Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000...

20
Rooftop Package Series R-407C 48-120 MBH 50 Hz For more technical information please visit www.coolex.com.kw Packaged Air Conditioning Units With Hermetic Compressor Tropical

Transcript of Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000...

Page 1: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw

Rooftop Package SeriesR-407C 48-120 MBH

50 Hz

For more technical information please visit www.coolex.com.kw

Packaged Air Conditioning UnitsWith Hermetic CompressorTropical

Page 2: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw1

Table of Contents

INTRODUCTION 2

NOMENCLATURE 2

UNIT RATING SUMMARY 3

OUT STANDING FEATURES 3

STANDARD SPECIFICATIONS 5

OPTIONAL SPECIFICATIONS 6

SELECTION PROCEDURE 7

GENERAL DATA 8

PERFORMANCE DATA TABLES 9

UNIT ELECTRICAL DATA 11

SUPPLY AIR PERFORMANCE 12

UNIT DIMENSIONS 13

TYPICAL WIRING DIAGRAMS 15

LOAD DISTRIBUTION 16

ABOUT RIC 17

COOLEX DISTRIBUTORS 18

1. Air Cooled Screw Water Chillers

2. Air Cooled Scroll Water Chillers

3. Air Handling Units

4. Ducted Split Units

5. Concealed Split Units

6. Fan Coil Units

OTHER COOLEX PRODUCTS

Page 3: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw2

NOMENCLATURE

PNGc 076 C 2 H10 A A

Unit Series Description PNGc Package New Generation, R-407C Refrigerant

ABCDEFGHIJ

External Overload for each condenser fan motorExternal overload for evaporator fan motorCircuit breaker for each compressorcircuit breaker for each condenser fan motorcircuit breaker for evaporator fan motor A, B C, D A, C, D C, D, E A, B, C, D, E

ABCDEFGHIJKLMNOPQ

Double skin2 in aluminum filterSight glassstainless steel drain pan condenser coating Evaporator coatingcopper finsModulating High and Low pressure switchesHigh and Low Pressure Gaugesair flow switchA, BA, B, DH, IE, FE, F, G D, E, FOther Combination and options to be assigned in the quotation

Cooling Capacity Nominal MBH 48 - 6076 - 90100 - 120

Electric Heater X X kW value

INTRODUCTION

COOLEX High Efficiency Package Units are de-signed for outdoor installation specifically for tropical operation with high performance, low power consumption, easy installation and low noise operations.

Coolex Packaged Units can be used for cooling or heating with optional electric heater.

Code Description A First Series B Second Series C Third SeriesD Fourth Series

Electrical Specifications

2 415/3Ph/50Hz

Page 4: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw3

Rating Conditions: Indoor Temperature DB = 80 0F (26.7 0C). WB 67 0F (19.4 0C).

UNIT RATING SUMMARY

OUT STANDING FEATURES Controls• Singlepointpowersupply• Colorcodedwires• WeatherproofControlpanel Microprocessor Controller

Options & Accessories• TotallyEnclosedFancooled(TEFC)BlowerMotor• IntelligentairQualitySystembyEconomizercontrol UltraViolet(UV)lamps Microprocessor based control

Superior Efficiency HighEER(EnergyEfficiencyRatio)exceedsthenew ASHRAE90.1efficiencylevels Low power consumption Highvolumetricefficiencyscrollcompressors Designedtooperateatsevereambienttemperature up to 52°C without tripping

Quiet operation• Lownoiselevelcompressors,condenserfans andevaporatorblower• Compactphysicalfootprint Specialdesignedrefrigerantpipinginadditionto theinsulationfortheevaporatorsection

Quality AssuranceAll units in the PNG series are:• Factoryruntested.• ProducedinanISO9001-2000listedmanufacturingfacility. ConstructedincompliancewithASHRAE15safetyrequirements. AHRIcertifiedcoolingcoils

ModelAir

Flow

(CFM)

Cooling Capacity (Btu/h)

Total Power (kW)

kW/Ton EER

Ambient temp 95°F Ambient temp 115°F Ambient temp 118.4°F Ambient temp 122°F

Cooling Capacity (Btu/h)

Total Power (kW)

kW/Ton EERCooling Capacity (Btu/h)

Total Power (kW)

kW/Ton EERCooling Capacity (Btu/h)

