves, they shall be connected in accordance with 6.3.5.1 through 6.3.5.3. [24:10.3.5]

6.3.5.1 Pipe, fittings, and appurtenances to be joined with grooved couplings shall contain cut, rolled, or cast grooves that are dimensionally compatible with the couplings. [24:10.3.5.1]

6.3.5.2 Pipe, fittings, and appurtenances that are connected with grooved couplings and are part of a listed assembly shall be permitted to be used. [24:10.3.5.2]

6.3.5.3* Pipe joined with grooved fittings shall be joined by a listed combination of fittings, gaskets, and grooves. [24:10.3.5.3]

6.3.6 All joints for the connection of copper tube shall be brazed or joined using pressure fittings as specified in Table 6.2.1.1. [24:10.3.6]

6.4 Protection of Private Fire Service Mains. [24:10.4] 6.4.1 Protection from Corrosion. [24:10.4.1]

6.4.1.1 Coatings. All bolted joint accessories shall be cleaned and thoroughly coated with asphalt or other corrosion-retarding material after installation. [24:10.4.1.1]

6.4.1.2 The requirements of 6.4.1.1 shall not apply to epoxy coated fittings, valves, glands, or other accessories. [24:10.4.1.2]

6.4.1.3* Where it is necessary to join metal pipe with pipe of dissimilar metal, the joint shall be insulated against the passage of an electric current using an approved method. [24:10.4.1.3]

6.4.2* Protection of Piping. [24:10.4.2] 6.4.2.1 Protection from Freezing. The depth of cover for private fire service mains and their appurtenances to protect against freezing shall be in accordance with 6.4.2. [24:10.4.2.1]

6.4.2.1.1* The top of the pipe shall be buried not less than 1 ft (300 mm) below the frost line for the locality. [24:10.4.2.1.1]

6.4.2.1.2 The depth of piping shall be measured from the top of the piping to the final grade. [24:10.4.2.1.2]

6.4.2.1.3 Where listed piping is used and the bury depth differs from this standard, the listing limitations shall apply. [24:10.4.2.1.3]

6.4.2.1.4 Where private fire service mains are installed above ground, they shall be protected from freezing in accordance with NFPA 13. [24:10.4.2.1.4]

6.4.2.1.5 Private fire service mains installed in water raceways or shallow streams shall be installed so that the piping will remain in the running water throughout the year. [24:10.4.2.1.5]

6.4.2.1.6

Page 8: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Where piping is installed adjacent to a vertical face, it shall be installed from the vertical face at the same distance as if the piping were buried. [24:10.4.2.1.6]

6.4.2.1.7 Protection of private fire service mains from freezing using heat tracing shall be permitted when the heat tracing is specifically listed for underground use. [24:10.4.2.1.7]

6.4.2.1.7.1 Heat tracing not listed for underground use shall be permitted when piping is installed in accordance with 6.1.4. [24:10.4.2.1.7.1]

6.4.2.2 Protection from Mechanical Damage. The depth of cover for private fire service mains and their appurtenances to protect against mechanical damage shall be in accordance with 6.4.2.2.3. [24:10.4.2.2]

6.4.2.2.1 The depth of piping shall be measured from the top of the piping to the final grade. [24:10.4.2.2.1]

6.4.2.2.2 In locations where freezing is not a factor, the depth of cover shall not be less than 30 in. (0.8 m) below grade to prevent mechanical damage. [24:10.4.2.2.2]

6.4.2.2.2.1 Where listed piping is used and the bury depth differs from this standard, the listing limitations shall apply. [24:10.4.2.2.2.1]

6.4.2.2.3 Private fire service mains installed under driveways or roadways shall be buried at a minimum depth of 3 ft (900 mm). [24:10.4.2.2.3]

6.4.2.2.3.1 Sidewalks, walkways and other paved or concrete pedestrian passageways shall not be required to comply with 6.4.2.2.3. [24:10.4.2.2.3.1]

6.4.2.2.4 Private fire service mains installed under railroad tracks shall be buried at a minimum depth of 4 ft (1.2 m). [24:10.4.2.2.4]

6.4.2.2.4.1 Where railroad operators require a greater depth of bury, the greater depth shall apply. [24:10.4.2.2.4.1]

6.4.2.2.5 Private fire service mains installed under large piles of heavy commodities or subject to heavy shock and vibrations shall be buried at a minimum depth of 4 ft (1.2 m). [24:10.4.2.2.5]

6.4.2.2.6 Where private fire service mains are installed above ground, they shall be protected with bollards or other means as approved by the AHJ when subject to mechanical damage. [24:10.4.2.2.6]

6.4.3 Private Fire Service Mains Under Buildings. Except as allowed by 6.4.3, private fire service mains shall not be allowed to run under buildings. [24:10.4.3]

6.4.3.1* Private fire service mains supplying fire protection systems within the building shall be permitted to extend no more than 10 ft (3 m), as measured from the outside of the building, under the building to the riser location. [24:10.4.3.1]

6.4.3.1.1* Pipe joints shall not be located directly under foundation fittings. [24:10.4.3.1.1]

6.4.3.1.2* Piping shall be installed a minimum of 12 in. (300 mm) below the bottom of building foundations or footers. [24:10.4.3.1.2]

dhague
Highlight
dhague
Sticky Note
750 mm
Page 9: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.4.3.1.2.1 The requirements of 6.4.3.1.2 shall not apply when the piping is sleeved with an approved material. [24:10.4.3.1.2.1]

6.4.3.2* Where approved, private fire service mains supplying systems within the building shall be permitted to extend more than 10 ft (3 m) under the building when all the requirements of 6.4.3.2.1, through 6.4.3.2.4 are met. [24:10.4.3.2]

6.4.3.2.1 Where the piping is installed under the building, all foundations or footers over the private fire service main shall be arched to create a minimum of 24 in. (600 mm) clearance. [24:10.4.3.2.1]

6.4.3.2.2 It shall be acceptable to install the piping in covered trenches where the trenches are accessible from within the building. [24:10.4.3.2.2]

6.4.3.2.3 All joints shall be mechanically restrained. [24:10.4.3.2.3]

6.4.3.2.4 A valve shall be installed before the piping enters under the building and within 24 in. (600 mm) of where the piping enters the building. [24:10.4.3.2.4]

6.5 Grounding and Bonding. [24:10.5]

6.5.1* In no case shall the underground piping be used as a grounding electrode for electrical systems. [24:10.5.1]

6.5.1.1* The requirement of 6.5.1 shall not preclude the bonding of the underground piping to the lightning protection grounding system as required by NFPA 780 in those cases where lightning protection is provided for the structure. [24:10.5.1.1]

6.6* Restraint. Private fire service mains shall be restrained against movement at changes in direction in accordance with 6.6.1, 6.6.2 or 6.6.3. [24:10.6]

6.6.1* Thrust Blocks. 6.6.1.1 Thrust blocks shall be permitted where soil is stable and capable of resisting the anticipated thrust forces. [24:10.6.1.1]

6.6.1.2 Thrust blocks shall be of concrete, of a mix not leaner than one part cement, two and one-half parts sand, and five parts stone. [24:10.6.1.2]

6.6.1.3 Thrust blocks shall be placed between undisturbed earth and the fitting to be restrained and shall be capable of resisting the calculated thrust forces. [24:10.6.1.3]

6.6.1.4 Wherever possible, thrust blocks shall be located so that the joints are accessible for repair. [24:10.6.1.4]

6.6.2* Restrained Joint Systems. Private fire service mains using restrained joint systems shall include one or more of the following: (1) Locking mechanical or push-on joints

(2) Mechanical joints utilizing setscrew retainer glands

(3) Bolted flange joints

Page 10: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

(4) Pipe clamps and tie rods

(5) Other approved methods or devices

[24:10.6.2]

6.6.2.1 Sizing Clamps, Rods, Bolts, and Washers. [24:10.6.2.1]

6.6.2.1.1 Clamps. [24:10.6.2.1.1]

6.6.2.1.1.1 Clamps shall have the following dimensions: (1) 1⁄2 in. × 2 in. (12 mm × 50 mm) for 4 in. (100 mm) to 6 in. (150 mm) pipe

(2) 5⁄8 in. × 21⁄2 in. (16 mm × 65 mm) for 8 in. (200 mm) to 10 in. (250 mm) pipe

(3) 5⁄8 in. × 3 in. (16 mm × 75 mm) for 12 in. (300 mm) pipe

[24:10.6.2.1.1.1]

6.6.2.1.1.2 The diameter of a bolt hole shall be 1⁄8 in. (3 mm) larger than that of the corresponding bolts. [24:10.6.2.1.1.2]

6.6.2.1.2 Rods. [24:10.6.2.1.2]

6.6.2.1.2.1 Rods shall be not less than 5⁄8 in. (16 mm) in diameter. [24:10.6.2.1.2.1]

6.6.2.1.2.2 Table 6.6.2.1.2.2 provides numbers of various diameter rods that shall be used for a given pipe size. [24:10.6.2.1.2.2]

Table 6.6.2.1.2.2 Rod Number — Diameter Combinations

Nominal Pipe Size (in.) (mm) 5⁄8 in. (16 mm) 3⁄4 in. (20 mm) 7⁄8 in. (22 mm) 1 in.

.

(25 mm)

4 (100) 2 — — —

6 (150) 2 — — —

8 (200) 3 2 — —

10 (250) 4 3 2 —

12 (300) 6 4 3 2

14 (350) 8 5 4 3

16 (400) 10 7 5 4

Note: This table has been derived using pressure of 225 psi (15.5 bar) and design stress of 25,000 psi (172.4 MPa).

[24:Table 10.6.2.1.2.2]

6.6.2.1.2.3 When using bolting rods, the diameter of mechanical joint bolts shall limit the diameter of rods to 3⁄4 in. (20 mm). [24:10.6.2.1.2.3]

6.6.2.1.2.4 Threaded sections of rods shall not be formed or bent. [24:10.6.2.1.2.4]

6.6.2.1.2.5

dhague
Highlight
dhague
Sticky Note
13 mm
Page 11: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Where using clamps, rods shall be used in pairs for each clamp. [24:10.6.2.1.2.5]

6.6.2.1.2.6 Assemblies in which a restraint is made by means of two clamps canted on the barrel of the pipe shall be permitted to use one rod per clamp if approved for the specific installation by the AHJ. [24:10.6.2.1.2.6]

6.6.2.1.2.7 Where using combinations of rods, the rods shall be symmetrically spaced. [24:10.6.2.1.2.7]

6.6.2.1.3 Clamp Bolts. Clamp bolts shall have the following diameters: (1) 5⁄8 in. (16 mm) for pipe 4 in. (100 mm), 6 in. (150 mm), and 8 in. (200 mm)

(2) 3⁄4 in. (20 mm) for 10 in. (250 mm) pipe

(3) 7⁄8 in. (22.2 mm) for 12 in. (300 mm) pipe

[24:10.6.2.1.3]

6.6.2.1.4 Washers. [24:10.6.2.1.4]

6.6.2.1.4.1 Washers shall be permitted to be cast iron or steel and round or square. [24:10.6.2.1.4.1]

6.6.2.1.4.2 Cast-iron washers shall have the following dimensions: (1) 5⁄8 in. × 3 in. (16 mm × 75 mm) for 4 in. (100 mm), 6 in. (150 mm), 8 in. (200 mm), and 10 in. (250 mm) pipe

(2) 3⁄4 in. × 31⁄2 in. (20 mm × 90 mm) for 12 in. (300 mm) pipe

[24:10.6.2.1.4.2]

6.6.2.1.4.3 Steel washers shall have the following dimensions: (1) 1⁄2 in. × 3 in. (12 mm × 75 mm) for 4 in. (100 mm), 6 in. (150 mm), 8 in. (200 mm), and 10 in. (250 mm) pipe

(2) 1⁄2 in. × 31⁄2 in. (12 mm × 90 mm) for 12 in. (300 mm) pipe

[24:10.6.2.1.4.3]

6.6.2.1.4.4 The diameter of holes shall be 1⁄8 in. (3.2 mm) larger than that of bolts or rods. [24:10.6.2.1.4.4]

6.6.2.2 Sizes of Restraint Straps for Tees. [24:10.6.2.2]

6.6.2.2.1 Restraint straps for tees shall have the following dimensions: (1) 5⁄8 in. (16 mm) thick and 21⁄2 in. (65 mm) wide for 4 in. (100 mm), 6 in. (150 mm), 8 in. (200 mm), and 10 in. (250 mm) pipe

(2) 5⁄8 in. (16 mm) thick and 3 in. (75 mm) wide for 12 in. (300 mm) pipe

[24:10.6.2.2.1]

6.6.2.2.2 The diameter of rod holes shall be 1⁄16 in. (1.6 mm) larger than that of rods. [24:10.6.2.2.2]

6.6.2.2.3 Figure 6.6.2.2.3 and Table 6.6.2.2.3 shall be used in sizing the restraint straps for both mechanical and push-on joint tee fittings. [24:10.6.2.2.3]

dhague
Highlight
dhague
Sticky Note
22 mm
dhague
Highlight
dhague
Sticky Note
3 mm
Page 12: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Figure 6.6.2.2.3 Restraint Straps for Tees. [24:Figure 10.6.2.2.3]

Table 6.6.2.2.3 Restraint Straps for Tees

Nominal .

