SAN JOSE CITY COLLEGE MSK-001 - SJECCD

10
Supplemental #: Original Drawing: Date: Scale: SAN JOSE CITY COLLEGE SYMBOL LIST & GENERAL NOTES - MECHANICAL MSK-001 1089-0002 11/10/15 PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING 1 ADDENDUM 1 01-15-2016 M0.01 NO SCALE DSA STRUCTURAL ANCHORAGE COORDINATION SCHEDULE sketch SYMBOL DESCRIPTION LOCATION MOUNTED ON SUPPORT TYPE SUPPORT MODEL NUMBER DIMENSIONS MAX WEIGHT (LBS) REFERENCE DRAWINGS ANCH MODEL NO DIA OVERALL DIMENSIONS (LxWxH) AHU-1 AIR HANDLER LOCKER ROOF CONCRETE PAD FANS SPRING ISOLATED SEE NOTES BELOW 66"Wx100"Hx210"L 6000 M2.02, 8/M7.03 KBTZ AHU-2 AIR HANDLER UPPER ROOF STEEL BEAMS FANS SPRING ISOLATED SEE NOTES BELOW 250"Wx104"Hx390"L 26000 M2.03, 5/S5.21, 3/M7.04 KBTZ AHU-3 AIR HANDLER UPPER ROOF STEEL BEAMS FANS SPRING ISOLATED SEE NOTES BELOW 198"Wx84"Hx365"L 17400 M2.03, 5/S5.21, 3/M7.04 KBTZ CHWP-1 BASE MOUNTED PUMP HYRONICS 157 CONCRETE PAD B-1 OR TYPE 1 SEE NOTES BELOW 540 1/M4.01, 5/M7.02 KBTZ CHWP-2 BASE MOUNTED PUMP HYDRONICS 157 CONCRETE PAD B-1 OR TYPE 1 SEE NOTES BELOW 540 1/M4.01, 5/M7.02 KBTZ CU-1 CONDENSING UNIT UPPER ROOF SLEEPERS SEE NOTES BELOW 532 M2.03, 2/M7.03 KBTZ EF-1 CENTRIFUGAL NORTH OFFICE ROOF ROOF CURB 5C SEE NOTES BELOW 24" 45 M2.02, 3/M7.02 KBTZ EF-2 CENTRIFUGAL LOCKERS ROOF ROOF CURB - SEE NOTES BELOW 50" 180 M2.02, 3/M7.02 KBTZ EF-3 CENTRIFUGAL UPPER ROOF ROOF CURB - SEE NOTES BELOW 36" 120 M2.03, 3/M7.02 KBTZ EF-4 CENTRIFUGAL WELLNESS CENTER ROOF ROOF CURB - SEE NOTES BELOW 22" 30 5/WM2.04, 3/M7.02 KBTZ EF-5 INLINE FAN EQUIPMENT STORAGE SPRING HANGER 5C SEE NOTES BELOW 37''Wx15''Hx17''L 68 5/M/7.05 KBTZ FC-1 CEILING HUNG HYDRONIC FAN COIL NORTH OFFICE SPRING HANGER 5C SEE NOTES BELOW 37"Wx22"Hx37"D 150 M2.01, 4/M7.02 KBTZ FC-2 CEILING HUNG HYDRONIC FAN COIL SOUTH OFFICE SPRING HANGER 5C SEE NOTES BELOW 48"Wx24"Hx402"D 150 M2.01, 4/M7.02 KBTZ FC-3 WALL MOUNTED UNITS TELECOM ROOM WALL MOUNTED - SEE NOTES BELOW 46"Wx15"Hx12"D 46 M2.01, 4/S7.08, 1/M7.03 KBTZ FC-5 CEILING HUNG DX FAN COIL MACH. ROOM 120 SPRING HANGER 5C SEE NOTES BELOW 71 M2.01, 4/M7.02 KBTZ FC-6 WALL MOUNTED UNITS ELECTRICAL WALL MOUNTED - SEE NOTES BELOW 46"Wx15"Hx12"D 46 M2.01, 4/S7.08, 1/M7.03 KBTZ GI-1 GRAVITY INTAKE UNITS NORTH OFFICE ROOF ROOF CURB - SEE NOTES BELOW 15 M2.02, 5/M7.03 KBTZ GI-2 NORTH OFFICE ROOF ROOF CURB - SEE NOTES BELOW 29 M2.02, 5/M7.03 KBTZ HWP-1 BASE MOUNTED PUMP HYDRONICS 157 CONCRETE PAD B-1 OR TYPE 1 SEE NOTES BELOW 220 1/M4.01, 4/M7.04 KBTZ HWP-2 BASE MOUNTED PUMP HYDRONICS 157 CONCRETE PAD B-1 OR TYPE 1 SEE NOTES BELOW 220 1/M4.01, 4/M7.04 KBTZ NOTES: 1. SEE SPECIFICATIONS 23 05 48 FOR FURTHER DESCRIPTIONS OF VIBRATION ISOLATOR TYPES. 2. TYPE "1" - 3/4" NEOPRENE PAD: RUBBER WAFFLE PAD (MASON TYPE: SUPER WMH). 3. TYPE "2" - NEOPRENE MOUNT: DOUBLE DEFLECTION TYPE (MASON TYPE: BR). 4. TYPE "3" - SPRING: FREESTANDING, LATERALLY STABLE, OPEN-SPRING ISOLATORS (MASON TYPE: SLFH). 5. TYPE "4a" - RESTRAINED SPRING ISOLATORS: FREESTANDING, STEEL, OPEN-SPRING ISOLATORS WITH SEISMIC RESTRAINT (MASON TYPE: SLR). 6. TYPE "4b" -HOUSED SPRING MOUNTS: HOUSED SPRING ISOLATOR WITH INTEGRAL SEISMIC SNUBBERS (MASON TYPE: SSLFH). 7. TYPE "5a" - RESTRAINED ELASTOMERIC HANGERS: DOUBLE-DEFLECTION TYPE (MASON TYPE: RWHD). 8. TYPE "5c" - SPRING HANGERS WITH VERTICAL-LIMIT STOP: COMBINATION COIL-SPRING AND ELASTOMERIC-INSERT HANGER WITH SPRING AND INSERT IN COMPRESSION AND WITH A VERTICAL-LIMIT STOP (MASON TYPE: RW30) 9. TYPE "6" - HORIZONTAL THRUST RESTRAINTS: COMBINATION COIL SPRING AND ELASTOMERIC INSERT WITH SPRING AND INSERT IN COMPRESSION AND WITH A LOAD STOP (MASON TYPE: WBI OR WBD). 1 1 1

Transcript of SAN JOSE CITY COLLEGE MSK-001 - SJECCD

Page 1: SAN JOSE CITY COLLEGE MSK-001 - SJECCD

Supplemental #:

Original Drawing:

Date:

Scale:

SAN JOSE CITY COLLEGE

SYMBOL LIST & GENERAL NOTES -MECHANICAL

MSK-0011089-0002

11/10/15

PHYSICAL EDUCATION BUILDING AND RENOVATED LABBUILDING

1 ADDENDUM 1 01-15-2016

M0.01

NO SCALE

DSA STRUCTURAL ANCHORAGE COORDINATION SCHEDULE sketch

SYMBOL DESCRIPTION LOCATIONMOUNTED

ON SUPPORT TYPESUPPORT MODEL

NUMBER

DIMENSIONS

MAXWEIGHT

(LBS)REFERENCEDRAWINGS

ANCHMODEL

NODIA

OVERALLDIMENSIONS

(LxWxH)

AHU-1 AIR HANDLER LOCKER ROOF CONCRETE PAD FANS SPRING ISOLATED SEE NOTES BELOW 66"Wx100"Hx210"L 6000 M2.02, 8/M7.03 KBTZ

AHU-2 AIR HANDLER UPPER ROOF STEEL BEAMS FANS SPRING ISOLATED SEE NOTES BELOW 250"Wx104"Hx390"L 26000 M2.03, 5/S5.21, 3/M7.04 KBTZ

