VERTICAL NOTCHES OF SENERGY ADHESIVE / BASE COAT APPLIED TO APPROVED EPS INSULATION BOARD APPROVED EPS INSULATION BOARD 1/2" (13mm) 2" (50mm) 1/2" (13mm) 01 TYPICAL ADHESIVE PATTERN Structure, substrates, flashing, and other items which are not part of the BASF Senergy Channeled Adhesive CI Design system are the responsibility of others. This detail is subject to change without notice. BASF Corporation - Wall Systems (herein after BASF Wall Systems) accepts no liability for the end use of this detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. NTS SCALE: SENERGY CHANNELED ADHESIVE CI DESIGN REV 180205

Transcript of SCALE: NTS 01

Page 1: SCALE: NTS 01

VERTICAL NOTCHES OF SENERGYADHESIVE / BASE COAT APPLIED TOAPPROVED EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

1/2" (13mm)

2" (50mm) 1/2" (13mm)

01

TYPICAL ADHESIVE PATTERN

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 2: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R;-RS;-VBOR WS FLASH W/ FLASHING PRIMER

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

FRAMING

*BY OTHERS

02

TYPICAL APPLICATION

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 3: SCALE: NTS 01

CMU*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R;-RS;-VB,OR WS FLASH W/ FLASHING PRIMER

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

FLASHING*

*BY OTHERS

03

TYPICAL APPLICATION OVER CMU

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 4: SCALE: NTS 01

BRICK*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R;-RS;-VB,OR WS FLASH W/ FLASHING PRIMER

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

FLASHING*

*BY OTHERS

04

TYPICAL APPLICATION OVER BRICK

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 5: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

AESTHETIC REVEAL

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

*BY OTHERS

05

TYPICAL AESTHETIC REVEAL

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

MIN. 3/4" (19MM)

Page 6: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

SENERGY ADHESIVE/ BASE COAT

APPROVED EPS INSULATION BOARD

SENERGY FINISH COAT

FLEXGUARD 4, INTERMEDIATE 6 ORINTERMEDIATE 12 REINFORCING MESHEMBEDDED IN SENERGY BASE COAT

CORNER MESH EMBEDDED INSENERGY BASE COAT

*BY OTHERS

NOTE: A CONTINUOUS OVERLAY OFFLEXGUARD 4, INTERMEDIATE 6, ORINTERMEDIATE 12 IS REQUIRED OVERCORNER MESH

06

TYPICAL CORNER MESH APPLICATION

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

Page 7: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

BACKER ROD AND SEALANT*

PIPE*

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

*BY OTHERS

MAXFLASH OR SEALANT* ATPERIMETER OF PENETRATION

07

TYPICAL PIPE PENETRATION

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 8: SCALE: NTS 01

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

ACCEPTABLE SHEATHING*

SET FLANGE IN SEALANTOR PROVIDE GASKET*

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

BACKER ROD AND SEALANT*

LIGHT FIXTURE*

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

*BY OTHERS

FRAMING*

08

TYPICAL LIGHT FIXTURE

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

SEALANT*

Page 9: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

WS FLASH W/ FLASHING PRIMER

BACKER ROD AND SEALANT(WIDTH PER DESIGN)*

BASF COLOR COAT(OPTIONAL)

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

*BY OTHERS

09

TYPICAL VERTICAL EXPANSION JOINT DETAIL

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 10: SCALE: NTS 01

FRAMING*

ACCEPTABLE SUBSTRATE*

ACCEPTABLE SHEATHING*

WS FLASH WITH FLASHING PRIMER

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

BASF COLOR COAT(OPTIONAL)

BACKER ROD & SEALANT(WIDTH PER DESIGN)*

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

*BY OTHERS

10

TYPICAL EXPANSION JOINT AT CHANGE IN SUBSTRATE

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 11: SCALE: NTS 01

FLOOR SLAB*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

WS FLASH W/ FLASHING PRIMER

BACKER ROD AND SEALANT*(WIDTH PER DESIGN)*

BASF COLOR COAT(OPTIONAL)

