SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

39
Second Revision No. 68-NFPA 101-2013 [ Global Comment ] Update the edition dates for the NFPA referenced publications in C.1.1 NFPA Publications that have document numbers (i.e., NFPA 1 through NFPA 5000) to be the most current at the time of NFPA 101-2015 publication. Leave, as is, the references to the NFPA Fire Protection Handbook and the SFPE Handbook of Fire Protection Engineering. Submitter Information Verification Submitter Full Name: Ron Coté Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Fri May 31 09:37:05 EDT 2013 Committee Statement Committee Statement: It is the SAF-FUN committee's intent that the NFPA referenced publications in C.1.1 NFPA Publications that have document numbers (i.e., NFPA 1 through NFPA 5000) be the most current at the time NFPA 101- 2015 is published. Response Message: Page 1 of 331 National Fire Protection Association Report 8/26/2013 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment... SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Transcript of SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Page 1: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 68-NFPA 101-2013 [ Global Comment ]

Update the edition dates for the NFPA referenced publications in C.1.1 NFPA Publications that have document numbers (i.e., NFPA 1 through NFPA 5000) to be the most current at the time of NFPA 101-2015 publication. Leave, as is, the references to the NFPA Fire Protection Handbook and the SFPE Handbook of Fire Protection Engineering.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri May 31 09:37:05 EDT 2013

Committee Statement

CommitteeStatement:

It is the SAF-FUN committee's intent that the NFPA referenced publications in C.1.1 NFPA Publications that have document numbers (i.e., NFPA 1 through NFPA 5000) be the most current at the time NFPA 101-2015 is published.

Response Message:

Page 1 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 1 of 39

Page 2: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 16-NFPA 101-2013 [ Section No. 2.2 ]

2.2* NFPA Publications.National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 10, Standard for Portable Fire Extinguishers, 2010 2013 edition.

NFPA 11, Standard for Low-, Medium-, and High-Expansion Foam, 2010 edition.

NFPA 12, Standard on Carbon Dioxide Extinguishing Systems, 2011 edition.

NFPA 12A, Standard on Halon 1301 Fire Extinguishing Systems, 2009 edition.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2010 2013 edition.

NFPA 13D, Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, 2010 2013 edition.

NFPA 13R, Standard for the Installation of Sprinkler Systems in Low-RiseResidential Occupancies up to and Including Four Stories in Height , 2010 2013edition.

NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2010 2013edition.

NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, 2012edition.

NFPA 16, Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems, 2011 edition.

NFPA 17, Standard for Dry Chemical Extinguishing Systems, 2009 2013 edition.

NFPA 17A, Standard for Wet Chemical Extinguishing Systems, 2009 2013 edition.

NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2011 2014 edition.

NFPA 30, Flammable and Combustible Liquids Code, 2012 2015 edition.

NFPA 30B, Code for the Manufacture and Storage of Aerosol Products, 2011 2015edition.

NFPA 31, Standard for the Installation of Oil-Burning Equipment, 2011 edition.

NFPA 40, Standard for the Storage and Handling of Cellulose Nitrate Film, 2011edition.

NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals, 2011edition.

NFPA 54, National Fuel Gas Code, 2012 2015 edition.

NFPA 58, Liquefied Petroleum Gas Code, 2011 2014 edition.

NFPA 70®, National Electrical Code®, 2011 2014 edition.

NFPA 72®, National Fire Alarm and Signaling Code, 2010 2013 edition.

NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2010 2013edition.

NFPA 82, Standard on Incinerators and Waste and Linen Handling Systems and Equipment, 2009 2014 edition.

Page 2 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 2 of 39

Page 3: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

NFPA 88A, Standard for Parking Structures, 2011 2015 edition.

NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, 2012 2015 edition.

NFPA 90B, Standard for the Installation of Warm Air Heating and Air-Conditioning Systems, 2012 2015 edition.

NFPA 91, Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible Particulate Solids, 2010 edition.

NFPA 92, Standard for Smoke Control Systems, 2012 edition.

NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, 2011 2014 edition.

NFPA 99, Health Care Facilities Code, 2012 2015 edition.

NFPA 101A, Guide on Alternative Approaches to Life Safety, 2010 2013 edition.

NFPA 105, Standard for Smoke Door Assemblies and Other Opening Protectives, 2010 2013 edition.

NFPA 110, Standard for Emergency and Standby Power Systems, 2010 2013edition.

NFPA 111, Standard on Stored Electrical Energy Emergency and Standby Power Systems, 2010 2013 edition.

NFPA 160, Standard for the Use of Flame Effects Before an Audience, 2011edition.

NFPA 170, Standard for Fire Safety and Emergency Symbols, 2009 2012 edition.

NFPA 204, Standard for Smoke and Heat Venting, 2012 2015 edition.

NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel–Burning Appliances, 2010 2013 edition.

NFPA 220, Standard on Types of Building Construction, 2012 2015 edition.

NFPA 221, Standard for High Challenge Fire Walls, Fire Walls, and Fire Barrier Walls, 2012 2015 edition.

NFPA 241, Standard for Safeguarding Construction, Alteration, and Demolition Operations, 2009 2013 edition.

NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials, 2006 edition.

NFPA 252, Standard Methods of Fire Tests of Door Assemblies, 2008 2012edition.

NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, 2011 edition.

NFPA 257, Standard on Fire Test for Window and Glass Block Assemblies, 2007 2012 edition.

NFPA 259, Standard Test Method for Potential Heat of Building Materials, 2008 2013 edition.

NFPA 260, Standard Methods of Tests and Classification System for Cigarette Ignition Resistance of Components of Upholstered Furniture, 2009 2013 edition.

NFPA 261, Standard Method of Test for Determining Resistance of Mock-Up Upholstered Furniture Material Assemblies to Ignition by Smoldering Cigarettes, 2009 2013 edition.

NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls, 2011 edition.

Page 3 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 3 of 39

Page 4: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

NFPA 271, Standard Method of Test for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter, 2009edition.

NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, 2011 edition.

NFPA 288, Standard Methods of Fire Tests of Floor Horizontal Fire Door Assemblies Installed Horizontally in in Horizontal Fire Resistance–Rated FloorSystems Assemblies , 2007 2012 edition.

NFPA 289, Standard Method of Fire Test for Individual Fuel Packages, 2009 2013edition.

NFPA 400, Hazardous Materials Code, 2013 edition.

NFPA 415, Standard on Airport Terminal Buildings, Fueling Ramp Drainage, and Loading Walkways, 2008 2013 edition.

NFPA 418, Standard for Heliports, 2011 edition.

NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films, 2010 edition.

NFPA 703, Standard for Fire Retardant–Treated Wood and Fire-Retardant Coatings for Building Materials, 2012 2015 edition.

NFPA 720, Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, 2012 2015 edition.

NFPA 731, Standard for the Installation of Electronic Premises Security Systems, 2014 edition.

NFPA 750, Standard on Water Mist Fire Protection Systems, 2010 2014 edition.

