  • Sl.

    No.Description of items Qty Unit

    1

    1.1

    Supply, install, test and commission Intelligent

    Addressable Fire Alarm Control Panel (MCP) as per the

    technical specification and not limited to having Visual

    Display Unit (VDU) preferably 640 character LCD display

    with battery back up for 24 hours for normal operation and

    another 1 hours on alarm condition. The control panel,

    battery charger etc, shall be UL Listed and FM approved.

    The panel shall work in a flash scan protocol and shall be

    capable of networking with other compatible panels and

    Central Station. The panel shall have 1 Loop Capacity and

    shall be expandable up to 2 Loops.

    2 Set

    1.2

    Supply, install, test and commission Double Action Manual

    Pull Station having an integrally mounted addressable

    module that monitors and reports contact status.

    82 Nos.

    1.3Supply, install, test and commission Loop Addressable

    Sounder, as per specification.76 Nos.

    1.4

    Supply, install, test and commission Intelligent

    Addressable Input/Monitor Module, as per specification

    for interface with Fire Sprinkler Annunciating System.

    42 Nos.

    1.5

    Supply, install, test and commission Intelligent

    Addressable Fault Isolator Module capable of monitoring

    shorted loop circuit and automatically restore

    communications when shorted conditions are corrected.

    12 Nos.

    1.6Supply, install, test and commission 24V, 2.5Amps DC

    Power Supply Unit for the above sounders.20 Nos.

    1.7

    Supply, install, test and commission 2 core x 1.5 mm2

    FRLS Cable confirming to IS: 1554 and as per specification.

    (Approx. Quantity)

    6000 Mtr.

    1.8

    Supply, install, test and commission 25mm. approved

    make PVC Conduits conforming to IS and specification on

    walls / ceiling / floor etc complete with all accessories like

    junction boxes, collars, bends etc.(Approx. Quantity)

    1500 Mtr.

    SCHEDULE OF QUANTITIES

    INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM

    TOTAL FOR INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM

  • 22.1

    Supply, install, test and commission 25-Zone Public

    Addressing Control Desk, approved make, CRCA Powder

    Coated, with all call/call back facility, power supply unit

    etc, complete, as per specification.

    2 Set

    2.2

    Supply, install, test and commission Solid State Amplifier,

    480 W RMS Out Put in rack, including necessary control

    wires, jacks etc, as per specification.

    4 Set

    2.3

    Supply, install, test and commission Solid State Mixing

    Amplifier, 60 W RMS Out Put in rack, including necessary

    control wires, jacks etc, as per specification.

    4 Set

    2.4

    Supply, installation, testing and commissioning of 15 Watt

    Wall/Ceiling Mounted Type Speakers with talk back

    facility, in CRCA sheet fabricated housing, as per

    specification.

    76 Set

    2.5Supply, installation, testing and commissioning of

    Gooseneck Microphone, as per specifications. 2 Set

    2.6Supply, installation, testing and commissioning of Tone

    Generator, as per specification. 2 Mtr.

    2.7

    Supply, install, test and commission 2 core x 1.0 mm2

    Cable confirming to IS: 1554 and as per specification.

    (Approx. Quantity)

    3000 Mtr.

    2.8

    Supply, install, test and commission 25mm. approved

    make PVC Conduits conforming to IS and specification on

    walls / ceiling / floor etc complete with all accessories like

    junction boxes, collars, bends etc.(Approx. Quantity)

    1500 Mtr.

    3 FIRE HOSE REEL AND HYDRANT SYSTEMS

    3.1

    Supply, installation, testing and commissioning of Manual

    Swing Type Fire Hose Reel complete with heavy duty reel,

    19mm. dia.x30Mtr. long 2-ply polyester yarn braided

    /rubber braided pressure hose bearing IS:444 Type II mark,

    6 mm bore Red Coloured, heavy duty nylon on/off jet/spray

    nozzle conforming to IS:884, 22mm. isolating valve and all

    other necessary fixing accessories.

