    TELZAS sp. z o.o. Bugno 3 Street, 78-400 Szczecinek, tel. +48 94 37 29 750, fax +48 94 37 29 800, e-mail: [email protected], www.telzas.com.plv2.0 - valid since: 05.10.2011 Warning: Telzas Sp. z o.o. reserves the right to initiate changes and modifications above-mentioned data without notify.

    Basic parameters of the system:

    Input parametersInput voltage VAC

    3 x 230/400(-23,5%; +26%)

    Frequency Hz 45...65

    Max. phase current AAC 26

    Power factor 1

    Output parametersRange of voltage VDC 48...58

    Characteristic - UPI

    Stabilization of output voltage % 1

    Maximum output current ADC 170

    Maximum output power W 8000

    Output voltage ripples(psophometric value)

    mV < 2

    General dataRange of ambient temperature C 5...+40

    Cooling - fan-cooled

    Efficiency %91 (PDC)95.3 (PDM)

    Protection class IP20

    Electromagnetic compatibility - PN-EN 300-386

    Safety -

    in accordance

    withEN 60 950

    System dimensions (HxWxD) mm

    134(3U) x 483 x300223(5U) x 483 x300

    System weight withoutrectifier units

    kg 27

    Dimensions of the rectifierunit (HxWxD)

    mm 88 x 85,5 x 273

    Weight of the rectifier kg 2,4

    | Basic functions of the control unit:

    +output voltage measurement and control setting ofalarm threshold for low and high system voltage andrectifiers blocking voltage,

    + rectifiers current measurement+battery temperature and ambient temperature

    measurement;+ temperature compensation of float voltage during

    float operation mode;+automatic battery charging;+battery asymmetry monitoring;+ visualization of alarm states;+status control of battery protections;+status control of load protections;+programming of cut-out battery from the loads

    (protection of the battery against deep discharge);

    +sending alarm signals;+automatic reporting of alarm states to WinCN

    supervisory system;+creating register of events with occurrence date and

    time;+possibility of configuration by:

    - locally by PC with RS232 or USB port or userinterface (color OLED screen and manipulator),- remote by modem or TCP/IP converter;

    +possibility of alarm mapping on any relay contact orsending this as information to WinCN supervisorysystem.

    | Extended functions of the control unit:

    + remote supervision of the system by means ofWinCN software with using:- dial-up line (telephone modem),- logical network (TCP/IP).

    DC Power Supply System SDC 170