AHU-3 AIR HANDLER UPPER ROOF STEEL BEAMS FANS SPRING ISOLATED SEE NOTES BELOW 198"Wx84"Hx365"L 17400 M2.03, 5/S5.21, 3/M7.04 KBTZ

CHWP-1 BASE MOUNTED PUMP HYRONICS 157 CONCRETE PAD B-1 OR TYPE 1 SEE NOTES BELOW 540 1/M4.01, 5/M7.02 KBTZ

CHWP-2 BASE MOUNTED PUMP HYDRONICS 157 CONCRETE PAD B-1 OR TYPE 1 SEE NOTES BELOW 540 1/M4.01, 5/M7.02 KBTZ

CU-1 CONDENSING UNIT UPPER ROOF SLEEPERS SEE NOTES BELOW 532 M2.03, 2/M7.03 KBTZ

EF-1 CENTRIFUGAL NORTH OFFICE ROOF ROOF CURB 5C SEE NOTES BELOW 24" 45 M2.02, 3/M7.02 KBTZ

EF-2 CENTRIFUGAL LOCKERS ROOF ROOF CURB - SEE NOTES BELOW 50" 180 M2.02, 3/M7.02 KBTZ

EF-3 CENTRIFUGAL UPPER ROOF ROOF CURB - SEE NOTES BELOW 36" 120 M2.03, 3/M7.02 KBTZ

EF-4 CENTRIFUGAL WELLNESS CENTER ROOF ROOF CURB - SEE NOTES BELOW 22" 30 5/WM2.04, 3/M7.02 KBTZ

EF-5 INLINE FAN EQUIPMENT STORAGE SPRING HANGER 5C SEE NOTES BELOW 37''Wx15''Hx17''L 68 5/M/7.05 KBTZ

FC-1 CEILING HUNG HYDRONIC FAN COIL NORTH OFFICE SPRING HANGER 5C SEE NOTES BELOW 37"Wx22"Hx37"D 150 M2.01, 4/M7.02 KBTZ

FC-2 CEILING HUNG HYDRONIC FAN COIL SOUTH OFFICE SPRING HANGER 5C SEE NOTES BELOW 48"Wx24"Hx402"D 150 M2.01, 4/M7.02 KBTZ

FC-3 WALL MOUNTED UNITS TELECOM ROOM WALL MOUNTED - SEE NOTES BELOW 46"Wx15"Hx12"D 46 M2.01, 4/S7.08, 1/M7.03 KBTZ

FC-5 CEILING HUNG DX FAN COIL MACH. ROOM 120 SPRING HANGER 5C SEE NOTES BELOW 71 M2.01, 4/M7.02 KBTZ

FC-6 WALL MOUNTED UNITS ELECTRICAL WALL MOUNTED - SEE NOTES BELOW 46"Wx15"Hx12"D 46 M2.01, 4/S7.08, 1/M7.03 KBTZ

GI-1 GRAVITY INTAKE UNITS NORTH OFFICE ROOF ROOF CURB - SEE NOTES BELOW 15 M2.02, 5/M7.03 KBTZ

GI-2 NORTH OFFICE ROOF ROOF CURB - SEE NOTES BELOW 29 M2.02, 5/M7.03 KBTZ

HWP-1 BASE MOUNTED PUMP HYDRONICS 157 CONCRETE PAD B-1 OR TYPE 1 SEE NOTES BELOW 220 1/M4.01, 4/M7.04 KBTZ

HWP-2 BASE MOUNTED PUMP HYDRONICS 157 CONCRETE PAD B-1 OR TYPE 1 SEE NOTES BELOW 220 1/M4.01, 4/M7.04 KBTZ

NOTES:1. SEE SPECIFICATIONS 23 05 48 FOR FURTHER DESCRIPTIONS OF VIBRATION ISOLATOR TYPES.2. TYPE "1" - 3/4" NEOPRENE PAD: RUBBER WAFFLE PAD (MASON TYPE: SUPER WMH).3. TYPE "2" - NEOPRENE MOUNT: DOUBLE DEFLECTION TYPE (MASON TYPE: BR).4. TYPE "3" - SPRING: FREESTANDING, LATERALLY STABLE, OPEN-SPRING ISOLATORS (MASON TYPE: SLFH).5. TYPE "4a" - RESTRAINED SPRING ISOLATORS: FREESTANDING, STEEL, OPEN-SPRING ISOLATORS WITH SEISMIC RESTRAINT (MASON TYPE: SLR).6. TYPE "4b" -HOUSED SPRING MOUNTS: HOUSED SPRING ISOLATOR WITH INTEGRAL SEISMIC SNUBBERS (MASON TYPE: SSLFH).7. TYPE "5a" - RESTRAINED ELASTOMERIC HANGERS: DOUBLE-DEFLECTION TYPE (MASON TYPE: RWHD).8. TYPE "5c" - SPRING HANGERS WITH VERTICAL-LIMIT STOP: COMBINATION COIL-SPRING AND ELASTOMERIC-INSERT HANGER WITH SPRING AND INSERT IN COMPRESSION AND WITH A VERTICAL-LIMIT STOP (MASON TYPE: RW30)9. TYPE "6" - HORIZONTAL THRUST RESTRAINTS: COMBINATION COIL SPRING AND ELASTOMERIC INSERT WITH SPRING AND INSERT IN COMPRESSION AND WITH A LOAD STOP (MASON TYPE: WBI OR WBD).

1

1

1

Page 2: SAN JOSE CITY COLLEGE MSK-001 - SJECCD

EFORPDERETSI

GE R

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

No. 030802

M

E C H A N IC A

L

HO

RM

OZ L. JANSS

EN

S

E N G I N E E R I N G

I N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Jesse Agosta

2014-0174

RENEWAL

DATE

ARCHIT

ECT

LIC

ENSED

CALI FORN

IA

STA

TE

O F

TROY PENNINGTON

C-31285

5-31-17

IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT

OFFICE OF REGULATION SERVICES

AC FLS SS

DATE

01-114593

FILE NO.43-C1

DSA COMMENTS 09-15-2015

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

SCHEDULES - MECHANICAL

M0.02

9.15.2015

1089-0002

DSA SUBMITTAL

FAN SCHEDULE

SYMBOL AREA SERVED

BASIS OF DESIGN

TYPE DRIVEAIR FLOW

(CFM)ESP

(IN H20) FRPMSOUNDSSONES

ELECTRICAL

CONTROLS REF MAX WT (LBS)COMMENTS

MFR MODEL VOLTS PH HP WATTSCF-1 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14

CF-2 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14

CF-3 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14

CF-4 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14

CF-5 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14

CF-6 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14

CF-7 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14

CF-8 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14

EF-1 NORTH RESTROOMS GREENHECK G-90-VG CENTRIFUGAL DIRECT 400 0.3 1246 5.2 115 1 0.16 2/M6.02 45 1, 2

EF-2 LOCKERS AND LAUNDRY GREENHECK GB-300HP-15 CENTRIFUGAL BELT 5070 1 699 14.6 460 3 1.5 2/M6.02 180 1, 2

EF-3 FITNESS CENTER SHOWERS GREENHECK GB-240HP-20 CENTRIFUGAL BELT 4485 1.5 1023 16 460 3 2 2/M6.02 120 1, 2

EF-4 WELLNESS CENTER RESTROOMS GREENHECK G-085-VG CENTRIFUGAL DIRECT 350 .5 1615 8 115 1 0.16 2/M6.02 30 1, 2

EF-5 FIRST FLOOR STUDENTRESTROOMS

GREENHECK CSP-A1750 INLINE FAN DIRECT 1500 0.4 1130 4 115 1 0 550 2/M6.02 68

PUMP SCHEDULE

SYMBOL SERVING

BASIS OF DESIGN

PUMP TYPEIMPELLER

SIZE RPMEFFICIENCY

%

FLOWRATE(GPM)

HEAD(FT H20)

ELECTRICAL MOTORTYPE ODP or

TEFCVFD(Y/N)

CONTROLSREF

MAX WT(LBS) COMMENTSMFR MODEL VOLTS PH BHP MHP

CHWP-1 AHUs & FAN COILS Bell & Gossett 1510 - 3 BD BASE MOUNTED PUMP 8 1770 75 300 60.00 460 3 6.1 10 ODP Y 2/M6.01 540

