IM 05P04D41-11EN page 1/10
Contents1. Safety Precautions2. ModelandSuffixCodes3. How to Install4. HardwareSpecifications5. HowtoConnectWires6. TerminalWiringDiagrams
IntroductionThankyouforpurchasingtheUT35A-LDigitalIndicatingController.Thisoperationguidedescribes thebasicoperationsof theUT35A-L.Theguideshouldbeprovidedtotheenduserofthisproduct.Besure to read thisoperationguidebeforeusing theproduct inorder toensurecorrect operation.Fordetailsofeachfunction,refertotheelectronicmanual.Beforeusingtheproduct,refertothetableofModelandSuffixCodestomakesurethatthedeliveredproductisconsistentwiththemodelandsuffixcodesyouordered.Alsomakesurethatthefollowingitemsareincludedinthepackage.
•DigitalIndicatingController(themodelyouordered) ..............................x1• Set of Brackets ........................................................................................x1•UnitLabel(L4502VZ) ..............................................................................x1•TagLabel(L4502VE) ..............................................................................x1(Onlywhenordered.)•OperationGuide(thisdocument) ............................................................x5(A3size)(InstallationandWiring,InitialSettings,Operations,andParameters)
lTargetReadersThisguideisintendedforthefollowingpersonnel;• Engineersresponsibleforinstallation,wiring,andmaintenanceoftheequipment.• Personnelresponsiblefornormaldailyoperationoftheequipment.
1. Safety PrecautionsThefollowingsymbol isusedonthe instrument. It indicatesthepossibilityof injurytotheuserordamagetotheinstrument,andsignifiesthattheusermustrefertotheoperationguideoruser’smanualforspecialinstructions.Thesamesymbolisusedintheoperationguideanduser’smanualonpagesthattheuserneedstoreferto,togetherwiththeterm“WARNING”or“CAUTION.”
WARNING
Calls attention to actions or conditions that could cause serious or fatal injury to the user, and indicates precautions that should be taken to prevent such occurrences.
CAUTION
Calls attention to actions or conditions that could cause injury to the user or damage to the instrument or property and indicates pre-cautions that should be taken to prevent such occurrences.
AC
AC/DC
Theequipmentwhollyprotectedbydoubleinsulationorreinforcedinsulation.
Functionalgroundingterminals (Donotusethisterminalasaprotectivegroundingterminal).
NoteIdentifiesimportantinformationrequiredtooperatetheinstrument.
n Warning and Disclaimer(1)YOKOGAWAmakesnowarrantiesregardingtheproductexceptthosestatedin
theWARRANTYthatisprovidedseparately.(2)Theproductisprovidedonan"asis"basis.YOKOGAWAassumesnoliabilityto
anypersonorentity forany lossordamage,director indirect,arisingfromtheuseoftheproductorfromanyunpredictabledefectoftheproduct.
nSafety,Protection,andModificationoftheProduct(1) Inorder toprotect thesystemcontrolledbythisproductandtheproduct itself,
andtoensuresafeoperation,observethesafetyprecautionsdescribed in theoperationguide.Useof the instrument inamannernotprescribedhereinmaycompromise the product's functions and the protection features inherent in the device.Weassumenoliabilityforsafety,orresponsibilityfortheproduct'squality,performanceorfunctionalityshouldusersfailtoobservetheseinstructionswhenoperatingtheproduct.
(2) Installationof protectionand/or safety circuitswith respect toa lightningprotector;protectiveequipmentforthesystemcontrolledbytheproductandtheproductitself;foolprooforfail-safedesignofaprocessorlineusingthesystemcontrolledbytheproductortheproductitself;and/orthedesignandinstallationofotherprotectiveandsafetycircuitsaretobeappropriatelyimplementedasthecustomer deems necessary.
(3)BesuretousethesparepartsapprovedbyYOKOGAWAwhenreplacingpartsorconsumables.
(4)Thisproduct isnotdesignedormanufacturedtobeusedincriticalapplicationsthatdirectlyaffector threatenhuman lives.Suchapplications includenuclearpower equipment, devices using radioactivity, railway facilities, aviationequipment,airnavigation facilities,aviation facilities,andmedicalequipment.If soused, it is theuser’s responsibility to include in thesystemadditionalequipmentanddevicesthatensurepersonnelsafety.
(5)Modificationoftheproductisstrictlyprohibited.(6)Thisproduct is intendedtobehandledbyskilled/trainedpersonnel forelectric
devices.(7)ThisproductisULRecognizedComponent.InordertocomplywithULstandards,
end-productsarenecessarytobedesignedbythosewhohaveknowledgeoftherequirements.
WARNING
lPower Supply Ensure that the instrument’s supply voltage matches the voltage
of the power supply before turning ON the power.l Do Not Use in an Explosive Atmosphere Do not operate the instrument in locations with combustible
or explosive gases or steam. Operation in such environments constitutes an extreme safety hazard. Use of the instrument in environments with high concentrations of corrosive gas (H2S, SOX, etc.) for extended periods of time may cause a failure.
l Do Not Remove Internal Unit The internal unit should not be removed by anyone other than
YOKOGAWA's service personnel. There are dangerous high voltage parts inside. Additionally, do not replace the fuse by yourself.
l Damage to the Protective Construction Operation of the instrument in a manner not specified in the
operation guide may damage its protective construction.
CAUTION
This instrument is an EMC class A product. In a domestic environ-ment this product may cause radio interference in which case the user needs to take adequate measures.
2. ModelandSuffixCodes
n UT35A-L Model Suffixcode Option
code Description
UT35ADigitalIndicatingController (providedwithretransmissionoutput,2DIs,and3DOs)(Powersupply:100-240VAC)
Type1:Basic control
-L Limitcontroltype
Type2:Functions 0 Always"0"
Type3:Opennetworks
0 None
1 RS-485communication(Max.38.4kbps,2-wire/4-wire)
2 Ethernetcommunication(withserialgatewayfunction)Displaylanguage -1 English
Casecolor0 White(Lightgray)1 Black(Lightcharcoalgray)
Fixedcode -00 Always"-00"Optioncodes /DC Powersupply24VAC/DC
n Accessories (sold separately)Thefollowingisanaccessorysoldseparately.
• LL50AParameterSettingSoftwareModel Suffixcode Description
LL50A -00 ParameterSettingSoftware
• TerminalCover Model:UTAP001• User’sManual(A4size) Note:User’sManualcanbedownloadedfromawebsite.URL:http://www.yokogawa.com/ns/ut/im/• Brackets Partnumber:L4502TP(2pcsforupperandlowersides)
3. How to Install
n Installation LocationThe instrument shouldbe installed in indoor locationsmeeting the followingconditions:• Instrumented panel This instrument isdesignedtobemounted inan instrumentedpanel.Mount theinstrumentinalocationwhereitsterminalswillnotinadvertentlybetouched.
• Well ventilated locations Mounttheinstrumentinwellventilatedlocationstopreventtheinstrument’sinter-naltemperaturefromrising.
However,makesurethattheterminalportionsarenotexposedtowind.Exposureto wind may cause the temperature sensor accuracy to deteriorate. To mount mul-tiple indicatingcontrollers,seetheexternaldimensions/panelcutoutdimensionswhich follow. Ifmountingother instrumentsadjacent to the instrument,complywiththesepanelcutoutdimensionstoprovidesufficientclearancebetweentheinstruments.
• Locations with little mechanical vibration Installtheinstrumentinalocationsubjecttolittlemechanicalvibration.• Horizontal location Mounttheinstrumenthorizontallyandensurethatitislevel,withnoinclinationtotherightorleft.
Front panelof controller
Keep this anglewithin 30°
Rear ofcontroller
30°
NoteIf the instrument ismovedfroma locationwith lowtemperatureand lowhumiditytoaplacewithhightemperatureandhighhumidity,or if thetemperaturechangesrapidly,condensationwill result.Moreover, in thecaseof thermocouple inputs,measurementerrorswillresult.Toavoidsuchasituation,leavetheinstrumentinthenewenvironmentunderambientconditionsformorethan1hourpriortousingit.
Donotmounttheinstrumentinthefollowinglocations:• Outdoors• Locations subject to direct sunlight or close to a heater Installtheinstrumentinalocationwithstabletemperaturesthatremainclosetoanaveragetemperatureof23°C.Donotmountitinlocationssubjecttodirectsunlightorclosetoaheater.Doingsoadverselyaffectstheinstrument.
• Locations with substantial amounts of oily fumes, steam, moisture, dust, or corrosive gases
Thepresenceofoily fumes,steam,moisture,dust,orcorrosivegasesadverselyaffectstheinstrument.Donotmounttheinstrumentinlocationssubjecttoanyofthesesubstances.
• Areasnearelectromagneticfieldgeneratingsources Donotplacemagnetsortoolsthatgeneratemagnetismneartheinstrument.Iftheinstrument isusedin locationsclosetoastrongelectromagneticfieldgeneratingsource,themagneticfieldmaycausemeasurementerrors.
• Locationswherethedisplayisdifficulttosee The instrumentusesanLCDfor thedisplayunit,andthiscanbedifficult toseefromextremelyobliqueangles.Mounttheinstrumentinalocationwhereitcanbeseenasmuchaspossiblefromthefront.
• Areasclosetoflammablearticles Absolutelydonotplacetheinstrumentdirectlyonflam-mablesurfaces. Ifsuchacircumstance isunavoidableandtheinstrumentmustbeplacedclosetoaflammableitem,provideashieldforitmadeof1.43mmthickplatedsteel or 1.6 mm thick unplated steel with a space of at least150mmbetweenitandtheinstrumentonthetop,bottom,andsides.
• Areas subject to being splashed with water
WARNING
Be sure to turn OFF the power supply to the controller before in-stalling it on the panel to avoid an electric shock.
150 mm150 mm
150 mm
150 mm
OperationGuideIM 05P04D41-11EN
UT35A-LDigital Indicating Controller (Limit Control Type)Operation Guide
This operation guide describes installation, wiring, and other tasks required to make the controller ready for operation.
