SAN JOSE CITY COLLEGE MSK-001 - SJECCD
Transcript of SAN JOSE CITY COLLEGE MSK-001 - SJECCD
Supplemental #:
Original Drawing:
Date:
Scale:
SAN JOSE CITY COLLEGE
SYMBOL LIST & GENERAL NOTES -MECHANICAL
MSK-0011089-0002
11/10/15
PHYSICAL EDUCATION BUILDING AND RENOVATED LABBUILDING
1 ADDENDUM 1 01-15-2016
M0.01
NO SCALE
DSA STRUCTURAL ANCHORAGE COORDINATION SCHEDULE sketch
SYMBOL DESCRIPTION LOCATIONMOUNTED
ON SUPPORT TYPESUPPORT MODEL
NUMBER
DIMENSIONS
MAXWEIGHT
(LBS)REFERENCEDRAWINGS
ANCHMODEL
NODIA
OVERALLDIMENSIONS
(LxWxH)
AHU-1 AIR HANDLER LOCKER ROOF CONCRETE PAD FANS SPRING ISOLATED SEE NOTES BELOW 66"Wx100"Hx210"L 6000 M2.02, 8/M7.03 KBTZ
AHU-2 AIR HANDLER UPPER ROOF STEEL BEAMS FANS SPRING ISOLATED SEE NOTES BELOW 250"Wx104"Hx390"L 26000 M2.03, 5/S5.21, 3/M7.04 KBTZ
AHU-3 AIR HANDLER UPPER ROOF STEEL BEAMS FANS SPRING ISOLATED SEE NOTES BELOW 198"Wx84"Hx365"L 17400 M2.03, 5/S5.21, 3/M7.04 KBTZ
CHWP-1 BASE MOUNTED PUMP HYRONICS 157 CONCRETE PAD B-1 OR TYPE 1 SEE NOTES BELOW 540 1/M4.01, 5/M7.02 KBTZ
CHWP-2 BASE MOUNTED PUMP HYDRONICS 157 CONCRETE PAD B-1 OR TYPE 1 SEE NOTES BELOW 540 1/M4.01, 5/M7.02 KBTZ
CU-1 CONDENSING UNIT UPPER ROOF SLEEPERS SEE NOTES BELOW 532 M2.03, 2/M7.03 KBTZ
EF-1 CENTRIFUGAL NORTH OFFICE ROOF ROOF CURB 5C SEE NOTES BELOW 24" 45 M2.02, 3/M7.02 KBTZ
EF-2 CENTRIFUGAL LOCKERS ROOF ROOF CURB - SEE NOTES BELOW 50" 180 M2.02, 3/M7.02 KBTZ
EF-3 CENTRIFUGAL UPPER ROOF ROOF CURB - SEE NOTES BELOW 36" 120 M2.03, 3/M7.02 KBTZ
EF-4 CENTRIFUGAL WELLNESS CENTER ROOF ROOF CURB - SEE NOTES BELOW 22" 30 5/WM2.04, 3/M7.02 KBTZ
EF-5 INLINE FAN EQUIPMENT STORAGE SPRING HANGER 5C SEE NOTES BELOW 37''Wx15''Hx17''L 68 5/M/7.05 KBTZ
FC-1 CEILING HUNG HYDRONIC FAN COIL NORTH OFFICE SPRING HANGER 5C SEE NOTES BELOW 37"Wx22"Hx37"D 150 M2.01, 4/M7.02 KBTZ
FC-2 CEILING HUNG HYDRONIC FAN COIL SOUTH OFFICE SPRING HANGER 5C SEE NOTES BELOW 48"Wx24"Hx402"D 150 M2.01, 4/M7.02 KBTZ
FC-3 WALL MOUNTED UNITS TELECOM ROOM WALL MOUNTED - SEE NOTES BELOW 46"Wx15"Hx12"D 46 M2.01, 4/S7.08, 1/M7.03 KBTZ
FC-5 CEILING HUNG DX FAN COIL MACH. ROOM 120 SPRING HANGER 5C SEE NOTES BELOW 71 M2.01, 4/M7.02 KBTZ
FC-6 WALL MOUNTED UNITS ELECTRICAL WALL MOUNTED - SEE NOTES BELOW 46"Wx15"Hx12"D 46 M2.01, 4/S7.08, 1/M7.03 KBTZ
GI-1 GRAVITY INTAKE UNITS NORTH OFFICE ROOF ROOF CURB - SEE NOTES BELOW 15 M2.02, 5/M7.03 KBTZ
GI-2 NORTH OFFICE ROOF ROOF CURB - SEE NOTES BELOW 29 M2.02, 5/M7.03 KBTZ
HWP-1 BASE MOUNTED PUMP HYDRONICS 157 CONCRETE PAD B-1 OR TYPE 1 SEE NOTES BELOW 220 1/M4.01, 4/M7.04 KBTZ
HWP-2 BASE MOUNTED PUMP HYDRONICS 157 CONCRETE PAD B-1 OR TYPE 1 SEE NOTES BELOW 220 1/M4.01, 4/M7.04 KBTZ
NOTES:1. SEE SPECIFICATIONS 23 05 48 FOR FURTHER DESCRIPTIONS OF VIBRATION ISOLATOR TYPES.2. TYPE "1" - 3/4" NEOPRENE PAD: RUBBER WAFFLE PAD (MASON TYPE: SUPER WMH).3. TYPE "2" - NEOPRENE MOUNT: DOUBLE DEFLECTION TYPE (MASON TYPE: BR).4. TYPE "3" - SPRING: FREESTANDING, LATERALLY STABLE, OPEN-SPRING ISOLATORS (MASON TYPE: SLFH).5. TYPE "4a" - RESTRAINED SPRING ISOLATORS: FREESTANDING, STEEL, OPEN-SPRING ISOLATORS WITH SEISMIC RESTRAINT (MASON TYPE: SLR).6. TYPE "4b" -HOUSED SPRING MOUNTS: HOUSED SPRING ISOLATOR WITH INTEGRAL SEISMIC SNUBBERS (MASON TYPE: SSLFH).7. TYPE "5a" - RESTRAINED ELASTOMERIC HANGERS: DOUBLE-DEFLECTION TYPE (MASON TYPE: RWHD).8. TYPE "5c" - SPRING HANGERS WITH VERTICAL-LIMIT STOP: COMBINATION COIL-SPRING AND ELASTOMERIC-INSERT HANGER WITH SPRING AND INSERT IN COMPRESSION AND WITH A VERTICAL-LIMIT STOP (MASON TYPE: RW30)9. TYPE "6" - HORIZONTAL THRUST RESTRAINTS: COMBINATION COIL SPRING AND ELASTOMERIC INSERT WITH SPRING AND INSERT IN COMPRESSION AND WITH A LOAD STOP (MASON TYPE: WBI OR WBD).
1
1
1
EFORPDERETSI
GE R
REEN
IGN
E
LANOISS
C A L I F OR N I AS T A T E O F
No. 030802
M
E C H A N IC A
L
HO
RM
OZ L. JANSS
EN
S
E N G I N E E R I N G
I N T E R F A C E
TEL
FAX
PROJECT
CONTACT
www.interfaceengineering.com
717 Market Street
Suite 500
San Francisco, CA 94103
415.489.7240
415.489.7289
SHEET NO:
DATE:
PROJECT NO:
THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.
THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.
