www.gst.uk.com GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
-
8/22/2019 Safie Commissioning
2/31
www.gst.uk.com
SAFIE EQUIPMENT REQUIRED
GST SMOKE AND FLAME INTELLIGENT EYE
Appropriate installers manual
Copy of commissioning checklist/CCTV
Test apparatus
SAFIE Commissioning Operation
-
8/22/2019 Safie Commissioning
3/31
www.gst.uk.com
BASIC CCTV INSTALLATION GUIDE
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
Image Graber Card
Using proper tools, fitting way of connector and complying with
standard recommendation helps to reduce the signal loss
-
8/22/2019 Safie Commissioning
4/31
www.gst.uk.com
BASIC CCTV INSTALLATION GUIDE
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
Coax Cable RG59 RG6U RG11
Max Working Distance (meter) 245 365 500
Coax Cable Signal Loss (Attenuation) in dB per 100ft* (30m)
Loss* RG-59 RG-6 RG-11
1MHz 0.4dB 0.2dB 0.2dB
10MHz 1.4dB 0.6dB 0.4dB
Since losses in cables need to be considered, obviously for
longer cable runs a lower loss per metre cable should be used
to keep overall losses within acceptable limits. A 6dB loss is
generally considered acceptable dB meter
-
8/22/2019 Safie Commissioning
5/31
www.gst.uk.com
BASIC HARDWARE INSTALLATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
Insert the Graphics Acquisition card(s) and relay output card into the PCI slot on the main
board of the industrial PC one by one, and tight them with screws. Then, connect the relay
output card and the terminal block with the accessory cable.
-
8/22/2019 Safie Commissioning
6/31
www.gst.uk.com
BASIC SOFTWARE INSTALLATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
Install the SAFIE SETUP
software
Note: Drivers for Graphic Acquisition card and Relay
Output card are packed with SAFIE setup
Make sure the dongle is fixed on the PC
-
8/22/2019 Safie Commissioning
7/31www.gst.uk.com
BASIC SOFTWARE INSTALLATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
Hardware Update Wizard
Select a hardware to be updated,
The right click select
update Drivers
Window update to search for
software, tick No
Tick Installed from a list..
1 2 3
-
8/22/2019 Safie Commissioning
8/31www.gst.uk.com
BASIC SOFTWARE INSTALLATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
Hardware Update Wizard
Tick Search for the best driver in these
location Tick Include this location ,
then select the path
c:\WINDOWS\system 32
Repeat the
wizard until
the
hardware's
were all
update!!
4 5 6
Finish
-
8/22/2019 Safie Commissioning
9/31www.gst.uk.com
BASIC SOFTWARE INSTALLATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
SAFIE will enter to the detection mode automatically after the system starts
-
8/22/2019 Safie Commissioning
10/31www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
1. Password Configuration
2. Setting camera number and name
3. Configure the zones and sensitivity of each camera
4. Setting of Relay Output Cause and Effect
-
8/22/2019 Safie Commissioning
11/31www.gst.uk.com
SAFIE MAIN WINDOW
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
Channel Status
Alarm Indicator
To enter into the programming menu
Operation Menu
Visual Confirmation
-
8/22/2019 Safie Commissioning
12/31www.gst.uk.com
PASSWORD CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
Factory default value
Greenwell
Two levels of password
1. User Password
2. System Password
-
8/22/2019 Safie Commissioning
13/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
GENERAL
On the Setup
General
to configure the basic
system information
-
8/22/2019 Safie Commissioning
14/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
GENERAL
Video Channel
Valid ticked to register and
allow particular camera in the
system
Text box- allowed 40 characters
for camera location details
-
8/22/2019 Safie Commissioning
15/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
GENERAL
Relay Output
Valid ticked to enable the
function of relay out put
Text box- allowed 10 characters
for relay details
Read- to validate the changes in
the relays details
Okto confirm
-
8/22/2019 Safie Commissioning
16/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
GENERALOther Options
Video Switch Interval duration in second before the
display switch to the next channel
Auto Switch Waiting Timeduration in second before
allowed 40 characters for camera location details
Log Save Path the location of local disk you wish to save
the history
Log Save Time
Setting the time in month for saving ahistory
Log Save Number- to validate the changes in the relays