2nd Edition : Mar. 2016
Installation and Wiring
www.yokogawa.com/ns
YOKOGAWA ELECTRIC CORPORATIONNetwork Solutions Business Division
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPANYOKOGAWA CORPORATION OF AMERICA
Head office and for product sales2 Dart Road, Newnan, Georgia 30265, USA
YOKOGAWA EUROPE B.V.Headquarters
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
All Rights Reserved, Copyright © 2011 Yokogawa Electric Corporation
IM 05P04D41-11EN page 2/10
n Mounting the Instrument Main UnitProvideaninstrumentedpanelsteelsheetof1to10mmthickness.Afteropeningthemountingholeonthepanel,followtheproceduresbelowtoinstallthecontroller:1) Insert thecontroller into theopening from the frontof thepanelso that the
terminalboardontherearisatthefarside.2) Setthebracketsinplaceonthetopandbottomofthecontrollerasshowninthe
figurebelow,thentightenthescrewsofthebrackets.Takecarenottoovertightenthem.
Bracket(top mounting hardware)
Terminal board
Bracket(bottom mounting hardware)
Panel
Insert a screwdriver into thebrackets to tighten the screws.
Direction to insert thecontroller
Appropriatetightening torque:0.25 N•m
Insert the controllerinto the opening atthe front of the panel.
CAUTION
• Tighten the screws with appropriate tightening torque within 0.25 N•m. Otherwise it may cause the case deformation or the bracket damage.
• Make sure that foreign materials do not enter the inside of the instrument through the case’s slit holes.
n External Dimensions and Panel Cutout Dimensions
(25)
(53) (2.09)
[(N-1)×96+92]117 (4.61) min.
145 (5.71)min.
+0.80
+0.8092
“N” stands for the number of controllers to beinstalled.However, the measured value applies if N≥5.
65 (2.56)
20 (0.79)
11(0.43)
UT35A-L
1 to 10 mm (0.04 to 0.39 inch) (panel thickness)Bracket
Bracket
94.6
(3.7
2)
91.6
(3.6
1)
105.
2 (4
.14)
Unit: mm (approx. inch)96 (3.78)
96 (3
.78)
• General mounting • Side-by-side close mounting
Terminal cover
Normal tolerance: ±(value of JIS B 0401-1998 tolerance class IT18)/2
+0.8092
+0.030(3.62 )
(0.98)+0.030(3.62 )
+0.8092
+0.030(3.62 )
([(N-1)×3.78+3.62] )+0.030
4. HardwareSpecifications
WARNING
This instrument is for Measurement Category No.1.Do not use it for measurements in locations falling under Measure-ment Categories No.2, No.3, and No.4.
Internal Wiring
Outlet
Entrance IVCable
III TO( I )
II
Category IEC/EN/CSA/UL 61010-1 EN 61010-2-030 Remarks
No.1 Measurement CategoryI O(Other) For measurements performed on circuits not
directlyconnectedtoMAINS.
No.2 Measurement CategoryII
Measurement CategoryII
For measurements performed on circuits directly connectedtothelow-voltageinstallation.
No.3 Measurement CategoryIII
Measurement CategoryIII
Formeasurementsperformedinthebuildinginstal-lation.
No.4 Measurement CategoryIV
Measurement CategoryIV
For measurements performed at the source of the low-voltageinstallation.
n InputSpecifications
UniversalInput(Equippedasstandard)• Numberofinputs:1• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow,
Input Type Instrument Range
AccuracyºC ºF
Thermo-couple
K-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±2%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleK±1%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleT
-270.0to1000.0ºC -450.0to2300.0ºF-200.0to500.0ºC -200.0to1000.0ºF
J -200.0to1200.0ºC -300.0to2300.0ºF
T-270.0to400.0ºC -450.0to750.0ºF
0.0to400.0ºC -200.0to750.0ºF
B 0.0to1800.0ºC 32to3300ºF
±0.15%ofinstrumentrange±1digitfor400°Cormore ±5%ofinstrumentrange±1digitforlessthan400°C
S 0.0to1700.0ºC 32to3100ºF±0.15%ofinstrumentrange±1digit
R 0.0to1700.0ºC 32to3100ºF
N -200.0to1300.0ºC -300.0to2400.0ºF±0.1%ofinstrumentrange±1digit±0.25%ofinstrumentrange±1digitforlessthan0°C
E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±1.5%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleE.
L -200.0to900.0ºC -300.0to1600.0ºF
U-200.0to400.0ºC -300.0to750.0ºF
0.0to400.0ºC -200.0to1000.0ºF
W 0.0to2300.0ºC 32to4200ºF ±0.2%ofinstrumentrange±1digit(Note2)
Platinel 2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit
PR20-40 0.0to1900.0ºC 32to3400ºF
±0.5%ofinstrumentrange±1digitfor800°Cormore Accuracyisnotguaranteedforlessthan800°C.
W97Re3-W75Re25 0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit
RTD
JPt100-200.0to500.0ºC -300.0to1000.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Pt100-200.0to850.0ºC -300.0to1560.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)-200.0to500.0ºC -300.0to1000.0ºF-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Standardsignal0.400to2.000V
±0.1%ofinstrumentrange±1digit
1.000to5.000V4.00to20.00mA
DCvoltage/current
0.000to2.000V0.00to10.00V0.00to20.00mA-10.00to20.00mV0.0to100.0mV
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpowerfrequencyat50/60Hz.
Note1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherange between-100and200°C.
Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988
•Inputsampling(control)period:200ms•Burnoutdetection: FunctionsatTC,RTD,andstandardsignal. Upscale,downscale,andoffcanbespecified. Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4 mAorless.
•Inputbiascurrent:0.05µA(forTCorRTD)•Measuredcurrent(RTD):About0.16mA•Inputresistance: TCormVinput:1MΩormore Vinput:About1MΩ mAinput:About250Ω•Allowablesignalsourceresistance: TCormVinput:250Ωorless Effectsofsignalsourceresistance:0.1µV/Ωorless DCvoltageinput:2kΩorless Effectsofsignalsourceresistance:About0.01%/100Ω• Allowablewiringresistance: RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewires shallbeequal.)
Wiringresistanceeffect:±0.1ºC/10Ω• Allowableinputvoltage/current: TC,mV,mAandRTDinput:±10VDC Vinput:±20VDC mAinput:±40mA• Noiserejectionratio: Normalmode:40dBormore(at50/60Hz) Commonmode:120dBormore(at50/60Hz) For100-240VAC, thepower frequencycanbesetmanually.Automatic detectionisalsoavailable.
For24VAC/DC,thepowerfrequencycanbesetmanually.• Referencejunctioncompensationerror: ±1.0ºC(15to35ºC) ±1.5ºC(-10to15ºCand35to50ºC)• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD
nStepResponseTimeSpecificationsWithin1s(63%ofanalogoutputresponsetimewhenastepchangeof10to90%ofinputspanisapplied)
nRelayContactOutputSpecifications• Contacttypeandnumberofoutputs: Limitcontroloutput:contactpoint1c;1point Alarmoutput:contactpoint1a;3points(commonisindependent)• Contactrating: Contactpoint1c(limitcontroloutput):250VAC,3Aor30VDC,3A(resistanceload) Contactpoint1a(alarmoutput):240VAC,1Aor30VDC,1A(resistanceload)• Use:Alarmoutput,FAILoutput,etc.• Timeresolutionoflimitcontroloutput:10msor0.1%ofoutput,whicheverislargerNote:Thecontroloutputshouldalwaysbeusedwithaloadof10mAormore. Thealarmoutputshouldalwaysbeusedwithaloadof1mAormore.
n RetransmissionOutputSpecifications• Numberofoutputs:Retransmissionoutput;1• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless• Currentoutputaccuracy(conversionaccuracyfromPVdisplayonthesetscale):±0.1%ofspan(±5%ofspanfor1mAorless)
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH, andpowerfrequencyat50/60Hz. This isnotconversionaccuracythroughinputandoutputbut theperformanceof
transmission output itself.
nContactInputSpecifications• Numberofinputs:2points• Inputtype:No-voltagecontactinputortransistorcontactinput• Inputcontactrating:12VDC,10mAormore Useacontactwithaminimumon-currentof1mAorless.• ON/OFFdetection: No-voltagecontactinput: Contactresistanceof1kΩorlessisdeterminedas“ON”andcontact resistanceof50kΩormoreas“OFF.” Transistorcontactinput: Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmust notexceed100µAwhen“OFF.”• Minimumstatusdetectionholdtime:Controlperiod+50ms• Use:Confirmationoperation,etc.
SafetyandEMCStandards• Safety: CompliantwithIEC/EN61010-1(CE),IEC/EN61010-2-201(CE),IEC/EN61010-2-030(CE),approvedbyCAN/CSAC22.2No.61010-1(CSA),approvedbyUL61010-1.
CertifiedforFM-3810andFM-3545. Installationcategory:II Pollutiondegree:2 Measurementcategory:I(CATI)(UL,CSA) O(Other)(CE) Ratedmeasurementinputvoltage:Max.10VDC Ratedtransientovervoltage:1500V(*) *ThisisareferencesafetystandardvalueformeasurementcategoryIofCSA/UL61010-
1,andformeasurementcategoryOofIEC/EN61010-2-030.Thisvalueisnotnecessarilyaguaranteeofinstrumentperformance.
• EMCstandards: CompliantwithCEmarking EN61326-1ClassA,Table2(Foruseinindustriallocations), EN61326-2-3 *Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%ofthe
rangeduringtesting. EN55011ClassA,Group1 EN61000-3-2ClassA EN61000-3-3 EMCRegulatoryArrangementinAustraliaandNewZealand(forallmodelinclud-
ingLL50A) EN55011ClassA,Group1• KCmarking: Electromagneticwave interferencepreventionstandard,electromagneticwave
protection standard compliance
Construction,Installation,andWiring• DegreeofprotectionprovidedbyEnclosure: IP66(for frontpanel)(Notavailableforside-by-sideclosemounting.)
• Material:Polycarbonate(Flameretardancy:UL94V-0)• Casecolor:White(Lightgray)orBlack(Lightcharcoalgray)• Weight:0.5kgorless• Externaldimensions(mm):96(W)×96(H)×65(depthfromthepanelface) (Depthexcepttheprojectionontherearpanel)• Installation:Directpanelmounting;mountingbracket,oneeach forupperandlowermounting
• Panelcutoutdimensions(mm):92+0.8/0(W)×92+0.8/0(H)• Mountingattitude:Upto30degreesabovethehorizontal.Nodownwardtitlingallowed.• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)
PowerSupplySpecificationsandIsolation• Powersupply: Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz 24VAC/DC(+10%/-15%)(for/DCoption)• Powerconsumption:18VA(DC:9VA,AC:14VAif/DCoptionisspecified)• Databackup:Nonvolatilememory• Powerholduptime:20ms(for100VACdrive)• Withstandingvoltage Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute(UL,CSA) Betweenprimaryterminalsandsecondaryterminals:3000VACfor1minute(CE) Betweenprimaryterminals:1500VACfor1minute Betweensecondaryterminals:500VACfor1minute (Primaryterminals:Power*andrelayoutputterminals;Secondaryterminals: AnalogI/Osignalterminals,contactinputterminals,communicationterminals andfunctionalgroundingterminals.)
*:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.• Insulationresistance:Betweenpowersupplyterminalsandagroundingterminal20MΩormoreat500VDC
• Isolationspecifications
PV (universal) input terminals
Control relay (contact point c) output terminals
Alarm-1 relay (contact point a) output terminals
Alarm-2 relay (contact point a) output terminals
Alarm-3 relay (contact point a) output terminals
Contact input terminalsRS-485 communication terminals
Ethernet communication terminal
Retransmission (analog) output terminals
Internalcircuits
Powersupply
The circuits divided by lines are insulated mutually.
EnvironmentalConditions
Normal Operating Conditions:• Ambienttemperature:-10to50ºC(-10to40ºCforside-by-sideclosemounting)• Ambienthumidity:20to90%RH(nocondensationallowed)• Magneticfield:400A/morless• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90minuteseachinthethreeaxisdirections
Continuousvibrationat9to150Hz:4.9m/s2orless,1oct/minfor90minuteseachinthethreeaxisdirections
• Short-periodvibration:14.7m/s2, 15 seconds or less• Shock:98m/s2 or less, 11 ms• Altitude:2000morlessabovesealevel• Warm-uptime:30minutesormoreafterthepoweristurnedon• Startuptime:Within10seconds *: TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.
TheLCDhasacharacteristicthatthedisplayactionbecomeslateatthelow temperature.However,thecontrolfunctionisnotaffected.
Transportation and Storage Conditions:• Temperature:-25to70ºC• Temperaturechangerate:20ºC/horless• Humidity:5to95%RH(nocondensationallowed)
Effects of Operating Conditions• Effectofambienttemperature: VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger Currentinput:±0.01%ofF.S./ºC RTDinput:±0.05ºC/ºC(ambienttemperature)orless Analogoutput:±0.02%ofF.S./ºCorless• Effectofpowersupplyvoltagefluctuation Analoginput:±0.05%ofF.S.orless Analogoutput:±0.05%ofF.S.orless (Eachwithinratedvoltagerange)
IM 05P04D41-11EN page 3/10
5. How to Connect Wires
WARNING
• Wiring work must be carried out by a person with basic electrical knowledge and practical experience.
• Be sure to turn OFF the power supply to the controller before wiring to avoid an electric shock. Use a tester or similar device to ensure that no power is being supplied to a cable to be connected.
• For the wiring cable, the temperature rating is 75 °C or more.• As a safety measure, always install a circuit breaker (an IEC
60947-compatible product, 5 A, 100 V or 220 V AC) in an easily accessible location near the instrument. Moreover, provide indication that the switch is a device for turning off the power to the instrument.
• Install the power cable keeping a distance of more than 1 cm from other signal wires.
• The power cable is required to meet the IEC standards concerned or the requirements of the area in which the instrument is being installed.
• Wiring should be installed to conform to NEC (National Electrical Code: ANSI/NFPA-70) or the wiring construction standards in countries or regions where wiring will be installed.
• Since the insulation provided to each relay output terminal is Functional insulation, provide Reinforced insulation to the external of the device as necessary. (Refer to the drawing below.)
This product
Functional insulation
A safety voltage circuit
A safety voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional insulation
A hazardous voltage circuit
A hazardous voltage circuit
A safety voltage circuit
A safety voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional insulation
A hazardous voltage circuit
A hazardous voltage circuit
A hazardous voltage circuit
A hazardous voltage circuit
CAUTION
• When connecting two or more crimp-on terminal lugs to the single terminal block, bend the crimp-on terminal lugs before tightening the screw.
• Note that the wiring of two or more crimp-on terminal lugs to the single high-voltage terminal of the power supply and relay, etc. does not comply with the safety standard.
CAUTION
• Provide electricity from a single-phase power supply. If the power is noisy, install an isolation transformer on the primary side, and use a line filter on the secondary side. When measures against noise are taken, do not install the primary and secondary power cables close to each other.
• If there is a risk of external lightning surges, use a lightning arrester etc.
• For TC input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires.
• Since the limit control output relay has a life span (resistance load of 100,000 times), use the auxiliary relay to perform ON/OFF control.
• The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as a spark-removal surge suppression circuit, into the line in parallel with the load.
• After completing the wiring, the terminal cover is recommended to use for the instrument.
RecommendedCrimp-onTerminalLugs
(A)
(F)
(ød)
5.5 3.3
Recommendedtighteningtorque:0.6N·m Applicablewiresize:Powersupplywiring1.25mm2 or moreApplicable terminal lug Applicable wire size mm2 (AWG#) (φd) (A) (F)M3 0.25to1.65(22to16) 3.3 5.5 4.2
CableSpecificationsandRecommendedCablesPurpose Name and Manufacturer
Power supply, relay contact outputs 600VGradeheat-resistantPVCinsulatedwires,JISC3317(HIV),0.9to2.0mm2
Thermocouple Shieldedcompensatingleadwires,JISC1610Forthermocoupleinput(PVinputandremoteinputwithdirectinput),shieldedcompensatingleadwireofcross-sectionalarealessthanorequalto0.75mm2isrecommended.Ifthecross-sectionalareaiswide,thereferencejunctioncompensationerrormaybelarge.
RTD Shieldedwires(three/fourconductors),UL2482(HitachiCable)Othersignals(otherthancontactinput/output) Shielded wiresOthersignals(contactinput/output) UnshieldedwiresRS-485communication Shielded wiresEthernetcommunication 100BASE-TX(CAT-5)/10BASE-T
DC Relay Wiring
R
External DC power supplyRelayUT35A-L
UT’s contact
Diode(Mount it directlyto the relay coilterminal (socket).)
Relay(Use one with a relay coil rating
less than the UT’s contact rating.)
AC Relay Wiring
UT35A-L
R
UT’s contact CR filter(Mount it directlyto the relay coilterminal (socket).)
External AC power supply
Relay(Use one with a relay coilrating less than the UT’s
contact rating.)
6. Terminal Wiring Diagrams
CAUTION
• Do not use an unassigned terminal as the relay terminal. Do not use a 100-240 V AC power supply for the 24 V AC/DC
model; otherwise, the instrument will malfunction.
UT35A-L
E3-terminal area
PVPV inputTC input RTD input
Voltage (mV, V) input
A
+
-
+
-
Current (mA) input
+
-
B
b
(24 V AC/DC power supply: Option code /DC)
(Equippedas standard)
Power supply
101
102
103
104
105
106
107
108
109
110
111
407
401
408
409
410
411
412
201
202
203
204
207
208
205
206
210
211
212
101-112
501-512
401-412
301-306
201-212
ALM (Equipped as standard)Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load)
Alarm-3 output(PV high limit)
Alarm-2 output( PV low limit)
Alarm-1 output(PV high limit)
Common
Common
Common
UT104
105
106
107
108
109
100-240 V AC power supply
N
L
Allowable range: 100-240VAC (+10%/-15%) (free voltage) 50/60 Hz shared
110
111
24 V AC/DC power supply
-
+
110
111
202
203
201
202
203
202
203
203
204
Factory default: PV input type is undefined.
(Equipped as standard)OUTLimit control output
101
102
Relay contact output
103
NC
NO
COM
Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)
RETRetransmission output
4-20 mA DC or0-20 mA DC
+
-
Default: 4-20 mA DC
Default: PV retransmission
Load resistance 600 Ω or less
Retransmission output (Equipped as standard)
207
208
DI (Equipped as standard)Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI2
DI1
COM
Factory default: No function
RESET when DI=ON(However, setup parameter CNF=DI)
Common
DI2
DI1
COM
+5V
+5V
No-voltagecontact
Transistor contactUT UT
210
211
212
210
211
212
Function can be assigned to the terminals with no function.
112
112 112
N
L
Wiring direction
RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS-485 communication(Suffix code: Type 3=1)
407
408
409
410
411
RS485
(Suffix code: Type 3=2)
Ethernet communication (with gateway function)
10BASE-T/100BASE-TXRJ45 connector
ColorLitUnlit
Amber100M bps10M bps
Green
LinkedActiveLink failure
Color
LitBlinkUnlit
Upper side LED (baud rate)
Lower side LED (link activity)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
ETHR
401-412
Do not use.
IM 05P04D41-11EN page 4/10
Intentionallyblank
IM 05P04D41-11EN page 5/10
Contents1. NamesandFunctionsofDisplayParts2. Setup Procedure3. QuickSettingFunction4. SettingLimitControlType5. SettingAlarmType6. SettingAlarmSetpoint
1. Names and Functions of Display Parts
(1)
(2)
(10)
(4)
(8)
(9)(13)(12)
(11)
(3) (6)(7)(5)
(14)
(15)(16)
No.infigure Name Description
(1) PVdisplay (whiteorred)
DisplaysPV.Displaysanerrorcodeifanerroroccurs.DisplaysthescrollingguideintheMenuDisplayandParameterSettingDisplaywhentheguidedisplayON/OFFissettoON.
(2) Groupdisplay(green) Displaysterminalarea(E3).E3isdisplayedintheParameterSettingDisplay.
(3) Symboldisplay(orange) Displaysaparametersymbol.(4) Datadisplay(orange) Displaysaparametersetpointandmenusymbol.
(5) EXCEEDEDindicator(red)
LighttoindicatetheexceededstatusofPV.LightswhilePVexceedsSP.
(6) OUTindicator (orange)
Lighttoindicatetheoutputstatus.LightswhiletherelayoutputisOFF.
(7) Eventindicator (orange)
Litwhenthealarms1to3occur.Eventdisplaysotherthanalarmscanbesetbytheparameter.
(8) Keynavigationindica-tor(green)
LitorblinkswhentheUp/DownorLeft/Rightarrowkeyoperationispossible.
(9) Parameterdisplaylevelindicator(green)
Displaysthesettingconditionsoftheparameterdisplaylevelfunc-tion.
