S8000-E Ring Network

98

Click here to load reader

Transcript of S8000-E Ring Network

Page 1: S8000-E Ring Network

!"

#$ %

& '(

!'()*

&*

!

%

!)

& '+

, -&

( #

&).

),*/

"!')

* !#

"!$

$#%

)0#*

1

, &)

(, ,+

%, ,

!% +

#&!(

),+

&)!

%

! "

# "

# $

%

!

&

&

'

(

"

#

&

#

"&

# $

)

# "

# #

&

# *

&

+

%& (%+. !"#$ %&+&)!%

, ,

4 56

C. KERVENEC

PowerElectrical and Control Systems

P–TP20–A40561 E

B

2 2 -

3 2 %

Page 2: S8000-E Ring Network

" # !#$%$ $! &

? (@ % " +.A!% +%& (! )(,& @ (,)!%

6 7 56

Page 3: S8000-E Ring Network

8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > &

Page 4: S8000-E Ring Network

' (

1. FOREWORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 2

2. INTRODUCTION AND NOTICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 2

3. DEFINITION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 3

4. ETHERNET / FAST ETHERNET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 4

4.1. THE OSI MODEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 4

4.2. TOPOLOGY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3. ACCESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 5

SHEET 6

4.4. FAST ETHERNET 100 MBITS/S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 6

4.5. 10BASE–T HUBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.6. 100BASE–T HUBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.7. 10BASE–T SWITCHES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.8. 100BASE–T SWITCHES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.9. 10 MBITS/S ETHERNET WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.9.1. 10BASE5 (thick Ethernet) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 7

SHEET 8

SHEET 9

SHEET 9

SHEET 11Sheet 11

4.9.2. 10BASE2 (ThinWire, Cheapernet) . . . . . . . . . . . . . . . . . . . . . . . .

Sheet 11

4.9.3. 10BASE–T (twisted pair) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Sheet 12

4.9.4. 10BASE–F (fiber optic) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Sheet 13

4.10. 100 MBITS/S FAST ETHERNET WIRING . . . . . . . . . . . . . . . . . . . . . . .

SHEET 14

4.10.1. 100BASE–TX4.10.2. 100BASE–FX

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . .. . . . . . . . . . . . . . . . . . . . . . . . . .

Page 5: S8000-E Ring Network

. . . . . . . . . . . . . . . . Sheet 14 Sheet 14

5. TECHNOLOGY UTILIZED FOR THE S8000–E NETWORK . . . . . . . . .

SHEET 15

5.1. INTERFACE WITH P320 SYSTEM DEVICES . . . . . . . . . . . . . . . . . . . .

SHEET 16

5.1.1. Interface with the C80–35 Cell Controller5.1.2. Interface with the C80–75 Cell Controller5.1.3. Interface with the CSS–F Front End PC

. . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . .

Sheet 16Sheet 17Sheet 18

5.1.4. Interface with the Centralog Control Room . . . . . . . . . . . . . . . . .

Sheet 19

5.1.5. Combining S8000–E and CONTRONET Networks . . . . . . . . . .

Sheet 22

5.1.6. Interface with the Controcad Engineering PC . . . . . . . . . . . . . . .

Sheet 23

6 7 56

Page 6: S8000-E Ring Network

6. PRESENTATION OF THE 10 MBITS/S S8000–E RING . . . . . . . . . . . . .

SHEET 24

6.1. GENERAL HARDWARE CHARACTERISTICS . . . . . . . . . . . . . . . . . .

SHEET 24

6.2. HARDWARE USED FOR THE 10 MBITS/S RING . . . . . . . . . . . . . . . .

SHEET 25

6.3. REDUNDANCY OF THE S8000–E 10 MBITS/S RING . . . . . . . . . . . .

SHEET 28

6.4. DOUBLE CONNECTION OF A S8000–E 10 MBITS/S SUSCRIBER SHEET 31

6.5. S8000–E 10 MBITS/S DOUBLE RING . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 32

6.6. HUB MALFUNCTION MANAGEMENT ON THE S8000–E 10 MBITS/S RING . . . .SHEET 33

6.7. SUPPLEMENTARY HARDWARE ON THE S8000–E 10 MBITS/S RING . . . . . . . .SHEET 34

7. 100 MBITS/S S8000–E RING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 35

7.1. GENERAL CHARACTERISTICS OF THE HARDWARE USED . . . . SHEET 35

7.2. HARDWARE USED FOR THE S8000–E 100 MBITS/S RING . . . . . .

SHEET 36

7.3. REDUNDANCY OF THE 100 MBITS/S S8000–E RING . . . . . . . . . . .

SHEET 41

7.4. DOUBLE CONNECTION OF A S8000–E 100 MBITS/S SUSCRIBER SHEET 44

7.5. S8000–E 100 MBITS/S DOUBLE RING . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 45

7.6. MANAGEMENT OF ENCLOSURE MALFUNCTIONS (HUB OR SWITCH) . . . . . .SHEET 47

7.7. SUPPLEMENTARY HARDWARE FOR 100 MBITS/S S8000–E RING SHEET 48

7.8. MANAGEMENT OF THE NETWORK VIA THE 100 MBITS/S S8000–E WEBINTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 49

8. MULTIPLE–RING S8000–E ARCHITECTURE . . . . . . . . . . . . . . . . . . . . .

SHEET 50

9. POWER SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 52

10. APPLICABLE DATA SHEETS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 53

10.1. S8000–E NETWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SHEET 53

Page 7: S8000-E Ring Network

6 7 56

Page 8: S8000-E Ring Network

ALSPA P320 SYSTEM

S8000–E UNIT NETWORK

CONFIGURATION RULES

6 7

Page 9: S8000-E Ring Network

1. Foreword

The present document describes the topology configuration rules applicable to theS8000–E unit network.

2. Introduction and Notice

The S8000–E unit network has been validated by T3 as implementing the Hirschmann range of Ethernet DIN Rail components (Hubs and Switches). The present document therefore covers only this solution.

Solutions using Ethernet components (Hubs, Switches etc.) implementing other technologies are not administered by the development teams. This provision applies for the full range of development activities: definition of the topology configuration rules, test and implementation of devices, documentation, datasheets, anomalymanagement etc.

3. Definition

The Alspa P320 power plant control and supervision system integrates three networks based on Ethernet technology:

The Ethernet site network manages communications between the operator stations and peripherals: the printers, X–terminals, office PCs and modems for remote communications (remote maintenance, access to Centralog variables via Internet technology). It also manages communications between the CONTROCAD engineering PC and the Centralog for the purpose of downloading the views and database produced by CONTROCAD.

The CONTRONET network manages the exchange of variables between the servers and the operator stations in the CENTRALOG control room for the purpose of animating the operating views, for the production of operating logs,

Page 10: S8000-E Ring Network

storage of variables and communications with alien systems (dispatching or remote access). This type of network is only utilized in CENTRALOG 30 or 50 architectures.

The S8000–E unit network is used to manage communications between the C80–35 or C80–75 cell controllers, the control stations in the CENTRALOG control room and the CSS–F interface devices (implementation on a case–by–case basis for specific interfaces).

It is also used to download the cell controllers from the CONTROCADengineering station, and for the observation and tuning of the control functions.

In certain types of architecture, the S8000–E and CONTRONET unit networks can co–exist on a single physical medium as described in the paragraph “Combining S8000–E and CONTRONET unit networks”.