    50 Set

    PUBLIC ADDRESSING SYSTEM

    TOTAL FOR PUBLIC ADDRESSING SYSTEM

  • 3.2

    Supply, installation, testing and commissioning of Fire

    Hydrant Valve, bearing to ISI:5290 Type-A mark, Stainless

    Steel-304 body with 63mm. oblique instantaneous single

    outlet, 75mm. N.B. flanged inlet, Stainless Steel -304

    spindle, complete with PVC blank cap, G.I. chain,flange OD

    200 mm, PCD 160 mm, four 19 mm dia holes etc.

    52 No.

    3.3

    Supply, installation, testing and commissioning of Fire

    Hose, RRL hose jacketed with circular woven synthetic fibre.

    conforming to IS: 636:88, with Working Pressure 14

    Kg/Cm2, Proof Pressure 22 Kg/Cm2 and Burst Pressure 38

    Kg/Cm2. The Fire Hose shall be with IS: 636 Type-A

    marking and 63mm.dia.x15Mtr.long x 2 Nos. with 2 pair of

    63mm. male and female instantaneous couplings, Stainless

    steel-304, having IS: 903 mark and duly S. S. wire

    wounded. The hose shall be rolled and hung to suitable M.

    S. support in the Fire Station.

    52 Set

    3.4

    Supply, installation, testing and commissioning of Branch

    Pipe, Stainless Steel-304, short type, with 63mm. male

    instantaneous inlet, male threaded outlet, fitted with 16mm.

    bore nozzle, having IS: 903 mark.

    52 Set

    3.5

    Supply, installation, testing and commissioning of Air

    Release Valve Gunmetal, conforming to IS 903:1993,

    having rubber ball with sealing seat and with 25mm. BSP

    threaded male inlet, including necessary accessories and

    connections.

    6 Set

    3.6

    Supply, installation, testing and commissioning of 25mm.

    Ball Valve,PN-20gunmetal/cast alloy, conforming to IS:

    13095, including necessary accessories and connections.

    6 Set

    3.7

    Supply, installation, testing and commissioning of 4" dia.

    Pressure Gauge. ISI Marked from Approved

    Manufacturers.

    6 No.

    3.8

    Supply, installation, testing and commissioning of Butterfly

    Valve, slim seal, standard lever operated type confirming to

    BS:5155 with IS: 13095 Mark, slim seal standard lever

    operated type confirming with required flanges, nuts, bolts

    etc. complete.

    3.8.a 150mm. PN-20 RO No.

    3.8.b 150mm. PN-16 12 No.

    3.8c 100mm. PN-16 2 No.

    3.8d 80mm. PN-16 6 No.

    3.8e 50mm. PN-16 2 No

  • 3.9

    Supply, installation, testing and commissioning of Pressure

    Reducing Station complete with Pressure Reducing Valve,

    conforming to AFNOR NF 43-006 and BS6765, including all

    necessary accessories, 25 Bar Rating, (3.5 to 8 Bar) as

    detailed in the Technical Specifications and with Pressure

    Gauges with siphon connections on upstream and down

    stream etc. This Station shall be for reducing pressure in

    Fire Hydrant System in lower floors.

    3.9a 150mm. 2 No.

    3.10

    Supply, installation, testing and commissioning of Non

    Return Valve, Wafer Swing Check type, PN-20,

    conforming to IS: 13095 type confirming with companion

    flanges, nuts, bolts etc. complete. 150mm.

    4 No.

    3.11

    Supply, installation, testing and commission Y-Strainer with

    Cast Iron Body with ANSI Flanges, 1/8" heavy gauge

    perforated. S. S. Screen, etc. confirming with suitable fixing

    flanges, nuts, bolts etc. complete. 150mm.

