s120 Vector

1816
sinamics s SINAMICS S List Manual 07/2007

Transcript of s120 Vector

List Manual 07/2007

SINAMICS S

sinamicss

sForeword

SINAMICS SINAMICS S List ManualManual

Parameters Function Diagrams Faults and Alarms Appendix List of abbreviations References

1 2 3 A B C D

Valid for Drive SINAMICS Firmware version 2.5 SP1

Index

6SL3 097-2AP00-0BP6

07/2007

Safety-related informationThis manual contains information that must be observed to ensure your personal safety and to prevent property damage. Notices referring to your personal safety are highlighted in the manual by a safety alert symbol; notices referring to property damage only have no safety alert symbol, These notices shown below are graded according to the level of danger:

Dangerindicates that death or serious injury will result if proper precautions are not taken.

Alarmindicates that death or serious injury may result if proper precautions are not taken.

Cautionwith a safety alert symbol, indicates that minor personal injury may result if proper precautions are not taken.

Cautionwithout a safety alert symbol, indicates that property damage may result if proper precautions are not taken.

Cautionmeans an undesirable result or state can occur if the corresponding instruction is not followed. If more than one level of danger exists, the warning notice for the highest level of danger is used. If a warning notice with a safety alert symbol is to indicate physical injury, the same warning may also contain information about damage to property.

Qualified personnelThe associated device/system may only be installed and used in conjunction with this documentation. Only qualified personnel should be allowed to commission and operate the device/system. For the purpose of the safety information in this documentation, a qualified person is someone who is authorized to energize, ground, and tag equipment, systems, and circuits in accordance with established safety procedures.

Intended usePlease note the following:

AlarmThis equipment is only allowed to be used for the applications described in the catalog and in the technical description, and only in conjunction with non-Siemens equipment and components recommended by Siemens. This product can function correctly and safely only if it is transported, stored, set up, and installed correctly, and operated and maintained as recommended.

TrademarksAll names identified by are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.

Copyright Siemens AG 2007 All Rights Reserved The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Violation of this rule can lead to claims for damage compensation. All rights reserved, especially for granting patents or for GM registration. Siemens AG Automation & Drives Postfach 4848 D - 90437 Nuremberg Germany

Liability Disclaimer We have checked that the contents of this document correspond to the hardware and software described. Nevertheless, we cannot assume responsibility for any deviations that may arise. The data in this document is regularly checked and the necessary corrections are included in subsequent editions.

Siemens AG 2007 Subject to change without prior notice

Siemens Aktiengesellschaft

SINAMICS S List Manual (LH1)

ForewordSINAMICS Documentation The SINAMICS documentation is organized in 2 parts: General documentation/catalogs Manufacturer/service documentation A current overview of the documentation in the available languages is provided in the Internet: http://www.siemens.com/motioncontrol Follow menu items - "Support" -> "Technical documentation" -> "Overview of publications". The Internet version of DOConCD (DOConWEB) is available in the Internet: http://www.automation.siemens.com/doconweb Information on the range of training courses and FAQs (Frequently Asked Questions) are available in the Internet: http://www.siemens.com/motioncontrol Follow the menu item "Support". Usage phases and their tools/documents (as an example)Table Foreword-1 Usage phase Orientation Planning/configuration Usage phases and the available tools/documents Tools/documents SINAMICS S Sales Documentation SIZER configuration tool Configuration Manuals, Motors Decision making/ordering Installation/assembly SINAMICS S Catalogs SINAMICS S120 Equipment Manual for Control Units and Supplementary System Components SINAMICS S120 Equipment Manual Power Modules Booksize SINAMICS S120 Equipment Manual Power Modules in chassis format SINAMICS S150 operating instructions

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Foreword-5

Foreword

Table Foreword-1 Usage phase Commissioning

Usage phases and the available tools/documents, continued Tools/documents STARTER parameterization and commissioning tool SINAMICS S120 Getting Started SINAMICS S120 Commissioning Manual SINAMICS S120 CANopen Commissioning Manual SINAMICS S120 Function Manual SINAMICS S List Manual SINAMICS S150 operating instructions SINAMICS S120 Commissioning Manual SINAMICS S List Manual SINAMICS S150 operating instructions SINAMICS S120 Commissioning Manual SINAMICS S List Manual SINAMICS S150 operating instructions

Usage/operation

Maintenance/servicing

Target group This documentation is aimed at machine manufacturers, commissioning engineers, and service personnel who use SINAMICS. Benefits This documentation contains the comprehensive information about parameters, function diagrams and faults and alarms required to commission and service the system. This manual should be used in addition to the other manuals and tools provided for the product. Standard version The scope of the functionality described in this document can differ from the scope of the functionality of the drive system that is actually supplied. Other functions not described in this documentation might be able to be executed in the drive system. However, no claim can be made regarding the availability of these functions when the equipment is first supplied or in the event of servicing. Functions can be described in the documentation that are not available in a particular product version of the drive system. The functionality of the supplied drive system should only be taken from the ordering documentation. Extensions or changes made by the machine manufacturer must be documented by the machine manufacturer. For reasons of clarity, this documentation does not contain all of the detailed information on all of the product types. This documentation cannot take into consideration every conceivable type of installation, operation and service/maintenance.

Foreword-6

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Foreword

Search tools The following guides are provided to help you locate information in this manual: 1. Table of contents General table of contents for the complete manual (after the preface). Table of contents for function diagrams (Chapter 2.1). 2. List of abbreviations 3. References 4. Index Technical Support If you have any questions, please contact our hotline:Europe/Africa Phone Fax Internet +49 (0) 180 5050 - 222 +49 (0) 180 5050 - 223 http://www.siemens.de/automation/support-request

America Phone Fax E-mail +1 423 262 2522 +1 423 262 2200 [email protected]

Asia/Pacific Phone Fax E-mail +86 1064 719 990 +86 1064 747 474 [email protected]

Note: For technical support telephone numbers for different countries, go to: http://www.siemens.com/automation/service&support

Questions about the Manual Please send any questions about the technical documentation (e.g. suggestions for improvement, corrections) to the following fax number or E-Mail address: Fax: E-Mail: Fax form: +49 (0) 9131 / 98 - 63315 [email protected] Refer to the feedback sheet at the end of the manual

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Foreword-7

Foreword

Internet address for SINAMICS http://www.siemens.com/sinamics EC declaration of conformity The EC Declaration of Conformity for the EMC Directive can be obtained from: Internet http://www.ad.siemens.de/csinfo Product/Order No.: 15257461 Branch offices For the responsible regional offices of the A&D MC business division of Siemens AG.

Foreword-8

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Table of Contents1 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 1.1.1 1.1.2 1.2 1.3 1.3.1 1.3.2 1.3.3 1.3.4 1.3.5 2 Overview of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Explanation of list of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Numerical ranges of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . List of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameters for data sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameters for Command Data Sets (CDS) . . . . . . . . . . . . . . . . . . . . . Parameters for Drive Data Sets (DDS) . . . . . . . . . . . . . . . . . . . . . . . . . Parameters for Encoder Data Sets (EDS). . . . . . . . . . . . . . . . . . . . . . . Parameters for Motor Data Sets (MDS) . . . . . . . . . . . . . . . . . . . . . . . . Parameters for Power unit Data Sets (PDS) . . . . . . . . . . . . . . . . . . . . . 1-11 1-12 1-12 1-28 1-30 1-1069 1-1069 1-1072 1-1082 1-1084 1-1087 2-1089 2-1091 2-1101 2-1106 2-1130 2-1134 2-1141 2-1143 2-1147 2-1187 2-1200 2-1203 2-1208 2-1225 2-1235 2-1237 2-1253 2-1258 2-1267 2-1286 2-1314 2-1322 2-1326

Function Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 2.19 2.20 2.21 2.22 Table of contents, function diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . Explanations for the function diagrams . . . . . . . . . . . . . . . . . . . . . . . . . Overviews . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CU310 input/output terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CU320 input/output terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CU_LINK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CX32 input/output terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PROFIdrive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Internal control/status words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sequence control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Braking control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Integrated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setpoint channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setpoint channel not activated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic positioner (EPOS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Position control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Encoder evaluation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Servo control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Vector control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technology functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technology controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Signals and monitoring functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Contents-9

Table of Contents

2.23 2.24 2.25 2.26 2.27 2.28 2.29 2.30 2.31 2.32 2.33 2.34 2.35 2.36 2.37 3

Faults and alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Measuring sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Data sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Infeed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Smart Infeed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Active Infeed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal Board 30 (TB30). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communication Board CAN 10 (CBC10) . . . . . . . . . . . . . . . . . . . . . . . Terminal Module 15 for SINAMICS (TM15DI/DO) . . . . . . . . . . . . . . . . Terminal Module 31 (TM31) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal Module 41 (TM41) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliaries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage Sensing Module (VSM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Operator Panel 20 (BOP20) . . . . . . . . . . . . . . . . . . . . . . . . . . . . Braking Module external . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-1333 2-1338 2-1340 2-1346 2-1353 2-1362 2-1374 2-1379 2-1386 2-1390 2-1401 2-1411 2-1414 2-1418 2-1420 3-1423 3-1424 3-1424 3-1429 3-1432 3-1434 A-1751 A-1752 A-1753 A-1753 A-1775 B-1779 C-1787 D-1793

