AS-906E 1 Specifications SCS (System Core Server) Model BCY44100M General SCS (System Core Server) is a controller that integrates DDC (direct digital controller) and RS (remote station), such as PARAMATRIX -III and Infilex series controllers, into BMS (building management system) savic-net FX. SCS is also a B-BC (BACnet ® building controller) and thus interoperable with other manufacturers’ (third-party) devices. SCS saves the data, collected by DDC every minute, for 48 hours. (Note that alarm data is excluded.) Regarding ON/OFF data points and status data points, equipment runtime and ON/OFF count are recorded and saved in SCS. Direct input terminals (fire DI, private generation DI, power feeding information DI) are provided on SCS. SCS, in case of power failure, is reliable to receive and save the data, and the BMS therefore can be recovered. SCS conforms to all the applicable standards of CE Marking (Class A). Specifications Item Specification CPU 32-bit CPU Main storage capacity 128MB SDRAM 128MB CompactFlash ® memory Max. data points 1,000 points Host system communication BACnet ® IP (Ethernet: 10BASE-T/100BASE-TX), 1 channel LC-bus (LonTalk ® protocol) (LAN cable: compliant with EIA/TIA-568 Category 5 or over (φ0.5 mm × 4 poles)), 78 kbps NC-bus (JIS IPEV-S cable (0.9 mm × 1 pole)), 4,800 bps Modbus TCP (Ethernet) To communicate with Modbus RTU (RS-485), media converter is required. Remote units communication CPL (RS-485) Media converter is required. Connectable lines 4 lines connectable Connectable remote units 100 remote units connectable Time backup 72 hours Rated input voltage 100 V AC to 240 V AC Allowable voltage range 90 V AC to 264 V AC Allowable ambient condition 5 °C 40 °C (in operation) 10 %RH to 85 %RH (non-condensing) 2000 m or lower altitude Dimensions (mm) 100 (W) × 106 (D) × 140 (H) Weight 1.0 kg Grounding condition 100 Ω or lower ground resistance Note: JIS: Japanese Industrial Standards CE Marking Conformity This product must be installed in a panel cabinet. Besides, the product in the panel cabinet must be out of reach of unauthorized people who are not well-trained for electric facilities. This product complies with the following Electromagnetic Compatibility (EMC) and the Low Voltage Directive (LVD). EMC : EN61326-1 Class A, Table 2 (For use in an industrial electromagnetic environment) LVD : EN61010-1 Overvoltage category II Pollution degree 2

Transcript of savic-net FX SCS (System Core Server) Model BCY44100M ... · PDF fileSCS (System Core Server)...

Page 1: savic-net FX SCS (System Core Server) Model BCY44100M ... · PDF fileSCS (System Core Server) Model BCY44100M General ... BMS (building management system) ... Item Specification

AS-906E

1

Specifications

SCS (System Core Server) Model BCY44100M

General SCS (System Core Server) is a controller that integrates DDC (direct digital controller) and RS (remote station), such as PARAMATRIX™-III and Infilex™ series controllers, into BMS (building management system) savic-net™ FX.

SCS is also a B-BC (BACnet® building controller) and thus interoperable with other manufacturers’ (third-party) devices.

SCS saves the data, collected by DDC every minute, for 48 hours. (Note that alarm data is excluded.) Regarding ON/OFF data points and status data points, equipment runtime and ON/OFF count are recorded and saved in SCS.

Direct input terminals (fire DI, private generation DI, power feeding information DI) are provided on SCS. SCS, in case of power failure, is reliable to receive and save the data, and the BMS therefore can be recovered.

SCS conforms to all the applicable standards of CE Marking (Class A).

Specifications Item Specification

CPU 32-bit CPU Main storage capacity 128MB SDRAM

128MB CompactFlash® memory Max. data points 1,000 points Host system communication BACnet® IP (Ethernet: 10BASE-T/100BASE-TX), 1 channel

LC-bus (LonTalk® protocol) (LAN cable: compliant with EIA/TIA-568 Category 5 or over (φ0.5 mm × 4 poles)), 78 kbps NC-bus (JIS IPEV-S cable (0.9 mm × 1 pole)), 4,800 bps Modbus TCP (Ethernet) To communicate with Modbus RTU (RS-485), media converter is required.

Remote units communication

CPL (RS-485) Media converter is required.