    2 Set

    3.12

    Supply, installation, pressure testing and commissioning of

    Above Ground Fire Hydrant Pipe Work with Heavy Duty

    (Class-C) Mild Steel Pipes, confirming to IS :1239 Part - I,

    with Heavy Duty Fittings, confirming to IS:1239 Part - II,

    (Forged Steel Screwed Fittings for Pipes up to 50mm. dia.

    and But Welded Fittings, for pipes above 50mm. dia), such

    as tees, elbows, check nuts, unions, flanges, nipples etc.

    including cutting, threading, welding, jointing, fixing in

    ducts, on walls, ceiling by using suitable supports, providing

    higher sizes of Sleeves/Opening, wherever required, and

    protecting with approved wash primer and top coat (two

    coats) painting system as per specification.

    3.12a 150mm. dia 308 Mtr.

    3.12b 100mm. dia 60 Mtr.

    3.12c 80mm. dia. 16 Mtr.

    3.12d 25mm. dia. 12 Mtr.

    3.13

    Fire Station Shutter, fabricated out of 16 swg. M.S. Sheet.

    Door shall be 1000 x 1600 mm. min. & fixed with 4 mm

    thick Wired Glass, Rubber Beading and Locking

    arrangement. Quoted rate shall be includes all fasteners etc,

    and complete shutter shall be powder coated of approved

    colour both inside and out side. (OPTIONAL)

    50 Set

  • 44.1

    Supply, installation, testing and commissioning of Standard

    Response Upright Type Automatic Fire Sprinkler, 68/79

    degree, K- Factor: 5.6 or equal with necessary accessories

    and fittings.

    564 Nos.

    4.2

    Supply, installation, testing and commissioning of Standard

    Response Pendant Type Automatic Fire Sprinkler, 68/79

    degree, K- factor: 5.6 or equal with necessary accessories

    and fittings.

    284 Nos.

    4.3

    Supply, installation, testing and commissioning of Standard

    Response Side Wall Type Automatic Fire Sprinkler, 68

    degree, K- factor: 5.6 or equal with necessary accessories

    and fittings.

    884 Nos.

    4.4

    Supply and installation of 2 piece Chrome Plated friction

    fit recessed escutcheon for pendant sprinklers in lobby

    and side wall sprinklers in apartments.

    1168 Nos.

    4.5Supply only above Upright Type Automatic Fire Sprinkler.

    (5% extra.) RO Nos.

    4.6Supply only above Pendant Type Automatic Fire

    Sprinkler. (5% extra.) RO Nos.

    4.7Supply only above Side Wall Type Automatic Fire

    Sprinkler. (5% extra.) RO Nos.

    4.8

    Supply, installation, testing and commissioning of Air

    Release Valve Gunmetal, conforming to IS 903:1993,

    having rubber ball with sealing seat and with 25mm. BSP

    threaded male inlet, including necessary accessories and

    connections.

    6 Set

    4.9

    Supply, installation, testing and commissioning of 25mm.

    Ball Valve, PN-20 gunmetal/cast alloy, conforming

    to IS: 13095, including necessary accessories and

    connections.

    4 Nos.

    4.10

    Supply, installation, testing and commissioning of Butterfly

    Valve, slim seal, standard lever operated type confirming to

    BS:5155 with IS: 13095 Mark, slim seal standard lever

    operated type confirming with required flanges, nuts, bolts

    etc. complete.

    4.10a 150mm. PN-20 RO No.

    4.10b 150mm. PN-16 10 No.

    4.10c 100mm. PN-16 4 No.

    4.10d 80mm. PN-16 32 No.

    4.10e 65mm. PN-16 2 No.

    TOTAL FOR FIRE HOSE REEL AND HYDRANT SYSTEM

    AUTOMATIC FIRE SPRINKLER SYSTEM

  • 4.10f 50mm. PN-16 42 No.