CHWP-2 AHUs & FAN COILS Bell & Gossett 1510 - 3 BD BASE MOUNTED PUMP 8 1770 75 300 60.00 460 3 6.1 10 ODP Y 2/M6.01 540

HWP-1 AHUs, VAVs & FAN COILS Bell & Gossett 1510 - 2.5 AC-es BASE MOUNTED PUMP 6.625 1750 76 160 55.00 460 3 2.1 3 ODP Y 1/M6.01 220

HWP-2 AHUs, VAVs & FAN COILS Bell & Gossett 1510 - 2.5 AC-es BASE MOUNTED PUMP 6.625 1750 76 160 55.00 460 3 2.1 3 ODP Y 1/M6.01 220

AIR HANDLING UNIT SCHEDULE (INDIRECT EVAPORATIVE COOLER)

SYMAREA

SERVED

BASIS OF DESIGN SUPPLY FAN RETURN FAN CHILLED WATER COOLING COIL HOT WATER HEATING COIL FILTER ELECTRICAL

SMOKEDETECTOR

(Y/N)

MAXWT

(LBS) COMMENTSMFR MODELTOTALCFM

MINOSACFM

ESP(IN

H2O)# OFFANS BHP HP FRPM

VFD(Y/N)

TOTALCFM

ESP(IN

H2O)# OFFANS BHP HP FRPM

VFD(Y/N)

TOTALCAP

(MBH)

SENSCAP

(MBH)FPI/

ROWS

WATERFLOWGPM

EWT(°F)

LWT(°F)

EDB(°F)

EWB(°F)

LDB(°F)

LWB(°F)

MAXFACEVEL.(FPM)

MAXAPD

(IN H2O)

MAXWPD

(FT H2O)

CHW MINBRANCH

PIPESIZE

MINCAP

(MBH)#

ROWS FPI

WATERFLOW(GPM)

EWT(°F)

LWT(°F)

EDB(°F)

LDB(°F)

MAXFACEVEL.(FPM)

MAXAPD

(IN H2O)

MAXWPD

(FT H2O)

HW MINBRANCH

PIPESIZE

EFFMERV VOLTS PH FLA MCA

MOCP

AHU-1 LOCKERS ENERGYLABS

C-058-066-FCHI-L 6500 6500 2 1 6.26 7.5 2385 Y 0 0 0 0 0 0 N/A 245.0 155.0 8/6 41 44 56 76 66 54 53 400 0.70 10.00 2" 415 2 7 22 180 140 29 88 400 0.25 10.00 2" 13 460 3 13.7 16.5 25 Y 6000 1

AHU-2 GYMNASIUM ENERGYLABS

C-090-128-FCHI-L 24000 7200 2 4 5.65 7.5 2002 Y 24000 1.5 3 4.08 5 1904 Y 950.0 595.0 9/6 158 44 56 76 66 53 53 400 0.70 10.00 4" 725 2 7 36 180 140 55 83 400 0.25 10.00 2" 13 460 3 71.0 81.0 110 Y 26000 2

AHU-3 FITNESSCENTER

ENERGYLABS

C-084-080-FCHI-L 0 8530 2 2 8.44 10 1913 Y 8250 1.5 2 3.1 5 1052 Y 418.0 327.0 8/4 60 44 56 76 66 54 53 400 0.70 10.00 2 1/2" 562 1 10 28 180 140 55 86 400 0.25 10.00 2" 13 460 3 55.6 62.4 80 Y 17400 3,4

TERMINAL UNIT SCHEDULE

SYMBOL AREA SERVED

BASIS OFDESIGN

INLETSIZE

COOLINGAIR FLOW

INLETSP (INH2O)

DNSTREAM SP

(IN H2O)

MININLET SP(IN H2O)

HOT WATER HEATING COILSOUNDDATA ELECTRICAL

CONTROLSREF

VALVETYPE

(2-WAYOR

3-WAY) COMMENTSMFR MODELMAXCFM

MINCFM

MAXHTGCFM

MINCAPMBH GPM

EAT(°F)

LAT(°F)

EWT(°F)

LWT(°F)

#ROWS FPI

WPD(FT H2O)

MINBRANCHPIPE SIZE

RADNC

DISCHNC VOLTS PH

VAV-1 TICKETS/CONCESSION TITUS DESV 8" 490 155 1.00 0.25 0.11 245 9.3 0.8 55 90 180 155 1 10 0.39 3/4" 19 18 24 1 3/M6.01 2 1-11

VAV-2 TELECOM TITUS DESV 10" 800 800 1.00 0.25 0.01 0 0.0 0.0 0 0 0 0 0 0 0.00 0" 24 19 24 1 3/M6.01 2 1-11

VAV-3 OFFICE/EQUIPMENT STORAGE TITUS DESV 8" 480 195 1.00 0.25 0.11 230 8.8 0.7 55 90 180 153 1 10 0.29 3/4" 19 18 24 1 3/M6.01 2 1-11

VAV-4 TRAINING ROOM TITUS DESV 8" 450 180 1.00 0.25 0.10 225 8.6 0.6 55 90 180 152 1 10 0.26 3/4" 19 18 24 1 3/M6.01 2 1-11

VAV-5 TRAINING ROOM TITUS DESV 8" 550 470 1.00 0.25 0.01 0 0.0 0.0 0 0 0 0 0 0 0.00 0" 22 21 24 1 3/M6.01 2 1-11

VAV-6 MULTIPURPOSE CLASSROOM TITUS DESV 10" 600 125 1.00 0.25 0.09 300 11.4 0.8 55 90 180 153 1 10 0.08 3/4" 22 18 24 1 3/M6.01 2 1-11

VAV-7 MULTIPURPOSE CLASSROOM TITUS DESV 10" 900 365 1.00 0.25 0.17 365 13.9 1.4 55 90 180 160 1 10 0.21 3/4" 23 19 24 1 3/M6.01 2 1-11

VAV-8 FOOTBALL LOCKER ROOM TITUS DESV 40 2000 2000 1.00 0.25 0.15 2000 76.0 2.3 55 90 180 111 2 10 0.33 3/4" 27 21 24 1 3/M6.01 2 1-11

VAV-9 MENS TEAM TOILETS/SHOWER/TEAN DRESSSING

ROOM

TITUS DESV 12" 1295 1295 1.00 0.25 0.37 1295 49.2 2.5 55 90 180 139 2 10 0.84 3/4" 20 20 24 1 3/M6.01 2 1-11

VAV-10 WOMENS TEAM SHOWER/TOILETS/ TEAM DRESSING

ROOM

TITUS DESV 40 2325 2325 1.00 0.25 0.18 2325 88.3 2.9 55 90 180 118 2 10 0.54 3/4" 29 22 24 1 3/M6.01 2 1-11

VAV-11 FITNESS CENTER TITUS DESV 12" 900 450 1.00 0.25 0.10 450 17.1 1.2 55 90 180 152 1 10 0.12 3/4" 19 18 24 1 3/M6.01 2 1-11

VAV-12 FITNESS CENTER TITUS DESV 14" 1400 355 1.00 0.25 0.12 700 26.6 2.1 55 90 180 155 1 10 0.50 3/4" 20 15 24 1 3/M6.01 2 1-11

VAV-13 FITNESS CENTER TITUS DESV 12" 960 255 1.00 0.25 0.11 480 18.2 1.5 55 90 180 154 1 10 0.29 3/4" 20 18 24 1 3/M6.01 2 1-11

VAV-14 FITNESS CENTER TITUS DESV 14" 1305 695 1.00 0.25 0.10 695 26.4 2.1 55 90 180 154 1 10 0.48 3/4" 20 15 24 1 3/M6.01 2 1-11

VAV-15 FITNESS CENTER TITUS DESV 14" 1350 675 1.00 0.25 0.11 675 25.6 1.9 55 90 180 153 1 10 0.41 3/4" 20 15 24 1 3/M6.01 2 1-11

VAV-16 FITNESS CENTER TITUS DESV 12" 1080 360 1.00 0.25 0.13 540 20.5 2.0 55 90 180 160 1 10 0.57 3/4" 22 20 24 1 3/M6.01 2 1-11

