RSIC ACOUSTIC ASSEMBLY
FLOOR CEILING ASSEMBLY
DIRECT FIX TO WOOD I JOIST
F4543.05 STC 62 IIC 61
CONSTRUCTIONMannington Hometown Lexington Hickory HardwoodHacker Industries, Inc. Firm-Fill Gypsum ConcreteHacker Industries, Inc. Firm-Fill SCM-250 Sound Control MatOriented Strand Board SheathingJohns Manville R-13 Fiberglass InsulationWeyerhaeuser TrusJoist 360 TJI JoistRSIC-1 Installed @ 24"x48"Clark Dietrich 087F125-18 Furring Channel @ 24" O.C.2 Layers Type C Gypsum Panel
STC 62Test Number F4543.05 IIC 61
©2016 PAC International, LLC. All Rights Reserved. • (866) 774-2100 • Fax (866) 649-2710RSIC® is a registered Trade Mark of PAC International, LLC.
ST
C
IIC
-
130 Derry Courtaa
York, PA 17406aa
p. 717.764.7700
f. 717.764.4129www.archtest.com · www.intertek.com/building
Ceiling Isolation: 28 mm PAC International RSIC-1 Classic Isolation Clips
Ceiling Isolation: 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel
Ceiling: 15.9 mm Type C Gypsum Panel
Ceiling: 15.9 mm Type C Gypsum Panel
Reference should be made to Intertek-ATI Report F4543.05-113-11 for complete test specimen
description. This page alone is not a complete report.
Subfloor Topping: 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete
Subfloor Underlayment: 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat
Subfloor: 18.8 mm Oriented Strand Board Sheathing
Insulation: 88.9 mm Johns Manville R-13 Fiberglass Insulation
Joist: 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist
Test Specimen Identification:
Floor Topping: 12.07 mm Mannington® Hometown Lexington Hickory Hardwood
Specimen Type: Weyerhauser TJI Assembly - 302 mm
Overall Size: 3023 mm by 3632 mm
STC 62
IIC 61
Series/Model: FIRM-FILL® Brand Gypsum Concrete and FIRM-FILL® SCM-250
Sound Control Mat - Mannington Hometown Lexington Hickory Hardwood
F4543.05-113-11-R2
ACOUSTICAL PERFORMANCE TEST REPORT
ASTM E 90 AND ASTM E 492
Rendered to
HACKER INDUSTRIES INC.
-
130 Derry Courtaa
York, PA 17406aa
p. 717.764.7700
f. 717.764.4129www.archtest.com · www.intertek.com/building
ASTM E 989-06 (2012), Classification for Determination of Impact Insulation Class (IIC)
ASTM E 2235-04 (2012) Standard Test Method for Determination of Decay Rates for Use in
Sound Insulation Test Methods
Test Procedure
All testing was conducted in the VT test chambers at Intertek-ATI located in York,
Pennsylvania. The microphones were calibrated before conducting the tests.
The airborne transmission loss test was conducted in accordance with the ASTM E 90 test
method using the single direction method. Two background noise sound pressure level and five
sound absorption measurements were conducted at each of five microphone positions. Four
sound pressure level measurements were made simultaneously in both rooms, at each of five
microphone positions.
Test Methods
The acoustical tests were conducted in accordance with the following standards. The equipment
listed in the attachments meets the requirements of the following standards.
ASTM E 90-09, Standard Test Method for Laboratory Measurement of Airborne Sound
Transmission Loss of Building Partitions
ASTM E 413-10, Classification for Rating Sound Insulation
ASTM E 492-09, Standard Test Method for Laboratory Measurement of Impact Sound
Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine
Report Date 03/03/16
Revision Date 04/29/16
Project Scope
Architectural Testing, Inc., a subsidiary of Intertek (Intertek-ATI), was contracted to conduct
airborne sound transmission loss and impact sound transmission tests. The complete test data is
included as attachments to this report. The client provided the test specimen. The specimen was
constructed on the date of testing.
Newport Beach, California 92660
Report F4543.05-113-11
Test Date 02/04/16
Page 1 of 5
Acoustical Performance Test Report
HACKER INDUSTRIES INC.
1600 Newport Center Drive, Suite 275
F4543.05-113-11-R2
-
TJI Joist57.2 by 3023 301.6 Weyerhaeuser TrusJoist® 360 21.2 lin m 4.46 kg/m
Note: Fastened to perimeter frame on 610 mm centers
2962 by 584 88.9 Johns Manville R-13 10.98 m² 1.25 kg/m²
Note: Laid directly over furring/hat channels.