Pipe Size A B C D

in. mm in. mm in. mm in. mm in. mm

4 100 121⁄2 318 101⁄8 257 21⁄2 64 13⁄4 44

6 150 141⁄2 368 121⁄8 308 39⁄16 90 213⁄16 71

8 200 163⁄4 425 143⁄8 365 421⁄32 118 329⁄32 99

10 250 191⁄16 484 1611⁄16 424 53⁄4 146 5 127

12 300 225⁄16 567 193⁄16 487 63⁄4 171 57⁄8 149

[24:Table 10.6.2.2.3]

6.6.2.3 Sizes of Plug Strap for Bell End of Pipe. [24:10.6.2.3]

6.6.2.3.1 The strap shall be 3⁄4 in. (20 mm) thick and 21⁄2 in. (65 mm) wide. [24:10.6.2.3.1]

6.6.2.3.2 The strap length shall be the same as dimension A for tee straps as shown in Figure 6.6.2.2.3. [24:10.6.2.3.2]

6.6.2.3.3 The distance between the centers of rod holes shall be the same as dimension B for tee straps as shown in Figure 6.6.2.2.3. [24:10.6.2.3.31]

6.6.2.4* Material. Clamps, rods, rod couplings or turnbuckles, bolts, washers, restraint straps, and plug straps shall be of a material that has physical and chemical characteristics that indicate its deterioration under stress can be predicted with reliability. [24:10.6.2.4]

6.6.2.5 Corrosion Resistance. After installation, rods, nuts, bolts, washers, clamps, and other restraining devices shall be cleaned and thoroughly coated with a bituminous or other acceptable corrosion-retarding material. [24:10.6.2.5]

6.6.2.5.1

Page 13: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

The requirements of 6.6.2.5 shall not apply to epoxy coated fittings, valves, glands or other accessories. [24:10.6.2.5.1]

6.6.3* Private fire service mains utilizing one or more of the following connection methods shall not require additional restraint, provided that such joints can pass the hydrostatic test of 6.10.2.2 without shifting of piping. (1) Threaded connections

(2) Grooved connections

(3) Welded connections

(4) Heat fused connections

(5) Chemical or solvent cemented connections

[24:10.6.3]

6.7 Steep Grades. [24:10.7]

6.7.1 On steep grades, mains shall be additionally restrained to prevent slipping. [24:10.7.1]

6.7.1.1 Pipe shall be restrained at the bottom of a hill and at any turns (lateral or vertical). [24:10.7.1.1]

6.7.1.1.1 The restraint specified in 6.7.1.1 shall be to natural rock or to suitable piers built on the downhill side of the bell. [24:10.7.1.1.1]

6.7.1.2 Bell ends shall be installed facing uphill. [24:10.7.1.2]

6.7.1.3 Straight runs on hills shall be restrained as determined by a design professional. [24:10.7.1.3]

6.8 Installation Requirements. [24:10.8]

6.8.1 Piping, valves, hydrants, gaskets, and fittings shall be inspected for damage when received and shall be inspected prior to installation. [24:10.8.1]

6.8.2 The tightness of bolted joints shall be verified by the bolt torque or by the method described in the listing information or manufacturer’s installation instructions. [24:10.8.2]

6.8.3 Pipe, valves, hydrants, and fittings shall be clean and free from internal debris. [24:10.8.3]

6.8.4 When work is stopped, the open ends of piping, valves, hydrants, and fittings shall be plugged or covered to prevent foreign materials from entering. [24:10.8.4]

6.8.5 All piping, fittings, valves, and hydrants shall be examined for cracks or other defects while suspended above the trench and lowered into the trench using appropriate equipment. [24:10.8.5]

6.8.6 Plain ends shall be inspected for signs of damage prior to installation. [24:10.8.6]

6.8.7

Page 14: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Piping, fittings, valves, hydrants and appurtenances shall not be dropped, dumped or rolled or skidded against other materials. [24:10.8.7]

6.8.8 Pipes shall be supported in the trench throughout their full length and shall not be supported by the bell ends only or by blocks. [24:10.8.8]

6.8.9 If the ground is soft, other means shall be provided to support the pipe. [24:10.8.9]

6.8.10 Valves and fittings used with nonmetallic pipe shall be supported and restrained in accordance with the manufacturer’s installation instructions. [24:10.8.10]

6.9 Backfilling. [24:10.9]

6.9.1 Backfill material shall be tamped in layers or puddled under and around pipes to prevent settlement or lateral movement. [24:10.9.1]

6.9.2 Backfill material shall not contain ash, cinders, refuse, organic matter or other corrosive materials. [24:10.9.2]

6.9.3 Rocks shall not be used for backfill. [24:10.9.3]

6.9.4 Frozen earth shall not be used as backfill material. [24:10.9.4]

6.9.5 In trenches cut through rock, tamped backfill shall be used for at least 6 in. (150 mm) under and around the pipe and for at least 2 ft (600 mm) above the pipe. [24:10.9.5]

6.9.6 Where using piping listed for private fire service mains, the manufacturer’s installation instructions for backfill shall be followed. [24:10.9.6]

6.10 Testing and Acceptance. [24:10.10]

6.10.1 Approval of Underground Piping. The installing contractor shall be responsible for the following: (1) Notifying the AHJ and the owner’s representative of the time and date testing is to be performed

(2) Performing all required acceptance tests

(3) Completing and signing the contractor’s material and test certificate(s) shown in Figure 6.10.1.

[24:10.10.1]

Page 15: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Figure 6.10.1 Sample of Contractor’s Material and Test Certificate for Underground Piping. [24: Figure 10.10.1]

Page 16: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]
Page 17: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]
Page 18: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.10.2 Acceptance Requirements. [24:10.10.2]

6.10.2.1* Flushing of Piping. [24:10.10.2.1]

6.10.2.1.1 Underground piping, from the water supply to the system riser, and lead-in connections to the system riser, including all hydrants, shall be completely flushed before connection is made to downstream fire protection system piping. [24:10.10.2.1.1]

6.10.2.1.2 The flushing operation shall continue until water flow is verified to be clear of debris. [24:10.10.2.1.2]

6.10.2.1.3 The minimum rate of flow shall be in accordance with Table 6.10.2.1.3. [24:10.10.2.1.3]

Table 6.10.2.1.3 Flow Required to Produce a Velocity of 10 ft/sec (3 m/sec) in Pipes

Pipe Size Flow Rate

in. mm gpm L/min

2 50 100 379

21⁄2 65 150 568

3 75 220 833

4 100 390 1,500

5 125 610 2,300

6 150 880 3,350

8 200 1,560 5,900

10 250 2,440 9,250

12 300 3,520 13,300

[24: Table 10.10.2.1.3]

6.10.2.1.3.1 Where the flow rates established in Table 6.10.2.1.3 are not attainable, the maximum flow rate available to the system shall be acceptable. [24:10.10.2.1.3.1]

6.10.2.1.4 Provision shall be made for the proper disposal of water used for flushing or testing. [24:10.10.2.1.4]

6.10.2.2 Hydrostatic Test. [24:10.10.2.2]

6.10.2.2.1* All piping and attached appurtenances subjected to system working pressure shall be hydrostatically tested at gauge pressure of 200 psi (13.8 bar) or 50 psi (3.4 bar) in excess of the system working pressure, whichever is greater, and shall maintain that pressure at gauge pressure of ±5 psi (0.34 bar) for 2 hours. [24:10.10.2.2.1]

6.10.2.2.2 Acceptable test results shall be determined by indication of either a pressure loss less than gauge pressure of 5 psi or by no visual leakage. [24:10.10.2.2.2]

6.10.2.2.3 The test pressure shall be read from one of the following, located at the lowest elevation of the system or the portion of the system being tested: (1) A gauge located at one of the hydrant outlets

dhague
Highlight
dhague
Sticky Note
380 lpm
Page 19: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

(2) A gauge located at the lowest point where no hydrants are provided

[24:10.10.2.2.3]

6.10.2.2.4* The trench shall be backfilled between joints before testing to prevent movement of pipe. [24:10.10.2.2.4]

6.10.2.2.5 Where required for safety measures presented by the hazards of open trenches, the pipe and joints shall be permitted to be backfilled, provided the installing contractor takes the responsibility for locating and correcting leakage. [24:10.10.2.2.5]

6.10.2.2.6* Hydrostatic Testing Allowance. Where additional water is added to the system to maintain the test pressures required by 6.10.2.2.1, the amount of water shall be measured and shall not exceed the limits of Table 6.10.2.2.6, which are based upon the following equation: .

U.S. Customary Units:

[6.10.2.2.6a] where:

L = testing allowance (makeup water) [gph (gal/hr)]

S = length of pipe tested (ft)

D = nominal diameter of the pipe (in.)

P = average test pressure during hydrostatic test (gauge psi) .

Metric Units:

[6.10.2.2.6b] where:

L = testing allowance (makeup water) (L/hr)

S = length of pipe tested (m)

D = nominal diameter of pipe (mm)

P = average test pressure during the hydrostatic test (kPa) .

[24:10.10.2.2.6]

Table 6.10.2.2.6 Hydrostatic Testing Allowance at 200 psi (gph/100 ft of Pipe)

Nominal Pipe Diameter Testing Allowance

in.(mm) in.(mm)

2 (50) 0.019 (0.236)

4 (100) 0.038 (0.472)

6 (150) 0.057 (0.708)

8 (200) 0.076 (0.944)

10 (250) 0.096 (1.19)

12 (300) 0.115 (1.43)

14 (350) 0.134 (1.66)

dhague
Sticky Note
0.019 (0.475) 0.038 (0.95) 0.057 (1.425) 0.076 (1.9) 0.096 (2.58) 0.115 (3.09) 0.134 (3.35) 0.153 (3.83) 0.172 (4.3) 0.191 (4.78) 0.229 (5.73)
dhague
Highlight
dhague
Highlight
dhague
Highlight
dhague
Highlight
dhague
Highlight
dhague
Highlight
dhague
Highlight
Page 20: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Nominal Pipe Diameter Testing Allowance

in.(mm) in.(mm)

16 (400) 0.153 (1.90)

18 (450) 0.172 (2.14)

20 (500) 0.191 (2.37)

24 (600) 0.229 (2.84)

Notes:

(1) For other length, diameters, and pressures, utilize Equation 10.10.2.2.6a or 10.10.2.2.6b to determine the appropriate testing allowance.

(2) For test sections that contain various sizes and sections of pipe, the testing allowance is the sum of the testing allowances for each size and section.