VAV-17 FITNESS CENTER TITUS DESV 16" 1690 855 1.00 0.25 0.11 855 32.5 2.5 55 90 180 153 1 10 0.71 3/4" 16 14 24 1 3/M6.01 2 1-11

VAV-18 EXERCISE LAB TITUS DESV 12" 900 420 1.00 0.25 0.10 420 16.0 1.0 55 90 180 149 1 10 0.16 3/4" 19 18 24 1 3/M6.01 2 1-11

VAV-19 EXERCISE LAB TITUS DESV 12" 1080 215 1.00 0.25 0.13 540 20.5 2.0 55 90 180 160 1 10 0.57 3/4" 22 20 24 1 3/M6.01 2 1-11

VAV-20 EXERCISE LAB TITUS DESV 16" 1600 465 1.00 0.25 0.10 800 30.4 2.1 55 90 180 150 1 10 0.51 3/4" 15 13 24 1 3/M6.01 2 1-11

VAV-21 PUBLIC WOMENS RESTROOM TITUS DESV 8" 500 275 1.00 0.25 0.12 275 10.5 1.1 55 90 180 161 1 10 0.77 40" 19 18 24 1 3/M6.01 2 1-11

NOTES:1) ALL BOXES SHALL BE PROVIDED WITH HIGH CFM CONTROL.2) ALL BOXES SHALL BE PRESSURE INDEPENDANT AND COMPLETE WITH CENTER AVERAGING AIRFLOW SENSOR.3) SEISMIC BRACE UNIT PER SMACMA GUIDELINES.4) COIL CONNECTION AND CONTROL BOX SHALL BE ON OPPOSITE SIDE.5) CONTROL VALVES TO BE FIELD INSTALLED AS REQUIRED. (2-WAY & 3-WAY)6) ALL TERMINAL BOXES SHALL HAVE MINIMUM 1 INCH INSULATION CONFORMING TO UL181 AND NFPA90A.

7) ALL PERFORMANCE SHALL BE ARI CERTIFIED.8) ROOM NC LEVEL SHOWN INCLUDES ATTENUATION TRANSFER FUNCTIONS OBTAINED FROM TABLES IN ARI STANDARD 885.9) SOUND DATA SHALL BE OBTAINED FROM TESTS CONDUCTED IN ACCORDANCE WITH ARI STANDARD 880-98.10) 120V POWER TO CONTROL TRANSFORMER BY DIVISION 26. 24V DDC CONTROL WIRING BY "RELIABLE" CONTROL CONTRACTOR.11) SEE 1/M6.02 FOR MOUNTING DETAIL AND 4/M5.01 FOR TERMINAL BOX PIPING DIAGRAM.

NOTES:1) PROVIDE BACKDRAFT DAMPER.2) PROVIDE ROOFCURB.

CHILLED AND HEATING WATER FAN COIL SCHEDULE

SYMBOL SERVING

BASIS OF DESIGN

AIR FLOW(CFM) MIN OSA

FAN ESP(IN H2O)

COOLING CHW MIN.BRANCHPIPE SIZE

HEATING HW MINBRANCHPIPE SIZE

ELECTRICAL

FILTEREFF MERV

CONTROLSREF

MAX WT(LBS) COMMENTSMFR MODEL

TOTALCAP (MBH)

SENS CAP(MBH) GPM EWT (°F) LWT (°F) EDB (°F) EWB (°F) LDB (°F) LWB (°F) WPD

MIN CAP(MBH) GPM EWT (°F) LWT (°F) EAT (°F) LAT (°F) WPD VOLTS PH FLA

FC-1 NORTHOFFICES

IEC HBD20 950 400 1.5 69.0 46.0 11.6 44 56 76 66 55 54 6.50 1 1/2" 146.0 7.3 180 140 29 96 3.00 1" 480 3 2.8 13 5/M6.02 150 1

FC-2 SOUTHOFFICES

IEC HBD06 300 75 0.95 18.4 12.0 3.1 44 56 76 66 55 54 1.20 3/4" 42.0 2.1 180 140 29 106 1.20 3/4" 480 3 1.1 13 5/M6.02 150 1

CONDENSING UNIT SCHEDULE

SYMBOL

BASIS OF DESIGN

RELATED FANNOMTONS

COOLING MINEFF

(EER)

ELECTRICAL

CONTROLSREF

MAX WT(LBS) COMMENTSMFR MODEL CAP (MBH)

AMBTEMP (F) VOLTS PH MCA MOCP

CU-1 MITSUBISHI PUHY-P96YLMU-A FC-3, FC-5, FC-6 8 96.0 94 15.5 460 3 14.0 20 4/M6.02 532 1

SPLIT SYSTEM FAN COIL SCHEDULE

SYMBOLAREA

SERVED

BASIS OF DESIGN AIRFLOW(CFM)

COOLING ELECTRICAL

MAX WT.(LBS) COMMENTSMANUFACTURER MODEL

TOTAL(MBH)

SENS.(MBH)

ENT. AIR

VOLTAGE PH MOCP(°F DB)FC-3 TELECOM ROOM MITSUBISHI ELECTRIC PKFY-P30NKMU-E 710 30 28 78 208 1 15 46 1

FC-5 MACH. ROOM 120 MITSUBISHI ELECTRIC PEFY-P24NMAU-E 800 24 24 78 208 1 15 71 1

FC-6 ELECTRICAL MITSUBISHI ELECTRIC PKFY-P30NKMU-E 710 30 28 78 208 1 15 46 1

GRAVITY RELIEF AND GRAVITY INTAKE SCHEDULE

SYMBOLSERVING

BASIS OF DESIGNAIR FLOW

(CFM)ESP

(IN H20)

THROATVELOCITY(FT/MIN)

MAX WT(LBS) COMMENTS

MFRMODEL

GI-1 OFFICE NORTH GREENHECK GRSI 475 0.05 350 15 1, 2

GI-2 OFFICE NORTH GREENHECK GRSI 1200 0.05 370 29 1, 2, 3

SOUND ATTENUATOR SCHEDULE

SYMBOL SERVING

BASIS OF DESIGN

CFM LENGTH

SILENCERPRESSURE DROP

(IN WG) VELOCITY

MIN DYNAMIC INSERTION LOSS (DB)OCTAVE BAND MID-FREQUENCY HZ

COMMENTSMFR MODEL 63 125 250 500 1K 2K 4K 8KS-1 AHU-2 SUPPLY VAW SYSTEMS RSA-30V70 24000 7' - 0" 0.20 1694 FPM 5 11 19 23 25 18 17 13 1

S-2 AHU-2 RETURN VAW SYSTEMS RSA-30V70 24000 7' - 0" 0.18 -1694 FPM 6 13 19 23 22 18 16 12 1

S-3 AHU-3 SUPPLY VAW SYSTEMS RSA-38V60 17035 7' - 0" 0.14 1480 FPM 7 13 22 24 24 16 15 11 1

S-4 AHU-3 RETURN VAW SYSTEMS RSA-38V60 12100 7' - 0" 0.12 -1480 FPM 6 10 18 32 37 27 22 13 1

NOTES:1) PROVIDE GOBI CONDENSATE PUMP KIT, ELECTRICAL SERVICE - 120 V, 16 W

DIFFUSER, REGISTER AND GRILLE SCHEDULE

SYMBOL TYPE FACE FRAME DAMPER FINISH

BASIS OF DESIGN

COMMENTSMFR. MODELCD-1 CEILING DIFFUSER PERFORATED LAY-IN NONE WHITE TITUS MCD 1-5

CD-2 CEILING SUPPLY DIFFUSER LAY-IN NONE WHITE ACUTHERM TF-HC 1-5

CEG-1 CEILING EXHAUST GRILLE EGGCRATE LAY-IN NONE WHITE TITUS 50F 1-5

CRG-1 CEILING RETURN GRILLE EGGCRATE LAY-IN NONE WHITE TITUS 50F 1-5

CTG-1 CEILING TRANSFER GRILLE EGGCRATE LAY-IN NONE WHITE TITUS 50F 1-5

EG-1 SIDEWALL EXHAUST GRILLE DOUBLE DEFL. 1/4" BORDER NONE WHITE TITUS 350RL 1-5

LS-1 LINEAR SLOT DIFFUSER 2" SLOT SURFACE NONE ALUMINUM TITUS ML-37 1-5

RG-1 SIDEWALL RETURN GRILLE DOUBLE DEFL. 1/4" BORDER NONE WHITE TITUS 350RL 1-5

SD-1 SIDEWALL SUPPLY GRILLE DOUBLE DEFL. 1/4" BORDER NONE WHITE TITUS 300RL 1-5

TG-1 SIDEWALL TRANSFER GRILLE DOUBLE DEFL. 1/4" BORDER NONE WHITE TITUS 350RL 1-5

NOTES:1) CONSTUCTION - CASING: 22GA. GALV., PERF: 22GA. GALV., MEDIA: FIBERGLASS.