details
Okto confirm
-
8/22/2019 Safie Commissioning
17/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
PARAMETER
Under the Setup
PARAMETERfor setting
the parameters of each
channel
-
8/22/2019 Safie Commissioning
18/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
PARAMETER
Current Channelselection of
channels to be configured
-
8/22/2019 Safie Commissioning
19/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
PARAMETER
Parameterdetailed parameters setting of
each channel such as signal algorithm, fire
algorithm, sensitivity and programs
Warning: changing the parameter will inhibitthe performance of the system
-
8/22/2019 Safie Commissioning
20/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
PARAMETER
A Grideach grid can set the sensitivity
Note:
To set sensitivitymouse left click
To set the groupmouse right click
Grid Definition assigning to the numbers of grid particular
channel (a grid= a zone)
4 x 3 = 12 zones
8 x 6 = 48 zones
12 x 9 = 108 zones16 x 12 = 192 zones
20 x 15 = 300 zones
Grid Sensitivityfor smoke or flame
Sensitivity Levels: High, Normal, Low, Disabble
-
8/22/2019 Safie Commissioning
21/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
PARAMETER
Grid Groupgroup of zones and the maximum
groups can be set up is 24
Note:
To set sensitivitymouse left click
To set the groupmouse right click
-
8/22/2019 Safie Commissioning
22/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
PARAMETER
Relay Output Each group can be linked in one
or more relays by ticking the box.
Output Condition - is the cause and effect for
each groupFor example: the group A0 has 9 zones, and set the output
condition into 1 of 9, it means any zones goes into an alarm in
group A0 will activate the relay of DO.1
TESTto test the setting
SAVE-To save the setting
Okto confirm
-
8/22/2019 Safie Commissioning
23/31
www.gst.uk.com GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
-
8/22/2019 Safie Commissioning
24/31
www.gst.uk.com
BASIC OPERATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
1. System Silence
2. Disable the Alarm
3. Manual Operation of Relay Output
4. History Log
5. Basic Trouble Shooting
-
8/22/2019 Safie Commissioning
25/31
www.gst.uk.com
BASIC OPERATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
Channel StatusNormal Disable NotProgram
FaultFire
Alarm Indicator
Operation
MenuVisual Confirmation
-
8/22/2019 Safie Commissioning
26/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
MUTE
Mute Manual Start and Stop
command of relay output.
Note: by default, relay output 1 is set
to sounder relay (latching), once the
mute pressed it stop.
-
8/22/2019 Safie Commissioning
27/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
DISABLE THE ALARM
Disable to stop detecting fire
even from the display video image
Enable To resume the channel
into operating mode
Pink
Pink
-
8/22/2019 Safie Commissioning
28/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
MANUAL OPERATION OF RELAY OUTPUT
Manual
Manual Start and Stopcommand of relay output.
Note: by default, relay output 1 is
set to sounder relay (Latching) and
relay 16 is set to fault relay.
-
8/22/2019 Safie Commissioning
29/31
www.gst.uk.com
BASIC CONFIGURATION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
HISTORY LOG
Log two types of history log:
Image or Text
-
8/22/2019 Safie Commissioning
30/31
www.gst.uk.com
BASIC TROUBLESHOOTING
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation
No. Fault indication Possible Cause Solution1 Access device failed The address of the relay output card is
incorrect. See , go into the System Settingdialog and press the Read button.
2 Relay Output Card Fault! The driver of the relay output card is notinstalled or incorrect. Reinstall/update the driver.
3 Hardware key not found. The dongle is not connected or thedongle driver is installed incorrect. Check the parallel port connection ofthe PC or reinstall/update the dongle
driver.
4 The number of the video channels isreduced.
The PCI slot is loose or the incorrect
installation of the driver.Make sure the connection is good or
reinstall/update the driver.5 Not enough virtual memory for video card,
please reset it! The memory allocated for the card is toosmall. Go to the path:C:\windows\system32\, and executefile okdevman.exe, select the Buffer
Allocator tag and input the size of the
memory and restart the PC.
-
8/22/2019 Safie Commissioning
31/31
t k
ANSWER AND QUESTION
GST SMOKE AND FLAME INTELLIGENT EYE
SAFIE Commissioning Operation