The Ethernet site network, the CONTRONET network and the S8000–E unit network may be based on Ethernet or Fast Ethernet technology, depending on the configuration chosen.

This document describes only the S8000–E unit network, the other networks are described in the document “CENTRALOG Configuration Rules”.

4. Ethernet / Fast Ethernet

4.1. THE OSI MODEL

The ISO/OSI model (International Standardization Organization/ Open Systems Interconnection) is a 7–layer model describing the OSI protocols. This model is often used to describe the architecture of the networks and the corresponding protocols.

The 7–layer ISO model defines the protocols that allow systems to communicate among themselves on each layer.

The different layers (or levels) are:

Level 1: Physical bit (lowest level).This is the transparent transmission of bit sequences via any medium. Supports different transmission modes, without explicit error processing.

Level 2: Data linkEstablishment of a correct link between the system and the network access, assembly of data into blocks, synchronization of blocks, detection and correction of transfer errors.

Level 3: NetworkChoice and control of the network used for transmission, routing mediation,

Page 11: S8000-E Ring Network

connection between networks, multiplexing of physical network access.

Level 4: TransportEstablishment and maintenance of a virtual link between two processing units (end–to–end), delivery of an independent mechanism of transmission from a particular network, attribution of an address to the interlocutor.

Level 5: Communication controlEstablishment and control of the communication session, access control, definition of distribution points.

Level 6: PresentationUnified global presentation of information, data compression, interpretation, encryption.

Level 7: ApplicationSpecific applications (file transfer, message transfer, information systems etc.).

4.2. TOPOLOGY

The topology of a network is defined by the type of physical connection used for the network intersections. In general, there are four standard connection types, i.e.

Bus: in a topology of this type, communication between the network stations takes place over a shared cable. A typical example of this topology is the thick Ethernet cable (10BASE5) or thin Ethernet cable (10BASE2).

Star: from a central point (Hub, Switch), a point–to–point link is established with the network intersections. The Ethernet hub with Ethernet twisted pair (10BASE–T) wiring connecting all the network intersections is an example of this topology.

Ring: as the name indicates, the cable linking the different network intersections is in the form of a ring. The utilization of industry standard hubs or switches provides an Ethernet solution that can administer communications redundancy.

Tree: a tree structure is obtained when the hubs or switches are deployed in cascade form by point–to–point links.

The topology implemented in the context of the S8000–E unit network is that of an Ethernet or Fast Ethernet network in a secure ring structure integrating fault tolerance mechanisms.

4.3. ACCESS

Standard Ethernet, Fast Ethernet and Gigabit Ethernet all use the same access procedure.

Page 12: S8000-E Ring Network

One of the features of Ethernet and of the IEEE 802.3 standard is the fact that a large number of stations can use one single line of communication, without any one of the stations controlling access to the line.

When a station needs to transmit data, it first checks that the communications channel is available (CS = Carrier Sense): if the channel is available, the station starts to transmit. At the same time, the station listens in to the signal on the cable. If another station has started to transmit (almost) simultaneously (MA = Multiple Access), the signal collision is detected (CD = Collision Detect) and the transmitting station briefly sends a jam signal to inform other stations that the data transmitted is invalid. The transmitting station then retransmits after a random delay. This process is known as CSMA/CD.

The use of switches on fast 100 Mbits/s networks enables simultaneous communications by different subscribers, as each section between two switches is considered as a distinct network in terms of access. The implementation of these technologies enables the network to be rendered deterministic.

4.4. FAST ETHERNET 100 MBITS/S

Fast Ethernet 100BASE–T is standardized as IEEE 802.3u by the IEEE committee.

The physical interface is defined on the physical layer. This is known as the

AttachmentUnit Interface (AUI) for 10 Mbits/s Ethernet, and as the Medium Independent Interface(MII) for 100 Mbits/s Fast Ethernet .

A self–negotiation function can be provided for the stations, PCs and switches. This function enables the transmission mode of the subscriber (10 or 100 Mbits/s) to be recognized automatically.

4.5. 10BASE–T HUBS

Several Ethernet segments – thin, thick or other Ethernet cable types – can be interconnected by hubs or switches.

This allows the maximum length for a 10BASE5 (500 m) or 10BASE2 (185 m) segment to be extended. The hubs also increase the availability of the networks, which are divided into sub–segments: hubs thus prevent the interference generated by one segment from being transmitted to another.

A hub is a signal amplifier which has more than one (minimum two) network connections. It operates on the physical layer of the OSI model. As soon as it receives the first bits of a frame at one of its inputs, it retransmits these instantly to all its outputs. A hub does not modify data in any way.

Multiport 10BASE–T hubs normally are fitted with 8 or 16 ports (RJ45), and sometimes more. They also have least one additional port available for the connection of a further segment.

Stackable multiport hubs are connected via special ports to form a hub stack. There

Page 13: S8000-E Ring Network

are two methods of connecting hubs:

in the first method hubs are interconnected by means of a thin Ethernet cable.This is possible since the hubs are fitted in series with a 10BASE2 connector. In this case, each hub counts as one hub according to the hub configuration rules.

in the second method the hubs are interconnected by means of special bus ports and by very short bus cables. In this case, the interconnected hubs count as one hub according to the hub configuration rules.

Hub configuration rules: there may never be more than two pairs of hubs between any two stations, inasmuch as these stations are not separated by bridges, switches or routers. A transmission path is composed of a maximum of five segments and a maximum of four sets of hubs. Each set consists of two pairs of hubs. In this construction, up to three of the segments linking the stations may be of coaxial type. The other segments must be point to point links, to provide inter–hub links.

The S8000–E unit network utilizes RH1–TP/FL hubs in the 10 Mbits/s ring topology. The technology chosen enables the standard hub configuration rule to be surpassed. The S8000–E ring can incorporate up to 13 hubs (cf Chapter “10 Mbits/s OpticalRing”).

4.6. 100BASE–T HUBS

100 Mbits/s Fast Ethernet hubs operate like 10 Mbits/s Ethernet hubs the only difference being a higher rate of data transfer.

The Ethernet standard defines a maximum ”Round Trip Delay” within each collision domain of 576 bit periods. This corresponds to 5.76 microseconds at 100 Mbits/s and57.6 microseconds at 10 Mbits/s. This value defines the maximum geographicalextension of a network within the collision domain. If the signal time exceeds this value, a collision is recognized by default. Thus when fiber optic cables are used along with class II hubs, the geographical diameter of a collision domain changes from 2,500 m for Ethernet 10 Mbits/s to 205 m for Fast Ethernet 100 Mbits/s.

The 100BASE–T standard recognizes two classes of hub: class I hubs and class IIhubs.

class I hubs have a longer round–trip delay than class II hubs. Only one class I hub may be located between two connected peripherals for a maximum cable length of 100 m between node and hub (utilization of twisted pair cable).

class II hubs have a round–trip of 0.46 microseconds or less. Two class II hubs can be connected between peripherals for a maximum cable length of 100 m between node and hub (utilization of twisted pair cable). The inter–hub link between the two hubs may be no longer than 5 m.

However a hub that is cascaded via an internal bus enables the number of ports to be increased without breaking the hub configuration rules. In this case, the hubs are “stacked” and thus count as one single hub.

Fiber optic components can be used to increase the range of the network.