[24: Table 10.10.2.2.6]

6.10.2.3 Other Means of Hydrostatic Tests. Where required by the AHJ, hydrostatic tests shall be permitted to be completed in accordance with the requirements of AWWA C600, AWWA C602, AWWA C603, and AWWA C900. [24:10.10.2.3]

6.10.2.4 Operating Test. [24:10.10.2.4]

6.10.2.4.1 Each hydrant shall be fully opened and closed under system water pressure. [24:10.10.2.4.1]

6.10.2.4.2 Dry barrel hydrants shall be checked for proper drainage. [24:10.10.2.4.2]

6.10.2.4.3 All control valves shall be fully closed and opened under system water pressure to ensure proper operation. [24:10.10.2.4.3]

6.10.2.4.4 Where fire pumps supply the private fire service main, the operating tests required by 6.10.2.4 shall be completed with the pumps running. [24:10.10.2.4.4]

6.10.2.5 Backflow Prevention Assemblies. [24:10.10.2.5]

6.10.2.5.1 The backflow prevention assembly shall be forward flow tested to ensure proper operation. [24:10.10.2.5.1]

6.10.2.5.2 The minimum flow rate required by 6.10.2.5.1 shall be the system demand, including hose stream demand where applicable. [24:10.10.2.5.2]

Chapter 7 Requirements for System Components and Hardware 7.1 General. This chapter shall provide requirements for correct use of sprinkler system components and hardware.

7.1.1* Listing. 7.1.1.1

dhague
Highlight
dhague
Highlight
dhague
Highlight
dhague
Highlight
Page 21: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Dimensions Found in NFPA 13‐2016 

8/21/2017 1 

 

Length 

.003”  .08 mm  7.5”  190 mm  26”  650 mm 

.0315”  .8 mm  8”  200 mm  27.6”  690 mm 

1/32”  0.8 mm  8.5”  215 mm  28”  700 mm 

1/16”  1.6 mm  9”  225 mm  29”  725 mm 

3/32”  2 mm  9.25”  230 mm  30”  750 mm 

1/8”  3 mm  9.5”  240 mm  30.5”  765 mm 

3/16”  5 mm  10”  250 mm  31”  775 mm 

¼”  6 mm  11”  275 mm  32”  800 mm 

5/16”  8 mm  11.5”  290 mm  33”  825 mm 

3/8”  10 mm  12”  300 mm  35”  875 mm 

½”  13 mm  12.25”  305 mm  35.4”  885 mm 

17/32”  13 mm  12.5”  315 mm  36”  900 mm 

9/16”  14 mm  12.75”  320 mm  37”  925 mm 

5/8”  16 mm  14”  350 mm  38”  950 mm 

¾”  19 mm  15”  375 mm    40”  1000 mm 

7/8”  22 mm  15.5”  390 mm  42”  1050 mm 

1”  25 mm  16”  400 mm  44”  1100 mm 

1.5”  40 mm  16.25”  410 mm  47”  1175 mm 

1.75”  45 mm  16.5”  415 mm  48”  1200 mm 

2”  50 mm  17”  425 mm  54”  1350 mm 

2.5”  65 mm  17.5”  440 mm  55”  1375 mm 

2.75”  70 mm  18”  450 mm  57”  1425 mm 

3”  75 mm  19”  475 mm  58”  1450 mm 

3.5”  90 mm  20”  500 mm  66”  1650 mm 

4”  100 mm  21”  525 mm  68”  1700 mm 

4.5”  115 mm  22”  550 mm  72”  1800 mm 

5”  125 mm  22.5”  565 mm  76”  1900 mm 

5.5”  140 mm  23”  575 mm  78”  1950 mm 

5.75”  145 mm  24”  600 mm  96”  2400 mm 

6”  150 mm  25”  625 mm  102”  2550 mm 

7”  175 mm  25.5”  640 mm  120”  3000 mm 

        148”  3700 mm 

           

 

   

Page 22: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Dimensions Found in NFPA 13‐2016 

8/21/2017 2 

 

 

 

Length 

3.5ft  1.1 m  10’‐10”  3.3 m  22’‐6”  6.9 m 

3’‐8”  1.1 m  11’‐0”  3.4 m  24ft  7.3 m 

4ft  1.2 m  11’‐3”  3.4 m  25ft  7.6 m 

4’‐2”  1.3 m  11’‐5”  3.5 m  25’‐3”  7.7 m 

4.5ft  1.4 m  11’‐6”  3.5 m  26ft  7.9 m 

4’‐7”  1.4 m  11’‐611/16”  3.5 m  27ft  8.2 m 

4’‐9”  1.4 m  11’‐8”  3.6 m  28ft  8.5 m 

5ft  1.5 m  12ft  3.7 m  28’‐8”  8.7 m 

5’‐2”  1.6 m  12’‐4”  3.8 m  29’‐8”  9 m 

5.5ft  1.7 m  13ft  4.0 m  30ft  9.1 m 

5’‐8”  1.7 m  13’‐6”  4.1 m  32ft  10 m 

5’‐9 5/16”  1.8 m  13’‐71/2”  4.2 m  33ft  10 m 

6ft  1.8 m  13’‐11”  4.2 m  35ft  11 m 

6’‐3”  1.9 m  14ft  4.3 m  36ft  11 m 

6’‐4”  1.9 m  14’‐6”  4.4 m  40ft  12 m 

6.5ft  2 m  15ft  4.6 m  41’‐3”  13 m 

6’‐10”  2.1 m  15’‐4”  4.7 m  45ft  14 m 

7ft  2.1 m  16ft  4.9 m  50ft  15 m 

7.5ft  2.3 m  16’‐6”  5.0 m  51’‐6”  16 m 

7’‐7”  2.3 m  16’‐8”  5.1 m  55ft  17 m 

7’‐9”  2.4 m  17ft  5.2 m  60ft  18 m 

8ft  2.4 m  18ft  5.5 m  65ft  20 m 

8’‐2”  2.5 m  18’‐6”  5.6 m  70ft  21 m 

8’‐4”  2.5 m  19’‐2”  5.8 m  75ft  23 m 

8’‐77/8”  2.6 m  19’‐10”  6 m  76ft  23 m 

9ft  2.7 m  19’‐11”  6.1 m  80ft  24 m 

9’‐5”  2.9 m  20ft  6.1 m  100ft  30 m 

9’‐6”  2.9 m  20’‐8”  6.3 m  200ft  61 m 

10ft  3 m  21’‐6”  6.6 m  250ft  76 m 

10.5ft  3.2 m  21’‐10”  6.7 m  300ft  91 m  

10’‐9”  3.3 m  22 ft  6.7 m  400ft  120 m 

           

           

           

           

 

 

   

Page 23: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Dimensions Found in NFPA 13‐2016 

8/21/2017 3 

 

Area 

3.5 ft2  0.3 m2  256 ft2  24 m2  2,700 ft2  250 m2 

6 ft2  0.6 m2  300 ft2  28 m2  2,734 ft2  255 m2 

10 ft2  0.9 m2  306 ft2  28 m2  2,800 ft2  260 m2 

12 ft2  1.1 m2  324 ft2  30 m2  3,000 ft2  280 m2 

16 ft2  1.5 m2  395 ft2  37 m2  3,250 ft2  300 m2 

18 ft2  1.7m2  400 ft2  37 m2  3,300 ft2  305 m2 

20 ft2  1.9m2  450 ft2  42 m2  3,450 ft2  320 m2 

24 ft2  2.2m2  504 ft2  47 m2  3,500 ft2  325 m2 

25 ft2  2.3 m2  585 ft2  54 m2  3,600 ft2  335 m2 

32 ft2  3.0 m2  600 ft2  56 m2  3,750 ft2  350 m2 

50 ft2  4.6 m2  648 ft2  60 m2  3,900 ft2  360 m2 

55 ft2  5.1 m2  700 ft2  65 m2  4,000 ft2  370 m2 

64 ft2  5.9 m2  756 ft2  70 m2  4,100 ft2  380 m2 

70 ft2  6.5 m2  768 ft2  71 m2  4,500 ft2  420 m2 

80 ft2  7.4 m2  800 ft2  74 m2  4,800 ft2  445 m2 

90 ft2  8.4 m2  1,000 ft2  93 m2  5,000 ft2  465 m2 

100 ft2  9 m2  1,200ft2  112 m2  6,000 ft2  555 m2 

110 ft2  10 m2  1,300 ft2  120 m2  6,400 ft2  595 m2 

120 ft2  11 m2  1,365 ft2  125 m2  8,000 ft2  740 m2 

124 ft2  12 m2  1,400 ft2  130 m2  8,800 ft2  820 m2 

130 ft2  12 m2  1,500 ft2  140 m2  10,000 ft2  930 m2 

144 ft2  13 m2  1,700 ft2  160 m2  13,100 ft2  1 215 m2 

150 ft2  14 m2  1,800 ft2  165 m2  25,000 ft2  2 320 m2 

168 ft2  16 m2  1,950 ft2  180 m2  40,000 ft2  3 720 m2 

175 ft2  16 m2  2,000 ft2  185 m2  50,000 ft2  4 650 m2 

196 ft2  18 m2  2,300 ft2  215 m2  52,000 ft2  4 830 m2 

200 ft2  18 m2  2,500 ft2  230m2  100,000 ft2  9 230 m2 

225 ft2  20 m2  2,535 ft2  235 m2     

250 ft2  23 m2  2,600 ft2  240 m2     

           

 

 

   

Page 24: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Dimensions Found in NFPA 13‐2016 

8/21/2017 4 

 

Volume 

1.76 cuin  28 ml  160 ft3  4.5 m3 

15.5 ft3  0.5 m3  400 ft3  11 m3 

17.4 ft3  0.5 m3  1,000 ft3  28 m3 

17.6 ft3  0.5 m3  1,800 ft3  51 m3 

20.7 ft3  0.6 m3  2,100 ft3  59 m3 

21.1 ft3  0.6 m3  2,300 ft3  65 m3 

22 ft3  0.6 m3  6,500 ft3  184 m3 

100 ft3  2.8 m3  2.25M ft3  63,720 m3 

       

       

 

Capacity 

16 oz.  0.5 l 

32 oz.  1 l 

1 gal  4 l 

5 gal  20 l 

40 gal  150 l 

100 gal  380 l 

150 gal  570 l 

250 gal  950 l 

500 gal  1900 l 

750 gal  2850 l 

300,000 gal  1,135,500 l 

 

Drill Size 

3/32”  2,3 mm 

1/8”  3,2 mm 

3/8”  10 mm 

   

 

Density of Cotton Bales 

22.0 lb/ft3  350 kg/m3 

22.7 lb/ft3  365 kg/m3 

24.2 lb/ft3  390 kg/m3 

28.4 lb/ft3  455 kg/m3 

28.7 lb/ft3  460 kg/m3 

32.2 lb/ft3  515 kg/m3 

   

 

   

Page 25: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Dimensions Found in NFPA 13‐2016 

8/21/2017 5 

 

Flow 

30 gpm  115 lpm  300 gpm  1150 lpm  1000 gpm  3800 lpm 

15 gpm  57 lpm  400 gpm  1500 lpm  1500 gpm  5700 lpm 

20 gpm  75 lpm  500 gpm  1900 lpm  1992 gpm  7540 lpm 

50 gpm  190 lpm  600 gpm  2250 lpm  1993 gpm  7543 lpm 

60 gpm  230 lpm  700 gpm  2650 lpm  2156 gpm  8160 lpm 

100 gpm  380 lpm  750 gpm  2850 lpm  2575 gpm  9750 lpm 

102.8 gpm  390 lpm  800 gpm  3050 lpm  4907 gpm  18,572 lpm 

200 gpm  760 lpm  850 gpm  3200 lpm     

215.8 gpm  815 lpm  900 gpm  3400 lpm     

250 gpm  950 lpm         

           

           

           

 

Pressure 5 psi 0.3 bar 75 5.2 bar 7 0.5 bar 90 6.2 bar 10 0.7 bar 100 6.9 bar 11 .8 bar 150 10 bar 15 1.0 bar 165 11 bar 20 1.4 bar 175 12 bar 22 15 bar 189 13 bar 25 1.7 bar 200 14 bar 30 2.1 bar 259 17 bar 35 2.4 bar 300 21 bar 50 3.4 bar 400 28 bar 63 4.3 bar