Total Power (kW)

kW/Ton EER

PNGc-048 C2

PNGc-060 C2

PNGc-076 C2

PNGc-090 C2

PNGc-100 C2

PNGc-120 C2

1800

2200

2750

3150

3500

4150

56,261

66,217

82,131

96,115

106,315

123,638

4.59

5.60

7.04

8.27

9.26

10.74

12.25

11.82

11.67

11.63

11.48

11.51

51,129

61,304

73,906

91,203

98,656

116,466

5.55

6.71

8.55

9.83

11.34

13.01

1.30

1.31

1.39

1.29

1.38

1.34

9.22

9.14

8.64

9.27

8.70

8.96

50,160

59,640

72,400

84,000

95,440

114,470

5.75

6.95

8.80

10.10

11.65

13.39

1.38

1.40

1.46

1.44

1.47

1.40

8.72

8.58

8.23

8.32

8.19

8.55

48,899

57,600

70,467

81,158

91,597

110,597

5.98

7.21

9.07

10.33

11.98

13.79

1.47

1.50

1.54

1.53

1.57

1.50

8.18

7.99

7.77

7.86

7.65

8.02

0.98

1.02

1.03

1.03

1.04

1.04

Page 5: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw4

OUT STANDING FEATURES

Evaporator’s Side• Easyaccesstotheevaporatorsidewithremovablepanelfor

maintenance purpose for the fan, motor, belt, pulleys, and expansiondevice

• Easyaccesstodrainpanforcleaning

Compressor’s Side• Easyaccesstothecompressorsidewithremovablepanel

for maintenance purpose for the compressor, and filter drier• Easyaccesstocondenserfans,andmotors

Electrical Panel• Easyaccesstotheelectricalpanelwithhingeddoorfor

microprocessor access and electrical parts

Page 6: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw5

STANDARD SPECIFICATIONSGeneral• ThePackageNewGenerationunitisafactoryassembledcoolingorcombinationofcoolingandheating,suitableforoutdoorinstallation mounting on the roof or ground. • Thepackagedunitconsistsofscrollcompressors,coolingcoil,condensercoil,fans,electricheater(optional),controlwiringand interconnecting piping-all factory assembled. • TheunitsareratedandtestedinaccordancewithAHRI210/240&AHRI340/360standard.

Condenser CoilsThecoilsarebuiltupseamlesscopper tubes and mechanically bonded to scientifically designed louveredfins.Theassembledcoilsarefactoryleak tested under water at a pressureof450psigforqualityand leak free unit.

Condenser FansThefansareselectedforoptimumefficiency and maximum sound power reduction, propeller type and directdriven,upwarddischargeandprovidedwithfangrillemountedonthe casing.

Unit CasingThecasingsheetmetalisfabricatedfromhotdippedG90,Zinccoatingandzerospanglegalvanizedsteel,oven-bakedpowder coated.Theunitisprovidedwithanintegral weather resistant control panel for outdoor application.

Evaporator CoilsThecoilsarebuiltupofripplefinnedseamlesscoppertubes and mechanically bonded to scientifically designed louveredfins.Theassembledcoilsarefactoryleaktestedunderwateratapressureof350psigforqualityandleakfreeunits.

Drain PanThedrainpanisfabricatedofgalvanizedsteel.Thedrainpanispowder coat painted and the outer surface is thermally insulated.

Condenser Fan Motor Condenser fan motors are totallyenclosedair-overtypewithclassFinsulation.Themotorsareprovidedwithinherent thermal protection and auto rest type.

Evaporator FanTheunitsareprovidedwithcentrifugal fans which are statically and dynamically balanced, designed for low soundleveloperationDirectdrivemotorsforPNG048/060modelsandremainingmodelsPNG076to120arebeltdriven.

CompressorThecompressorsarescrolltypewith crankcase heater, internal pressurereliefvalvewhichprovideshigh pressure protection to the refrigerant system and rubber vibrationisolatorsforquietandefficient operation. Thecompressorsareequippedwith internal motor protector for safeoperation.ThecompressorsarebuilttoNF,VPE,CSA,&ULcertification.

Page 7: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw6

Microprocessor Based Controller

ThePackageNewGenerationunitsareprovidedwithtechnologicallyadvancedMicroprocessor based controller, incorporating the following benefits and features:

• Compressorlockoutfunction

• Balanceloadingofcompressors

• Compressorslead-lagoperation

• Pumpdownoption.

• Faultdiagnostics

• Indicatorlightsforhigh&lowpressureSafeties

OPTIONAL SPECIFICATIONS

MICROPROCESSOR CONTROLLER

Electrical

• Electricheaters(opencoiltype)• Electricheaters(fintype)• Compressorcircuitbreaker• Mildambient(fancycling)control• Ductsensor• Anti-icethermostat• Voltfreecontacts• Externaloverload• Ultravioletlight• Dirtyfilterindication• Firealarmconnection• Economizercontroller

Construction

• Pumpdownsolenoidvalve(pds) • Hotgasbypassvalve • Condensercoilguard • Adjustablehighpressureswitch• Adjustablelowpressureswitch• Muffler• Replaceablefilterdrierwithmechanicalshut-offvalve• Coilcoat,tinnedcopperfins • Filterandfilterbox • Doublesidedrainconnections • Stainlesssteeldrainpan • Lockabledoorforthecontrolpanel • Mixingbox

Page 8: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw7

ThebelowexampleillustratestheselectionproceduretoassistusingthiscatalogtoselecttheappropriatePNGcunitthatmeetsthedesignrequirements.