Oriented Strand
Board Sheathing
1219 by 2438 18.8 N/A 10.98 m² 10.25 kg/m²
Note: Fastened to joists with 76 mm by 3 mm framing nails on 203 mm centers along perimeter and
305 mm centers in the field.
Fiberglass Insulation
Sound Control Mat1219 by 3023 6.4
Hacker Industries, Inc. FIRM-
FILL® SCM-25010.98 m² 0.49 kg/m²
Note: Installed per manufacturer's specifications with seams overlapping and taped
Gypsum Concrete3632 by 3023 25.4
Hacker Industries, Inc. FIRM-
FILL® Brand10.98 m² 48.82 kg/m²
Note: The gypsum concrete was allowed to cure for a minimum of 14 days. The gypsum layer had a
closed cell foam perimeter isolation. The product name was specified by client.
HardwoodVaried by 127 12.1
Mannington® Hometown
Lexington Hickory10.98 m² 7.9 kg/m²
Note: Loose laid
Test Specimen Materials and Installation Details
MaterialDimensions
(mm)
Thickness
(mm)Manufacturer and Series Quantity
Average
Weight
Average Relative Humidity 65% Average Relative Humidity 68%
Test Calculations
The STC (Sound Transmission Class) and IIC (Impact Insulation Class) ratings were calculated
in accordance with ASTM E 413 and ASTM E 989, respectively.
Test Conditions
Source Room Receive Room
Average Temperature 19.9°C Average Temperature 17.3°C
Page 2 of 5
Test Procedure (Continued)
The impact sound transmission test was conducted in accordance with the ASTM E 492 test
method. Two background noise sound pressure level, two sound pressure level measurements
with the tapping machine operating at each position specified by ASTM E 492, and five sound
absorption measurements were conducted at each of five microphone positions.
The air temperature and relative humidity conditions were monitored and recorded during all
measurements.
F4543.05-113-11-R2
-
Comments
The total weight of the floor/ceiling assembly was 1125.7 kg. Intertek-ATI will store samples
of the test specimen for four years. Photographs of the test specimen are included in the
attachments. A drawing of the test specimen is included in the attachments.
Gypsum Panel1219 by 3023 15.9 Type C 10.98 m² 11.9 kg/m²
Note: Fastened to the furring channels on 305 mm centers with 41.3 mm Type S bugle head screws.
Seams and perimeter sealed with Pecora AC-20 FTR Acoustical Sealant.
Gypsum Panel1219 by 3023 15.9 Type C 10.98 m² 11.9 kg/m²
Note: Fastened to the furring channels on 305 mm centers with 25.4 mm Type S bugle head screws.
Furring/Hat Channel3657.6 by 76.2 22.3 ClarkDietrich 087F125-18 29.1 lin m 0.48 kg/m
Note: Installed into the PAC International RSIC-1 Classic, spaced 610 mm on center.
Isolation Clips76.9 by 35.6 28.0 PAC International RSIC-1 Classic 24 clips 0.06 kg/clip
Note: Fastened to joists in a 610 mm by 1220 mm traditional pattern.
F4543.05-113-11-R2
Page 3 of 5
Test Specimen Materials and Installation Details (Continued)
MaterialDimensions
(mm)
Thickness
(mm)Manufacturer and Series Quantity
Average
Weight
-
Technician II - Acoustical Testing Project Manager - Acoustical Testing
Attachments (7 Pages): This report is complete only when all attachments are included.
* Stated by Client/Manufacturer
N/A - Non Applicable
Intertek-ATI will service this report for the entire test record retention period. Test records,
such as detailed drawings, datasheets, representative samples of test specimens, or other
pertinent project documentation, will be retained by Intertek-ATI for the entire test record
retention period. The test record retention period ends four years after the test date.
This report does not constitute certification of this product nor an opinion or endorsement by
this laboratory. It is the exclusive property of the client so named herein and relates only to the
specimen tested. This report is intended to help in the client’s quality assurance program, but it
does not represent a continuous or exhaustive evaluation of the specimen tested or of other
products or materials that were not evaluated. The statements and data provided herein do not
constitute approval, disapproval, certification, or acceptance of performance or materials.
This report may not be reproduced, except in full, without the written approval of
Intertek-ATI.
