SAFETY INSTRUCTIONS · Incorrect neutral sensor could cause nuisance trip-ping or improper...

2
SAFETY INSTRUCTIONS Siemens Energy & Automation, Inc. Bellefontaine, Ohio 43311 U.S.A. Installation Instructions Hazardous voltage. Will cause death or severe in- jury. Turn off and lock out all power before installing this device. Replace the covers and shields before power supply- ing this device is restored. Item: Neutral Sensor For use with: I-T-E ® JD Frame Types SJD6(-A), SHJD6(-A), SCJD6(-A); LD Frame Types SLD6(- A), SHLD6(-A), and SCLD6(-A), equipped with ground fault protection for 3 phase, 4 wire, 208Y/120, 480Y/277 or 600Y/347 volt AC systems. Page 1 of 2 CAUTION Incorrect neutral sensor could cause nuisance trip- ping or improper operation of the ground fault function. Use only the above series of neutral sensors. The Ampere Rating of the neutral sensor must match the Maximum Continuous Current rating (In) of the Circuit Breaker. 1. Turn off power feeding this device before starting the installation. 2. Also turn off any line power within the immediate vi- cinity to prevent the incidental or accidental contact of tools by the installer. Note: This instruction sheet outlines the recommended installation procedure for the following Neutral Sensors: Neutral Sensor Neutral Sensor Cat. No . Ampere Rating N02SJD 200 Amps N03SJD 300 Amps N04SJD 400 Amps N05SLD 500 Amps N06SLD 600 Amps This neutral sensor is designed to be mounted on one 3.00” x .50” bus bar or, two 500 MCM cables, maximum. Mounting: Position the neutral sensor within easy wiring range of the associated circuit breaker and fabricate two .312 di- ameter holes 2.25 inches apart in bus or panel, as shown in Figure 1. Orient L — Mounting brackets as necessary for the mounting configuration being used and secure to the neutral sensor with the hardware provided. Mount the neutral sensor to bus or panel with 1/4-20 hard- ware (not provided). Important: The SJD and SLD series of electronic trip circuit break- ers equipped with ground fault protection may be used in the Residual or Ground Return modes. When used in the Residual mode the orientation of the neutral sensor is important for proper operation. See Figures 2 and 3 for proper orientation of the neutral sensor for Residual mode Ground Fault. Orientation of the neutral sensor is not required when used in the Ground Return mode of Ground Fault. See Figure 4 for installation of neutral sensor. Terminal Connections: After properly orienting and mounting the neutral sensor, maintain the correct polarity by attaching the white lead from the circuit breaker to terminal X1 of the neutral sen- sor, and the black lead to terminal X2. Hardware List: Quantity 10-32 Terminal Screw 2 #10 Lockwasher 2 Cupped Washer 2 L Mounting Bracket 2 1/4-20 x 5/8” machine screw 2 1/4” lockwasher 2 Breaker Label 1 Breaker Label (Figure 5): This label is to be attached to the associated circuit breaker at installation.

Transcript of SAFETY INSTRUCTIONS · Incorrect neutral sensor could cause nuisance trip-ping or improper...

Page 1: SAFETY INSTRUCTIONS · Incorrect neutral sensor could cause nuisance trip-ping or improper operation of the ground fault function. Use only the above series of neutral sensors. The

SAFETY INSTRUCTIONS

Siemens Energy & Automation, Inc.Bellefontaine, Ohio 43311 U.S.A.

Installation Instructions

Hazardous voltage.Will cause death or severe in-jury.

Turn off and lock out all powerbefore installing this device.

Replace the covers andshields before power supply-ing this device is restored.

Item: Neutral Sensor

For use with: I-T-E® JD Frame Types SJD6(-A),SHJD6(-A), SCJD6(-A); LD Frame Types SLD6(-A), SHLD6(-A), and SCLD6(-A), equipped withground fault protection for 3 phase, 4 wire,208Y/120, 480Y/277 or 600Y/347 volt AC systems.