CONSULTANT
6910 5 31112 8 7 4 2 1
J
K
H
G
F
E
D
C
B
A
B
A
J
K
H
G
F
E
D
C
6910 5 31112 8 7 4 2 1
NO. ISSUE DATE
ARCHITECT'S STAMP APPROVAL
Jesse Agosta
2014-0174
RENEWAL
DATE
ARCHIT
ECT
LIC
ENSED
CALI FORN
IA
STA
TE
O F
TROY PENNINGTON
C-31285
5-31-17
IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT
OFFICE OF REGULATION SERVICES
AC FLS SS
DATE
01-114593
FILE NO.43-C1
DSA COMMENTS 09-15-2015
SAN JOSE CITYCOLLEGE
PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING
SAN JOSE, CALIFORNIA
SCHEDULES - MECHANICAL
M0.02
9.15.2015
1089-0002
DSA SUBMITTAL
FAN SCHEDULE
SYMBOL AREA SERVED
BASIS OF DESIGN
TYPE DRIVEAIR FLOW
(CFM)ESP
(IN H20) FRPMSOUNDSSONES
ELECTRICAL
CONTROLS REF MAX WT (LBS)COMMENTS
MFR MODEL VOLTS PH HP WATTSCF-1 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14
CF-2 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14
CF-3 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14
CF-4 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14
CF-5 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14
CF-6 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14
CF-7 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14
CF-8 GYMNASIUM AIRIUS AIR PEAR 45-EC CIRCULATING FAN DIRECT 1290 .1 3050 79 dBA 277 1 3/M6.02 14
EF-1 NORTH RESTROOMS GREENHECK G-90-VG CENTRIFUGAL DIRECT 400 0.3 1246 5.2 115 1 0.16 2/M6.02 45 1, 2
EF-2 LOCKERS AND LAUNDRY GREENHECK GB-300HP-15 CENTRIFUGAL BELT 5070 1 699 14.6 460 3 1.5 2/M6.02 180 1, 2
EF-3 FITNESS CENTER SHOWERS GREENHECK GB-240HP-20 CENTRIFUGAL BELT 4485 1.5 1023 16 460 3 2 2/M6.02 120 1, 2
EF-4 WELLNESS CENTER RESTROOMS GREENHECK G-085-VG CENTRIFUGAL DIRECT 350 .5 1615 8 115 1 0.16 2/M6.02 30 1, 2
EF-5 FIRST FLOOR STUDENTRESTROOMS
GREENHECK CSP-A1750 INLINE FAN DIRECT 1500 0.4 1130 4 115 1 0 550 2/M6.02 68
PUMP SCHEDULE
SYMBOL SERVING
BASIS OF DESIGN
PUMP TYPEIMPELLER
SIZE RPMEFFICIENCY
%
FLOWRATE(GPM)
HEAD(FT H20)
ELECTRICAL MOTORTYPE ODP or
TEFCVFD(Y/N)
CONTROLSREF
MAX WT(LBS) COMMENTSMFR MODEL VOLTS PH BHP MHP
CHWP-1 AHUs & FAN COILS Bell & Gossett 1510 - 3 BD BASE MOUNTED PUMP 8 1770 75 300 60.00 460 3 6.1 10 ODP Y 2/M6.01 540
CHWP-2 AHUs & FAN COILS Bell & Gossett 1510 - 3 BD BASE MOUNTED PUMP 8 1770 75 300 60.00 460 3 6.1 10 ODP Y 2/M6.01 540
HWP-1 AHUs, VAVs & FAN COILS Bell & Gossett 1510 - 2.5 AC-es BASE MOUNTED PUMP 6.625 1750 76 160 55.00 460 3 2.1 3 ODP Y 1/M6.01 220
HWP-2 AHUs, VAVs & FAN COILS Bell & Gossett 1510 - 2.5 AC-es BASE MOUNTED PUMP 6.625 1750 76 160 55.00 460 3 2.1 3 ODP Y 1/M6.01 220
AIR HANDLING UNIT SCHEDULE (INDIRECT EVAPORATIVE COOLER)
SYMAREA
SERVED
BASIS OF DESIGN SUPPLY FAN RETURN FAN CHILLED WATER COOLING COIL HOT WATER HEATING COIL FILTER ELECTRICAL
SMOKEDETECTOR
(Y/N)
MAXWT
(LBS) COMMENTSMFR MODELTOTALCFM
MINOSACFM
ESP(IN
H2O)# OFFANS BHP HP FRPM
VFD(Y/N)
TOTALCFM
ESP(IN
H2O)# OFFANS BHP HP FRPM
VFD(Y/N)
TOTALCAP
(MBH)
SENSCAP
(MBH)FPI/
ROWS
WATERFLOWGPM
EWT(°F)
LWT(°F)
EDB(°F)
EWB(°F)
LDB(°F)
LWB(°F)
MAXFACEVEL.(FPM)
MAXAPD
(IN H2O)
MAXWPD
(FT H2O)
CHW MINBRANCH
PIPESIZE
MINCAP
(MBH)#
ROWS FPI
WATERFLOW(GPM)
EWT(°F)
LWT(°F)
EDB(°F)
LDB(°F)
MAXFACEVEL.(FPM)
MAXAPD
(IN H2O)
MAXWPD
(FT H2O)
HW MINBRANCH
PIPESIZE
EFFMERV VOLTS PH FLA MCA
MOCP
AHU-1 LOCKERS ENERGYLABS
C-058-066-FCHI-L 6500 6500 2 1 6.26 7.5 2385 Y 0 0 0 0 0 0 N/A 245.0 155.0 8/6 41 44 56 76 66 54 53 400 0.70 10.00 2" 415 2 7 22 180 140 29 88 400 0.25 10.00 2" 13 460 3 13.7 16.5 25 Y 6000 1
AHU-2 GYMNASIUM ENERGYLABS
C-090-128-FCHI-L 24000 7200 2 4 5.65 7.5 2002 Y 24000 1.5 3 4.08 5 1904 Y 950.0 595.0 9/6 158 44 56 76 66 53 53 400 0.70 10.00 4" 725 2 7 36 180 140 55 83 400 0.25 10.00 2" 13 460 3 71.0 81.0 110 Y 26000 2
AHU-3 FITNESSCENTER
ENERGYLABS
C-084-080-FCHI-L 0 8530 2 2 8.44 10 1913 Y 8250 1.5 2 3.1 5 1052 Y 418.0 327.0 8/4 60 44 56 76 66 54 53 400 0.70 10.00 2 1/2" 562 1 10 28 180 140 55 86 400 0.25 10.00 2" 13 460 3 55.6 62.4 80 Y 17400 3,4
TERMINAL UNIT SCHEDULE
SYMBOL AREA SERVED
BASIS OFDESIGN
INLETSIZE