Connectable lines 4 lines connectable Connectable remote units 100 remote units connectable Time backup 72 hours Rated input voltage 100 V AC to 240 V AC Allowable voltage range 90 V AC to 264 V AC Allowable ambient condition 5 °C 40 °C (in operation)

10 %RH to 85 %RH (non-condensing) 2000 m or lower altitude

Dimensions (mm) 100 (W) × 106 (D) × 140 (H) Weight 1.0 kg Grounding condition 100 Ω or lower ground resistance

Note: ∗ JIS: Japanese Industrial Standards

CE Marking Conformity This product must be installed in a panel cabinet. Besides, the product in the panel cabinet must be out of reach of unauthorized people who are not well-trained for electric facilities.

This product complies with the following Electromagnetic Compatibility (EMC) and the Low Voltage Directive (LVD).

EMC : EN61326-1 Class A, Table 2 (For use in an industrial electromagnetic environment)

LVD : EN61010-1 Overvoltage category II

Pollution degree 2

Page 2: savic-net FX SCS (System Core Server) Model BCY44100M ... · PDF fileSCS (System Core Server) Model BCY44100M General ... BMS (building management system) ... Item Specification

AS-906E

2

Model Numbers Model number Description

BCY44100 SCS base model number M 100 V AC to 240 V AC power 0 0 Fixed 0 NC-bus model: 4 NC-bus lines (Applicable to Infilex controllers for IP) 1 Redundant NC-bus model: 4 NC-bus lines 2 LC-bus (LonTalk® protocol) model: 4 LC-bus lines (2 channels: 2 lines per 1 channel) 6 NC-bus/Modbus/CPL model: 4 lines 0 DIN rail mount type 1 Sub panel mount type

Safety Instructions Please read instructions carefully and use the product as specified in this manual. Be sure to keep this manual near by for ready reference.

Usage Restrictions

This product is targeted for general air conditioning. Do not use this product in a situation where human life may be affected. If this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact Azbil Corporation's sales representative. Azbil Corporation will not bear any responsibility for the results produced by the operators.

CAUTION

• Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.

• This product must be installed under the operating conditions (power, temperature, humidity, vibration, shock, installation position, atmospheric condition, etc) specified in this manual to prevent product damages.

• This product must be operated within its rated operating ranges specified in this manual. Failure to comply will cause product damages.

Trademark information: Infilex, Neopanel, PARAMATRIX, and savic-net are trademarks or registered trademarks of Azbil Corporation in Japan or in other countries. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). Ethernet is a U.S. registered trademark of Xerox Corporation. Linux is a trademark of Linus Torvalds. LonTalk is a trademark of Echelon Corporation registered in the United States and other countries.

Page 3: savic-net FX SCS (System Core Server) Model BCY44100M ... · PDF fileSCS (System Core Server) Model BCY44100M General ... BMS (building management system) ... Item Specification

AS-906E

3

Cellular phone for Alarm e-mail or Short Message

Service

Client PCs (Web Access via Browser)

Infilex VC

LS-bus (LonTalk)

Infilex series Controllers for IP

BACnet/OPC

Server

LC-bus (LonTalk)

System Core

Server (SCS)

Client PCs (Web Access via Browser)

3rd Party Intelligent Building

Management System

System Management

Server (SMS)

Data Storage Server (DSS)

Remote Access via telephone line

Yamatake NC-bus Devices

3rd Party Modbus Devices

3rd Party BACnet

Systems**

** Fire Alarm, Chiller, etc.

Infilex GC(Operator Panel I-type Option)

Infilex AC (Operator Panel I-type Option)

Infilex VC

Infilex SC

Infilex ZM

Infilex FC

Infilex SC

Infilex GD(Operator Panel I-type Option)

PMX-III for Pump/Chiller

UT module

Operator Panel P-typeor Neopanelor Neoplate

Neopanelor Neoplateor Operator Panel P-type

Neoplateor Neopanelor Operator Panel P-type

3rd Party Lon Devices

Infilex FC

Antivirus Firewalls

Neopanelor

Neoplate

Neopanelor

Neoplate

Neopanelor

Neoplate

Neopanelor

Neoplate

Virtual Private Network

Management Integration Server (MIS)

R series Controllers

3rd Party PLC

Annunciator Graphic Driver

Master (AGM)

Annunciator (ANN) and

Graphic Driver (GDR)

Laser printer

BACnet IP network

UT module

UT module

ANN/GDR Line

System Configurations savic-net FX BMS configuration

Figure 1. System configuration Notes: ∗ Azbil Corporation's Model R series controllers communicate with CPL (Controller Peripheral Link, developed by Azbil Corporation) over

RS-485. Media converter therefore is required to connect to SCS (BACnet IP over Ethernet). ∗ Though SCS directly communicates with Modbus TCP over Ethernet, SCS cannot directly communicate with Modbus RTU over RS-485.