Faults and Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1 3.1.1 3.1.2 3.1.3 3.2 Overview of faults and alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General information about faults and alarms . . . . . . . . . . . . . . . . . . . . Explanation of the List of Faults and Alarms . . . . . . . . . . . . . . . . . . . . . Numerical ranges of faults and alarms . . . . . . . . . . . . . . . . . . . . . . . . . List of faults and alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A

Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A.1 A.2 A.2.1 A.2.2 ASCII table (excerpt) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . List for motor code/encoder code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Motor code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Encoder code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B C D

List of abbreviations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Contents-10

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

ParametersContent 1.1 1.2 1.3 Overview of parameters List of parameters Parameters for data sets

11-12 1-30 1-1069

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-11

Parameters Overview of parameters

1.1

Overview of parameters

1.1.1

Explanation of list of parameters

Basic structure of parameter descriptions The data in the following example has been chosen at random. The table below shows all the information which can be included in the description of a parameter. Some of the information is optional. The structure of the parameter list (See Section 1.2) is as follows: - - - - - - - - - - - - - - - - - - - - Start of example- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - pxxxx[0...n]Drive object (function module)

BICO: Full parameter name / Abbreviated nameChangeable in: C1(x), C2(x), U, T Data type: Unsigned32 / Integer16 P group: Cl.-lp. control Not for motor type: FEM Min 0.00 [Nm] Max 10.00 [Nm] are calculated: CALC_MOD_REG Access level: 2 Dynamic index: CDS, p0170 Unit Group: 7_1 Function diagram: 2080 Unit selection: p0505 Expert list: 1 Factory setting 0.00 [Aeff]

Description: Values:

Text 0: 1: 2: etc. Text [0] = Name and meaning of index 0 [1] = Name and meaning of index 1 [2] = Name and meaning of index 2 etc. Bit 00 01 02 Signal name Name and meaning of bit 0 Name and meaning of bit 1 Name and meaning of bit 2 etc. 1 signal Yes Yes Yes 0 signal No No No FP 8010 8012 Name and meaning of value 0 Name and meaning of value 1 Name and meaning of value 2

Recommendation: Index:

Bit array:

Depends on:

Text See also: pxxxx, rxxxx See also: Fxxxxx, Axxxxx Warning: Caution: Safety-related information with a safety alert symbol

Danger:

Caution: Note:

Notice: Information which might be useful.

Safety-related information without a safety alert symbol

- - - - - - - - - - - - - - - - - - - - End of example- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

1-12

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters Overview of parameters

pxxxx[0...n]

Parameter number The parameter number consists of a "p" or "r", followed by the parameter number and the index (optional). Examples of number representation in the parameter list: p... r... p0918 p0099[0...3] p1001[0...n] r0944 Adjustable parameter (read and write parameter) Display parameter (read only) Adjustable parameter 918 Adjustable parameter 99, indices 0 to 3 Adjustable parameter 1001, indices 0 to n (n = configurable) Display parameter 944

Other examples of notation in the documentation: p1070[1] p2098[1].3 r0945[2](3) p0795.4 r2129.0...15 Adjustable parameter 1070, index 1 Adjustable parameter 2098, index 1 bit 3 Display parameter 945, index 2 of drive object 3 Adjustable parameter 795, bit 4 Display parameter 2129 with bit field (maximum 16 bit)

The following applies to adjustable parameters: The "shipped" parameter value is specified under "Factory setting" with the relevant unit in square parenthesis. The value can be adjusted within the range defined by "Min" and "Max". The term "linked parameterization" is used in cases where changes to adjustable parameters affect the settings of other parameters. Linked parameterization can occur, for example, as a result of the following actions or parameters: Execute macros p0015, p0700, p1000, p1500 Set PROFIBUS telegram (BICO interconnection) p0922 Set component lists p0230, p0300, p0301, p0400 Calculate and preset automatically p0112, p0340, p0578, p3900 Restore factory settings p0970 The following applies to display parameters: The fields "Min", "Max" and "Factory setting" are specified with a dash "-" and the relevant unit in square parenthesis.

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-13

Parameters Overview of parameters

Note: The parameter list can contain parameters that are not visible in the expert lists of the particular commissioning software (e.g. parameters for trace functions).

BICO: Full parameter name / Abbreviated name The following abbreviations can be placed in front of the parameter name: BI: BO: Binector input This parameter is used for selecting the source of a digital signal. Binector output This parameter is available as a digital signal for interconnection with other parameters. Connector input This parameter is used for selecting the source of an analog signal. Connector output This parameter is available as an "analog" signal for interconnection with other parameters.

CI: CO:

CO/BO: Connector/Binector Output This parameter is available as an "analog" and digital signal for interconnection with other parameters.

Note: A connector input (CI) cannot be just interconnected with any connector output (CO, signal source). When interconnecting a connector input using the commissioning software, only the corresponding possible signal sources are listed.

Drive object (function module) A drive object (DO) is an independent, "self-contained" functional unit which possesses its own parameters and, in some cases, faults and alarms. When carrying out commissioning using the commissioning software, you can select/deselect additional functions and their parameters by activating/deactivating function modules accordingly. Note: References: /FH1/ SINAMICS S120 Function Manual Drive Functions

The parameter list specifies the associated drive object and function module for each individual parameter.

1-14

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters Overview of parameters

Examples: p1070 CI: Main setpoint SERVO (extended setpoint), VECTOR The parameter is available only in association with drive object SERVO and the "Extended setpoint channel" function module or with drive object VECTOR irrespective of activated function modules. p1055 BI: Jog bit 0 SERVO, VECTOR The parameter is available in association with drive objects SERVO and VECTOR irrespective of activated function modules, i.e. it is available with every activated function module belonging to the drive object. A parameter can belong to either one, several, or all drive objects. The following information relating to "Drive object" and "Function module" can be displayed under the parameter number:Table 1-1 Data in "Drive object (function module)" field Type 10 Meaning This parameter belongs to all drive objects. Active Infeed closed-loop control Closed-loop-controlled, self-commutated infeed/regenerative feedback unit for generating a constant DC-link voltage. A_INF (parallel) A_INF (RKA) A_INF (CBE) B_INF 30 Active Infeed with "Parallel connection" function module (r0108.15). Active Infeed with "Cooling system" function module (r0108.28). Active Infeed with "CBE COMMUNICATION BOARD" function module (r0108.31). Basic Infeed closed-loop control Unregulated line infeed unit (without feedback) for rectifying the line voltage of the DC Link. B_INF (parallel) B_INF (RKA) B_INF (CBE) CU CU(CAN) CU_S CU_S (CAN) CU_CX32 CU_LINK CU_I DMC20 1 254 150 Basic Infeed with "Parallel connection" function module (r0108.15). Basic Infeed with "Cooling system" function module (r0108.28). Basic Infeed with "CBE COMMUNICATION BOARD" function module (r0108.31). Control Unit, all versions. Control Unit with "CAN" function module. Control Unit SINAMICS S (SINAMICS S120/S150). Control Unit SINAMICS S with "CAN" function module Controller Extension for boosting the processing performance. Object for Controller Extension 32 (CX32). Control Unit SINAMICS Integrated (SIMOTION D4xx only). DRIVE-CLiQ Hub Module Cabinet.

Drive object (function module) All objects A_INF

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-15

Parameters Overview of parameters

Table 1-1

Data in "Drive object (function module)" field, continued Type 20 Smart Infeed control Unregulated line infeed/feedback unit for generating the DC link voltage. Meaning

Drive object (function module) S_INF

S_INF (parallel) S_INF (CBE) SERVO SERVO (extended M_ctrl) SERVO (position ctrl) SERVO (EPOS) SERVO (APC) SERVO (extended setpoint) SERVO (Lin) SERVO (Safety red) SERVO (ext. brake) SERVO (Tech_ctrl) SERVO (extended reports) SERVO (RKA) SERVO(CAN) SERVO (CBE) TB30 TM15 TM15DI_DO TM17 TM31 TM41 VECTOR

11 100 203 204 202 200 201 12

Smart Infeed with "Parallel connection" function module (r0108.15). Smart Infeed with "CBE COMMUNICATION BOARD" function module (r0108.31). Servo drive. Servo drive with "Extended torque control" function module (r0108.1). Servo drive with "Position control" function module (r0108.3). Servo drive with "Basic positioner" function module (r0108.4). Servo drive with "Advanced Positioning Control (APC)" function module (r0108.7). Servo drive with "Extended setpoint channel" function module (r0108.8). Servo drive with "Linear motor" function module (r0108.12). Servo drive with "Safety rotary axis" function module (r0108.13). Servo drive with "Extended braking control" function module (r0108.14) Servo drive with "Technology controller" function module (r0108.16) Servo drive with "Extended messages/monitoring functions" function module (r0108.17) Servo drive with "Cooling system" function module (r0108.28). Servo drive with "CAN" function module (r0108.29). Servo drive with "CBE COMMUNICATION BOARD" function module (r0108.31). Terminal Board 30. Terminal Module 15 (SIMOTION D4xx only). Terminal Module 15 (for SINAMICS). Terminal Module 17 (SIMOTION D4xx only). Terminal Module 31. Terminal Module 41. Vector drive.