SELECTION PROCEDURE

Sea level

1000

2000

3000

4000

5000

6000

7000

Altitude[ft]

Correctionfactor

1

0.996

0.990

0.984

0.980

0.974

0.965

0.960

Example :

Designrequirements

• Totalcoolingcapacity 68 [MBH]

• Sensiblecoolingcapacity 51 [MBH]

• Designambienttemperature 118.4 [°F]

• Evaporatorairflow 2600 [CFM]

• EvaporatorenteringtemperatureDB/WB 80/67 [°F/°F]

• Externalstaticpressure 0.2 [in.wg]

• Altitude 2000 [ft]

• Powersupply 415V/3Ph/50Hz

*Using the correction factor table at the specified altitude, thereby the requiredcapacitywillbe:

Corrected capacity =Requiredcapacity /corr.factor

Corrected total capacity =68[MBH]/0.99 =68.69MBH

Corrected sensible capacity =51[MBH]/0.99 =51.52MBH

Fromthecoolingcapacityatperformancedatatables(page9),the closestselectionmodeltotherequiredcapacityisPNGc076.Fromthe performance table:

Total capacity =71.2[MBH]

Sensible capacity =53.9[MBH]

Page 9: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw8

GENERAL DATA

PNGc-048 C2 PNGc-060 C2 PNGc-076 C2 PNGc-090 C2 PNGc-100 C2 PNGc-120 C2

Compressor

Condenser Fan

Condenser Coil

Evaporator

Blower

Air Filter

Expansion Device

Operating Weight

Evaporator Coil

Type

Quantity

Refrigerant

Refrigerant circuits

Type

Diameter, mm

Air flow, m³/min. (CFM)

Number of Fans

Motor Enclosure/Ins Class

Nominal kW (HP)

RPM

Type

Number of Rows

Type

Motor Enclosure/Ins Class

Nominal kW (HP)

Type

Number of Rows

Type

Type

Thickness [inch]

kg

Scroll Hermetic

1

R - 407C

1

1

Propeller

610 762

95 (3360) 102 (3605) 198 (6995)

Totally Enclosed Air Cooled, Class F

0.37 (1/2) 0.56 (3/4) 1.12 (1.5)0.75 (1)

900

Enhanced Fins & Tubes

2R

Centrifugal

Open Drip-Proof, Class B

0.56 (3/4) 1.12 (1.5)0.75 (1) 1.5 (2) 2.2 (3)