NOTES:1) ALL POWER WIRING TO BE INSTALLED UNDER THE ELECTRICAL WORK.

NOTES:1) PROVIDE WITH GOBI CONDENSATE PUMP. ELECTRICAL SERVICE - 120 V, 16 W.

NOTES:1) COORDINATE EXACT LOCATION WITH LIGHTS, SPRINKLER HEADS AND ARCHITECTURAL RCP.2) USE BORDER TYPE 2 FOR SURFACE MOUNT IN HARD CEILINGS.3) COORDINATE WITH WALL ELEVATIONS.4) SEE FLOOR PLANS FOR NECK SIZES.5) SEE FLOOR PLANS FOR FACE SIZES.

NOTES:1) PROVIDE WITH ROOF CURB.2) PROVIDE WITH BIRD SCREEN.3) PROVIDE WITH BAROMETRIC RELIEF DAMPER.

1

1

1

1

1

1

1

1

1

1

1

1 ADDENDUM 1 11-06-2015

NOTES:1) IDEC SECTION TO BE MODEL NO. 1-60-48, EAT(DB)=88 F, EAT(WB)=68 F, LAT(DB)=75.1 F, LAT(WB)=64.1 F, MEDIA EFF=64.1%, SENS. CAP=88.46MBH, CYC. OF CONCENTRATION=4, WATER REQ'D FOR SENS. COOLING=84 LBS/HR, BLEED RATE=28 LBS/HR, MAKEUP WATER=0.22 GPM, PUMP= BURKS GA5N-1-1/4, 3/4 HP.2) IDEC SECTIONS 1&2 TO BE MODEL NO. 1-120-48, EAT(DB)=88 F, EAT(WB)=68 F, LAT(DB)=74.8 F, LAT(WB)=64.0 F, MEDIA EFF=66%, SENS. CAP=167.06MBH, WATER REQ'D FOR SENS. COOLING=158.5 LBS/HR, BLEED RATE=39.64 LBS/HR, MAKEUP WATER=0.4 GPM.3) IDEC SECTION 1 TO BE MODEL NO. 1-95-48, EAT(DB)=88 F, EAT(WB)=68 F, LAT(DB)=75.1 F, LAT(WB)=64.2 F, MEDIA EFF=64%, SENS. CAP=135.12MBH, WATER REQ'D FOR SENS. COOLING=128.2 LBS/HR, BLEED RATE=32.06 LBS/HR, MAKEUP WATER=0.32 GPM.4)IDEC SECTION 2 TO BE MODEL NO. 1-60-48, EAT(DB)=88 F, EAT(WB)=68 F, LAT(DB)=75.1 F, LAT(WB)=64.1 F, MEDIA EFF=65%, SENS. CAP=88.46MBH, CYC. OF CONCENTRATION=4, WATER REQ'D FOR SENS. COOLING=84.0 LBS/HR, BLEED RATE=28.0 LBS/HR, MAKEUP WATER=0.22 GPM, PUMP= BURKS GA5N-1-1/4, 3/4 HP.

1

Page 3: SAN JOSE CITY COLLEGE MSK-001 - SJECCD

CO2CO2

CO2

CO2P

ELEV.

E1.1

HALL

167

PUBLIC WOMEN'SRESTROOM

122

SPECTATOR GYMNASIUM

160

PUBLIC MEN'S RESTROOM

126

MEN'S TEAM SHOWER

147

FOOTBALL LOCKER ROOM

146

TEAM DRESSING ROOM

148

VEST.

149

TEAM DRESSING ROOM

155

HYDRONICS

157

WOMEN'S STUDENTLOCKERS

129

MULTIPURPOSE CLASSROOM

141

SOUTH CORRIDOR

150

TRAINING ROOM

138

EQUIPMENT STORAGE

133

TICKETS/ CONCESSIONS

124

TELECOM

125

LOBBY

101

DEAN'S OFFICE

104

OFFICE

111

OFFICE

112OFFICE

113

OFFICE

110

OFFICE

109

M4.01

1

E F GA.5 F.2 JH

5

6

7

8

9

B C D

ELEC.

136

TRAINING STAFF ROOM

139

JAN.

140

10x10

(490 CFM )(0.8 GPM )

VAV-1

(800 CFM )(0 GPM )

VAV-2

(450 CFM )(0.6 GPM )

VAV-4

(600 CFM )(0.8 GPM )

VAV-6

(900 CFM )(1.4 GPM )

VAV-7

(550 CFM )(0 GPM )

VAV-5

(480 CFM )(0.7 GPM )

VAV-3

20x14 (

2270)

20x12 (

1790)

26x20 (4770)

26x20

24x20

(1295 CFM )(2.5 GPM )

VAV-9

(2000 CFM )(2.3 GPM )

VAV-8

(2325 CFM )(2.9 GPM )

VAV-10

28x22 18x16

12x12

WOMEN'S TEAM TOILETS

153

MEN'S TEAM TOILETS

145

MEN'S STUDENT RESTROOM

131

WOMEN'S STUDENTRESTROOM

130

MACH. ROOM

120

STAFF LOCKER

108

WOMENS

107

MENS

106

STAFF LOCKER

105

OPEN OFFICE

102

SEE M2.02 FOR SCOPEOF MECHANICAL WORKIN THE GYMNAISUM

28x22 (

5520)

28x22

1

ELEC.

151

28x22

T

T

T

(TYP)

UP TOMECHSHAFT

14x1414x10

20x24

20x24

1

1

1

14x12

10x10

T T

T

T

TT

T

T

T

26x12

16x12

FC-1

FC-2

(VAV-10)

(VA

V-9

)

(VAV-8)

(VAV-7)(VAV-6)

(VAV-4)

(VAV-5)

(VAV-3)

T

T

(VAV-2)

(VAV-1)

(FC-1)

(FC-2)

(FC-3)

T

(VAV-14)

(AHU-2)

24x22

FC-3

OFFICE

135

A

1

2

3

4

3

4" CHWR

4" CHWS

4" CHWR

4" CHWS

5

M7.02

1

M7.03

OFFICE

103

VEST.

144

12x12

T (FC-6)

20x18 (

2050)

115

EG-16x6

LAUNDRY

159

340

340

340

340

340

280

250250

490

490 565

565

570

500290

290

290

290

285

290

285

280

280

490

490

16"

280

400

EG-112x12

20x18

GYM EQUIPMENT

134

4

M7.02

150

150

150

150

150

10''Ø

12''Ø

80

160

10''Ø

155

155

150

150

150 150 150 150

10''Ø

12''Ø

10''Ø

14''Ø

175 175150

150 150

150

60

CD-2TYP 5

6"ø

60 60 60

60

340

33512x12

400

400

310320

320

310320

320

230

230

230

230

EAST CORRIDOR

137

3

M4.01

20x12 (

1500)

290

TEAM DRESSING ROOM

154

WOMEN'S TEAM SHOWER

156

VEST.