Page 1 of 2

CAUTIONIncorrect neutral sensor could cause nuisance trip-ping or improper operation of the ground faultfunction.Use only the above series of neutral sensors.The Ampere Rating of the neutral sensor mustmatch the Maximum Continuous Current rating (In)of the Circuit Breaker.

1. Turn off power feeding this device before starting theinstallation.

2. Also turn off any line power within the immediate vi-cinity to prevent the incidental or accidental contactof tools by the installer.

Note: This instruction sheet outlines the recommendedinstallation procedure for the following NeutralSensors:

Neutral Sensor Neutral SensorCat. No. Ampere RatingN02SJD 200 AmpsN03SJD 300 AmpsN04SJD 400 AmpsN05SLD 500 AmpsN06SLD 600 Amps

This neutral sensor is designed to be mounted on one3.00” x .50” bus bar or, two 500 MCM cables, maximum.

Mounting:

Position the neutral sensor within easy wiring range ofthe associated circuit breaker and fabricate two .312 di-ameter holes 2.25 inches apart in bus or panel, as shownin Figure 1. Orient L — Mounting brackets as necessaryfor the mounting configuration being used and secure tothe neutral sensor with the hardware provided.

Mount the neutral sensor to bus or panel with 1/4-20 hard-ware (not provided).

Important:

The SJD and SLD series of electronic trip circuit break-ers equipped with ground fault protection may be used inthe Residual or Ground Return modes. When used in theResidual mode the orientation of the neutral sensor isimportant for proper operation. See Figures 2 and 3 forproper orientation of the neutral sensor for Residual modeGround Fault. Orientation of the neutral sensor is notrequired when used in the Ground Return mode of GroundFault. See Figure 4 for installation of neutral sensor.

Terminal Connections:

After properly orienting and mounting the neutral sensor,maintain the correct polarity by attaching the white leadfrom the circuit breaker to terminal X1 of the neutral sen-sor, and the black lead to terminal X2.

Hardware List: Quantity10-32 Terminal Screw 2#10 Lockwasher 2Cupped Washer 2L Mounting Bracket 21/4-20 x 5/8” machine screw 21/4” lockwasher 2Breaker Label 1

Breaker Label (Figure 5):

This label is to be attached to the associated circuitbreaker at installation.

Page 2: SAFETY INSTRUCTIONS · Incorrect neutral sensor could cause nuisance trip-ping or improper operation of the ground fault function. Use only the above series of neutral sensors. The

Siemens Energy & Automation, Inc.Bellefontaine, OH 43311 U.S.A.

Installation InstructionsInstallation Instructions

Hazardous voltage.Will cause death or severe injury.

Turn off and lock out all power be-fore installing this device.

Replace the covers and shieldsbefore power supplying this de-vice is restored.

Page 2 of 2Part No. 761466A03© Siemens Energy & Automation, Inc. 1989

Figure 1

STANDARD CONNECTION

Figure 2

Figure 4 Figure 5

REVERSE CONNECTION(Types SJD6 and SLD6 only)

Figure 3

BREAKER IS EQUIPPED WITH ANEUTRAL SENSINGTRANSFORMER

720219-A00

TERMINALFACE

1/4-20 HARDWARERECOMMENDED.(NOT PROVIDED)

1/4-20 HARDWARERECOMMENDED.(NOT PROVIDED)

BUS

2.25

2.25

PANEL

CABLES

TERMINAL FACE

CABLE MOUNTINGBUS MOUNTING

Grounding ElectrodeBonding Jumper

Grounding ElectrodeBonding Jumper

NeutralDisconnect

NeutralDisconnect

NeutralDisconnect

Bonding Jumper

Grounding Electrode

Neutral Sensor(terminal face)

Neutral Sensor(terminal face)

Neutral Sensor(terminal face)