Enhanced Fins & Tubes

3R/4R

Washable Aluminum Mesh

Capillary

1/2

180 196 233 277 361 375

Thermostatic

1

Model

Page 10: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw9

PERFORMANCE DATA TABLES

PN

Gc-

060

C2P

NG

c-04

8 C2

58,491

54,374

48,256

42,376

59,936

55,738

49,450

43,411

60,527

56,261

49,927

43,831

86

80

74

68

86

80

74

68

86

80

74

68

72

67

62

57

72

67

62

57

72

67

62

57

36,476

36,556

35,286

33,460

37,349

37,440

36,147

34,265

37,712

37,803

36,487

34,594

4.54

4.41

4.22

4.01

4.67

4.54

4.33

4.12

4.73

4.59

4.39

4.17

56,949

49,406

41,270

29,727

58,356

50,616

42,270

34,234

58,924

51,129

42,677

34,555

36,784

34,328

31,861

28,664

37,659

35,155

32,626

29,369

38,024

35,629

32,930

29,612

5.69

5.34

5.00

4.76

5.85

5.49

5.15

4.90

5.91

5.55

5.20

4.96

55,754

48,369

40,404

29,103

57,131

49,554

41,383

33,515

57,687

50,160

41,782

33,829

5.90

5.55

5.19

4.95

6.06

5.70

5.34

5.08

6.14

5.75

5.40

5.14

54,488

47,271

39,487

28,443

55,836

48,429

40,444

32,754

56,379

48,899

40,834

33,061

35,981

33,580

31,166

28,038

36,838

34,388

31,915

28,728

37,195

34,852

32,213

28,966

6.13

5.76

5.39

5.13

6.30

5.92

5.55

5.28

6.37

5.98

5.61

5.34

1360

1530

1800

69,922

65,594

62,885

57,891

70,255

65,904

63,183

58,167

70,587

66,217

63,481

58,443

86

80

74

68

86

80

74

68

86

80

74

68

72

67

62

57

72

67

62

57

72

67

62

57

41,414

43,264

44,917

43,481

41,828

43,470

45,124

43,688

41,806

43,677

45,330

43,894

5.48

5.53

5.32

5.22

5.52

5.56

5.36

5.26

5.54

5.60

5.39

5.29

67,890

60,713

55,276

47,843

68,216

61,005

55,532

48,065

68,543

61,304

55,789

48,286

42,904

42,904

41,626

37,422

43,307

43,588

41,816

37,590

43,307

43,307

42,007

37,758

6.76

6.63

6.40

6.21

6.79

6.67

6.44

6.25

7.02

6.71

6.48

6.28

8.45

8.35

8.16

8.03

8.53

8.43

8.26

8.11

8.66

8.55

8.37

8.24

65,904

58,938

53,660

46,444

66,222

59,221

53,909

46,659

66,539

59,640

54,158

46,874

7.00

6.88

6.63

6.43

7.04

6.91

6.67

6.46

7.28

6.95

6.71

6.50

63,802

57,058

51,949

44,962

64,109

57,332

52,189

45,171

64,418

57,600

52,431

45,379

41,162

41,162

39,936

35,902

41,550

41,818

40,119

36,063

41,550

41,550

40,301

36,225

7.25

7.13

6.88

6.67

7.29

7.17

6.91

6.71

7.55

7.21

6.95

6.74

1890

2000

2200

87,903

80,106

73,154

66,795

88,793

80,918

73,890

67,476

90,121

82,131

74,999

68,487

86

80

74

68

86

80

74

68

86

80

74

68

PN

Gc-

076

C2

72

67

62

57

72

67

62

57

72

67

62

57

61,428

59,604

57,675

55,782

62,048

60,212

58,261

56,345

62,977

61,107

59,133

57,194

6.95

6.87

6.72

6.61

7.01

6.94

6.79

6.68

7.12

7.04

6.90

6.78

79,113

72,088

65,831

60,108

79,903

72,812

66,499

60,721

81,106

73,906

67,489

61,634

56,848

55,169

53,386

51,627

57,422

55,720

53,915

52,156

58,285

56,560

54,732

52,938

77,326

70,460

64,344

58,750

78,098

71,167

64,997

59,350

79,274

72,400

65,966

60,241

8.69

8.60

8.41

8.27

8.78

8.68

8.49

8.36

8.92

8.80

8.62

8.48

75,434

68,736

62,770

57,313

76,188

69,426

63,407

57,897

77,335

70,467

64,352

58,768

52,952

51,389

49,729

48,089

53,488

51,903

50,221

48,582

54,291

52,685

50,981

49,311

8.95

8.86

8.66

8.53

9.05

8.94

8.75

8.61

9.19

9.07

8.88

8.74

2300

2600

2750

36,394

33,965

31,524

28,360

37,260

34,782

32,281

29,057

37,621

35,252

32,582

29,298

54,955

53,332

51,609

49,909

55,511

53,866

52,121

50,420

56,345

54,677

52,910

51,176

42,058

42,058

40,805

36,683

42,453

42,728

40,992

36,849

42,453

42,453

41,179

37,014

Model

AirFlow

CFMAir Flow 95 115 118.4

Condenser Ambient Temperature [ºF]