SLIP TRACK*

FRAMING*

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

*BY OTHERS

11

TYPICAL EXPANSION JOINT DETAIL AT FLOORLINE

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 12: SCALE: NTS 01

FLOOR SLAB*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R;-RS;-VB,OR WS FLASH W/ FLASHING PRIMER

ACCEPTABLE SHEATHING*

WS FLASH WITH FLASHING PRIMER

FLASHING*

BACKER ROD & SEALANT(WIDTH PER DESIGN)*

BASF COLOR COAT(OPTIONAL)

APPROVED EPS INSULATION BOARD

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

*BY OTHERS

12

TYPICAL DRAINAGE AT FLOORLINE

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 13: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

MAXFLASH, SHEATHING FABRIC EMBEDDEDIN SENERSHIELD-R;-RS;-VB, OR WS FLASHW/ FLASHING PRIMER

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

APPROVED EPS INSULATION BOARD

FLASHING*

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

BACKER ROD & SEALANT*(WIDTH PER DESIGN)*

WS FLASH WITH FLASHING PRIMER

BRICK*

*BY OTHERS

13

TYPICAL ABUTMENT TO BRICK WITH DRAINAGE AT FLOORLINE

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 14: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

APPROVED EPS INSULATION BOARD

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

BACKER ROD & SEALANT(WIDTH PER DESIGN)*

BRICK*

*BY OTHERS

14

TYPICAL CHANNELED ADHESIVE CI DESIGN ABUTMENT TO BRICK

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 15: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

SENERSHIELD-R/SENERSHIELD-RS /SENERSHIELD-VB

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R; -RS; -VB,OR WS FLASH W/ FLASHING PRIMER

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

WRAP BASE COAT ANDSENERGY REINFORCING MESH

FLASHING*

SEALANT*

FOUNDATION*

*BY OTHERS

NOTE:TERMINATE SENERGY CHANNELEDADHESIVE CI DESIGN SYSTEM MIN.8" (203 mm) ABOVE GRADE

MIN: 2" (50mm)MAX: 12" (305mm)

15

TYPICAL TERMINATION AT FOUNDATION

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 16: SCALE: NTS 01

FRAMING*

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

APPROVED EPS INSULATION BOARD

SENERGY LAMINA:SENERGY BASE COATSENERGY REINFORCING MESHSENERGY FINISH COAT

WS FLASH W/ FLASHING PRIMER

WRAP BASE COAT ANDSENERGY REINFORCING MESH

BACKER ROD AND SEALANT(WIDTH PER DESIGN)*

WEEP TUBE*

FOUNDATION*

*BY OTHERS

16

TYPICAL TERMINATION AT FOUNDATION (FLUSH)

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 17: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY LAMINA:SENERGY BASE COATSENERGY REINFORCING MESHSENERGY FINISH COAT

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R; -RS; -VB,OR WS FLASH W/ FLASHING PRIMER

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

FLASHING*

SEALANT*

WINDOW*

*BY OTHERS

NOTE: WRAP MAXFLASH, SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R; -RS; -VB OR WS FLASH W/ FLASHING PRIMER INTO ROUGH OPENING ON HEAD IF ALSO INTENDED TO BE AN AIR BARRIER.

17

TYPICAL WINDOW HEAD (FLUSH)

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

Page 18: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

SENERGY ADHESIVE/ BASE COATAPPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R; -RS; -VB,OR WS FLASH W/ FLASHING PRIMER

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

BASF COLOR COAT(OPTIONAL)

BACKER ROD & SEALANT W/WEEP TUBES AT MAX .16" O.C.*

FLASHING*

SEALANT*

WINDOW*

*BY OTHERS

NOTE: WRAP MAXFLASH, SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R; -RS; -VB OR WS FLASH W/ FLASHING PRIMER INTO ROUGH OPENING ON HEAD IF ALSO INTENDED TO BE AN AIR BARRIER.

