    2008 IEEE PES General Meeting: Panel on Best Practices in State Estimation

    Experiences and practices on State Estimation in

    RTE (French Transmission System Operator)

    Patrick Panciatici (RTE), Yacine Hassaine (RTE)

  • 7/28/2019 RTE France

    2/14

    2008 IEEE PES General Meeting: Panel on Best Practices in State Estimation, 2

    Presentation of SE in RTE

    RTE operates the whole French transmission system : (400kV to 63kV, 2500

    substations, 100300 km of circuits and 1150 transformers), 7 regional control

    centers and 1 National

    State Estimation provides input for all networks analysis

    Measurements are received every 10 s.

    An event is sent, when the status of a switching device changes.

    Which kind of measurements ?Active and reactive power flows on branches,

    Active and reactive powers on load and generators,

    Voltage magnitudes in substation on busbars,

    Internal substation current measurements and tap positions are not transmitted.

    Coherent stateMeasurements, Topology

    Electrical characteristics

    State

    Estimation

  • 7/28/2019 RTE France

    3/14

  • 7/28/2019 RTE France

    4/14

    2008 IEEE PES General Meeting: Panel on Best Practices in State Estimation, 4

    Snapshot Generation : Consistency between topology and measurements

    A new status may arrive before measurements affected by the switching, this could lead

    to an incoherent state between topology and measurements and to a problem in state

    estimation.

    To minimize the probability of occurrence of this problem, we apply a very important and

    classical rule to generate a snapshot

    We wait 20s to generate a snapshot after the reception of the last switching device

    status.

    A snapshot is generated after 1mn even if the condition isnt fulfilled

    Presentation of SE in RTE

    t t+10

    Measurements (t)

    Measurements (t+10)

    switching

    Inconsistent

    Snapshot

  • 7/28/2019 RTE France

    5/142008 IEEE PES General Meeting: Panel on Best Practices in State Estimation, 5

    Observability :

    A numerical observability is used, with a decoupled Jacobian matrix.

    better numerical robustness in SE

    Critical pseudo-measurements are added in unobservable areas to restore

    observability.

    no effect on estimated states

    The EHV network is more observable than HV network.

    pair measurement s ( P,Q) in EHV sometimes not in HV

    The percentage of observable nodes varies from 80% to 92%.

    Presentation of SE in RTE

  • 7/28/2019 RTE France

    6/142008 IEEE PES General Meeting: Panel on Best Practices in State Estimation, 6

    Presentation of SE in RTE

    Computing algorithms :

    For real time : A classical L2 cost function is minimized using Gauss-Newton

    algorithm

    For off line data validation : A M-estimation function is minimized using a trust

    region method based on Luvember-Marquardt algorithm.

    Estimation of OLTC taps, there are two steps :

    First step : ratios of transformers are considered as continuous variables

    Second step : ratios are fixed to the nearest discrete value

    For each node, the estimated nodal injection is dispatched among loads and

    generators

    Maximum values are taken into account

    If the estimated nodal injection is greater than the total of maximum values, a fictitious

    load is created to balance the s stem.

  • 7/28/2019 RTE France

    7/142008 IEEE PES General Meeting: Panel on Best Practices in State Estimation, 7

    Presentation of SE in RTE

    Bad data detection :

    Detection of bad data is based on a 2 test.

    If2 test fails, we use normalized residuals to detect bad data

    an iterative process deletes one by one bad data and reruns a SE (maximum 10 iterations)

    This approach suppose that only measurement may be contaminated by bad

    data. This hypothesis is not always satisfied, in this case robust state estimation

    helps to find the problem.

    We define two kind of robustness:Numerical robustness, it deals with the reduction of divergence

    Trust region method

    Bad data robustness, which reduce the bad data effect.

    M-estimator rather L2 estimator

  • 7/28/2019 RTE France

    8/142008 IEEE PES General Meeting: Panel on Best Practices in State Estimation, 8

    Presentation of SE in RTE

    Visualization

    The same tool in :

    Real time

    Study mode.

    we can load a snapshot (green :

    observable, red : unobservable)

    For each substation, a comparison is

    possible between :

    Estimated state

    Measured state

    Figure : The EHV network of RTE (study mode)

  • 7/28/2019 RTE France

    9/142008 IEEE PES General Meeting: Panel on Best Practices in State Estimation, 9

    Presentation of SE in RTE

    Visualization :

    Figure 2 : 400kV substation , measured state Figure 3 : 400kV substation , estimated state

  • 7/28/2019 RTE France

    10/14

    2008 IEEE PES General Meeting: Panel on Best Practices in State Estimation, 10

    Use of SE in RTE

    a. Real time operations :

    State estimation builds a coherent state before any contingency analysis.

    b. Building of reference base cases :

    From 2 to 4 reference cases per day are built, which are used to build forecast casesfor operational planning , for ATC computation, .

    We developed a collaborative process between our 7 regional control centers and

    our national control center

    Building of reference base cases : principles

  • 7/28/2019 RTE France

    11/14

    2008 IEEE PES General Meeting: Panel on Best Practices in State Estimation, 11

    Initialization by National Control Center

    Import snapshot of Region 1

    EHV-HV

    Import snapshot of Region 7 EHV-

    HV

    Merging of 7 regional snapshots (EHV-

    HV)

    Export state of Region 1 EHV(National)-

    HV(regional)

    Export state of Region 7 EHV(National)-

    HV(regional)

    manual validation

    (Region 1)

    manual validation

    (Region 7)

    Merging of 7 regional corrected states

    (EHV-HV)

    Final manual validation by NCC (EHV-HV)

    Export final corrected state of Region 1

    EHV(National)-HV(regional)

    Export final corrected state of Region 7

    EHV(National)-HV(regional)

    .

    .

    Building of reference base cases : principles

  • 7/28/2019 RTE France

    12/14

    2008 IEEE PES General Meeting: Panel on Best Practices in State Estimation, 12

    Manual Validation based on quality criteria

    SE quality criteria :

    Number of iterations or divergenceNumber of unobservable nodesRate of redundancyNumber of fictitious loadsPossible inconsistencies between topology and measurementsNumber of critical measurementsNumber of bad data

    A change of one these criteria requires an analysis

    A global quality index based on these criteria is given to each

    reference base case.

  • 7/28/2019 RTE France

    13/14

    2008 IEEE PES General Meeting: Panel on Best Practices in State Estimation, 13

    Building of reference base cases : Work Flow monitoring

  • 7/28/2019 RTE France

    14/14

    2008 IEEE PES General Meeting: Panel on Best Practices in State Estimation, 14

    Most important challenges

    We need to have more coordination between European TSOs, an

    European network model is mandatory Hierarchical SE.

    The robustness of state estimation :

    Still a challenging subject No substation internal measurements transmitted => difficult to detect an erroron topology

    A state estimation running at the substation level could improve the situation. Ensuring the consistency between topology and measurements, full coherent

    state transmitted (status of switching devices and measurements for example

    each 1 sec.).

    To improve the measurement system, the worst stage must be

    improved first.In our case the first limiting factor is the LAN at substation level ( old protocol

    using 8 bits for measurements).