 

 

 

 

Gauge 

12  2.8 mm 

14  1.98 mm 

16  1.57 mm 

22  .78 mm 

24  .63mm 

 

 

Page 26: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Dimensions Found in NFPA 13‐2016 

8/21/2017 6 

 

 

Weight 

6 lb  2.7 kg  350 lb  160 kg 

10 lb  4.5 kg  440 lb  200 kg 

20 lb  9.1 kg  520 lb  235 kg 

40 lb  18 kg  750 lb  340 kg 

61 lb  27 kg  787 lb   355 kg 

91 lb  41 kg  1200 lb  544 kg 

131 lb  59 kg  1634 lb  740 kg 

200 lb  91 kg  2000 lb   907 kg 

250 lb  115 kg  2300 lb  1043 kg 

    4000 lb  1815 kg 

       

 

Velocity 

30 mph  49 km/h 

 

   

Page 27: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Dimensions Found in NFPA 13‐2016 

8/21/2017 7 

 

Discharge Density 

gpm/ft2  mm/min  gpm/ft2  mm/min 

.005  .2  .425  17.3 

.05  2.04  .426  17.4 

.1  4.1  .44  17.9 

.15  6.1  .45  18.3 

.16  6.5  .46  18.7 

.17  7.0  .49  20 

.18  7.3  .5  20.4 

.19  7.7  .55  22.4 

.2  8.2  .56  22.8 

.21  8.6  .57  23.2 

.225  9.2  .6  24.5 

.24  9.8  .61  24.9 

.25  10.2  .65  26.5 

.26  10.6  .68  27.7 

.28  11.4  .7  28.5 

.29  11.8  .74  30.2 

.3  12.2  .75  30.6 

.31  12.6  .77  31.4 

.32  13.0  .8  32.6 

.33  13.4  .85  34.6 

.34  13.9  .9  36.7 

.35  14.3  .92  37.5 

.37  15.1  .96  39.1 

.375  15.3  1.1  44.8 

.39  15.9  1.2  48.9 

.4  16.3  6.0  245 

.42  17.1  7.5  306 

       

 

Page 28: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Second Revision No. 1025-NFPA 13-2017 [ Chapter 6 ]

Chapter 6 Installation Underground Piping

6.1* Piping.

[24:10.1]

A.6.1

Copper tubing (Type K) with brazed joints conforming to Table 6.1.1.1 and Table 6.2.1.1 is acceptable forunderground service.

(1) Listing and labeling.certification Certification organizations list or label the following:

(a) Cast iron and ductile iron pipe (cement-lined and unlined, coated and uncoated)

(b) Steel pipe

(c) Copper pipe

(d) Fiberglass filament-wound epoxy pipe and couplings

(e) Polyethylene pipe

(f) Polyvinyl chloride (PVC) pipe and couplings

(g) Reinforced concrete pipe (cylinder pipe, nonprestressed and prestressed)

[24:A.10.1]

6.1.1*

All piping used in private fire service mains shall be in accordance with 6.1.1.1, 6.1.1.2, or 6.1.1.3. [24:10.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 32 10/27/2017, 8:33 AM

Page 29: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.1.1.1 Listing.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 32 10/27/2017, 8:33 AM

Page 30: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Piping manufactured in accordance with Table 6.1.1.1 shall be permitted to be used. [24:10.1.1.1]

Table 6.1.1.1 Manufacturing Standards for Underground Pipe

Materials and Dimensions Standard

Ductile Iron

Cement-Mortar Lining for Ductile-Iron Pipe and Fittings for WaterAWWAC104/A21.4

Polyethylene Encasement for Ductile-Iron Pipe SystemsAWWAC105/A21.5

Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and FittingsAWWAC111/A21.11

Flanged Ductile-Iron Pipe with Ductile-Iron or Gray-Iron Threaded FlangesAWWAC115/A21.15

Thickness Design of Ductile-Iron PipeAWWAC150/A21.50

Ductile-Iron Pipe, Centrifugally Cast for WaterAWWAC151/A21.51

Standard for the Installation of Ductile Iron Water Mains and Their Appurtenances AWWA C600

Concrete

Reinforced Concrete Pressure Pipe, Steel-Cylinder Type AWWA C300

Prestressed Concrete Pressure Pipe, Steel-Cylinder Type AWWA C301

Reinforced Concrete Pressure Pipe, Non-Cylinder Type AWWA C302

Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, Pretensioned AWWA C303

Standard for Asbestos-Cement Distribution Pipe, 4 in. Through 16 in., for WaterDistribution Systems

AWWA C400

Cement-Mortar Lining of Water Pipe Lines in Place, 4 in. (100 mm) and Larger — in Place AWWA C602

Plastic

Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in.(100 mm Through 300 mm) ,for Water Transmission and Distribution

AWWA C900

Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings , 14 in. Through 48 in. (350mm Through 1200 mm) , for Water Transmission and Distribution

AWWA C905

Polyethylene (PE) Pressure Pipe and Fittings, 4 in. (100 mm) Through 63 in. (1575 mm) forWaterworks Distribution

AWWA C906

Molecularly Oriented Polyvinyl Chloride (PVCO) 4 in. Through 24 in. (100 mm Through600 mm) for Water, Wastewater, and Reclaimed Water Service

AWWA C909

Brass

Specification for Seamless Red Brass Pipe, Standard Sizes ASTM B43

Copper

Specification for Seamless Copper TubeASTMB75/B75M

Specification for Seamless Copper Water Tube ASTM B88

Requirements for Wrought Seamless Copper and Copper-Alloy Tube ASTM B251

Stainless Steel

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

3 of 32 10/27/2017, 8:33 AM

Page 31: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Materials and Dimensions Standard

Specification for Standard Specification for Seamless, Welded, and Heavily Cold WorkedAustenitic Stainless Steel Pipes

ASTMA312/312M

[24:Table 10.1.1.1]

6.1.1.2

Piping specifically listed for use in private fire service mains shall be permitted to be used. [24:10.1.1.2]

6.1.1.2.1

Where listed pipe is used, it shall be installed in accordance with the listing limitations including installationinstructions. [24:10.1.1.2.1]

6.1.1.2.2

Where listing limitations or installation instructions differ from the requirements of this standard, the listinglimitations and installation instructions shall apply. [24:10.1.1.2.2]

6.1.1.3

Steel piping manufactured in accordance with Table 6.1.1.3 that is externally coated and wrapped andinternally galvanized shall be permitted to be used between the hose coupling(s) on the fire departmentconnection and the check valve installed in the fire department connection piping. [24:10.1.1.3]

Table 6.1.1.3 Steel Piping for Fire Department Connections

Materials and Dimensions Standard

Standard Specification for Black and Hot-Dipped Zinc-Coated (Galvanized) Welded andSeamless Steel Pipe for Fire Protection Use

ASTMA795/A795M

Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded andSeamless

ASTM A53/A53M

Standard Specification for Electric-Resistance-Welded Steel PipeASTM

A135/A135M

[24:Table 10.1.1.3]

6.1.1.3.1

External coating and wrapping as required by 6.1.1.3 shall be approved. [24:10.1.1.3.1]

6.1.1.4 Dry Pipe Underground.

6.1.1.4.1

Where necessary to place pipe that will be under air pressure underground, the pipe shall be protectedagainst corrosion.

6.1.1.4.2

Unprotected cast-iron or ductile-iron pipe shall be permitted where joined with a gasketed joint listed for airservice underground.

6.1.2*

All piping used in private fire service mains shall be rated for the maximum system working pressure to whichthe piping is exposed to but shall not be rated at less than 150 psi (10 10.3 bar). [24:10.1.2]

6.1.3*

When lined piping is used, the manufacturer’s literature for internal diameter shall be used for all hydrauliccalculations. [24:10.1.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

4 of 32 10/27/2017, 8:33 AM

Page 32: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

A.6.1.3

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

5 of 32 10/27/2017, 8:33 AM

Page 33: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

For internal diameters of cement-lined ductile iron pipe, see See Table A.6.1.3. [ 24: A.10.1.3]

Table A.6.1.3 Internal Diameters (IDs) for Cement-Lined Ductile Iron Pipe

Pipe Size(in.)

OD(in.)

PressureClass

ThicknessClass

WallThickness

Minimum LiningThickness*

ID (in.) withLining

3 3.96 350 0.25 1⁄16 3.34

3 3.96 51 0.25 1⁄16 3.34

3 3.96 52 0.28 1⁄16 3.28

3 3.96 53 0.31 1⁄16 3.22

3 3.96 54 0.34 1⁄16 3.16

3 3.96 55 0.37 1⁄16 3.10

3 3.96 56 0.40 1⁄16 3.04

4 4.80 350 0.25 1⁄16 4.18

4 4.80 51 0.26 1⁄16 4.16

4 4.80 52 0.29 1⁄16 4.10

4 4.80 53 0.32 1⁄16 4.04

4 4.80 54 0.35 1⁄16 3.98

4 4.80 55 0.38 1⁄16 3.92

4 4.80 56 0.41 1⁄16 3.86

6 6.90 350 0.25 1⁄16 6.28

6 6.90 50 0.25 1⁄16 6.28

6 6.90 51 0.28 1⁄16 6.22

6 6.90 52 0.31 1⁄16 6.16

6 6.90 53 0.34 1⁄16 6.10

6 6.90 54 0.37 1⁄16 6.04

6 6.90 55 0.40 1⁄16 5.98

6 6.90 56 0.43 1⁄16 5.92

8 9.05 350 0.25 1⁄16 8.43

8 9.05 50 0.27 1⁄16 8.39

8 9.05 51 0.30 1⁄16 8.33

8 9.05 52 0.33 1⁄16 8.27

8 9.05 53 0.36 1⁄16 8.21

8 9.05 54 0.39 1⁄16 8.15

8 9.05 55 0.42 1⁄16 8.09

8 9.05 56 0.45 1⁄16 8.03

10 11.10 350 0.26 1⁄16 10.46

10 11.10 50 0.29 1⁄16 10.40

10 11.10 51 0.32 1⁄16 10.34

10 11.10 52 0.35 1⁄16 10.28

10 11.10 53 0.38 1⁄16 10.22

10 11.10 54 0.41 1⁄16 10.16

10 11.10 55 0.44 1⁄16 10.10

10 11.10 56 0.47 1⁄16 10.04

12 13.20 350 0.28 1⁄16 12.52

12 13.20 50 0.31 1⁄16 12.46

12 13.20 51 0.34 1⁄16 12.40

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

6 of 32 10/27/2017, 8:33 AM

Page 34: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Pipe Size(in.)

OD(in.)

PressureClass

ThicknessClass

WallThickness

Minimum LiningThickness*

ID (in.) withLining

12 13.20 52 0.37 1⁄16 12.34

12 13.20 53 0.40 1⁄16 12.28

12 13.20 54 0.43 1⁄16 12.22

12 13.20 55 0.46 1⁄16 12.16

12 13.20 56 0.49 1⁄16 12.10

14 15.30 250 0.28 3⁄32 14.55

14 15.30 300 0.30 3⁄32 14.51

14 15.30 350 0.31 3⁄32 14.49

14 15.30 50 0.33 3⁄32 14.45

14 15.30 51 0.36 3⁄32 14.39

14 15.30 52 0.39 3⁄32 14.33

14 15.30 53 0.42 3⁄32 14.27

14 15.30 54 0.45 3⁄32 14.21

14 15.30 55 0.48 3⁄32 14.15

14 15.30 56 0.51 3⁄32 14.09

16 17.40 250 0.30 3⁄32 16.61

16 17.40 300 0.32 3⁄32 16.57

16 17.40 350 0.34 3⁄32 16.53

16 17.40 50 0.34 3⁄32 16.53

16 17.40 51 0.37 3⁄32 16.47

16 17.40 52 0.40 3⁄32 16.41

16 17.40 53 0.43 3⁄32 16.35

16 17.40 54 0.46 3⁄32 16.29

16 17.40 55 0.49 3⁄32 16.23

16 17.40 56 0.52 3⁄32 16.17

18 19.50 250 0.31 3⁄32 18.69

18 19.50 300 0.34 3⁄32 18.63

18 19.50 350 0.36 3⁄32 18.59

18 19.50 50 0.35 3⁄32 18.61

18 19.50 51 0.35 3⁄32 18.61

18 19.50 52 0.41 3⁄32 18.49

18 19.50 53 0.44 3⁄32 18.43

18 19.50 54 0.47 3⁄32 18.37

18 19.50 55 0.50 3⁄32 18.31

18 19.50 56 0.53 3⁄32 18.25

20 21.60 250 0.33 3⁄32 20.75

20 21.60 300 0.36 3⁄32 20.69

20 21.60 350 0.38 3⁄32 20.65

20 21.60 50 0.36 3⁄32 20.69

20 21.60 51 0.39 3⁄32 20.63

20 21.60 52 0.42 3⁄32 20.57

20 21.60 53 0.45 3⁄32 20.51

20 21.60 54 0.48 3⁄32 20.45

20 21.60 55 0.51 3⁄32 20.39

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

7 of 32 10/27/2017, 8:33 AM

Page 35: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Pipe Size(in.)