COOLINGAIR FLOW
INLETSP (INH2O)
DNSTREAM SP
(IN H2O)
MININLET SP(IN H2O)
HOT WATER HEATING COILSOUNDDATA ELECTRICAL
CONTROLSREF
VALVETYPE
(2-WAYOR
3-WAY) COMMENTSMFR MODELMAXCFM
MINCFM
MAXHTGCFM
MINCAPMBH GPM
EAT(°F)
LAT(°F)
EWT(°F)
LWT(°F)
#ROWS FPI
WPD(FT H2O)
MINBRANCHPIPE SIZE
RADNC
DISCHNC VOLTS PH
VAV-1 TICKETS/CONCESSION TITUS DESV 8" 490 155 1.00 0.25 0.11 245 9.3 0.8 55 90 180 155 1 10 0.39 3/4" 19 18 24 1 3/M6.01 2 1-11
VAV-2 TELECOM TITUS DESV 10" 800 800 1.00 0.25 0.01 0 0.0 0.0 0 0 0 0 0 0 0.00 0" 24 19 24 1 3/M6.01 2 1-11
VAV-3 OFFICE/EQUIPMENT STORAGE TITUS DESV 8" 480 195 1.00 0.25 0.11 230 8.8 0.7 55 90 180 153 1 10 0.29 3/4" 19 18 24 1 3/M6.01 2 1-11
VAV-4 TRAINING ROOM TITUS DESV 8" 450 180 1.00 0.25 0.10 225 8.6 0.6 55 90 180 152 1 10 0.26 3/4" 19 18 24 1 3/M6.01 2 1-11
VAV-5 TRAINING ROOM TITUS DESV 8" 550 470 1.00 0.25 0.01 0 0.0 0.0 0 0 0 0 0 0 0.00 0" 22 21 24 1 3/M6.01 2 1-11
VAV-6 MULTIPURPOSE CLASSROOM TITUS DESV 10" 600 125 1.00 0.25 0.09 300 11.4 0.8 55 90 180 153 1 10 0.08 3/4" 22 18 24 1 3/M6.01 2 1-11
VAV-7 MULTIPURPOSE CLASSROOM TITUS DESV 10" 900 365 1.00 0.25 0.17 365 13.9 1.4 55 90 180 160 1 10 0.21 3/4" 23 19 24 1 3/M6.01 2 1-11
VAV-8 FOOTBALL LOCKER ROOM TITUS DESV 40 2000 2000 1.00 0.25 0.15 2000 76.0 2.3 55 90 180 111 2 10 0.33 3/4" 27 21 24 1 3/M6.01 2 1-11
VAV-9 MENS TEAM TOILETS/SHOWER/TEAN DRESSSING
ROOM
TITUS DESV 12" 1295 1295 1.00 0.25 0.37 1295 49.2 2.5 55 90 180 139 2 10 0.84 3/4" 20 20 24 1 3/M6.01 2 1-11
VAV-10 WOMENS TEAM SHOWER/TOILETS/ TEAM DRESSING
ROOM
TITUS DESV 40 2325 2325 1.00 0.25 0.18 2325 88.3 2.9 55 90 180 118 2 10 0.54 3/4" 29 22 24 1 3/M6.01 2 1-11
VAV-11 FITNESS CENTER TITUS DESV 12" 900 450 1.00 0.25 0.10 450 17.1 1.2 55 90 180 152 1 10 0.12 3/4" 19 18 24 1 3/M6.01 2 1-11
VAV-12 FITNESS CENTER TITUS DESV 14" 1400 355 1.00 0.25 0.12 700 26.6 2.1 55 90 180 155 1 10 0.50 3/4" 20 15 24 1 3/M6.01 2 1-11
VAV-13 FITNESS CENTER TITUS DESV 12" 960 255 1.00 0.25 0.11 480 18.2 1.5 55 90 180 154 1 10 0.29 3/4" 20 18 24 1 3/M6.01 2 1-11
VAV-14 FITNESS CENTER TITUS DESV 14" 1305 695 1.00 0.25 0.10 695 26.4 2.1 55 90 180 154 1 10 0.48 3/4" 20 15 24 1 3/M6.01 2 1-11
VAV-15 FITNESS CENTER TITUS DESV 14" 1350 675 1.00 0.25 0.11 675 25.6 1.9 55 90 180 153 1 10 0.41 3/4" 20 15 24 1 3/M6.01 2 1-11
VAV-16 FITNESS CENTER TITUS DESV 12" 1080 360 1.00 0.25 0.13 540 20.5 2.0 55 90 180 160 1 10 0.57 3/4" 22 20 24 1 3/M6.01 2 1-11
VAV-17 FITNESS CENTER TITUS DESV 16" 1690 855 1.00 0.25 0.11 855 32.5 2.5 55 90 180 153 1 10 0.71 3/4" 16 14 24 1 3/M6.01 2 1-11
VAV-18 EXERCISE LAB TITUS DESV 12" 900 420 1.00 0.25 0.10 420 16.0 1.0 55 90 180 149 1 10 0.16 3/4" 19 18 24 1 3/M6.01 2 1-11
VAV-19 EXERCISE LAB TITUS DESV 12" 1080 215 1.00 0.25 0.13 540 20.5 2.0 55 90 180 160 1 10 0.57 3/4" 22 20 24 1 3/M6.01 2 1-11
VAV-20 EXERCISE LAB TITUS DESV 16" 1600 465 1.00 0.25 0.10 800 30.4 2.1 55 90 180 150 1 10 0.51 3/4" 15 13 24 1 3/M6.01 2 1-11
VAV-21 PUBLIC WOMENS RESTROOM TITUS DESV 8" 500 275 1.00 0.25 0.12 275 10.5 1.1 55 90 180 161 1 10 0.77 40" 19 18 24 1 3/M6.01 2 1-11
NOTES:1) ALL BOXES SHALL BE PROVIDED WITH HIGH CFM CONTROL.2) ALL BOXES SHALL BE PRESSURE INDEPENDANT AND COMPLETE WITH CENTER AVERAGING AIRFLOW SENSOR.3) SEISMIC BRACE UNIT PER SMACMA GUIDELINES.4) COIL CONNECTION AND CONTROL BOX SHALL BE ON OPPOSITE SIDE.5) CONTROL VALVES TO BE FIELD INSTALLED AS REQUIRED. (2-WAY & 3-WAY)6) ALL TERMINAL BOXES SHALL HAVE MINIMUM 1 INCH INSULATION CONFORMING TO UL181 AND NFPA90A.
7) ALL PERFORMANCE SHALL BE ARI CERTIFIED.8) ROOM NC LEVEL SHOWN INCLUDES ATTENUATION TRANSFER FUNCTIONS OBTAINED FROM TABLES IN ARI STANDARD 885.9) SOUND DATA SHALL BE OBTAINED FROM TESTS CONDUCTED IN ACCORDANCE WITH ARI STANDARD 880-98.10) 120V POWER TO CONTROL TRANSFORMER BY DIVISION 26. 24V DDC CONTROL WIRING BY "RELIABLE" CONTROL CONTRACTOR.11) SEE 1/M6.02 FOR MOUNTING DETAIL AND 4/M5.01 FOR TERMINAL BOX PIPING DIAGRAM.
NOTES:1) PROVIDE BACKDRAFT DAMPER.2) PROVIDE ROOFCURB.