18

TYPICAL WINDOW HEAD (FLUSH) WITH WEEP TUBES

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

Page 19: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

SENERGY ADHESIVE/ BASE COATAPPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R; -RS; -VB,OR WS FLASH W/ FLASHING PRIMER

DIVERTER TRACK*

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

BASF COLOR COAT(OPTIONAL)

BACKER ROD & SEALANT(WIDTH PER DESIGN)*

WINDOW*

*BY OTHERS

NOTE: WRAP MAXFLASH, SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R; -RS; -VB OR WS FLASH W/ FLASHING PRIMER INTO ROUGH OPENING ON HEAD IF ALSO INTENDED TO BE AN AIR BARRIER.

19

TYPICAL WINDOW HEAD (FLUSH) WITH DIVERTER TRACK

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

Page 20: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-VB/SENERSHIELD-RS

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R; -RS; -VB,OR WS FLASH W/ FLASHING PRIMER

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

ACCEPTABLE SEALANTAS END DAM*

FLASHING*

SEALANT*

WINDOW*

*BY OTHERS

20

TYPICAL WINDOW HEAD FLASHING W/ SEALANT END DAM

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

NOTE: WRAP MAXFLASH, SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R; -RS; -VB OR WS FLASH W/ FLASHING PRIMER INTO ROUGH OPENING ON HEAD IF ALSO INTENDED TO BE AN AIR BARRIER.

Page 21: SCALE: NTS 01

ACCEPTABLE SHEATHING*

APPROVED EPS INSULATION BOARD

FRAMING*

ADHESIVE / BASE COAT APPLIED TOEPS INSULATION BOARD

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

SENERGY LAMINA:SENERGY BASE COATSENERGY REINFORCING MESHSENERGY FINISH COAT

BASF COLOR COAT(OPTIONAL)BACKER ROD AND SEALANT(WIDTH PER DESIGN)*WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R;-RS;-VB, ORWS FLASH w/ FLASHING PRIMER

WINDOW*

*BY OTHERS

21

TYPICAL WINDOW JAMB (FLUSH)

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

Page 22: SCALE: NTS 01

WINDOW*

BACKER ROD AND SEALANT(WIDTH PER DESIGN)*

BASF COLOR COAT(OPTIONAL)

SENERGY LAMINA:SENERGY BASE COATSENERGY REINFORCING MESHSENERGY FINISH COAT

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R;-RS;-VB,OR WS FLASH 9 w/ FLASHING PRIMER

APPROVED EPS INSULATION BOARD

SENERGY ADHESIVE / BASE COATAPPLIED TO EPS INSULATION BOARD

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

ACCEPTABLE SHEATHING*

FRAMING*

*BY OTHERS

22

TYPICAL WINDOW SILL DETAIL (FLUSH)

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 23: SCALE: NTS 01

SENERGY ADHESIVE / BASE COATAPPLIED TO EPS INSULATION

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

APPROVED EPS INSULATION BOARD

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

SENERGY LAMINA:SENERGY BASE COATSENERGY REINFORCING MESHSENERGY FINISH COAT

BACKER ROD AND SEALANT(WIDTH PER DESIGN)*

WINDOW*

*BY OTHERS

23

TYPICAL WINDOW HEAD (RECESSED)

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

NOTE: WRAP MAXFLASH, SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R; -RS; -VB OR WS FLASH W/ FLASHING PRIMER INTO ROUGH OPENING ON HEAD IF ALSO INTENDED TO BE AN AIR BARRIER.