Page 14: S8000-E Ring Network

The S8000–E unit network uses 100 Mbits/s switches instead of 100 Mbits/s hubs to ensure determinism and provide a flexible network architecture.

4.7. 10BASE–T SWITCHES

These switches transform the Ethernet bus structure into a bus/star structure. Partial segments with a bus structure are connected together to the ports of the switch in the form of a star. Packets can be transmitted between the ports at the maximum Ethernet speed. The switches can execute several simultaneous transmissions between different segments. The bandwidth of the whole network is increased in a corresponding manner.

These switches are used to obtain a deterministic system network architecture.

The S8000–E unit network uses 100 Mbits/s switches instead of 10 Mbits/s switches to ensure determinism and performance, and to provide a flexible network architecture.

4.8. 100BASE–T SWITCHES

100BASE–T Fast Ethernet switches operate according to the same principle as10BASE–T switches.

Certain Fast Ethernet switches can regulate the transmission proprieties of one or more ports (full or half duplex, 10 or 100Mbits self–negotiation).

Because of restrictions on the length of cables, switches must be used when extending Fast Ethernet networks. The utilization of a switch results in the creation of a new collision domain. In Fast Ethernet technology the bandwidth of the network is increased when switches are used.

There are two fast switching solutions: ”on–the–fly” and ”store–and–forward”.

In the “on–the–fly” solution the switch does not wait to read the whole packet before transmitting. It only needs to receive the 6–byte address. This allows the time delay to be reduced. If the receiving segment is busy, the switch stores the packet.

The “store–and–forward” solution meets the IEEE standard. Products that implement this solution do not only read the 6–byte destination address, but also check the quality of the packet. The packet is only retransmitted if and when it is received correctly andentirely. This process avoids the retransmission of defective packets.

Which technology is preferable ?

Page 15: S8000-E Ring Network

”on–the–fly” switching is preferable when a very short time delay is needed for retransmission between two nodes. This technology should therefore be used when a large number of variables must be transferred between a small number of nodes on a relatively limited network.

the ”store–and–forward” solution is advantageous for more complex networks and communication channels because defective segments are prevented from overloading the network following collisions. In these cases, the overall transfer rate is of primary importance and and the delay is secondary. This solution is implemented by Hirschmann RS2 switches.

The S8000–E unit network utilizes RS2 switches in the 100 Mbits/s ring topology. The technology chosen allows the flexibility of the architecture to be managed. The S8000–E ring can incorporate up to 50 switches (cf Chapter “100 Mbits/s optical or copper ring”).

The “Store and Forward” solution is implemented by Hirschmann RS2 switches. All variables received by the RS2 switch is stored and its validity is checked. Invalid packets or frames are abandoned (CRC and size check). Only valid variables are transmitted to other subscribers on the network, which prevents invalid variables fromoverloading the network and reducing overall performance.

4.9. 10 MBITS/S ETHERNET WIRING

4.9.1. 10BASE5 (thick Ethernet)

The 10BASE5 Ethernet cable is also designated thick Ethernet or yellow cable.

The physical medium is a coaxial cable.

In the simplest 10BASE5 Ethernet configuration, each station is connected to a transceiver and a drop cable via an AUI connector.

The maximum length of this type of cable is 500 meters per segment, with up to 100 transceivers connected. The distance between two transceivers must be at least 2.5m or a multiple of this length.

The Ethernet cable does not need to be cut to install a transceiver; instead the cable is pierced and the transceiver is connected electrically to the coaxial cable by means of a pin. Since the cable does not need to be cut, network operations can continue without interruption.

A transceiver (transmitter–receiver) both receives and transmits data. It handles transmissions without signal regeneration over a 500 m length of cable. It also ensures collision recognition, ”carrier sensing” and the generation of the preamble (synchronization signal).

The transceiver also isolates the station and the10BASE5 Ethernet cable electrically. The transceiver is powered via the drop cable from the station.

The S8000–E unit network does not use 10BASE5 wiring.

Page 16: S8000-E Ring Network

4.9.2. 10BASE2 (ThinWire, Cheapernet)

This version of Ethernet corresponds to the10BASE2 standard and functions in principle like the Ethernet 10BASE5, but with a much thinner and more flexible coaxial cable. It is also less costly, which explains the designation Cheapernet.

If the workstations and PCs are delivered with a direct Ethernet 10BASE2 connection, there is no need for a transceiver and a drop cable.

Stations with an AUI socket can be fitted with a drop cable and an Ethernet 10BASE2 transceiver.

Ethernet 10BASE2 mini–transceivers can be connected directly to the AUI socket without a drop cable.

The main drawbacks of Ethernet 10BASE2 are the maximum total length of the cable(185 m) and the maximum number of stations (limited to 30). The minimum distance between two stations is 0.5 m).

Furthermore, when a station is installed on an Ethernet 10BASE2, the cable must be cut. A T–connector links the adaptor to each of the two cut cable ends. The T–connector must be connected directly to the adapter and may not be extended by a coaxial cable.

The two ends of a thin Ethernet cable must be fitted with a 50 Ohm terminator (as with other types of cable, the transfer of data is impossible if the two extremities are not terminated). If the cable is open (e.g. during the installation of a new system, or even by mistake) the communication is blocked.

The utilization of hubs restricts errors to one segment and prevents their propagation to other segments.

The S8000–E unit network does not use 10BASE2 wiring.

4.9.3. 10BASE–T (twisted pair)

High quality Ethernet 10BASE–T (twisted pair) wiring is used for the transmission of faster signals (e.g. Fast Ethernet, Gigabit Ethernet ).

UTP (Unshielded Twisted Pair) or SUTP (Screened Unshielded Twisted Pair) cables may be used. These cables conform to the EIA/TIA 568 TSB–36 (Technical System Bulletin) standard with regard to category 5 attenuation and impedance. Twisted pair Ethernet cables must therefore in all cases conform to category 5.

10BASE–T or twisted pair Ethernet wiring uses a point to point type connection with a maximum length of 100 m.

A distinction is made between paired transmission and reception lines. There are thus two types of cable: crossed cable, or direct cable.

10BASE–T wiring is used in the S8000–E unit network to connect subscribers to theRH1–TP/FL hubs or RS2 switches on the ring.

Page 17: S8000-E Ring Network

4.9.4. 10BASE–F (fiber optic)

Fiber optic cable incorporates a filament of silicon or plastic matter used to transport an optical ray. Two types of fibers are used: multimode fibers with relatively large diameters generate several modes of propagation, which limits the distance (in general less than 3,000 m), and monomode fibers which have a very thin glass core and which generate a single mode of propagation, which gives them a very high flow rate.

The speed of propagation is in the order of 100,000 km per second for multi–mode fiber and 250,000 km per second for single–mode fiber .

Fiber optic cables present a number of advantages:

very large bandwidth: in the order of 1 GHz for 1 km,

physically small and very light,

very low attenuation,

very high quality of transmission,

good resistance to temperature changes,

good resistance to cold and heat,

no EMI radiation.

However the installation of fiber optics necessitates the utilization of specialized personnel and equipment.

Fiber optic Ethernet, like twisted pair Ethernet wiring, can only be used for point to point links. Because of this, fiber optic is principally utilized for links between switches and/or hubs.

In general, the cable used is a multimode cable fitted with ST or SC connectors. The maximum length of cable for 10BASE–FL components is 3,000 m.

The length of a single mode cable may be 10,000 m or more.