Parameter display level EASY PROEasysettingmode Lit UnlitStandardsettingmode Unlit UnlitProfessionalsettingmode Unlit Lit
(10) Securityindicator(red) Litifapasswordisset.Thesetupparametersettingsarelocked.
(11) DISPLAYkey
UsedtoswitchtheOperationDisplays.PressthekeyintheOperationDisplaytoswitchtheprovidedOperationDisplays.PressthekeyintheMenuDisplayorParameterSettingDisplaytoreturntotheOperationDisplay.
(12) PARAMETERkey
Holddownthekeyfor3secondstomovetotheOperationParameterSettingDisplay.HolddownthekeyandtheLeftarrowkeysimultaneouslyfor3secondstomovetotheSetupParameterSettingDisplay.PressthekeyintheParameterSettingDisplaytoreturntotheMenuDisplay.Pressthekeyoncetocanceltheparameterset-ting(setpointisblinking).
(13)SET/ENTERkeyUp/Down/Left/Rightarrow keys
SET/ENTERkeyPressthekeyintheMenuDisplaytomovetotheParameterSettingDisplayoftheMenu.PressthekeyintheParameterSettingDisplaytotransfertotheparametersettingmode(setpointisblinking),andtheparametercanbechanged.Pressthekeyduringparametersettingmodetoregisterthe setpoint.Up/Down/Left/RightarrowkeysPresstheLeft/RightarrowkeysintheMenuDisplaytoswitchtheDisplays.PresstheUp/Down/Left/RightarrowkeysintheParameterSettingDisplaytoswitchtheDisplays.PresstheUp/Downarrowkeysduringparametersettingmode(setpointisblinking)tochangeasetpoint.PresstheLeft/Rightarrowkeysduringparametersettingmode (setpointisblinking)tomovebetweendigitsaccordingtotheparameter.
(14) Light-loaderinterfaceItisthecommunicationinterfacefortheadaptercableusedwhensettingandstoringparametersfromaPC.TheLL50AParameterSettingSoftware(soldseparately)isrequired.
(15) RSTkey Usedtoconfirmandresetthelimitoutputandrelatedparam-eters.
(16) Userfunctionkeys Theusercanassignafunctiontothekey.Thefunctionissetbythe parameter.
Note: Thecommunicationconnector(maintenanceport)forLL50AParameterSettingSoftwareison the top of the unit.
2. Setup ProcedureThefollowingflowchartshowsthesetupprocedureforUT35A-L.
Install and wire a controller.
Monitoring and control of regular operations
Other setup
Operation
NO
YES
Set the other parameters as needed.
Alarm setup Set the alarm parameters as needed.
Input setup
Installationand wiring
Power ON
Limit Control type setup
Limit control type setupInput setup
UseQuick setting
function?
OperationGuide
Initial Settings
UT35A-LDigital Indicating Controller (Limit Control Type)Operation Guide
This operation guide describes basic settings and operations of the UT35A-L.For details of each function, see the electronic manual.The scrolling guide is displayed on PV display in the Parameter Setting Display.This guide can be turned on/off with the Fn key.
3. Quick Setting FunctionTheQuicksettingfunctionisafunctiontoeasilysetthebasicfunctionofthecontrol-ler.TurnonthecontrollertostarttheQuicksettingfunction.Thisfunctionallowsyoutoeasilysetthelimitcontroltypeandinput,andquicklystartthe control action.Theitems(parameters)tobesetbyQuicksettingfunctionareasfollows.(1)Limitcontroltype(Highlimitcontrolorlowlimitcontrol)(2)Inputfunction(PVinputtype,range,scale(atvoltageinput),etc.)
Afterturningonthecontroller,firstdecidewhetherornottousetheQuicksettingfunc-tion.
Operation in Initial Display· PresstheSET/ENTERkeywhileYESisdisplayedtostarttheQuicksettingfunction.· IfyouchangeYEStoNOandpresstheSET/ENTERkey,OperationDisplaywillappearwithoutstartingtheQuicksettingfunction.
Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.
· Tochangeandset theparametersetting,presstheSET/ENTERkeytostart thesetpointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeys tochangethesetpoint.Press theSET/ENTERkeytoregisterthesetting.
Making Settings Using Quick Setting FunctionExample: Setting to the low limit control type and the thermocouple type K
(range of 0.0 to 500.00F)Forthedetailedprocedureandswitchingofdisplays,see"FlowofQuickSettingFunction"below.Fortheparameterstoset,seethenextcolum.
(1)PresstheSET/ENTERkeywhileYESforQSM(Quicksettingmode)isdisplayed.(2)Setthelimitcontroltypeparameter(HI.LO)toLOW(Lowlimitcontrol).(3)SetthePVinputtypeparameter(IN)toK1(-450.0to2500.00F).(4)SetthePVinputunitparameter(UNIT)toF(DegreeFahrenheit).(5)SetthemaximumvalueofPVinputrangeparameter(RH)to500.0.(6)SettheminimumvalueofPVinputrangeparameter(RL)to0.0.(7)Finally,EXITisdisplayed.ChangeNOtoYESandpresstheSET/ENTERkeyto
completethesetup.OperationDisplayappears.
FlowofQuickSettingFunctionInQuicksettingmode,theparameterguideappearsonPVdisplay.Thisguidecanbeturnedon/offwiththeFnkey.
Press the SET/ENTER key while YES is displayed to start the Quick setting.
[NO]
Select NO with the Down arrow key and press the SET/ENTER key.
Select NO to return to the Operation Display.
Power-on
The PV input type parameter (IN) is displayed.Initial value: OFF
Press the SET/ENTER key.
Press the SET/ENTER key.
OFF blinks.Blinking allows you to change the setting.
HIGH blinks.Blinking allows you to change the setting.
Press the Up arrow key.
K1 is displayed.
LOW is displayed.
K1 has been registered.
LOW has been registered.
Press the SET/ENTER key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
[YES]
1.
6.
7.
8.
9.
Quick setting starts
The limit control type parameter (HI.LO) is displayed.Initial value: HIGH
Press the SET/ENTER key.
2.
3.
4.
5.
The last digit of the upper limit value blinks.
The parameter RH (maximum value of PV input range) has been changed to 500.0.
The setpoint for the parameter RH has been registered.
Press the Down arrow key.
Operation Display
11.
12.
13.
14.
15.
The PV input unit parameter (UNIT) is displayed.Initial value: F (Degree Fahrenheit)
10.
Press the Down arrow key.
Follow the same procedure to set RL to 0.0.Set other parameters as needed.
Displays the measured input value (PV).Displays the target setpoint (SP).
Finally, EXIT is displayed.Press the SET/ENTER key to swtich to the setting mode.Change NO to YES and press the SET/ENTER key to complete the setup of the basic function.Operation Display appears.The Quick setting function continues in the NO state.
The upper limit value of the setting range is displayed for the parameter RH (maximum value of PV input range).
Press the SET/ENTER key.
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Press the SET/ENTER key while YES is displayed to start the Quick setting.
[NO]
Select NO with the Down arrow key and press the SET/ENTER key.
Select NO to return to the Operation Display.
Power-on
The PV input type parameter (IN) is displayed.Initial value: OFF
Press the SET/ENTER key.
Press the SET/ENTER key.
OFF blinks.Blinking allows you to change the setting.
HIGH blinks.Blinking allows you to change the setting.
Press the Up arrow key.
K1 is displayed.
LOW is displayed.
K1 has been registered.
LOW has been registered.
Press the SET/ENTER key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
[YES]
1.
6.
7.
8.
9.
Quick setting starts
The limit control type parameter (HI.LO) is displayed.Initial value: HIGH
Press the SET/ENTER key.
2.
3.
4.
5.
The last digit of the upper limit value blinks.
The parameter RH (maximum value of PV input range) has been changed to 500.0.
The setpoint for the parameter RH has been registered.
Press the Down arrow key.
Operation Display
11.
12.
13.
14.
15.
The PV input unit parameter (UNIT) is displayed.Initial value: F (Degree Fahrenheit)
10.
Press the Down arrow key.
Follow the same procedure to set RL to 0.0.Set other parameters as needed.
Displays the measured input value (PV).Displays the target setpoint (SP).
Finally, EXIT is displayed.Press the SET/ENTER key to swtich to the setting mode.Change NO to YES and press the SET/ENTER key to complete the setup of the basic function.Operation Display appears.The Quick setting function continues in the NO state.
The upper limit value of the setting range is displayed for the parameter RH (maximum value of PV input range).
Press the SET/ENTER key.
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Parameterstobeset
Limit Control Function
Parameter Symbol Name of Parameter Setting Range
HI.LO Limitcontroltype LOW:LowlimitcontrolHIGH:Highlimitcontrol
Input FunctionParameter Symbol Name of Parameter Setting Range
IN PVinputtype
OFF:DisableK1:-270.0to1370.00C/-450.0to2500.0 0FK2:-270.0to1000.00C/-450.0to2300.0 0FK3:-200.0to500.00C/-200.0to1000.0 0FJ:-200.0to1200.00C/-300.0to2300.0 0FT1:-270.0to400.00C/-450.0to750.0 0FT2:0.0to400.00C/-200.0to750.0 0FB:0.0to1800.00C/32to3300 0FS:0.0to1700.00C/32to3100 0FR:0.0to1700.00C/32to3100 0FN:-200.0to1300.00C/-300.0to2400.0 0FE:-270.0to1000.00C/-450.0to1800.0 0FL:-200.0to900.00C/-300.0to1600.0 0FU1:-200.0to400.00C/-300.0to750.0 0FU2:0.0to400.00C/-200.0to1000.0 0FW:0.0to2300.00C/32to4200 0FPL2:0.0to1390.00C/32.0to2500.0 0FP2040:0.0to1900.00C/32to3400 0FWRE:0.0to2000.00C/32to3600 0FJPT1:-200.0to500.00C/-300.0to1000.0 0FJPT2:-150.00to150.000C/-200.0to300.0 0FPT1:-200.0to850.00C/-300.0to1560.0 0FPT2:-200.0to500.00C/-300.0to1000.0 0FPT3:-150.00to150.000C/-200.0to300.0 0F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV
UNIT PVinputunit -:Nounit,C:DegreeCelsius-:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit
RH MaximumvalueofPVinputrange
Dependsontheinputtype.-Fortemperatureinput-Setthetemperaturerangethatisactuallycontrolled.(RL<RH)-Forvoltage/currentinput-Settherangeofavoltage/currentsignalthatisapplied.Thescaleacrosswhichthevoltage/currentsignalisactuallycontrolledshouldbesetusingthemaximumvalueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)
RL MinimumvalueofPVinputrange
SDPPVinputscaledecimal point position
0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces
3:Threedecimalplaces4:Fourdecimalplaces
SH MaximumvalueofPVinputscale
-19999to30000,(SL<SH),|SH-SL|≤30000SL Minimumvalueof
PVinputscale
Note1:SDP,SH,andSLaredisplayedonlyforvoltage/currentinput.Note2:W:W-5%Re/W-26%Re(HoskinsMfg.Co.),ASTME988
IM 05P04D41-11EN page 6/10
4. Setting Limit Control TypeThefollowingoperatingproceduredescribesanexampleofchanging limitcontroltype(factory-setdefault:highlimittype)tolowlimittype.