DB WBCapacity Btu/Hr kw

InputTotal Sen.kw

InputTotal Sen.kw

InputTotal Sen.kw

InputTotal Sen.Capacity Btu/Hr Capacity Btu/Hr Capacity Btu/Hr

122

Page 11: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw10

PERFORMANCE DATA TABLES

122

PN

Gc-

090

C2

105,609

93,752

85,463

76,527

106,678

94,698

86,324

77,305

108,275

96,115

87,618

78,459

86

80

74

68

86

80

74

68

86

80

74

68

72

67

62

57

72

67

62

57

72

67

62

57

77,926

69,177

63,060

56,467

78,714

69,875

63,695

57,041

79,893

70,920

64,651

57,893

9.08

8.06

7.35

6.58

9.17

8.14

7.42

6.65

9.31

8.27

7.54

6.75

100,213

88,961

81,096

72,617

101,227

89,859

81,913

73,355

102,742

91,203

83,141

74,450

74,553

66,182

60,331

54,023

75,307

66,850

60,938

54,572

76,435

67,850

61,852

55,387

10.80

9.59

8.74

7.83

10.91

9.69

8.83

7.91

11.08

9.83

8.96

8.03

92,298

81,935

74,691

66,881

93,231

82,762

75,443

67,561

94,627

84,000

76,574

68,570

70,033

62,170

56,673

50,748

70,742

62,798

57,244

51,263

71,801

63,737

58,103

52,029

11.10

9.85

8.98

8.04

11.21

9.95

9.07

8.12

11.38

10.10

9.21

8.24

89,174

79,162

72,163

64,618

90,077

79,961

72,890

65,275

91,425

81,158

73,983

66,250

68,435

60,752

55,380

49,590

69,128

61,365

55,938

50,094

70,163

62,283

56,777

50,842

11.35

10.07

9.18

8.22

11.46

10.17

9.28

8.31

11.63

10.33

9.41

8.43

2600

2800

3150

119,845

103,708

94,369

82,833

121,058

104,750

95,321

83,671

122,872

106,315

96,749

84,918

86

80

74

68

86

80

74

68

86

80

74

68

PN

Gc-

100

C2

72

67

62

57

72

67

62

57

72

67

62

57

80,560

74,555

72,615

70,122

81,371

75,304

73,352

70,834

82,599

76,434

74,457

71,890

9.50

9.03

8.69

8.28

9.61

9.12

8.78

8.37

9.73

9.26

8.91

8.49

111,199

96,221

87,560

76,855

112,325

97,197

88,445

77,636

114,001

98,656

89,765

78,796

76,757

71,033

69,193

66,813

77,533

71,747

69,894

67,489

78,697

72,824

70,933

68,503

11.64

11.06

10.64

10.16

11.75

11.17

10.75

10.26

11.94

11.34

10.92

10.41

107,335

92,877

84,517

74,184

108,421

93,819

85,371

74,938

110,040

95,440

86,647

76,058

75,176

69,570

67,768

65,437

75,936

70,269

68,454

66,100

77,077

71,324

69,472

67,093

11.95

11.36

10.94

10.43

12.08

11.47

11.05

10.54

12.26

11.65

11.21

10.70

73,502

68,022

66,259

63,980

74,245

68,705

66,930

64,628

75,361

69,737

67,926

65,598

12.29

11.69

11.24

10.72

12.41

11.80

11.36

10.84

12.60

11.98

11.54

11.00

2900

3100

3500

103,243

89,337

81,296

71,356

104,289

90,243

82,117

72,081

105,846

91,597

83,343

73,159

133,932

120,322

106,054

92,160

135,707

121,920

107,455

93,384

137,609

123,638

108,956

94,696

86

80

74

68

86

80

74

68

86

80

74

68

PN

Gc-

120

C2

72

67

62

57

72

67

62

57

72

67

62

57

87,051

80,270

72,669

64,927

88,464

81,858

74,177

66,020

90,208

83,386

75,463

67,439

11.19

10.52

9.74

9.38

11.49

10.60

9.92

9.32

11.64

10.74

10.05

9.44

123,950

111,354

98,151

85,290

125,594

112,833

99,446

86,423

127,355

114,470

100,835

87,637

82,773

76,324

69,098

61,737

84,117

77,835

70,533

62,776

85,775

79,317

71,756

64,126

13.95

13.11

12.15

11.36

14.33

13.22

12.36

11.56

14.51

13.39

12.52

11.71

80,885

74,583

67,522

60,329

82,198

76,059

68,924

61,344

83,818

77,508

70,119

62,663

14.36

13.51

12.51

11.81

14.76

13.61

12.73

11.93

14.95

13.79

12.90

12.08

3300

3800

4150

126,139

113,321

99,884

86,797

127,811

114,826

101,202

87,950

129,603

116,466

102,616

89,185

83,861

77,328

70,007

62,549

85,223

78,859

71,460

63,602

86,903

80,354

72,699

64,969

13.54

12.74

11.80

11.14

13.92

12.84

12.01

11.24

14.10

13.01

12.16

11.39

119,756

107,586

94,830

82,404

121,344

109,015

96,081

83,499

123,045

110,597

97,423

84,671

Model

AirFlow

CFMAir Flow 95 115 118.4

Condenser Ambient Temperature [ºF]

DB WBCapacity Btu/Hr kw

InputTotal Sen.kw

InputTotal Sen.kw

InputTotal Sen.kw

InputTotal Sen.Capacity Btu/Hr Capacity Btu/Hr Capacity Btu/Hr

CFM :Airflowrate(Ft3/minute)DB :Drybulbtemperature(°F)WB :Wetbulbtemperature(°F)P.I :PowerinputisTotalPower(kW)Note: Capacity in kW= (Btu/hr/12000)*3.517. Cooling capacities are gross ratings

LEGEND:

Page 12: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw11

UNIT ELECTRICAL DATA

Model

PNGc-048C2

PNGc-060C2

PNGc-076C2

PNGc-090C2

PNGc-100C2

PNGc-120C2

Power Supply

VOLTAGE RANGE

Evaporator Blower Motor Electric HeaterFM Compressor

(V-PH-Hz) FLAMAX.MIN. RLA LRA HP FLA

-

5

7.5

10

-

5

7.5

10

-

5

7.5

10

-

5

7.5

10

15

-

7.5

10

15

20

-

7.5

10

15

20

415-3-50

415-3-50

415-3-50

415-3-50

415-3-50

415-3-50

374

374

374

374

374

374

457

457

457

457

457

457

1.3

1.3

1.6

1.6

2.4

3

8.3

10

12.1

16.4

17.3

19.2

61.8

65.5

101

95

111

118

0.75

1

1

1.5

2

3

2.5

3.3

2.4

2.9

4.3

4.6

-

7

10.5

14

-

7

10.5

14

-

7

10.5

14

-

7

10.5

14

21

-

10.5

14

21

28

-

10.5

14

21

28

14.2

14.2

14.2

16.5

17.1

17.1

17.1

17.3

19.1

19.1

19.1

19.1

25.8

25.8

25.8

25.8

25.8

28.4

28.4

28.4

28.4

32.3

31.6

31.6

31.6

31.6

32.6

25

25

25

25

30

30

30

30

32

32

32

32

45

45

45

45

45

50

50

50

50

50

55

55

55

55

55

KW FLA

MCA MOCP

Page 13: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw12

SUPPLY AIR PERFORMANCE

CFM Values, PNGc 048 & PNGc 060 (Direct driven motor)

RPM Values, PNGc 076 - 120 (Belt Driven)

MODEL

PNGc-048 C2

PNGc-060 C2

940

932

920

966

959

947

External Static Pressure [in.wg]

0.1

1800

1700

1630

2200

2075

2000

RPM0.2

1690

1530

1490

2100

2000

1940

0.3

1580

1420

1380

1990

1946

1900

0.4

1460

1390

-

1960

1895

-

0.5

1360

-

-

1890

-

-

External Static Pressure [in.wg]Model

PNGc-076 C2

PNGc-090 C2

PNGc-100 C2

PNGc-120 C2

2300

2600

2750

2600

2800

3150

2900

3100

3500

3300

3800

4150

CFM0.1 0.2 0.3 0.4 0.5 0.6 0.7

826

900

992

930

957

984

-

-

1057

-

878

896

845

946

1022

953

979

1006

-

1045

1109

882

896

913

932

984

1122

977

1002

1027

942

1076

1155

893

907

943

984

1022

1222

1001

1025

1049

980

1106

1212

904

916

974

1042

1060

1322

1025

1048

1072

1017

1137

1278

914

951

1012

1076

1098

1422

1050

1072

1094

1055

1167

1300

924

985

1051

1114

1136

1522

1075

1096

1117

1092

1198

-

935

1018

1089

Page 14: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw13

UNIT DIMENSIONS

Page 15: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw14

UNIT DIMENSIONS

Page 16: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw15

TYPICAL WIRING DIAGRAM

WITH MICROPROCESSOR BASED CONTROLLER (STANDARD)

Page 17: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw16

LOAD DISTRIBUTION

X2 (kg)

45

47

59

68

87

90

A (mm)

75

75

75

75

75

75

X1 (kg)

50

51

64

71

94

98

W (mm)

1130

1130

1130

1405

1405

1405

L (mm)

1290

1290

1290

1740

1740

1740

MODEL

PNGc-048 C2

PNGc-060 C2

PNGc-076 C2

PNGc-090 C2

PNGc-100 C2

PNGc-120 C2

LOAD DISTRIBUTION

Page 18: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw17

About RIC

Refrigeration Industries Company (KSE 504) is a group holdingcompanywithdiversifiedinterestsinmanufacturing,contractingandservices. Recognized regionally for our engineering capabilities andmanagementexcellence,RICand its subsidiariesofferawiderangeofhighqualityproductsandservicesthatcatertobothresidentialandcommercial customers, in the areas of climate control technologies andspecializedstoragesolutions.

In viewof thegrowingKuwait infrastructureand the limitationsimposedonitbythecountry’saridclimate,theRefrigerationIndustriesCompanywasestablished43yearsagoin1973,byAmiriDecree.Thecompany’s operations began with the construction of the first cold stores in the region, to enable the storage of the imported foods, on whichKuwait relied.Alongwith thedevelopmentandadvancementof the country, so has RIC prospered and expanded, and is now amilestoneinthehistoryofmodernKuwait.

RICtakesprideinitssuccessfulrecordandthemanyaccoladesithasgarneredover time,but thegreatestachievementhasbeen theprovision of comfort and protection from the harsh climate, to thepeopleofKuwait.

Morethan43yearsofuninterruptedservice,overcomingextremeweather conditions, war, economic recessions and ever increasingcompetition,istestimonytothefactthatRIChasmettheexpectationsand responsibilities that was envisioned at the beginning and alsohighlightsthetenacityandvisiontoexceedtheminthefuture.Facts throughout the years

1973WarehouseswereestablishedbyAmiriDecree.

1979RICConstructed theMedicalColdStoresComplex, theworld’slargest at that time.

1980RICAirConditioningmanufacturingplantsetupinSulaibya.

1981ProductionofPackage&Mini-SplitA/CsstartedunderYork-Gulf.