NFPA 914, Code for Fire Protection of Historic Structures, 2010 edition.

NFPA 1124, Code for the Manufacture, Transportation, Storage, and Retail Sales of Fireworks and Pyrotechnic Articles, 2006 2013 edition.

NFPA 1126, Standard for the Use of Pyrotechnics Before a Proximate Audience,2011 edition.

NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems, 2012 edition.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 22 11:59:48 EDT 2013

Committee Statement

Page 4 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 4 of 39

Page 5: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Committee Statement:

NFPA 400 was added to Chapter 36 during processing for 2012, but was not added to Chapter 2. NFPA 731 is to be referenced by new 11.8.8 on stairway video monitoring for some high-rise buildings. NFPA 271 was deleted as it has been withdrawn.

ResponseMessage:

Page 5 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 5 of 39

Page 6: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 18-NFPA 101-2013 [ Section No. 2.3.6 ]

2.3.6 ASTM Publications.ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. www.astm.org

ASTM C 1629/C 1629M, Standard Classification for Abuse-Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels, 2006 (2011).

ASTM D 1929, Standard Test Method for Determining Ignition Temperatures of Plastic, 2011 2012 .

ASTM D 2859, Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials, 2006 (2011).

ASTM D 2898, Standard Test Methods for Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing, 2010.

ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2012 2013 .

ASTM E 108, Standard Test Methods for Fire Tests of Roof Coverings, 2011.

ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, 2012a .

ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 Degrees C, 2011 2012 .

ASTM E 648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, 2010 e1.

ASTM E 814, Standard Test Method for Fire Tests of Through-Penetration Fire Stops, 2011a.

ASTM E 1354, Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter, 2011b.

ASTM E 1537, Standard Test Method for Fire Testing of Upholstered Furniture, 2012.

ASTM E 1590, Standard Test Method for Fire Testing of Mattresses, 2012.

ASTM E 1591, Standard Guide for Obtaining Data for Deterministic Fire Models, 2007.

ASTM E 1966, Standard Test Method for Fire-Resistive Joint Systems, 2007 (2011).

ASTM E 2072, Standard Specification for Photoluminescent (Phosphorescent) Safety Markings, 2010.

ASTM E 2074, Standard Test Method for Fire Tests of Door Assemblies, Including Positive Pressure Testing of Side-Hinged and Pivoted Swinging Door Assemblies,2000 e1 (withdrawn 2007).

ASTM E 2307, Standard Test Method for Determining Fire Resistance of Perimeter Fire Barrier Systems Using Intermediate-Scale, Multi-Story Test Apparatus, 2010.

ASTM E 2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Vinyl Polymeric (Including Vinyl) Wall or Ceiling Coverings, and of Facings and Wood Veneers Intended to be Applied on Site Over a Wood Substrate, to Assess Surface Burning Characteristics, 2010 2012 .

Page 6 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 6 of 39

Page 7: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

ASTM E 2573, Standard Practice for Specimen Preparation and Mounting of Site-Fabricated Stretch Systems to Assess Surface Burning Characteristics, 2012.

ASTM E 2599, Standard Practice for Specimen Preparation and Mounting of Reflective Insulation Materials and , Radiant Barrier, and Vinyl Stretch CeilingMaterials for Building Applications to Assess Surface Burning Characteristics, 2011.

ASTM E 2652, Standard Test Method for Behavior of Materials in a Tube Furnace with a Cone-shaped Airflow Stabilizer, at 750 Degrees C, 2009a 2012 .

ASTM E 2768, Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials (30 min Tunnel Test) , 2011.

ASTM F 851, Standard Test Method for Self-Rising Seat Mechanisms, 1987(2005).

ASTM F 1577, Standard Test Methods for Detention Locks for Swinging Doors, 2005.

ASTM G 155, Standard Practice for Operating Xenon Arc Light Apparatus forExposure of Non-Metallic Materials, 2005a.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 22 12:11:09 EDT 2013

Committee Statement

Committee Statement:

The changes update the standards' edition dates to the most current at the time of the committee's Second Draft meeting. The title of ASTM E2404 has been updated. The title of ASTM E 2599 has been updated. ASTM E 2768 was added for agreement with Chapter 10. ASTM E 2074 was withdrawn and replaced with NFPA 252.

ResponseMessage:

Public Comment No. 59-NFPA 101-2013 [Section No. 2.3.6]

Page 7 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 7 of 39

Page 8: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 19-NFPA 101-2013 [ Section No. 2.3.9 ]

2.3.9 UL Publications.Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096. www.ul.com

ANSI/UL 9, Standard for Fire Tests of Window Assemblies, 2009.

ANSI/UL 10B, Standard for Fire Tests of Door Assemblies, 2008, Revised 2009.

ANSI/UL 10C, Standard for Positive Pressure Fire Tests of Door Assemblies, 2009.

ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, 2011.

ANSI/UL 294, Standard for Access Control System Units, 1999, Revised 2010.

ANSI/UL 300, Standard for Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment, 2005, Revised 2010.

UL 300A, Extinguishing System Units for Residential Range Top Cooking Surfaces,2006.

ANSI/UL 305, Standard for Safety Panic Hardware, 1997, Revised 2011 2012 .

ANSI/UL 555, Standard for Fire Dampers, 2006, Revised 2012.

ANSI/UL 555S, Standard for Smoke Dampers, 1999, Revised 2012.

ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008, Revised 2010.

ANSI/UL 790, Test Methods for Fire Tests of Roof Coverings, 2004, Revised 2008.

ANSI/UL 924, Standard for Emergency Lighting and Power Equipment, 2006, Revised 2011.

ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction, 1996 2009 , Revised 2007 2013 .

ANSI/UL 1315, Standard for Safety for Metal Waste Paper Containers, 2007, Revised 2013 .

ANSI/UL 1479, Standard for Fire Tests of Through-Penetration Firestops, 2003, Revised 2010 2012 .

ANSI/UL 1715, Standard for Fire Test of Interior Finish Material, 1997, Revised 2008 2013 .

ANSI/UL 1784, Standard for Air Leakage Tests for Door Assemblies, 2001, Revised 2009.

ANSI/ UL 1975, Standard for Fire Tests for Foamed Plastics Used for DecorativePurposes, 2006.

ANSI/UL 1994, Standard for Luminous Egress Path Marking Systems, 2004, Revised 2010.

ANSI/UL 2079, Standard for Tests for Fire Resistance of Building Joint Systems, 2004, Revised 2008 2012 .

Submitter Information Verification

Page 8 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 8 of 39

Page 9: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 22 12:13:31 EDT 2013

Committee Statement

Committee Statement:

The changes update the currently referenced UL documents to reflect the edition available at the time of the committee's Second Draft meeting.

Response Message:

Public Comment No. 124-NFPA 101-2013 [Section No. 2.3.9]

Page 9 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 9 of 39

Page 10: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 263-NFPA 101-2013 [ Section No. 2.4 ]

2.4 References for Extracts in Mandatory Sections.NFPA 1, Fire Code, 2012 2015 edition.

NFPA 72®, National Fire Alarm and Signaling Code, 2010 2013 edition.

NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2010 2013edition.

NFPA 88A, Standard for Parking Structures, 2011 2015 edition.

NFPA 221, Standard for High Challenge Fire Walls, Fire Walls, and Fire Barrier Walls, 2015 edition.

NFPA 252, Standard Methods of Fire Tests of Door Assemblies, 2008 2012edition.

NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, 2011 edition.

NFPA 288, Standard Methods of Fire Tests of Floor Fire Door Assemblies Installed Horizontally in Fire Resistance–Rated Floor Systems, 2007 2012 edition.

NFPA 301, Code for Safety to Life from Fire on Merchant Vessels, 2008 2013edition.

NFPA 415, Standard on Airport Terminal Buildings, Fueling Ramp Drainage, and Loading Walkways, 2008 2013 edition.

NFPA 703, Standard for Fire Retardant–Treated Wood and Fire-Retardant Coatings for Building Materials, 2015 edition.

NFPA 914, Code for Fire Protection of Historic Structures, 2010 edition.

NFPA 921, Guide for Fire and Explosion Investigations, 2011 2014 edition.

ASCE/SEI 7, Minimum Design Loads for Buildings and Other Structures, 2010.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 08 09:27:54 EDT 2013

Committee Statement

CommitteeStatement:

NFPA procedures require that the technical committee take action to update the edition date of publications from which text is extracted.

ResponseMessage:

Page 10 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 10 of 39

Page 11: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 44-NFPA 101-2013 [ Section No. 3.3.62 ]

3.3.62 Device.3.3.62.1* Emergency Stair Travel Device.Device designed and constructed to facilitate travel over interior floor surfaces, interior and exterior stairs, and exterior accessible pathways.3.3.62.2 Multiple Station Multiple-Station Alarm Device.Two or more single station single-station alarm devices that can be interconnected so that actuation of one causes all integral or separate audible alarms to operate; or one single station single-station alarm device having connections to other detectors or to a manual fire alarm box. [72,2010 2013 ]3.3.62.2* Stair Descent Device.A portable device, incorporating a means to control the rate of descent, used to transport a person with a severe mobility impairment downward on stairs during emergency egress.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue May 28 11:10:47 EDT 2013

Committee Statement

CommitteeStatement:

The term Emergency Stair Travel Device replaces the term Stair Descent Device in A.7.2.12. This is consistent with how the term is defined and used in the new RESNA document ED-1, Emergency Stair Travel Devices Used by Individuals with Disabilities.

Response Message:

Page 11 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 11 of 39

Page 12: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 45-NFPA 101-2013 [ New Section after 3.3.72 ]

3.3.73 Emergency Stair Travel Device.See 3.3.62.1 .

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue May 28 11:17:46 EDT 2013

Committee Statement

CommitteeStatement:

Cross referencing to assist the user as the term Emergency Stair Travel Device appears under Device in the Dees and not within the Eees.

ResponseMessage:

Page 12 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 12 of 39

Page 13: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 54-NFPA 101-2013 [ Section No. 3.3.125 ]

3.3.126* Grade Plane.A reference plane upon which vertical measurements of a building are basedrepresenting the average of the finished ground level adjoining the building at all exterior walls .3.3.126.1 First Story Above Grade Plane.Any story having its finished floor surface entirely above grade plane, except that a basement is to be considered as a first story above grade plane where the finished surface of the floor above the basement is (1) more than 6 ft (1830 mm) above grade plane or (2) more than 12 ft (3660 mm) above the finished ground level at any point.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 29 13:31:16 EDT 2013

Committee Statement

CommitteeStatement:

The deletion of the definition of Grade Plane, as requested by the Correlating Committee, does not serve the user well. The retained text is needed.

ResponseMessage:

Page 13 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 13 of 39

Page 14: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 30-NFPA 101-2013 [ Section No. 3.3.222.1 ]

3.3.223.1* Fire Protection Rating.The designation indicating the duration of the fire test exposure to which a fire door assembly or fire window assembly an opening protective assembly was exposed.[ 221, 2015]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 22 17:11:44 EDT 2013

Committee Statement

Committee Statement:

Fire dampers also have a fire protection rating so the language should not be limited to just doors and windows.

ResponseMessage:

Page 14 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 14 of 39

Page 15: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 46-NFPA 101-2013 [ Section No. 3.3.265 ]

3.3.266 Stair Descent Device.See 3.3.61.2.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue May 28 11:20:45 EDT 2013

Committee Statement

CommitteeStatement:

The term Stair Descent Device has been replaced with the term Emergency Stair Travel Device.

Response Message:

Page 15 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 15 of 39

Page 16: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 24-NFPA 101-2013 [ Section No. 11.8.5.2.4 ]

11.8.5.2.4The standby power system shall be connected to the following:

(1) Electric fire pump

(2) Jockey pump, except as otherwise provided in 40.4.2 for special-purpose industrial occupancies

(3) Air compressor serving dry-pipe and pre-action systems, except as otherwise provided in 40.4.2 for special-purpose industrial occupancies

(4) Emergency command center equipment and lighting

(5) Not less than one elevator serving all floors, with standby power transferable to any elevator

(6) Mechanical equipment for smokeproof enclosures

(7) Mechanical equipment required to conform with the requirements of Section 9.3

(8) Stairway video monitoring equipment as required by 11.8.8

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 22 14:45:22 EDT 2013

Committee Statement

Committee Statement:

Standby power is needed for the new video monitoring equipment added in section 11.8.8.

Response Message:

Page 72 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 16 of 39

Page 17: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 23-NFPA 101-2013 [ Section No. 11.8.6.2 ]

11.8.6.2The emergency command center shall contain the following:

(1) Voice fire alarm system panels and controls

(2) Fire department two-way telephone communication service panels and controls where required by another section of this Code

(3) Fire detection and fire alarm system annunciation panels

(4) Elevator floor location and operation annunciators

(5) Elevator fire recall switch in accordance with ASME A17.1/CSA B44, Safety Code for Elevators and Escalators

(6) Elevator emergency power selector switch(es) where provided in accordance with ASME A17.1/CSA B44

(7) Sprinkler valve and waterflow annunciators

(8) Emergency generator status indicators

(9) Controls for any automatic stairway door unlocking system

(10) Fire pump status indicators

(11) Telephone for fire department use with controlled access to the public telephone system

(12) Stairway video monitoring equipment as required by 11.8.8

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 22 14:40:44 EDT 2013

Committee Statement

Committee Statement: Item is necessary in recognition of new 11.8.8.