CTL menu is displayed.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the Dwon arrow key.
Hold down the keys for 3 seconds.+
Show the Operation Display.
HIGH blinks.
Press the SET/ENTER key.
1.
2.
4.
5.
6.
7.
* When a password is set, PASS is displayed. If the correct password is not entered, setup parameters cannot be changed.
The parameter HI.LO (limit control type) is displayed.
LOW is displayed.Blinks during the change.
The setpoint has been registered.After the adjustment is completed, press the DISPLAY key once to return to the Operation Display.
5. Setting Alarm TypeThefollowingoperatingprocedureshowsanexampleofchangingthealarm-1type(factorydefault:PVhighlimitalarm)toPVlowlimitalarm(setpoint:02).
SP menu is displayed.
Press the Right arrow key until ALRM menu appears.
Press the SET/ENTER key.
Press the SET/ENTER key.
Hold down the key for 3 seconds.
Show the Operation Display.
ALRM menu is displayed.
Press the SET/ENTER key.
1.
2.
3.
4.
5.
6.
Energized/De-energizedLatch action
Stand-by action
The alarm-1 type setpoint 02 (PV low limit)is registered.After the setup is completed, press the DISPLAY key or DISP key once to return to the Operation Display.
Symbol
To change the alarm type, change the last 2 digits of the 5-digit value. Stand-by action and excitation are turned on or off by selecting 1 or 0. (See “ Setting Display of Alarm Type.”) For the latch action, see User ’s Manual.
The parameter AL1 (alarm-1 type) is displayed.
The last digit of the setpoint blinks.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Hysteresis
Alarm setpoint PV
SP or Target SP
Hysteresis
PV Deviation setpoint
SP or Target SP
Deviation setpoint
PV
Hysteresis Hysteresis
Open (unlit)
Closed (lit)
SP or Target SPPVDeviation setpoint
Hysteresis
- -
SP or Target SP
PV
Hysteresis Hysteresis
Deviation setpoint
Open (unlit)
Alarm setpoint
Hysteresis
PV
Hysteresis
Alarm setpoint PV
SP or Target SP
Hysteresis
PV Deviation setpoint
SP or Target SP
Deviation setpoint
PV
Hysteresis Hysteresis
SP or Target SPPVDeviation setpoint
Hysteresis
SP or Target SP
PV
Hysteresis Hysteresis
Deviation setpoint
Closed (unlit)
Alarm setpoint
Hysteresis
PV
No alarm (00)
Alarm Action (De-energized)
PV high limit (01)
PV low limit (02)
Deviation high limit (05)
Deviation low limit (06)
Deviation high and low limits (07)
Deviation within high and low limits (08)
PV velocity (29)
Fault diagnosis alarm (30)
FAIL (31)
Alarm Type (Alarm Setpoint) Alarm Action (Energized)
Open (unlit)
Open (lit)
Closed (unlit)
Closed (unlit)
Open (lit)
Open (lit)Closed
(lit)Closed
(lit)
Closed (lit)
Closed (lit)
Closed (lit)
Closed (lit)
Open (unlit)
Open (unlit)
Open (unlit)
Open (unlit)
Open (lit)
Open (lit)
Open (lit)
Open (lit)
Closed (unlit)
Closed (unlit)
Closed (unlit)
Closed (unlit)
Burnout of PV input, ADC failure, RJC error.
For the factory default, the contact output is turned ON in normal operation, OFF at the time of FAIL. Limit control output: OFF or 0%, Alarm output: OFF
Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.Note 2: Positive setpoint, Negative setpoint
Setting Display of Alarm Type Stand-by Action
Energized (0) / De-energized (1)
Alarm typeWithout (0) or With (1) Stand-by action
Latch action (0/1/2/3/4)See User’s Manual.
PV low limit alarm setpoint
Treatedas normal
ºC
Power-on Time
The alarm output does not turn onin this region even if the PV valuleis below PV low limit alarm setpoint.
Normal Abnormal
The alarm outputturns on.
6. Setting Alarm SetpointThefollowingoperatingprocedureshowsanexampleofsettingthealarm-1setpointofgroup1to180.0.Beforesettingthealarmsetpoint,checkthealarmtype.Tochangethealarmtype,see“5.SettingAlarmType.”
Press the SET/ENTER key.
Blinks during the change.
The setpoint has been registered.After the setup is completed, press the DISPLAY key once to return to the Operation Display.
Press the SET/ENTER key.
Press the Down arrow key until A1 appears.
Press the SET/ENTER key.
3.
4.
5.
The parameter A1 is displayed.A1 to A3 represent the alarm-1 to -3 setpoints.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
SP menu is displayed.
Hold down the key for 3 seconds.
Show the Operation Display.
1.
2.
IM 05P04D41-11EN page 7/10
Contents1. Monitoring-purposeOperationDisplaysAvailableduringOperation2. SettingTargetSetpoint(SP)3. ConfirmationoftheLimitOutput4. OperationinConfirmationDisplay5. Troubleshooting6. DescriptionofLimitControlFunctions7. ParametersintheConfirmationDIsplays8. FunctionBlockDiaram
1. Monitoring-purpose Operation Displays Available during Operation Operation Display Switching Diagram
PV Display(SP can be changed.)
PV Display(SP can be changed.)
SP Display(SP can be changed.)
SP Display(SP can be changed.)
Duration Time Display
Maximum Value Display Minimum Value Display
When setup parameter HOME is set to PV1.
When setup parameter HOME is set to SP1.
Setup parameter HOME is for Professional setting mode. See User’s Manual
Power-on
2. Setting Target Setpoint (SP)
When the required value is displayed, press the SET/ENTER key to register the setpoint.
Show the SP Display (Operation Display).(This is an example of setting the target setpoint to 150.0).
Press the SET/ENTER key to start the last digit of the setpoint blinking.Blinking allows you to change the value.
To set the setpoint, use the Left/Right arrow keys to move between digits and the Up/Down arrow keys to increase and decrease the value.
1.
2.
3.
4.
3. ConfirmationoftheLimitOutputWhenPVexceedsthesetpointforlimitcontrol(SP),
Procedure1)Theexceededlamplights,andalsotheoutputlamplights.Procedure2)ExceededlampisoffwhenthePVrecoverstothenormalstatuswherePVdoesn'texceedSP,whileOUTlampkeepslituntiltheconfirmationisdone.
Procedure3)Confirmationofthelimitoutputcanbedoneeitherbyafrontpanelorexternalcontactinput.
Hereexplainsthewaytoresetkeyoperation.
Show the Operation Display.1.
2.
Confirm that the EXCEEDED lamp is off and the OUT lamp is lit.OUT status cannot be reset while the EXCEEDED lamp is lit.
Ex.) SP= 120.0, PV= 125.0, Hysteresis= 4.0
Ex.) SP= 120.0, PV= 115.0, Hysteresis= 4.0
OUT lamp is lit.EXCEED lamp is lit.
OUT lamp is lit.EXCEED lamp is off.
3. Confirm that OUT lamp becomes OFF.The output has been on.
Press the RST key for about one second.
OUT lamp is off.EXCEED lamp is off.
ConfirmationofLimitStatusLimitcontroloutputandrelatedparametersuchasduration timeandmaximum/minimumPVvaluecanbeconfirmedbyafrontkeyoperation.Itispossibletocon-firmlimitcontroloutputbyusingexternalcontact input.Thewayofconfirmation issetbysetupparameterCNF.TableblowshowstheitemwhichcanbeconfirmedbyfrontkeyorexternalcontactinputaccordingtothesettingofCNF.
Item to be confirmed
CNF parameter = KEY CNF parameter = DIKEY DI KEY DI
Outputrelay Enable Disable Disable EnableDurationtime Enable Disable Enable DisableMaximum/Minimumvalue
Enable Disable Enable Disable
4. OperationinConfirmationDisplayFollowingparameterscanbeseen in theconfirmationdisplay.Theseparameterscanbeconfirmedandresetbypressingthe“RST”keyateachparameterdisplay. Durationtime(TIME) MaximumvalueofPV(HIGH)orMinimumvalueofPV(LOW)
Show the Operation Display.1.
2.
Press the DISPLAY key once to display the parameter “TIME”.
The SP display shows the duration time after PV exceeds SP. If “0.00” shows here, PV has not exceeded SP or the time is already confirmed.
If you want to reset the duration time, press the RST key for about one second.
<For “high limit control” type>Press the DISPLAY key. If the controller is specified as the high limit control type, “HIGH” will be displayed.The maximum value of PV that has been measured up to now is shown in the SP display.Press the RST key if reset is designated.
When the instrument is specified as high limit control type, go to the step 4.When the instrument is specified as low limit control type, go to the step 5.
Ex.) SP= 120.0, PV= 115.0, Hysteresis= 4.0
3.
Displays 0.00
4.
<For “low limit control” type>Press the DISPLAY key. If the controller is specified as the low limit control type, “LOW” will be displayed.The minimum value of PV that has been measured up to now is shown in the SP display.Press the RST key if reset is designated.
5.
OperationGuide
UT35A-LDigital Indicating Controller (Limit Control Type)Operation Guide
This operation guide describes key entries for operating the UT35A-L.For operations using external contact inputs, see “DI” of “6. Terminal Wiring Diagrams” in “Installation and Wiring.” If you cannot remember how to carry out an operation during setting, press the DISPLAY key once. This brings you to the display (Operation Display) that appears at power-on. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.