CHILLED AND HEATING WATER FAN COIL SCHEDULE
SYMBOL SERVING
BASIS OF DESIGN
AIR FLOW(CFM) MIN OSA
FAN ESP(IN H2O)
COOLING CHW MIN.BRANCHPIPE SIZE
HEATING HW MINBRANCHPIPE SIZE
ELECTRICAL
FILTEREFF MERV
CONTROLSREF
MAX WT(LBS) COMMENTSMFR MODEL
TOTALCAP (MBH)
SENS CAP(MBH) GPM EWT (°F) LWT (°F) EDB (°F) EWB (°F) LDB (°F) LWB (°F) WPD
MIN CAP(MBH) GPM EWT (°F) LWT (°F) EAT (°F) LAT (°F) WPD VOLTS PH FLA
FC-1 NORTHOFFICES
IEC HBD20 950 400 1.5 69.0 46.0 11.6 44 56 76 66 55 54 6.50 1 1/2" 146.0 7.3 180 140 29 96 3.00 1" 480 3 2.8 13 5/M6.02 150 1
FC-2 SOUTHOFFICES
IEC HBD06 300 75 0.95 18.4 12.0 3.1 44 56 76 66 55 54 1.20 3/4" 42.0 2.1 180 140 29 106 1.20 3/4" 480 3 1.1 13 5/M6.02 150 1
CONDENSING UNIT SCHEDULE
SYMBOL
BASIS OF DESIGN
RELATED FANNOMTONS
COOLING MINEFF
(EER)
ELECTRICAL
CONTROLSREF
MAX WT(LBS) COMMENTSMFR MODEL CAP (MBH)
AMBTEMP (F) VOLTS PH MCA MOCP
CU-1 MITSUBISHI PUHY-P96YLMU-A FC-3, FC-5, FC-6 8 96.0 94 15.5 460 3 14.0 20 4/M6.02 532 1
SPLIT SYSTEM FAN COIL SCHEDULE
SYMBOLAREA
SERVED
BASIS OF DESIGN AIRFLOW(CFM)
COOLING ELECTRICAL
MAX WT.(LBS) COMMENTSMANUFACTURER MODEL
TOTAL(MBH)
SENS.(MBH)
ENT. AIR
VOLTAGE PH MOCP(°F DB)FC-3 TELECOM ROOM MITSUBISHI ELECTRIC PKFY-P30NKMU-E 710 30 28 78 208 1 15 46 1
FC-5 MACH. ROOM 120 MITSUBISHI ELECTRIC PEFY-P24NMAU-E 800 24 24 78 208 1 15 71 1
FC-6 ELECTRICAL MITSUBISHI ELECTRIC PKFY-P30NKMU-E 710 30 28 78 208 1 15 46 1
GRAVITY RELIEF AND GRAVITY INTAKE SCHEDULE
SYMBOLSERVING
BASIS OF DESIGNAIR FLOW
(CFM)ESP
(IN H20)
THROATVELOCITY(FT/MIN)
MAX WT(LBS) COMMENTS
MFRMODEL
GI-1 OFFICE NORTH GREENHECK GRSI 475 0.05 350 15 1, 2
GI-2 OFFICE NORTH GREENHECK GRSI 1200 0.05 370 29 1, 2, 3
SOUND ATTENUATOR SCHEDULE
SYMBOL SERVING
BASIS OF DESIGN
CFM LENGTH
SILENCERPRESSURE DROP
(IN WG) VELOCITY
MIN DYNAMIC INSERTION LOSS (DB)OCTAVE BAND MID-FREQUENCY HZ
COMMENTSMFR MODEL 63 125 250 500 1K 2K 4K 8KS-1 AHU-2 SUPPLY VAW SYSTEMS RSA-30V70 24000 7' - 0" 0.20 1694 FPM 5 11 19 23 25 18 17 13 1
S-2 AHU-2 RETURN VAW SYSTEMS RSA-30V70 24000 7' - 0" 0.18 -1694 FPM 6 13 19 23 22 18 16 12 1
S-3 AHU-3 SUPPLY VAW SYSTEMS RSA-38V60 17035 7' - 0" 0.14 1480 FPM 7 13 22 24 24 16 15 11 1
S-4 AHU-3 RETURN VAW SYSTEMS RSA-38V60 12100 7' - 0" 0.12 -1480 FPM 6 10 18 32 37 27 22 13 1
NOTES:1) PROVIDE GOBI CONDENSATE PUMP KIT, ELECTRICAL SERVICE - 120 V, 16 W
DIFFUSER, REGISTER AND GRILLE SCHEDULE
SYMBOL TYPE FACE FRAME DAMPER FINISH
BASIS OF DESIGN
COMMENTSMFR. MODELCD-1 CEILING DIFFUSER PERFORATED LAY-IN NONE WHITE TITUS MCD 1-5
CD-2 CEILING SUPPLY DIFFUSER LAY-IN NONE WHITE ACUTHERM TF-HC 1-5
CEG-1 CEILING EXHAUST GRILLE EGGCRATE LAY-IN NONE WHITE TITUS 50F 1-5
CRG-1 CEILING RETURN GRILLE EGGCRATE LAY-IN NONE WHITE TITUS 50F 1-5
CTG-1 CEILING TRANSFER GRILLE EGGCRATE LAY-IN NONE WHITE TITUS 50F 1-5
EG-1 SIDEWALL EXHAUST GRILLE DOUBLE DEFL. 1/4" BORDER NONE WHITE TITUS 350RL 1-5
LS-1 LINEAR SLOT DIFFUSER 2" SLOT SURFACE NONE ALUMINUM TITUS ML-37 1-5
RG-1 SIDEWALL RETURN GRILLE DOUBLE DEFL. 1/4" BORDER NONE WHITE TITUS 350RL 1-5
SD-1 SIDEWALL SUPPLY GRILLE DOUBLE DEFL. 1/4" BORDER NONE WHITE TITUS 300RL 1-5
TG-1 SIDEWALL TRANSFER GRILLE DOUBLE DEFL. 1/4" BORDER NONE WHITE TITUS 350RL 1-5
NOTES:1) CONSTUCTION - CASING: 22GA. GALV., PERF: 22GA. GALV., MEDIA: FIBERGLASS.
NOTES:1) ALL POWER WIRING TO BE INSTALLED UNDER THE ELECTRICAL WORK.
NOTES:1) PROVIDE WITH GOBI CONDENSATE PUMP. ELECTRICAL SERVICE - 120 V, 16 W.
NOTES:1) COORDINATE EXACT LOCATION WITH LIGHTS, SPRINKLER HEADS AND ARCHITECTURAL RCP.2) USE BORDER TYPE 2 FOR SURFACE MOUNT IN HARD CEILINGS.3) COORDINATE WITH WALL ELEVATIONS.4) SEE FLOOR PLANS FOR NECK SIZES.5) SEE FLOOR PLANS FOR FACE SIZES.
NOTES:1) PROVIDE WITH ROOF CURB.2) PROVIDE WITH BIRD SCREEN.3) PROVIDE WITH BAROMETRIC RELIEF DAMPER.
1
1
1
1
1
1
1
1
1
1
1
1 ADDENDUM 1 11-06-2015
NOTES:1) IDEC SECTION TO BE MODEL NO. 1-60-48, EAT(DB)=88 F, EAT(WB)=68 F, LAT(DB)=75.1 F, LAT(WB)=64.1 F, MEDIA EFF=64.1%, SENS. CAP=88.46MBH, CYC. OF CONCENTRATION=4, WATER REQ'D FOR SENS. COOLING=84 LBS/HR, BLEED RATE=28 LBS/HR, MAKEUP WATER=0.22 GPM, PUMP= BURKS GA5N-1-1/4, 3/4 HP.2) IDEC SECTIONS 1&2 TO BE MODEL NO. 1-120-48, EAT(DB)=88 F, EAT(WB)=68 F, LAT(DB)=74.8 F, LAT(WB)=64.0 F, MEDIA EFF=66%, SENS. CAP=167.06MBH, WATER REQ'D FOR SENS. COOLING=158.5 LBS/HR, BLEED RATE=39.64 LBS/HR, MAKEUP WATER=0.4 GPM.3) IDEC SECTION 1 TO BE MODEL NO. 1-95-48, EAT(DB)=88 F, EAT(WB)=68 F, LAT(DB)=75.1 F, LAT(WB)=64.2 F, MEDIA EFF=64%, SENS. CAP=135.12MBH, WATER REQ'D FOR SENS. COOLING=128.2 LBS/HR, BLEED RATE=32.06 LBS/HR, MAKEUP WATER=0.32 GPM.4)IDEC SECTION 2 TO BE MODEL NO. 1-60-48, EAT(DB)=88 F, EAT(WB)=68 F, LAT(DB)=75.1 F, LAT(WB)=64.1 F, MEDIA EFF=65%, SENS. CAP=88.46MBH, CYC. OF CONCENTRATION=4, WATER REQ'D FOR SENS. COOLING=84.0 LBS/HR, BLEED RATE=28.0 LBS/HR, MAKEUP WATER=0.22 GPM, PUMP= BURKS GA5N-1-1/4, 3/4 HP.
1
CO2CO2
CO2
CO2P
ELEV.
E1.1
HALL
167
PUBLIC WOMEN'SRESTROOM
122
SPECTATOR GYMNASIUM
160
PUBLIC MEN'S RESTROOM
126
MEN'S TEAM SHOWER
147
FOOTBALL LOCKER ROOM
146
TEAM DRESSING ROOM
148
VEST.
