CITY OF ANAHEIM DRAINAGE MANUAL FOR PUBLIC AND PRIVATE DRAINAGE FACILITIES
APPENDIXES
AUGUST 2005
Appendix B
Sample Sump Pump Design
h 2.79 ft1=
h L f⋅:=
f 0.0397 ft0=f
V
1.318 C⋅ R0.63⋅
1.852
1sec
1.852
ft0.685
⋅
⋅:=
V 7.234ft
sec=V
Q
π4
D2
:=
R 0.083 ft=RD
4:=
Q 0.63126ft
3
sec=orQ 283.33
gal
min:=
C 150:=L 70.36ft:=D 4in:=4" P.V.C., L = 70.36ft, C = 150
1. Force Main:
City of AnaheimDepartment of Public Works
Development Services Division
Grading Design Manual
Appendix H - Sample of Sump Pump Design
I. Calculation of Total Dynamic Head (T.D.H.)A. Static Head:(Maximum force main elevation - minimum wetwell elevation)
Elevation of force main discharge:
Elev_FM 100.24ft:=
Elevation of floor of wet well:Elev_WW 89.07ft:=
Pump Off Level = 0.5 ft above floor: Then Static Head:
H_ST Elev_FM Elev_WW− 0.5ft−:=
H_ST 10.67 ft=
B. Friction Head:Use Hazen-Williams Equation
h L f⋅:= f fV
1.318 C⋅ R0.63⋅
1.852
:=C
V = Velocity (fps) = Q/A
C = Hazen-Williams Coefficient
R = Hydraulic Radius = Area/ Wetted Perimeter = D/4
SumpPump.mcd 1 of 3 8/10/2005 4:17 PM
2 ea 22.00 ft
PVC, 4" 1 ea 1.50 ft
Tee, 4" x 4" x 4" 1 ea 17.00 ft
Reducer, 3" x 4" 1 ea 0.35 ft
Total L 72.85ft:=
h L f⋅:= , f 0.06 ft0=
h 4.37 ft1=
Total Dynamic Head = Static Head + Friction Head
= Static Head + Force Main + Spool + Fittings
= 7.34 ft + 2.79 ft + 0.18 ft + 4.37 ft
T.D.H. = 14.68 ft
Use T.D.H. = 14.7 ft
2. Spool on Force Main:
4" D.I.P., L = 3.00ft, C = 120
D 4in:= L 3ft:= C 120:=
R 0.083 ft=
V 7.234ft
sec=
fV
1.318 C⋅ R0.63⋅
1.852
1sec
1.852
ft0.685
⋅
⋅:= f 0.06 ft
0=
h L f⋅:=
h 0.18 ft1=
3. Fittings (Valves and Elbows using Equivalent Length Method):Values for Equivalent Length taken from: Crane Co., “Flow of Fluids through Valves, Fittings and Pipe”, Crane Technical Paper No. 410, New York, 1991
EQUIVALENT LENGTHOF STRAIGHT PIPEDESCRIPTION QUANTITY
PVC to DIP, fitting 4" x 6" 2 ea 1.00 ft
Vertical Swing Check Valve, 4" 1 ea 31.00 ft
90 Elbow, 4"
SumpPump.mcd 2 of 3 8/10/2005 4:17 PM
II. Calculation of Float Setting in Well to Satisfy Pumps:
Well Storage Dimensions (plan dimensions): L x W = 4' x 4'
Storage per 1 foot rise within well given by:
Storage 4 ft⋅ 4⋅ ft⋅ 7.48gal
ft3
⋅
⋅:=
Storage 119.681
ftgal=
Float Setting in Well:
RiseQ
Storage:= Q 283.33
gal
min=
Rise 2.367ft
min=
Assuming that the pump cycle is 60 seconds:
Float Rise 60⋅ sec:=
Float 2.37 ft=
Then, 2.37 feet is the float setting between lead pump on and off position inwell to satisfy pump cycle.