    4.11

    Supply, installation, testing and commissioning of Pressure

    Reducing Station complete with Pressure Reducing

    Valve, conforming to AFNOR NF 43-006 and BS6765,

    including all necessary accessories, 25 Bar Rating, (3.5 to 8

    Bar) as detailed in the Technical Specifications and with

    Pressure Gauges with siphon connections on upstream and

    down stream etc. This Station shall be for reducing pressure

    in Fire Sprinkler System in lower floors

    4.11a 150mm. dia. 2 No.

    OPTIONAL FOR REVISED DESIGN, IF REQUIRED

    4.11b 150mm. dia. RO No.

    4.11c 100mm. dia. RO No.

    4.11d 80mm. dia. RO No.

    4.12

    Supply, installation, testing and commissioning of 4" dia.

    Pressure Gauge. ISI Marked from Approved

    Manufacturers.

    44 No.

    4.13

    Supply, installation, testing and commissioning of Flow

    Switch, Paddle type, IP 65 Protection with 20 Bar Working

    Pressure Protection with all necessary accessories, for

    monitoring Fire Sprinkler System. The control cabling from

    flow switches to Fire Sprinkler Annunciating Panel shall be

    measured separately.

    42 Set

    4.14

    Supply, installation, testing and commissioning of

    Hydraulically Operated Fire Sprinkler Alarm Valve (

    Installation Control Valve) UL Listed / FM approved,

    complete with check valve, trim set, water motor gong,

    control valves, pressure switch, pressure gauges etc.

    including all necessary flanges and fixing accessories.4.14a 150mm. dia. 2 No.

  • 4.15

    Supply, installation, pressure testing and commissioning of

    Above Ground Fire Hydrant Pipe Work with Heavy Duty

    (Class-C) Mild Steel Pipes, confirming to IS :1239 Part - I,

    with Heavy Duty Fittings, confirming to IS:1239 Part - II,

    (Forged Steel Screwed Fittings for Pipes up to 50mm. dia.

    and But Welded Fittings, for pipes above 50mm. dia), such

    as tees, elbows, check nuts, unions, flanges, nipples etc.

    including cutting, threading, welding, jointing, fixing in

    ducts, on walls, ceiling by using suitable supports, providing

    higher sizes of Sleeves/Opening, wherever required, and

    protecting with approved wash primer and top coat (two

    coats) painting system as per specification.

    4.15a 150mm.dia 218 Mtr.

    4.15b 100mm. dia. 148 Mtr.

    4.15c 80mm. dia. 406 Mtr.

    4.15d 65mm. dia. 768 Mtr.

    4.15e 50mm. dia. 1438 Mtr.

    4.15f 40mm. dia. 603 Mtr.

    4.15g 32mm. dia. 1572 Mtr.

    4.15h 25mm. dia. 3468 Mtr.

    4.15i 20mm.dia 12 Mtr.

    5

    Supply, test, commission and install in position following

    Portable Fire Extinguisher with Relevant IS Marks.

    5.1 CO2 - 4.5 Kg. IS: 2878. 4 Nos.

    5.2 Water CO2 - 9 Ltr. IS: 940 54 Nos.

    5.3ABC Dry Chemical - 5 Kg. IS: 2171. (Approx. Vary with no.

    of parking.)50 Nos.

    5.4 Fire Bucket. (Approx. Vary with no. of parking.) 54 Nos.

    6

    Supply and install in position Sign Boards made out of

    3mm thick "Opaque" PVC foam board with computer cut,

    PVC non-reflective self adhesive vinyl painted foam board,

    complete with mirror fasteners.

    TOTAL FOR FIRE SPRINKLER SYSTEM

    FIRE EXTINGUISHERS

    TOTAL FOR FIRE EXTINGUISHERS

    SIGNAGE

  • 6.1

    Signage Printed "IN CASE OF FIRE, USE STAIRS UNLESS

    INSTRUCTED OTHERWISE" of 1.25cm. height letters in red

    with white back ground. The size of the board shall be 25 x

    25 Cms. and shall be fixed at the height of 2Mts. from

    finished floor near Manual Pull Stations.