Response Message:

Page 73 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 17 of 39

Page 18: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 20-NFPA 101-2013 [ New Section after 11.8.7 ]

11.8.8 Stairway Video Monitoring.11.8.8.1* General.11.8.8.1.1For high-rise buildings having an occupant load of 4,000 or more persons, real-time remote monitoring of exit stair usage shall be provided in accordance with 11.8.8.2 through 11.8.8.4 and shall be displayed at the emergency command center.11.8.8.1.2Where the monitoring system is integrated with a security system, the security system shall be in accordance with NFPA 731 , Standard for the Installation of Electronic Premises Security Systems . 11.8.8.1.3Where the monitoring system includes video cameras also used for video image smoke detection, the portions of the system used for such detection shall be in accordance with NFPA 72 , National Fire Alarm and Signaling Code .11.8.8.2Approved video monitoring equipment shall be provided at the exit stairs immediately adjacent to exit stairway discharge doors to capture discharge from, entry to, and passage through the discharge floor landing.11.8.8.3Approved video monitoring equipment shall be provided for exit stairs above the level of exit discharge, at building height intervals not exceeding 5 stories, so that descent and ascent flows on the stairways, at the floor entry landings, can be remotely monitored.11.8.8.4Approved video monitoring equipment shall be provided, at locations stipulated by the authority having jurisdiction, for exit stairs below the level of exit discharge where levels are normally occupied by the public.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 22 14:34:21 EDT 2013

Committee Statement

Page 74 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 18 of 39

Page 19: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Committee Statement:

FR-465 The proposed text of 11.8.8 provides additions to the current provision of the code that have the potential to help the fire service, other fire safety personnel and building management to effectively monitor and manage egress during an emergency in a building. The use of equipment that would provide real time data to building’s emergency command centers could lead to better direction of building evacuations and provide the ability for the commandcenter to see conditions throughout the building. This would allow building officials and the fire service to observe if an egress route has become untenable and where they can most effectively redistribute occupants in the building, thus increasing the levels of life safety to occupants throughout the building. A concern regarding privacy of occupants has been raised in the past. However, in a report, “Public Perceptions of High-Rise Building Safety and Emergency Evacuation Procedures” completed for HRB-SAC in 2007 by the Fire Protection Research Foundation, it was found that very few persons have concern over privacy issues if their exit stairwells were equipped with video cameras. When asked about their level of concern over privacy issues if the exit stairwells in their building were equipped with video cameras to permitmonitoring of stairwells during evacuations, about nine out of ten respondents (89 percent) reported they would not be concerned at all. Of the remaining, 7 percent reported they would be somewhat concerned and 3 percent would be very concerned. The High Rise Building Safety Advisory Committee (HRB-SAC) concluded that while this language would provide the ability to better manage and control egress through real-time management, at this time it is only feasible for it to be included in new high-rise buildings with occupant loads of over 4000. The topic of improving situation awareness of what happens in exit stairs during an evacuation is seen as an important topic with regards to occupant life safety and one worthy of new attention in the Code. The proposed language is being submitted for the high-rise building section, 11.8, as the proposed text is strictly a high rise building issue and should be located, along with the other high rise specific issues in the Code. The HRB-SAC committee recognizes that Section 11.8 is applicable to all new high-rise buildings, thus the intent of proposed text is to be applicable to new buildingsonly. Several issues were highlighted in response to the proposed textregarding video monitoring that was submitted during the Public Input stage. This committee has carefully reviewed and evaluated the concerns and responses that were outlined and has addressed all applicable issues in this submission along with the proposed corresponding Annex language (See Section A.11.8.8.1.) The language has been revised from the Public Input stage to more clearly identify the requirements and installation of video monitoring equipment, how it can interface with a building security system, and where it needs to be located. Along with that, references to NFPA 731 and NFPA 72 have been added, as the expert documents on the installation of premises security systems and detection systems. NFPA 731 can be used to provide guidance for combined security and video monitoring systems. The proposed Annex language addresses the benefits of such a system, the performance of the system, and sample design solutions. In addition, the proposed Annex language provides operational criteria that should be taken into consideration when designing and installing the video monitoring equipment. It was not of the opinion of this committee that specific operational and performance criteria be identified in the body of the Code. The performance and operation of the system should be verified with the AHJ to best meet the needs of the building. This public input was prepared by the NFPA High Rise Building Safety Advisory Committee. The HRB-SAC members are: James Quiter (Chair), Arup Geoff Craighead, UniversalProtection Service Jon Magnusson, National Council of Structural EngineersAssociations John Miller, Los Angeles City Fire Department Jack Murphy, Fire Safety Directors Association of Greater New York Steven Nilles, Council on Tall Buildings and Urban Habitat Jake Pauls, American Public Health Association Jim Shea, Tishman Speyer William Stewart, Metropolitan Fire Chiefs-IAFC Sally Regenhard, The Skyscraper Safety Campaign Charles

Page 75 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 19 of 39

Page 20: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

ResponseMessage:

Public Comment No. 129-NFPA 101-2013 [New Section after 11.8.7]

Page 76 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 20 of 39

Page 21: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 47-NFPA 101-2013 [ Section No. A.3.3.62.2 ]

A.3.3.62.1 Emergency Stair Descent Travel Device.A stair descent An emergency stair travel device should be designed, constructed, and operated in accordance with ANSI/RESNA ED-1 , Emergency Stair TravelDevices Used by Individuals with Disabilities . The device typically requires theassistance of a trained operator.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue May 28 11:23:04 EDT 2013

Committee Statement

CommitteeStatement:

The advisory annex is consistent with the change in terminology from Stair Descent Device to Emergency Stair Travel Device and its treatment in the A.7.2.12s.

Response Message:

Page 267 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 21 of 39

Page 22: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 48-NFPA 101-2013 [ Section No. A.4.8.2.1(3) ]

A.4.8.2.1(3)It is assumed that a majority of buildings will use a total evacuation strategy during a fire. It should be noted that evacuation from a building could occur for reasons other than a fire, but such other reasons are not the primary focus of the Code. As used herein, total evacuation is defined as the process in which all, or substantially all, occupants leave a building or facility in either an unmanaged or managed sequence or order. An alternative to total evacuation is partial evacuation, which can be defined as the process in which a select portion of a building or facility is cleared or emptied of its occupants while occupants in other portions mostly carry on normal activity. In either case, the evacuation process can be ordered or managed in accordance with an established priority in which some or all occupants of a building or facility clear their area and utilize means of egress routes. This is typically done so that the more-endangered occupants are removed before occupants in less-endangered areas. Alternative terms describing this sequencing or ordering of evacuation are staged evacuation and phased evacuation.

Table A.4.8.2.1(3) illustrates options for extent of management and extent of evacuation. Some of the options shown might not be appropriate. As noted in Table A.4.8.2.1(3) , either total or partial evacuation can include staged (zoned) evacuation or phased evacuation, which is referred to as managed or controlled evacuation. It should also be noted that the evacuation process might not include relocation to the outside of the building but might instead include relocation to an area of refuge or might defend the occupants in place to minimize the need for evacuation.