1-16

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters Overview of parameters

Table 1-1

Data in "Drive object (function module)" field, continued Type Meaning Vector drive with "Closed-loop speed/torque control" function module (r0108.2). Vector drive with "Position control" function module (r0108.3). Vector drive with "Basic positioner" function module (r0108.4). Vector drive with "Extended brake control" function module (r0108.14). Vector drive with "Parallel connection" function module (r0108.15). Vector drive with "Technology controller" function module (r0108.16). Vector drive with "Extended messages/monitoring functions" function module (r0108.17). Vector drive with "Cooling system" function module (r0108.28). Vector drive with "CAN" function module (r0108.29). Vector drive with "CBE COMMUNICATION BOARD" function module (r0108.31).

Drive object (function module) VECTOR (n/M) VECTOR (pos ctrl) VECTOR (EPOS) VECTOR (ext. brake) VECTOR (parallel) VECTOR (Tech_ctrl) VECTOR (ext. mess.) VECTOR (RKA) VECTOR(CAN) VECTOR (CBE)

Note: The drive object type is used to identify the drive objects in the drive system (e.g. r0107, r0975[1]).

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-17

Parameters Overview of parameters

Changeable in The "-" sign indicates that the parameter can be changed in any object state and that the change will be effective immediately. The letters "C1(x), C2(x), T, U" ((x): optional) mean that the parameter can be changed only in the specified drive object state and that the change will not take effect until the object switches to another state. This can be one or more states. The following states may be specified: C1(x) Device commissioning C1: Commissioning 1 Converter commissioning is in progress (p0009>0). Pulses cannot be enabled. The parameter can only be changed in the following device commissioning settings (p0009 > 0): C1: Changeable for all settings p0009 > 0. C1(x): Only changeable when p0009 = x. A modified parameter value does not take effect until converter commissioning mode is exited with p0009 = 0. C2(x) Drive object commissioning C2: Commissioning 2

Drive commissioning is in progress (p0009 = 0 and p0010 > 0). Pulses cannot be enabled. The parameter can only be changed in the following drive commissioning settings (p0010 > 0): C2: Changeable for all settings p0010 > 0. C2(x): Only changeable when p0010 = x. A modified parameter value does not take effect until drive commissioning mode is exited with p0010 = 0. U T Operation Pulses are enabled. Ready T: Ready to run A: Run

The pulses are not enabled and status "C1(x)" or "C2(x)" is not active.

Note: Parameter p0009 is CU-specific (belongs to Control Unit). Parameter p0010 is drive-specific (belongs to each drive object). The operating status of individual drive objects is displayed in r0002.

1-18

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters Overview of parameters

Calculated Specifies whether the parameter is influenced by automatic calculations. The calculation attribute defines which activities influence the parameter. The following attributes apply: CALC_MOD_ALL p0340 = 1 Project download with commissioning software and send from p0340 = 3 CALC_MOD_CON p0340 = 1, 4 CALC_MOD_EQU p0340 = 1, 2 CALC_MOD_LIM_REF p0340 = 1, 3, 5 p0578 = 1 CALC_MOD_REG p0340 = 1, 3 Note: For p3900 > 0, also p0340 = 1 is automatically called. After p1910 = 1, p0340 = 3 is automatically called.

Access level Specifies the access level required to be able to display and change the relevant parameter. The required access level can be set via p0003. The system uses the following access levels: 1. Standard 2. Advanced 3. Expert 4. Service Please contact your local Siemens office for the password for parameters with access level 4 (Service). 5. Macro (the parameter can only be changed via macro) Note: Parameter p0003 is CU-specific (belongs to Control Unit).

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-19

Parameters Overview of parameters

Data type The information on the data type can consist of the following two pieces of information (separated by a slash): First information Data type of the parameter Second information (only for binector or connector input) Data type of the signal source to be interconnected (binector/connector output). The possible data types of parameters are as follows: I8 I16 I32 U8 U16 U32 Float Integer8 Integer16 Integer32 Unsigned8 Unsigned16 Unsigned32 FloatingPoint32 8-bit integer 16-bit integer 32-bit integer 8 bits without sign 16 bits without sign 32 bits without sign 32-bit floating point number

Depending on the data type of the BICO input parameter (signal sink) and BICO output parameter (signal source) the following combinations are possible when creating BICO interconnections:Table 1-2 Possible combinations of BICO interconnections BICO input parameter CI parameter BICO output parameter CO: Unsigned8 CO: Unsigned16 CO: Integer16 CO: Unsigned32 CO: Integer32 CO: FloatingPoint32 BO: Unsigned8 BO: Unsigned16 BO: Integer16 BO: Unsigned32 Unsigned32 / Integer16 x x x x x x Unsigned32 / Integer32 x x x x x x Unsigned32 / FloatingPoint32 x1 BI parameter Unsigned32 / Binary x x x x

1-20

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters Overview of parameters

Table 1-2

Possible combinations of BICO interconnections, continued BICO input parameter CI parameter BI parameter Unsigned32 / FloatingPoint32 Unsigned32 / Binary x

BICO output parameter BO: Integer32 BO: FloatingPoint32

Unsigned32 / Integer16 Legend:

Unsigned32 / Integer32

x: BICO interconnection permitted : BICO interconnection not permitted1 Exception: BICO input parameters with data type "Unsigned32 / FloatingPoint32" can also be interconnected with the following BICO output parameters although these are not of the "FloatingPoint32" data type: CO: r8850 CO: r8860 CO: r2050 CO: r2060

Dynamic index For parameters with a dynamic index [0...n], the following information is specified here: Data set (if this is available). Parameter for the number of indices (n = number - 1). The following information can be contained in this field: "CDS, p0170" (Command Data Set, CDS count) Example: p1070[0] p1070[1] main setpoint [command data set 0] main setpoint [command data set 1], etc.

"DDS, p0180" (Drive Data Set, DDS count) "EDS, p0140" (Encoder Data Set, EDS count) "MDS, p0130" (Motor Data Set, MDS count) "PDS, p0120" (Power unit Data Set, PDS count) "p2615" (traversing blocks count) Note: Information on the data sets can be taken from the following references: References: /FH1/ SINAMICS S120 Function Manual Drive Functions Section "Data sets"

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-21

Parameters Overview of parameters

Function diagram The parameter is included in this function diagram. The structure of the parameter function and its interrelationship with other parameters is shown in the specified function diagram. Example: Function diagram: 3060.3 3060: 3: Function diagram number Signal path (optional)

P group (refers only to access via BOP (Basic Operator Panel)) Specifies the functional group to which the parameter belongs. The required parameter group can be set via p0004. Note: Parameter p0004 is CU-specific (belongs to Control Unit).

Unit, Unit Group and Unit Choice The standard units of a parameter is specified in square brackets after the values for "Min", "Max" and "Factory setting". For parameters where the units can be changed over, for "Unit Group" and "Unit Choice" it is specified as to which group this parameter belongs and with which parameter the units can be changed over. Example: Unit Group: 7_1, Unit Choice: p0505 The parameter belongs to Unit Group 7_1 and the units can be changed-over using p0505. Note: Detailed information on changing-over units can be taken from the following references: References: /FH1/ References: /BA3/ SINAMICS S120 Function Manual Drive Functions SINAMICS S150 Operating Instructions

All of the Unit Groups that may occur and the possible Unit Choice is listed below.Table 1-3 Unit Groups (p0100) Unit Choice for p0100= 0 7_4 8_4 Nm N lbf ft lbf 1 Reference quantity for %

Unit group

1-22

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters Overview of parameters

Table 1-3

Unit Groups (p0100), continued Unit Choice for p0100= 0 1 HP HP lb ft2 lb lbf ft/A lbf/Arms ft Reference quantity for %

Unit group

14_2 14_6 25_1 27_1 28_1 29_1 30_1 Table 1-4

W kW kgm2 kg Nm/A N/Arms m Unit Groups (p0349)

Unit group

Unit Choice for p0349 = 1 2 %

Reference quantity for % 1000 p0304 ---------------------------------------------------------------2 3 p0305 p0310 ( p0304 --------------------------3 p0305

15_1

mH

16_1

Ohms

%

Table 1-5

Unit Groups (p0505) Unit Choice for p0505 = 1 2 % % % % m/min % % % % % % % % % Hz kHz rpm ft/min ft/min Vrms V V mArms Aeff mA A A lbf ft 3 % % % % ft/min % % % % % % % % % 4 p2000 p2000 p2000 p2000 p2001 p2001 p2001 p2002 p2002 p2002 p2002 p2002 p2003 Reference quantity for %

Unit group

2_1 2_2 3_1 4_1 4_2 5_1 5_2 5_3 6_1 6_2 6_3 6_4 6_5 7_1

Hz kHz rpm m/min m/min Vrms V V mArms Aeff mA A A Nm

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-23

Parameters Overview of parameters

Table 1-5

Unit Groups (p0505), continued Unit Choice for p0505 = 1 2 Nm % % N % % % % % % % W kW 3 lbf ft lbf ft lbf lbf lbf HP HP HP HP HP HP HP HP lbf ft s/rad V/A A/V F F ft/s2 ft/s2 4 lbf ft % % lbf % % % % % % % HP HP % % % F F ft/s2 % 1.0 p2003 1.0 r2004 r2004 r2004 r2004 r2004 r2004 p2000/p2003 p2002/p2001 p2001/p2002 p2007 Reference quantity for %

Unit group

7_2 7_3 8_1 8_2 8_3 14_1 14_3 14_4 14_5 14_7 14_8 14_9 14_10 17_1 18_1 19_1 21_1 21_2 22_1 22_2 23_1 24_1 24_2 26_1 39_1 Table 1-6

Nm Nm N N N W W W kW kW kW W kW

Nms/rad % V/A A/V C K m/s2

% % C K m/s2 % Vrms s/m Ns/m % m/s %3

m/s2 Vrms s/m Ns/m Ns/m m/s3 1/s2

Vrms s/ft Vrms s/ft lbf s/ft lbf s/ft ft/s3

lbf s/ft % ft/s %3

p2000/p2003 p2007

1/s2

Unit Group (p0595) Unit Choice for p0595 = Value Unit Reference quantity for %

Unit group

9_1

The values that can be set and the technological units are shown in p0595 (See Section 1.2).