1984RICwaslistedinKuwaitStockExchange.

1986COOLEXbrandProductionLaunched.

1991RICrebuiltthemanufacturingplantdestroyedduringthewar.

1997AchievedISOCertificationISO9001:1994.

2002ETLDesignedtestinglabbecamefullyoperational.

2004PrivatizationofRIC.

2010 COOLEX becomes the first A/C Unit to Pass MEW’s newregulations.

2010RICFactoryRenovationandExpansionintoneighboringcountries.

2012AchievedUL&AHRICertificationforCoolexUnits.

2014AchievedSASOCertificationforConcealedDuctedSplitSeries.

2014AchievedEUROVENTCertificationforAirHandlingUnitsAHU.

2014AchievedULCertificationforAirCooledChillers.

2015AchievedISO17025CertificationforPsychrometricLaboratory.

2016AchievedEnergyEfficiencyCertificationforConcealedDuctedSplitSeries&RooftopPackageunits(KingdomofBahrain).

نبذة عن ال�شركة �سركة �سناعات التربيد (متداولة يف �سوق الكويت للأوراق املالية برقم الت�سنيع واملقاوالت االأن�سطة تعمل يف جمال 504) هي �سركة متنوعة واخلدمات. ونحن نقدم جمموعة كبرية من املنتجات واخلدمات واحللول التقنية يف جمال مواجهة الظروف املناخية وحلول التخزين. وقد حازت

ال�سركة على اإعرتاف اإقليمي بقدراتها الهند�سية وكفاءتها االإدارية.�سركة �سناعات التربيد هي جمموعة �سركات تهدف اإلى توفري اأعلى اإحتياجات تلبي التي واخلدمات املنتجات حيث من اجلودة م�ستويات عملئها ال�سكنية والتجارية. وعلى مدى ثلثة و اأربعون عاما م�ست على اإن�ساء �سركتنا فقد اإ�ستطعنا اأن نوطد اأقدامنا يف جميع قطاعات ال�سوق الكويتي. ونحن اإذ نفتخر باالإجنازات التي حققناها, اإال اأننا اأ�سد فخرا باأننا متكنا من الوقوف اإلى جانب اأهل الكويت على مدى �سنوات طويلة درجات حيث من �سواء القا�سية املناخية الظروف تقلبات مواجهة يف

احلرارة العالية اأو االأتربة اأو الرطوبة.وباإعتبارها اإحدى ال�سركات ال�سناعية العاملة يف دولة الكويت, فقد وقد النجاح, لتحقيق �سعيها يف كبرية واآمال ال�سركة حتديات واجهت كانت ال�سركة – وال تزال – معلما من املعامل املهمة يف نظر اأهل الكويت القا�سية الطبيعة تغري اأن اإ�ستطاعت وخدمات منتجات من قدمته ملا ملناخ الكويت. فبعد نحو 43 عاما تقريبا, ال يزال ال�سوؤال مطروحا حول حتقيقنا لهذه التوقعات, فهل اإ�ستطاعت ال�سركة اأن تتحمل م�سوؤولياتها اأربعني و ثلثة مدى فعلى باالإيجاب, الرد وياأتي االأكمل؟ الوجه على عاما تقريبا مل تتوقف ال�سركة خللها عن االإ�ستمرار يف تقدمي خدماتها اأو القا�سية الطق�س ظروف يف متثلت التي ال�سعوبات رغم واأعمالها اإرتفاع حدة املناف�سة, فقد كانت كل اأو اأو الك�ساد االقت�سادي احلروب واحدة من هذه الظروف مبثابة �سهادة على اأننا حققنا ما وعدنا به وما

عقدنا العزم على تنفيذه. حقائق وتواريخ

1973 مت اإن�ساء امل�ستودعات بناء على مر�سوم اأمريي.باإن�ساء التربيد �سناعات ل�سركة الكويتية ال�سحة وزارة عهدت 1979جممع م�ستودعات خمازن التربيد الطبية, وقد كان هذا املجمع حينها اإلى هو االأ�سخم من نوعه على م�ستوى العامل, وقد و�سلت تكلفته

12,000,000 دينار كويتي.1980 مت اإن�ساء م�سنع مكيفات الهواء التابع ل�سركة �سناعات التربيد يف

ال�سليبية.1981 بدء اإنتاج اأجهزة التكييف املدجمة واملنف�سلة ال�سغرية حتت علمة

.York-Gulf1984 مت قيد �سركة �سناعات التربيد يف �سوق الكويت للأوراق املالية.

1986 بدء اإنتاج مكيفات علمة كولك�س.1991 قامت �سركة �سناعات التربيد باإعادة بناء م�سنعها الذي دمرته

احلرب.1997 احل�سول على �سهادة االآيزو 1994:9001

(ETL) 2002 بدء ت�سغيل خمترب فح�س وحدات التكييف2004 خ�سخ�سة �سركة �سناعات التربيد.