Page 24: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

APPROVED EPS INSULATION BOARD

SENERGY ADHESIVE / BASE COATAPPLIED TO EPS INSULATION BOARD

SENERGY LAMINA:SENERGY BASE COATSENERGY REINFORCING MESHSENERGY FINISH COAT

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R;-RS;-VB,OR WS FLASH w/ FLASHING PRIMER

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

BASF COLOR COAT(OPTIONAL)

BACKER ROD AND SEALANT*(WIDTH PER DESIGN)*

WINDOW*

*BY OTHERS

24

TYPICAL WINDOW JAMB (RECESSED)

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 25: SCALE: NTS 01

WINDOW*

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R;-RS;-VB, ORWS FLASH W/ FLASHING PRIMER

PAN FLASHING W/ END DAMS*

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

APPROVED EPS INSULATION BOARD

SEALANT*

SENERGY LAMINA:SENERGY BASE COATSENERGY REINFORCING MESHSENERGY FINISH COAT

SENERGY ADHESIVE/ BASE COATAPPLIED TO EPS INSULATION BOARD

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

ACCEPTABLE SHEATHING*

FRAMING*

25

TYPICAL WINDOW SILL DETAIL (RECESSED)

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

*BY OTHERS

NOTE: -EXTEND FLASHING MIN 2" (50 mm) OVER CHANNELED ADHESIVE CI DESIGN -FLASHINGS ARE BY OTHERS AND SHALL BE AS PER DESIGN / CODE REQUIREMENT

Page 26: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R; -RS; -VB,OR WS FLASH W/ FLASHING PRIMER

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

BACKER ROD AND SEALANT*(WIDTH PER DESIGN)

WINDOW*

*BY OTHERS

26TYPICAL FLANGED WINDOW HEAD

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

NOTE: WRAP MAXFLASH, SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R; -RS; -VB OR WS FLASH W/ FLASHING PRIMER INTO ROUGH OPENING ON HEAD IF ALSO INTENDED TO BE AN AIR BARRIER.

Page 27: SCALE: NTS 01

ACCEPTABLE SHEATHING*

APPROVED EPS INSULATION BOARD

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

FRAMING*

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R; -RS; -VB,OR WS FLASH W/ FLASHING PRIMER

BACKER ROD AND SEALANT(WIDTH PER DESIGN)*WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

WINDOW*

*BY OTHERS

27TYPICAL FLANGED WINDOW JAMB

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 28: SCALE: NTS 01

WINDOW*MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R; -RS; -VB,OR WS FLASH W/ FLASHING PRIMER

BACKER ROD AND SEALANT(WIDTH PER DESIGN)*WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESHACCEPTABLE SHEATHING*

APPROVED EPS INSULATION BOARD

SENERGY ADHESIVE/BASE COATAPPLIED TO EPS INSULATION BOARD

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

FRAMING*

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

*BY OTHERS

28TYPICAL FLANGED WINDOW SILL

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

Page 29: SCALE: NTS 01

ROOF SYSTEM*

METAL COPING*

EXTEND SHEATHING FABRIC EMBEDDEDIN SENERSHIELD-R;-RS;-VB, MAXFLASHOR WS FLASH W/ FLASHING PRIMERONTO BOTTOM & FACE OF BLOCKING

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

SEALANT*

SENERGY LAMINA:SENERGY BASE COATSENERGY REINFORCING MESHSENERGY FINISH COAT

APPROVED EPS INSULATION BOARD

SENERGY ADHESIVE / BASE COATAPPLIED TO EPS INSULATION BOARD

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

ACCEPTABLE SHEATHING*

FRAMING*

*BY OTHERS

MIN 2" (50 mm)

29

TYPICAL METAL COPING DETAIL

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

Page 30: SCALE: NTS 01

EPS CAP

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R;-RS;-VB,OR WS FLASH w/ FLASHING PRIMER

SENERGY LAMINA:SENERGY BASE COATSENERGY REINFORCING MESHSENERGY FINISH COAT

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

APPROVED EPS INSULATION BOARD

SENERGY ADHESIVE / BASE COATAPPLIED TO EPS INSULATION BOARD

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

ACCEPTABLE SHEATHING*

FRAMING*

SEALANT*

FLASHING*

ROOF COUNTER FLASHING*

*BY OTHERS

12"