1-24

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters Overview of parameters

Parameter values Min Max Factory setting Minimum value of the parameter [unit] Maximum value of the parameter [unit] Shipped value (default) [unit] A different value may be displayed for certain parameters (e.g. p1800) at the initial commissioning stage. Reason: The setting of these parameters is determined by the operating environment of the Control Unit (e.g.depending on converter type, macro, Power Module).

Note: For SINAMICS G150/G130/S150, the macros and their settings are provided in the following documentation: References: /BAx/ x = 1, 2, 3 SINAMICS G150/G130/S150 Operating Instructions

Not for motor type Specifies for which motor type this parameter has no significance. ASM: Induction motor FEM: Separately excited synchronous motor PEM: Permanently excited synchronous motor REL: Reluctance motor/SIEMOSYN-Motor Expert List Specifies whether this parameter is available in the expert list of the specified drive objects in the commissioning software. 1: Parameter does exist in the expert list. 0: Parameter does not exist in the expert list. Notice: The user shall assume full responsibility for using parameters marked "Expert list: 0" (Parameter does not exist in the expert list). These parameters and their functionalities have not been tested and no further user documentation is available for them (e.g. function description). Moreover no support is ensured for these parameters by "Technical Support" (hotline).

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-25

Parameters Overview of parameters

Description Explanation of the function of a parameter. Values Lists the possible values of a parameter. Recommendation Information about recommended settings. Index The name and meaning of each individual index is specified for indexed parameters. The following applies to the values (min, max, factory setting) of indexed setting parameters: Min, Max: The setting range and unit apply to all indices. Factory setting: When all indices have the same factory setting, index 0 is specified with unit to represent all indices. When the indices have different factory settings, they are all listed individually with unit. Bit field For parameters with bit fields, the following information is provided about each bit: Bit number and signal name Meaning with signal states 0 and 1 Function diagram (optional) The signal is shown on this function diagram. Dependency Conditions which need to be fulfilled in connection with this parameter. Also includes special effects which can occur between this parameter and others. See also: List of other relevant parameters.

1-26

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters Overview of parameters

Safety-related information Important information which must be heeded to avoid the risk of physical injury or property damage. Information which must be observed to avoid problems. Information which the user or operator may find useful. Danger The description of this safety-related information can be found at the beginning of this manual (see Safety-related information). The description of this safety-related information can be found at the beginning of this manual (see Safety-related information). The description of this safety-related information can be found at the beginning of this manual (see Safety-related information). The description of this safety-related information can be found at the beginning of this manual (see Safety-related information). The description of this safety-related information can be found at the beginning of this manual (see Safety-related information). Information which the user or operator may find useful.

Alarm

Caution

Caution

Caution

Note

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-27

Parameters Overview of parameters

1.1.2

Numerical ranges of parameters

Note: The following numerical ranges for the parameters represent a complete overview of SINAMICS. The parameters for the product described in this List Manual are described in detail in Chapter 1.2. Parameters are grouped into the following numerical ranges:Table 1-7 Numerical Ranges of Parameters Description to 0099 0199 0299 0399 0499 0599 0699 0799 0839 0879 0899 0999 1199 1299 1399 1799 1899 1999 2099 2199 2399 2930 3699 3899 Operation and visualization Commissioning Power unit Motor Encoder Technology and units Thermal motor protection and motor model, maximum current Command sources and terminals on Control Unit, measuring sockets CDS, DDS data sets (e.g. switch over, copy) Sequencer (e.g. source for ON/OFF1) Control and status words PROFIBUS/PROFIdrive Setpoint channel Functions (e.g. motor holding brake) V/f control Closed-loop control Gating unit Power unit and motor identification Communication (PROFIBUS) Faults and alarms, monitoring functions Technology controller Fixed values (e.g. per cent, torque) Infeed control (Active Line Module) Friction characteristic

Range of 0000 0100 0200 0300 0400 0500 0600 0700 0800 0840 0880 0900 1000 1200 1300 1400 1800 1900 2000 2100 2200 2900 3400 3800

1-28

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters Overview of parameters

Table 1-7

Numerical Ranges of Parameters, continued Description to 3999 4199 4399 6999 7499 7899 8599 8799 8899 9399 9499 9899 9949 9999 10099 20999 25999 Management parameters Terminal Boards, Terminal Modules (e.g. TB30, TM31) Terminal Modules (e.g. TM15, TM17) SINAMICS GM/SM/GL Parallel connection of power units EEPROM read/write parameters Data and macro management CAN bus Communication Board Safety Integrated Parameter consistency and storage Safety Integrated Topology Diagnostics (internal) Safety Integrated Freie Funktionsblcke Drive Control Chart (DCC)

Range of 3900 4000 4200 6000 7000 7800 8500 8600 8800 9300 9400 9500 9900 9950 10000 20000 21000

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-29

Parameters List of parameters

1.2r0002CU_CX32, CU_S

List of parametersProduct: SINAMICS S, Version: 2503100, Language: eng

Control Unit operating display / CU op_displayCan be changed: Data type: Integer16 P-Group: Not for motor type: Min 0 Max 99 [00] Operation [10] Ready [20] Wait for run-up [31] Commissioning software download active [33] Remove topology error / acknowledge [34] Exit the commissioning mode [35] Carry out first commissioning [70] Initialization [80] Reset active [99] Internal software error Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting -

Description: Values:

Operating display for the Control Unit (CU). 0: 10: 20: 31: 33: 34: 35: 70: 80: 99:

Notice:

For several missing enable signals, the corresponding value with the highest number is displayed.

r0002A_INF, S_INF

Infeed operating display / INF op_displayCan be changed: Data type: Integer16 P-Group: Not for motor type: Min 0 Max 250 [00] Operation - everything enabled [21] Ready - set "enable operation" = "1" (p0852) [31] Rdy to power-up - pre-chrg running (p0857) [32] Ready to power-up - set "ON/OFF1" = "0/1" (p0840) [41] Power-on inhibit - set "ON/OFF1" = "0" (p0840) [42] Power-on inhibit - set "OC/OFF2" = "1" (p0844, p0845) [44] Power-on inhibit - connect 24 V to terminal EP (hardware) [45] Power-on inhib - remove fault cause, acknowledge fault [46] Power-on inhibit - exit comm mode (p0009, p0010) [60] Infeed de-activated/not operational [250] Device signals a topology error Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting -

Description: Values:

Operating display for the infeed. 0: 21: 31: 32: 41: 42: 44: 45: 46: 60: 250:

Dependency: Notice: Note:

Refer to: r0046 For several missing enable signals, the corresponding value with the highest number is displayed. OC: Operating condition EP: Enable Pulses (pulse enable) COMM: Commissioning

1-30

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters List of parameters

r0002SERVO, VECTOR

Drive operating display / Drv op_displayCan be changed: Data type: Integer16 P-Group: Not for motor type: Min 0 Max 250 [00] Operation - everything enabled [10] Operation - set "enable setpoint" = "1" (p1142, p1152) [11] Operation - set "enable speed controller" = "1" (p0856) [12] Operation - RFG frozen, set "RFG start" = "1" (p1141) [13] Operation - set "enable RFG" = "1" (p1140) [14] Oper. - MotID, excit. running and/or brake opens, SS2, SOS [15] Operation - open brake (p1215) [16] Oper - withdraw braking w/ OFF1 using "ON/OFF1" = "1" [17] Oper - braking w/ OFF3 can only be interrupted w/ OFF2 [18] Operation - brake on fault remove fault acknowledge [19] Operation - armature short-circuit active (p1230, p1231) [21] Ready - set "enable operation" = "1" (p0852) [22] Ready - de-magnetization running (p0347) [23] Ready - set "infeed operation" = "1" (p0864) [31] Ready to power-up - set "ON/OFF1" = "0/1" (p0840) [41] Power-on inhibit - set "ON/OFF1" = "0" (p0840) [42] Power-on inhibit - set "OC/OFF2" = "1" (p0844, p0845) [43] Power-on inhibit - set "OC/OFF3" = "1" (p0848, p0849) [44] Power-on inhibit - connect 24 V to terminal EP (hardware) [45] Power-on inhib - remove fault cause, acknowledge fault [46] Power-on inhibit - exit comm mode (p0009, p0010) [60] Infeed de-activated/not operational [250] Device signals a topology error Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting -

Description: Values:

Operating display for the drive. 0: 10: 11: 12: 13: 14: 15: 16: 17: 18: 19: 21: 22: 23: 31: 41: 42: 43: 44: 45: 46: 60: 250:

Dependency: Notice: Note:

Refer to: r0046 For several missing enable signals, the corresponding value with the highest number is displayed. OC: Operating condition EP: Enable Pulses (pulse enable) RFG: Ramp-function generator COMM: Commissioning MotID: Motor data identification SS2: Safe Stop 2 SOS: Safe Operating Stop

r0002B_INF

Infeed operating display / INF op_displayCan be changed: Data type: Integer16 P-Group: Not for motor type: Min 0 Max 250 [00] Operation - everything enabled [31] Rdy to power-up - pre-chrg running (p0857) [32] Ready to power-up - set "ON/OFF1" = "0/1" (p0840) [41] Power-on inhibit - set "ON/OFF1" = "0" (p0840) [42] Power-on inhibit - set "OC/OFF2" = "1" (p0844, p0845) [44] Power-on inhibit - connect 24 V to terminal EP (hardware) [45] Power-on inhib - remove fault cause, acknowledge fault Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting -

Description: Values:

Operating display for the infeed. 0: 31: 32: 41: 42: 44: 45:

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-31

Parameters List of parameters

46: 60: 250: Dependency: Notice: Note:

[46] Power-on inhibit - exit comm mode (p0009, p0010) [60] Infeed de-activated/not operational [250] Device signals a topology error

Refer to: r0046 For several missing enable signals, the corresponding value with the highest number is displayed. OC: Operating condition COMM: Commissioning

r0002TB30

TB30 operating display / TB30 op_displayCan be changed: Data type: Integer16 P-Group: Not for motor type: Min 0 Max 250 [00] Module in cyclic operation [40] Module not in cyclic operation [60] Fault [70] Initialization [80] Reset active [120] Module de-activated [250] Device signals a topology error Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting -

Description: Values:

Operating display for terminal board 30 (TB30). 0: 40: 60: 70: 80: 120: 250:

Notice:

For several missing enable signals, the corresponding value with the highest number is displayed.

r0002DMC20

DMC operating display / DMC op_displayCan be changed: Data type: Integer16 P-Group: Not for motor type: Min 0 Max 250 [00] Module in cyclic operation [40] Module not in cyclic operation [50] Alarm [60] Fault [70] Initialization [120] Module de-activated [250] Device signals a topology error Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting -

Description: Values:

Operating display for the DRIVE-CLiQ Hub Module Cabinet (DMC). 0: 40: 50: 60: 70: 120: 250:

Notice:

For several missing enable signals, the corresponding value with the highest number is displayed.

r0002TM31

TM31 operating display / TM31 op_displayCan be changed: Data type: Integer16 P-Group: Not for motor type: Min 0 Max 250 [00] Module in cyclic operation [40] Module not in cyclic operation [50] Alarm [60] Fault [70] Initialization Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting -

Description: Values:

Operating display for Terminal Module 31 (TM31). 0: 40: 50: 60: 70:

1-32

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters List of parameters

120: 250: Notice:

[120] Module de-activated [250] Device signals a topology error

For several missing enable signals, the corresponding value with the highest number is displayed.

r0002TM41

TM41 operating display / TM41 op_displayCan be changed: Data type: Integer16 P-Group: Not for motor type: Min 0 Max 250 [00] Operation - everything enabled [10] Operation - set "enable setpoint" = "1" (p1142) [12] Operation - RFG frozen, set "RFG start" = "1" (p1141) [13] Operation - set "enable RFG" = "1" (p1140) [18] Operation - brake on fault remove fault acknowledge [21] Ready - set "enable operation" = "1" (p0852) [31] Ready to power-up - set "ON/OFF1" = "0/1" (p0840) [41] Power-on inhibit - set "ON/OFF1" = "1/0" (p0840) [42] Power-on inhibit - set "OC/OFF2" = "1" (p0844) [43] Power-on inhibit - set "OC/OFF3" = "1" (p0848) [45] Power-on inhib - remove fault cause, acknowledge fault [46] Power-on inhibit - exit comm mode (p0009, p0010) [120] Module de-activated [250] Device signals a topology error Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting -

Description: Values:

Operating display for Terminal Module 41 (TM41). 0: 10: 12: 13: 18: 21: 31: 41: 42: 43: 45: 46: 120: 250:

Notice: Note:

For several missing enable signals, the corresponding value with the highest number is displayed. OC: Operating condition RFG: Ramp-function generator COMM: Commissioning

r0002TM17

TM17 operating display / TM17 op_displayCan be changed: Data type: Integer16 P-Group: Not for motor type: Min 0 Max 250 [00] Module in cyclic operation [40] Module not in cyclic operation [50] Alarm [60] Fault [70] Initialization [120] Module de-activated [250] Device signals a topology error Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting -

Description: Values:

Operating display for Terminal Module 17 (TM17). 0: 40: 50: 60: 70: 120: 250:

Notice:

For several missing enable signals, the corresponding value with the highest number is displayed.

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-33

Parameters List of parameters

r0002TM15

TM15 operating display / TM15 op_displayCan be changed: Data type: Integer16 P-Group: Not for motor type: Min 0 Max 250 [00] Module in cyclic operation [40] Module not in cyclic operation [50] Alarm [60] Fault [70] Initialization [120] Module de-activated [250] Device signals a topology error Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting -

Description: Values:

Operating display for Terminal Module 15 (TM15). 0: 40: 50: 60: 70: 120: 250:

Notice:

For several missing enable signals, the corresponding value with the highest number is displayed.

r0002TM15DI_DO

TM15DI/DO operating display / TM15D op_displayCan be changed: Data type: Integer16 P-Group: Not for motor type: Min 0 Max 250 [00] Module in cyclic operation [40] Module not in cyclic operation [50] Alarm [60] Fault [70] Initialization [120] Module de-activated [250] Device signals a topology error Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting -

Description: Values:

Operating display for Terminal Module 15 (TM15). 0: 40: 50: 60: 70: 120: 250:

Notice:

For several missing enable signals, the corresponding value with the highest number is displayed.

r0002TM54F_MA, TM54F_SL

TM54F operating display / TM54F op_displayCan be changed: Data type: Integer16 P-Group: Not for motor type: Min 0 Max 99 [00] Operation [10] Ready [20] Wait for run-up [31] Commissioning software download active [33] Remove topology error / acknowledge [34] Exit the commissioning mode [35] Carry out first commissioning [70] Initialization [80] Reset active [99] Internal software error Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting -

Description: Values:

Operating display for Terminal Module 54F (TM54F). 0: 10: 20: 31: 33: 34: 35: 70: 80: 99:

Notice:

For several missing enable signals, the corresponding value with the highest number is displayed.

1-34

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters List of parameters

p0003CU_CX32, CU_S

BOP access level / BOP access levelCan be changed: C1, U, T Data type: Integer16 P-Group: Not for motor type: Min 0 Max 4 Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting 1

Description: Values:

Sets the access level for reading and writing parameters using the Basic Operator Panel (BOP) and Advanced Operator Panel (AOP). 0: 1: 2: 3: 4: User-defined Standard Extended Expert Service

Note:

Access level 0 (user-defined): Parameters from the user-defined list (p0013). Access level 1 (standard): Parameters for the simplest operator control possibility (e.g. p1120 = ramp-function generator, ramp-up time). Access level 2 (extended): Parameters to operate the basic functions of the drive unit. Access level 3 (experts): Expert know-how is required for these parameters (e.g. BICO parameterization). Access level 4 (service): For these parameters, it is necessary that authorized service personnel enter the appropriate password (p3950).

p0004CU_CX32, CU_S

BOP display filter / BOP display filterCan be changed: C2(1), U, T Data type: Integer16 P-Group: Not for motor type: ASM Min 0 Max 99 All parameters Displays, signals Power unit Motor Encoder/pos enc Technology/units Digital inputs/outputs commands sequence control Analog inputs/outputs Setpoint channel/ramp-fct generator Functions V/f control Control Data sets Basic positioner Gating unit Motor identification Communication Faults, alarms, monitoring functions Closed-loop position control Free function blocks Trace and function generator OA parameter Topology Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting 0

Description: Values:

Sets the display filter for parameters for Basic Operator Panel (BOP) and Advanced Operator Panel (AOP). 0: 1: 2: 3: 4: 5: 7: 8: 10: 12: 13: 14: 15: 17: 18: 19: 20: 21: 25: 28: 47: 50: 90:

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-35

Parameters List of parameters

95: 98: 99: Dependency: Note:

Safety Integrated Command Data Sets (CDS) Drive Data Sets (DDS)

Refer to: p0003 Example: p0004 = 3: Only the parameters for the motor are displayed.