Media converter therefore is required to connect to Modbus RTU devices.

Azbil Corporation

Page 4: savic-net FX SCS (System Core Server) Model BCY44100M ... · PDF fileSCS (System Core Server) Model BCY44100M General ... BMS (building management system) ... Item Specification

AS-906E

4

Items shown in Fig. 1 indicate the devices and protocols configuring the system. See Table 1 for the descriptions. Table 1. Devices and protocols configuring savic-net FX system

Item Description AGM Azbil Corporation's Annunciator/Graphic Driver Master ANN Annunciator BACnet® Data communication protocol for Building Automation and Control Networks (developed by ASHRAE) DSS Azbil Corporation's Data Storage Server GDR Graphic Driver Infilex™ AC Azbil Corporation's AHU (air handling unit) controller for LonTalk® protocol Infilex™ FC Azbil Corporation's FCU (fan coil unit) controller for LonTalk® protocol Infilex™ GC Azbil Corporation's multipurpose controller for LonTalk® protocol Infilex™ GD Azbil Corporation's multipurpose data gathering panel for LonTalk® protocol Infilex™ SC Azbil Corporation's AHU (air handling unit) controller for LonTalk® protocol Infilex™ VC Azbil Corporation's VAV (variable air volume) controller with damper actuator for LonTalk® protocol Infilex™ ZM Azbil Corporation's zone manager for LonTalk® protocol IP Internet Protocol LC-bus LonTalk® protocol Controller bus (provided by Azbil Corporation) LonTalk® Communication protocol for LONWORKS network LS-bus LonTalk® protocol Sub-controller bus (provided by Azbil Corporation) MIS Azbil Corporation's Management Integration Server Modbus Serial communication protocol for PLC (developed by Modicon) Modbus RTU Modbus protocol over RS-485 (RTU: Remote Terminal Unit) Modbus TCP Modbus protocol over Ethernet (TCP: Transmission Control Protocol) Neopanel™ Azbil Corporation's digital user terminal Neoplate Azbil Corporation's analog user terminal Operator Panel (I-type) Azbil Corporation's Integral type Operator Panel Operator Panel (P-type) Azbil Corporation's Panel-mount type Operator Panel PLC Programmable Logic Controller PMX-III Azbil Corporation's PARAMATRIX™-III DDC controller for LonTalk® protocol R series controllers Azbil Corporation's single loop controllers SCS Azbil Corporation's System Core Server SMS Azbil Corporation's System Management Server UT module Azbil Corporation's user terminal interface

Page 5: savic-net FX SCS (System Core Server) Model BCY44100M ... · PDF fileSCS (System Core Server) Model BCY44100M General ... BMS (building management system) ... Item Specification

AS-906E

5

Dimensions Model BCY44100M000 / BCY44100M002 / BCY44100M006

Figure 2. Dimensions (mm): Model BCY44100M000 / BCY44100M002 / BCY44100M006

Model BCY44100M001 (Redundant NC-bus model)

Figure 3. Dimensions (mm): Model BCY44100N001

100 106 14

0

130 106

140

Page 6: savic-net FX SCS (System Core Server) Model BCY44100M ... · PDF fileSCS (System Core Server) Model BCY44100M General ... BMS (building management system) ... Item Specification

AS-906E

6

Page 7: savic-net FX SCS (System Core Server) Model BCY44100M ... · PDF fileSCS (System Core Server) Model BCY44100M General ... BMS (building management system) ... Item Specification

AS-906E

7

Page 8: savic-net FX SCS (System Core Server) Model BCY44100M ... · PDF fileSCS (System Core Server) Model BCY44100M General ... BMS (building management system) ... Item Specification

AS-906E

Specifications are subject to change without notice.

Building Systems Company http://www.azbil.com/ Rev.7.0 Sep. 2015 AS-906E H (W03) Printed in Japan.