FOR INTERTEK-ATI:
David M. Dacheux Jordan Strybos
F4543.05-113-11-R2
Page 4 of 5
-
This report produced from controlled document template ATI 00629(d), Revised 02/09/15.
R2 04/29/16 Page 3 Clip spacing installation note corrected
R0 03/03/16 N/A Original Report Issue
R1 03/10/16 All pagesJob extension number changed per
client's request
F4543.05-113-11-R2
Page 5 of 5
Revision Log
Revision Date Page(s) Description
-
Test Chambers
VT Receive Room Volume 157.31 m³
VT Source Room Volume 190 m³
Page 1 of 7
Tapping Machine Look Line s.r.l. EM50 (TM50) 65351 11/15
* The calibration frequency for this equipment is every two years per the manufacturer's recommendation.
Source Room Microphone Scantek 378B20 63741 04/15
Source Room Environmental
IndicatorComet T7510 63812 11/15
Source Room Microphone PCB Piezotronics 378B20 63740 04/15
Source Room Microphone PCB Piezotronics 378B20 63742 04/15
Source Room Microphone PCB Piezotronics 378B20 63738 04/15
Source Room Microphone PCB Piezotronics 378B20 63739 04/15
Receive Room Environmental
IndicatorComet T7510
63810
63811
10/15
10/15
Receive Room Microphone PCB Piezotronics 378B20 63746 05/15
Receive Room Microphone PCB Piezotronics 378B20 63747 05/15
Receive Room Microphone PCB Piezotronics 378B20 63744 05/15
Receive Room Microphone PCB Piezotronics 378B20 63745 05/15
Microphone Calibrator Norsonic 1251 Y002919 07/15
Receive Room Microphone Scantek 378B20 63748 05/15
Data Acquisition Unit National Instruments PXI-1033 63763 06/14 *
F4543.05-113-11-R2
Attachments
Instrumentation
Instrument Manufacturer Model ATI NumberDate of
Calibration
-
STC Rating (Sound Transmission Class)
Deficiencies (Sum of Deficiencies)
Notes: 1) Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.
2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.
3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied
ATI 00614 Revised 02/09/15 Page 2 of 7
23
62
0.80 -
10000 6.6 28.9 92 8 82 0.70 -
8000 6.5 23.2 97 15 80
0.60 -
6300 6.3 17.3 98 19 78 0.80 -
5000 6.5 13.4 103 28 75
0.70 0
4000 6.8 11.4 104 32 72 0.70 0
3150 8.9 10.2 103 33 71
0.40 0
2500 10.3 9.2 102 36 68 0.40 0
2000 14.7 8.6 104 38 68
0.80 0
1600 21.0 7.8 104 38 68 0.60 0
1250 24.4 7.6 104 40 67
0.60 1
1000 23.9 7.7 103 42 64 0.50 1
800 22.4 7.8 104 43 63
0.60 1
630 22.8 7.9 105 45 63 0.80 0
500 24.8 8.0 103 45 61
1.00 4
400 21.7 8.5 103 48 58 0.90 3
315 25.0 10.5 105 52 54
0.90 2
250 27.9 10.7 103 52 52 1.40 3
200 26.3 10.0 104 56 50
1.50 4
160 32.8 8.5 107 64 45 1.70 4
125 34.9 10.2 105 65 42
4.00 -
100 41.9 12.2 105 66 39 1.80 -
80 50.4 17.2 107 66 40
-
63 44.5 29.3 100 60 37 2.70 -
(dB) Limit Deficiencies
50 45.7 24.5 100 65 33 5.00
SPL SPL SPL Confidence of
(Hz) (dB) (m²) (dB) (dB)
Technician David M. Dacheux
FreqBackground
AbsorptionSource Receive Specimen
TL
95% Number
Client Hacker Industries Inc.
Description 12.07 mm Mannington® Hometown Lexington Hickory Hardwood, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand GypsumConcrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9
mm Johns Manville R-13 Fiberglass Insulation, 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist, 28 mm PAC International RSIC-1
Classic Isolation Clips, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm Type C Gypsum Panel, 15.9 mm Type C
Gypsum Panel
Specimen Area 10.98 m²
F4543.05-113-11-R2
AIRBORNE SOUND TRANSMISSION LOSS
ASTM E 90
Test Date 02/04/16
Data File No. F4543.05
-
Specimen Area 10.98 m²
Technician David M. Dacheux
ATI 00614 Revised 02/09/15 Page 3 of 7
Data File No. F4543.05
Client Hacker Industries Inc.