Table A.4.8.2.1(3) Occupant Evacuation Strategies

Managed Sequence Unmanaged Sequence

Shelter in placeNo-movement No movement —Shelter-in-place Shelter in place upon direction

No-movement No movement —Shelter-in-place Shelter in placeper prior instruction

Relocation or partial evacuation

Managed or controlled partial evacuation

• In-building relocation on same floor

• In-building relocation to different floors

• Occupants of some floors leave building

Unmanaged movement

Totalevacuation

Managed or controlled total evacuation

Unmanaged or controlled total evacuation

The different methods of evacuation are also used in several contexts throughout the Code. Though most of the methods of evacuation are not specifically defined or do not have established criteria, various sections of the Code promulgate them as alternatives to total evacuation. The following sections discuss these alternatives in more detail:

(1) Section 4.7 — Provides requirements for fire and relocation drills

(2) 7.2.12 — Provides requirements for area of refuge

(3) 7.2.4 — Provides requirements for horizontal exits

Page 268 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 22 of 39

Page 23: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

(4) 9.6.3.6 — Provides the alarm signal requirements for different methods ofevacuation

(5) 9.6.3.9 — Permits automatically transmitted or live voice evacuation or relocation instructions to occupants and requires them in accordance withNFPA 72, National Fire Alarm and Signaling Code

(6) 14.3.4.2.3 (also Chapter 15) — Describes alternative protection systems in educational occupancies

(7) 18.1.1.2/18.1.1.3/Section 18.7 (also Chapter 19) — Provide methods of evacuation for health care occupancies

(8) Chapters 22 and 23 — Provide methods of evacuation for detention and correctional occupancies, including the five groups of resident user categories

(9) Chapters 32 and 33 — Provide methods of evacuation for residential board and care occupancies

(10) 32.1.5/33.1.5 — For residential board and care occupancies, state that “no means of escape or means of egress shall be considered as complying with the minimum criteria for acceptance, unless emergency evacuation drills are regularly conducted”

(11) 40.2.5.2.2 — For industrial occupancies, states that “ancillary facilities inspecial-purpose industrial occupancies where delayed evacuation is anticipated shall have not less than a 2-hour fire resistance–rated separation from the predominant industrial occupancy and shall have one means of egress that is separated from the predominant industrial occupancy by 2-hour fire resistance–rated construction”

The method of evacuation should be accomplished in the context of the physical facilities, the type of activities undertaken, and the provisions for the capabilities of occupants (and staff, if available). Therefore, in addition to meeting the requirements of the Code, or when establishing an equivalency or a performance-based design, the following recommendations and general guidance information should be taken into account when designing, selecting, executing, and maintaining a method of evacuation:

(1) When choosing a method of evacuation, the available safe egress time (ASET) must always be greater than the required safe egress time (RSET).

(2) The occupants’ characteristics will drive the method of evacuation. For example, occupants might be incapable of evacuating themselves because of age, physical or mental disabilities, physical restraint, or a combination thereof. However, some buildings might be staffed with people who could assist in evacuating. Therefore, the method of evacuation is dependent on the ability of occupants to move as a group, with or without assistance. For more information, see the definitions under the term Evacuation Capability in Chapter 3.

(3) An alternative method of evacuation might or might not have a faster evacuation time than a total evacuation. However, the priority of evacuation should be such that the occupants in the most danger are given a higher priority. This prioritization will ensure that occupants more intimate with the fire will have a faster evacuation time.

(4) Design, construction, and compartmentation are also variables in choosing a method of evacuation. The design, construction, and compartmentation should limit the development and spread of a fire and smoke and reduce the need for occupant evacuation. The fire should be limited to the room or compartment of fire origin. Therefore, the following factors need to be considered:

(a) Overall fire resistance rating of the building

Page 269 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 23 of 39

Page 24: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

(b) Fire-rated compartmentation provided with the building

(c) Number and arrangement of the means of egress

(5) Fire safety systems should be installed that compliment complement the method of evacuation, and should include consideration of the following:

(a) Detection of fire

(b) Control of fire development

(c) Confinement of the effects of fire

(d) Extinguishment of fire

(e) Provision of refuge or evacuation facilities, or both

(6) One of the most important fire safety systems is the fire alarm and communication system, particularly the notification system. The fire alarm system should be in accordance with NFPA 72, National Fire Alarm and Signaling Code, and should take into account the following:

(a) Initial notification of only the occupants in the affected zone(s) (e.g., zone of fire origin and adjacent zones)

(b) Provisions to notify occupants in other unaffected zones to allow orderly evacuation of the entire building

(c) Need for live voice communication

(d) Reliability of the fire alarm and communication system

(7) The capabilities of the staff assisting in the evacuation process should be considered in determining the method of evacuation.

(8) The ability of the fire department to interact with the evacuation should be analyzed. It is important to determine if the fire department can assist in the evacuation or if fire department operations hinder the evacuation efforts.

(9) Evacuation scenarios for hazards that are normally outside of the scope of the Code should be considered to the extent practicable. (See 4.3.1.)

(10) Consideration should be given to the desire of the occupants to self-evacuate, especially if the nature of the building or the fire warrants evacuation in the minds of the occupants. Self-evacuation might also be initiated by communication between the occupants themselves through face-to-face contact, mobile phones, and so forth.

(11) An investigation period, a delay in the notification of occupants after the first activation of the fire alarm, could help to reduce the number of false alarms and unnecessary evacuations. However, a limit to such a delay should be established before a general alarm is sounded, such as positive alarm sequence, as defined in NFPA 72, National Fire Alarm and Signaling Code.

(12) Consideration should be given to the need for an evacuation that might be necessary for a scenario other than a fire (e.g., bomb threat, earthquake).

(13) Contingency plans should be established in the event the fire alarm and communication system fail, which might facilitate the need for total evacuation.

(14) The means of egress systems should be properly maintained to ensure thedependability of the method of evacuation.

(15) Fire prevention policies or procedures, or both, should be implemented that reduce the chance of a fire (e.g., limiting smoking or providing fire-safe trash cans).

Page 270 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 24 of 39

Page 25: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

(16) The method of evacuation should be properly documented, and written forms of communication should be provided to all of the occupants, which might include sign postings throughout the building. Consideration should be given to the development of documentation for an operation and maintenance manual or a fire emergency action plan, or both.

(17) Emergency egress drills should be performed on a regular basis. For more information, see Section 4.7.

(18) The authority having jurisdiction should also be consulted when developing the method of evacuation.

Measures should be in place and be employed to sequence or control the order of a total evacuation, so that such evacuations proceed in a reasonably safe, efficient manner. Such measures include special attention to the evacuation capabilities and needs of occupants with disabilities, either permanent or temporary. For comprehensive guidance on facilitating life safety for such populations, go to www.nfpa.org. For specific guidance on emergency stair descent travel devices, see A.7.2.12.2.3 (2) ANSI/RESNA ED-1, Emergency Stair Travel Devices Used by individuals with Disabilities .

In larger buildings, especially high-rise buildings, it is recommended that allevacuations — whether partial or total — be managed to sequence or control theorder in which certain occupants are evacuated from their origin areas and to make use of available means of egress. In high-rise buildings, the exit stairs, at any level, are designed to accommodate the egress flow of only a very small portion of the occupants — from only one or a few stories, and within a relatively short time period — on the order of a few minutes. In case of a fire, only the immediately affected floor(s) should be given priority use of the means of egress serving that floor(s). Other floors should then be given priority use of the means of egress, depending on the anticipated spread of the fire and its combustion products and for the purpose of clearing certain floors to facilitate eventual fire service operations. Typically, this means that the one or two floors above and below a fire floor will have secondary priority immediately after the fire floor. Depending on where combustion products move — , for example, upwards through a building with cool-weather stack effect — , the next priority floors will be the uppermost occupied floors in the building.