OD(in.)

PressureClass

ThicknessClass

WallThickness

Minimum LiningThickness*

ID (in.) withLining

20 21.60 56 0.54 3⁄32 20.33

24 25.80 200 0.33 3⁄32 24.95

24 25.80 250 0.37 3⁄32 24.87

24 25.80 300 0.40 3⁄32 24.81

24 25.80 350 0.43 3⁄32 24.75

24 25.80 50 0.38 3⁄32 24.85

24 25.80 51 0.41 3⁄32 24.79

24 25.80 52 0.44 3⁄32 24.73

24 25.80 53 0.47 3⁄32 24.67

24 25.80 54 0.50 3⁄32 24.61

24 25.80 55 0.53 3⁄32 24.55

24 25.80 56 0.56 3⁄32 24.49

ID: internal diameter; OD: outside diameter.

*Note: This table is appropriate for single lining thickness only. The actual lining thickness should beobtained from the manufacturer. [24:Table A.10.1.3]

6.1.4*

Where piping installed in a private fire service main must be installed above grade, the piping materials shallconform to NFPA 13. [ 24: 10.1.4] Underground piping shall be permitted to extend into the building throughthe slab or wall not more than 24 in. (600 mm). [ 24: 10.1.4]

6.1.4.1

Underground piping shall be permitted to extend into the building through the slab or wall not more than 24in. (600 mm). [ 24: 10.1.4.1]

6.2 Fittings.

[24:10.2]

6.2.1

All fittings used in private fire service mains shall be in accordance with 6.2.1.1 or 6.2.1.2. [24:10.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

8 of 32 10/27/2017, 8:33 AM

Page 36: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.2.1.1

Fittings manufactured in accordance with Table 6.2.1.1 shall be permitted to be used. [24:Table 10.2.1.1]

Table 6.2.1.1 Fittings Materials and Dimensions

Materials and Dimensions Standard

Cast Iron

Gray Iron Threaded Fittings, Classes 125 and 250 ASME B16.4

Gray Iron Pipe Flanges and Flanged Fittings, Classes 25, 125, and 250 ASME B16.1

Ductile Iron

Ductile-Iron and Gray-Iron Fittings, 3 in. Through 48 in., for Water and other LiquidsAWWAC110/A21.10

Ductile-Iron Compact Fittings, 3 in. Through 24 in. and 54 in. through 64 in. for WaterService

AWWAC153/A21.53

Malleable Iron

Malleable Iron Threaded Fittings, Classes 150 and 300 ASME B16.3

Steel

Factory-Made Wrought Steel Buttweld Fittings ASME B16.9

Buttwelding Ends ASME B16.25

Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderateand Elevated Temperatures

ASTM A234

Pipe Flanges and Flanged Fittings NPS 1 ⁄2 Through 24 ASME B16.5

Forged Steel Fittings, Socket-Welded and Threaded ASME B16.11

Steel Pipe Flanges for Waterworks Service — Sizes 4 in. Through 144 in. AWWA C207

Dimensions for Fabricated Steel Water Pipe Fittings AWWA C208

Copper

Wrought Copper and Bronze Copper Alloy Solder Joint Pressure Fittings ASME B16.22

Cast Cast Bronze Cast Copper Alloy Solder Joint Pressure Fittings ASME B16.18

Bronze Fittings

Cast Bronze Copper Alloy Threaded Fittings, Classes 125 and 250 ASTM B16.15

[24:Table 10.2.2.1 10.2.1.1 ]

6.2.1.2 Special Listed Fittings.

Fittings specifically listed for use in private fire service mains shall be permitted to be used. [24:10.2.1.2]

6.2.1.2.1

Where listed fittings are used, they shall be installed in accordance with their listing limitations includinginstallation instructions. [24:10.2.1.2.1]

6.2.1.2.2

Where listing limitations or installation instructions differ from the requirements of this standard, the listinglimitations and installation instructions shall apply. [24:10.2.1.2.2]

6.2.2

All fittings used in private fire service mains shall be rated for the maximum system working pressure to whichthe fittings are exposed, but shall not be rated at less than 150 psi (10 10.3 bar). [24:10.2.2]

6.2.3

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

9 of 32 10/27/2017, 8:33 AM

Page 37: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Where fittings installed in a private fire service main must be installed above grade, the fittings shall conformto NFPA 13. [24:10.2.3]

6.2.3.1

Fittings in accordance with 6.2.1 shall be permitted for the transition to the above ground piping or fittings.[24:10.2.3.1]

6.3 Connection of Pipe, Fittings, and Appurtenances.

[24:10.3]

6.3.1*

Connection of all fittings and appurtenances to piping shall be in accordance with Section 6.3. [24:10.3.1]

A.6.3.1

The following standards apply to joints used with the various types of pipe:

(1) ASME B16.1, Cast Gray Iron Pipe Flanges and Flanged Fittings Classes 25, 125, and 250

(2) AWWA C111/A21.11 , Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings

(3) AWWA C115/A21.15 , Flanged Ductile-Iron Pipe with Ductile-Iron or Gray-Iron Threaded Flanges

(4) AWWA C206, Field Welding of Steel Water Pipe

(5) AWWA C606, Grooved and Shouldered Joints

[24:A.10.3.1]

6.3.2

Connections of pipe and fittings indicated in Table 6.1.1.1 and Table 6.2.1.1 shall be in accordance with thereferenced standard in the Table table . [24:10.3.2]

6.3.3 Listed Connections.

Connections utilizing listed products shall be in accordance with the listing limitations and the manufacturer’sinstallation instructions. [24:10.3.3]

6.3.3.1

Where listing limitations or installation instructions differ from the requirements of this standard, the listinglimitations and installation instructions shall apply. [24:10.3.3.1]

6.3.4 Threaded Pipe and Fittings.

Where pipe, fittings or appurtenances are connected using threads, all threads shall be in accordance withANSI/ ASME B1.20.1, Pipe Threads, General Purpose (Inch) . [24:10.3.4]

6.3.5 Grooved Connections.

Where pipe, fittings, or appurtenances are connected using grooves, they shall be connected in accordancewith 6.3.5.1 through 6.3.5.3. [24:10.3.5]

6.3.5.1

Pipe, fittings, and appurtenances to be joined with grooved couplings shall contain cut, rolled, or cast groovesthat are dimensionally compatible with the couplings. [24:10.3.5.1]

6.3.5.2

Pipe, fittings, and appurtenances that are connected with grooved couplings and are part of a listed assemblyshall be permitted to be used. [24:10.3.5.2]

6.3.5.3*

Pipe joined with grooved fittings shall be joined by a listed combination of fittings, gaskets, and grooves.[24:10.3.5.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

10 of 32 10/27/2017, 8:33 AM

Page 38: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.3.6 Copper Tube.

All joints for the connection of copper tube shall be brazed or joined using pressure fittings as specified inTable 6.2.1.1. [24:10.3.6]

6.4 Protection of Private Fire Service Mains. [24:10.4]

6.4.1 Protection from Corrosion.

[24:10.4.1]

6.4.1.1 Coatings.

All bolted joint accessories shall be cleaned and thoroughly coated with asphalt or other corrosion-retardingmaterial after installation. [24:10.4.1.1]

6.4.1.2

The requirements of 6.4.1.1 6.3.5.3 shall not apply to epoxy-coated fittings, valves, glands, or otheraccessories. [24:10.4.1.2]

6.4.1.3*

Where it is necessary to join metal pipe with pipe of dissimilar metal, the joint shall be insulated against thepassage of an electric current using an approved method. [24:10.4.1.3]

A.6.4.1.3

Gray cast iron is not considered galvanically dissimilar to ductile iron. Rubber gasket joints (unrestrainedpush-on or mechanical joints) are not considered connected electrically. Metal thickness should not beconsidered a protection against corrosive environments. In the case of cast iron or ductile iron pipe for soilevaluation and external protection systems, see Appendix A of AWWA C105/A21.5 , PolyethyleneEncasement for Ductile-Iron Pipe Systems. [24:A.10.4.1.3]

6.4.2* Protection of Piping. [24:10.4.2]

6.4.2.1 Protection from Freezing.

The depth of cover for private fire service mains and their appurtenances to protect against freezing shall be inaccordance with 6.4.2. [24:10.4.2.1]

6.4.2.1.1*

The top of the pipe shall be buried not less than 1 ft (300 mm) below the frost line for the locality.[24:10.4.2.1.1]

6.4.2.1.2

The depth of piping shall be measured from the top of the piping to the final grade. [24:10.4.2.1.2]

6.4.2.1.3

Where listed piping is used and the bury depth differs from this standard, the listing limitations shall apply.[24:10.4.2.1.3]

6.4.2.1.4

Where private fire service mains are installed above ground, they shall be protected from freezing inaccordance with NFPA 13. [24:10.4.2.1.4]

6.4.2.1.5

Private fire service mains installed in water raceways or shallow streams shall be installed so that the pipingwill remain in the running water throughout the year. [24:10.4.2.1.5]

6.4.2.1.6

Where piping is installed adjacent to a vertical face, it shall be installed from the vertical face at the samedistance as if the piping were buried. [24:10.4.2.1.6]

6.4.2.1.7

Protection of private fire service mains from freezing using heat tracing shall be permitted when the heattracing is specifically listed for underground use. [24:10.4.2.1.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

11 of 32 10/27/2017, 8:33 AM

Page 39: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.4.2.1.7.1

Heat tracing not listed for underground use shall be permitted when piping is installed in accordance with6.1.4. [24:10.4.2.1.7.1]

6.4.2.2 Protection from Mechanical Damage.

The depth of cover for private fire service mains and their appurtenances to protect against mechanicaldamage shall be in accordance with 6.4.2.2.3 6.4.2.2 . [24:10.4.2.2]

6.4.2.2.1

The depth of piping shall be measured from the top of the piping to the final grade. [24:10.4.2.2.1]

6.4.2.2.2

In locations where freezing is not a factor, the depth of cover shall not be less than 30 in. (0.8 m) below gradeto prevent mechanical damage. [24:10.4.2.2.2]

6.4.2.2.2.1

Where listed piping is used and the bury depth differs from this standard, the listing limitations shall apply.[24:10.4.2.2.2.1]

6.4.2.2.3

Private fire service mains installed under driveways or roadways shall be buried at a minimum depth of 3 ft(900 mm). [24:10.4.2.2.3]

6.4.2.2.3.1

Sidewalks, walkways, and other paved or concrete pedestrian passageways shall not be required to complywith 6.4.2.2.3. [24:10.4.2.2.3.1]

6.4.2.2.4

Private fire service mains installed under railroad tracks shall be buried at a minimum depth of 4 ft (1.2 m).[24:10.4.2.2.4]

6.4.2.2.4.1

Where railroad operators require a greater depth of bury, the greater depth shall apply. [24:10.4.2.2.4.1]