6"

30

TYPICAL PARAPET CAP DETAIL

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

MIN 1" (25 mm )

12"

6"

MIN. 8" (203 mm)ABOVE ROOF

Page 31: SCALE: NTS 01

ACCEPTABLE SUBSTRATE*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R; -RS; -VB,OR WS FLASH W/ FLASHING PRIMER

SENERGY ADHESIVE/ BASE COATAPPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

BACKER ROD & SEALANT*

STEP FLASHING*

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

FLASHING*

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

KICK-OUT FLASHING*

ROOF SHINGLES*

*BY OTHERS

31

TYPICAL KICK-OUT FLASHING

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 32: SCALE: NTS 01

ROOF EDGE FLASHING*

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

SEALANT*

SENERGY LAMINA:SENERGY BASE COATSENERGY REINFORCING MESHSENERGY FINISH COAT

APPROVED EPS INSULATION BOARD

SENERGY ADHESIVE / BASE COATAPPLIED TO EPS INSULATION BOARD

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

ACCEPTABLE SHEATHING*

FRAMING*

*BY OTHERS

MIN. 2" (50MM)

32

TYPICAL ROOF EDGE FLASHING DETAIL

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

Page 33: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

SENERGY ADHESIVE/ BASE COATAPPLIED TO EPS INSULATION BOARD

MAXFLASH, SHEATHING FABRICEMBEDDED IN SENERSHIELD-R;-RS;-VB,OR WS FLASH W/ FLASHING PRIMER

APPROVED EPS INSULATION BOARD

SENERGY LAMINA:SENERGY BASE COATSENERGY REINFORCING MESHSENERGY FINISH COAT

WRAP BASE COAT ANDSENERGY REINFORCING MESH

FLASHING*

SEALANT*

ACCEPTABLE SHEATHING*

SENERGY LAMINA:SENERGY BASE COATSENERGY REINFORCING MESHSENERGY FINISH COAT

*BY OTHERS

33

TYPICAL SECTION AT FASCIA / SOFFIT

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

Page 34: SCALE: NTS 01

RAILING*

RAILING BASE COVER SET IN SEALANT*

BACKER ROD & SEALANT(WIDTH PER DESIGN)*

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

WRAP SENERGY BASE COAT ANDSENERGY REINFORCING MESH

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

APPROVED EPS INSULATION BOARD

ACCEPTABLE SUBSTRATE*

*BY OTHERS

12" MIN.6" MIN.

34

TYPICAL CORE MOUNTED RAILING ATTACHMENT

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180702

Page 35: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

ADHESIVE/ BASE COAT APPLIED TOEPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

MOUNTING BRACKET SET IN SEALANT*

SLEEVE SET IN SEALANT*

WOOD BLOCKING*

MECHANICAL FASTENER SET INSEALANT*

RAILING*

*BY OTHERS

35

TYPICAL RAILING ATTACHMENT

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205

Page 36: SCALE: NTS 01

FRAMING*

ACCEPTABLE SHEATHING*

SENERSHIELD-R/SENERSHIELD-RS/SENERSHIELD-VB

ADHESIVE/ BASE COAT APPLIED TOEPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

SIGN*

SLEEVE SET IN SEALANT*

SEALANT AT PERIMETER OFPENETRATION*

WOOD BLOCKING*

MOUNTING BRACKET*

MECHANICAL FASTENER SET INSEALANT*

WASHER*

*BY OTHERS

36

TYPICAL SIGN ATTACHMENT

Structure, substrates, flashing, and other items which are not part of the BASF SenergyChanneled Adhesive CI Design system are the responsibility of others. This detail is subjectto change without notice. BASF Corporation - Wall Systems (herein after BASF WallSystems) accepts no liability for the end use of this detail. For conditions not shown, consultBASF Wall Systems for review of specific detail.

NTSSCALE:SENERGY CHANNELED ADHESIVE CI DESIGN

REV 180205