149
TEAM DRESSING ROOM
155
HYDRONICS
157
WOMEN'S STUDENTLOCKERS
129
MULTIPURPOSE CLASSROOM
141
SOUTH CORRIDOR
150
TRAINING ROOM
138
EQUIPMENT STORAGE
133
TICKETS/ CONCESSIONS
124
TELECOM
125
LOBBY
101
DEAN'S OFFICE
104
OFFICE
111
OFFICE
112OFFICE
113
OFFICE
110
OFFICE
109
M4.01
1
E F GA.5 F.2 JH
5
6
7
8
9
B C D
ELEC.
136
TRAINING STAFF ROOM
139
JAN.
140
10x10
(490 CFM )(0.8 GPM )
VAV-1
(800 CFM )(0 GPM )
VAV-2
(450 CFM )(0.6 GPM )
VAV-4
(600 CFM )(0.8 GPM )
VAV-6
(900 CFM )(1.4 GPM )
VAV-7
(550 CFM )(0 GPM )
VAV-5
(480 CFM )(0.7 GPM )
VAV-3
20x14 (
2270)
20x12 (
1790)
26x20 (4770)
26x20
24x20
(1295 CFM )(2.5 GPM )
VAV-9
(2000 CFM )(2.3 GPM )
VAV-8
(2325 CFM )(2.9 GPM )
VAV-10
28x22 18x16
12x12
WOMEN'S TEAM TOILETS
153
MEN'S TEAM TOILETS
145
MEN'S STUDENT RESTROOM
131
WOMEN'S STUDENTRESTROOM
130
MACH. ROOM
120
STAFF LOCKER
108
WOMENS
107
MENS
106
STAFF LOCKER
105
OPEN OFFICE
102
SEE M2.02 FOR SCOPEOF MECHANICAL WORKIN THE GYMNAISUM
28x22 (
5520)
28x22
1
ELEC.
151
28x22
T
T
T
(TYP)
UP TOMECHSHAFT
14x1414x10
20x24
20x24
1
1
1
14x12
10x10
T T
T
T
TT
T
T
T
26x12
16x12
FC-1
FC-2
(VAV-10)
(VA
V-9
)
(VAV-8)
(VAV-7)(VAV-6)
(VAV-4)
(VAV-5)
(VAV-3)
T
T
(VAV-2)
(VAV-1)
(FC-1)
(FC-2)
(FC-3)
T
(VAV-14)
(AHU-2)
24x22
FC-3
OFFICE
135
A
1
2
3
4
3
4" CHWR
4" CHWS
4" CHWR
4" CHWS
5
M7.02
1
M7.03
OFFICE
103
VEST.
144
12x12
T (FC-6)
20x18 (
2050)
115
EG-16x6
LAUNDRY
159
340
340
340
340
340
280
250250
490
490 565
565
570
500290
290
290
290
285
290
285
280
280
490
490
16"
280
400
EG-112x12
20x18
GYM EQUIPMENT
134
4
M7.02
150
150
150
150
150
10''Ø
12''Ø
80
160
10''Ø
155
155
150
150
150 150 150 150
10''Ø
12''Ø
10''Ø
14''Ø
175 175150
150 150
150
60
CD-2TYP 5
6"ø
60 60 60
60
340
33512x12
400
400
310320
320
310320
320
230
230
230
230
EAST CORRIDOR
137
3
M4.01
20x12 (
1500)
290
TEAM DRESSING ROOM
154
WOMEN'S TEAM SHOWER
156
VEST.
152
4
2
150
200
200
250
250
(500 CFM )(1.1 GPM )
VAV-21
T(VAV-21)
8x8
8x8
3/4''HWS/R
150
3/4''HWS/R
3" HWS
3" HWR
3'' HWS
3'' HWR
1 1/4" HWR1 1/4" HWS
1 1/4" CHWR1 1/4" CHWS
1" HWS1" HWR
20x18 (2500)
1
5
T
4
M7.02
FC-61
M7.03
1
M7.05SEE DETAIL
FC-5
FSD
FSD
800
RG-120x8
800
SD-120x8
20x8 SA TOP
20x8 RA BOTTOM
4
M7.02
1
M7.05SEE
300
SD-112x8
RL/RS TOASSOCIATEDROOMS
7
1
20x12
20x12
800
SD-122x10
---TG-124x24
4
M7.058
9
101
1
1
EF-5
UD
UD
---TG-118x18
11
1
1
70
SD-16x6
6''Ø
190
SD-18x8
220
SD-18x8
---CTG-1TYP 2
12"ø
---CRG-1TYP 5
8"ø
---CTG-1TYP 2
12"ø
---CRG-112"ø
10x16
8x16
---CRG-112"ø
6
12"ø
245
SD-1
TYP 2
12x6
---TG-118x18
---CRG-112"ø
1
1
1
1
---TG-112x6
1
400
SD-112x10
12''Ø24x24
1
12
12x6
5
M7.05
6
M7.05
6
M7.05
EFORPDERETSI
GE R
REEN
IGN
E
LANOISS
C A L I F OR N I AS T A T E O F
No. 030802
M
E C H A N IC A
L
HO
RM
OZ L. JANSS
EN
S
E N G I N E E R I N G
I N T E R F A C E
TEL
FAX
PROJECT
CONTACT
www.interfaceengineering.com
717 Market Street
Suite 500
San Francisco, CA 94103
415.489.7240
415.489.7289
SHEET NO:
DATE:
PROJECT NO:
THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.
THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.
CONSULTANT
6910 5 31112 8 7 4 2 1
J
K
H
G
F
E
D
C
B
A
B
A
J
K
H
G
F
E
D
C
6910 5 31112 8 7 4 2 1
NO. ISSUE DATE
ARCHITECT'S STAMP APPROVAL
Jesse Agosta
2014-0174
RENEWAL
DATE
ARCHIT
ECT
LIC
ENSED
CALI FORN
IA
STA
TE
O F
TROY PENNINGTON
C-31285
5-31-17
IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT
OFFICE OF REGULATION SERVICES
AC FLS SS
DATE
01-114593
FILE NO.43-C1
DSA COMMENTS 09-15-2015
SAN JOSE CITYCOLLEGE
PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING
SAN JOSE, CALIFORNIA
1ST FLOOR PLAN -PHYSICAL EDUCATIONBUILDING - MECHANICAL
M2.01
9.15.2015
1089-0002
DSA SUBMITTAL
0' 4' 8' 16'
1/8" = 1'-0"
1 1ST FLOOR PLAN - PHYSICAL EDUCATION BUILDING - MECHANICAL
SHEET KEYNOTES1 ALUMINUM OR STAINLESS STEEL DUCT SLOPED AT
1% BACK TO THE LAST DIFFUSER.
2 12x12 UP TO GRAVITY INTAKE ON ROOF.
1. SEE DIFFUSER, REGISTER AND GRILLE SCHEDULE
NOTE:
EXHAUST GRILLES
RETURN GRILLES
CD-1
SUPPLY DIFFUSER
DIFFUSER/GRILLES
TAG CFM RANGE
311-400
201-310
0-200
CD-1
CD-1
NECK SIZE
8"Ø
10"Ø
12"Ø
CRG-1
TAG CFM RANGE
375-600
211-370
0-210
CRG-1
CRG-1
NECK SIZE
8"Ø
10"Ø
12"Ø
CEG-1
TAG CFM RANGE
375-600
211-370
0-210
CEG-1
CEG-1
NECK SIZE
8"Ø
10"Ø
12"Ø
2. ALL DIFFUSERS , REGISTERS AND GRILLES TO BE TYPE CD-1, CRG-1 AND CEG-1 UNLESS NOTED OTHERWISE.
3. ALL BRANCH DUCTWORK TO DIFFUSERS, REGISTERS AND GRILLES TO BE SAME SIZE AS NECK SIZE, UNLESS NOTED OTHERWISE.
3 HWS/R & CHWS&R UP TO AHU.
4 PRESSURE SENSOR, SEE CONTROL DIAGRAMS.
GENERAL SHEET NOTES1 ALL PIPE TO BE COLOR COORDINATED PER
DISTRICT STANDARDS. SEE ARCHITECTURALDRAWINGS FOR COLOR REQUIREMENTS.
