SDS_SSL_MPM_UN_A4
-
Upload
robson-fernandes -
Category
Documents
-
view
213 -
download
0
description
Transcript of SDS_SSL_MPM_UN_A4
SmartStruxure™ LiteSolution
MPM SeriesMulti-purpose Manager (MPM-UN)
Get Control. Get Efficient. Get Value.
CompatibleSite and zone managers providing wired and wireless integrated control solutions for HVAC, lighting, and metering, as well as remote management via StruxureWare™ Building Expert.
SmartStruxure Lite solution Multi-Purpose Manager Features
AT A GLANCE Networking
• Ethernet connector for BACnet Ethernet/IP
• 802.15.4 wireless mesh (25 nodes/network)
• Wired serial bus for daisy chain (CANbus)
Third-party interoperability
• BACnet, EWS, oBIX, FTP
• EnOcean (wireless)
• ZigBee Pro (wireless)
• Modbus
• CANbus
Inputs/Outputs
• Inputs: 6 universal (analog: 4-20mA, 0-10V, digital: dry contact, thermistor: 1-100K)
• Outputs: 2 relay, 4 analog
• EnOcean (wireless): 49 devices
• ZigBee Pro (wireless): 30 peripherals
Other
• Real-time clock
• 400MHz processor
• 64MB of RAM
• 4GB of Flash for local storage
• StruxureWare™ Building Expert
2
Multi-Purpose Management devices (MPM) enable the control, monitoring, and management of entire sites via StruxureWare Building Expert. They can also be used for wired and wireless zone control in larger buildings.
Control features• Control of wired end-devices (6 inputs, 6 outputs)• Wireless control of EnOcean end-devices
(optional, 49 points per MPM)• Wireless control of ZigBee Pro end-devices
(optional, 30 peripherals per MPM)• Modbus RTU• Programmable via StruxureWare Building Expert• Points visible through BACnet®, EcoStruxure®
Web Services (EWS), and oBIX®
• Real-time response to scripting/graphical programming
ApplicationsSupports HVAC, lighting, and metering application including:• HVAC and lighting room and zone control• Unitary equipment such as rooftop HVAC
units, air handling units, heat pumps, and dehumidification units
• Mechanical rooms and equipment cabinets• Metering: Modbus option enables management
of a wide variety of power meters and other metering devices. Can also manage wireless meters and sub-meters
Networking Between Units• Wireless: ZigBeePro wireless mesh network (self-forming/healing, 25 nodes per network)• Wired: Daisy chain• IP/Ethernet: Ethernet port
Embedded Gateway• EnOcean (wireless) to BACnet IP/oBIX/EWS• ZigBee Pro (wireless) to BACnet IP/oBIX/EWS• Modbus to BACnet IP/oBIX/EWS
StruxureWare Building ExpertAll MPM models have an embedded web server hosting Building Expert, a web-based intelligent building management system that allows complete configuration and management of small sites. Building Expert offers dashboards, maps, graphical programming, scripting, scheduling, trend logging and more. It is the perfect mini-iBMS for small and medium buildings. It can also be integrated with other SmartStruxure™ solutions
SmartStruxure Lite solution Multi-Purpose Manager Specifications3
SpecificationsPower
Voltage
24VAC; ± 15%; 50/60HZ
24VDC ± 10%
Typical consumption
5 VA + Output (VAC), 1.6 W + Output (VDC)
Battery
CR1220 3v Lithium Coin Cell Battery
General
Processor
ARM9 32-bit, 400MHz
Memory
64MB flash
Storage
4GB flash for local storage
Real-time clock
Battery backed (10,000 hours)
Communication
ZigBee Pro, EnOcean, BACnet
CANbus (125-500 Kbps)
Ethernet (10/100 Mbps)
Enclosure
Material
Rigid ABS
Dimensions
132mm (5.20 in) x 126mm (4.96 in)
Rating
UL94V0-5VB
Mounting
Din-rail, wall or ceiling mount
Environmental
OperatingTemperature
0°C (32°F) - 60°C (140°F)
Storage Temperature
-20°C (-4°F) - 60°C (140°F)
Relative Humidity
0 to 90% non-condensing
Inputs
Quantity
6 universal inputs (configurable)
Analog inputs
Current: 4-20mA with 249 external resistor
Voltage: 0-10V
Digital inputs
Dry contacts
Thermistor
1 k - 100 k
Resolution
14-bit
Outputs
Analog (x4)
0-12V,nominal 50mAmax each, 12-bit
resolution
Relay (x2)
24V, 1.1 Amp per relay
RS485 (optional)