Description 12.07 mm Mannington® Hometown Lexington Hickory Hardwood, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand GypsumConcrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9
mm Johns Manville R-13 Fiberglass Insulation, 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist, 28 mm PAC International RSIC-1
Classic Isolation Clips, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm Type C Gypsum Panel, 15.9 mm Type C
Gypsum Panel
F4543.05-113-11-R2
AIRBORNE SOUND TRANSMISSION LOSS
ASTM E 90
Test Date 02/04/16
0
10
20
30
40
50
60
70
80
90
100
63
125
250
500
100
0
200
0
400
0
800
0
Sou
nd
Tra
nsm
issi
on
Loss
(d
B)
Frequency (Hz)
Airborne Sound Transmission Loss
Specimen TL
Contour Curve
-
IIC Rating (Impact Insulation Class)
Deficiencies (Sum of Deficiencies)
61
32
Note: Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.
ATI 00615 Revised 02/09/15 Page 4 of 7
10000 6.6 28.8 9 0.6 -
8000 6.4 22.9 9 0.3 -
6300 6.1 17.3 10 0.4 -
5000 5.7 13.5 14 0.7 -
4000 5.4 11.6 18 0.6 -
3150 6.7 10.1 22 0.4 0
2500 9.7 9.3 29 0.4 0
2000 15.1 8.5 34 0.3 0
1600 21.2 7.6 37 0.1 0
1250 25.4 7.7 41 0.6 0
1000 25.2 7.6 46 0.6 0
800 23.8 7.7 51 0.6 4
630 24.0 7.9 51 0.9 3
500 26.4 7.9 50 0.6 1
400 23.3 8.6 51 0.6 1
315 26.5 10.3 51 1.0 0
250 28.9 11.5 52 1.3 1
200 27.5 10.7 53 2.1 2
160 30.7 8.5 58 2.5 7
125 35.3 10.2 58 3.4 7
100 44.2 13.0 57 1.1 6
80 48.4 19.1 56 2.4 -
63 44.7 27.8 62 1.9 -
50 45.1 25.3 65 4.0 -
(Hz) (dB) (m²) (dB) Limit Deficiencies
Technician David M. Dacheux
Freq Background SPL AbsorptionNormalized Impact
SPL
95% Number
Confidence of
Client Hacker Industries Inc.
Description 12.07 mm Mannington® Hometown Lexington Hickory Hardwood, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand GypsumConcrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9
mm Johns Manville R-13 Fiberglass Insulation, 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist, 28 mm PAC International RSIC-1
Classic Isolation Clips, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm Type C Gypsum Panel, 15.9 mm Type C
Gypsum Panel
Specimen Area 10.98 m²
F4543.05-113-11-R2
IMPACT SOUND TRANSMISSION
ASTM E 492
Test Date 02/04/16
Data File No. F4543.05
-
Technician David M. Dacheux
ATI 00615 Revised 02/09/15 Page 5 of 7
Client Hacker Industries Inc.
Description 12.07 mm Mannington® Hometown Lexington Hickory Hardwood, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand GypsumConcrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9
mm Johns Manville R-13 Fiberglass Insulation, 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist, 28 mm PAC International RSIC-1
Classic Isolation Clips, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm Type C Gypsum Panel, 15.9 mm Type C
Gypsum Panel
Specimen Area 10.98 m²
F4543.05-113-11-R2
IMPACT SOUND TRANSMISSION
ASTM E 492
Test Date 02/04/16
Data File No. F4543.05
10
20
30
40
50
60
70
80
90
100
1100
10
20
30
40
50
60
70
80
90
100
63
125
250
500
100
0
200
0
400
0
800
0
Imp
act
In
sula
tion
Cla
ss (
IIC
)
So
un
d P
ress
ure
Lev
el (
dB
)
Frequency (Hz)
Impact Sound Transmission
Normalized Impact SPL
Contour Curve
-
Page 6 of 7
Receive Room View of Test Specimen Installation
Source Room View of Test Specimen Installation
F4543.05-113-11-R2
Photographs
-
Page 7 of 7
4-Subfloor
5-Insulation
6-Joist
7-Ceiling Isolation
8-Ceiling
1-Floor Topping
2-Subfloor Topping
3-Subfloor Underlayment
Drawing
F4543.05-113-11-R2