5 MOTORIZED DAMPER, TYPICAL.
6 DUCTWORK 5 FT AFTER LAST BRANCH AS NOTEDTO BE FLAT AND GALVANIZED.
7 REFRIGERANT LINE SIZING PER MANUFACTURER'SRECOMMENDATION.
1
8 ACOUSTICALLY SEALED PENETRATIONS. TYPICALFOR ALL SOUND-RATED WALLS. SEEARCHITECTURAL DRAWINGS.
9 PROVIDE DOOR LOUVER WITH 0.7 SF NFA.
10 TEMPERATURE SENSOR FOR FCU-5.
11 PROVIDE 4 SF FOR TRANSFER AIR PATH ABOVECEILING.
12 PROVIDE HIGH FREE AREA METAL SCREEN ONOPENING.
1 ADDENDUM 1 11-06-2015
CORRIDOR
201
E F GA.5 F.2 JH
5
6
7
8
9
AHU-1
B C D
1
EF-1
EF-2
(1400 CFM )(2.1 GPM )
VAV-12
(960 CFM )(1.5 GPM )
VAV-13
(1350 CFM )(1.9 GPM )
VAV-15
(1690 CFM )(2.5 GPM )
VAV-17
(1080 CFM )(2 GPM )
VAV-16
(1080 CFM )(2 GPM )
VAV-19
(900 CFM )(1 GPM )
VAV-18
(1600 CFM )(2.1 GPM )
VAV-20
38x32(12265)
34x26 (
4565)
34x26 (
8685)
26x18 (
3580)
32"ø (8000)
32"ø (8000)
24x22
2
M4.01
2
TERRACE
T1
JANITOR
203
ELEV.
E1.1
16"ø
42"ø (16000)
8"ø
T
T
T
T
T
T
T (VAV-12)
(VAV-15)
(VAV-16)
(VAV-17)
(VAV-18)
(VAV-20)
(VAV-19)
T
(VAV-13)
GI-1
(TYP.)
(4410)
A
1
2
3
4
50x30
2
2
1 1/4" HWR 1 1/4" HWS
1 1/2" CHWS
1 1/2" CHWR
(1305 CFM )(2.1 GPM )
VAV-14
18"ø12"ø
12"ø
16"ø
14"ø
14"ø
14"ø
12"ø 14"ø
12"ø
14"ø
18"ø
14"ø
3
M7.02
5
M7.03
3
M7.03
3
M7.02
1 1/2" HWS
1 1/2" HWR
32x30
CF-1 CF-2
CF-3
CF-4
CF-5CF-6
CF-7CF-8
24X22 UP
26x22 (4465)
30x24 (
6390)
895
RG-1
TYP 3
18x12
890
RG-1
TYP 2
18x12
34x36
(12000)
34x36
(12000)
28x22 DN
6000
RG-1
TYP-4
36x32
EXERCISE LAB
205
SPECTATOR GYMNASIUM
160
FITNESS CENTER
202
32"ø (8000)
3
M4.01
3
3
270
SD-1
TYP 4
12x6
240
SD-1
TYP 4
12x6
400
SD-1
TYP 4
12x6
270
SD-1
TYP 2
8x8
12"ø
225
SD-1
TYP 2
12x6 285
SD-1
TYP 2
8x8
280
SD-1
TYP 4
12x6
795
RG-1
TYP 2
18x12
800
RG-1
TYP 6
18x12
225
SD-1
TYP 4
8x8
225
SD-1
TYP 6
8x8
280
SD-1
TYP 5
12x6
26x18
60x34(24000)
270
SD-1
TYP 2
8x8
75
EG-16x6
(900 CFM )(1.2 GPM )
VAV-11
T (VAV-11)
12"ø
12"ø
3/4" HWS
3/4" HWR
385
LS-1
TYP 3
4x48
1-1/4" HWS
1-1/4" HWR
9
M7.01
4
M7.03
8
M7.03
OS
A
EXH
2" HWS&R,4" CHWS&RUP
2 1/2" HWR
2 1/2" HWS
3" HWR
3" HWS
3" CHWS&R,2" HWS&R UP
5" CHWS&R,3" HWS&R DN
4" CHWS
4" CHWR
1-1/2" CHWS&R,1-1/4" HWS&R DN
60x34 UPTO AHU-2
60x34 UPTO AHU-2
42x36 UP
RL/RS TOASSOCIATEDROOMS
4
GI-25
M7.03
UD
1
1
1
150
SD-18x8
8x8
1
---RG-1
TYP 2
24x24
EFORPDERETSI
GE R
REEN
IGN
E
LANOISS
C A L I F OR N I AS T A T E O F
No. 030802
M
E C H A N IC A
L
HO
RM
OZ L. JANSS
EN
S
E N G I N E E R I N G
I N T E R F A C E
TEL
FAX
PROJECT
CONTACT
www.interfaceengineering.com
717 Market Street
Suite 500
San Francisco, CA 94103
415.489.7240
415.489.7289
SHEET NO:
DATE:
PROJECT NO:
THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.
THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.
CONSULTANT
6910 5 31112 8 7 4 2 1
J
K
H
G
F
E
D
C
B
A
B
A
J
K
H
G
F
E
D
C
6910 5 31112 8 7 4 2 1
NO. ISSUE DATE
ARCHITECT'S STAMP APPROVAL
Jesse Agosta
2014-0174
RENEWAL
DATE
ARCHIT
ECT
LIC
ENSED
CALI FORN
IA
STA
TE
O F
TROY PENNINGTON
C-31285
5-31-17
IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT
OFFICE OF REGULATION SERVICES
AC FLS SS
DATE
01-114593
FILE NO.43-C1
DSA COMMENTS 09-15-2015
SAN JOSE CITYCOLLEGE
PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING
SAN JOSE, CALIFORNIA
2ND FLOOR PLAN -PHYSICAL EDUCATIONBUILDING - MECHANICAL
M2.02
9.15.2015
1089-0002
DSA SUBMITTAL
0' 4' 8' 16'
1/8" = 1'-0"
1 2ND FLOOR PLAN - PHYSICAL EDUCATION BUILDING - MECHANICAL
1 10'' VENT THROUGH ROOF FROM DRYERS BELOW.INSTALL PER MANUFACTURER'SRECOMMENDATIONS. PROVIDE NECESSARYOFFSETS AS REQUIRED TO COORDINATE ROUTINGWITH OTHER DISCIPLINES.
2 DUCT WITHIN THE GYM IS TO BE DUCT-SOX OREQUIVALENT.
3 OPEN RETURN DUCT INTO SHAFT AND TERMINATEMECHANICAL SHAFT AS RETURN PLENUM
SHEET KEYNOTES
GENERAL SHEET NOTES1 ALL PIPE TO BE COLOR COORDINATED PER
DISTRICT STANDARDS. SEE ARCHITECTURALDRAWINGS FOR COLOR REQUIREMENTS.