Multimode 10BASE–FL wiring is used in the S8000–E unit network to inter–connect the RH1–TP/FL hubs on the 10 Mbits/s ring.

4.10. 100 MBITS/S FAST ETHERNET WIRING

IEEE802.3u 100BASE–T wiring is based on the principle of point to point

connections. Coaxial cable cannot be used.

100BASE–T supports three physical layers: two of these layers (100BASE–TX and100BASE–T4) define a 100 m length of twisted pair wiring and the third (100BASE–FX) a multimode (2,000 m in full duplex mode) or single–mode (10,000 m or more) fiber optic wiring segment.

Page 18: S8000-E Ring Network

4.10.1. 100BASE–TX

100BASE–TX: because of the high frequency, requires two–pair UTP cable, category5 or a two–pair type 1 IBM STP cable.

4–pair UTP–5 wiring provides optional utilization in full duplex mode (200 Mbits/s) if this mode is supported by the interconnected devices.

Full duplex mode is possible between the station and the switch or between two switches.

For 100BASE–TX, the 8–pole RJ45 connector is identical to that used for 10BASE–

T. The maximum length of a twisted pair segment is100 m.

100BASE–TX wiring is used in the S8000–E unit network to interconnect the RS2 switches on the 100 Mbits/s copper ring and to connect the 100 Mbits/s subscribers to the RS2 switches on the ring.

4.10.2. 100BASE–FX

100BASE–FX specifies single pair fiber optic wiring (multi–mode or single–mode. The maximum length of fiber optic segments varies according to the components used.

For a switch–to–switch or switch to adaptor connection, a maximum length of 412 m can be attained by using multimode wiring. If full duplex mode is supported, this distance can be extended to 2,000 m.

In full duplex mode single mode wiring enables distances of up to 10,000 meters or more to be attained.

100BASE–FX multimode or 100BASE–FX–SM single mode wiring is used in the S8000–E unit network to interconnect the RS2 switches on the 100 Mbits/s optical ring.

5. Technology Utilized for the S8000–E Network

The S8000–E unit network implements a solution based on one or more Ethernet or Fast Ethernet high performance rings integrating concepts of safety and redundancy based on the principle of fault tolerance.

The availability of this solution depends on the configuration chosen: 10 or 100Mbits/s, optical, multimode, single mode or copper twisted pair technology.

Page 19: S8000-E Ring Network

5.1. INTERFACE WITH P320 SYSTEM DEVICES

5.1.1. Interface with the C80–35 Cell Controller

The interface between the cell controller and the S8000–E unit network is provided by the Ethernet EEM interface module on the UT364 processing unit in the C80–35 controller.

The EEM interface module is integrated to the UT364 and occupies the same slot as the processing unit in the C80–35 cell controller rack.

The EEM interface module provides a connection to the S8000–E network in single medium mode whether the solution implemented for the network is single or dual/ redundant.

D & ($)%+.

)& &> (% &

6

9

Page 20: S8000-E Ring Network

6 6

C

5

C

5

.,'+ 9 5 " .. "!%&(!.. (,

9

6 7 56 8,& $

Page 21: S8000-E Ring Network

5.1.2. Interface with the C80–75 Cell Controller

The interface between the cell controller and the S8000–E unit network is provided by an Ethernet CMM742 interface module on the controller C80–75.

The CMM742 interface module occupies a single slot in the C80–75 cell controller rack.

The CMM742 interface module provides a connection to the S8000–E network in single medium mode whether the solution implemented for the network is single or dual/redundant.

D & ($)%+.

)& &> (% &

6

9

6 6

6

6

6

6

.,'+ 9 " .. "!%&(!.. (,

9

6 7

Page 22: S8000-E Ring Network

56 8,& $

Page 23: S8000-E Ring Network

E

5.1.3. Interface with the CSS–F Front End PC

The interface between the CSS–F Front End PC and the S8000–E unit network is provided by a Fast Ethernet interface module.

The interface module provides a connection to the S8000–E network in single medium mode whether the solution implemented for the network is single ordual/redundant.

D & ($)%+.

)& &> (% &

6

9

6 6

(!%& % E

6 7

Page 24: S8000-E Ring Network

56 8,& $

Page 25: S8000-E Ring Network

5.1.4. Interface with the Centralog Control Room

The CENTRALOG control room can be connected to three Ethernet networks depending on the type of configuration:

The Ethernet site network manages communications between the operator stations and peripherals: printers, X–terminals, office PCs, modems for remote communications (remote maintenance, access to Centralog variables via Internet technology). It also manages communications between the CONTROCAD engineering PC and the Centralog for the purpose of downloading the views and database produced by CONTROCAD.

The CONTRONET network manages the exchange of variables between the servers and the operator stations in the CENTRALOG control room for the purpose of animating the operating views, for the production of the operating logs, storage of the variables and communications with alien systems (dispatching or remote access). This type of network is only used in CENTRALOG 30 or 50 architectures.

The S8000–E unit network manages data communications between the C80–35 or C80–75 cell controllers, the command stations in the CENTRALOG control room and the CSS–F interface devices.

In certain types of architecture, the S8000–E and CONTRONET unit networks can co–exist on a single physical medium as described in the paragraph “Combining the S8000–E unit networks and CONTRONET”.

The interface between the CENTRALOG (Unix Station or PC NT) and the S8000–Eunit network is provided by a Fast Ethernet interface module.

The interface module provides a connection to the S8000–E network in single medium mode whether the solution implemented for the network is single or dual/redundant.

Page 26: S8000-E Ring Network

6 7

Page 27: S8000-E Ring Network

9

<)

. 3#,

9

<)

. 3#,

The figure below shows a C10–based CENTRALOG architecture:

Controcad server

9 5 !( 9 " .. "!

%&(!.. (

9 5 !( 9 " .. "!

%&(!.. (

9 5 !( 9 " .. "!

%&(!.. (

9 5 !( 9 " .. "!

%&(!.. (

Controcad client

.,'+ 9 5 <) . "!%&(!.. (

.,'+ 9 5 <) . "!%&(!.. (

.,'+ 9 5 <) . "!%&(!.. (

.,'+ 9 5 <) . "!%&(!.. (

Controcad client

.,'+ 9 5 E @)"

.,'+ 9 5 E @)"

6 7

Page 28: S8000-E Ring Network

9

<)

. 3#,

9

<)

. 3#,

The figure below shows a C30/C50–based CENTRALOG architecture:

!) & *

! !

Controcad

9 5 !( 9 5 !( 9 5 9 5 !( 9 5 F G 9 9 9 " ..

" .. " .. " " .. "!%&(!.. ("!%&(!.. ( "!%&(!.. ( "!%&(!.. "!%&(!.. (

+(&% ( '(! #"&, +(&% ( '(! #"&, .,'+ 9 5

<) . "!%&(!.. (

.,'+ 9 5 <) . "!%&(!.. (

.,'+ 9 5 <) . "!%&(!.. (

.,'+ 9 5 <) . "!%&(!.. (

! 3#,

.,'+ 9 5 E @)"

.,'+ 9 5 E @)"

6 7

Page 29: S8000-E Ring Network

9

<)

. 3#,

9

<)

. 3#,

5.1.5. Combining S8000–E and CONTRONET Networks

The S8000–E and CONTRONET unit networks can be combined on a single physical medium. This solution is based exclusively on a fault tolerant Fast Ethernet ring fitted with RS2 switches.