p0005[0...1]A_INF, B_INF, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR

BOP operating display selection / BOP op_disp selCan be changed: U, T Data type: Unsigned16 P-Group: Not for motor type: Calculated: Dynamic index: Units group: Access level: 2 Func. diagram: Unit selection: Expert list: 1

Min 0 Description:

Max 65535

Factory setting [0] 2 [1] 0

Sets the parameter number and parameter index for display for p0006 = 2, 4 for the Basic Operator Panel (BOP). Examples for the SERVO drive object: p0005 = 21: Speed actual value smoothed (r0021) p0005 = 25: Drive output voltage smoothed (r0025) p0005 = 26: Speed actual value smoothed (r0026) p0005 = 27: Absolute current actual value, smoothed (r0027)

Index: Dependency: Note:

[0] = Parameter number [1] = Parameter index Refer to: p0006 Procedure: 1. The parameter number to be displayed should be set in index 0. Only the monitoring parameters (only read parameters) can be set, that actually exist for the actual drive object. If the set parameter number is not indexed, or if there is an index in index 1 that lies outside the valid range of the set parameter, then index 1 is automatically set to 0. 2. The index that belongs to the parameter set in index 0 should be set in index 1. The permissible changes in index 1 always depend on the parameter number set in index 0.

p0006CU_S, DMC20, TB30, TM15, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL

BOP operating display mode / BOP op_ disp modeCan be changed: U, T Data type: Integer16 P-Group: Not for motor type: Calculated: Dynamic index: Units group: Access level: 3 Func. diagram: Unit selection: Expert list: 1

Min 4 Description: Values: Dependency: Note:

Max 4

Factory setting 4

Sets the mode of the operating display for the Basic Operator Panel (BOP) in the operating states "ready" and "operation". 4: p0005 Refer to: p0005 Mode 0 ... 3 can only be selected if also r0020, r0021 are available on the drive object. Mode 4 is available for all drive objects.

1-36

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters List of parameters

p0006A_INF, B_INF, SERVO, S_INF, VECTOR

BOP operating display mode / BOP op_ disp modeCan be changed: U, T Data type: Integer16 P-Group: Not for motor type: Min 0 Max 4 Calculated: Dynamic index: Units group: Access level: 3 Func. diagram: Unit selection: Expert list: 1 Factory setting 4

Description: Values:

Sets the mode of the operating display for the Basic Operator Panel (BOP) in the operating states "ready" and "operation". 0: 1: 2: 3: 4: Operation --> r0021, otherwise r0020 r0021 Operation --> r0021, otherwise r0020 Operation --> p0005, otherwise p0005 r0020 Operation --> r0002, otherwise r0002 r0020 p0005

Dependency: Note:

Refer to: p0005 Mode 0 ... 3 can only be selected if also r0020, r0021 are available on the drive object. Mode 4 is available for all drive objects.

p0007CU_S

BOP background lighting / BOP lightingCan be changed: U, T Data type: Unsigned32 P-Group: Not for motor type: Min 0 [s] Max 2000 [s] Calculated: Dynamic index: Units group: Access level: 3 Func. diagram: Unit selection: Expert list: 1 Factory setting 0 [s]

Description: Note:

Sets the delay time until the background lighting of the Basic Operator Panel (BOP) is switched-off. If no keys are actuated, then the background lighting automatically switches itself off after this time has expired. p0007 = 0: Background lighting is always switched on (factory setting).

p0008CU_S

BOP drive object after booting / BOP DO selectCan be changed: U, T Data type: Unsigned16 P-Group: Not for motor type: Min 1 Max 65535 Calculated: Dynamic index: Units group: Access level: 3 Func. diagram: Unit selection: Expert list: 1 Factory setting 1

Description: Note:

Sets the required drive object that is active at the Basic Operator Panel (BOP) after booting. The value from p0008 initializes the display on the Basic Operator Panel (BOP) at the top left after booting. The drive object Control Unit is selected using the value 1.

p0009CU_CX32, CU_S

Device commissioning parameter filter / Dev comm par_filtCan be changed: C1, T Data type: Integer16 P-Group: Not for motor type: Min 0 Max 50 Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting 1

Description:

Sets the device and basic drive commissioning. By appropriately setting this parameter, those parameters are filtered that can be written into in the various commissioning steps.

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-37

Parameters List of parameters

Values:

0: 1: 2: 3: 4: 29: 30: 50:

Ready Device configuration Defining the drive type/function module Drive basis configuration Data set basis configuration Device download Parameter reset OA application configuration

Note:

The drives can only be powered-up outside the device commissioning (the inverter enabled). In this case, p0009 must be 0 (Ready) and the individual drive objects must have already gone into operation (p0010). p0009 = 1: Device configuration At the first commissioning of the devices, after booting, the device is in the "device configuration" state. To start the internal automatic first commissioning of the drive unit, p0009 should be set to 0 (Ready) after the ID for the actual topology (r0098) was transferred into the ID for the target topology (p0099). To do this, it is sufficient to set a single index value of p0099[x] the same as r0098[x]. Before the device has been completely commissioned, no other parameter can be changed. After the first commissioning was carried out, in this state, when required, other basic device configuration parameters can be adapted (e.g. the basic sampling time in p0110). p0009 = 2: Defines the drive type / function module In this state, the drive object types and/or the function modules can be changed or selected for the individual drive objects. To do this, the drive object type can be set using p0107[0...15] and the function can be set using p0108[0...15] (refer to p0101[0...15]). p0009 = 3: Drive basis configuration In this state, after the device has been commissioned for the first time, basic changes can be made for the individual drive objects (e.g. sampling times in p0111, p0112, p0115 and the number of data sets in p0120, p0130, p0140, p0170, p0180). p0009 = 4: Data set basis configuration In this state, after the device has been commissioned for the first time, for the individual drive objects changes can be made regarding the assignment of the components (p0121, p0131, p0141, p0151, p0161) to the individual data sets and the assignment of the power unit, motor and encoder to the drive data sets (p0185, ...). p0009 = 29: Device download If a download is made using the commissioning software, the device is automatically brought into this state. After the download has been completed, p0009 is automatically set to 0 (ready). It is not possible to manually set p0009 to this value. p0009 = 30: Parameter reset In order to bring the complete unit into the "first commissioning" state or to load the parameters saved using p0977, to start, p0009 must be set to this value. p0976 can then be changed to the required value. p0009 = 50: OEM application configuration In this state, after the device has been commissioned for the first time, changes can be made for the individual drive objects regarding the activity (p4956) of the OEM applications.

p0010A_INF, B_INF, S_INF

Infeed commissioning parameter filter / INF comm par_filtCan be changed: C2(1), T Data type: Integer16 P-Group: Not for motor type: Min 0 Max 30 Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting 1

Description: Values:

Sets the parameter filter to commission an infeed unit. Setting this parameter filters-out the parameters that can be written into in the various commissioning steps. 0: 1: 2: 5: 29: 30: Ready Quick commissioning Power unit commissioning Technological application/units Download Parameter reset

Note:

The drive can only be powered-up outside the drive commissioning (inverter enable). To realize this, this parameter must be set to 0.

1-38

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters List of parameters

For p3900 not equal to 0, at the end of the quick commissioning, this parameter is automatically reset to 0. Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.

p0010SERVO, VECTOR

Drive, commissioning parameter filter / Drv comm. par_filtCan be changed: C2(1), T Data type: Integer16 P-Group: Not for motor type: Min 0 Max 95 Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: 2800, 2846 Unit selection: Expert list: 1 Factory setting 1

Description: Values:

Sets the parameter filter to commission a drive. Setting this parameter filters-out the parameters that can be written into in the various commissioning steps. 0: 1: 2: 3: 4: 5: 15: 17: 25: 29: 30: 95: Ready Quick commissioning Power unit commissioning Motor commissioning Encoder commissioning Technological application/units Data sets Basic positioning commissioning Commissioning the position control Download Parameter reset Safety Integrated commissioning

Note:

The drive can only be powered-up outside the drive commissioning (inverter enable). To realize this, this parameter must be set to 0. For p3900 not equal to 0, at the end of the quick commissioning, this parameter is automatically reset to 0. Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.

p0010TB30

TB30 commissioning parameter filter / TB30 comm.par_filtCan be changed: C2(1), T Data type: Integer16 P-Group: Not for motor type: Min 0 Max 30 Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting 0

Description:

Sets the parameter filter for commissioning a terminal board 30 (TB30). Setting this parameter filters-out the parameters that can be written into in the various commissioning steps. For the BOP, this setting also causes the read access operations to be filtered.

Values:

0: 29: 30:

Ready Download Parameter reset

Dependency: Note:

Refer to: p0970 Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.

p0010TM31

TM31 commissioning parameter filter / TM31 comm par_filtCan be changed: C2(1), T Data type: Integer16 P-Group: Not for motor type: Min 0 Max 30 Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting 0

Description:

Sets the parameter filter for commissioning a Terminal Module 31 (TM31). Setting this parameter filters-out the parameters that can be written into in the various commissioning steps.