4 REFRIGERANT LINE SIZING PER MANUFACTURER'SRECOMMENDATION.
1
1
1 ADDENDUM 1 11-06-2015
F GF.2 H
5
6
AHU-3
42x36
38x32
1 S-3
S-4
2
2
RL/RS TOASSOCIATEDROOMS
2
M7.03
6
M7.03
3
OSA
EA
CU-1
4
M7.034 3
M7.04
Supplemental #:
Original Drawing:
Date:
Scale:
SAN JOSE CITY COLLEGE
ROOF PLAN - MECHANICAL
MSK-0021089-0002
11/10/15
PHYSICAL EDUCATION BUILDING AND RENOVATED LABBUILDING
1 ADDENDUM 1 01-15-2016
M2.03
1/8" = 1'-0"
A.5
9
HYDRONICS
157
1
3'' HWS/R
4'' CHWS/R
(TYP. 2)
3'' HWS/R
4'' CHWS/R
A
VFD VFD VFD VFD
(TYP. 2) CHWP-2CHWP-1HWP-2
HWP-1
4
M5.011
M7.04
2
M7.04
1
M5.01
1
M5.01
TCP TCP BMS
1ST FLOOR0' - 0"
2ND FLOOR15' - 0"
FITNESS T.O.DECK31' - 6"
GYM T.O. DECK36' - 2 1/2"
5 6 76.24.12.9 5.33 4
42"ø 32"ø
30x50
36x32 RETURNAIR DUCT (TYP 4)
27' -
2"
31' -
4"
AIR PEAR FAN (TYP)
32"ø32"ø
FIRE PROTECTION PIPINGFIRE PROTECTION PIPE
60x34 SA
32"ø
1ST FLOOR0' - 0"
2ND FLOOR15' - 0"
2.92 3
GI-1
FC-2
8x8 8x8
MOTORIZEDDAMPER (TYP 2)
CHWS/R ANDHWS/R PIPE TOFC-1 AND FC-2
12x12
DOMESTIC CWAND DOMESTICHWS/R PIPE.
10x16 8x16
FIREPROTECTIONPIPE
FIRE PROTECTIONPIPE
STORM DRAIN/OVERFLOWPIPE
OPEN OFFICE
102
OFFICE
113
EFORPDERETSI
GE R
REEN
IGN
E
LANOISS
C A L I F OR N I AS T A T E O F
No. 030802
M
E C H A N IC A
L
HO
RM
OZ L. JANSS
EN
S
E N G I N E E R I N G
I N T E R F A C E
TEL
FAX
PROJECT
CONTACT
www.interfaceengineering.com
717 Market Street
Suite 500
San Francisco, CA 94103
415.489.7240
415.489.7289
SHEET NO:
DATE:
PROJECT NO:
THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.
THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.
CONSULTANT
6910 5 31112 8 7 4 2 1
J
K
H
G
F
E
D
C
B
A
B
A
J
K
H
G
F
E
D
C
6910 5 31112 8 7 4 2 1
NO. ISSUE DATE
ARCHITECT'S STAMP APPROVAL
Jesse Agosta
2014-0174
RENEWAL
DATE
ARCHIT
ECT
LIC
ENSED
CALI FORN
IA
STA
TE
O F
TROY PENNINGTON
C-31285
5-31-17
IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT
OFFICE OF REGULATION SERVICES
AC FLS SS
DATE
01-114593
FILE NO.43-C1
DSA COMMENTS 09-15-2015
SAN JOSE CITYCOLLEGE
PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING
SAN JOSE, CALIFORNIA
ENLARGED PLANS ANDSECTIONS - MECHANICAL
M4.01
9.15.2015
1089-0002
DSA SUBMITTAL
0' 1' 2' 4'
1/2" = 1'-0"
1 ENLARGED VIEW - MECHANICAL
1 10'' VENT THROUGH ROOF FROM DRYERS BELOW.INSTALL PER MANUFACTURER'SRECOMMENDATIONS. PROVIDE NECESSARYOFFSETS AS REQUIRED TO COORDINATE ROUTINGWITH OTHER DISCIPLINES.
0' 4' 8' 16'
1/8" = 1'-0"
2 SECTION VIEW - GYM DUCT - MECHANICAL
SHEET KEYNOTES
GENERAL SHEET NOTES1 ALL PIPE TO BE COLOR COORDINATED PER
DISTRICT STANDARDS. SEE ARCHITECTURALDRAWINGS FOR COLOR REQUIREMENTS.
0' 2' 4' 8'
1/4" = 1'-0"
3 SECTION VIEW - OFFICE FAN COIL UNITS - MECHANICAL
1
1
1
1 ADDENDUM 1 11-06-2015
CT
SEQUENCE OF OPERATION:
THE FAN COILS SHALL BE START/STOPPED THROUGH THE BAS SCHEDULE. A CURRENT RELAY WILL PROVIDE AN ALARM IF THERE IS NOPROOF OF STATUS WITHIN 20 SECONDS OF ENERGIZING THE FAN COIL.
THE ZONE TEMPERATURE SHALL BE MAINTAINED AT AN ADJUSTABLE SETPOINT THROUGH THE MODULATION OF THE CHILLED WATER ORHOT WATER VALVE AND MODULATION OF THE ECM MOTOR.
MODULATING DAMPER TO OPEN AND CLOSE BASED ON BUILDING SCHEDULE. CALIBRATE DAMPER OPEN POSITION WITH MINIMUMOUTSIDE AIR REQUIREMENTS.
SETPOINT ADJ
ROOM TEMP
T
M
M
AI
AO
DI
DO
AI
AO
AI
AO
H
C
MODULATE
POSITION
HWSHWR
FAN COIL UNIT (TYP)
STATUS
M/S
START/STOP
C
C
MODULATE
POSITION
CHWSCHWR
CLG. COILHTG. COIL
TEMPERATURE SENSOR
(INITIAL 74ºF COOLING; 70ºF HEATING FOR FC-1 & FC-2)
RA
OSA
MD
AFMS
Supplemental #:
Original Drawing:
Date:
Scale:
SAN JOSE CITY COLLEGE
DETAILS - MECHANICAL
MSK-0031089-0002
11/10/15
PHYSICAL EDUCATION BUILDING AND RENOVATED LABBUILDING
0' 4' 8' 16'
NO SCALE
1 HEATING/CHILLED WATER FAN COIL CONTROL DIAGRAM
1
1 ADDENDUM 1 01-15-2016
M6.02
No Scale
FULL UNITCONNECTIONSIZE OPEN END WITHVENT CAP
CONNECT TO TOP OFMAIN FOR MAINCONDENSATE PIPE.
BOTH ENDS
CLEAN OUT PLUG,
1. DRAIN LINE TO BE GALVANIZED STEEL IN MECHANICAL ROOMSAND WHERE EXPOSED AND MAY BE COPPER IN CONCEALED AREAS(ABOVE HUNG CEILINGS).
3. CONNECT TO SANITARY SEWER THROUGH AIR GAPFITTING AND TRAP PRIMER.
2. USE DWV FITTINGS ON 1-1/4" AND. LARGER PIPE.
H2
AT DRAIN PAN IN INCHES
NEGATIVE STATIC PRESSURE
H2 =
H3 =
H1 =
PLUS 1 INCH.
1" MINIMUM
H1 (2"MINIMUM)
SUNCTION SIDE OF FAN)
(NEAGATIVE PRESSURE
COOLING COIL
DRAIN PAN
H1
NOTE:
3"
H3
APPLICATION)
DIELECTRIC FITTING
(FOR COPPER PIPE
FULL UNITCONNECTIONSIZE
ROUTING OF CD.SEE DRAWING FOR
CLEANOUT TEE
IN DIRECTION
W/ M.P.T. PLUGAT ALL CHANGES
AHU-2 PLAN VIEW
(18") (46") (46") (18")
(5")
(56")
(48'')
(48")
(5")
(32) ANCHORSTOTAL
(390")
(128")
UNIT BASE RAIL 12" MIN.
2" WIDE MASON TYPE "W"
NEOPRENE WAFFLE PAD
SIZE BASED ON 60#/SQ.IN.