Operations
Show the Operation Display.1.
2.
Press the DISPLAY key once to display the parameter “TIME”.
The SP display shows the duration time after PV exceeds SP. If “0.00” shows here, PV has not exceeded SP or the time is already confirmed.
If you want to reset the duration time, press the RST key for about one second.
<For “high limit control” type>Press the DISPLAY key. If the controller is specified as the high limit control type, “HIGH” will be displayed.The maximum value of PV that has been measured up to now is shown in the SP display.Press the RST key if reset is designated.
When the instrument is specified as high limit control type, go to the step 4.When the instrument is specified as low limit control type, go to the step 5.
Ex.) SP= 120.0, PV= 115.0, Hysteresis= 4.0
3.
Displays 0.00
4.
<For “low limit control” type>Press the DISPLAY key. If the controller is specified as the low limit control type, “LOW” will be displayed.The minimum value of PV that has been measured up to now is shown in the SP display.Press the RST key if reset is designated.
5.
5. Troubleshooting
TroubleshootingFlowIftheOperationDisplaydoesnotappearafterturningonthecontroller’spower,checktheproceduresinthefollowingflowchart.Ifaproblemappearstobecomplicated,contactoursalesrepresentatives.
Is the controllerdefective?
Contact us for repair. Problem solved.
No communicationcapability
Completelyinactive?
Yes
Yes
Yes
No
No
No
Keyoperationfailure?
Yes
No
Yes
Check wiring of thepower terminals.
Check the key locksetting.
Displayfailure?
*Yes
No
Turn off power, andthen turn it on again.
I/O signalfailure?
Yes
No
Check the supply voltage.
Check the specifications and polarity
of connected devices .
Check the communication-related parameters.
Check the specificationsof communication
devices.
Check thecommunication wiring.
Communicationfailure?
No Withcommuni-
cation?
Yes
Yes
Normal?Is the
key locked?
Check the specificationsof the controller.
Yes
NoCorrect?
Correct the error(s).
Cancel the setting.
Check the I/O specificationsof the controller.
* The LCD (a liquid crystal display) is used for a display portion of this product. The LCD has a characteristic that the display action becomes late at the low temperature. Additionally, the luminance and contrast degradation are caused due to aged deterioration. However, the control function is not affected.
Remedies if Power Failure Occurs during Operations• Instantaneouspowerfailurewithin20ms. Apowerfailureisnotdetected.Normaloperationcontinues.• Powerfailureforlessthanabout5seconds,orforabout5secondsormore. Affectsthe"settings"and"operationstatus." Fordetails,seeUser'sManual.
NOTEWritedownthesettingsofparametersforarepairrequest.
IM 05P04D41-11EN page 8/10
n Errors at Power OnTheerrorsshownbelowmayoccurinthefaultdiagnosiswhenthepoweristurnedon.(FordetailsofSetpointdisplayandinput/outputactionwheneacherroroccurs,seeUser’sManual.
PV display (Operation
Display)
Setpoint display(Operation Display)
Status indicator(Operation Display)
Parameter that displays error details Error description Cause and diagnosis Remedy
Indication off Indication off — — FaultyMCURAM/MCUROM MCURAM/MCUROMarefailed. Faulty. Contactusforrepair.
ERR
SYS-----
—
— System data error System data is corrupted. Faulty. Contactusforrepair.
PAR0004 (foruserdefaultvalueerroronly)
Setupparameter(PA.ER)
User(parameter)defaultvalueerror
Userparameteriscorrupted.Initializedtofactorydefaultvalue.
Checkandreconfiguretheinitializedsettingparameters.Errorindicationiserased when the power is turned on again.
PAR0010(forsetupparametererroronly)
Setup parameter error Setup parameter data is corrupted.Initializedtouserdefaultvalue.
PAR0020(foroperationparametererroronly) Operationparametererror Operationparameterdataiscorrupted.
Initializedtouserdefaultvalue.
SLOT0004(0004:ErroroccurstohardwareofE3-terminalareas.)
Setupparameter(OP.ER)Nonrespondinghardwareofextendedfunction(E3-terminalareas)
Inconsistence of system data and hardwareofextendedfunction.Nonrespondingcommunicationbetweenhardwareofextendedfunction(E3-terminalareas).
Faulty.Contactusforrepair.
Normalindication Normalindication
RightmostdecimalpointonPVdisplayblinks.
Setupparameter(PA.ER)Calibrationvalueerror Initializedtocalibrateddefaultvaluebecause
ofcorruptedfactorydefaultvalue. Faulty.Contactusforrepair.Rightmostdecimalpoint
onSymboldisplayblinks. FaultyFRAM Datawriting(storing)toFRAMisimpossible.
n Errors during OperationTheerrorsshownbelowmayoccurduringoperation.(Forinput/outputactionwheneacherroroccurs,seeUser’sManual.
PV display (Operation
Display)
Setpoint display(Operation Display)
Status indicator(Operation Display)
Parameter that displayserror details Error description Cause and diagnosis Remedy
AD.ERR Normalindication(Note) — Setupparameter(AD1.E) AnaloginputterminalADCerror•PVinput AnaloginputterminalADvalueerror Faulty.
Contactusforrepair.
RJC.E(DisplaysRJC.EandPValternately.)
Normalindication(Note) — Setupparameter(AD1.E) UniversalinputterminalRJCerror•PVinput UniversalinputterminalRJCerror
Faulty.Contactusforrepair.SettheparameterRJCtoOFFtoeraseerror indication.
B.OUT Normalindication(Note) —
Setupparameter(AD1.E) Analoginputterminalburnouterror•PVinput Analoginputterminalsensorburnout
Checkwiringandsensor.Errorindicationiserasedinnormaloperation.
Setupparameter(PV1.E) PVinputburnouterror BurnoutofanaloginputconnectedtoPV
Checkwiringandsensorofconnectedanaloginputterminals.Errorindicationiserasedinnormaloperation.
OVER-OVER
Normalindication — Setupparameter(PV1.E)PVinputover-scalePVinputunder-scale(PVvaluesoutof-5to105%)
PVinputisoutof-5to105%.Alsooccurswhenthedataoutofrangewhichistheladder calculation result is input.
Checkanaloginputvalueorladderprogram.
Normalindication
0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)
— Setupparameter(OP.ER) Communicationerror(RS-485communication)
FramingparityerrorBufferoverflowInter-charactertime-outChecksumerror(PClinkcommunicationwithchecksum)CRCcheckerror(Modbus/RTU)LRCcheckerror(Modbus/ASCII)
Checkthecommunicationparameters.Recoveryatnormalreceipt.Holddownanykeytostopblinking.
Normalindication Normalindication Rightmostdecimalpointon
Symboldisplayblinks. Setupparameter(PA.ER) FaultyFRAM Writing(storing)datatoFRAMisimpossible. Faulty.Contactusforrepair.
Undefined Undefined — — FaultyMCU/DCU(ROM/RAMerror,corrupted) MCU/DCUiscorrupted. Faulty.Contactusforrepair.
Power on StatusThestateofoutputrelayatpower-oncanbesetbyasetupparameterrestartmodeR.MD.RestartmodeR.MD: 0:Limitoutputrelayisde-energizedatpoweron. 1:Limitoutputrelayisenergizedatpoweron.
When parameter R.MD is set to 0.Thelimitoutputrelayisalwaysde-energizedatpoweron,evenifPVdoesn’texceedSP(pointA).(NCterminal:CLOSE,NOterminal:OPEN).“OUT”lampislit.Aftertheconfirmation,stateofoutputrelay isenergized(NCterminal:OPEN,NOterminal:CLOSE)and“OUT”lampturnsoff,ifthePVdoesn’texceedSP(pointB).
SP
PV
Confirmation(accepted)
Hysteresis
EXCEEDEDLamp
OUTLamp
Output Relay
Operation(RST key or external contact input)
(A) (B)
Confirmation(accepted)
lit
litlit
on onoffoff
off
off offoff
Power on
In Case of High Limit Control
When parameter R.MD is set to 1.Thelimitoutputrelayisalwaysenergizedatpoweron(pointA)(NCterminal:OPEN,NOterminal:CLOSE)and“OUT”lampisoff,exceptwhenPVexceedsSPatpoweron.
SP
PV
Hysteresis
EXCEEDEDLamp
OUTLamp
Output Relay
Operation(RST key or external contact input)
(A)
Confirmation(accepted)
Power on
lit
lit
on onoffoff
off
off off
In Case of High Limit Control
7. ParametersintheConfirmationDisplaysDuration TimeThetimewhilePVexceedsSPiscountedandstoredinthememory.Itisdisplayedinthe“TIME”displayintheconfirmationdisplay.
Displaytimerange:0.00to99.59
Unitoftimeisbeeither“hour.minute”or“minute.second”,andcanbesetbyopera-tionparameterTMU.
-ToRESET-Push“RST”keyforaboutonesecondtoresetthedurationtimeintheconfirma-tiondisplaywhere“TIME”isdisplayed.Whenthecountarereset,“0.00”isdisplayeduntilPVexceedsSPagain.
-Thetimecountareresetwhenpoweristurnedon.-IfPVexceedsSPduringtheoldtimecountdataisretainedinthememory,theolddatashouldbeautomaticallyreset,andthenewtimecountingstartsfrom“0.00”.
-ItisimpossibletoresetthetimecountwhilePVexceedsSPbyanyoperation.-Durationtimecannotberesetbyanexternalcontactinput.
Maximum / Minimum ValueThemaximumvalueorminimumvalueofPVisstoredinthememoryanddisplayinthe“HIGH”or“LOW”displayintheconfirmationdisplay.Whenthecontrol type isspecifiedashigh limitcontrol, themaximumvalue isdis-playedin the“HIGH”display,andcontrol type isspecifiedas lowlimitcontrol, themaximumvalueisdisplayedinthe“LOW”display.WhenthePVexceedsSPandthenreturnstothenormalstatus,Maximum/Mini-mumValueisretainedasit is,butwhenPVexceedsSPagain, it isautomaticallyresetandstartstakingnewvalueforitsminimum/maximumvalue.
-ToRESET-Pushthe“RST”keyforaboutonesecondtoresetthemaximum/minimumval-ueintheconfirmationdisplaywhere“HIGH”or“LOW”isdisplayed.Thevalueisreset,andthevalueimmediatelyaftertheconfirmationshouldberecognizedasamaximumorminimumvalue.