Supported protocols
Modbus
EnOcean (optional)
Frequency
315MHz, 868MHz, 902MHz
Receiver Sensitivity
–95dBm
Conducted Output Power
5dBm
Range
Recommended: 45ft/15m
Line of sight: 100ft/30m
Antenna
External whip, RP SMA 0dBi
ZigBee Pro (optional)
Frequency
2400 – 2483.5MHz, 16RF channels
Data rate / Mod.type
250Kbps
Receiver Sensitivity
-101dBm/-105dBm (amplified)
Nominal Output Power
8dBm/18dBm (amplified)
Range
Recommended to MPM: 150ft/50m
Line of sight to MPM: 300ft/100m
Recommended to peripherals: 50ft/17m
Line of sight to peripherals: 100ft/30m
Antenna
External whip, RP SMA 2.5dbi
StruxureWare™ Building Expert
Software type
Embedded web interface
Local installation
None necessary
PDA/Tablet/Smartphone compatible
Yes, using compatible browsers
Browser compatibility
Firefox ESR
Internet Explorer 10 (only)
Google Chrome
Safari (Mac only)
Agency approvals
Energy Management Equipment, UL 916, Fourth Edition, December 23, 1998, rev. December 17, 2007
CSA Standard for Signal Equipment C22.2 No. 205-M1983 (R2004)
CFR47 FCC Part15, Subpart B:2009
ICES-003: Issue 4 (2004)
CE
Japanese Radio Law
RoHS
Disclaimer
If the equipment is used in a manner not
specified by the manufacturer, the protec-
tion provided by the equipment may be
impaired.
DisclaimerThis device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
• this device may not cause harmful interference
• this device must accept any interference received, including interference that may cause undesired operation.
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions:
this device may not cause interference
this device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes :
l’appareil ne doit pas produire de brouillage
l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.
Changes or modifications not approved by the manufacturer could void the user’s authority to operate the equipment.
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. In order to avoid the possibility of exceeding the FCC radio frequency exposure limits, human proximity to the antenna shall not be less than 20cm during normal operation.
This equipment complies with IC RSS-102 radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator & your body.
© 2
014
Sch
neid
er E
lect
ric. A
ll rig
hts
rese
rved
.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Ordering information
SmartStruxure Lite solution Multi-Purpose ManagerSpecifications (continued)
Output port126mm(4.96 in)
132m
m (5
.20
in)
Ethernet 100B/T
Input port
B A GN
DA
I6G
ND
AI5
GN
DA
I4G
ND
AI3
GN
DA
I2G
ND
AI1
24V AC/DCCAN HCAN LGND
OP
1A
OP
1B
OP
2A
OP
2B
15V
DC
AO
1G
ND
AO
2G
ND
AO
3G
ND
AO
4
EnOcean (optional)(Green striped antenna for 315MHz)(Gray striped antenna for 868MHz)(Yellow striped antenna for 902MHz)
ZigBee Pro (optional)(Pink striped antenna for 2.4GHz)
RS 485 connectors for Modbus (optional)
34mm (1.34 in)
for DIN rail mount
24V AC/DCCAN HCAN L
GND
Manager EnOcean* ZigBee Pro I/O VAV
Part numbers
Build
ing
Expe
rt
Stru
xure
War
e in
tegr
atio
n
315
MH
z
868
MH
z
902
MH
z
Hig
h po
wer
6 in
puts
6 ou
tput
s
Mod
bus
Flow
sen
sor
Actu
ator
MPM-UN-004-5045 x x x x x
MPM-UN-0I4-5045 x x x x x x
MPM-UN-C00-5045 x x x x x
MPM-UN-C04-5045 x x x x x x
MPM-UN-CI4-5045 x x x x x x x
MPM-UN-D04-5045 x x x x x x
MPM-UN-DI4-5045 x x x x x x x
MPM-UN-E00-5045 x x x x x
MPM-UN-E04-5045 x x x x x x
MPM-UN-EI4-5045 x x x x x x x
*EnOcean: Contact EnOcean for the latest information about the frequency in your country.315MHz: Americas, Hong Kong, India, Japan, Thailand, Taiwan868MHz: Europe, China, Malaysia, Singapore, Vietnam, New Zealand902MHz: USA has transitioned to 902 MHz in 2013. Other countries may do so as well.
Schneider Electric- Small Building Systems Americas: Boston ONE Campus, Andover, MA 1-800-225-0962, Europe: Malmö, Sweden +46 40 38 68 50, Asia Pacific: Hong Kong +852 2565 SDS-SSL-MPM-UN-A4.EN.08.2014.v3 www.schneider-electric.com/buildings August 2014
4