ROOFING/FLASHING, SEEARCH DRAWINGS
3/4" DIAMETER SS-304 KBTZ LOCATE2" FROM CENTERLINE OF THE TEE
LOADING
UNIT
SEE STRUCTURAL ANDARCHITECTURALDRAWINGS
(5'')
(5'')
(5'')
(5'')
(5'')
(5'')
(5'')
(106'')
(56'')
(56'')
(5'')
(5")
(107'')
(48'')
AHU-3 PLAN VIEW
(18") (22") (22") (18")
(5")
(56")
(55'')
(55")
(5")
(32) ANCHORSTOTAL
(365")
(80")
(5'')
(5'')
(5'')
(5'')
(5'')
(5'')
(5'')
(119'')
(56'')
(56'')
(5'')
(5")
(83'')
(48'')
(55'')
(48'')
(60'')
(60'')
(60'')
NOTE:
1. DIMENSIONS SHOWN ARE APPROXIMATE AND NOT TO SHOWNTO SCALE . COORDINATE EXACT MOUNTING WITH STRUCTURALENGINEER PRIOR TO INSTALLATION.
EFORPDERETSI
GE R
REEN
IGN
E
LANOISS
C A L I F OR N I AS T A T E O F
No. 030802
M
E C H A N IC A
L
HO
RM
OZ L. JANSS
EN
S
E N G I N E E R I N G
I N T E R F A C E
TEL
FAX
PROJECT
CONTACT
www.interfaceengineering.com
717 Market Street
Suite 500
San Francisco, CA 94103
415.489.7240
415.489.7289
SHEET NO:
DATE:
PROJECT NO:
THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.
THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.
CONSULTANT
6910 5 31112 8 7 4 2 1
J
K
H
G
F
E
D
C
B
A
B
A
J
K
H
G
F
E
D
C
6910 5 31112 8 7 4 2 1
NO. ISSUE DATE
ARCHITECT'S STAMP APPROVAL
Jesse Agosta
2014-0174
RENEWAL
DATE
ARCHIT
ECT
LIC
ENSED
CALI FORN
IA
STA
TE
O F
TROY PENNINGTON
C-31285
5-31-17
IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT
OFFICE OF REGULATION SERVICES
AC FLS SS
DATE
01-114593
FILE NO.43-C1
DSA COMMENTS 09-15-2015
SAN JOSE CITYCOLLEGE
PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING
SAN JOSE, CALIFORNIA
DETAILS - MECHANICAL
M7.04
9.15.2015
1089-0002
DSA SUBMITTAL
NO SCALE
2 CHWP-1,2 ANCHORAGE DETAIL
NO SCALE
1 HWP-1,2 ANCHORAGE DETAIL
NO SCALE
4 CONDENSATE DRAIN DETAIL
NO SCALE
3 AIR HANDLER MOUNTING DETAIL (AHU-2 & AHU-3)
1
1 ADDENDUM 1 11-06-2015
CEILING
COLOR TO MATCH THE CEILING COLOR.WITH GASKETED FLUSH PLATE, CUSTOMCONCEALED OPERATOR
THE DIFFUSER ASFAR UPSTREAM FROMLOCATE DAMPER AS
POSSIBLE
FOR RIGHT ANGLE OPERATION.MITER GEARS WHERE REQ'D
ARE NOT ALIGNED
3/8" CONNECTING ROD
UNIVERSAL JOINT IF CONNECTIONS
QUADRANT OPERATOR
TYPICAL DUCT PENETRATION
TYPICAL DUCT, PIPE OR CONDUIT PENETRATIONNOTE: APPLICABLE AT ALL SOUND-RATEDCONSTRUCTION INCLUDING INSULATED ASSEMBLIES.
ACOUSTICAL SEALANT
FOAM BACKER ROD
1" SAFING BATT INSULATION
4" TO 8"(TYP. ONBOTHSIDES)
1" +/- 1/4"
DUCT SUPPORT
ACOUSTICAL SEALANT
FOAM BACKER ROD
1" SAFING BATT INSULATION
4" TO 8"(TYP. ONBOTHSIDES)
1" +/- 1/4"
SUPPORT SUPPORT
(DUCT, PIPE OR CONDUIT 3" DIAMETER OR GREATER)
DUCT
CONNECT TO STRUCTURE.
CABLES IN EACH OF 4 DIRECTIONS.
PROVIDE SEISMIC RESTRAINT
45° MAX.
FAN.
IN-LINE 1/2"Ø STEEL THREADED ROD.
ENTIRE CONTACT AREA (TYP.).
NEOPRENE PAD OVER
HANGER ROD (4 REQ'D.)
DUCT TRANSITION AS
REQUIRED.
SUPPORT FROM
STRUCTURE AS
REQUIRED.
FLEXIBLE CONN.
(TYP.).
MOUNTING
BRACKETS (TYP.).
.
SPRING ISOLATOR,(TYP)
FLEX DUCT,SEEPLAN FOR SIZES
1" ACOUSTICAL
LINED BOX
T-BAR CEILING
SURFACE MOUNT
ON GYP.BD
CEILING
EFORPDERETSI
GE R
REEN
IGN
E
LANOISS
C A L I F OR N I AS T A T E O F
No. 030802
M
E C H A N IC A
L
HO
RM
OZ L. JANSS
EN
S
E N G I N E E R I N G
I N T E R F A C E
TEL
FAX
PROJECT
CONTACT
www.interfaceengineering.com
717 Market Street
Suite 500
San Francisco, CA 94103
415.489.7240
415.489.7289
SHEET NO:
DATE:
PROJECT NO:
THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.
THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.
CONSULTANT
6910 5 31112 8 7 4 2 1
J
K
H
G
F
E
D
C
B
A
B
A
J
K
H
G
F
E
D
C
6910 5 31112 8 7 4 2 1
NO. ISSUE DATE
ARCHITECT'S STAMP APPROVAL
Jesse Agosta
2014-0174
RENEWAL
DATE
ARCHIT
ECT
LIC
ENSED
CALI FORN
IA
STA
TE
O F
TROY PENNINGTON
C-31285
5-31-17
IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT
OFFICE OF REGULATION SERVICES
AC FLS SS
DATE
01-114593
FILE NO.43-C1
DSA COMMENTS 09-15-2015
SAN JOSE CITYCOLLEGE
PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING
SAN JOSE, CALIFORNIA
DETAILS - MECHANICAL
M7.05
9.15.2015
1089-0002
DSA SUBMITTAL
NOT TO SCALE
1 FIRESTOP DETAIL
NO SCALE
3 DUCTWORK DAMPER OPERATOR
NO SCALE
2 VAV MOUNTING DETAIL
NO SCALE
4 ACOUSTICAL PENETRATION
1
NO SCALE
5 INLINE FAN MOUNTING DETAIL
1
1 ADDENDUM 1 11-06-2015
NO SCALE
6 TRANSFER AIR DUCT INSTALLATION DETAIL
1
Supplemental #:
Original Drawing:
Date:
Scale:
SAN JOSE CITY COLLEGE
SCHEDULES - MECHANICAL
MSK-W 11089-0002
11/10/15
PHYSICAL EDUCATION BUILDING AND RENOVATED LABBUILDING
1 ADDENDUM 1 11-06-2015
WELLNESS CENTER - CONDENSED PACKAGED ROOFTOP AIR CONDITIONING UNIT SCHEDULE (GAS FURNACE)
SYMBOL SERVING
BASIS OF DESIGN ELECTRICAL
EERCONTROLS
REF
APPROX.DIMENSIONS
(HxWxL)MAX WT
(LBS) COMMENTSMFR MODEL MCA MOCP VOLTS PHAC-1 WELLNESS
CENTERALLIED KGA090S4B 44.0 60.0 208 3 11 47x47x96 (IN) 1000
AC-2 WELLNESSCENTER
ALLIED KGA090S4B 44.0 60.0 208 3 11 47x47x96 (IN) 1000
1
WM0.03