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-39

Parameters List of parameters

For the BOP, this setting also causes the read access operations to be filtered. Values: 0: 29: 30: Ready Download Parameter reset

Dependency: Note:

Refer to: p0970 Only the following values are possible: p0010 = 0, 30 Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.

p0010TM41

TM41 commissioning parameter filter / TM41 comm par_filtCan be changed: C2(1), T Data type: Integer16 P-Group: Not for motor type: Min 0 Max 30 Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting 0

Description:

Sets the parameter filter for commissioning a Terminal Module 41 (TM41). Setting this parameter filters-out the parameters that can be written into in the various commissioning steps. For the BOP, this setting also causes the read access operations to be filtered.

Values:

0: 4: 5: 29: 30:

Ready Encoder commissioning Technological application/units Download Parameter reset

Dependency: Note:

Refer to: p0970 Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.

p0010TM17

TM17 commissioning parameter filter / TM17 comm par_filtCan be changed: C2(1), T Data type: Integer16 P-Group: Not for motor type: Min 0 Max 30 Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting 0

Description:

Sets the parameter filter for commissioning a Terminal Module 17 (TM17). Setting this parameter filters-out the parameters that can be written into in the various commissioning steps. For the BOP, this setting also causes the read access operations to be filtered.

Values:

0: 29: 30:

Ready Download Parameter reset

Dependency: Note:

Refer to: p0970 Only the following values are possible: p0010 = 0, 30 Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.

p0010TM15

TM15 commissioning parameter filter / TM15 comm par_filtCan be changed: C2(1), T Data type: Integer16 P-Group: Not for motor type: Min 0 Max 30 Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting 0

Description:

Sets the parameter filter for commissioning a Terminal Module 15 (TM15). Setting this parameter filters-out the parameters that can be written into in the various commissioning steps. For the BOP, this setting also causes the read access operations to be filtered.

1-40

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters List of parameters

Values:

0: 29: 30:

Ready Download Parameter reset

Dependency: Note:

Refer to: p0970 Only the following values are possible: p0010 = 0, 30 Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.

p0010TM15DI_DO

TM15DI/DO commissioning the parameterizing filter / TM15D com par_filtCan be changed: C2(1), T Data type: Integer16 P-Group: Not for motor type: Min 0 Max 30 Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting 0

Description:

Sets the parameter filter for commissioning a Terminal Module 15 (TM15). Setting this parameter filters-out the parameters that can be written into in the various commissioning steps. For the BOP, this setting also causes the read access operations to be filtered.

Values:

0: 29: 30:

Ready Download Parameter reset

Dependency: Note:

Refer to: p0970 Only the following values are possible: p0010 = 0, 30 Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.

p0010TM54F_MA

TM54F commissioning parameter filter / TM54F com par_filtCan be changed: C2(1), T Data type: Integer16 P-Group: Not for motor type: Min 0 Max 95 Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting 0

Description:

Sets the parameter filter for commissioning a Terminal Module 54F (TM54F). Setting this parameter filters-out the parameters that can be written into in the various commissioning steps. For the BOP, this setting also causes the read access operations to be filtered.

Values:

0: 29: 30: 95:

Ready Download Parameter reset Safety Integrated commissioning

Dependency: Note:

Refer to: p0970 Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.

p0011CU_S

BOP password entry (p0013) / BOP passw ent p13Can be changed: U, T Data type: Unsigned16 P-Group: Functions Not for motor type: Min 0 Max 65535 Calculated: Dynamic index: Units group: Access level: 3 Func. diagram: Unit selection: Expert list: 1 Factory setting 0

Description: Dependency:

Sets the password for the Basic Operator Panel (BOP). Refer to: p0012, p0013

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-41

Parameters List of parameters

p0012CU_S

BOP password acknowledgement (p0013) / BOP passw ackn p13Can be changed: U, T Data type: Unsigned16 P-Group: Functions Not for motor type: Min 0 Max 65535 Calculated: Dynamic index: Units group: Access level: 3 Func. diagram: Unit selection: Expert list: 1 Factory setting 0

Description: Dependency:

Acknowledges the password for the Basic Operator Panel (BOP). Refer to: p0011, p0013

p0013[0...49]A_INF, B_INF, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR

BOP user-defined list / BOP listCan be changed: U, T Data type: Unsigned16 P-Group: Functions Not for motor type: Calculated: Dynamic index: Units group: Access level: 3 Func. diagram: Unit selection: Expert list: 1

Min 0 Description: Activation: 1. p0003 = 3 (expert).

Max 65535

Factory setting 0

Sets the required parameters to read and write via the Basic Operator Panel (BOP).

2. p0013[0...49] = requested parameter number 3. If required, enter p0011 = password in order to prevent non-authorized de-activation. 4. p0003 = 0 --> activates the selected user-defined list. De-activation/change: 1. p0003 = 3 (expert). 2. If required, p0012 = p0011, in order to be authorized to change or de-activate the list. 3. If required p0013[0...49] = required parameter number. 4. p0003 = 0 --> activates the modified user-defined list. 5. p0003 > 0 --> de-activates the user-defined list. Dependency: Note: Refer to: p0009, p0011, p0012, p0976 The following parameters can be read and written on the Control Unit drive object: - p0003 (access stage) - p0009 (device commissioning, parameter filter) - p0012 (BOP password acknowledgement (p0013)) The following applies for the user-defined list: - password protection is only available on the drive object Control Unit and is valid for all of the drive objects. - p0013 cannot be included in the user-defined list for all drive objects. - p0003, p0009, p0011, p0012, p0976 cannot, for the drive object Control Unit, be included in the user-defined list. - the user-defined list can be cleared and de-activated "restore factory setting". A value of 0 means: Entry is empty.

1-42

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters List of parameters

p0015CU_CX32, CU_S

Macro drive unit / Macro drv unitCan be changed: C1 Data type: Unsigned32 P-Group: Not for motor type: Min 0 Max 999999 Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting 0

Description:

Runs the appropriate ACX file on the CompactFlash card. The selected ACX file must be located in the following directory: ... /PMACROS/DEVICE/P15/PMxxxxxx.ACX Example: p0015 = 6 --> the file PM000006.ACX is run.

Dependency:

The ACX file to be run must be created according to the definition for ACX macros and must be saved in the directory intended on the CompactFlash card. Refer to: p0700, p1000, p1500, r8570 The macros in the specified directory are displayed in r8570. r8570 is not in the Expert list of the commissioning software. Macros available as standard are described in the technical documentation of the particular product.

Note:

p0015

Macro drive object / Macro DOCalculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Max 999999 Factory setting 0

Can be changed: C2(1) A_INF, B_INF, SERVO, S_INF, Data type: Unsigned32 TM15DI_DO, TM31, P-Group: Commands VECTOR Not for motor type: Min 0 Description:

Runs the appropriate ACX file on the CompactFlash card. The selected ACX file must be located in the following directory: ... /PMACROS//P15/PMxxxxxx.ACX Example: p0015 = 6 --> the file PM000006.ACX is run.

Dependency:

The ACX file to be run must be created according to the definition for ACX macros and must be saved in the directory intended on the CompactFlash card. Refer to: p0700, p1000, p1500, r8570 No errors were issued during fast commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group! The macros in the specified directory are displayed in r8570. r8570 is not in the Expert list of the commissioning software. Macros available as standard are described in the technical documentation of the particular product.

Notice: Note:

r0018CU_CX32, CU_S

Control Unit Firmware-Version / CU FW versionCan be changed: Data type: Unsigned32 P-Group: Not for motor type: Min Max Calculated: Dynamic index: Units group: Access level: 1 Func. diagram: Unit selection: Expert list: 1 Factory setting -

Description: Dependency: Note:

Displays the firmware version of the Control Unit. Refer to: r0128, r0148, r0158, r0197, r0198 Example: The value 1010100 should be interpreted as V01.01.01.00.

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-43

Parameters List of parameters

r0019.0...14CU_S

CO/BO: Control word BOP / STW BOPCan be changed: Data type: Unsigned16 P-Group: Displays, signals Not for motor type: Min Max Signal name ON / OFF (OFF1) No coast-down / coast-down (OFF2) No Quick Stop / Quick Stop (OFF3) Acknowledge fault (0 -> 1) Motorized potentiometer raise Motorized potentiometer lower 1 signal ON No coast down No Quick Stop Yes Yes Yes Calculated: Dynamic index: Units group: Access level: 3 Func. diagram: Unit selection: Expert list: 1 Factory setting 0 signal OFF (OFF1) Coast down (OFF2) Quick Stop (OFF3) No No No FP -

Description: Bit field:

Displays the control word for the Basic Operator Panel (BOP). Bit 00 01 02 07 13 14

r0020SERVO, VECTOR

Speed setpoint smoothed / n_set smthCan be changed: Data type: Floating Point P-Group: Displays, signals Not for motor type: Min - [RPM] Max - [RPM] Calculated: Dynamic index: Units group: 3_1 Access level: 2 Func. diagram: 5020, 6799 Unit selection: p0505 Expert list: 1 Factory setting - [RPM]

Description: Dependency: Note:

Displays the actual, smoothed speed setpoint at the input of the speed controller or V/f characteristic (after the interpolator). Refer to: r0060 Smoothing time constant = 100 ms The signal is not suitable as process quantity and may only be used as display quantity. The speed setpoint is available smoothed (r0020) and unsmoothed (r0060).

r0020SERVO (Lin)

Velocity setpoint smoothed / v_set smthCan be changed: Data type: Floating Point P-Group: Displays, signals Not for motor type: Min - [m/min] Max - [m/min] Calculated: Dynamic index: Units group: 4_1 Access level: 2 Func. diagram: 5020, 6799 Unit selection: p0505 Expert list: 1 Factory setting - [m/min]

Description: Dependency: Note:

Displays the actual, smoothed velocity setpoint at the input of the velocity controller or V/f characteristic (after the interpolator). Refer to: r0060 Smoothing time constant = 100 ms The signal is not suitable as process quantity and may only be used as display quantity. The velocity setpoint is available smoothed (r0020) and unsmoothed (r0060).