Generally, in order to minimize evacuation time for most or all of a relatively tall building to be evacuated, occupants from upper floors should have priority use of exit stairs. For people descending many stories of stairs, this priority will maximize their opportunity to take rest stops without unduly extending their overall time to evacuate a building. Thus, the precedence behavior of evacuees should be that people already in an exit stair should normally not defer to people attempting to enter the exit stair from lower floors, except for those lower floors most directlyimpacted by a fire or other imminent danger. Notably, this is contrary to the often observed behavior of evacuees in high-rise building evacuations where lower floor precedence behavior occurs. (Similarly, in the most commonly observed behavior of people normally disembarking a passenger airliner, people within the aisle defer to people entering the aisle, so that the areas closest to the exit typically clear first.) Changing, and generally managing, the sequence or order in which egress occurs will require effectively informing building occupants and evaluating resulting performance in a program of education, training, and drills.

When designing the method of evacuation for a complex building, all forms of egress should be considered. For example, consideration could be given to an elevator evacuation system. An elevator evacuation system involves an elevator design that provides protection from fire effects so that elevators can be used safely for egress. See 7.2.13 and A.7.2.12.2.4 for more information.

For further guidance, see the following publications:

Page 271 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 25 of 39

Page 26: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

(1) NFPA Fire Protection Handbook, 19th edition, Section 2, Chapter 2, which provides good methodology for managing exposures and determining themethod of evacuation

(2) NFPA Fire Protection Handbook, 19th edition, Section 13, which provides further commentary on methods of evacuation for different occupancies

(3) SFPE Handbook of Fire Protection Engineering, Section 3, Chapter 13,which provides an overview of some of the research on methods ofevacuation

For further guidance, see the following publications:

(1) SFPE Engineering Guide to Human Behavior in Fire, which provides information on occupant characteristics, response to fire cues, decision making in fire situations, and methods for predicting evacuation times.

(2) NFPA Fire Protection Handbook, 19th edition, Section 2, Chapter 2, which provides good methodology for managing exposures and determining themethod of evacuation

(3) NFPA Fire Protection Handbook, 19th edition, Section 13, which provides further commentary on methods of evacuation for different occupancies

(4) SFPE Handbook of Fire Protection Engineering, Section 3, Chapters 11–13,which provide an overview of some of the research on methods of evacuation and methods for predicting evacuation times

Supplemental Information

File Name Description

101_table_A.4.8.2.1_3_.DOCX

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue May 28 11:29:44 EDT 2013

Committee Statement

CommitteeStatement:

The revised text relative to RESNA ED-1 is consistent with revisions made within the A.7.2.12's.

Response Message:

Page 272 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 26 of 39

Page 27: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

First Revision No. 94:NFPA 101-2012 [FR 128: FileMaker]

Table A.4.8.2.1(3) Occupant Evacuation Strategies

Managed Sequence Unmanaged Sequence

Shelter in place No Evacuation

No movement — Remain in place Shelter in place upon direction

No movement — Remain in place Shelter in place

Relocation or partial evacuation

per prior instruction

Managed or controlled partial evacuation • In-building relocation on same floor • In-building relocation to different floors • Occupants of some floors leave building

Unmanaged movement or uncontrolled partial evacuation

Total evacuation Managed or controlled total evacuation

Unmanaged or controlled total evacuation

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 27 of 39

Page 28: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 22-NFPA 101-2013 [ New Section after

A.11.8.6 ]

A.11.8.8.1With video systems, such as standard CCTV security systems typically installed in high-rise buildings, real-time images of occupants’ and emergency responders’ presence and movement (or lack thereof) in exits, especially at multiple locations of the same exit stairway, can provide critical information about current and developing conditions that should be taken into account in emergency management in accordance with the building’s Emergency Action Plan.

Having video cameras positioned to capture images of an exit stairway, including just prior to the discharge doorway from the exit, provides information on the number and flow (in persons per minute, for example) of the occupants, among other information, including access by responding fire fighters using stairs if elevators are not available. It is not essential that the camera views and image resolution be sufficient to identify specific individuals. Depending on the context (including security applications), such specific-person identification might be essential, desirable, undesirable or forbidden. For post-incident evaluation and analysis of egress performance, it is helpful to have image quality and camera angle such that the lateral and front-to-back positions of individuals, relative to the stair width, are clear.

For example, a high-rise building could have cameras at the ground level (assuming this is the level of exit discharge) and at every fifth floor above, and perhaps below grade, for each of the exit stairs. As well as providing a reasonable sampling of evacuee presence and movement within the exit stair system (information important for real-time situation awareness), a comparison of times at which particular individuals pass different cameras provides important data on evacuation movement speed and (indirectly) average occupant density, in addition to flow and number of evacuees overall.

When designing and installing a video monitoring system, and in conjunction with the authority having jurisdiction, the following items should be considered in the operation of the system:

(1) Inspection, testing, and maintenance of equipment

(2) Duration/hours of operation

(3) Storage and retention of information

(4) Activation of the system

(5) Integration with the building’s emergency action plan

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 22 14:36:57 EDT 2013

Page 292 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 28 of 39

Page 29: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Committee Statement:

The proposed text of 11.8.8 provides additions to the current provision of the code that have the potential to help the fire service, other fire safety personnel and building management to effectively monitor and manage egress during anemergency in a building. The use of equipment that would provide real timedata to building’s emergency command centers could lead to better direction of building evacuations and provide the ability for the command center to see conditions throughout the building. This would allow building officials and the fire service to observe if an egress route has become untenable and where they can most effectively redistribute occupants in the building, thus increasing the levels of life safety to occupants throughout the building. A concern regarding privacy of occupants has been raised in the past. However, in a report, “Public Perceptions of High-Rise Building Safety and Emergency Evacuation Procedures” completed for HRB-SAC in 2007 by the Fire Protection Research Foundation, it was found that very few persons have concern over privacy issues if their exit stairwells were equipped with video cameras. When asked about their level of concern over privacy issues if the exit stairwells in their building were equipped with video cameras to permitmonitoring of stairwells during evacuations, about nine out of ten respondents (89 percent) reported they would not be concerned at all. Of the remaining, 7 percent reported they would be somewhat concerned and 3 percent would be very concerned. The High Rise Building Safety Advisory Committee (HRB-SAC) concluded that while this language would provide the ability to better manage and control egress through real-time management, at this time it is only feasible for it to be included in new high-rise buildings with occupant loads of over 4000. The topic of improving situation awareness of what happens in exit stairs during an evacuation is seen as an important topic with regards to occupant life safety and one worthy of new attention in the Code. The proposed language is being submitted for the high-rise building section, 11.8, as the proposed text is strictly a high rise building issue and should be located, along with the other high rise specific issues in the Code. The HRB-SAC committee recognizes that Section 11.8 is applicable to all new high-rise buildings, thus the intent of proposed text is to be applicable to new buildingsonly. Several issues were highlighted in response to the proposed textregarding video monitoring that was submitted during the Public Input stage. This committee has carefully reviewed and evaluated the concerns and responses that were outlined and has addressed all applicable issues in this submission along with the proposed corresponding Annex language (See Section A.11.8.8.1.) The language has been revised from the Public Input stage to more clearly identify the requirements and installation of video monitoring equipment, how it can interface with a building security system, and where it needs to be located. Along with that, references to NFPA 731 and NFPA 72 have been added, as the expert documents on the installation of premises security systems and detection systems. NFPA 731 can be used to provide guidance for combined security and video monitoring systems. The proposed Annex language addresses the benefits of such a system, the performance of the system, and sample design solutions. In addition, the proposed Annex language provides operational criteria that should be taken into consideration when designing and installing the video monitoring equipment. It was not of the opinion of this committee that specific operational and performance criteria be identified in the body of the Code. The performance and operation of the system should be verified with the AHJ to best meet the needs of the building. This public input was prepared by the NFPA High Rise Building Safety Advisory Committee. The HRB-SAC members are: James Quiter (Chair), Arup Geoff Craighead, UniversalProtection Service Jon Magnusson, National Council of Structural EngineersAssociations John Miller, Los Angeles City Fire Department Jack Murphy, Fire Safety Directors Association of Greater New York Steven Nilles, Council on Tall Buildings and Urban Habitat Jake Pauls, American Public Health Association Jim Shea, Tishman Speyer William Stewart, Metropolitan Fire Chiefs-IAFC Sally Regenhard, The Skyscraper Safety Campaign Charles

Page 294 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 29 of 39

Page 30: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

ResponseMessage:

Public Comment No. 130-NFPA 101-2013 [New Section after A.11.8.6]

Page 295 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 30 of 39

Page 31: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 264-NFPA 101-2013 [ Section No. C.1.1 ]

Global SR-68 Hide Deleted

Global SR-342 Hide Deleted

C.1.1 NFPA Publications.

Global SR-68 Hide Deleted

Global SR-342 Hide Deleted

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 1, Fire Code, 2012 2015 edition.

NFPA 10, Standard for Portable Fire Extinguishers, 2010 2013 edition.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2010 2013 edition.

NFPA 13D, Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, 2010 2013 edition.

NFPA 13R, Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height, 2010 2013 edition.

NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2010 2013edition.

NFPA 22, Standard for Water Tanks for Private Fire Protection, 2008 2013 edition.

NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2011 2014 edition.

NFPA 30, Flammable and Combustible Liquids Code, 2012 2015 edition.

NFPA 30A, Code for Motor Fuel Dispensing Facilities and Repair Garages, 2015 edition

NFPA 58, Liquefied Petroleum Gas Code, 2011 2014 edition.

NFPA 61, Standard for the Prevention of Fires and Dust Explosions in Agricultural and Food Processing Facilities, 2008 2013 edition.

NFPA 68, Standard on Explosion Protection by Deflagration Venting, 2007 2013edition.

NFPA 70®, National Electrical Code®, 2011 2014 edition.

NFPA 72®, National Fire Alarm and Signaling Code, 2010 2013 edition.

NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2010 2013edition.

NFPA 88A, Standard for Parking Structures , 2015 edition .

NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, 2012 2015 edition.

NFPA 92, Standard for Smoke Control Systems, 2012 edition.

NFPA 96 , Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations , 2011 edition.

NFPA 99, Health Care Facilities Code, 2012 2015 edition.

Page 323 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 31 of 39

Page 32: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

NFPA 101A, Guide on Alternative Approaches to Life Safety, 2010 2013 edition.

NFPA 105, Standard for Smoke Door Assemblies and Other Opening Protectives, 2010 2013 edition.

NFPA 110, Standard for Emergency and Standby Power Systems, 2010 2013edition.

NFPA 170, Standard for Fire Safety and Emergency Symbols, 2009 2012 edition.

NFPA 204, Standard for Smoke and Heat Venting, 2012 edition.

NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel–Burning Appliances, 2010 2013 edition.

NFPA 220, Standard on Types of Building Construction, 2012 2015 edition.

NFPA 241, Standard for Safeguarding Construction, Alteration, and DemolitionOperations, 2009 2013 edition.

NFPA 251 , Standard Methods of Tests of Fire Resistance of Building Construction and Materials , 2006 edition.

NFPA 252, Standard Methods of Fire Tests of Door Assemblies , 2012 edition

NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, 2011 edition.

NFPA 257, Standard on Fire Test for Window and Glass Block Assemblies , 2012edition

NFPA 259, Standard Test Method for Potential Heat of Building Materials, 2008 2013 edition.

NFPA 260, Standard Methods of Tests and Classification System for Cigarette Ignition Resistance of Components of Upholstered Furniture, 2009 2013 edition.

NFPA 261, Standard Method of Test for Determining Resistance of Mock-Up Upholstered Furniture Material Assemblies to Ignition by Smoldering Cigarettes, 2009 2013 edition.

NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls, 2011 edition.

NFPA 269, Standard Test Method for Developing Toxic Potency Data for Use in Fire Hazard Modeling, 2007 2012 edition.

NFPA 275, Standard Method of Fire Tests for the Evaluation of Thermal Barriers , 2013 edition

NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, 2011 edition.

NFPA 289, Standard Method of Fire Test for Individual Fuel Packages, 2009 2013edition.

NFPA 307, Standard for the Construction and Fire Protection of Marine Terminals, Piers, and Wharves, 2011 edition.

NFPA 409, Standard on Aircraft Hangars, 2011 edition.

NFPA 501A, Standard for Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities, 2009 2013 edition.

NFPA 551, Guide for the Evaluation of Fire Risk Assessments, 2010 2013 edition.

NFPA 601, Standard for Security Services in Fire Loss Prevention, 2010 edition.

NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films, 2010 edition.

Page 324 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 32 of 39

Page 33: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

NFPA 703, Standard for Fire Retardant–Treated Wood and Fire-Retardant Coatings for Building Materials, 2012 2015 edition.

NFPA 720, Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, 2012 2015 edition.

NFPA 850, Recommended Practice for Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations , 2010 edition

NFPA 914, Code for Fire Protection of Historic Structures, 2010 edition.

NFPA 1124, Code for the Manufacture, Transportation, Storage, and Retail Sales of Fireworks and Pyrotechnic Articles, 2006 2013 edition.

NFPA 1221, Standard for the Installation, Maintenance, and Use of Emergency Services Communications Systems, 2010 2013 edition.

NFPA 1600®, Standard on Disaster/Emergency Management and BusinessContinuity Programs, 2010 2013 edition.

NFPA 5000®, Building Construction and Safety Code®, 2012 2015 edition.

NFPA Fire Protection Handbook, 19th edition, 2003.

NFPA Fire Protection Handbook, 20th edition, 2008.

Waksman, D., and J. B. Ferguson. August 1974 2008 . Fire Tests of Building Interior Covering Systems. In Fire Technology, 10:211 – 220.

SFPE Handbook of Fire Protection Engineering, 4th edition, 2008 .

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 08 09:34:24 EDT 2013

Committee Statement

CommitteeStatement:

NFPA 251 was withdrawn. The committee believes that it has deleted all references to NFPA 251 in annex text.

Response Message:

Page 325 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 33 of 39

Page 34: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 66-NFPA 101-2013 [ New Section after C.1.2.5 ]

C.1.2.6 ASSE Publications.American Society of Sanitary Engineering, 901 Canterbury Road, Suite A, Westlake, OH 44145-1480.

ANSI/ASSE A1264.2, Standard for the Provision of Slip Resistance on Walking/Working Surfaces , 2012.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Thu May 30 14:13:29 EDT 2013

Committee Statement

Committee Statement: The standard is referenced in A.7.2.2.3.3.3.

Response Message:

Page 326 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 34 of 39

Page 35: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 41-NFPA 101-2013 [ Section No. C.1.2.6 ]

C.1.2.7 ASTM Publications.ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. www.astm.org

ASTM C 1629/C 1629M, Standard Classification for Abuse-Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels, 2006 (2011).

ASTM D 2859, Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials, 2006 (2011).

ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2012 2013 .

ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, 2012a .

ASTM E 648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source , 2010.

ASTM E 814, Standard Test Method for Fire Tests of Through-Penetration Fire Stops, 2011a.

ASTM E 1352, Standard Test Method for Cigarette Ignition Resistance of Mock-Up Upholstered Furniture Assemblies , 2008.

ASTM E 1353, Standard Test Methods for Cigarette Ignition Resistance of Components of Upholstered Furniture , 2008.

ASTM E 1472, Standard Guide for Documenting Computer Software for Fire Models, 2007 (withdrawn 2011).

ASTM E 1537, Standard Test Method for Fire Testing of Upholstered Furniture, 2012 2013 .

ASTM E 1590, Standard Test Method for Fire Testing of Mattresses, 2012 2013 .

ASTM E 1966, Standard Test Method for Fire-Resistive Joint Systems, 2007 (2011).

ASTM E 2030, Standard Guide for Recommended Uses of Photoluminescent (Phosphorescent) Safety Markings, 2009a.

ASTM E 2174, Standard Practice for On-Site Inspection of Installed Fire Stops,2010a e1.

ASTM E 2238, Standard Guide for Evacuation Route Diagrams, 2002 (withdrawn 2011) 2012 .

ASTM E 2280, Standard Guide for Fire Hazard Assessment of the Effect of Upholstered Seating Furniture Within Patient Rooms of Health Care Facilities, 2009.

ASTM E 2307, Standard Test Method for Determining Fire Resistance of Perimeter Fire Barrier Systems Using Intermediate-Scale, Multi-Story Test Apparatus, 2010.

ASTM E 2393, Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers, 2010a.

ASTM E 2484, Standard Specification for Multi-Story Building External Evacuation Controlled Descent Devices, 2008.

Page 327 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 35 of 39

Page 36: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

ASTM E 2513, Standard Specification for Multi-Story Building External Evacuation Platform Rescue Systems, 2007.

ASTM E 2768, Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials , 2011.

ASTM F 1637, Standard Practice for Safe Walking Surfaces, 2010.

ASTM F 1870, Standard Guide for Selection of Fire Test Methods for the Assessment of Upholstered Furnishings in Detention and Correctional Facilities,2011.

Submitter Information Verification

Submitter Full Name: Jeanne Moreau-Correia

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Tue May 28 09:56:45 EDT 2013

Committee Statement

CommitteeStatement:

Standards editions updated to reflect edition dates current at time of committee's Second Draft meeting. Also, at request of SAF-MEA, ASTM E 2238 was changed from "withdrawn 2011" to "2012" edition to reflect the reinstatement of the document.

ResponseMessage:

Public Comment No. 112-NFPA 101-2013 [Section No. C.1.2.6]

Page 328 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 36 of 39

Page 37: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 43-NFPA 101-2013 [ New Section after

C.1.2.11 ]

C.1.2.12 RESNA Publications.Rehabilitation Engineering and Assistive Technology Society of North America, 1700 N Moore St, Suite 1540, Arlingtron, VA 22209.

ANSI/RESNA ED-1, Emergency Stair Travel Devices Used by Individuals with Disabilities, Volume 1 , 2013.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue May 28 11:03:06 EDT 2013

Committee Statement

CommitteeStatement:

The new RESNA document is being referenced by revised text within A.7.2.12.

Response Message:

Page 329 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 37 of 39

Page 38: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 42-NFPA 101-2013 [ Section No. C.1.2.12 ]

C.1.2.14 UL Publications.Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096. www.ul.com

UL Fire Resistance Directory, 2012 2013 .

ANSI/UL 217, Single and Multiple Station Smoke Alarms , 2012.

ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, 2003,Revised 2011.

ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008, Revised 2010.

ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction, 1996 2009 , Revised 2007 2013 .

ANSI/UL 1479, Standard for Fire Tests of Through-Penetration Firestops, 2003, Revised 2010 2012 .

ANSI/UL 1715, Standard for Fire Test of Interior Finish Material, 1997, Revised 2008 2013 .

ANSI/ UL 1975, Standard for Fire Tests for Foamed Plastics Used for Decorative Purposes, 2006.

ANSI/UL 2079, Standard for Tests for Fire Resistance of Building Joint Systems, 2004, Revised 2008 2012 .

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue May 28 10:32:15 EDT 2013

Committee Statement

CommitteeStatement:

The changes update the currently referenced UL documents to reflect the edition available at the time of the committee's Second Draft meeting. The change also adds UL 217 to the list as the SAF-BSF committee added Annex A text that references the document.

ResponseMessage:

Public Comment No. 125-NFPA 101-2013 [Section No. C.1.2.12]

Page 330 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 38 of 39

Page 39: SAF-FUN SECOND REVISIONS WITH STATEMENTS Page 1 of 39

Second Revision No. 265-NFPA 101-2013 [ Section No. C.3 ]

C.3 References for Extracts in Informational Sections.NFPA 80 , Standard for Fire Doors and Other Opening Protectives , 2010 edition.

NFPA 72 ® , National Fire Alarm and Signaling Code , 2013 edition.

NFPA 88A , Standard for Parking Structures , 2015 edition.

NFPA 5000®, Building Construction and Safety Code®, 2012 2015 edition.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 08 09:44:11 EDT 2013

Committee Statement

CommitteeStatement:

NFPA procedures require that the technical committee take action to update the edition date of publications from which text is extracted. No extracts within the annex text come from NFPA 80, so the document was deleted from the list.

Response Message:

Page 331 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-FUN SECOND REVISIONS WITH STATEMENTS

Page 39 of 39