152

4

2

150

200

200

250

250

(500 CFM )(1.1 GPM )

VAV-21

T(VAV-21)

8x8

8x8

3/4''HWS/R

150

3/4''HWS/R

3" HWS

3" HWR

3'' HWS

3'' HWR

1 1/4" HWR1 1/4" HWS

1 1/4" CHWR1 1/4" CHWS

1" HWS1" HWR

20x18 (2500)

1

5

T

4

M7.02

FC-61

M7.03

1

M7.05SEE DETAIL

FC-5

FSD

FSD

800

RG-120x8

800

SD-120x8

20x8 SA TOP

20x8 RA BOTTOM

4

M7.02

1

M7.05SEE

300

SD-112x8

RL/RS TOASSOCIATEDROOMS

7

1

20x12

20x12

800

SD-122x10

---TG-124x24

4

M7.058

9

101

1

1

EF-5

UD

UD

---TG-118x18

11

1

1

70

SD-16x6

6''Ø

190

SD-18x8

220

SD-18x8

---CTG-1TYP 2

12"ø

---CRG-1TYP 5

8"ø

---CTG-1TYP 2

12"ø

---CRG-112"ø

10x16

8x16

---CRG-112"ø

6

12"ø

245

SD-1

TYP 2

12x6

---TG-118x18

---CRG-112"ø

1

1

1

1

---TG-112x6

1

400

SD-112x10

12''Ø24x24

1

12

12x6

5

M7.05

6

M7.05

6

M7.05

EFORPDERETSI

GE R

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

No. 030802

M

E C H A N IC A

L

HO

RM

OZ L. JANSS

EN

S

E N G I N E E R I N G

I N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Jesse Agosta

2014-0174

RENEWAL

DATE

ARCHIT

ECT

LIC

ENSED

CALI FORN

IA

STA

TE

O F

TROY PENNINGTON

C-31285

5-31-17

IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT

OFFICE OF REGULATION SERVICES

AC FLS SS

DATE

01-114593

FILE NO.43-C1

DSA COMMENTS 09-15-2015

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

1ST FLOOR PLAN -PHYSICAL EDUCATIONBUILDING - MECHANICAL

M2.01

9.15.2015

1089-0002

DSA SUBMITTAL

0' 4' 8' 16'

1/8" = 1'-0"

1 1ST FLOOR PLAN - PHYSICAL EDUCATION BUILDING - MECHANICAL

SHEET KEYNOTES1 ALUMINUM OR STAINLESS STEEL DUCT SLOPED AT

1% BACK TO THE LAST DIFFUSER.

2 12x12 UP TO GRAVITY INTAKE ON ROOF.

1. SEE DIFFUSER, REGISTER AND GRILLE SCHEDULE

NOTE:

EXHAUST GRILLES

RETURN GRILLES

CD-1

SUPPLY DIFFUSER

DIFFUSER/GRILLES

TAG CFM RANGE

311-400

201-310

0-200

CD-1

CD-1

NECK SIZE

8"Ø

10"Ø

12"Ø

CRG-1

TAG CFM RANGE

375-600

211-370

0-210

CRG-1

CRG-1

NECK SIZE

8"Ø

10"Ø

12"Ø

CEG-1

TAG CFM RANGE

375-600

211-370

0-210

CEG-1

CEG-1

NECK SIZE

8"Ø

10"Ø

12"Ø

2. ALL DIFFUSERS , REGISTERS AND GRILLES TO BE TYPE CD-1, CRG-1 AND CEG-1 UNLESS NOTED OTHERWISE.

3. ALL BRANCH DUCTWORK TO DIFFUSERS, REGISTERS AND GRILLES TO BE SAME SIZE AS NECK SIZE, UNLESS NOTED OTHERWISE.

3 HWS/R & CHWS&R UP TO AHU.

4 PRESSURE SENSOR, SEE CONTROL DIAGRAMS.

GENERAL SHEET NOTES1 ALL PIPE TO BE COLOR COORDINATED PER

DISTRICT STANDARDS. SEE ARCHITECTURALDRAWINGS FOR COLOR REQUIREMENTS.

5 MOTORIZED DAMPER, TYPICAL.

6 DUCTWORK 5 FT AFTER LAST BRANCH AS NOTEDTO BE FLAT AND GALVANIZED.

7 REFRIGERANT LINE SIZING PER MANUFACTURER'SRECOMMENDATION.

1

8 ACOUSTICALLY SEALED PENETRATIONS. TYPICALFOR ALL SOUND-RATED WALLS. SEEARCHITECTURAL DRAWINGS.

9 PROVIDE DOOR LOUVER WITH 0.7 SF NFA.

10 TEMPERATURE SENSOR FOR FCU-5.

11 PROVIDE 4 SF FOR TRANSFER AIR PATH ABOVECEILING.

12 PROVIDE HIGH FREE AREA METAL SCREEN ONOPENING.

1 ADDENDUM 1 11-06-2015

Page 4: SAN JOSE CITY COLLEGE MSK-001 - SJECCD

CORRIDOR

201

E F GA.5 F.2 JH

5

6

7

8

9

AHU-1

B C D

1

EF-1

EF-2

(1400 CFM )(2.1 GPM )

VAV-12

(960 CFM )(1.5 GPM )

VAV-13

(1350 CFM )(1.9 GPM )

VAV-15

(1690 CFM )(2.5 GPM )

VAV-17

(1080 CFM )(2 GPM )

VAV-16

(1080 CFM )(2 GPM )

VAV-19

(900 CFM )(1 GPM )

VAV-18

(1600 CFM )(2.1 GPM )

VAV-20

38x32(12265)

34x26 (

4565)

34x26 (

8685)

26x18 (

3580)

32"ø (8000)

32"ø (8000)

24x22

2

M4.01

2

TERRACE

T1

JANITOR

203

ELEV.

E1.1

16"ø

42"ø (16000)

8"ø

T

T

T

T

T

T

T (VAV-12)

(VAV-15)

(VAV-16)

(VAV-17)

(VAV-18)

(VAV-20)

(VAV-19)

T

(VAV-13)

GI-1

(TYP.)

(4410)

A

1

2

3

4

50x30

2

2

1 1/4" HWR 1 1/4" HWS

1 1/2" CHWS

1 1/2" CHWR

(1305 CFM )(2.1 GPM )

VAV-14

18"ø12"ø

12"ø

16"ø

14"ø

14"ø

14"ø

12"ø 14"ø

12"ø

14"ø

18"ø

14"ø

3

M7.02

5

M7.03

3

M7.03

3

M7.02

1 1/2" HWS

1 1/2" HWR

32x30

CF-1 CF-2

CF-3

CF-4

CF-5CF-6

CF-7CF-8

24X22 UP

26x22 (4465)

30x24 (

6390)

895

RG-1

TYP 3

18x12

890

RG-1

TYP 2

18x12

34x36

(12000)

34x36

(12000)

28x22 DN

6000

RG-1

TYP-4

36x32

EXERCISE LAB

205

SPECTATOR GYMNASIUM

160

FITNESS CENTER

202

32"ø (8000)

3

M4.01

3

3

270

SD-1

TYP 4

12x6

240

SD-1

TYP 4

12x6

400

SD-1

TYP 4

12x6

270

SD-1

TYP 2

8x8

12"ø

225

SD-1

TYP 2

12x6 285

SD-1

TYP 2

8x8

280

SD-1

TYP 4

12x6

795

RG-1

TYP 2

18x12

800

RG-1

TYP 6

18x12

225

SD-1

TYP 4

8x8

225

SD-1

TYP 6

8x8

280

SD-1

TYP 5

12x6

26x18

60x34(24000)

270

SD-1

TYP 2

8x8

75

EG-16x6

(900 CFM )(1.2 GPM )

VAV-11

T (VAV-11)