The connection between the CENTRALOG and the Fast Ethernet ring is a single medium connection. A single Ethernet port on the interface module in the CIS server or in the CENTRALOG C10 station is used to manage the two combined networks.

An independent Ethernet network is required to connect the CONTROCADengineering station, the printers, the X terminals or other CENTRALOG client PCs.

The following architecture is proposed:

Controcad

F G

9 5 !( 9 " ..

"!%&(!.. (

9 5 !( 9 " ..

"!%&(!.. (

9 5 !( 9 " ..

"!%&(!.. (

9 5 !( 9 " ..

"!%&(!.. (

9 5 " .. "!%&(!.. (

(! #)&,

'+(& %+)( , .,'+ 9 5 <) . "!%&(!.. (

.,'+ 9 5 <) . "!%&(!.. (

.,'+ 9 5 <) . "!%&(!.. (

.,'+ 9 5 <) . "!%&(!.. (

! 3#,

(! #)&,'+(& %+)( ,

.,'+ 9 5 E @)"

.,'+ 9 5 E @)"

This type of architecture is liable to disturb inter–controller communications. The following limitations must therefore be imposed:

the number of CVS stations and CIS servers must not exceed 5,

the number of cells must not exceed10.

In all cases, you should consult ALSTOM before envisaging this type of architecture.

6 7

Page 30: S8000-E Ring Network

56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > & 66

Page 31: S8000-E Ring Network

5.1.6. Interface with the Controcad Engineering PC

The interface between the Controcad engineering PC (NT) and the S8000–E unit network is supplied by a Fast Ethernet interface module.

The interface module provides a connection to the S8000–E network in single medium mode whether the solution implemented for the network is single or dual/redundant.

The Controcad engineering PC (NT) is connected to one of the hubs (RH1–TP/FL) or switches (RS2) on the S8000–E ring. It is also connected to the site Ethernet network in order to enable of the CENTRALOG views and database to be downloaded and to benefit from printer sharing.

If multiple S8000–E unit networks are implemented please refer to the corresponding chapter.

)& &> (% &

6

9 #%)& % &:!(;

6 6

C

5

C

5

.,'+ 9 5 " .. "!%&(!.. (,

9

6 7

Page 32: S8000-E Ring Network

56 8,& $

Page 33: S8000-E Ring Network

6. Presentation of the 10 Mbits/s S8000–E Ring

6.1. GENERAL HARDWARE CHARACTERISTICS

The principal qualities of the hubs and switches implemented on the S8000–E unit network are as follows:

Industrial design

Operating temperature range 0 degrees C to + 60 degrees C

24 V DC redundant input power supply

DIN Rail ‘‘Plug and Play‘‘ installation

High availability obtained by utilization of fault tolerant ring structure

CE, FCC, UL, cUL, FM certifications

6 7

Page 34: S8000-E Ring Network

6.2. HARDWARE USED FOR THE 10 MBITS/S RING

The S8000–E 10 Mbits/s ring is available in multi–mode optical technology(10BASE–FL).

The hardware devices used for the 10 Mbits/s ring are RH1–TP/FL hubs, which are capable of managing a ring in multi–mode optical technology.

RH1–TP/FL hubs (DIN rail enclosures) can be used to connect up to 3 subscribers each. They are fitted with a redundant power supply, and a malfunction contact.

An RH1–TP/FL hub integrates the following connections:

2 10BASE–FL ports for connection to the optical ring using BFOC connectors

3 10BASE–T ports or connection to subscribers via a twisted pair using RJ45 connectors

To manage the ring topology, one of the hubs must be configured as the “redundancy manager” of the ring.

+.<#%"&)!% $+%+= $ %& "!%&+"& +% ( #% +%& 6

'!: ( ,#''.8

&> (% & '!(&F %&(+.!= !( 9 H ,#3,"()3 (G

&> (% & '!(&F %&(+.!= !( 9 H ,#3,"()3 (G

&> (% & '!(&F %&(+.!= !( 9 H ,#3,"()3 (G

#+. !'&)"+. '!(& F 9 G

#+. !'&)"+. '!(& F 9 G

6 7 56

Page 35: S8000-E Ring Network

The principal limits of the 10 Mbits/s ring concern the topology of the ring:

the maximum number of hubs traversed, i.e. maximum 13 RH1–TP/FL hubs depending on the “variability value” measured in bit–time units or BTs:

— maximum BTs = 40

— each RH1–TP/FL hub counts as:

3 BTs between the two optical ports on the ring (FL/FL)

6 BTs between the optical port of the ring and the copper port of a subscriber (FL/TP)

— each RH1–TP hub counts as 4 BTs between two copper ports (TP/TP)

— each RT1–TP/FL transceiver counts as 1 BT between the optical port and the copper port (FL/TP).

the maximum length between the most distant subscribers is limited to 4,520 meters in compliance with the following rules:

— the length of a multimode fiber optic cable between two RH1–TP/FL hubs depends on the type of fiber used and must be less than or equal to:

2,600 m for a 50/125 um fiber,

3,100 m for a 62.5/125 um fiber,

— the length of the copper link between a subscriber and the RH1–TP/FLhub must not exceed 100 m ,

— each RH1–TP/FL hub counts as:

260 m between the two ports optical of the ring (FL/FL)

360 m between the port optical of the ring and the port copper of a subscriber (FL/TP)

— each hub RH1–TP counts as190 m between the two copper ports(TP/TP),

— each RT1–TP/FL transceiver counts as 100 m between the optical port and the copper port (FL/TP),

— an Ethernet board on a station or PC counts as 140 m.

6 7

Page 36: S8000-E Ring Network

56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > & 67

Page 37: S8000-E Ring Network

Maximum length between two subscribers = 140m + (L1+360m) + (L2+260m) + (L3+260m) + (L4+360m) + L6 + 140m < 4,520m

6 7

Page 38: S8000-E Ring Network

56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > & 6

Page 39: S8000-E Ring Network

6.3. REDUNDANCY OF THE S8000–E 10 MBITS/S RING

Management of the fault tolerant ring

The Hirschmann “Redundancy manager” is an Ethernet switch that has the facility of surpassing the limitations of normal Ethernet architectures in bus or star topology.

As well as managing all the standard Ethernet switching functions, the RH1–TP/FL hub offers the possibility of managing a ring (optical) in full duplex mode at speeds of up to 20 Mbits/s.

The “Redundancy Manager’ RH1–TP/FL hub enables the ring to be transformed into a bus by opening the ring in the case of normal operation or closing it in the case of a malfunction on the medium or on one of the network hubs. The utilization of “Redundancy Manager” RH1–TP/FL hubs is wholly transparent for the operation of the S8000–E unit network. Even if the “Redundancy Manager” is defective the network continues to operate and variables are exchanged between the subscribers that are connected to the other RH1–TP/FL hubs.

The “Redundancy Manager” RH1–TP/FL hub receives and transmits the real time diagnostics messages from the other hubs on the ring at both the ring ports. Messages are sent with an identifier. The identifier enables the ”Redundancy Manager” switch to count the messages and to manage the state of the network at all times.

If a malfunction is detected on the S8000–E ring (either the loss of a hub or of a part of the ring medium), the “Redundancy Manager” RH1–TP/FL hub continues to transmit at both the ring ports. However, because of the malfunction the diagnostics messages cannot travel around the full ring. The “Redundancy Manager” RH1–TP/FL hub is thuscapable of interpreting the loss of a diagnostics message as a network malfunction.