-Whenthepoweristurnon,thememoryshouldberesetandthefirstPVshouldberecognizedasmaximum.
-Maximum/Minimumvaluecannotberesetbyanexternalcontactinput.-Itisimpossibletoresetthemaximum/minimumvaluewhilePVexceedsSPby
any operation.
8. Function Block Diagram
BS
FL
DI2.SCNF
UNIT
IN
RH, RL SDP SH, SL
A.BS
A.FL
RTSRTH RTL
RST
Input type
PV analog input bias
PV analog input filter
Input unit
Input range/scale
PV input bias
PV input filter
Equipped as standard Equipped as standard
RelayCurrent
RET retransmission output Alarm
Limit Control computation
Contact inputs
PV
PV input
Equipped as standardEquipped as standard.
Ala
rm 1
(PV
hig
h lim
it)
Ala
rm 2
(PV
low
lim
it)
Ala
rm 3
(PV
hig
h lim
it)
PV display SP display
Com.
OUT
DI2DI1
RET AL3AL2AL1
RS-485, Ethernet
Terminal Parameter Function
Analog signal Contact signal Front panel keyLegend
Confirmation
Target setpointSP
SP limiter
Latch release, etc
SPH, SPL
HI.LO
HYS
6. Description of Limit Control FunctionsIn Case of High Limit ControlWhenPVexceedsasetpoint(SP),"EXCEEDED"lamplights,and"OUT"lampturnsON(pointA).Thelimitcontroloutputrelayisde-energizedthen."EXCEEDED"lampturnsoffwhenPVgoesintonormalcondition,while"OUT"lampstaysonasitis(pointB)."OUT"lampturnsoffwhenaconfirmingoperationisdonebyanoperator(pointC).Thewaytoconfirmispushingthe"RST"key(orbyanexe-ternalcontact,accordingtothesettingofsetupparameterCNF).Theconfirmingop-erationisnotacceptedduringPVexceedsSP(pointD).Stateofoutputrelayisde-energizedwhenever"OUT"lampison.(NCterminal:CLOSE,NOterminal:OPEN)
SP
PV
(A)
Confirmation(accepted)
Hysteresis
EXCEEDEDLamp
OUTLamp
Output Relay
Operation(RST key or external contact input)
(B) (C) (A) (D) (B)
Confirmation(not accepted)
litlit
lit lit
onon
off
off
off
offoff
off
off
In Case of Low Limit ControlWhenPVexceedsasetpoint(SP),“EXCEEDED”lamplights,and“OUT”lampturnsON(pointA).Thelimitcontroloutputrelayisde-energizedthen.“EXCEEDED”lampturnsoffwhenPVgoesintonormalcondition,while“OUT”lampstaysonasitis(pointB).“OUT”lampturnsoffwhenaconfirmingoperationisdonebyanoperator(pointC).Thewaytoconfirmispushingthe“RST”key(orbyanexe-ternalcontact,accordingtothesettingofsetupparameterCNF).Theconfirmingop-erationisnotacceptedduringPVexceedsSP(pointD).Stateofoutputrelayisde-energizedwhenever“OUT”lampison.(NCterminal:CLOSE,NOterminal:OPEN)
SP
PV
(A)
Confirmation(accepted)
Hysteresis
EXCEEDEDLamp
OUTLamp
Output Relay
Operation(RST key or external contact input)
(B) (C) (A) (D) (B)
Confirmation(not accepted)
litlit
lit lit
onon
off
off
off
offoff
off
off
IM 05P04D41-11EN page 9/10
Operation ParametersHolddownthePARAMETERkeyfor3secondstomovefromtheOperationDisplaytotheOperationParameterSettingDisplay.PresstheDISPLAYkeyoncetoreturntotheOperationDisplay.
Menu
Hold down PARAMETER keyfor 3 sec.
DISPLAY key
SET/ENTER key PARAMETER key
key key key
key key
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
ParameterEND
Menu
END
Menu END
END
Menu D isp lay and Parameter Set t ing Display are changed in a circular pattern.
Move to the Setup Parameter Setting Display: Hold down the PARAMETER key and the Left arrow key simultaneously for 3 sec.
Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.
· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.
Notethattherearesomeparameterswhicharenotdisplayeddependingonthesuffixcodes.Theparametersforprofessionalsettingmode(LEVL:PRO)arenotdescribedinthismanual.SeeUser’sManual.
n SP and Alarm Setpoint Setting ParameterMenusymbol: (SP)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(SP)Targetsetpoint 0.0to100.0%ofPVinputrange(EU)
(Settingrange:SPLtoSPH) SPH
EASY(A1)
Alarm-1setpointSetadisplayvalueofsetpointofPValarm,deviationalarm,orvelocityalarm. -19999to30000(Setavaluewithintheinputrange.) Decimalpointpositiondependsontheinput type
0
(A2)Alarm-2setpoint 0
(A3)Alarm-3setpoint 0
n SP-related Setting ParameterMenusymbol: (SPS)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(TMU)Time unit for duration time
HH.MM:HourandminuteMM.SS:Minuteandsecond HH.MM EASY
n Alarm Function Setting ParameterMenusymbol: (ALRM)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(AL1)
Alarm-1to3typeExample:Alarm-1
Stand-by action
Latch actionEnergized/De-energize
Alarm type
Seta5-digitvalueinthefollowingorder.[Alarmtype:2digits(seebelow)]+[Without(0)orWith(1)Stand-byac-tion]+[Energized(0)orDe-energized(1)]+[Latchaction(0/1/2/3/4)]Forlatchaction,seeUser'sManual.
AL1, AL3:
PVhighlimit(01) WithoutStand-by
action (0)
Ener-gized(0)
Latchaction (0)
AL2:PVlowlimit(02)WithoutStand-by
action (0)
Ener-gized(0)
Latchaction (0)
EASY(AL2) Alarmtype:2digits
00:Disable01:PVhighlimit02:PVlowlimit05:Deviationhighlimit06:Deviationlowlimit07:Deviationhighandlowlimits08:Deviationwithinhighandlowlimits29:PVvelocity30:Faultdiagnosis31:FAIL
(AL3)
(VT1)PVvelocityalarmtimesetpoint 1
0.01to99.59(minute.second)
1.00
EASY(VT2)
PVvelocityalarmtimesetpoint 2 1.00
(VT3)PVvelocityalarmtimesetpoint 3 1.00
(HY1)Alarm-1hysteresis Setadisplayvalueofsetpointof
hysteresis. -19999to30000(Setavaluewithintheinputrange.) Decimalpointpositiondependsonthe input type.Whenthedecimalpointpositionfortheinputtypeissetto"1",theinitialvalueofthehysteresisis"1.0".
10
EASY(HY2)
Alarm-2hysteresis 10
(HY3)Alarm-3hysteresis 10
(DYN1)Alarm-1On-delaytimer
AnalarmoutputisONwhenthedelaytimerexpiresafterthealarmsetpointis reached. 0.00to99.59(minute.second)
0.00
STD(DYN2)
Alarm-2On-delaytimer 0.00
(DYN3)Alarm-3On-delaytimer 0.00
n PV-related Setting Parameter Menusymbol: (PVS)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(BS)PVinputbias -100.0to100.0%ofPVinputrange
span(EUS)
0.0%ofPVinput rangespan
EASY(FL)
PVinputfilter OFF,1to120s OFF
(HYS)Limitcontroloutputhysteresis
0.0to100.0%ofPVinputrangespan(EUS)
0.5%ofPVinputrangespan
Setup ParametersHolddownthePARAMETERkeyandLeftarrowkeysimultaneouslyfor3secondstomovefromtheOperationDisplayorOperationParameterSettingDisplaytotheSetupParameterSettingDisplay.PresstheDISPLAYkeyoncetoreturntotheOperationDisplay.
Menu
DISPLAY key
SET/ENTER key PARAMETER key
key key key
key key
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
ParameterEND
Menu
END
Menu END
END
Menu D isp lay and Parameter Set t ing Display are changed in a circular pattern.
Move to the Operation Parameter Setting Display: Hold down the PARAMETER key for 3 sec.
Hold down PARAMETER key and Left arrow key simultaneously for 3 sec.
Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.
· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.
NotethattherearesomeparameterswhicharenotdisplayeddependingontheSuffixcodes.Theparametersforprofessionalsettingmode(LEVL:PRO)arenotdescribedinthismanual.SeeUser’sManual.
n Control Function Setting ParameterMenusymbol: (CTL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(HI.LO)Limitcontroltype
LOW:LowlimitcontrolHIGH:Highlimitcontrol HIGH
EASY
(CNF)Thewayofconfirmingoperation
KEY:BykeyoperationDI:ByDI KEY
n PV Input Setting Parameter Menusymbol: (PV)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(IN)PVinputtype
OFF:DisableK1:-270.0to1370.00C/-450.0to2500.0 0FK2:-270.0to1000.00C/-450.0to2300.0 0FK3:-200.0to500.00C/-200.0to1000.0 0FJ:-200.0to1200.00C/-300.0to2300.0 0FT1:-270.0to400.00C/-450.0to750.0 0FT2:0.0to400.00C/-200.0to750.0 0FB:0.0to1800.00C/32to3300 0FS:0.0to1700.00C/32to3100 0FR:0.0to1700.00C/32to3100 0FN:-200.0to1300.00C/-300.0to2400.0 0FE:-270.0to1000.00C/-450.0to1800.0 0FL:-200.0to900.00C/-300.0to1600.0 0FU1:-200.0to400.00C/-300.0to750.0 0FU2:0.0to400.00C/-200.0to1000.0 0FW:0.0to2300.00C/32to4200 0FPL2:0.0to1390.00C/32.0to2500.0 0FP2040:0.0to1900.00C/32to3400 0FWRE:0.0to2000.00C/32to3600 0FJPT1:-200.0to500.00C/-300.0to1000.0 0FJPT2:-150.0to150.00C/-200.0to300.0 0FPT1:-200.0to850.00C/-300.0to1560.0 0FPT2:-200.0to500.00C/-300.0to1000.0 0FPT3:-150.00to150.000C/-200.0to300.0 0F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV
OFF
EASY
(UNIT)PVinputunit
-:Nounit,C:DegreeCelsius -:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit
F
(RH)MaximumvalueofPVinputrange
Dependsontheinputtype.-Fortemperatureinput-Setthetemperaturerangethatisactuallycontrolled.(RL<RH)-Forvoltage/currentinput-Settherangeofavoltage/currentsignalthatisapplied.Thescaleacrosswhichthevoltage/currentsignalisactuallycontrolledshouldbesetusingthemaximumvalueofinputscale(SH)andmini-mumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)
Dependson the
input type
(RL)MinimumvalueofPVinputrange
Dependson the
input type
(SDP)PVinputscaledecimalpoint position
0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces
Dependson the
input type
(SH)MaximumvalueofPVinput scale
-19999to30000,(SL<SH),|SH-SL|≤30000
Dependson the
input type
(SL)MinimumvalueofPVinput scale
Dependson the
input type
(BSL)PVinputburnoutaction
OFF:DisableUP:UpscaleDOWN:Downscale
Dependson the
input type
STD(A.BS)
PVanaloginputbias -100.0to100.0%ofeachinputrangespan(EUS)
0.0%ofPVinputrangespan
(A.FL)PVanaloginputfilter OFF,1to120s OFF
W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988,WRE:W97Re3-W75Re25
OperationGuide
UT35A-L Digital Indicating Controller (Limit Control Type)Operation Guide
This operation guide describes the functions of parameters briefly. The parameter symbols listed are in the order shown on the display in each group of menu symbols. In addition, each parameter table has a “User Setting” column, where you can record your setpoints when setting them in the controller. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.