    82 Nos.

    6.2

    Floor Identification Signage ( ie, GROUND FLOOR etc.) at

    each stair enclosure on every floor, indicating the floor

    number in words, lettering size shall be 5 Cm. with

    contrasting colour from back ground. Size shall be 15cm x

    30cm.

    90 Nos.

    6.3

    Supply and install in position the Signage " FIRE ORDER" it

    should contain the following matter on 3mm thick "Opaque"

    PVC foam board of computerised cut, PVC non-reflective self

    adhesive vinyl painted foam board of 2' x 3'.

    98 Nos.

    A) ALERT THE SECURITY AT SECURITY ROOM BY

    ACTUATING MANUAL CALL POINT LOCATED AT

    STRATEGIC LOCATIONS.

    B) EVACUATE THE OCCUPANTS BY USING FIRE EXITS

    AND EMERGENCY EXITS ONLY AND ASSEMBLE AT

    VARIOUS ASSEMBLY POINTS.

    C) IF POSSIBLE TRY TO EXTINGUISH THE FIRE BY USING

    NEAREST / SUITABLE PORTABLE EXTINGUISHER OR

    WATER FROM NEAREST WET RISER.

    D) BE CALM AND DO NOT GIVE ANY ROOM FROM PANIC,

    WALK, DO NOT RUN.

    E) IF YOU ENCOUNTER SERIOUS DIFFICULTY IN

    EVACUATION, FLAT AND TRY TO ATTRACT ATTENTION OF

    RESCUE TEAM.

    6.4

    ACTION BY SECURITY/RECEPTION UPON RECEIPT OF

    INFORMATION THROUGH FIRE ALARM OR FIRE

    DETECTORS OR BY USING PUBLIC ADDRESS SYSTEM.

    8 Nos.

    A) ALERT THE OCCUPANTS BY USING PUBLIC ADDRESS

    SYSTEM.

    B) INFORM FIRE CONTROL THROUGH ANY ONE OF THE

    FOLLOWING PHONE NUMBERS: 101 / ..

    C) REFER EVACUATION PLAN FROM EVACUATING

    STANDARD PEOPLE.

    D) GUIDE THE FIRE FORCE, ON THEIR ARRIVAL TO THE

    SEAT OF FIRE.

  • E) IN CASE OF THE CASUALTIES, CALL AMBULANCE BY

    DIALING NUMBER..

    FIRE FIGHTING AGENCY -------------------------------

    PHONE : -----------------------

    FAX : ----------------------------

    TOTAL FOR SIGNAGE

    1

    2

    3

    4

    5

    6

    FIRE EXTINGUISHERS

    SIGNAGE

    ABSTRACT

    INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM

    PUBLIC ADDRESSING SYSTEM

    FIRE HOSE REEL AND HYDRANT SYSTEM

    FIRE SPRINKLER SYSTEM

  • GRAND TOTAL

  • Rate Amount

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    SCHEDULE OF QUANTITIES

    INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM

    TOTAL FOR INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM

  • 0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    PUBLIC ADDRESSING SYSTEM

    TOTAL FOR PUBLIC ADDRESSING SYSTEM

  • 0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

  • 0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

  • 0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    TOTAL FOR FIRE HOSE REEL AND HYDRANT SYSTEM

    AUTOMATIC FIRE SPRINKLER SYSTEM

  • 0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

  • 0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    TOTAL FOR FIRE SPRINKLER SYSTEM

    FIRE EXTINGUISHERS

    TOTAL FOR FIRE EXTINGUISHERS

    SIGNAGE

  • 0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

  • 0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    0.00

    FIRE EXTINGUISHERS

    SIGNAGE

    ABSTRACT

    INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM

    PUBLIC ADDRESSING SYSTEM

    FIRE HOSE REEL AND HYDRANT SYSTEM

    FIRE SPRINKLER SYSTEM

  • 0.00GRAND TOTAL