Sampling Sample point - tap sampling

15
To go to next page, click on Page- Chlorine testing with HACH Chlorine testing with HACH colorimeters colorimeters 12 Sampling Sample point - tap sampling Why is water not allowed to have sat in the pipe- work or tap for any period of time when sampling? Click here for the answer.

description

Sampling Sample point - tap sampling Why is water not allowed to have sat in the pipe-work or tap for any period of time when sampling? Click here for the answer. 12. Sampling Sample point - tap sampling Why is water not allowed to have sat in the pipe work or tap for any period of time? - PowerPoint PPT Presentation

Transcript of Sampling Sample point - tap sampling

Page 1: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

12

Sampling

Sample point - tap sampling

Why is water not allowed to have sat in the pipe-work or tap for any period of time when sampling?

Click here for the answer.

Page 2: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

Sampling

Sample point - tap sampling

Why is water not allowed to have sat in the pipe work or tap for any period of time?

1. Must reflect true condition of the water being tested.

2. Need to test water in main pipe and not the off-take pipe.

12

Page 3: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

13

Sampling process

The following steps will describe the sampling process.

Step 1:

• Run the tap on full flow for 2 minutes then reduced to a slow steady flow.

Note: When the off-take point is a long distance from the main pipe, more time is needed to flush the pipe – 5 minutes or more may be needed.

Page 4: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

14

Sampling process

Step 2:

• Sample container and cap rinsed with the sample three (3) times.

Step 3:

• Fill the sample cell and adjust volume to the line.

Page 5: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

15

Sampling process

Step 4:

Cap immediately.

Why is the cell capped immediately in step 4?

Click here for the answer.

Page 6: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

15

Sampling process

Step 4:

Cap immediately.

Why is the cell capped immediately in step 4?

To prevent loss of chlorine from the sample.

Page 7: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

16

Sampling

When taking a sample, why is it important to run the tap for at least 2 minutes?

Click here for answer.

Page 8: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

16

Sampling

When taking a sample, why is it important to run the tap for at least 2 minutes?

To ensure that a fresh sample from the main pipe is tested (and not the water that has been sitting in the off-take pipe and tap)

Page 9: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

17

Sampling

When taking a sample, describe how to correctly prepare the sample cells?

Click here for answer.

Page 10: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

17

Sampling

Before taking a samples, are the sample cells prepared?

The cells and caps are rinsed three (3) times with the sample.

Also - check the cells for dirt and staining – clean them if necessary. Replace the dirty cells if they cannot be cleaned.

Page 11: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

18

Measuring free & total chlorine - residual

• DPD method - N,N diethyl-p-phenylenediamine.

• Forms reddish pink dye - colour proportional to chlorine concentration (the more chlorine present, the darker the pink colour becomes).

• Chlorine concentration is measured using a HACH pocket colorimeter or other HACH models: DR 800 & 2000 series.

• Free chlorine – ready to measure within 1 minute.

• Total chlorine – ready to measure between 3 - 6 minutes.

Page 12: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

19

Chlorine reading

• Free chlorine = Hypochlorous acid (HOCl )

• Total chlorine = HOCl + Combined chlorine

• Combined chlorine is the sum of all chloramines

Can Free chlorine be greater than Total chlorine?

Click here for the answer.

Page 13: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

Chlorine reading

Can Free chlorine be greater than Total chlorine? Free chlorine shouldn’t be greater than Total but it can happen due to instrumental inaccuracies under certain conditions.

FREE CHLORINE COMBINED CHLORINE

TOTAL CHLORINE

80% 20%

19

Page 14: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

20

Sample cell types – Your HACH chlorine colorimeter will take specific size cells. Learn which ones you need to use in both Low and High ranges.

Page 15: Sampling Sample point - tap sampling

To go to next page, click on Page-

Chlorine testing with HACH colorimetersChlorine testing with HACH colorimeters

21

Sample cell types