Yokogawa Electric Corporation
Parameters
IM 05P04D41-11EN page 10/10
n Input Range, SP Limiter Setting ParameterMenusymbol: (MPV)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(P.UNI)ControlPVinputunit
-:NounitC:DegreeCelsius-:Nounit--:Nounit---:NounitF:DegreeFahrenheit
Same asPVinput unit
STD
(P.DP)ControlPVinputdecimalpoint position
0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces
1
(P.RH)MaximumvalueofcontrolPVinputrange
-19999to30000,(P.RL<P.RH),|P.RH-P.RL|≤30000
Dependson the
input type
(P.RL)MinimumvalueofcontrolPVinputrange
Dependson the
input type
(SPH)SPhighlimit
0.0to100.0%ofPVinputrange(EU),(SPL<SPH)
100.0%ofPVinput range
(SPL)SP low limit
0.0%ofPVinput range
n Output Setting ParameterMenusymbol: (OUT)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(RTS)RetransmissionoutputtypeofRET
OFF:DisablePV1:PVSP1:SP
PV1 EASY
(RTH)
Maximumvalueofretransmission output scaleofRET
WhenRTS=PV1orSP1, RTL+1digitto30000 -19999toRTH-1digit
Decimalpointposition: WhenRTS=PV1orSP1,decimalpoint position is same as that of PVinput.
100%ofPVinput range
STD
(RTL)
Minimumvalueofretransmission output scaleofRET
0%ofPVinput range
(RET.A)RETcurrentoutputrange
4-20:4to20mA0-20:0to20mA20-4:20to4mA20-0:20to0mA
4-20
n RS-485 Communication Setting Parameter (E3-terminal Area)Menusymbol: (R485)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(PSL)Protocol selection
PCL:PClinkcommunicationPCLSM:PClinkcommunication(withchecksum)
LADR:LaddercommunicationMBASC:Modbus(ASCII)MBRTU:Modbus(RTU)
MBRTU
EASY
(BPS)Baud rate
600:600bps1200:1200bps2400:2400bps4800:4800bps9600:9600bps19200:19.2kbps38400:38.4kbps
19200
(PRI)Parity
NONE:None EVEN:Even ODD:Odd
EVEN
(STP)Stopbit 1:1bit,2:2bits 1
(DLN)Datalength 7:7bits,8:8bits 8
(ADR)Address 1to99 1
Ethernet Communication Setting Parameter (E3-terminal Area)Menusymbol: (ETHR)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(HSR)High-speedresponsemode OFF,1to8 1
EASY
(BPS) Baud rate9600:9600bps19200:19.2kbps38400:38.4kbps
38400
(PRI) ParityNONE:NoneEVEN:EvenODD:Odd
EVEN
to
(IP1toIP4)
IP address 1 to 4
0to255Initialvalue: (IP1).(IP2).(IP3).(IP4)=(192).(168).(1).(1)
See left Tablebelow
to
(SM1toSM4)
Subnetmask1to4
0to255Initialvalue: (SM1).(SM2).(SM3).(SM4)=(255).(255).(255).(0)
See left Tablebelow
to
(DG1toDG4)
Defaultgateway1to4
0to255Initialvalue: (DG1).(DG2).(DG3).(DG4)=(0).(0).(0).(0)
See left Tablebelow
(PRT)Portnumber 502,1024to65535 502
(IPAR)IP access restriction OFF:Disable,ON:Enable OFF
to ,
to
(1.IP1to1.IP4,2.IP1to2.IP4)
PermittedIPaddress1-1to1-4PermittedIPaddress2-1to2-4
0to255Initialvalue: (1.IP1).(1.IP2).(1.IP3).(1.IP4)=(255).(255).(255).(255)(2.IP1).(2.IP2).(2.IP3).(2.IP4)=(255).(255).(255).(255)
See left Tablebelow
(ESW)Ethernetsettingswitch
Settingthisparameterto“ON”enablestheEthernetcommunicationparametersettings.OFF,ON
OFF
UsethefollowingtabletorecordEthernetcommunicationsettingvalue.
Parameter n=1 n=2 n=3 n=4
IPn
SMn
DGn
1.IPn
2.IPn
KeyActionSettingParameterMenusymbol: (KEY)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(F1)Userfunctionkey-1 actionsetting
OFF:DisableLTUP:LCDbrightnessUPLTDN:LCDbrightnessDOWNBRI:AdjustLCDbrightnessLCD:LCDbacklightON/OFFswitchLAT:Latchrelease
OFF
EASY(F2)
Userfunctionkey-2 actionsetting OFF
(Fn)Userfunctionkey-n actionsetting OFF
DisplayFunctionSettingParameterMenusymbol: (DISP)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(PCMD)ActivecolorPVdisplayswitch
0:Fixedinwhite1:Fixedinred2:Linktoalarm1(AlarmOFF:white,AlarmON:red)
3:Linktoalarm1(AlarmOFF:red,AlarmON:white)
4:Linktoalarm1or2(AlarmOFF:white,AlarmON:red)
5:Linktoalarm1or2(AlarmOFF:red,AlarmON:white)
6:PVlimit(Withinrange:white,Outofrange:red)
7:PVlimit(Withinrange:red,Outofrange:white)
8:SPdeviation(Withindeviation:white,Outofdeviation:red)
9:SPdeviation(Withindeviation:red,Outofdeviation:white)
10:LinktoDI2(ON:red,OFF:white)(*)
11:LinktoEXCEEDEDlamp(Unlit:white,lit:red)
12:LinktoOUTlamp(Unlit:white,lit:red)
*:SettheparameterDI2.S=PVRW
0
EASY
(PCH)PVcolorchangehighlimit
SetadisplayvaluewheninPVlimitorSPdeviation. -19999to30000(Setavaluewithintheinputrange.) Decimalpointpositiondependsonthe input type.
0
(PCL)PVcolorchangelowlimit 0
(GUID)GuidedisplayON/OFF OFF:Nondisplay,ON:Display ON
STD
(ECO)Economymode
OFF:Disable1:EconomymodeON(AllindicationsexceptPVdisplayOFF)
2:EconomymodeON(AllindicationsOFF)
3:Brightness10%(wholeindication)
OFF
(BRI)Brightness (Dark)1to5(Bright) 3 EASY
(MLSD)LeastsignificantdigitalmaskofPVdisplay
OFF:Withleastsignificantdigit ON:Withoutleastsignificantdigit OFF STD
KeyLockSettingParameterMenusymbol: (KLOC)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(COM.W)Communicationwriteenable/disable OFF:Enable,ON:Disable OFF
STD
(DATA)Front panel parameter data(,)keylock OFF:Unlock,ON:Lock OFF
n DI Function Registration ParameterMenusymbol: (DI.SL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(DI2.S)DI2functionselection
OFF:Nofunction LAT:Latchrelease LCD:LCDbacklightON/OFFswitch PVRW:PVred/whiteswitch(*) MG1:Messagedisplayinterruption1 MG2:Messagedisplayinterruption2 MG3:Messagedisplayinterruption3 MG4:Messagedisplayinterruption4*:SettheparameterPCMD=10.
OFF STD
SystemSettingParameterMenusymbol: (SYS)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(R.MD)Restartmode
0:LimitcontroloutputisONatpoweron in any cases
1:LimitcontroloutputisOFFatpoweronwhenPVdoesn'texceedSP
0 STD
(FREQ)Powerfrequency AUTO,60:60Hz,50:50Hz AUTO
EASY(QSM)
Quicksettingmode OFF:Disable ON:Enable ON
(PASS)Passwordsetting 0(Nopassword)to65535 0
ErrorandVersionConfirmationParameter(fordisplayonly)Menusymbol: (VER)
Parameter symbol Name of Parameter Status record Display
level
(PA.ER)Parameter error status
EASY
(OP.ER)Optionerrorstatus
(AD1.E)A/Dconvertererrorstatus1
(PV1.E)PVinputerrorstatus
(MCU)MCUversion
(DCU)DCUversion
(ECU3)ECU-3version(E3-terminalarea)
(PARA)Parameterversion
(H.VER)Productversion
(SER1)Serialnumber1
(SER2)Serialnumber2
(MAC1)MACaddress1(E3-terminalarea)
(MAC2)MACaddress2(E3-terminalarea)
(MAC3)MACaddress3(E3-terminalarea)
Trademarks Our product names or brand names mentioned in this manual are the trademarks or registered trademarks of Yokogawa Electric Corporation. Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of Adobe Systems Incorporated. Ethernet is a registered trademark of XEROX Corporation in the United States. Modbus is a registered trademark of Schneider Electric. We do not use the TM or ® mark to indicate these trademarks or registered trademarks in this manual. All other product names mentioned in this manual are trademarks or registered trademarks of their respective companies.
ParameterDisplayLevelParameterMenusymbol: (LVL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(LEVL)Parameterdisplaylevel
EASY:EasysettingmodeSTD:StandardsettingmodePRO:Professionalsettingmode
STD EASY
*ForProfessionalsettingmode,seeUser’sManual.