2010 كانت وحدات كولك�س اأول وحدات تكييف هواء جتتاز اللوائح التي اأقرتها (وزارة الكهرباء واملاء).

2010 مت جتديد م�سنع �سركة �سناعات التربيد وبدء التو�سع والت�سدير اإلى الدول املجاورة.

2012 احل�سول على �سهادة UL و AHRI الأجهزة التكييف كولك�س. 2014 احل�سول على �سهادة SASO الأجهزة التكييف املنف�سلة.

2014 احل�سول على �سهادة EUROVENT الأجهزة مناولة الهواء.2014 احل�سول على �سهادة UL ملربدات الهواء ال�سيلر.

2015 احل�سول على �سهادة االأيزو ISO 17025 ملخترب ال�سيكرومرتية.و املنف�سلة التكييف الطاقة الأجهزة كفاء �سهادة 2016 احل�سول على

الوحدات املدجمة (مملكة البحرين).

Page 19: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw18

CENTRAL AIR CONDITIONING AND SPLIT UNITCoolex continuously works towards the improvement of its products. Hence, the design and specifications of the ordered product may vary without prior notice.

Please contact Sales and Marketing Department [email protected] or www.coolex.com.kw for specific information on the current design and specifications. Ref no.: CPRC 18-5-000

COOLEX is a subsidiary of the RIC Groupwww.ric.com.kw

NOTES

Sultanate of Oman

Al Noor Projects Engineering & Trading Company Address

TelFaxEmailEmailWebsite

:ThirdFloor,OmanHouseP.O.Box:1047,P.C:114HayAlMina-Muscat:+96824709402/403:+96824709401:[email protected]:[email protected]:www.alnoorprojects.com

Kingdom of Bahrain

Y.K. Almoayyed & Sons Address

TelDirectFaxEmailEmailWebsite

:EHAD–ProjectDepartment,SehlaWorkshopP.O.Box143,Manama,KingdomofBahrain:+97317400444,Extn.205:+97317405250:+97317400388: [email protected]: [email protected]: www.almoayyed.com

Iran

Capital ICEBERG Limited Company Address

TelFaxMobileEmailEmailEmailWebsite

:No.31,3rdFloor,AghdasieyehTradeCenterAghdasiyehStreet.Tehran–Iran:+98(021)26110510:+98(021)26110510:+989121192961: [email protected]: [email protected]: [email protected]: www.capitaliceberg.com

Sudan

Abina For Advises And Engineering Work Company Address

TelFaxMobileEmail

:KatrenaStreet-EastQurashiParkSudan–Khartoum:+249574064:+249574064:+249900900246/247/248/249/250/251/252:[email protected]

Islamic Republic of Pakistan

AG TEK Pvt. Ltd.Address

TelFaxCellMobileEmailEmailWebsite

:179-S,ImperialGardenParagonCity Lahore - Pakistan :+92-42-37187640-43:+92-42-37187644:+92-300-4745624:+92-321-2280011: [email protected]: [email protected]: www.agtek.com.pk

Egypt

Total Group Egypt CompanyAddress

TelMobileMobileEmailEmailWebsite

:4BuildingsAl-Noor–SheratonHousings Cairo – Egypt:+202267240/837:+20109966627:+21201299444: [email protected]: [email protected]: www.coolex-eg.com

United Arab Emirates UAE

Obaid Humaid Al-Tayer Engineering DivisionAl Tayer GroupAddressTelFaxMobileEmailWebsite

:Dubai–UAE,POBox2623:+97142011272:+97142825008:+971503500747: [email protected]: www.altayer.com

State of Qatar

Al Jaber for air conditioning & Refrigeration industriesAddressTelFaxMobileMobileEmailWebsite

:PO.Box23546Doha:+97444210963:+97444448919:+97455610321:+97455843255:[email protected]:www.jaric-qa.com

Kingdom of Saudi Arabia KSA

Al-Etmad for Refrigeration and Air Conditioning Industries CompanyAddress

TelFaxMobileEmailWebsite

:AlQortobahQuartier,KingAbdullahRoadRiyadh–KSA,P.O.Box50467Riyadh11533:+966112447789:+966114958812:+966560034240:[email protected]: www.Coolex.co

Republic of Iraq

SWEER Company Limited Address

TelMobileEmailWebsite

:AlSenak-JumhuriaStreet-Baghdad-IraqP.O.Box:8095:+96418181196:+9647705884444: [email protected]: www.sweerco.com

Page 20: Rooftop Package Series R-407C...SELECTION PROCEDURE Sea level 1000 2000 3000 4000 5000 6000 7000 Altitude [ft] Correction factor 1 0.996 0.990 0.984 0.980 0.974 0.965 0.960 Example

www.coolex.com.kw