12"ø

12"ø

3/4" HWS

3/4" HWR

385

LS-1

TYP 3

4x48

1-1/4" HWS

1-1/4" HWR

9

M7.01

4

M7.03

8

M7.03

OS

A

EXH

2" HWS&R,4" CHWS&RUP

2 1/2" HWR

2 1/2" HWS

3" HWR

3" HWS

3" CHWS&R,2" HWS&R UP

5" CHWS&R,3" HWS&R DN

4" CHWS

4" CHWR

1-1/2" CHWS&R,1-1/4" HWS&R DN

60x34 UPTO AHU-2

60x34 UPTO AHU-2

42x36 UP

RL/RS TOASSOCIATEDROOMS

4

GI-25

M7.03

UD

1

1

1

150

SD-18x8

8x8

1

---RG-1

TYP 2

24x24

EFORPDERETSI

GE R

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

No. 030802

M

E C H A N IC A

L

HO

RM

OZ L. JANSS

EN

S

E N G I N E E R I N G

I N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Jesse Agosta

2014-0174

RENEWAL

DATE

ARCHIT

ECT

LIC

ENSED

CALI FORN

IA

STA

TE

O F

TROY PENNINGTON

C-31285

5-31-17

IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT

OFFICE OF REGULATION SERVICES

AC FLS SS

DATE

01-114593

FILE NO.43-C1

DSA COMMENTS 09-15-2015

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

2ND FLOOR PLAN -PHYSICAL EDUCATIONBUILDING - MECHANICAL

M2.02

9.15.2015

1089-0002

DSA SUBMITTAL

0' 4' 8' 16'

1/8" = 1'-0"

1 2ND FLOOR PLAN - PHYSICAL EDUCATION BUILDING - MECHANICAL

1 10'' VENT THROUGH ROOF FROM DRYERS BELOW.INSTALL PER MANUFACTURER'SRECOMMENDATIONS. PROVIDE NECESSARYOFFSETS AS REQUIRED TO COORDINATE ROUTINGWITH OTHER DISCIPLINES.

2 DUCT WITHIN THE GYM IS TO BE DUCT-SOX OREQUIVALENT.

3 OPEN RETURN DUCT INTO SHAFT AND TERMINATEMECHANICAL SHAFT AS RETURN PLENUM

SHEET KEYNOTES

GENERAL SHEET NOTES1 ALL PIPE TO BE COLOR COORDINATED PER

DISTRICT STANDARDS. SEE ARCHITECTURALDRAWINGS FOR COLOR REQUIREMENTS.

4 REFRIGERANT LINE SIZING PER MANUFACTURER'SRECOMMENDATION.

1

1

1 ADDENDUM 1 11-06-2015

Page 5: SAN JOSE CITY COLLEGE MSK-001 - SJECCD

F GF.2 H

5

6

AHU-3

42x36

38x32

1 S-3

S-4

2

2

RL/RS TOASSOCIATEDROOMS

2

M7.03

6

M7.03

3

OSA

EA

CU-1

4

M7.034 3

M7.04

Supplemental #:

Original Drawing:

Date:

Scale:

SAN JOSE CITY COLLEGE

ROOF PLAN - MECHANICAL

MSK-0021089-0002

11/10/15

PHYSICAL EDUCATION BUILDING AND RENOVATED LABBUILDING

1 ADDENDUM 1 01-15-2016

M2.03

1/8" = 1'-0"

Page 6: SAN JOSE CITY COLLEGE MSK-001 - SJECCD

A.5

9

HYDRONICS

157

1

3'' HWS/R

4'' CHWS/R

(TYP. 2)

3'' HWS/R

4'' CHWS/R

A

VFD VFD VFD VFD

(TYP. 2) CHWP-2CHWP-1HWP-2

HWP-1

4

M5.011

M7.04

2

M7.04

1

M5.01

1

M5.01

TCP TCP BMS

1ST FLOOR0' - 0"

2ND FLOOR15' - 0"

FITNESS T.O.DECK31' - 6"

GYM T.O. DECK36' - 2 1/2"

5 6 76.24.12.9 5.33 4

42"ø 32"ø

30x50

36x32 RETURNAIR DUCT (TYP 4)

27' -

2"

31' -

4"

AIR PEAR FAN (TYP)

32"ø32"ø

FIRE PROTECTION PIPINGFIRE PROTECTION PIPE

60x34 SA

32"ø

1ST FLOOR0' - 0"

2ND FLOOR15' - 0"

2.92 3

GI-1

FC-2

8x8 8x8

MOTORIZEDDAMPER (TYP 2)

CHWS/R ANDHWS/R PIPE TOFC-1 AND FC-2

12x12

DOMESTIC CWAND DOMESTICHWS/R PIPE.

10x16 8x16

FIREPROTECTIONPIPE

FIRE PROTECTIONPIPE

STORM DRAIN/OVERFLOWPIPE

OPEN OFFICE

102

OFFICE

113

EFORPDERETSI

GE R

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

No. 030802

M

E C H A N IC A

L

HO

RM

OZ L. JANSS

EN

S

E N G I N E E R I N G

I N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Jesse Agosta

2014-0174

RENEWAL

DATE

ARCHIT

ECT

LIC

ENSED

CALI FORN

IA

STA

TE

O F

TROY PENNINGTON

C-31285

5-31-17

IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT

OFFICE OF REGULATION SERVICES

AC FLS SS

DATE

01-114593

FILE NO.43-C1

DSA COMMENTS 09-15-2015

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

ENLARGED PLANS ANDSECTIONS - MECHANICAL

M4.01

9.15.2015

1089-0002

DSA SUBMITTAL

0' 1' 2' 4'

1/2" = 1'-0"

1 ENLARGED VIEW - MECHANICAL

1 10'' VENT THROUGH ROOF FROM DRYERS BELOW.INSTALL PER MANUFACTURER'SRECOMMENDATIONS. PROVIDE NECESSARYOFFSETS AS REQUIRED TO COORDINATE ROUTINGWITH OTHER DISCIPLINES.

0' 4' 8' 16'

1/8" = 1'-0"

2 SECTION VIEW - GYM DUCT - MECHANICAL

SHEET KEYNOTES

GENERAL SHEET NOTES1 ALL PIPE TO BE COLOR COORDINATED PER

DISTRICT STANDARDS. SEE ARCHITECTURALDRAWINGS FOR COLOR REQUIREMENTS.

0' 2' 4' 8'

1/4" = 1'-0"

3 SECTION VIEW - OFFICE FAN COIL UNITS - MECHANICAL

1

1

1

1 ADDENDUM 1 11-06-2015

Page 7: SAN JOSE CITY COLLEGE MSK-001 - SJECCD

CT

SEQUENCE OF OPERATION:

THE FAN COILS SHALL BE START/STOPPED THROUGH THE BAS SCHEDULE. A CURRENT RELAY WILL PROVIDE AN ALARM IF THERE IS NOPROOF OF STATUS WITHIN 20 SECONDS OF ENERGIZING THE FAN COIL.

THE ZONE TEMPERATURE SHALL BE MAINTAINED AT AN ADJUSTABLE SETPOINT THROUGH THE MODULATION OF THE CHILLED WATER ORHOT WATER VALVE AND MODULATION OF THE ECM MOTOR.

MODULATING DAMPER TO OPEN AND CLOSE BASED ON BUILDING SCHEDULE. CALIBRATE DAMPER OPEN POSITION WITH MINIMUMOUTSIDE AIR REQUIREMENTS.

SETPOINT ADJ

ROOM TEMP

T

M

M

AI

AO

DI

DO

AI

AO

AI

AO

H

C

MODULATE

POSITION

HWSHWR

FAN COIL UNIT (TYP)

STATUS

M/S

START/STOP

C

C

MODULATE

POSITION

CHWSCHWR

CLG. COILHTG. COIL

TEMPERATURE SENSOR

(INITIAL 74ºF COOLING; 70ºF HEATING FOR FC-1 & FC-2)

RA

OSA

MD

AFMS

Supplemental #:

Original Drawing:

Date:

Scale:

SAN JOSE CITY COLLEGE

DETAILS - MECHANICAL

MSK-0031089-0002

11/10/15

PHYSICAL EDUCATION BUILDING AND RENOVATED LABBUILDING

0' 4' 8' 16'

NO SCALE

1 HEATING/CHILLED WATER FAN COIL CONTROL DIAGRAM

1

1 ADDENDUM 1 01-15-2016

M6.02

No Scale

Page 8: SAN JOSE CITY COLLEGE MSK-001 - SJECCD

FULL UNITCONNECTIONSIZE OPEN END WITHVENT CAP

CONNECT TO TOP OFMAIN FOR MAINCONDENSATE PIPE.