Page 40: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> & 69

Page 41: S8000-E Ring Network

When the network malfunction is detected, the ’Redundancy Manager” hub connects the two interfaces of the ring internally, which renders the network operational. Detection and re–setting network the to operational state takes between 20 and 300 ms depending on the number of hubs (max 13) and on the size of the network.

If the malfunction concerns a part of the ring medium the operation of the ring is not affected.

If the malfunction concerns a RH1–TP/FL hub, the following types of problem may occur:

— a problem on one of the two ring ports; the hub continues to function on the other port,

— a problem on one of the ports or on the medium used to connect a subscriber; communications with this subscriber are lost,

— a general problem with the hub; communications with the subscribers connected to the hub are lost, but the rest of the network continues to function.

When the malfunction disappears on the ring, the “Redundancy Manager” hub disconnects the two interfaces of the ring internally, thus enabling the initialconfiguration of the network to be rendered operational.

6 7

Page 42: S8000-E Ring Network

56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > & 6B

Page 43: S8000-E Ring Network

'&)"+. '!(&

#% +%"8 +%+= (

E D

D

'&)"+. '!(&

#% +%& &> (% & 9 !'&)"+. ()%=

E E

'&)"+. '!(& '&)"+. '!(& '&)"+. '!(& '&)"+. '!(&

Each optical port of an RH1–TP/FL hub is equipped with two connections: one optical transmission connection, one optical reception connection. each optical port comprises two connectors, the first for transmission, the second for the reception.

Each optical port of an RH1–TP/FL hub monitors the reception of the light carrier from the corresponding subscriber. If the reception is detected as defective at one of the two ports,the wholly defective port

(transmission + reception) is declared non–operational, whiled the other port remains operational.

The optical links between two hubs can be provided by two different optical cables or by a single cable comprising several optical fibers. In accordance with the rule detailed above, if one of the two optical cables is cut, the link between two hubs becomes wholly non–operational (transmission + reception). In this case messages transit via the otherpart of the ring and are processed by the other optical port, which remains operational.

Page 44: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> & 5

Page 45: S8000-E Ring Network

6.4. DOUBLE CONNECTION OF A S8000–E 10 MBITS/S SUSCRIBER

To process special types of architecture, a double connection of a suscriber to the 10Mbits/s ring can be managed with a double RT2–TX–R transceiver.

The RT2–TX–R transceiver has:

2 10/100 BASE–TX ports for connection to two S8000–E RH1–TP/FL hubs

a 10/100 BASE–TX port for connection to a network suscriber

Site network

Contronet

CVS CVS CVS/CIS CVS/CIS

RT2–TX–R RT2–TX–R Controcad

RH1–TP/FL RH1–TP/FL

Unit network S8000–ERH1–TP/FL

RH1–TP/FL

RH1–TP/FLRH1–TP/FL RH1–TP/FL RH1–TP/FL

RH1–TP/FLRH1–TP/FL

RT2–TX–R RT2–TX–R RT2–TX–R RT2–TX–R RT2–TX–R RT2–TX–R RT2–TX–R RT2–TX–R

The CONTRONET and S8000–E networks cannot be combined in the case of a 10Mbits/s double ring based on RH1–TP/FL hubs .

For further information regarding the utilization of this type of architecture, please consult ALSTOM.

Page 46: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> & 5

Page 47: S8000-E Ring Network

6.5. S8000–E 10 MBITS/S DOUBLE RING

A 10 Mbits/s double ring can be administered to process special types of architecture. The rings must be connected together to manage the inter–controller communications and communications with the Centralog supervisor.

The link between the rings can therefore be rendered redundant by the utilization of two RS2 switches. These two switches are used to exchange variables between the two rings via two redundant (master / slave) links. To manage this redundant link, the two redundant switches of one of the two rings are connected via a special ”Control Line” link (10 Ohm crossed twisted pair cable) connected to the “Stand–by” port ofthese two switches. The “Control Line” link may not exceed 15 meters.

Site network

Contronet

CVS CVS CVS/CIS CVS/CIS

RH1–TP/FLControl Line

RH1–TP/FL

Controcad

RS2 RS2

RH1–TP/FL

S8000–E

RH1–TP/FL

RH1–TP/FL RH1–TP/FL RH1–TP/FL

RH1–TP/FL

RH1–TP/FL

RH1–TP/FL

The CONTRONET and S8000–E networks cannot be combined in the case of a 10Mbits/s double ring based on RH1–TP/FL hubs.

For further information regarding the utilization of this type of architecture, please consult ALSTOM.

Page 48: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> & 56

Page 49: S8000-E Ring Network

6.6. HUB MALFUNCTION MANAGEMENT ON THE S8000–E 10 MBITS/S RING

The RH1–TP/FL hubs are provided with a malfunction signal connected to a input on a logic board of a field controller of the corresponding cell.

This malfunction signal can be used as an application switchover criterion for controller redundancy processing.

#% +%"8 +%+= (

E

E E

"

+

,

"

+

,

H+$'. ) .

!%&(!.. ( .,'+

9 5

" +.<#%"&)!

%

# )=%+.

-, * H+$'. *

) . !%&(!.. (

.,'+ 9 5

%

Page 50: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> & 55

Page 51: S8000-E Ring Network

6.7. SUPPLEMENTARY HARDWARE ON THE S8000–E 10 MBITS/S RING

The following supplementary hardware can be used in the case of special topologies implementing the Ethernet 10 Mbits/s ring described above:

RH1–TP: Rail Hub. 4 10BASE–T ports (RJ45 connector)

RT1–TP/FL: Converter. 1 optical multi–mode 10BASE–FL port (ST connector). 1 copper 10BASE–T port (RJ45 connector)

For further information regarding the utilization of this hardware, please consultALSTOM.

6 7

Page 52: S8000-E Ring Network

56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > & 5

Page 53: S8000-E Ring Network

7. 100 Mbits/s S8000–E Ring

7.1. GENERAL CHARACTERISTICS OF THE HARDWARE USED

The principal qualities of the switches used for the S8000–E 100 Mbits/s unit network are as follows:

Industrial design

Operating temperature range 0 degrees C to + 60 degrees C

24 V DC redundant input power supply

DIN Rail ‘‘Plug and Play‘‘ installation

High availability obtained by utilization of fault tolerant ring structure

CE, FCC, UL, cUL, FM certifications

6 7

Page 54: S8000-E Ring Network

56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > & 5

Page 55: S8000-E Ring Network

7.2. HARDWARE USED FOR THE S8000–E 100 MBITS/S RING

The 100 Mbits/s ring is available in three technologies:

copper twisted pair (100BASE–TX),

multimode optical (100BASE–FX),

single mode optical (100BASE–FX–SM).

The devices implemented for the 100 Mbits/s ring are RS2 switches.

The types of RS2 switch implemented are as follows:

RS2–TX/TX : for copper ring

RS2–FX/FX : for multimode optical ring

RS2–FX–SM/FX–SM : for single mode optical ring

Each RS2 switch (DIN rail interface enclosure) can each be used to connect up to 5 subscribers at 10 or 100 Mbits/s. The speed is self–negotiating (limited to 10 Mbits/s in the case of C80–35 or C80–75 cell controller type subscribers). RS2 switches use full duplex mode, so the ring delivers a flow of 200 Mbits/s in copper or optical technology.