6.4.2.2.5

Private fire service mains installed under large piles of heavy commodities or subject to heavy shock andvibrations shall be buried at a minimum depth of 4 ft (1.2 m). [24:10.4.2.2.5]

6.4.2.2.6

Where private fire service mains are installed above ground, they shall be protected with bollards or othermeans as approved by the AHJ when subject to mechanical damage. [24:10.4.2.2.6]

6.4.3 Private Fire Service Mains Under Buildings.

Except as allowed by 6.4.3, private fire service mains shall not be allowed to run under buildings. [24:10.4.3]

6.4.3.1*

Private fire service mains supplying fire protection systems within the building shall be permitted to extend nomore than 10 ft (3 3.0 m), as measured from the outside of the building, under the building to the riserlocation. [24:10.4.3.1]

6.4.3.1.1*

Pipe joints shall not be located directly under foundation fittings. [24:10.4.3.1.1]

6.4.3.1.2*

Piping shall be installed a minimum of 12 in. (300 mm) below the bottom of building foundations or footers.[24:10.4.3.1.2]

6.4.3.1.2.1

The requirements of 6.4.3.1.2 shall not apply when the piping is sleeved with an approved material.[24:10.4.3.1.2.1]

6.4.3.2*

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

12 of 32 10/27/2017, 8:33 AM

Page 40: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Where approved, private fire service mains supplying systems within the building shall Private fire servicemains shall not be permitted to extend more than 10 ft (3 m) under the building when all the requirementsof except as allowed in 6.4.3.2.1, through 6.4.3.2.4 are met . [24:10.4.3.2]

6.4.3.2.1

Where the piping is installed under the building, all foundations or footers over the private fire service mainshall be arched to create a minimum of 24 in. (600 mm) clearance. Where private fire service mains extendmore than 10 ft (3 m) into the building, they shall be run in a covered trench. [24:10.4.3.2.1]

6.4.3.2.1.1*

It shall be acceptable to install the piping in covered trenches where the trenches are The trench shall beaccessible from within the building. [24:10.4.3.2.2 10.4.3.2.1.1 ]

A.6.4.3.2.1.1

A grate or steel plate are common methods of accessing the trench. [ 24: A.10.4.3.2.1.1]

6.4.3.2.1.2

All joints shall be mechanically restrained. The trench shall have rigid walls and a base.[24:10.4.3.2.3 10.4.3.2.1.2 ]

6.4.3.2.1.3

A valve shall be installed before the piping enters under the building and within 24 in. (600 mm) of where thepiping enters the building. The trench shall be constructed of noncombustible materials.[24:10.4.3.2.4 10.4.3.2.1.3 ]

6.4.3.2.1.4*

Provisions for draining water shall be provided for the trench. [ 24: 10.4.3.2.1.4]

6.4.3.2.1.5

Where the piping in the trench is installed under foundations or footers, clearance shall be provided inaccordance with 6.4.3.1.2 or 6.4.3.1.2.1 . [ 24: 10.4.3.2.1.5]

6.4.3.2.2

Piping in the trench shall be permitted to be in accordance with 6.1.1 . [ 24: 10.4.3.2.2]

6.4.3.2.2.1

Aboveground piping in accordance with NFPA 13 shall be permitted to be used. [ 24: 10.4.3.2.2.1]

6.4.3.2.2.2

Where piping installed in the trench is in accordance with 6.1.1 , all joints shall be restrained in accordancewith 6.6.2 or 6.6.3 . [ 24: 10.4.3.2.2.2]

6.4.3.2.3*

Where piping is installed in a trench as permitted by 6.4.3.2.1 , a valve shall be provided where theunderground piping enters the trench. [ 24: 10.4.3.2.3]

6.4.3.2.4

When piping is installed in a trench, bury depths of 6.4.2.2 shall not apply. [ 24: 10.4.3.2.4]

6.4.3.2.4.1

Piping in the trench shall be protected from freezing in accordance with 6.4.2.1.4 . [ 24: 10.4.3.2.4.1]

6.5 Grounding and Bonding.

[24:10.5]

6.5.1*

In no case shall the underground piping be used as a grounding electrode for electrical systems. [24:10.5.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

13 of 32 10/27/2017, 8:33 AM

Page 41: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.5.1.1*

The requirement of 6.5.1 shall not preclude the bonding of the underground piping to the lightning protectiongrounding system as required by NFPA 780 in those cases where lightning protection is provided for thestructure. [24:10.5.1.1]

6.6* Restraint.

Private fire service mains shall be restrained against movement at changes in direction in accordance with6.6.1, 6.6.2, or 6.6.3. [24:10.6]

6.6.1* Thrust Blocks.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

14 of 32 10/27/2017, 8:33 AM

Page 42: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

A.6.6.1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

15 of 32 10/27/2017, 8:33 AM

Page 43: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

The use of concrete thrust blocks is one method of restraint, provided that stable soil conditions prevail andspace requirements permit placement. Successful blocking is dependent on factors such as location,availability and placement of concrete, and possibility of disturbance by future excavations.

Resistance is provided by transferring the thrust force to the soil through the larger bearing area of the blockso that the resultant pressure against the soil does not exceed the horizontal bearing strength of the soil.The design of thrust blocks consists of determining the appropriate bearing area of the block for a particularset of conditions. The parameters involved in the design include pipe size, design pressure, angle of thebend (or configuration of the fitting involved), and the horizontal bearing strength of the soil.

Table A.6.6.1(a) gives the nominal thrust at fittings for various sizes of ductile-iron and PVC piping. FigureA.6.6.1(a) shows an example of how thrust forces act on a piping bend.

Table A.6.6.1(a) Thrust at Fittings at 100 psi (6.9 bar) Water Pressure for Ductile Iron and PVC Pipe

Nominal PipeDiameter (in.)

Total Pounds

DeadEnd

90 DegreeBend

45 DegreeBend

221⁄2 DegreeBend

111⁄4 DegreeBend

51⁄8 DegreeBend

4 1,810 2,559 1,385 706 355 162

6 3,739 5,288 2,862 1,459 733 334

8 6,433 9,097 4,923 2,510 1,261 575

10 9,677 13,685 7,406 3,776 1,897 865

12 13,685 19,353 10,474 5,340 2,683 1,224

14 18,385 26,001 14,072 7,174 3,604 1,644

16 23,779 33,628 18,199 9,278 4,661 2,126

18 29,865 42,235 22,858 11,653 5,855 2,670

20 36,644 51,822 28,046 14,298 7,183 3,277

24 52,279 73,934 40,013 20,398 10,249 4,675

30 80,425 113,738 61,554 31,380 15,766 7,191

36 115,209 162,931 88,177 44,952 22,585 10,302

42 155,528 219,950 119,036 60,684 30,489 13,907

48 202,683 286,637 155,127 79,083 39,733 18,124

Notes:

(1) For SI units, 1 lb = 0.454 kg; 1 in. = 25.4 mm.

(2) To determine thrust at pressure other than 100 psi (6.9 bar), multiply the thrust obtained in the table bythe ratio of the pressure to 100 psi (6.9 bar). For example, the thrust on a 12 in., 90 degree bend at 125 psi(8.6 bar) is 19,353 × 125/100 = 24,191 lb (10,973 kg).

[24:Table A.10.6.1(a)]

Table A.6.6.1(b) Required Horizontal Bearing Block Area

Nominal PipeDiameter (in.)

Bearing Block

Area (ft2)Nominal PipeDiameter (in.)

Bearing Block

Area (ft2)Nominal PipeDiameter (in.)

Bearing Block

Area (ft2)

3 2.6 12 29.0 24 110.9

4 3.8 14 39.0 30 170.6

6 7.9 16 50.4 36 244.4

8 13.6 18 63.3 42 329.9

10 20.5 20 77.7 48 430.0

Notes:

(1) Although the bearing strength values in this table have been used successfully in the design of thrustblocks and are considered to be conservative, their accuracy is totally dependent on the accurate soilidentification and evaluation. The ultimate responsibility for selecting the proper bearing strength of a

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

16 of 32 10/27/2017, 8:33 AM

Page 44: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

particular soil type must rest with the design engineer.

(2) Values listed are based on a 90-degree horizontal bend, an internal pressure of 100 psi, a soil horizontal

bearing strength of 1,000 lb/ft2, a safety factor of 1.5, and ductile-iron pipe outside diameters.

(a) For other horizontal bends, multiply by the following coefficients: for 45 degree: 0.541; for 221⁄2 degree:0.276; for 111⁄4 degree: 0.139.

(b) For other internal pressures, multiply by ratio to 100 psi.

(c) For other soil horizontal bearing strengths, divide by ratio to 1,000 lb/ft2.

(d) For other safety factors, multiply by ratio to 1.5.

Example. Using Table A.6.6.1(b), find the horizontal bearing block area for a 6 in. diameter, 45-degree bend

with an internal pressure of 150 psi. The soil bearing strength is 3000 lb/ft2, and the safety factor is 1.5.

From Table A.6.6.1(b), the required bearing block area for a 6 in. diameter, 90-degree bend with an internal

pressure of 100 psi and a soil horizontal bearing strength of 1000 psi is 7.9 ft2.

 For example:

[A.10.6.1a] [A.6

[24:Table A.10.6.1(b)]

Table A.6.6.1(c) Horizontal Bearing Strengths

Bearing Strength, Sb

Soil lb/ft2 kN/m2

Muck 0 0

Soft clay 1000 47.9

Silt 1500 71.8

Sandy silt 3000 143.6

Sand 4000 191.5

Sandy clay 6000 287.3

Hard clay 9000 430.9

Note: Although the bearing strength values in this table have been used successfully in the design of thrustblocks and are considered to be conservative, their accuracy is totally dependent on accurate soilidentification and evaluation. The ultimate responsibility for selecting the proper bearing strength of aparticular soil type must rest with the design engineer.

[24:Table A.10.6.1(c)]

Figure A.6.6.1(a) Thrust Forces Acting on a Bend. [24:Figure A.10.6.1(a)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

17 of 32 10/27/2017, 8:33 AM

Page 45: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Thrust blocks are generally categorized into two groups — bearing and gravity blocks. Figure A.6.6.1(b)depicts a typical bearing thrust block on a horizontal bend. [24:A.10.6.1]

Figure A.6.6.1(b) Bearing Thrust Block. [24:Figure A.10.6.1(b)]

The following are general criteria for bearing block design:

(1) The bearing surface should, where possible, be placed against undisturbed soil.

(2) Where it is not possible to place the bearing surface against undisturbed soil, the fill between thebearing surface and undisturbed soil must be compacted to at least 90 percent Standard Proctordensity.

(3) Block height (h) should be equal to or less than one-half the total depth to the bottom of the block (Ht)

but not less than the pipe diameter (D).

(4) Block height (h) should be chosen such that the calculated block width (b) varies between one and twotimes the height.

(5) Gravity thrust blocks can be used to resist thrust at vertical down bends. In a gravity thrust block, theweight of the block is the force providing equilibrium with the thrust force. The design problem is then tocalculate the required volume of the thrust block of a known density. The vertical component of thethrust force in Figure A.6.6.1(c) is balanced by the weight of the block. For required horizontal bearingblock areas, see Table A.6.6.1(b).

The required block area (Ab) is as follows:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

18 of 32 10/27/2017, 8:33 AM

Page 46: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

[A.10.6.1b] [A.6

where:

Ab = required block area (ft2)

h = block height (ft)

b = calculated block width (ft)

T = thrust force (lbf)

Sf = safety factor (usually 1.5)

Sb = bearing strength (lb/ft2)

Then, for a horizontal bend, the following formula is used:

[A.10.6.2.1c] [A

where:

b = calculated block width (ft)

Sf = safety factor (usually 1.5 for thrust block design)

P = water pressure (lb/in.2)

A = cross-sectional area of the pipe based on outside diameter

h = block height (ft)

Sb = horizontal bearing strength of the soil (lb/ft2) (in.2)

A similar approach can be used to design bearing blocks to resist the thrust forces at locations such as teesand dead ends. Typical values for conservative horizontal bearing strengths of various soil types are listedin Table A.6.6.1(c). [24:A.10.6.1]

Figure A.6.6.1(c) Gravity Thrust Block. [24:Figure A.10.6.1(c)]

In lieu of the values for soil bearing strength shown in Table A.6.6.1(c), a designer might choose to usecalculated Rankine passive pressure (Pp) or other determination of soil-bearing strength based on actual

soil properties.