1-44

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters List of parameters

r0021SERVO, VECTOR

CO: Actual speed smoothed / n_ist smoothCan be changed: Data type: Floating Point P-Group: Displays, signals Not for motor type: Min - [RPM] Max - [RPM] Calculated: Dynamic index: Units group: 3_1 Access level: 2 Func. diagram: 1580, 1680, 4710, 6799 Unit selection: p0505 Expert list: 1 Factory setting - [RPM]

Description: Dependency: Note:

Displays the smoothed actual value of the motor speed. Refer to: r0063 Smoothing time constant = 100 ms The signal is not suitable as process quantity and may only be used as display quantity. The value displayed in r0021 is the smoothed value of r0063.

r0021SERVO (Lin)

CO: Actual velocity smoothed / v_act smoothCan be changed: Data type: Floating Point P-Group: Displays, signals Not for motor type: Min - [m/min] Max - [m/min] Calculated: Dynamic index: Units group: 4_1 Access level: 2 Func. diagram: 1580, 1680, 4710, 6799 Unit selection: p0505 Expert list: 1 Factory setting - [m/min]

Description: Dependency: Note:

Displays the smoothed actual value of the motor velocity. Refer to: r0063 Smoothing time constant = 100 ms The signal is not suitable as process quantity and may only be used as display quantity. The value displayed in r0021 is the smoothed value of r0063.

r0022SERVO, VECTOR

Speed actual value rpm smoothed / n_ist rpm smoothCan be changed: Data type: Floating Point P-Group: Displays, signals Not for motor type: Min - [RPM] Max - [RPM] Calculated: Dynamic index: Units group: Access level: 2 Func. diagram: 1580, 1680, 4710, 6799 Unit selection: Expert list: 1 Factory setting - [RPM]

Description: Dependency: Note:

Displays the smoothed actual value of motor speed. r0022 is identical to r0021, however, it always has units of rpm and contrary to r0021 cannot be changed over. Refer to: r0063 Smoothing time constant = 100 ms The signal is not suitable as process quantity and may only be used as display quantity. The value displayed in r0022 is the smoothed value of r0063.

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-45

Parameters List of parameters

r0022SERVO (Lin)

Actual velocity smoothed / v_act smoothCan be changed: Data type: Floating Point P-Group: Displays, signals Not for motor type: Min - [m/min] Max - [m/min] Calculated: Dynamic index: Units group: Access level: 2 Func. diagram: 1580, 1680, 4710, 6799 Unit selection: Expert list: 1 Factory setting - [m/min]

Description: Dependency: Note:

Displays the smoothed actual value of the motor velocity. Refer to: r0063 Smoothing time constant = 100 ms The signal is not suitable as process quantity and may only be used as display quantity. The value displayed in r0022 is the smoothed value of r0063.

r0024A_INF, S_INF

CO: Line supply frequency smoothed / f_line smoothCan be changed: Data type: Floating Point P-Group: Displays, signals Not for motor type: Min - [Hz] Max - [Hz] Calculated: Dynamic index: Units group: Access level: 3 Func. diagram: 8850, 8950 Unit selection: Expert list: 1 Factory setting - [Hz]

Description: Dependency: Note:

Displays the smoothed line supply frequency. Refer to: r0066 Smoothing time constant = 300 ms The signal is not suitable as process quantity and may only be used as display quantity. The line frequency is available smoothed (r0024) and unsmoothed (r0066). A positive sign of the frequency is obtained when the line supply phases U, V and W are connected with the correct phase sequence. A negative sign of the frequency is obtained when the 3 line phases are interchanged therefore designating a negative direction of the rotating field of the 3-phase line supply voltage.

r0024SERVO, VECTOR

Output frequency smoothed / f_outp smoothCan be changed: Data type: Floating Point P-Group: Displays, signals Not for motor type: Min - [Hz] Max - [Hz] Calculated: Dynamic index: Units group: Access level: 3 Func. diagram: 1690, 5300, 5730, 6799 Unit selection: Expert list: 1 Factory setting - [Hz]

Description: Dependency: Note:

Displays the smoothed converter frequency. Refer to: r0066 Smoothing time constant = 100 ms The signal is not suitable as process quantity and may only be used as display quantity. The output frequency is available smoothed (r0024) and unsmoothed (r0066).

1-46

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

Parameters List of parameters

r0025[0...3]A_INF, S_INF

CO: Input voltage smoothed / V_inp smoothCan be changed: Data type: Floating Point P-Group: Displays, signals Not for motor type: Min - [Vrms] Max - [Vrms] Calculated: Dynamic index: Units group: Access level: 2 Func. diagram: 8850, 8950 Unit selection: Expert list: 1 Factory setting - [Vrms]

Description: Index:

Displays the smoothed actual value of the input voltage. [0] = Voltage at the input terminals of the power unit [1] = Voltage at the VSM and at the input terminals of the line filter [2] = Voltage of the voltage source from the line supply model [3] = Smoothed voltage of the voltage source from line supply model Refer to: r0072 Smoothing time constant = 300 ms The signals are not suitable as process quantity and may only be used as display quantities. The input voltages are available smoothed (r0025) and unsmoothed (r0072). r0025[0]: Pulsed voltage at the line supply input terminals of the power unit. The value is calculated from the modulation depth r0074 and is therefore only correct in the closed-loop controlled mode and when the pulses are enabled. r0025[1]: Absolute voltage at the input terminals of the line filter or the connection point of a VSM. The value is calculated from the VSM measured values r3661 and r3662 and is therefore equal to 0 if a VSM is not connected. r0025[2]: Estimated value for the voltage of the voltage source that is calculated in the voltage model of the line supply PLL. r0025[3]: Smoothed display value of the filtered source voltage from r0072[3].

Dependency: Note:

r0025SERVO, VECTOR

CO: Output voltage smoothed / V_outp smoothCan be changed: Data type: Floating Point P-Group: Displays, signals Not for motor type: Min - [Vrms] Max - [Vrms] Calculated: Dynamic index: Units group: Access level: 2 Func. diagram: 1690, 5730, 6799 Unit selection: Expert list: 1 Factory setting - [Vrms]

Description: Dependency: Note:

Displays the smoothed output voltage of the power unit. Refer to: r0072 Smoothing time constant = 100 ms The signal is not suitable as process quantity and may only be used as display quantity. The output voltage is available smoothed (r0025) and unsmoothed (r0072).

r0026A_INF, B_INF, S_INF

CO: DC link voltage smoothed / Vdc smoothCan be changed: Data type: Floating Point P-Group: Displays, signals Not for motor type: Min - [V] Max - [V] Calculated: Dynamic index: Units group: Access level: 2 Func. diagram: 5730, 6799, 8750, 8850, 8950 Unit selection: Expert list: 1 Factory setting - [V]

Description: Dependency: Notice: Note:

Displays the smoothed actual value of the DC link voltage. Refer to: r0070 This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the unsmoothed value should be used. A_INF, B_INF, S_INF: smoothing time constant = 300 ms

Siemens AG 2007 All Rights Reserved SINAMICS S List Manual (LH1), 07/2007

1-47

Parameters List of parameters

The signal is not suitable as process quantity and may only be used as display quantity. The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).

r0026SERVO, VECTOR

CO: DC link voltage smoothed / Vdc smoothCan be changed: Data type: Floating Point P-Group: Displays, signals Not for motor type: Min - [V] Max - [V] Calculated: Dynamic index: Units group: Access level: 2 Func. diagram: 5730, 8750, 8850, 8950 Unit selection: Expert list: 1 Factory setting - [V]

Description: Dependency: Notice:

Displays the smoothed actual value of the DC link voltage. Refer to: r0070 For SINAMICS S120 AC Drive (AC/AC) the following applies: When measuring a DC link voltage < 200 V, for the Power Module (e.g. PM340) a valid measured value is not supplied. In this case, when an external 24V power supply is connected, a value of approx. 24 V is displayed in the display parameter.

Note:

SERVO, VECTOR: Smoothing time constant = 100 ms The signal is not suitable as process quantity and may only be used as display quantity. The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).

r0027A_INF, SERVO, S_INF, VECTOR

CO: Absolute actual current smoothed / I_act abs val smthCan be changed: Data type: Floating Point P-Group: Displays, signals Not for motor type: Min - [Arms] Max - [Arms] Calculated: Dynamic index: Units group: Access level: 2 Func. diagram: 5730, 6799, 8850, 8950 Unit selection: Expert list: 1 Factory setting - [Arms]

Description: Dependency: Notice: Note:

Displays the smoothed absolute actual current value. Refer to: r0068 This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations.