Roof Details
-
Upload
martin-fox -
Category
Documents
-
view
136 -
download
0
description
Transcript of Roof Details
TThhee SSccoottttiisshh BBuuiillddiinngg SSttaannddaarrddss AAggeennccyy AACCCCRREEDDIITTEEDD CCOONNSSTTRRUUCCTTIIOONN DDEETTAAIILLSS ((SSCCOOTTLLAANNDD))
STtRtHw
BIrmec
Thcaaaaccbl Tsis
LTipsdsw
ACCREDITED CONSTRUCTION DETAILS (SCOTLAND) (FOR THE LIMITATION OF THERMAL BRIDGING AND AIR LEAKAGE IN LOW AND MEDIUM RISE DOMESTIC TYPE)
tatus of this document his document provides guidance on one way to meet some of the requirements of
he functional standards set out in Regulation 9 of the Building (Scotland) egulations. There is however no need to follow the guidance in this document, as
here are other ways of meeting the functional standards. Access to the Technical andbook is available on the website of the Scottish Building Standards Agency at ww.sbsa.gov.uk, and it may be downloaded free of charge.
---------------- ------------------- N
ackground mproved energy performaneflected in the Scottish buildeans that buildings are mfficiencies than ever befoonstruction that limits:
• air infiltration; and • heat-loss through junc
he Scottish Building Standaow to address these two isan arise. The details prebsolute levels of airtightnesre currently ventilated, but cceptable level. The detavailable and minimise theondensation. The arrangemondensation risk, to making uilding elements, where tra
evels that can be achieved w
his document provides two elected construction type ans also provided on associaelection of membranes, air in
imitations on use he details illustrated here d
ntended to provide sufficienerformance presented in thhow principles of constructirawn to scale. It should be nhown; it is acceptable to pould be, in the timber frame
-------------------------------1 INTRODUCTIO
ce measures for new construction work are now ing regulations. Achieving these standards generally
ore highly insulated and have better heating system re, whilst simultaneously retaining a good level of
tions in the fabric.
rds Agency recognise the need to provide guidance on sues, whilst at the same time avoiding the risks which sented in this document do not endeavour to attain s that will result in a change in the way that dwellings when followed with care will limit air infiltration to an ils can be built using the construction skills currently risk of both surface condensation and interstitial ents shown however go further than simply minimising a useful contribution to reduce heat-loss at junctions of ditionally it can be difficult to maintain the insulation ithin the elements themselves.
levels of guidance. Specific guidance related to each d on each construction detail. Supplementary guidance ted issues including the selection of insulation, the filtration and some examples of construction issues.
o not form part of the Technical Handbooks but are t information to enable users to achieve the level of ese documents. These details are generic in nature, on and for this reason they are not dimensioned, nor oted that not all permutations of thermal insulation are rovide multiple layers of insulation. Examples of this wall an additional layer of insulation with a preserved
cavity may be provided to the outside of the sheathing board, or in the masonry cavity wall an insulated lining board may be installed in addition to the cavity insulation. All details are suitable for use in domestic type buildings up to six storeys high. Details are provided for the most common construction types:
• masonry walls with external insulation • masonry cavity walls with full fill insulation • masonry cavity walls with partial fill insulation • masonry walls with internal insulation • timber frame walls • steel frame walls • miscellaneous junctions, e.g. door thresholds and roof windows.
AimThe main aim in providing these details is to illustrate a ready means:
• to manage thermal loss (to reduce energy requirement) • to avoid interstitial condensation (which can damage construction) • to avoid surface condensation (which can lead to mould growth and endanger
health) • to limit air leakage (to reduce energy requirement) • to prevent rain penetration (which can damage construction and endanger
health). The common factors which are illustrated in each detail are:
• the position of insulation (to limit thermal bridging) • the position and extent of ventilation (to control condensation) • the position and the different performance characteristics of the building
membranes (to manage air and vapour movement and to prevent water entering the building)
• the position and type of cavity closers and cavity barriers (to minimise air movement and in the case of the latter, to provide fire resistance). Where these are proprietary types, it is assumed for the purposes of these details that they incorporate a DPC which is capable of directing moisture away from the inside of the building.
Other requirements of the Scottish building regulations which are not illustrated by these details, but which should be considered by the designer include:
• thermal performance of elements (U-values) • structural • fire resistance and flame spread • ventilation (of rooms) • airborne and impact noise (including flanking sound) • damp-proofing arrangements.
Supplementary Guidance
Selection of Insulation The selection of insulation material and the choice of thickness of insulation to be provided will be influenced by a number of factors which are determined by the building procurer and the designer (e.g. architectural features). These fall outwith the scope of this publication. In terms of construction of elements the key issues are a combination of the following:
• thermal transmittance (U-value) recommended in Scottish building regulations • thermal conductivity of the insulation material • thermal performance of the ‘non-insulating’ part of the construction (e.g.
linings and structural components) • interaction of the insulation material and the remainder of construction (e.g.
insulation position in relation to ventilation of the element or bridging of insulation by fixings).
The U-value calculation is outwith the scope of this document. Guidance on how this can be done and the other options available are in Section 6 of the Technical Handbooks. Layers of differing insulation materials Where different types of insulation are used within a construction, it is recommended that the insulation nearest to the outer surface of the construction be the least resistant to the passage of water vapour. This is to reduce the possibility of condensation forming in between the insulation layers. For example, where mineral wool is used in conjunction with polystyrene board, the mineral wool should be the outer layer. Where it is essential that the outer layers of insulation has a higher vapour resistivity than the inner layer then condensation risk analysis should always be carried out. Selection of Membranes The details illustrate the location and characteristics of the membranes related to their function in resisting water, water vapour or air. These characteristics are fundamental to the success of the construction and selection of the correct membrane should be made with care. Vapour control layer A vapour control layer should be used:
• principally to reduce the spread of water vapour throughout the construction element, where condensation can do harm to the building materials.
• as a secondary function to improve the airtightness of the building fabric.
Typically this layer is provided on the inside face of the insulation in, timber or steel frame walls, rooms in roof spaces, flat roofs and it may be incorporated as an integral part of a proprietary wall lining board A vapour control layer is a material with a vapour resistance greater than 200 MN·s/g.
Vapour permeable or breather membrane A vapour permeable or breather, water-resistant membrane should be used:
• as a primary protection to vulnerable construction materials from the harmful effects of precipitation during the construction process; and
• as a secondary protection to vulnerable construction materials from the harmful effects of precipitation, throughout the life of the building; and
• to allow water vapour to escape from vulnerable construction materials that would otherwise be entrapped due to lack of ventilation.
Typically this layer is provided on the outer face of the inner leaf of a timber frame wall or above sarking insulation where the space between the tiles or slates is ventilated. In the case of the former the membrane has a vapour resistance of no more than 0.6 MN·s/g and in the case of the latter, it has a vapour resistance of no more than 0.25 MN·s/g. Non-vapour permeable roofing membrane A non-vapour permeable, water-resistant roofing membrane should be used:
• as a primary protection to vulnerable roof construction materials from the harmful effects of precipitation during the construction process; and
• as a primary protection to vulnerable roof construction materials from the harmful effects of precipitation, for example the covering to a built-up felt flat roof directly above the insulation; and
• as a secondary protection to vulnerable roof construction materials from the harmful effects of precipitation, for example as a roof tile underlay where the roof space is ventilated above the insulation.
This type of layer has a vapour resistance of more than 0.25 MN·s/g. Sequence of construction Some of the details presented in this document can only be followed effectively if consideration is given to the sequence of construction. This is important with regard to the placing of insulation materials and particularly where insulation needs access from two sides to allow correct positioning. An example of this is at the eaves of a roof where it may be necessary to fit the insulation which links the wall and roof insulation before the soffit boards are fitted. Dense Block For the purposes of this document a dense block is one with a thermal conductivity greater than 0.7 W/mK. Thermal Conductivity (lambda - λ ) Thermal conductivity is a measure of a material’s ability to conduct heat. It is measured in W/mK and is the quantity of heat (in Watts) which will pass through 1 square metre of the material 1 metre thick for each degree difference in temperature between one side of the material and the other. Any quoted thermal conductivity of a given material is, therefore, independent of its thickness.
Air infiltrationThe details shown in this document contain measures designed to reduce air infiltration. This depends on the form of construction and the level of workmanship but the objective is to form a definable, continuous air barrier around the dwelling. Ways of preventing air infiltration should then be considered at every penetration of this barrier. Particular care on site should be paid to:
• joints between structural components e.g. wall to floors • joints around components and opening within walls • service penetrations – plumbing, electrical and ventilation.
General
• close any vertical ducts at the top and bottom where they meet the air barrier (e.g. boxing round soil vent pipe’s)
• seal any service penetrations through the air barrier • select the appropriate sealant or gap filler for the size of gap and degree of
movement anticipated.
Masonry Construction • ensure continuous ribbons of adhesive are used to fix to dry lining at
perimeters of external walls, openings, and services on external walls. The importance of correct sealing of dry lining on dabs needs to be stressed, as this is a key area of infiltration and can seriously affect the overall ventilation rate
• use joist hangers to support floor joists • seal under skirting boards where dry lining is used, or on suspended floors.
Timber Frame
• ensure DPC’s are turned up behind sole plates and lap with vapour control layers; alternatively seal with mastic or a gasket between the DPC and sole plate
• place bead of mastic on timber floor deck before positioning wall panels (timber ground floors and intermediate floors)
• ensure ‘sheet’ vapour control layers are properly lapped at junctions, and/or, • ensure any vapour control plasterboard is jointed in accordance with the
manufacturer’s instructions • always return vapour control layers into door and window reveals, head and
sills • cut vapour control layers tight to electrical outlets and seal at piped service
penetrations, (with tape or sealant as appropriate) • ensure all breather control membranes overlap each other and are stapled in
place.
Steel Frame • all joints between rigid insulation boards be lapped or sealed with tape
approved by insulation manufacturer • ensure ‘sheet’ vapour control layers are properly lapped at junctions, and/or, • ensure any vapour control plasterboard is jointed in accordance with
manufacturer’s instructions • always return vapour control layers into door and window reveals, heads and
sills • cut vapour control layers tight to electrical outlets and seal at piped service
penetrations. Examples of some common construction issues Poorly positioned cavity insulation The cavity wall insulation should be installed tight to the outer face of the inner leaf. This will prevent air circulation between the block and insulation reducing the performance of the insulation layer. Debris bridging the cavity Clear all debris including mortar droppings from the cavity as work progresses to prevent cold bridging occurring between the inner and outer leaf. Insulation cut short of the cavity closers Ensure that cavity insulation is cut to suit boards/batts that tightly butt against each other and against surrounding cavity closers and loose fill insulation. Service Penetrations Service penetrations should be core drilled to minimise damage to the insulation layer and facilitate remedial air sealing. Any damage caused to the insulation layer by penetrations through the air barrier should be made good following their installation. This can be achieved by filling any large gaps with loose fibrous insulation, expanding foam insulation and sealing with a thin mastic fillet. This includes behind bath panels, shower trays, kitchen units and into service shafts. Socket outlet/ switch plates Where the air barrier is formed by a plasterboard lining it is recommended that a continuous ribbon of adhesive is applied around the hole prior to installing the plasterboard. This will reduce air leakage through the sockets/ switches into the void beyond. Proprietary gasketed socket boxes and membranes are also available where required. Window and door frames Air leakage is often found to occur between window/door frames and the surrounding construction. Mastic seals are often required between plaster finishes, window boards and frames.
Recessed light fittings Recessed light fittings may permit air leakage where they breach the plasterboard ceiling line into the voids or lofts beyond. They should only be allowed to penetrate the primary air barrier if the units are of an air sealed type or a further secondary air barrier is formed beyond. Extract fans Termination of extract fan ducts should be installed and sealed to prevent air leakage occurring through plasterboard finishes. Where appropriate a continuous ribbon of adhesive should be installed around the penetration. Where possible the ducts should also be sealed to any masonry inner leaf. Extract fans may also be fitted with external flaps to minimise air infiltration through the unit. Stairs Plaster finishes are typically omitted from voids below staircases. Air infiltration may then occur through mortar joints in poor quality masonry into the externally ventilated wall cavities. Plaster finishes should be installed below stairs or a thin render/parge coat shoul be applied to the surface of the masonry. Dormers in room in roof The plasterboard linings surrounding the dormer will form the air barrier. Care should be taken to ensure that the linings form a continuous air barrier and are fully sealed to the window frames.
Section 1 Introduction and Supplementary Guidance Section 2 2.00 Masonry: External Wall Insulation Link 2.01 Pitched Roof, Ventilated Roofspace, Eaves Link 2.02 Pitched Roof, Ventilated Roofspace, Gable Link 2.03 Pitched Roof, Ventilated Rafter Void, Eaves Link 2.04 Pitched Roof, Ventilated Rafter Void, Gable Link 2.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves Link 2.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable Link 2.07 Timber Flat Roof Link 2.08 Timber Flat Roof with Parapet Link 2.09 Lintel at Window Head Link 2.10 Windows and doors, Jambs and sills Link 2.11 Ground Bearing Floor, Insulation Above Slab Link 2.12 Ground Bearing Floor. Insulation Below Slab Link 2.13 Raft Foundation Link 2.14 In-situ Suspended Ground Floor Slab Insulation Above Slab Link 2.15 In-situ Suspended Ground Floor Slab, Insulation Below Slab Link 2.16 Concrete Beam and Block Suspended Ground Floor Link 2.17 Timber Suspended Ground Floor Link 2.18 Separating Wall Link 2.19 Concrete Intermediate Floor Link 2.20 Timber Intermediate Floor Link Section 3 3.00 Masonry: Cavity Wall Insulation: Full Fill Link 3.01 Pitched Roof, Ventilated Roofspace, Eaves Link 3.02 Pitched Roof, Ventilated Roofspace, Gable Link 3.03 Pitched Roof, Ventilated Rafter Void, Eaves Link 3.04 Pitched Roof, Ventilated Rafter Void, Gable Link 3.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves Link 3.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable Link 3.07 Timber Flat Roof Link 3.08 Timber Flat Roof with Parapet Link 3.09 Windows and doors, Lintel Link 3.10 Windows and doors, Folded Lintel Link 3.11 Windows and doors, Independent Lintel Link 3.12 Windows and doors, Jambs and sills Link 3.13 Ground Bearing Floor. Insulation Above Slab Link 3.14 Ground Bearing Floor, Insulation Below Slab Link 3.15 Raft Foundation Link 3.16 In-situ Suspended Ground Floor Slab, Insulation above Slab Link 3.17 In-situ Suspended Ground Floor Slab, Insulation Below Slab Link 3.18 Concrete Beam and Block Suspended Ground Floor Link 3.19 Timber Suspended Ground Floor Link 3.20 Separating Wall Link 3.21 Concrete Intermediate Floor Link 3.22 Timber Intermediate Floor Link
Section 4 4.00 Masonry: Cavity Wall Insulation: Partial Fill Link 4.01 Pitched Roof. Ventilated Roofspace. Eaves. Link 4.02 Pitched Roof. Ventilated Roofspace. Gable Link 4.03 Pitched Roof, Ventilated Rafter Void, Eaves Link 4.04 Pitched Roof, Ventilated Rafter Void, Gable Link 4.05 Pitched Roof. Ventilated Batten Void (warm roof). Eaves. Link 4.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable Link 4.07 Timber Flat Roof Link 4.08 Timber Flat Roof with Parapet Link 4.09 Lintel at Window Head Link 4.10 Windows and doors. Folded Lintel Link 4.11 Windows and doors. Independent Lintel Link 4.12 Windows and doors. Jambs and sills Link 4.13 Ground Bearing Floor. Insulation Above Slab Link 4.14 Ground Bearing Floor. Insulation Below Slab Link 4.15 Raft Foundation Link 4.16 In-situ Suspended Ground Floor Slab, Insulation above Slab Link 4.17 In-situ Suspended Ground Floor Slab, Insulation Below Slab Link 4.18 Concrete Beam and Block Suspended Ground Floor Link 4.19 Timber Suspended Ground Floor Link 4.20 Separating Wall Link 4.21 Concrete Intermediate Floor Link 4.22 Timber Intermediate Floor Link Section 5 5.00 Masonry: Internal Wall Insulation Link 5.01 Pitched Roof, Ventilated Roofspace, Eaves Link 5.02 Pitched Roof. Ventilated Roofspace. Gable Link 5.03 Pitched Roof, Ventilated Rafter Void, Eaves Link 5.04 Pitched Roof. Ventilated Rafter Void. Gable Link 5.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves Link 5.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable Link 5.07 Timber Flat Roof Link 5.08 Timber Flat Roof with Parapet Link 5.09 Lintel at Window Head Link 5.10 Windows and doors, Folded Lintel Link 5.11 Windows and doors. Jambs and sills Link 5.12 Ground Bearing Floor. Insulation Above Slab Link 5.13 Ground Bearing Floor. Insulation Below Slab Link 5.14 Raft Foundation Link 5.15 In-situ Suspended Ground Floor Slab Insulation above Slab Link 5.16 Concrete Beam & Block Suspended Ground Floor Link 5.17 Timber Suspended Ground Floor Link 5.18 Separating Wall Link 5.19 Concrete Intermediate Floor Link 5.20 Timber Intermediate Floor Link
Section 6 6.00 Timber Frame Link 6.01 Pitched Roof, Ventilated Roofspace, Eaves Link 6.02 Pitched Roof. Ventilated Roofspace. Gable Link 6.03 Pitched Roof, Ventilated Rafter Void, Eaves Link 6.04 Pitched Roof, Ventilated Rafter Void, Gable Link 6.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves Link 6.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable Link 6.07 Timber Flat Roof Link 6.08 Timber Flat Roof with Parapet Link 6.09 Lintel at Window Head Link 6.10 Windows and doors, Jambs and sills Link 6.11 Ground Bearing Floor, Insulation Above Slab Link 6.12 Ground Bearing Floor, Insulation Below Slab Link 6.13 Raft Foundation Link 6.14 In-situ Suspended Ground Floor Slab. Insulation Above Slab Link 6.15 Concrete Beam and Block Ground Floor Link 6.16 Timber Suspended Ground Floor Link 6.17 Separating Wall Link 6.18 Timber Intermediate Floor Link 6.19 Wall junction Link Section 7 7.00 Steel frame Link 7.01 Pitched Roof, Ventilated Roofspace, Eaves Link 7.02 Pitched Roof. Ventilated Roofspace. Gable Link 7.03 Pitched Roof, Ventilated Rafter Void, Eaves Link 7.04 Pitched Roof, Ventilated Rafter Void, Gable Link 7.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves Link 7.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable Link 7.07 Timber Flat Roof Link 7.08 Timber Flat Roof with Parapet Link 7.09 Lintel at Window Head Link 7.10 Windows and doors, Jambs and sills Link 7.11 Ground Bearing Floor, Insulation Above Slab Link 7.12 Ground Bearing Floor, Insulation Below Slab Link 7.13 Raft Foundation Link 7.14 In-situ Suspended Ground Floor Slab. Insulation Above Slab Link 7.15 Concrete Beam and Block Ground Floor Link 7.16 Timber Suspended Ground Floor Link 7.17 Separating Wall Link 7.18 Timber Intermediate Floor Link 7.19 Wall junction Link Section 8 General Arrangements 8.00 For future development Link 8.01 For future development Link 8.02 Roof Window, Ventilated Rafter Void Link 8.03 Roof Window. Ventilated batten Void (Warm Roof) Link 8.04 Roof Window. Ventilated batten Void (Warm Roof) Link 8.05 Level Threshold, Insulation above Slab, Ramped Access Link 8.06 Level Threshold, Insulation below Slab, Ramped Access Link 8.07 Level Threshold, Timber Floor, Ramped Access Link 8.08 Ceilings, Services Penetrations Link
plaster or plasterboard on dabs
solid masonry wall(any type)
cladding(render finish shown)
externally applied insulation system, various fixing methods (see BRE publication Thermal Insulation: avoiding risks - BR262 to establish where it can be used avoiding technical risk)
Revision E
2.00 Masonry: External Wall Insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: External Wall Insulation2.01 Pitched Roof, Ventilated Roofspace, Eaves
proprietary cross flow ventilator to maintain
minimum 25mm air gap
lap roof and wall insulation, minimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
roofing membrane
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
ventilation gap equivilent to 10mm minimum continuous opening is
required where the roof pitch is above 15°
orventilation gap equivilent to
25mm minimum continuous opening is required where the
roof pitch is below 15°,insect mesh should be installed
Revision F
Read in conjunction withMasonry: External Wall InsulationPitched Roof, Ventilated Roofspace, Gable
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required where the roof pitch is greater than 35° or the roof span is more than 10m
sarking board
restraint required for insulation, for example metal banding, wire
mesh or similar material, fixed between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: External Wall Insulation2.02 Pitched Roof, Ventilated Roofspace, Gable
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
insulation between last truss and gable wall
Revision C
Read in conjunction withMasonry: External Wall InsulationPitched Roof, Ventilated Roofspace, Eaves
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
30 minute fire resistingcavity barrier
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
proprietary cross flow ventilator to maintain minimum
25mm air gaproofing membrane
inhabited space
where two insulation types are used together see supplementary guidance
Masonry: External Wall Insulation2.03 Pitched Roof, Ventilated Rafter Void, Eaves
Revision E
Read in conjunction withMasonry: External Wall InsulationPitched Roof, Ventilated Rafter Void, Gable
ventilation to roofspace
sarking board
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required
50mm air gap
sarking board
lap roof and wall insulation, minimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
vapour control layer
ventilation gap equivilent to 25mm minimum continuous
opening,insect mesh should be installed
restraint required for insulation, for example metal banding, wire
mesh or similar material, fixed between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
lap roof and wall insulation, roof insulation to be
compressed between sarking and wall head
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Revision E
wall insulation should be taken up level with
top of gable
Masonry: External Wall Insulation2.04 Pitched Roof, Ventilated Rafter Void, Gable
Read in conjunction withMasonry: External Wall InsulationPitched Roof, Ventilated Rafter Void, Eaves
fill gaps at top of gable masonry with mortar to
form an even surface
50mm ventilation path over insulation
vapour control layer
where two insulation types are used together see supplementary guidance
sarking boardroofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: External Wall Insulation2.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves.
ventilation to batten void
vapour control layer
proprietary over fascia ventilator
30 minute fire resistingcavity barrier
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
lap roof and wall insulationminimum 50mm
consider sequence of construction, see supplementary guidance
vapour permeable membrane with a vapour resistance of not more than
0.25 MN.s/g
support insulation between rafters on battens or clips
inhabited space
Revision F
Read in conjunction withMasonry: External Wall InsulationPitched Roof, Ventilated Batten Void (warm roof), Gable
where two insulation types are used together see supplementary guidance
ventilation gap equivalent to 5mm minimum continuous opening is required at ridge rigid insulation as sarking
restraint required for insulation, for example
metal banding, wire mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane (with a vapour resistance of not
more than 0.25 MN.s/g)
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
ventilation to tile batten void
lap roof and wall insulation, roof insulation to be
compressed between sarking insulation and wall head
Revision E
vapour control layer
insulation between rafters supported on battens or clips
ensure insulation is placed between gable wall and last rafter
Masonry: External Wall Insulation2.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction withMasonry: External Wall InsulationPitched Roof, Ventilated Batten Void (warm roof), Eaves
where two insulation types are used together see supplementary guidance
rigid insulation as sarking
wall insulation should be taken up level with top of gable
fill gaps at top of gable masonry with mortar to
form an even surface
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Revision F
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer,
and sealed
fix full height blocking piece and tightly pack mineral wool
into void and under deck
consider sequence of construction, see supplementary
guidance
roofing membrane
vapour control layer
Masonry: External Wall Insulation2.07 Timber Flat Roof
declevity piece
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
vapour control layer
Revision E
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer,
and sealed
minimum distance 300mm between top of edge
insulation and bottom of roof insulation
place 20mm strip of insulation with thermal conductivity (value) not exceeding 0.025W/mK around parapet
flashing minimum 150mm above finish roof level
Masonry: External Wall Insulation2.08 Timber Flat Roof with Parapet
render or impervious cladding
declevity piece
roofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
lintel of any type
15mm strip of insulation with thermal conductivity ( value)
not exceeding 0.025W/mK between packing pieces
Revision D
continuous ribbon of plaster adhesive, sealing joint between wall and board
sealant to back of framesealant to front of frame
Masonry: External Wall Insulation2.09 Lintel at Window Head The same thermal principles apply at the head of doors
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
wall insulation carried up to underside of sill
sealant to front and back of frame/sill
plan view
Revision E
continuous ribbon of plaster adhesive, sealing joint between wall and board
section view
Masonry: External Wall Insulation2.10 Windows and doors, Jambs and sills
15mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK between packing pieces
15mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK between packing pieces
sealant to front and back of frame/sill
continuous ribbon of plaster adhesive, sealing joint between
wall and board
damp proof course
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
wall insulation continued at least 150mm below top of
floor insulation
Revision F
vapour control layer under timber floor finish
damp proof membrane above or below slab
damp proof course
external ground level
Masonry: External Wall Insulation2.11 Ground Bearing Floor, Insulation Above Slab
mastic seal
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
continuous ribbon of plaster adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision F
wall insulation continued at least 150mm below top of
floor insulation
damp proof membrane
damp proof course
external ground level
Masonry: External Wall Insulation2.12 Ground Bearing Floor. Insulation Below Slab
mastic seal 20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
continuous ribbon of plaster adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision F
external ground level
wall insulation continued at least 150mm below top of
floor insulation
damp proof course
damp proof membrane
Masonry: External Wall Insulation2.13 Raft Foundation
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
mastic seal
continuous ribbon of plaster adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under timber floor finish
Revision F
external ground level
wall insulation continued at least 150mm below top of
floor insulation
damp proof course
damp proof membrane
Masonry: External Wall Insulation2.14 In-situ Suspended Ground Floor Slab Insulation Above Slab
mastic seal
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
continuous ribbon of plaster adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision F
external ground level
wall insulation continued at least 150mm below top of
perimeter insulation
damp proof course
damp proof membrane
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around slab and any screed
Masonry: External Wall Insulation2.15 In-situ Suspended Ground Floor Slab, Insulation Below Slab
mastic seal
dense blocks should not be used below slab
continuous ribbon of plaster adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under timber floor finish
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
Revision F
damp proof course
external ground level
wall insulation continued at least 150mm below top of
floor insulation damp proof membrane
solum
Masonry: External Wall Insulation2.16 Concrete Beam and Block Suspended Ground Floor
mastic seal
N.B. 20mm strip of perimeter insulation with thermal conductivity (value) not exceeding 0.025W/mK should be installed around any screed
continuous ribbon of plaster adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
insulation directly under flooring - supported either on battens or on netting draped over joists and stapled at required depths
Revision F
damp proof course
external ground level
wall insulation continued at least 150mm below top of
floor insulation
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ²per m ² floor area
expanding foam and continuous sealant
20mm strip of perimeter insulation with thermal
conductivity ( value) not exceeding 0.025W/mK should be
installed between wall and last joist
solum
Masonry: External Wall Insulation2.17 Timber Suspended Ground Floor
mastic seal floor joist ends supported on joist hangers or using scarcement wall
continuous ribbon of plaster adhesive sealing joint between wall and board
damp proof membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plan view
Revision C
Masonry: External Wall Insulation2.18 Separating Wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
wall insulation continued across floor zone
gaps between wall and floor sealed
Revision D
Masonry: External Wall Insulation2.19 Concrete Intermediate Floor
continuous ribbon of plaster adhesive, sealing joint between wall and board
separating floors require additional layers and components to comply with Section 2: Fire and Section 5: Noise
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Revision D
wall insulation continued across floor zone
Masonry: External Wall Insulation2.20 Timber Intermediate Floor
separating floors require additional layers and components to comply with Section 2: Fire andSection 5: Noise
continuous ribbon of plaster adhesive, sealing joint between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plaster or plasterboard on dabs
inner leaf (block shown)
outer leaf (brick shown)
full fill cavity wall insulation(see BRE publication Thermal Insulation: avoiding risks - BR262 to establish where it can be used avoiding technical risk)
3.00 Masonry: Cavity Wall Insulation: Full FillRevision C
render finish if required/desired
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Full Fill3.01 Pitched Roof, Ventilated Roofspace, Eaves
proprietary cross flow ventilator to maintain
minimum 25mm air gap
lap roof and wall insulation, minimum 50mm thickness at narrowest pointconsider sequence of construction,
see supplementary guidance
roofing membrane
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Revision E
Read in conjunction withMasonry: Cavity Wall Insulation: Full FillPitched Roof, Ventilated Roofspace, Gable
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required where the roof pitch is greater than 35° or the roof span is more than 10msarking board
ventilation gap equivilent to 10mm minimum continuous opening is
required where the roof pitch is below 15°
orventilation gap equivilent to 25mm
minimum continuous opening is required where the roof pitch is 15°
or above
insect mesh should be installed
cavity closer (thin calcium silicate board or similar)
restraint required for insulation, for example metal banding, wire
mesh or similar material, fixed between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Full Fill3.02 Pitched Roof, Ventilated Roofspace, Gable
Revision D
Read in conjunction withMasonry: Cavity Wall Insulation: Full FillPitched Roof, Ventilated Roofspace, Eaves
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
insulation between last truss and gable wall
continue wall insulation to top of gable or alternatively 270mm above
bottom of ceiling tie and insert cavity tray
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
30 minute fire resistingcavity barrier
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
proprietary cross flow ventilator to maintain minimum
25mm air gaproofing membrane
inhabited space
where two insulation types are used together see supplementary guidance
Revision E
sarking board
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required
50mm air gap
sarking board
lap roof and wall insulation, minimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
vapour control layer
Masonry: Cavity Wall Insulation: Full Fill3.03 Pitched Roof, Ventilated Rafter Void, Eaves
Read in conjunction withMasonry: Cavity Wall Insulation: Full FillPitched Roof, Ventilated Rafter Void, Gable
ventilation gap equivilent to 25mm minimum continuous opening
insect mesh should be installed cavity closer (thin calcium silicate board or similar)
restraint required for insulation, for example metal banding, wire
mesh or similar material, fixed between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Revision E
50mm ventilation path over insulation
vapour control layer
where two insulation types are used together see supplementary guidance
sarking board
Masonry: Cavity Wall Insulation: Full Fill3.04 Pitched Roof, Ventilated Rafter Void, Gable
Read in conjunction withMasonry: Cavity Wall Insulation: Full FillPitched Roof, Ventilated Rafter Void, Eaves
cavity closer (thin calcium silicate board or similar)
lap roof and wall insulation, roof insulation to be
compressed between sarking and wall head
wall insulation should be taken up level with
top of gable
fill gaps at top of gable masonry with mortar to
form an even surface
roofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Full Fill3.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves
Read in conjunction withMasonry: Cavity Wall Insulation: Full FillPitched Roof, Ventilated Batten Void (warm roof), Gable
ventilation to batten void
proprietary over fascia ventilator
30 minute fire resisting cavity barrier
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
lap roof and wall insulationminimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
vapour permeable membrane(with a vapour resistance of no more
than 0.25 MN.s/g)
support insulation between rafters on battens or clips
inhabited space
Revision E
where two insulation types are used together see supplementary guidance
ventilation gap equivalent to 5mm minimum continuous opening is required at ridge rigid insulation as sarking
vapour control layer
cavity closer (thin calcium silicate board or similar)
restraint required for insulation, for example
metal banding, wire mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Revision E
vapour control layer
insulation between rafters supported on battens or clips
ensure insulation is placed between gable wall and last rafter
where two insulation types are used together see supplementary guidance
rigid insulation as sarking
Masonry: Cavity Wall Insulation: Full Fill3.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction withMasonry: Cavity Wall Insulation: Full FillPitched Roof, Ventilated Batten Void (warm roof), Eaves
cavity closer (thin calcium silicate board or similar)
ventilation to tile batten void
lap roof and wall insulation, roof insulation to be
compressed between sarking insulation and wall head
wall insulation should be taken up level with top of gable
fill gaps at top of gable masonry with mortar to
form an even surface
vapour permeable membrane (with a vapour resistance of not
more than 0.25 MN.s/g)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Revision E
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer,
and sealedfix full height blocking piece and tightly pack mineral wool
into void and under deck
consider sequence of construction, see supplementary
guidance
roofing membrane
vapour control layer
Masonry: Cavity Wall Insulation: Full Fill3.07 Timber Flat Roof
declevity piece
cavity closer (thin calcium silicate board or similar)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
vapour control layer
Revision E
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer,
and sealed
minimum distance 300m between top of edge
insulation and bottom of roof insulation
place 20mm strip of insulation with thermal conductivity (value) not exceeding 0.025W/mK around parapet
flashing minimum 150mm above finish roof level
render or impervious cladding
declevity piece
Masonry: Cavity Wall Insulation: Full Fill3.08 Timber Flat Roof with Parapet
roofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision E
steel lintelcontinuous baseplate
steel lintelperforated baseplate
sealant to back of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board
sealant to front and back of frame
sealant to front of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board
Masonry: Cavity Wall Insulation: Full Fill3.09 Windows and doors, Lintel
15mm strip of insulation with thermal conductivity ( value)
not exceeding 0.025W/mK
N.B. in certain circumstances the lintel will require fire resistance - check with lintel manufacturer
weep hole taken through render
weep hole taken through render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
folded steel lintel
no baseplate
folded steel lintel
Revision E
continuous baseplate
sealant to front of frame sealant to front and
back of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board
continuous ribbon of plaster adhesive, sealing joint between wall and board
Masonry: Cavity Wall Insulation: Full Fill3.10 Windows and doors, Folded Lintel
15mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK
N.B. in certain circumstances the lintel will require fire resistance - check with lintel manufacturer
weep hole taken through render
weep hole taken through render
weep hole taken through render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
insulation brought down to window opening and cavity closed
cavity tray with a minimum upstand of 140mm and stop ends
any lintel type can be used
Revision D
sealant to back of framesealant to front of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board
Masonry: Cavity Wall Insulation: Full Fill3.11 Windows and doors, Independent Lintel
weep hole taken through render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
sealant to front and back of sill
plan view
Revision E
continuous ribbon of plaster adhesive, sealing joint between wall and board
sealant to front and back of sill
Masonry: Cavity Wall Insulation: Full Fill3.12 Windows and doors, Jambs and sills
insulation between packing pieces
sealant to front of frame
section view
insulation between packing pieces
sealant to back of frame
continuous ribbon of plaster
adhesive, sealing joint between wall
and board
damp proof course
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
wall insulation continued at least 150mm below top of
floor insulation
Revision E
damp proof course
external ground level
Masonry: Cavity Wall Insulation: Full-Fill3.13 Ground Bearing Floor. Insulation Above Slab
vapour control layer under timber floor finish
damp proof membrane above or below slab
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
continuous ribbon of plaster adhesive, sealing joint between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
external ground level
Masonry: Cavity Wall Insulation: Full Fill3.14 Ground Bearing Floor, Insulation Below Slab
wall insulation continued at least 150mm below top of
floor insulation
damp proof course
damp proof membrane
Revision E
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
continuous ribbon of plaster adhesive, sealing joint between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision E
external ground level
wall insulation continued at least 150mm below top of
perimeter insulation
damp proof course
damp proof membrane
Cavity Wall Insulation: Full Fill3.15 Raft Foundation
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
continuous ribbon of plaster adhesive, sealing joint between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under timber floor finish
Revision E
external ground level
wall insulation continued at least 150mm below top of
floor insulation
damp proof course
damp proof membrane
Masonry: Cavity Wall Insulation: Full Fill3.16 In-situ Suspended Ground Floor Slab, Insulation above Slab
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around any screed
continuous ribbon of plaster adhesive, sealing joint between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision E
external ground level
wall insulation continued at least 150mm below top of
perimeter insulation
damp proof course
damp proof membrane
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around slab and any screed
Masonry: Cavity Wall Insulation: Full Fill3.17 In-situ Suspended Ground Floor Slab, Insulation Below Slab
dense blocks should not be used below slab
continuous ribbon of plaster adhesive, sealing joint between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under timber floor finish
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
Revision E
damp proof course
external ground level
wall insulation continued at least 150mm below top of
floor insulation damp proof membrane
solum
Masonry: Cavity Wall Insulation: Full Fill3.18 Concrete Beam and Block Suspended Ground Floor
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
continuous ribbon of plaster adhesive, sealing joint between wall and board
cavity barrier type sleeve through cavity
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
insulation directly under flooring - supported either on battens or on netting draped over joists and stapled at required depths
Revision E
damp proof courseexternal ground level
wall insulation continued at least 150mm below top of
floor insulation
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ²floor area
expanding foam and continuous sealant
20mm strip of perimeter insulation with thermal
conductivity ( value) not exceeding 0.025W/mK should be
installed between wall and last joist
solum
Masonry: Cavity Wall Insulation: Full Fill3.19 Timber Suspended Ground Floor
floor joist ends supported on joist hangers or using scarcement wall
continuous ribbon of plaster adhesive, sealing joint between wall and board
damp proof membrane
cavity barrier type sleeve through cavity
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plan view
Revision D
plan view
Masonry: Cavity Wall Insulation: Full Fill3.20 Separating Wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
wall insulation continued across floor zone
gaps between wall and floor sealed
Revision D
Masonry: Cavity Wall Insulation: Full Fill3.21 Concrete Intermediate Floor
continuous ribbon of plaster adhesive, sealing joint between wall and board
separating floors require additional layers and components to comply with Section 2: Fire and Section 5: Noise
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
Revision D
wall insulation continued across floor zone
Masonry: Cavity Wall Insulation: Full Fill3.22 Timber Intermediate Floor
separating floors require additional layers and components to comply with Section 2: Fire andSection 5: Noise
continuous ribbon of plaster adhesive, sealing joint between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plaster or plasterboard on dabs
inner leaf (block shown)
outer leaf (brick shown)
partial fill cavity wall insulation
Revision C
render finish if required/desired
4.00 Masonry: Cavity Wall Insulation: Partial Fill
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill4.01 Pitched Roof. Ventilated Roofspace. Eaves.
Revision D
proprietary cross flow ventilator to maintain
minimum 25mm air gap
lap roof and wall insulation, minimum 50mm thickness at narrowest pointconsider sequence of construction,
see supplementary guidance
roofing membrane
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required where the roof pitch is greater than 35° or the roof span is more than 10m
sarking board
ventilation gap equivilent to 10mm minimum continuous opening is
required where the roof pitch is below 15°
orventilation gap equivilent to
25mm minimum continuous opening is required where the
roof pitch is 15° or above
insect mesh should be installed
30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
Read in conjunction with Masonry: Cavity Wall Insulation : Partial Fill, Ventilated Loft, Gable.
restraint required for insulation, for example metal banding, wire
mesh or similar material, fixed between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial-Fill4.02 Pitched Roof. Ventilated Roofspace. Gable.
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Revision C
continue wall insulation to top of gable or stop wall insulation 270mm above bottom of ceiling tie
place loft insulation between last truss and gable wall
Read in conjunction withMasonry: External Wall InsulationPitched Roof, Ventilated Roofspace, Eaves
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
proprietary cross flow ventilator to maintain minimum
25mm air gaproofing membrane
inhabited space
where two insulation types are used together see supplementary guidance
Masonry: Cavity Wall Insulation - Partial Fill4.03 Pitched Roof, Ventilated Rafter Void, Eaves Revision E
ventilation gap equivalent to 25mm minimum continuous
opening
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required
50mm air gap
sarking board
lap roof and wall insulationminimum 50mm thickness at
narrowest point - considersequence of construction
see supplementary guidance
vapour control layer
30 minute fire resisting cavity barrier
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
Read in conjunction withMasonry: Cavity Wall Insulation: Partial FillPitched Roof, Ventilated Rafter Void, Gable
restraint required for insulation, for example metal banding, wire mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision DMasonry: Cavity Wall Insulation: Partial Fill4.04 Pitched Roof, Ventilated Rafter Void, Gable
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
50mm ventilation path over insulation
vapour control layer
where two insulation types are used together see supplementary guidance
sarking board
Read in conjunction withMasonry: Cavity Wall Insulation: Partial FillPitched Roof, Ventilated Rafter Void, Eaves
30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
lap roof and wall insulation, roof insulation to be
compressed between sarking and wall head
wall insulation should be taken up level with
top of gable
fill gaps at top of gable masonry with mortar to
form an even surface
roofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill4.05 Pitched Roof. Ventilated Batten Void (warm roof). Eaves.
Revision C
ventilation to batten void
30 minute fire resisting cavity barrier
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
support insulation between rafters on battens or clips
inhabited space
where two insulation types are used together see supplementary guidance
ventilation gap equivalent to 5mm minimum continuous opening is required at ridge rigid insulation as sarking
Read in conjunction withMasonry: Cavity Wall Insulation: Partial FillPitched Roof, Ventilated Batten Void (warm roof), Gable
proprietary over fascia ventilator
lap roof and wall insulationminimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
vapour permeable membrane(with a vapour resistance of no more
than 0.25 MN.s/g)
vapour control layer
30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
restraint required for insulation, for example
metal banding, wire mesh or similar
material, fixed between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane (with a vapour resistance of no more than 0.25 MN.s/g)
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Revision D
vapour control layer
insulation between rafters supported on battens or clips
ensure insulation is placed between gable wall and last rafter
Masonry: Cavity Wall Insulation - Partial Fill4.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction withMasonry: Cavity Wall Insulation - Partial FillPitched Roof, Ventilated Batten Void (warm roof), Eaves
where two insulation types are used together see supplementary guidance
rigid insulation as sarking
30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
lap roof and wall insulation, roof insulation to be
compressed between sarking and wall head
wall insulation should be taken up level with
top of gable
fill gaps at top of gable masonry with mortar to
form an even surface
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Revision D
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer
and sealed
fix full height blocking piece and tightly pack mineral wool
into void and under deck
consider sequence of construction, see supplementary
guidance
roofing membranevapour control layer
Masonry: Cavity Wall Insulation - Partial Fill4.07 Timber Flat Roof
30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
declevity piece
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
vapour control layer
Revision E
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer,
and sealed
minimum distance 300mm between top of edge
insulation and bottom of roof insulation
place 20mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK around parapet
flashing minimum 150mm above finish roof level
Masonry: Cavity Wall Insulation - Partial Fill4.08 Timber Flat Roof with Parapet
render or impervious cladding
declevity piece
roofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision C
sealant to back of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board
Masonry: Cavity Wall Insulation: Partial Fill4.09 Lintel at Window Head
note that the same principal applies at the head of doors
steel lintelcontinuous baseplate
steel lintelperforated baseplate
sealant to front and back of frame
sealant to front of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board
15mm strip of insulation with thermal conductivity (
value) not exceeding 0.025W/mK
N.B. in certain circumstances the lintel will require fire resistance - check with lintel manufacturer
N.B. in areas of extreme exposure, a cavity tray type damp proof course will be applied on top of the lintel - check with lintel manufacturer
weep hole taken through render
weep hole taken through render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial-Fill4.10 Windows and doors. Folded Lintel
sealant to back of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board
15mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK
Revision C
N.B. in certain circumstances the lintel will require fire resistance - check with lintel manufacturer
N.B. in areas of extreme exposure, a cavity tray type DPC will be applied on top of the lintel - check with lintel manufacturer
steel lintelsteel lintel with continuous base plate
sealant to front and back of frame
sealant to front of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board
weep hole taken through render
weep hole taken through render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial-Fill4.11 Windows and doors. Independent Lintel
any lintel types can be used
insulation brought down to window opening and cavity closed
cavity tray with minimum upstand of 140mm and stop ends
sealant to back of frame
weep hole taken through render
continuous ribbon of plaster adhesive sealing joint between wall and board
Revision B
sealant to front of frame
30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill4.12 Windows and doors. Jambs and sills
plan view
Revision D
sealant to front and back of sill
continuous ribbon of plaster adhesive, sealing joint between wall and board
sealant to front and back of sill
insulation brought to underside of sill and 30
minute fire resisting proprietary fire /
insulating cavity barrier incorporating damp proof
course
sealant to front of frame
insulation brought to window frame and 30 minute fire resisting proprietary fire /
insulating cavity barrier incorporating damp proof course
sealant to back of frame
continuous ribbon of plaster adhesive, sealing joint between
wall and board
section view
damp proof course
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
wall insulation continued at least 150mm below top of
floor insulation
Revision C
damp proof membrane above or below slab
damp proof course
external ground level
Masonry: Cavity Wall Insulation: Partial Fill4.13 Ground Bearing Floor. Insulation Above Slab
vapour control layer under timber floor finish
N.B. 20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
continuous ribbon of plaster adhesive, sealing joint between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill4.14 Ground Bearing Floor. Insulation Below Slab
external ground level
wall insulation continued at least 150mm below top of
floor insulation
damp proof course
damp proof membrane
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
continuous ribbon of plaster adhesive sealing joint between wall and wallboard
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial-Fill4.15 Raft Foundation
external ground level
wall insulation continued at least 150mm below top of
perimeter insulation
damp proof course
damp proof membrane
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
Revision D
continuous ribbon of plaster adhesive sealing joint between wall and wallboard
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill4.16 In-situ Suspended Ground Floor Slab, Insulation above Slab
vapour control layer under timber floor finish
external ground level
wall insulation continued at least 150mm below top of
floor insulation
damp proof course
damp proof membrane
Revision D
continuous ribbon of plaster adhesive sealing joint between wall and wallboard
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision C
external ground level
wall insulation continued at least 150mm below top of
perimeter insulation
damp proof course
damp proof membrane
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around slab and any screed
Masonry: Cavity Wall Insulation: Partial Fill4.17 In-situ Suspended Ground Floor Slab, Insulation Below Slab
dense blocks should not be used below slab
continuous ribbon of plaster adhesive sealing joint between wall and wallboard
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under timber floor finish
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
Revision C
damp proof course
external ground level
wall insulation continued at least 150mm below top of
floor insulation damp proof membrane
solum
Masonry: Cavity Wall Insulation: Partial Fill4.18 Concrete Beam and Block Suspended Ground Floor
continuous ribbon of plaster adhesive sealing joint between wall and board
cavity barrier type sleeve through cavity
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial-Fill4.19 Timber Suspended Ground Floor
insulation directly under flooring - supported either on battens or on netting draped over joists and stapled at required depths
damp proof courseexternal ground level
wall insulation continued at least 150mm below top of
floor insulation
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
flexible insulation/expanding foam and continuous sealant
20mm strip of perimeter insulation with thermal conductivity ( value)
not exceeding 0.025W/mK should be installed between wall and last joist
solum
floor joist ends supported on joist hangers or using scarcement wall
Revision B
continuous ribbon of plaster adhesive sealing joint
between wall and board
damp proof membrane
cavity barrier type sleeve through cavity
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill4.20 Separating Wall
plan view
Revision B
plan view
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
wall insulation continued across floor zone
gaps between wall and floor sealed
Revision B
Masonry: Cavity Wall Insulation: Partial Fill4.21 Concrete Intermediate Floor
continuous ribbon of plaster adhesive, sealing joint between wall and board
separating floors require additional layers and components to comply with Section 2: Fire andSection 5: Noise
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill4.22 Timber Intermediate Floor Revision B
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
separating floors require additional layers and components to comply with Section 2: Fire andSection 5: Noise
continuous ribbon of plaster adhesive, sealing joint between wall and board
wall insulation continued across floor zone
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plaster or plasterboard
outer leaf (brick shown)
internally applied insulation system (various fixing methods)
5.00 Masonry: Internal Wall InsulationRevision B
render finish if required/desired
inner leaf (block shown)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
proprietary cross flow ventilator to maintain
minimum 25mm air gap
lap roof and wall insulation, minimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
roofing membrane
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
ventilation gap equivilent to 10mm minimum continuous opening is
required where the roof pitch is below 15°
orventilation gap equivilent to
25mm minimum continuous opening is required where the
roof pitch is 15° or above
insect mesh should be installed
Revision C
Read in conjunction withMasonry: Internal Wall InsulationPitched Roof, Ventilated Roofspace, Gable
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required where the roof pitch is greater than 35° or the roof span is more than 10m
sarking board
30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
Masonry: Internal Wall Insulation5.01 Pitched Roof, Ventilated Roofspace, Eaves
restraint required for insulation, for example metal banding, wire mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
insulation between last truss and gable wall
Revision A
Read in conjunction withMasonry: Internal Wall InsulationPitched Roof, Ventilated Roofspace, Eaves
Masonry: Internal Wall Insulation5.02 Pitched Roof. Ventilated Roofspace. Gable.
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
30 minute fire resisting cavity barriercontinuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
proprietary cross flow ventilator to maintain minimum
25mm air gaproofing membrane
inhabited space
where two insulation types are used together see supplementary guidance
Revision C
Read in conjunction withMasonry: External Wall InsulationPitched Roof, Ventilated Rafter Void, Gable
ventilation to roofspace
sarking board
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required
lap roof and wall insulation, minimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
vapour control layer
ventilation gap equivilent to 25mm minimum continuous
opening
insect mesh should be installed
Masonry: Internal Wall Insulation5.03 Pitched Roof, Ventilated Rafter Void, Eaves
30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
50mm air gap
sarking board
restraint required for insulation, for example metal banding, wire mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Revision C
Read in conjunction withMasonry: Internal Wall InsulationPitched Roof, Ventilated Rafter Void, Eaves
50mm ventilation path over insulation
where two insulation types are used together see supplementary guidance
sarking board
Masonry: Internal Wall Insulation5.04 Pitched Roof. Ventilated Rafter Void. Gable.
lap roof and wall insulation, roof insulation to be
compressed between sarking and wall head
wall insulation should be taken up level with
top of gable
fill gaps at top of gable masonry with mortar to
form an even surface
roofing membrane
30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation5.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves.
ventilation to batten void
vapour control layer
proprietary over fascia ventilator
30 minute fire resistingcavity barrier
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
lap roof and wall insulationminimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
vapour permeable membrane (with a vapour resistance of no more than
0.25 MN.s/g)
support insulation between rafters on battens or clips
inhabited space
Revision C
Read in conjunction withMasonry: Internal Wall InsulationPitched Roof, Ventilated Batten Void (warm roof), Gable
where two insulation types are used together see supplementary guidance
ventilation gap equivalent to 5mm minimum continuous opening is required at ridge rigid insulation as sarking
30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
restraint required for insulation, for example
metal banding, wire mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision C
Masonry: Internal Wall Insulation5.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction withMasonry: Internal Wall InsulationPitched Roof, Ventilated Batten Void (warm roof), Eaves
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
vapour control layer
insulation between rafters supported on battens or clips
ensure insulation is placed between gable wall and last rafter
where two insulation types are used together see supplementary guidance
rigid insulation as sarking
vapour permeable membrane (with a vapour resistance of no more than 0.25 MN.s/g)
lap roof and wall insulation, roof insulation to be
compressed between sarking and wall head
fill gaps at top of gable masonry with mortar to
form an even surface
30 minute fire resisting cavity barrier (thin calcium silicate
board or similar)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Revision C
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer,
and sealed
fix full height blocking piece and tightly pack mineral wool
into void and under deck
consider sequence of construction, see supplementary
guidance
roofing membrane
vapour control layer
Masonry: Internal Wall Insulation5.07 Timber Flat Roof
declevity piece
30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
vapour control layer
Revision D
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer,
and sealed
minimum distance 300mm between top of edge
insulation and bottom of roof insulation
place 20mm strip of insulation with thermal conductivity (value) not exceeding 0.025W/mK around parapet
flashing minimum 150mm above finish roof level
Masonry: Internal Wall Insulation5.08 Timber Flat Roof with Parapet
render or impervious cladding
declevity piece
roofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation5.09 Lintel at Window Head.
Revision C
The same thermal principles apply at the head of doors
N.B. in certain circumstances the lintel will require fire resistance - check with lintel manufacturer
N.B. in areas of extreme exposure, a cavity tray type DPC will be applied on top of the lintel - check with lintel manufacturer
steel lintel
continuous baseplate
sealant to back of frame
sealant to front of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board
weep hole taken through render 15mm strip of insulation with
thermal conductivity ( value) not exceeding 0.025W/mK
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation5.10 Windows and doors, Folded Lintel
Revision C
The same thermal principles apply at the head of doors
folded steel lintel
continuous baseplate
sealant to back of frame
sealant to front of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board
N.B. in certain circumstances the lintel will require fire resistance - check with lintel manufacturer
N.B. in areas of extreme exposure, a cavity tray type DPC will be applied on top of the lintel - check with lintel manufacturer
15mm strip of insulation with thermal conductivity ( value)
not exceeding 0.025W/mK
weep hole taken through render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial-Fill5.11 Windows and doors. Jambs and sills
30 minute fire resisting proprietary
fire / insulating cavity barrier, incorporating
damp proof course
30 minute fire resisting proprietary fire / insulating cavity barrier, incorporating damp proof course
sealant to front of frame
plan View
section view
Revision D
wall insulation carried up to underside of sill
continuous ribbon of plaster adhesive, sealing joint between wall and board
sealant to back of frame
sealant to front and back of sill
damp proof course
continuous ribbon of plaster adhesive,
sealing joint between wall and board
15mm strip of insulation with thermal conductivity ( value) not exceeding
0.025W/mK
15mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation5.12 Ground Bearing Floor. Insulation Above Slab
external ground level
damp proof coursevapour control layer under timber floor finish
damp proof membrane above or below slab
Revision D
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
flexible insulation /expanding foam
continuous ribbon of plaster adhesive applied to perimeter of wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation5.13 Ground Bearing Floor. Insulation Below Slab
external ground level
damp proof course
damp proof membrane
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around slab and any screed
Revision D
flexible insulation /expanding foam
continuous ribbon of plaster adhesive applied to perimeter of wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation5.14 Raft Foundation
external ground level
damp proof course
damp proof membrane
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around slab and any screed
Revision D
flexible insulation /expanding foam
continuous ribbon of plaster adhesive applied to perimeter of wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation5.15 In-situ Suspended Ground Floor Slab Insulation above Slab
Revision D
external ground level
vapour control layer under timber floor finish
damp proof membrane
damp proof course
flexible insulation /expanding foam
continuous ribbon of plaster adhesive applied to perimeter of wall
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation5.16 Concrete Beam & Block Suspended Ground Floor
external ground level
vapour control layer under timber floor finish
damp proof course
damp proof membrane
Revision D
solum
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
flexible insulation /expanding foam
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
cavity barrier type sleeve through cavity
continuous ribbon of plaster adhesive applied to perimeter
of wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation5.17 Timber Suspended Ground Floor
insulation directly under flooring - supported either on battens or on netting draped over joists and stapled at required depths
external ground level solum sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
floor joist ends supported on joist hangers or using scarcement wall
Revision C
20mm strip of perimeter insulation with thermal
conductivity ( value) not exceeding 0.025W/mK
should be installed between wall and last joist
flexible insulation /expanding foam
continuous ribbon of plaster adhesive applied to perimeter of wall
cavity barrier type sleeve through cavity and cavity
tray type damp proof course locally over sleeve
damp proof membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation5.18 Separating Wall
Plan View
Revision C
damp proof course
continuous ribbon of plaster adhesive applied to perimeter of wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation5.19 Concrete Intermediate Floor
continuous ribbon of plaster adhesive, sealing joint between wall and board
gaps between wall and floor sealed
Revision C
insulation should be installed in cavity projecting minimum
100mm above and below floor zone (insulation may need to be
damp proof course faced in areas of severe exposure)
100mm
100mm
flexible insulation /expanding foam
continuous ribbon of plaster adhesive applied to perimeter of wall
separating floors require additional layers & components to comply with Section 2: Fire and Section 5: Noise
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation5.20 Timber Intermediate Floor
continuous ribbon of plaster adhesive, sealing joint between wall and boardseparating floors require additional layers & components to comply with Section 2: Fire andSection 5: Noise
Revision C
20mm strip of insulation with thermal conductivity ( value)
not exceeding 0.025W/mK continued accross floor zone
flexible insulation /expanding foam
continuous ribbon of plaster adhesive applied to perimeter of wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plasterboard
sheathing board
outer leaf (brick shown)
Revision B
render finish if required/desired
6.00 Timber Frame
vapour control layer
structural timber frame
insulation
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
cavity
stainless steel wall tie
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate insulation material in timber frame
Timber Frame6.01 Pitched Roof, Ventilated Roofspace, Eaves
proprietary cross flow ventilator to maintain
minimum 25mm air gap
lap roof and wall insulation, minimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
roofing membrane
ventilation gap equivilent to 10mm minimum continuous opening is
required where the roof pitch is above 15°
orventilation gap equivilent to
25mm minimum continuous opening is required where the
roof pitch is below 15°
insect mesh should be installed
Revision D
Read in conjunction withTimber FramePitched Roof, Ventilated Roofspace, Gable
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required where the roof pitch is greater than 35° or the roof span is more than 10m
sarking board
vapour control layer
restraint required for insulation, for example metal banding, wire
mesh or similar material, fixed between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Timber Frame6.02 Pitched Roof. Ventilated Roof Space. Gable
vapour control layer
loft insulation continued up to sheathing of spandrel
panel
cavity barrier giving 30 minute fire resistance
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
Revision C
Read in conjunction withTimber FramePitched Roof, Ventilated Roofspace, Eaves
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
30 minute fire resisting cavity barrier
proprietary cross flow ventilator to maintain minimum
25mm air gaproofing membrane
inhabited space
where two insulation types are used together see supplementary guidance
Timber Frame6.03 Pitched Roof, Ventilated Rafter Void, Eaves
Revision C
Read in conjunction withTimber FramePitched Roof, Ventilated Rafter Void, Gable
sarking board
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required
50mm air gap
lap roof and wall insulation, minimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
vapour control layer
ventilation gap equivilent to 25mm minimum continuous
opening
insect mesh should be installed vapour control layer
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate insulation material within timber frame
restraint required for insulation, for example metal banding, wire
mesh or similar material, fixed between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
differential movement gap sealedwith compressible foam or sealant
cavity barrier giving 30minute fire resistance
50mm ventilation path over insulationlap roof and wall insulation, roof
insulation to be compressed between sarking and timber frame
Revision C
Timber Frame6.04 Pitched Roof, Ventilated Rafter Void, Gable
Read in conjunction withTimber FramePitched Roof, Ventilated Rafter Void, Eaves
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
vapour control layer
sarking boardroofing membrane
where two insulation types are used together see supplementary guidance
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Timber Frame6.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves.
ventilation to batten void
vapour control layer
proprietary over fascia ventilator
30 minute fire resisting cavity barrier
lap roof and wall insulationminimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
vapour permeable membrane (with a vapour resistance of not more than
0.6 MN.s/g)
support insulation between rafters on netting, battens
or clips
inhabited space
Revision D
Read in conjunction withTimber FramePitched Roof, Ventilated Batten Void (warm roof), Gable
where two insulation types are used together see supplementary guidance
ventilation gap equivalent to 5mm minimum continuous opening is required at ridge to batten space
rigid insulation as sarking
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate insulation material within timber frame
vapour control layer
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)restraint required for
insulation, for example metal banding, wire
mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane (with a vapour resistance of no more than 0.25 MN.s/g)
ventilation to tile batten void
lap roof and wall insulation, roof insulation to be compressed between
sarking and timber frame
Revision C
vapour control layer
insulation between rafters supported on battens, clips or netting
Timber Frame6.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction withTimber FramePitched Roof, Ventilated Batten Void (warm roof), Eaves
where two insulation types are used together see supplementary guidance
rigid insulation as sarking
cavity barrier giving 30 minute fire resistance
vapour control layer
differential movement gap sealedwith compressible foam or sealant
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision D
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer,
and sealed
eaves - fix full height blocking piece and tightly pack mineral wool into void and under deck
verge - tightly pack mineral wool into void over wall and under
deck (not shown)
roofing membrane
vapour control layer
Timber Frame6.07 Timber Flat Roof
declevity piece
vapour control layer
cavity barrier
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
consider sequence of construction, see supplementary
guidance
differential movement gap sealedwith compressible foam or sealant
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision A
vapour control layer
Timber Frame6.08 Timber Flat Roof with Parapet
differential movement gap sealedwith compressible foam or sealant
cavity barrier giving 30 minute fire resistance
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer, and sealed
roofing membrane to be taken minimum 150mm above finished roof level
declevity piece
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
cavity barrier giving 30 minute
fire resistance
vapour control layer
Revision E
Timber Frame6.09 Lintel at Window Head
sealant to front of frame
sealant to front and back of frame
vapour permeable membrane (with a vapour
resistance of no more than 0.6 MN.s/g)
The same thermal principles apply at the head of doors.
steel lintel
vapour control layer
sealant to back of frame
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
N.B. in certain circumstances the lintel will require fire resistance - check with lintel manufacturer
N.B. in areas of extreme exposure, a cavity tray type DPC will be applied on top of the lintel - check with lintel manufacturer alternative for heavy duty lintel
10mm strip of insulation with thermal conductivity ( value) not exceeding 0.25W/mK
weep hole taken through render
weep hole taken through render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
cavity barrier giving 30 minute fire resistance
sealant to front and back of frame/sill
Plan View
Revision C
section view
Timber Frame6.10 Windows and doors, Jambs and sills
sealant to front of frame
sealant to back of frame
cavity barrier giving 30 minute fire resistance
damp proof course
damp proof course vapour control layer
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
vapour permeable membrane (with a vapour resistance of
no more than 0.6 MN.s/g)
vapour control layer
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision D
vapour control layer under timber floor finish
damp proof membrane above or below slab
damp proof course
external ground level
Timber Frame6.11 Ground Bearing Floor, Insulation Above Slab
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screedvapour permeable membrane
(with a vapour resistance of no more than 0.6 MN.s/g)
vapour control layer
perpend vent
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
external ground level
Timber Frame6.12 Ground Bearing Floor, Insulation Below Slab
damp proof course
damp proof membrane
Revision D
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
vapour permeable membrane (with a vapour resistance of
no more than 0.6 MN.s/g)vapour control layer
perpend vent
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under timber floor finish
external ground level
damp proof course
damp proof membrane
Revision E
Timber Frame6.13 Raft Foundation
vapour permeable membrane (with a vapour resistance of
no more than 0.6 MN.s/g) vapour control layer
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
perpend vent
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under timber floor finish
Revision D
external ground level
damp proof course
damp proof membrane
Timber Frame6.14 In-situ Suspended Ground Floor Slab. Insulation Above Slab
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
vapour permeable membrane (with a vapour resistance of
no more than 0.6 MN.s/g) vapour control layer
perpend vent
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under timber floor finish
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
Revision C
damp proof course
external ground level
damp proof membrane
solum
Timber Frame6.15 Concrete Beam and Block Ground Floor
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screedvapour permeable membrane
(with a vapour resistance of no more than 0.6 MN.s/g)
vapour control layer
cavity barrier type sleeve through cavity
perpend vent
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
insulation directly under flooring - supported either on battens or on netting draped over joists and stapled at required depths
Revision D
damp proof course
external ground levelsub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
expanding foam or continuous sealant
solum
Timber Frame6.16 Timber Suspended Ground Floor
vapour permeable membrane (with a vapour resistance of
no more than 0.6 MN.s/g)
vapour control layer
damp proof membrane
perpend vent
cavity barrier type sleeve through cavity
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Plan View
Revision D
Timber Frame6.17 Separating Wall
acoustic insulation not shown
cavity barriers giving 30 minute fire resistance, ensure cavity barriers are not breeched by inappropriate
insulation material in the timber frame alternative corner details,
see Timber Frame, Wall Junction
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)vapour control layer
flexible cavity barrier
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous bead of sealant applied to floor deck prior to
positioning of upper wall panel
Revision E
Timber Frame6.18 Timber Intermediate Floor
20mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK installed around floor perimeter
vapour control layervapour permeable membrane (with a vapour resistance of no more
than 0.6 MN.s/g)
cavity barriers giving 30 minute fire resistance
separating floors require additional layers and components to comply with Section 2: Fire and Section 5: Noise
perpend vent
sealant between skirting and floor
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plan view
alternative detail where required for structural reasons - insulation placed in void before wall panels are erected
standard corner detail - insulation
tucked into corner
Revision C
Timber Frame6.19 Wall Junction
vapour permeable membrane(with a vapour resistance of no more than 0.6 MN.s/g)
vapour control layer
cavity barriers with 30 minute fire resistance are not shown, ensure that those provided are not breeched by inappropriate insulation in the timber frame
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plasterboard
rigid insulated sheathing board
outer leaf (brick shown)
render finish if required/desired
7.00 Steel Frame
vapour control layer
structural light gauge steel frame
compressible mineral wool insulation
cavity
stainless steel wall tie in channelsfixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material
Steel Frame7.01 Pitched Roof, Ventilated Roofspace, Eaves
proprietary cross flow ventilator to maintain
minimum 25mm air gap
lap roof and wall insulation, minimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
roofing membrane
ventilation gap equivilent to 10mm minimum continuous opening is
required where the roof pitch is above 15°
orventilation gap equivilent to
25mm minimum continuous opening is required where the
roof pitch is below 15°
insect mesh should be installedRead in conjunction withWarm Steel FramePitched Roof, Ventilated Roofspace, Gable
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required where the roof pitch is greater than 35° or the roof span is more than 10m
sarking board
restraint required for insulation, for example metal banding, wire
mesh or similar material, fixed between rafters
mineral wool insulation between the studs in addition to the rigid board over. This insulation must be tightly packed and be in direct contact with the rigid board
stainless steel wall tie in channelsfixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Steel Frame7.02 Pitched Roof. Ventilated Roof Space. Gable
loft insulation continued up to inner face of the rigid
sheathing insulant
Read in conjunction withSteel FramePitched Roof, Ventilated Roofspace, Eaves
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material
mineral wool insulation between the studs in addition to the rigid board over.This insulation must be tightly packed and be in direct contact with the rigid board
vapour control layer stainless steel wall tie in channelsfixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
30 minute fire resisting cavity barrier
proprietary cross flow ventilator to maintain minimum
25mm air gaproofing membrane
inhabited space
where two insulation types are used together see supplementary guidance
Steel Frame7.03 Pitched Roof, Ventilated Rafter Void, Eaves
Read in conjunction withSteel FramePitched Roof, Ventilated Rafter Void, Gable
sarking board
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required
50mm air gap
lap roof and wall insulation, minimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
vapour control layer
ventilation gap equivilent to 25mm minimum continuous
opening
insect mesh should be installed
restraint required for insulation, for example metal banding, wire mesh or similar material, fixed
between rafters
mineral wool insulation between the studs in addition to the rigid board over.This insulation must be tightly packed and be in direct contact with the rigid board
vapour control layer
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material
stainless steel wall tie in channelsfixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
differential movement gap sealedwith compressible foam or sealant
50mm ventilation path over insulationlap roof and wall insulation, roof
insulation to be compressed between sarking and timber frame
Steel Frame7.04 Pitched Roof, Ventilated Rafter Void, Gable
Read in conjunction withSteel FramePitched Roof, Ventilated Rafter Void, Eaves
sarking boardroofing membrane
where two insulation types are used together see supplementary guidance
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material
mineral wool insulation between the studs in addition to the rigid board over.This insulation must be tightly packed and be in direct contact with the rigid board
vapour control layer
stainless steel wall tie in channelsfixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Steel Frame7.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves.
ventilation to batten void
proprietary over fascia ventilator
lap roof and wall insulationminimum 50mm thickness at
narrowest pointconsider sequence of construction,
see supplementary guidance
vapour permeable membrane (with a vapour resistance of not more than
0.6 MN.s/g)
support insulation between rafters on netting, battens
or clips
inhabited space
Read in conjunction withSteel FramePitched Roof, Ventilated Batten Void (warm roof), Gable
where two insulation types are used together see supplementary guidance
ventilation gap equivalent to 5mm minimum continuous opening is required at ridge to batten space
rigid insulation as sarking
restraint required for insulation, for example
metal banding, wire mesh or similar material, fixed
between rafters
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation materialmineral wool insulation between the studs in addition to the rigid board over.This insulation must be tightly packed and be in direct contact with the rigid board
vapour control layer
30 minute fire resisting cavity barrier
vapour control layer
stainless steel wall tie in channels
fixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane (with a vapour resistance of no more than 0.25 MN.s/g)
ventilation to tile batten void
lap roof and wall insulation, roof insulation to be compressed between
sarking and frame
insulation between rafters supported on battens, clips or netting
Steel Frame7.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction withSteel FramePitched Roof, Ventilated Batten Void (warm roof), Eaves
where two insulation types are used together see supplementary guidance
rigid insulation as sarking
vapour control layer
differential movement gap sealedwith compressible foam or sealant
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material
mineral wool insulation between the studs in addition to the rigid board over. This insulation must be tightly packed and be in direct contact with the rigid board
vapour control layer
stainless steel wall tie in channelsfixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer,
and sealed
eaves - fix full height blocking piece and tightly pack mineral wool into void and under deck
verge - tightly pack mineral wool into void over wall and under
deck (not shown)
roofing membrane
vapour control layer
Steel Frame7.07 Timber Flat Roof
declevity piece
consider sequence of construction, see supplementary
guidance
differential movement gap sealedwith compressible foam or sealant
mineral wool insulation between the studs in addition to the rigid board over.This insulation must be tightly packed and be in direct contact with the rigid board
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material
vapour control layer
stainless steel wall tie in channelsfixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Steel Frame7.08 Timber Flat Roof with Parapet
differential movement gap sealedwith compressible foam or sealant
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer, and sealed
roofing membrane to be taken minimum 150mm above finished roof level
declevity piececavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material
mineral wool insulation between the studs in addition to the rigid board over.This insulation must be tightly packed and be in direct contact with the rigid board
vapour control layer
insulated upstand having a minimum R value of 0.75 m2K/W supported on a sheathing board around the parapet
tightly packed compressible insulant between the wall studs above the level of the roof deck
stainless steel wall tie in channelsfixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
proprietary cavity barriergiving 30 minute fireresistance
vapour control layer
Steel Frame7.09 Lintel at Window Head
sealant to frontof frame
sealant to front and backof frame
The same thermal principles apply at the head of doors.
steel lintel
vapour control layer
sealant to back of frameN.B. in certaincircumstances the lintel willrequire fire resistance -check with lintelmanufacturer
N.B. in areas of extremeexposure, a cavity traytype DPC will be applied ontop of the lintel - checkwith lintel manufacturer alternative for heavy duty lintel
weep hole takenthrough render
weep hole takenthrough render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to theintroduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
proprietary cavity barriergiving 30 minute fire
resistance
sealant to front and back offrame/sill
Plan View
section view
Steel Frame7.10 Windows and doors, Jambs and sills
sealant to front of frame
sealant to back offrame
proprietary cavity barriergiving 30 minute fire
resistance
damp proof course
damp proof course vapour control layer
vapour control layer
stainless steel wall tiein channels
fixed to stud structurethrough insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to theintroduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under timber floor finish
damp proof membrane above or below slab
damp proof course
external ground level
Steel Frame7.11 Ground Bearing Floor, Insulation Above Slab
vapour control layer
perpend vent
seal between the wall and floor membrane with a flexible sealant or seal the gap between the skirting board and floor using a flexible sealant
the wall insulation installed below the wall DPC must be
fit for purpose with regards to water absorption
stainless steel wall tie in channelsfixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Steel Frame7.12 Ground Bearing Floor, Insulation Below Slab
damp proof course
external ground level
perpend vent
seal between the wall and floor membrane with a flexible sealant or seal the gap between the skirting board and floor using a flexible sealant
the wall insulation installed below the wall DPC must be
fit for purpose with regards to water absorption
damp proof membrane
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
vapour control layer
stainless steel wall tie in channelsfixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under timber floor finish
external ground level
damp proof course
damp proof membrane
Steel Frame7.13 Raft Foundation
vapour control layer
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
perpend vent
the wall insulation installed below the wall DPC must be fit for
purpose with regards to water absorption
seal between the wall and floor membrane with a flexible sealant or seal the gap between the skirting board and floor using a flexible sealant
stainless steel wall tie in channelsfixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Steel Frame7.14 In-situ Suspended Ground Floor Slab. Insulation Above Slab
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
vapour control layer under timber floor finish
damp proof membrane
damp proof course
external ground level
vapour control layer
perpend vent
Seal between the wall and floor membrane with a flexible sealant or seal the gap between the skirting board and floor using a flexible sealant
the wall insulation installed below the wall DPC must be fit
for purpose with regards to water absorption
stainless steel wall tie in channelsfixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under timber floor finish
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
damp proof course
external ground level
damp proof membrane
solum
Steel Frame7.15 Concrete Beam and Block Ground Floor
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
cavity barrier type sleeve through cavity
perpend vent
vapour control layer
seal between the wall and floor membrane with a flexible sealant or seal the gap between the skirting board and floor using a flexible sealant
the wall insulation installed below the wall DPC must be
fit for purpose with regards to water absorption
stainless steel wall tie in channelsfixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Steel Frame7.16 Steel Suspended Ground Floor
vapour control layer under timber floor finish
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
insulating block
external ground level solum
cavity barrier type sleeve through cavity
perpend vent
vapour control layer
seal the gap between the skirting board and floor using a flexible sealantthe wall insulation installed
below the wall DPC must be fit for purpose with regards
to water absorptionoptional mineral wool insulation directly under flooring
damp proof membrane
damp proof course
rigid insulation fixed to the underside of the joists
light steel joist with bitumen coated ends built onto masonry wall
stainless steel wall tie in channelsfixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Plan View
Steel frame7.17 Separating Wall
acoustic insulation not shown
cavity barriers giving 30 minute fire resistance, ensure cavity barriers are not breeched by inappropriate
insulation material in the steel frame
vapour control layer
stainless steel wall tie in channelsfixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continue the wall insulation across the floor abutment
zone
Steel Frame7.18 Steel Intermediate Floor
vapour control layer
cavity barriers giving 30 minute fire resistance
separating floors require additional layers and components to comply with Section 2: Fire and Section 5: Noise
perpend vent
sealant between skirting and floor
stainless steel wall tie in channelsfixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plan view
Steel Frame7.19 Wall Junction
vapour control layer
cavity barriers with 30 minute fire resistance are not shown, ensure that those provided are not breached by inappropriate rigid sheathing insulation material
corner detail using standard sized studs - insulation placed in void before second stud is erected
alternative detail using increased stud size - insulation fitted within the stud
vapour control layer
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
ventilation to rafter voidconsideration to be given
to maintenance of circulation
roofing membrane
sarking board
vapour control layer
where two insulation types are used together see supplementary guidance
window frame to be level or lower than top of
counterbatten to minimise thermal bridging
push flexible insulation into gap between frame and tile
batten
10mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK to be installed around reveals
General Arrangements8.02 Roof Window, Ventilated Rafter Void
pack with insulation
proprietary flashing
proprietary drainage gutter
side gutter of proprietary flashing
proprietary flashing
Revision B
For proprietary details consult roof window manufacturer
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
General Arrangements8.03 Roof Window. Ventilated batten Void (Warm Roof)
ventilation to batten void
vapour permeable membrane (with a vapour resistance of not more than
0.25MN.s/g)rigid insulation as sarking
vapour control layer
where two insulation types are used together see supplementary guidance
push flexible insulation into gap between frame and tile
batten
10mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK to be installed around reveals
proprietary flashing
proprietary drainage gutter
proprietary flashing
pack with insulation
Revision A
window frame to be level or lower than top of
counterbatten to minimise thermal bridging
side gutter of proprietary flashing
For proprietary details consult roof window manufacturer
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
General Arrangements8.04 Loft Hatch
ensure loft hatch / proprietary hatch is fully draught sealed
counterbearers and boarding should be provided if access to loft is required
U-value through loft hatch should not exceed 0.35W/m ² K
revision B
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under timber floor finishdamp proof membrane above or below slab
damp proof course stepped down locally at entrance
continue floor insulation up to back of sill
General Arrangements8.05 Level Threshold, Insulation above Slab, Ramped Access
proprietary weather bar seal for air leakage / rain penetration
revision D
ramped access
surrounding ground level
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
damp proof membrane
damp proof course stepped down locally at entrance
continue floor insulation up to back of sill
proprietary weather bar seal for air leakage / rain penetrationfor sill types other than timber / plastic / composite also include a perimeter of insulation to the rear of sill, minimum 20mm thick, with thermal conductivity (value) not exceeding 0.025W/mK
General Arrangements8.06 Level Threshold, Insulation below Slab, Ramped Access
revision C
ramped access
surrounding ground level
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
General Arrangements8.07 Level Threshold, Timber Floor, Ramped Access
insert 20mm insulation with thermal conductivity ( value) not
exceeding 0.025W/mK against inner leaf and back of sill
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
solum
surrounding ground level
proprietary weather bar seal for air leakage and rain penetration
revision C
ramped access
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
General Arrangements8.08 Ceilings, Service Penetrations
seal all service penetrations with expanding foam or other suitable sealant
for large voids mineral wool or other material may be used to provide a backing for the sealant
similar arrangements should be adopted for service penetrations through ground floors
N.B. insulation material has been omitted for clarity
revision B
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
WWW.SBSA.GOV.UK