It can be easily be shown that Ty = PA sin θ. The required volume of the block is as follows:

[A.10.6.2.1d] [A

where:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

19 of 32 10/27/2017, 8:33 AM

Page 47: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Vg = block volume (ft3)

Sf = safety factor

P = water pressure (psi)

A = cross-sectional area of the pipe interior

Wm = density of the block material (lb/ft3)

In a case such as the one shown, the horizontal component of thrust force is calculated as follows:

[A.10.6.2.1e] [A

where:

Tx = horizontal component of the thrust force

P = water pressure (psi)

A = cross-sectional area of the pipe interior

The horizontal component of thrust force should must be resisted by the bearing of the right side of theblock against the soil. Analysis of this aspect follows the same principles as the previous section on bearingblocks. [24:A.10.6.1]

6.6.1.1

Thrust blocks shall be permitted where soil is stable and capable of resisting the anticipated thrust forces.[24:10.6.1.1]

6.6.1.2

Thrust blocks shall be of concrete of a mix not leaner than one part cement, two and one-half parts sand, andfive parts stone. [24:10.6.1.2]

6.6.1.3

Thrust blocks shall be placed between undisturbed earth and the fitting to be restrained and shall be capableof resisting the calculated thrust forces. [24:10.6.1.3]

6.6.1.4

Wherever possible, thrust blocks shall be located so that the joints are accessible for repair. [24:10.6.1.4]

6.6.2* Restrained Joint Systems.

Private fire service mains using restrained joint systems shall include one or more of the following:

(1) Locking mechanical or push-on joints

(2) Mechanical joints utilizing setscrew retainer glands

(3) Bolted flange joints

(4) Pipe clamps and tie rods

(5) Other approved methods or devices

[24:10.6.2]

6.6.2.1 Sizing Clamps, Rods, Bolts, and Washers.

[24:10.6.2.1]

6.6.2.1.1 Clamps.

[24:10.6.2.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

20 of 32 10/27/2017, 8:33 AM

Page 48: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.6.2.1.1.1

Clamps shall have the following dimensions:

(1) 1⁄2 in. × 2 in. (12 mm × 50 mm) for 4 in. (100 mm) to 6 in. (150 mm) pipe

(2) 5⁄8 in. × 21⁄2 in. (16 mm × 65 mm) for 8 in. (200 mm) to 10 in. (250 mm) pipe

(3) 5⁄8 in. × 3 in. (16 mm × 75 mm) for 12 in. (300 mm) pipe

[24:10.6.2.1.1.1]

6.6.2.1.1.2

The diameter of a bolt hole shall be 1⁄8 in. (3 3.2 mm) larger than that of the corresponding bolts .[24:10.6.2.1.1.2]

6.6.2.1.2 Rods.

[24:10.6.2.1.2]

6.6.2.1.2.1

Rods shall be not less than 5⁄8 in. (16 mm) in diameter. [24:10.6.2.1.2.1]

6.6.2.1.2.2

Table 6.6.2.1.2.2 provides the numbers of various diameter rods that shall be used for a given pipe size.[24:10.6.2.1.2.2]

Table 6.6.2.1.2.2 Rod Number — Diameter Combinations

Nominal Pipe Size (in.) (mm) 5⁄8 in. (16 mm) 3⁄4 in. (20 mm) 7⁄8 in. (22 mm) 1 in. (25 mm)

4 (100) 2 — — —

6 (150) 2 — — —

8 (200) 3 2 — —

10 (250) 4 3 2 —

12 (300) 6 4 3 2

14 (350) 8 5 4 3

16 (400) 10 7 5 4

Note: This table has been derived using pressure of 225 psi (15.5 bar) and design stress of 25,000 psi (172.4MPa).

[24:Table 10.6.2.1.2.2]

6.6.2.1.2.3

When using bolting rods, the diameter of mechanical joint bolts shall limit the diameter of rods to 3⁄4 in.(20 mm). [24:10.6.2.1.2.3]

6.6.2.1.2.4

Threaded sections of rods shall not be formed or bent. [24:10.6.2.1.2.4]

6.6.2.1.2.5

Where using clamps, rods shall be used in pairs for each clamp. [24:10.6.2.1.2.5]

6.6.2.1.2.6

Assemblies in which a restraint is made by means of two clamps canted on the barrel of the pipe shall bepermitted to use one rod per clamp if approved for the specific installation by the AHJ. [24:10.6.2.1.2.6]

6.6.2.1.2.7

Where using combinations of rods, the rods shall be symmetrically spaced. [24:10.6.2.1.2.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

21 of 32 10/27/2017, 8:33 AM

Page 49: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.6.2.1.3 Clamp Bolts.

Clamp bolts shall have the following diameters:

(1) 5⁄8 in. (16 mm) for pipe 4 in. (100 mm), 6 in. (150 mm), and 8 in. (200 mm)

(2) 3⁄4 in. (20 mm) for 10 in. (250 mm) pipe

(3) 7⁄8 in. (22.2 mm) for 12 in. (300 mm) pipe

[24:10.6.2.1.3]

6.6.2.1.4 Washers.

[24:10.6.2.1.4]

6.6.2.1.4.1

Washers shall be permitted to be cast iron or steel and round or square. [24:10.6.2.1.4.1]

6.6.2.1.4.2

Cast-iron washers shall have the following dimensions:

(1) 5⁄8 in. × 3 in. (16 mm × 75 mm) for 4 in. (100 mm), 6 in. (150 mm), 8 in. (200 mm), and 10 in. (250 mm)pipe

(2) 3⁄4 in. × 31⁄2 in. (20 mm × 90 mm) for 12 in. (300 mm) pipe

[24:10.6.2.1.4.2]

6.6.2.1.4.3

Steel washers shall have the following dimensions:

(1) 1⁄2 in. × 3 in. (12 mm × 75 mm) for 4 in. (100 mm), 6 in. (150 mm), 8 in. (200 mm), and 10 in. (250 mm)pipe

(2) 1⁄2 in. × 31⁄2 in. (12 mm × 90 mm) for 12 in. (300 mm) pipe

[24:10.6.2.1.4.3]

6.6.2.1.4.4

The diameter of holes shall be 1⁄8 in. (3.2 mm) larger than that of bolts or rods. [24:10.6.2.1.4.4]

6.6.2.2 Sizes of Restraint Straps for Tees.

[24:10.6.2.2]

6.6.2.2.1

Restraint straps for tees shall have the following dimensions:

(1) 5⁄8 in. (16 mm) thick and 21⁄2 in. (65 mm) wide for 4 in. (100 mm), 6 in. (150 mm), 8 in. (200 mm), and10 in. (250 mm) pipe

(2) 5⁄8 in. (16 mm) thick and 3 in. (75 mm) wide for 12 in. (300 mm) pipe

[24:10.6.2.2.1]

6.6.2.2.2

The diameter of rod holes shall be 1⁄16 in. (1.6 mm) larger than that of rods. [24:10.6.2.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

22 of 32 10/27/2017, 8:33 AM

Page 50: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.6.2.2.3

Figure 6.6.2.2.3 and Table 6.6.2.2.3 shall be used in sizing the restraint straps for both mechanical and push-on joint tee fittings. [24:10.6.2.2.3]

Figure 6.6.2.2.3 Restraint Straps for Tees. [24:Figure 10.6.2.2.3]

Table 6.6.2.2.3 Restraint Straps for Tees

Nominal Pipe Size A B C D

in. mm in. mm in. mm in. mm in. mm

4 100 121⁄2 318 101⁄8 257 21⁄2 64 13⁄4 44

6 150 141⁄2 368 121⁄8 308 39⁄16 90 213⁄16 71

8 200 163⁄4 425 143⁄8 365 421⁄32 118 329⁄32 99

10 250 191⁄16 484 1611⁄16 424 53⁄4 146 5 127

12 300 225⁄16 567 193⁄16 487 63⁄4 171 57⁄8 149

[24:Table 10.6.2.2.3]

6.6.2.3 Sizes of Plug Strap for Bell End of Pipe.

[24:10.6.2.3]

6.6.2.3.1

The strap shall be 3⁄4 in. (20 mm) thick and 21⁄2 in. (65 mm) wide. [24:10.6.2.3.1]

6.6.2.3.2

The strap length shall be the same as dimension A for tee straps as shown in Figure 6.6.2.2.3. [24:10.6.2.3.2]

6.6.2.3.3

The distance between the centers of rod holes shall be the same as dimension B for tee straps as shown inFigure 6.6.2.2.3. [24:10.6.2.3.31 ]

6.6.2.4 Material.

Clamps, rods, rod couplings or turnbuckles, bolts, washers, restraint straps, and plug straps shall be of amaterial that has physical and chemical characteristics that indicate its deterioration under stress can bepredicted with reliability. [24:10.6.2.4]

6.6.2.5* Corrosion Resistance.

After installation, rods, nuts, bolts, washers, clamps, and other restraining devices shall be cleaned andthoroughly coated with a bituminous or other acceptable corrosion-retarding material. [24:10.6.2.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

23 of 32 10/27/2017, 8:33 AM

Page 51: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

A.6.6.2.5

Examples of materials and the standards covering these materials are as follows:

(1) Clamps, steel

(2) Rods, steel

(3) Bolts, steel (ASTM A307, Standard Specification for Carbon Steel Bolts, Studs, Threaded Rod 60,000psi Tensile Strength )

(4) Washers, steel, cast iron (Class A cast iron as defined by ASTM A126, Standard Specification forGray Iron Castings for Valves, Flanges and Pipe Fittings )

(5) Anchor straps and , plug straps, steel

(6) Rod couplings or , turnbuckles, malleable iron (ASTM A197/A197M, Standard Specification for CupolaMalleable Iron )

The materials specified in A.6.6.2.5(1) through A.6.6.2.5(6) do not preclude the use of other materials thatwill also satisfy the requirements of this section. [24:A.10.6.2.4 5 ]

6.6.2.5.1

The requirements of 6.6.2.5 shall not apply to epoxy-coated fittings, valves, glands, or other accessories.[24:10.6.2.5.1]

6.6.3*

Private fire service mains utilizing one or more of the following connection methods shall not require additionalrestraint, provided that such joints can pass the hydrostatic test of 6.10.2.2 without shifting of piping.

(1) Threaded connections

(2) Grooved connections

(3) Welded connections

(4) Heat-fused connections

(5) Chemical or solvent cemented connections

[24:10.6.3]

6.7 Steep Grades.

[24:10.7]

6.7.1

On steep grades, mains shall be additionally restrained to prevent slipping. [24:10.7.1]

6.7.1.1

Pipe shall be restrained at the bottom of a hill and at any turns (lateral or vertical). [24:10.7.1.1]

6.7.1.1.1

The restraint specified in 6.7.1.1 shall be to natural rock or to suitable piers built on the downhill side of thebell. [24:10.7.1.1.1]

6.7.1.2

Bell ends shall be installed facing uphill. [24:10.7.1.2]

6.7.1.3

Straight runs on hills shall be restrained as determined by a design professional. [24:10.7.1.3]

6.8 Installation Requirements.

[24:10.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

24 of 32 10/27/2017, 8:33 AM

Page 52: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.8.1

Piping, valves, hydrants, gaskets, and fittings shall be inspected for damage when received and shall beinspected prior to installation. [24:10.8.1]

6.8.2

The tightness of bolted joints shall be verified by the bolt torque or by the method described in the listinginformation or manufacturer’s installation instructions. [24:10.8.2]

6.8.3

Pipe, valves, hydrants, and fittings shall be clean and free from internal debris. [24:10.8.3]

6.8.4

When work is stopped, the open ends of piping, valves, hydrants, and fittings shall be plugged or covered toprevent foreign materials from entering. [24:10.8.4]

6.8.5

All piping, fittings, valves, and hydrants shall be examined for cracks or other defects while suspended abovethe trench and lowered into the trench using appropriate equipment. [24:10.8.5]

6.8.6

Plain ends shall be inspected for signs of damage prior to installation. [24:10.8.6]

6.8.7

Piping, fittings, valves, hydrants, and appurtenances shall not be dropped, dumped or rolled or skiddedagainst other materials. [24:10.8.7]

6.8.8

Pipes shall be supported in the trench throughout their full length and shall not be supported by the bell endsonly or by blocks. [24:10.8.8]

6.8.9

If the ground is soft, other means shall be provided to support the pipe. [24:10.8.9]

6.8.10

Valves and fittings used with nonmetallic pipe shall be supported and restrained in accordance with themanufacturer’s installation instructions. [24:10.8.10]

6.9 Backfilling.

[24:10.9]

6.9.1

Backfill material shall be tamped in layers or in puddled puddles under and around pipes to preventsettlement or lateral movement and shall contain no ashes, cinders, refuse, organic matter, or other corrosivematerials . [24:10.9.1]

6.9.2

Backfill material shall not contain ash, cinders, refuse, organic matter or other corrosive materials. [24:10.9.2]

6.9.3*

Rocks shall not be used for backfill. In the absence of specific guidelines or specifications, the maximumallowable particle size for backfill within 1 ft (300 mm) of the pipe shall not be larger than 1 1 ⁄2 in. (40 mm).[24:10.9.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

25 of 32 10/27/2017, 8:33 AM

Page 53: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

A.6.9.3

The maximum particle size allowed next to most types of pipe can be found in ASTM C136/136M,Standard Test Method for Sieve Analysis of Fine and Coarse Aggregates, ASTM D2487, StandardPractice for Classification of Soils for Engineering Purposes (Unified Soil Classification System), AWWAM55, PE Pipe — Design and Installation , AWWA M23, PVC Pipe — Design and Installation, tradeassociation handbooks, or manufacturers’ literature. These publications typically recommend onemaximum allowable particle size that applies to the bedding, embedment, and backfill, which might bedifferent materials. The maximum particle size might be dependent on the pipe diameter. [ 24: A.10.9.3]

6.9.3.1

Nominal pipe sizes of 4 in. (100 mm) or smaller shall not exceed 1 ⁄2 in. (13 mm) maximum particle size.[ 24: 10.9.3.1]

6.9.3.2

Nominal pipe sizes of 6 in. to 12 in. (150 mm to 300 mm) shall not exceed 3 ⁄4 in. (19 mm) maximumparticle size. [ 24: 10.9.3.2]

6.9.4

Frozen earth shall not be used as backfill material. [24:10.9.4]

6.9.5

In trenches cut through rock, tamped backfill shall be used for at least 6 in. (150 mm) under and around thepipe and for at least 2 ft (600 mm) above the pipe. [24:10.9.5]

6.9.6

Where using piping listed for private fire service mains, the manufacturer’s installation instructions for backfillshall be followed. [24:10.9.6]

6.10 Testing and Acceptance.

[24:10.10]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

26 of 32 10/27/2017, 8:33 AM

Page 54: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.10.1 Approval of Underground Piping.

The installing contractor shall be responsible for the following:

(1) Notifying the AHJ and the owner’s representative of the time and date testing is to be performed

(2) Performing all required acceptance tests

(3) Completing and signing the contractor’s material and test certificate(s) shown in Figure 6.10.1

[24:10.10.1]

Figure 6.10.1 Sample of Contractor’s Material and Test Certificate for Underground Piping. [24:Figure10.10.1]

6.10.2 Acceptance Requirements.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

27 of 32 10/27/2017, 8:33 AM

Page 55: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

[24:10.10.2]

6.10.2.1* Flushing of Piping.

[24:10.10.2.1]

6.10.2.1.1

Underground piping, from the water supply to the system riser, and lead-in connections to the system riser,including all hydrants, shall be completely flushed before connection is made to downstream fire protectionsystem piping. [24:10.10.2.1.1]

6.10.2.1.2

The flushing operation shall continue until water flow is verified to be clear of debris. [24:10.10.2.1.2]

6.10.2.1.3*

The minimum rate of flow shall be in accordance with Table 6.10.2.1.3. [24:10.10.2.1.3]

Table 6.10.2.1.3 Flow Required to Produce a Velocity of 10 ft/sec (3 3.0 m/sec) in Pipes

Nominal Pipe Size Flow Rate

in. mm gpm L/min

2 50 100 379

21⁄2 65 150 568

3 75 220 833

4 100 390 1,500

5 125 610 2,300

6 150 880 3,350

8 200 1,560 5,900

10 250 2,440 9,250

12 300 3,520 13,300

[24:Table 10.10.2.1.3]

A.6.10.2.1.3

The velocity of approximately 10 ft/sec (3.0 m/sec) was used to develop Table 6.10.2.1.3 because thisvelocity has been shown to be sufficient for moving obstructive material out of the pipes. It is not importantthat the velocity equal exactly 10 ft/sec (3.0 m/sec), so there is no reason to increase the flow during thetest for slightly different internal pipe dimensions. Note that where underground pipe serves as suction pipefor a fire pump, NFPA 20 requires greater flows for flushing the pipe. [ 24: A.10.10.2.1.3]

6.10.2.1.3.1

Where the flow rates established in Table 6.10.2.1.3 are not attainable, the maximum flow rate available to thesystem shall be acceptable. [24:10.10.2.1.3.1]

6.10.2.1.4

Provision shall be made for the proper disposal of water used for flushing or testing. [24:10.10.2.1.4]

6.10.2.2 Hydrostatic Test.

[24:10.10.2.2]

6.10.2.2.1*

All piping and attached appurtenances subjected to system working pressure shall be hydrostatically tested atgauge pressure of 200 psi (13.8 bar) or 50 psi (3.4 bar) in excess of the system working pressure, whicheveris greater, and shall maintain that pressure at gauge pressure of ±5 psi (0.34 bar) for 2 hours. [24:10.10.2.2.1]

6.10.2.2.2

Acceptable test results shall be determined by indication of either a pressure loss less than gauge pressure of5 psi or by no visual leakage. [24:10.10.2.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

28 of 32 10/27/2017, 8:33 AM

Page 56: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

6.10.2.2.3

The test pressure shall be read from one of the following, located at the lowest elevation of the system or theportion of the system being tested:

(1) A gauge located at one of the hydrant outlets

(2) A gauge located at the lowest point where no hydrants are provided

[24:10.10.2.2.3]

6.10.2.2.4*

The trench shall be backfilled between joints before testing to prevent movement of pipe. [24:10.10.2.2.4]

6.10.2.2.5

Where required for safety measures presented by the hazards of open trenches, the pipe and joints shall bepermitted to be backfilled, provided the installing contractor takes the responsibility for locating and correctingleakage. [24:10.10.2.2.5]

6.10.2.2.6* Hydrostatic Testing Allowance.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

29 of 32 10/27/2017, 8:33 AM

Page 57: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

Where additional water is added to the system to maintain the test pressures required by 6.10.2.2.1, theamount of water shall be measured and shall not exceed the limits of Table 6.10.2.2.6, which are based uponthe following equations :  U.S. Customary Units:

[6.10.2.2.6a]

where:

L = testing allowance (makeup water) [gph (gal/hr)]

S = length of pipe tested (ft)

D = nominal diameter of the pipe (in.)

P = average test pressure during hydrostatic test (gauge psi) Metric Units:

[6.10.2.2.6b]

where:

L = testing allowance (makeup water) (L/hr)

S = length of pipe tested (m)

D = nominal diameter of pipe (mm)

P = average test pressure during the hydrostatic test (kPa) [24:10.10.2.2.6]

Table 6.10.2.2.6 Hydrostatic Testing Allowance at 200 psi (13.8 bar) (gph/100 ft of Pipe) (lph/100 m of Pipe)

Nominal Pipe Diameter Testing Allowance

in.(mm) in.(mm) gph/100 ft of pipe (lph/100 m of pipe)

2 (50) 0.019 (0.236)

4 (100) 0.038 (0.472)

6 (150) 0.057 (0.708)

8 (200) 0.076 (0.944)

10 (250) 0.096 (1.19)

12 (300) 0.115 (1.43)

14 (350) 0.134 (1.66)

16 (400) 0.153 (1.90)

18 (450) 0.172 (2.14)

20 (500) 0.191 (2.37)

24 (600) 0.229 (2.84)

Notes:

(1) For other length, diameters, and pressures, utilize Equation 10.10.2.2.6a 6.10.2.2.6a or10.10.2.2.6b 6.10.2.2.6b to determine the appropriate testing allowance.

(2) For test sections that contain various sizes and sections of pipe, the testing allowance is the sum of thetesting allowances for each size and section.

[24:Table 10.10.2.2.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

30 of 32 10/27/2017, 8:33 AM

Page 58: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

A.6.10.2.2.6

One acceptable means of completing this test is to utilize a pressure pump that draws its water supply froma full container. At the completion of the 2-hour test, the amount of water to refill the container can bemeasured to determine the amount of makeup water. To In order to minimize pressure loss, the pipingshould be flushed to remove any trapped air. Additionally, the piping should could be pressurized for 1 dayprior to the hydrostatic test to account for expansion, absorption, entrapped air, and so on.

The use of a blind flange or skillet is preferred for use when hydrostatically testing segments of new work.Metal-seated valves are susceptible to developing slight imperfections during transport, installation, andoperation and thus can be likely to leak more than 1 fl oz/in. (1.2 mL/mm) of valve diameter per hour. Forthis reason, the blind flange should be used when hydrostatically testing. [24:A.10.10.2.2.6]

6.10.2.3* Other Means of Hydrostatic Tests.

Where required by acceptable to the AHJ, hydrostatic tests shall be permitted to be completed in accordancewith the requirements of guidelines provided in AWWA C600, Installation of Ductile-Iron Mains and TheirAppurtenances, AWWA M9, Concrete Pressure Pipe, AWWA M23, PVC Pipe — Design and Installation, orC602, AWWA C603, and AWWA C900. AWWA M55, PE Pipe — Design and Installation , as long as the testpressure and test duration requirements of 6.10.2.2.1 are still employed. [24:10.10.2.3]

6.10.2.4 Operating Test.

[24:10.10.2.4]

6.10.2.4.1

Each hydrant shall be fully opened and closed under system water pressure. [24:10.10.2.4.1]

6.10.2.4.2

Dry barrel hydrants shall be checked for proper drainage. [24:10.10.2.4.2]

6.10.2.4.3

All control valves shall be fully closed and opened under system water pressure to ensure proper operation.[24:10.10.2.4.3]

6.10.2.4.4

Where fire pumps supply the private fire service main, the operating tests required by 6.10.2.4 shall becompleted with the pumps running. [24:10.10.2.4.4]

6.10.2.5 Backflow Prevention Assemblies.

[24:10.10.2.5]

6.10.2.5.1

The backflow prevention assembly shall be forward flow tested to ensure proper operation. [24:10.10.2.5.1]

6.10.2.5.2

The minimum flow rate required by tested in 6.10.2.5.1 shall be the system demand, including hose streamdemand where applicable. [24:10.10.2.5.2]

Supplemental Information

File Name Description Approved

Chapter_6_extract_updates.docx For staff use ✓

Submitter Information Verification

Submitter Full Name: AUT-PRI

Organization: National Fire Protection Assoc

Street Address:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

31 of 32 10/27/2017, 8:33 AM

Page 59: Second Revision No. 1040-NFPA 13-2017 [ Global Comment ]

City:

State:

Zip:

Submittal Date: Wed Aug 16 11:31:59 EDT 2017

Committee Statement and Meeting Notes

Committee Statement: Updates extracted material form NFPA 24.

Response Message:

Editorial Comment