RS2 switches comprise a redundant power supply and a malfunction contact.

a RS2–TX/TX hub integrates the following connections:

— 2 100BASE–TX ports for connection to the copper ring via a twisted pair using RJ45 connectors

— 5 10/100BASE–T/TX ports (self–negotiation) for connection to subscribers via a twisted pair using RJ45 connectors

a RS2–FX/FX hub integrates the following connections:

— 2 100BASE–FX ports or connection to the multimode optical ring with SCconnectors

— 5 10/100BASE–T/TX ports (self–negotiation) for connection to subscribers via a twisted pair with of connectors RJ45

a hub RS2–FX–SM/FX–SM integrates the following connections:

— 2 ports 100BASE–FX–SM for the connection à the ring optical single mode using SC connectors

— 5 ports 10/100BASE–T/TX (self–negociation) for the connection to subscribers via a twisted pair using RJ45 connectors

Page 56: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> & 57

Page 57: S8000-E Ring Network

For reasons of topology management one of the RS2 switches must be configured as the “redundancy manager” of the ring.

Connecting the RS2 switch in optical technology:

+.<#%"&)!% $+%+= $ %& "!%&+"& +% ( #% +%& 6

'!: ( ,#''.8 D #+. !'&)"+. '!(& F 9 G

D #+. !'&)"+. '!(& F 9 G

6 ,:)&">

D &> (% & '!(& F %&(+.!=!( 9 H ,#3,"()3 ( G

D &> (% & '!(& F %&(+.!= !( 9 H ,#3,"()3 (G

D &> (% & '!(& F &+% 38G

6 7

Page 58: S8000-E Ring Network

56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > & 5

Page 59: S8000-E Ring Network

The principal limits of the 100 Mbits/s ring concern the topology of the ring and are as follows:

maximum length in copper technology (twisted pair): 100 m between two switches whatever the technology: TP: 10BASE–T or TX: 100BASE–TX.

maximum lengths in fiber optic technology are dependent on the type of fiber optic used:

— multimode: maximum theoretical length of the ring is 100 Km, maximum length between two switches is 2,600 m for fiber optic type 50/125 um,3,100 m for fiber optic type 62.5/125 um.

— single mode: maximum theoretical length of the ring is 2,000 Km, maximum length between two switches is 40 Km for fiber optic 10/125

um.

no more than 50 RS2 switches may be traversed.

It is also possible to integrate several rings connected together.

The S8000–E network implementation rules are complex and cannot be fully indicated in this document. They are dependent on the components chosen for the configuration and topology of the network (consult ALSTOM).

RS2–TX/TXCopper

RS2–TX/TX

CopperRS2–TX/TX RT2–TX/FX

Multi–mode optical

CopperUnit network S8000–E RS2–FX/FX

RS2–TX/TX

Copper

RS2–TX/TXCopper

RS2–TX/TX RT2–TX/FX Multi–mode optical

Page 60: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> & 59

Page 61: S8000-E Ring Network

Rules for a 100 Mbits/s ring in copper technology:

6 7

Page 62: S8000-E Ring Network

56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > & 5B

Page 63: S8000-E Ring Network

Rules for a 100 Mbits/s ring in multimode optical technology:

Rules for a 100 Mbits/s ring in single mode optical technology:

6 7

Page 64: S8000-E Ring Network

56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > &

Page 65: S8000-E Ring Network

7.3. REDUNDANCY OF THE 100 MBITS/S S8000–E RING

Management of the fault tolerant ring

The Hirschmann “Redundancy manager” is an Ethernet switch that has the facility of surpassing the limitations of normal Ethernet architectures in bus or star topology.

As well as managing all the standard Ethernet switching functions, the RS2 switch offers the possibility of managing a ring (optical or copper) in full duplex mode with a speed of up to 200 Mbits/s.

The “Redundancy Manager’ RS2 switch enables the ring to be transformed into a bus by opening the ring in the case of normal operation or closing it in the case of a malfunction on the medium or on one of the network switches. The utilization of the “Redundancy Manager” RS2 is wholly transparent for the operation of the S8000–E unit network, even if the “Redundancy Manager” RS2 is defective the network continues to operate and the variables are exchanged between the subscribers that are connected to the other RS2 switches.

The “Redundancy Manager” RS2 switch receives and transmits the real time diagnostics messages from the other switches on the ring at both the ring ports. Messages are sent with an identifier. The identifier enables the ”Redundancy Manager” switch to count the messages and to manage the state of the network at all times.

If a malfunction is detected on the S8000–E ring (either the loss of a switch or of a part of the ring medium), the “Redundancy Manager” RS2 switch continues to transmit at both the ring ports. However, because of the malfunction the diagnostics messages cannot travel around the full ring. The “Redundancy Manager” RS2 switch is thuscapable of interpreting the loss of a diagnostics message as a network malfunction.

Page 66: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> &

Page 67: S8000-E Ring Network

When the network malfunction is detected, the ’Redundancy Manager” RS2 switch connects the two interfaces of the ring internally, which renders the network operational. Detection and re–setting network the to operational state takes between20 and 300 ms depending on the number of switches (max 50) and on the size of the network.

If the malfunction concerns a part of the ring medium the operation of the ring is not affected.

If the malfunction concerns a switch, the following types of problem may be present:

— a problem on one of the two ports of the ring; the switch continues to function on the other port,

— a problem on one of the ports or on the medium used to connect a subscriber; communications with this subscriber are lost,

— a general problem of the switch; communications with the subscribers connected to the switch are lost, but the rest of the network continues to function.

When the malfunction disappears on the ring, the “Redundancy Manager” RS2 switch disconnects the two interfaces of the ring internally, thus enabling the initial configuration of the network to be rendered operational.

When RS2 switches are used, the subscriber address arrays are recalculated when a malfunction appears or disappears.

The solution used for the S8000–E unit network not only protects the link between two switches but also the complete ring network. In addition it allows the architecture of the network to be extended in the course of the project without impacting the network flowor structure.

Page 68: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> & 6

Page 69: S8000-E Ring Network

'&)"+. '!(&

#% +%"8 +%+= (

6

D

D '&)"+. '!(&

#% +%& &> (% & 9 ()%= F!'&)"+. !( "!'' (G

6 6

'&)"+. '!(& '&)"+. '!(& '&)"+. '!(& '&)"+. '!(&

Each optical port of an RS2–FX/FX or RS2–FX–SM/FX–SM switch is equipped with two connections: one optical transmission connection, one optical reception connection. each optical port comprises two connectors, the first for transmission, the second for the reception.

Each optical port of an RS2 switch monitors the reception of the light carrier from the corresponding subscriber. If the reception is detected as defective at one of the two ports, the wholly defective port (transmission + reception) is declared non–operational, whiled the other port remains operational.

The optical links between two enclosures can be provided by two different optical cables or by a single cable comprising several optical fibers. In accordance with the rule detailed above, if one of the two optical cables is cut, the link between two switches becomes wholly non–operational (transmission + reception). In this case messages transit via the other part of the ring and are processed by the other optical port, whichremains operational.

Page 70: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> & 5

Page 71: S8000-E Ring Network

7.4. DOUBLE CONNECTION OF A S8000–E 100 MBITS/S SUSCRIBER

To process special types of architecture, a double connection of a suscriber to the 100Mbits/s ring can be managed with a double RT2–TX–R transceiver.

The RT2–TX–R transceiver has:

2 10/100 BASE–TX ports for connection to two S8000–E RH1–TP/FL hubs

a 10/100 BASE–TX port for connection to a network suscriber

Site network

CVS CVS CVS/CIS CVS/CIS

RT2–TX–R RT2–TX–R RT2–TX–R RT2–TX–R Controcad

RS2 RS2

S8000–E Unit network & CONTRONET

RS2RS2 RS2 RS2

RT2–TX–R RT2–TX–R RT2–TX–R RT2–TX–R RT2–TX–R RT2–TX–R RT2–TX–R RT2–TX–R

For further information regarding the utilization of this type of architecture, please consult ALSTOM.

Page 72: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> &

Page 73: S8000-E Ring Network

7.5. S8000–E 100 MBITS/S DOUBLE RING

A 100 Mbits/s double ring can be administered to process special types of

architecture. The rings must be connected together to manage the inter–controller

communicationsand communications with the Centralog supervisor.

The link between the rings can therefore be rendered redundant by the utilization of two RS2 switches. These two switches are used to exchange variables between the two rings via two redundant (master / slave) links. To manage this redundant link, the two redundant switches of one of the two rings are connected via a special ”Control Line” link (10 Ohm crossed twisted pair cable) connected to the “Stand–by” port ofthese two switches. The “Control Line” link may not exceed 15 meters.

S8000–E

Page 74: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> &

Page 75: S8000-E Ring Network

Site Network

CVS CVS CVS/CIS CVS/CIS

RS2RS2

Controcad

RS2 RS2

Control Line 15 meters

RS2

RS2

Contronet and S8000–E

RS2

RS2

RS2

RS2

The CONTRONET and S8000–E networks can be combined in the case of a 100Mbits/s double ring based on RS2 switches.

For further information regarding the utilization of this type of architecture, please consult ALSTOM.

6 7 56

Page 76: S8000-E Ring Network

8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > & 7

Page 77: S8000-E Ring Network

7.6. MANAGEMENT OF ENCLOSURE MALFUNCTIONS (HUB OR SWITCH)

RS2 switches comprise a malfunction signal connected to an input on a logic board of a field controller in the corresponding cell.

This malfunction signal can be used as an application switchover criterion for controller redundancy processing.

#% +%"8 +%+= (

6

6 6

"

+

,

"

+

,

H $'. !%&(I. #(, " ..#.

.,'+ 9 5

+.<#%"&)!% " ,)=%+. #

-, * H $'. *

!%&(I. #( & ((+)%

.,'+ 9 5

%

This example can also be applied to a Series 5 ES cell (C80–75 cell controllers / CE2000 or C80–35 field controllers) .

Page 78: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> &

Page 79: S8000-E Ring Network

7.7. SUPPLEMENTARY HARDWARE FOR 100 MBITS/S S8000–E RING

The following supplementary hardware devices can be implemented in case of special topologies, in addition to the Fast Ethernet 100 Mbits/s ring described above:

RH1–TP: Rail Hub. 4 10BASE–T ports (RJ45 connector)

RH2–TX: Rail Hub. 4 100BASE–TX ports (RJ45 connector)

RS2–TX: Rail switch. 8 10/100BASE–T/TX ports (RJ45 connector)

RT1–TP/FL: Converter. 1 10BASE–FL multi–mode optical port (ST connector). 1 10BASE–T copper port (RJ45 connector)

RT2–TX/FX: Converter. 1 100BASE–FX multi–mode optical port (SC connector). 1 100BASE–TX copper port (RJ45 connector)

RT2–TX/FX–SM: Converter. 1 100BASE–FX–SM single–mode optical port (connector SC). 1 100BASE–TX copper port (RJ45 connector)

Attention: hubs and converters fitted with 100Mbits/s ports can only be connected to subscribers equipped with 100Mbits/s interfaces.

For further information regarding the utilization of these hardware units please consultALSTOM.

Page 80: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> & 9

Page 81: S8000-E Ring Network

7.8. MANAGEMENT OF THE NETWORK VIA THE 100 MBITS/S S8000–E WEB INTERFACE

The RS2 switch integrates a WEB interface that can be used to manage the S8000–Enetwork from the CONTROCAD PC.

The WEB interface uses a standard browser (Netscape or Explorer version 4.x or later) to access any point of the network for the purpose of managing the RS2 switches by means of a JAVA applet that communicates with the RS2 via the SNMP protocol (single Network Management Protocol).

The RS2 switch with which the network is to be administered is accessed by inputting the browser address field with the Internet address (IP) of the in the form(http://xxx.xxx.xxx.xxx).

The principal functions available are as follows:

alarm display and record (network malfunction)

system information:

— the name and location of the device etc.

— the state of the power supplies

— the state of the dual/redundant link (if double ring architecture is implemented)

— the switch hardware and software version

configuration of RS2 ports (self–negotiation, full duplex etc.)

configuration of the network.

6 7

Page 82: S8000-E Ring Network

56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > & B

Page 83: S8000-E Ring Network

8. Multiple–ring S8000–E Architecture

The figure below shows a typical thermal architecture implementing one S8000–E unit network per unit and a unit network for the commons. This figure also shows the interfaces with the Site Controcad engineering workshop used for the observation and download of the control functions and the CENTRALOG control room functions.

Automation cells connected to an S8000–E unit network are downloaded and observed from the client Site CONTROCAD PC associated to this unit network.

6 7

Page 84: S8000-E Ring Network

56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > &

Page 85: S8000-E Ring Network

9

<)

. 3#,

9

<)

. 3#,

9

<)

. 3#,

Single multi–unit database

Controcad server

Controcad clientUnit 1 Unit 1

CIS

Unit 2CIS

Controcad clientUnit 2

Unit 1Centralog

Unit 2Centralog

+

+

Controcad client Commons

.,'+ 6 <) . "!%&(!.. (

.,'+ 6 <) . "!%&(!.. (

.,'+ 6 <) . "!%&(!.. (

.,'+ 6 <) . "!%&(!.. (

“Unit 1”automation cells .,'+ 6

<) . "!%&(!.. (

.,'+ 6 <) . "!%&(!.. (

“Unit 2”automation cells

“Common Auxiliary”automation cells

Page 86: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> &

Page 87: S8000-E Ring Network

9. Power Supply

Characteristics of the RPS 60 power supply module of:

input power supply: 115 / 230 V AC

output voltage: 24 VDC / 2.5 A

maximum intensity: 3,9 A (input current)

EMI Packaging

MTBF: 740,000 h at 40

The RPS 60 module can be used to power up to 7 RH1–TP/FL hubs or 3 RS2 switches.

Each RH1–TP/FL hub and RS2 switch comprises a redundant input power supply to ensure improved overall availability of the S8000–E network. In this case, two RPS 60 power supplies, powered by two independent sources, must be provided for eachgroup of hubs or switches.

Page 88: S8000-E Ring Network

6 7 56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. ,

> & 6

Page 89: S8000-E Ring Network

10. Applicable Data Sheets

10.1. S8000–E NETWORK

These data sheets are available in English:

RS2 switch:

S8000–E Ethernet Equipment – RS2: PTP09A49059

RH1–TP–FL hub:

S8000–E Ethernet Equipment – RH1: PTP09A49061

6 7

Page 90: S8000-E Ring Network

56 8,& $ 9 %)& &:!(; !%<)=#(+&)!% #. , > & 5