BOTH ENDS

CLEAN OUT PLUG,

1. DRAIN LINE TO BE GALVANIZED STEEL IN MECHANICAL ROOMSAND WHERE EXPOSED AND MAY BE COPPER IN CONCEALED AREAS(ABOVE HUNG CEILINGS).

3. CONNECT TO SANITARY SEWER THROUGH AIR GAPFITTING AND TRAP PRIMER.

2. USE DWV FITTINGS ON 1-1/4" AND. LARGER PIPE.

H2

AT DRAIN PAN IN INCHES

NEGATIVE STATIC PRESSURE

H2 =

H3 =

H1 =

PLUS 1 INCH.

1" MINIMUM

H1 (2"MINIMUM)

SUNCTION SIDE OF FAN)

(NEAGATIVE PRESSURE

COOLING COIL

DRAIN PAN

H1

NOTE:

3"

H3

APPLICATION)

DIELECTRIC FITTING

(FOR COPPER PIPE

FULL UNITCONNECTIONSIZE

ROUTING OF CD.SEE DRAWING FOR

CLEANOUT TEE

IN DIRECTION

W/ M.P.T. PLUGAT ALL CHANGES

AHU-2 PLAN VIEW

(18") (46") (46") (18")

(5")

(56")

(48'')

(48")

(5")

(32) ANCHORSTOTAL

(390")

(128")

UNIT BASE RAIL 12" MIN.

2" WIDE MASON TYPE "W"

NEOPRENE WAFFLE PAD

SIZE BASED ON 60#/SQ.IN.

ROOFING/FLASHING, SEEARCH DRAWINGS

3/4" DIAMETER SS-304 KBTZ LOCATE2" FROM CENTERLINE OF THE TEE

LOADING

UNIT

SEE STRUCTURAL ANDARCHITECTURALDRAWINGS

(5'')

(5'')

(5'')

(5'')

(5'')

(5'')

(5'')

(106'')

(56'')

(56'')

(5'')

(5")

(107'')

(48'')

AHU-3 PLAN VIEW

(18") (22") (22") (18")

(5")

(56")

(55'')

(55")

(5")

(32) ANCHORSTOTAL

(365")

(80")

(5'')

(5'')

(5'')

(5'')

(5'')

(5'')

(5'')

(119'')

(56'')

(56'')

(5'')

(5")

(83'')

(48'')

(55'')

(48'')

(60'')

(60'')

(60'')

NOTE:

1. DIMENSIONS SHOWN ARE APPROXIMATE AND NOT TO SHOWNTO SCALE . COORDINATE EXACT MOUNTING WITH STRUCTURALENGINEER PRIOR TO INSTALLATION.

EFORPDERETSI

GE R

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

No. 030802

M

E C H A N IC A

L

HO

RM

OZ L. JANSS

EN

S

E N G I N E E R I N G

I N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Jesse Agosta

2014-0174

RENEWAL

DATE

ARCHIT

ECT

LIC

ENSED

CALI FORN

IA

STA

TE

O F

TROY PENNINGTON

C-31285

5-31-17

IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT

OFFICE OF REGULATION SERVICES

AC FLS SS

DATE

01-114593

FILE NO.43-C1

DSA COMMENTS 09-15-2015

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

DETAILS - MECHANICAL

M7.04

9.15.2015

1089-0002

DSA SUBMITTAL

NO SCALE

2 CHWP-1,2 ANCHORAGE DETAIL

NO SCALE

1 HWP-1,2 ANCHORAGE DETAIL

NO SCALE

4 CONDENSATE DRAIN DETAIL

NO SCALE

3 AIR HANDLER MOUNTING DETAIL (AHU-2 & AHU-3)

1

1 ADDENDUM 1 11-06-2015

Page 9: SAN JOSE CITY COLLEGE MSK-001 - SJECCD

CEILING

COLOR TO MATCH THE CEILING COLOR.WITH GASKETED FLUSH PLATE, CUSTOMCONCEALED OPERATOR

THE DIFFUSER ASFAR UPSTREAM FROMLOCATE DAMPER AS

POSSIBLE

FOR RIGHT ANGLE OPERATION.MITER GEARS WHERE REQ'D

ARE NOT ALIGNED

3/8" CONNECTING ROD

UNIVERSAL JOINT IF CONNECTIONS

QUADRANT OPERATOR

TYPICAL DUCT PENETRATION

TYPICAL DUCT, PIPE OR CONDUIT PENETRATIONNOTE: APPLICABLE AT ALL SOUND-RATEDCONSTRUCTION INCLUDING INSULATED ASSEMBLIES.

ACOUSTICAL SEALANT

FOAM BACKER ROD

1" SAFING BATT INSULATION

4" TO 8"(TYP. ONBOTHSIDES)

1" +/- 1/4"

DUCT SUPPORT

ACOUSTICAL SEALANT

FOAM BACKER ROD

1" SAFING BATT INSULATION

4" TO 8"(TYP. ONBOTHSIDES)

1" +/- 1/4"

SUPPORT SUPPORT

(DUCT, PIPE OR CONDUIT 3" DIAMETER OR GREATER)

DUCT

CONNECT TO STRUCTURE.

CABLES IN EACH OF 4 DIRECTIONS.

PROVIDE SEISMIC RESTRAINT

45° MAX.

FAN.

IN-LINE 1/2"Ø STEEL THREADED ROD.

ENTIRE CONTACT AREA (TYP.).

NEOPRENE PAD OVER

HANGER ROD (4 REQ'D.)

DUCT TRANSITION AS

REQUIRED.

SUPPORT FROM

STRUCTURE AS

REQUIRED.

FLEXIBLE CONN.

(TYP.).

MOUNTING

BRACKETS (TYP.).

.

SPRING ISOLATOR,(TYP)

FLEX DUCT,SEEPLAN FOR SIZES

1" ACOUSTICAL

LINED BOX

T-BAR CEILING

SURFACE MOUNT

ON GYP.BD

CEILING

EFORPDERETSI

GE R

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

No. 030802

M

E C H A N IC A

L

HO

RM

OZ L. JANSS

EN

S

E N G I N E E R I N G

I N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Jesse Agosta

2014-0174

RENEWAL

DATE

ARCHIT

ECT

LIC

ENSED

CALI FORN

IA

STA

TE

O F

TROY PENNINGTON

C-31285

5-31-17

IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT

OFFICE OF REGULATION SERVICES

AC FLS SS

DATE

01-114593

FILE NO.43-C1

DSA COMMENTS 09-15-2015

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

DETAILS - MECHANICAL

M7.05

9.15.2015

1089-0002

DSA SUBMITTAL

NOT TO SCALE

1 FIRESTOP DETAIL

NO SCALE

3 DUCTWORK DAMPER OPERATOR

NO SCALE

2 VAV MOUNTING DETAIL

NO SCALE

4 ACOUSTICAL PENETRATION

1

NO SCALE

5 INLINE FAN MOUNTING DETAIL

1

1 ADDENDUM 1 11-06-2015

NO SCALE

6 TRANSFER AIR DUCT INSTALLATION DETAIL

1

Page 10: SAN JOSE CITY COLLEGE MSK-001 - SJECCD

Supplemental #:

Original Drawing:

Date:

Scale:

SAN JOSE CITY COLLEGE

SCHEDULES - MECHANICAL

MSK-W 11089-0002

11/10/15

PHYSICAL EDUCATION BUILDING AND RENOVATED LABBUILDING

1 ADDENDUM 1 11-06-2015

WELLNESS CENTER - CONDENSED PACKAGED ROOFTOP AIR CONDITIONING UNIT SCHEDULE (GAS FURNACE)

SYMBOL SERVING

BASIS OF DESIGN ELECTRICAL

EERCONTROLS

REF

APPROX.DIMENSIONS

(HxWxL)MAX WT

(LBS) COMMENTSMFR MODEL MCA MOCP VOLTS PHAC-1 WELLNESS

CENTERALLIED KGA090S4B 44.0 60.0 208 3 11 47x47x96 (IN) 1000

AC-2 WELLNESSCENTER

ALLIED KGA090S4B 44.0 60.0 208 3 11 47x47x96 (IN) 1000

1

WM0.03