TELZAS sp. z o.o. Bugno 3 Street, 78-400 Szczecinek, tel. +48 94 37 29 750, fax +48 94 37 29 800, e-mail: [email protected], www.telzas.com.plv2.0 - valid since: 05.10.2011 Warning: Telzas Sp. z o.o. reserves the right to initiate changes and modifications above-mentioned data without notify.
Basic parameters of the system:
Input parametersInput voltage VAC
3 x 230/400(-23,5%; +26%)
Frequency Hz 45...65
Max. phase current AAC 26
Power factor 1
Output parametersRange of voltage VDC 48...58
Characteristic - UPI
Stabilization of output voltage % 1
Maximum output current ADC 170
Maximum output power W 8000
Output voltage ripples(psophometric value)
mV < 2
General dataRange of ambient temperature C 5...+40
Cooling - fan-cooled
Efficiency %91 (PDC)95.3 (PDM)
Protection class IP20
Electromagnetic compatibility - PN-EN 300-386
Safety -
in accordance
withEN 60 950
System dimensions (HxWxD) mm
134(3U) x 483 x300223(5U) x 483 x300
System weight withoutrectifier units
kg 27
Dimensions of the rectifierunit (HxWxD)
mm 88 x 85,5 x 273
Weight of the rectifier kg 2,4
| Basic functions of the control unit:
+output voltage measurement and control setting ofalarm threshold for low and high system voltage andrectifiers blocking voltage,
+ rectifiers current measurement+battery temperature and ambient temperature
measurement;+ temperature compensation of float voltage during
float operation mode;+automatic battery charging;+battery asymmetry monitoring;+ visualization of alarm states;+status control of battery protections;+status control of load protections;+programming of cut-out battery from the loads
(protection of the battery against deep discharge);
+sending alarm signals;+automatic reporting of alarm states to WinCN
supervisory system;+creating register of events with occurrence date and
time;+possibility of configuration by:
- locally by PC with RS232 or USB port or userinterface (color OLED screen and manipulator),- remote by modem or TCP/IP converter;
+possibility of alarm mapping on any relay contact orsending this as information to WinCN supervisorysystem.
| Extended functions of the control unit:
+ remote supervision of the system by means ofWinCN software with using:- dial-up line (telephone modem),- logical network (TCP/IP).
DC Power Supply System SDC 170