SAIC-K-4002.xls

4

Click here to load reader

Transcript of SAIC-K-4002.xls

Page 1: SAIC-K-4002.xls

Page 1 of 2

SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - June 2008) Rev 3 30-Jun-08

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Exhaust Fan Installation Inspection SAIC-K-4002 15-Dec-09 HVAC

PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIMESAUDI ARAMCO USE ONLY

SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE

A1

A2 Variable speed fan shall be provided in variable air volume systems

A3

A4 All fans shall be isolated from their ducts by flexible connections.

A5

A6

A7

A8

REFERENCE DOCUMENTS:

1-SAES-K-001 -- Heating, Ventilating and Air Conditioning (HVAC), 25 November, 2006

2-SAES-K-002 -- Air Conditioning System for Essential Operating Facilities 31 May , 2004

3- Uniform Mechanical Code (UMC), 1997

4-SAES-K-100 -- Saudi Aramco Mechanical (HVAC) Code, 31 May , 2004

Contractor / Third-Party Saudi Aramco

Name, Initials and Date:Work is Complete and Ready for Inspection:

Name, Initials and Date:T&I Witnessed QC Record Reviewed Work Verified

QC Inspector PID Representative

Name, Initials and Date:Performed Inspection Work / Rework May Proceed

Name, Initials and Date:T&I Witnessed QC Record Reviewed Work Verified

QC Supervisor Proponent and Others

Name, Sign and Date: Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified

ITEM No.

Fans shall be air-foiled, backward-inclined, backward curved, or forward-curved.

SAES-K-001Para 4.8.9.1

SAES-K-001Para 4.8.9.1

All exhaust fans shall have back draft dampers which shall close when fan is off.

SAES-K-001Para 4.8.9.2

SAES-K-001Para 4.8.14.3

Equipment (fan assembly) clearance shall be provided with a minimum of 1 m clearance on each side of equipment with openable panel or controls, unless equipment manufacturer requires greater clearances.

SAES-K-001Para 5.1.4

Exhaust shall be directly to the outside with a point of discharge of at least 1.5 m away from any openable window or door, and a minimum of 1m above and 3 m away from any air intake.

SAES-K-001Para 4.4.10.3

Exhaust fan used for ventilating the Battery Room shall have their exhaust point (air outlet) located in the ceiling or its upper edge flush with ceiling if it is located in a wall.

SAES-K-002Para 6.4

Fans and their Motors shall be accessible for servicing and maintenance (UMC Para 503.1)

SAES-K-100Section 1

REMARKS:

Construction Representative* PMT Representative

Name, Organization,Initials and Date:

Page 2: SAIC-K-4002.xls

Page 2 of 2

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED