Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study...

122
1 Certified Door Dealer Consultant Section 5 Commercial Rolling and Rolling Steel Fire Door Technical Essentials Copyright© 2018 • Institute of Door Dealer Education and Accreditation All rights reserved • Version 102018 Rev 0 www.dooreducation.com

Transcript of Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study...

Page 1: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

1

Certified Door Dealer Consultant Section 5

Commercial Rolling and Rolling Steel Fire Door Technical Essentials

Copyright© 2018 • Institute of Door Dealer Education and Accreditation All rights reserved • Version 102018 Rev 0

www.dooreducation.com

Page 2: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

2

Table of ContentsSection One: An Introduction to Rolling Doors

History of Rolling Doors ........................................... 4 The Importance of Fire Walls and Fire Doors ........... 5 Industry Organizations ............................................. 6

Section Two: Understanding Codes and Standards

Published Standards .............................................. 10 Building Codes ...................................................... 10 Licensing ............................................................... 11 NEMA Standards ................................................... 11 Seismic Qualification ............................................. 11 Wind Load Requirements ...................................... 12

Understanding Loads Exerted by Rolling Doors ............................................................. 14 Rolling Door Operation under Wind Load Conditions ..................................................... 15 Rolling Doors and Hurricanes or High Wind Events ........................................................... 16

Fire Rating ............................................................. 17 Smoke Control ....................................................... 18 Final Approval........................................................ 19 Insulation

R-Value ......................................................... 19 K-Factor ......................................................... 19 U-Factor ........................................................ 19 Method of Determining Thermal Performance .................................................. 20 Flame Spread ................................................ 20 Smoke Developed ......................................... 20 Sound Transmission ...................................... 20

Section Three: Rolling Door Components

Materials and Finishes Steel Sheet Metal Components ..................... 21 Steel Components ......................................... 21 Stainless Steel Components .......................... 21 Most Common Stainless-Steel Finishes ......... 21 Aluminum Finishes ........................................ 22

Typical Rolling Door Components Curtains ......................................................... 24

Perforated Slats ..................................... 25 Fenestrated Slats ................................... 25 Vision Slats ............................................ 25 Grille Curtains ........................................ 26 Endlocks/Windlocks ............................... 26

Guides ........................................................... 26 Fire Door Guide Expansion Clearance ... 28

Bottom Bars ................................................... 29 Barrel ............................................................. 29

Counterbalance Mechanism .................. 30 Cycles .................................................... 30

Brackets Operating Mechanism ............................ 31 Tension Wheel ....................................... 32 Inside Tension Device ............................ 32 Compound Tension Device .................... 32 Inertia Brake .......................................... 33

Hoods ............................................................ 34 Governors ...................................................... 34 Sills and Countertops ..................................... 35 Options and Accessories

Locks ..................................................... 36 Weather Seals ....................................... 37 Wearstrips ............................................. 37 Exterior Mounted Doors ......................... 37 Fascia Panel .......................................... 37

ANSI/DASMA 203 Standard for Non-Fire Rated Rolling Doors ............ 38 ANSI/DASMA 204 Standard for Fire Rated Rolling Door Assemblies .. 42

Section Four: Types of Rolling Doors Rolling Service Door .............................................. 46 Rolling Counter Door ............................................. 46 Rolling Grilles ........................................................ 46 Types of Fire Rated Rolling Doors

Rolling Fire Door.................................... 47

Rolling Counter Fire Door ...................... 47

Service Counter Fire Door ..................... 47

Conveyor Openings ............................... 47

Specialty Applications

Pass Door ............................................. 48

Wood Rolling Doors ............................... 48

Combination Doors ................................ 49

Sloped Bottom Bar ................................ 49

Side Coiling Doors ................................. 49

Side Folding Doors ................................ 49

Integral Frame Doors ............................. 49

Sheet Doors .......................................... 50

Horizontal Doors .................................... 50

High Performance Doors ....................... 50

Crane-way Doors................................... 50

Mullions ................................................. 50

Section Five: Methods of Operation

Manual Push-Up Operation ................................... 52

Manual Chain Hoist Operation

Direct Drive Chain Hoists ....................... 53

Reduced Drive Chain Hoists .................. 53

Compound Reduction Chain Hoists ....... 53

Chain Hoist Mounting Locations ............ 54

Manual Hand Crank Operation .............................. 54

Electric Operators

Automatic Operators .............................. 55

Operator Usage ..................................... 55

Operator Size ........................................ 56

Operator Mounting Locations ................. 56

Emergency Egress ................................ 58

Electric Operator compliance with

UL 325................................................... 58

Environmental Considerations and NEMA

Standards .............................................. 60

Access Control Selection ....................... 60

Control Wiring on the Operator .............. 61

Door Operator Access Controls

Digital Keypads ..................................... 61

Stand-Alone Card Access ...................... 61

Door Receivers ...................................... 61

Radio Transmitters ................................ 62

Control Stations ..................................... 62

Automated Access Control .................... 63

Safety Accessories

Selection ............................................... 64

Sensing Devices

Electric Sensing Edge .................... 64

Air Wave Sensing Edge ................. 65

Pneumatic Sensing Edge............... 65

Non-Contact Sensing Edge ........... 65

Optical Sensing Edge .................... 65

Photoelectric Sensors .................... 65

Take-up Reel ................................. 66

Coil Cord ....................................... 66

Wireless Edge Transmitter ............. 66

Page 3: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

3

Section Six: Automatic Closing Devices

Rolling Fire Door Release Theory Push-Up Fire Doors ............................... 67

Chain, Crank or Motor Operated Fire

Doors ..................................................... 67

Rolling Fire Door Resetting Theory Push-Up Fire Doors ............................... 67

Chain, Crank or Motor Operated Fire

Doors ..................................................... 68

Automatic Closing .................................................. 68 Non-Spring Release Fire Door Operators .............. 68 Floor-Level Disconnect .......................................... 69 Release Devices

Fusible Link ........................................... 70

Sash Chain and Cable ........................... 71

Closing Speed ....................................... 71

Basic Electro-Mechanical Release

Device ................................................... 71

Electro-Mechanical Release Device with

Battery Back-Up ..................................... 72

Electro-Mechanical Release Device with

Battery Back-up and Motor Controller .... 72

Motor Controlled Release ...................... 72

Motor Controlled Release with Battery

Back-Up Non-Spring Release ................ 72

Detectors Smoke Detectors ................................... 73

Heat Detector......................................... 73

End of Line Device ................................. 73

Warning Devices .................................... 74

Location ................................................. 74

Section Seven: Obtaining and Installing the Correct Door

The Bid Specifications Rolling Door Specifications .................... 75

Ordering the Door .................................. 76

Receiving the Door ................................ 77

Rolling Door Installation Instructions Getting Started ....................................... 77

Site Inspection ....................................... 77

Assessing the Opening .......................... 78

Sizing the Opening................................. 78

Headroom Requirements ....................... 78

Job Site Organization ............................. 78

Tools and Equipment

Tool List ......................................... 79

Power Tools ................................... 79

Truck Inventory .............................. 79

Guide Installation ................................... 80

Wall Types and Mounting

Concrete Walls .............................. 80

Masonry Walls ............................... 81

Steel .............................................. 81

Stud Mounted Drywall .................... 81

Wood Walls.................................... 81

Tube Mounted Doors ..................... 81

Fire Door Jamb Construction ......... 82

Preparing the Barrel ............................... 82

Attaching Curtain to Barrel Assembly

Curtain Rolled on Barrel on Floor ... 83

Sling the Curtain ............................ 83

Installing the Tension Wheel .................. 84

Applying Tension ................................... 84

Inside Tension Holder/Wheel ......... 85

Compound Tension Wheel ............. 85

Operating Mechanism Assembly ........... 85

Hood Installation .................................... 85

Final Assembly ...................................... 86

Inspection and Drop Testing of Fire

Doors .................................................... 86

Miscellaneous Final Checklist ................ 88

Section Eight: Installation Instructions for Electric Operators

Important Safety Precautions ................................ 89

Preliminary Precautions ......................................... 90

Mounting Operator Support Plate .......................... 90

Mounting Operator ................................................ 90

Manual Operation of Electric Operator................... 91

Setting the Limits

Electronic Limit Adjustment.................... 92

Mechanical Limit Adjustment ................. 92

Control Wiring

Wiring Type ........................................... 92

Special Control Wiring ........................... 93

Locating the Control Station .................................. 93

Clutch Adjustment ................................................. 93

Brake Adjustment .................................................. 94

Test the System .................................................... 94

Section Nine: Service and Operation of Rolling Doors

Fire Door Repairs .................................................. 95 Servicing an Existing Rolling Door ......................... 96 Relocating an Existing Rolling Fire Door ................ 96 Safe Operation of Rolling Doors ............................ 98 Floor Level Disconnect Operation .......................... 99 Maintenance and Troubleshooting

Door and Operator Maintenance Schedule ............................................. 101 Troubleshooting Rolling Doors ............. 102 Troubleshooting Operators .................. 103 Electrical Procedures ........................... 105 Conclusion .......................................... 105

Section Ten: Glossary of Terms ....................................... 106 Section Eleven: DASMA Standards and Technical Data Sheets ................................................................................ 118

Page 4: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

4

Section One

An Introduction to Rolling DoorsThis study guide has been created by the Institute of Door Dealer Education and Accreditation as part of its goal to establish the door systems industry as a profession, and to recognize the skilled individuals who work within the industry as professional technicians. This is the fundamental objective of the IDEA programs, and all other professional designation courses offered by IDEA. Although it is intended that all students will learn some valuable new concepts in studying the curriculum, it is essential that each applicant begin the process with a broad base of knowledge and experience in the installation and service of rolling door products and accessories. Why is all this worth your time and energy? A professional can be defined as one possessing a high degree of skill or expertise. Individuals trained and experienced in installing, servicing or repairing rolling doors, operators and accessories meet that definition. Most people engaged in the door systems industry on a full-time basis would agree that they should be viewed as professionals. However, it is just as important that end-users and the general public share in that view. Professionalism goes beyond the pure technical knowledge of an industry’s practitioners. Professionals bring additional qualities to the industry: customer relations, safe work practices, leadership among colleagues, communication skills, and a comprehensive understanding of the industry and the organizations that support it. This program is intended to cover all aspects of commercial rolling doors, operators, and accessories. Specialty options and door types, such as very large custom rolling doors, sheet

doors and high-performance doors, are outside of the scope of this study guide. These doors have a specialized set of requirements and require a highly technical and specialized knowledge.

History of Rolling Doors

Providing cover, security, and protection from the elements has been a part of mankind’s history. From the use of animal hides to cover cave dwellings to the use of wood and other available raw materials for any other conceivable purpose, doors, access and security, are fundamental to human existence. As time marched on, millennia of bartering systems emerged into organized commerce, creating industries and businesses that transformed rural, agricultural lifestyles into urban industrial centers. Since the industrial revolution, a practical and economical means of access and security was in need. Rolling doors were a very good way of securing and opening commercial facilities. The cost and clearances required to install these products limited their use primarily to the commercial market. The formation of an industry providing door and access systems is a relatively recent development. In modern history, the first commercial doors were swinging and sliding. The swing door was manufactured of wood and made in various designs and styles to complement different architectural requirements. Since the design was simple and could be made by the typical carpenter on the jobsite, this became the standard for many years, even centuries.

Page 5: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

5

Swing type doors served an important purpose in the early 20th Century, but as commerce continued to develop, improvements were made. Swing type doors were cumbersome, did not work well over time, required constant cutting as the doors sagged and were especially troublesome in snow. The first company to produce the interlocking slat rolling steel door was founded in Columbus, Ohio in 1895. These doors solved many of the inherent issues with swing type doors and set the stage for the development of the rolling door industry. As time moved on, the rolling door grew in popularly. More and more companies saw the advantages of this invention and sought individuals to install this new product. Different manufacturing techniques were developed, and options were introduced that enhanced the quality, installation, and appearance of the doors. This innovation has continued unabated to this day. Early installing dealers had a limited market. It took many years for buildings to evolve to accommodate this style of door and for existing doors to reach their expected lives. As more doors were sold, the market expanded, more installing dealers entered the field. Today this still holds true as the commercial market continues to grow. Rolling doors are only a part of the commercial market today, as sectional doors and a variety of specialty doors have been designed to fit a diversity of applications. As a result, more specialized, skilled workers are required due to the growing diversity and complexity of the products. The door industry has grown to such an extent that door manufacturers have expanded on a global scale. Additionally, suppliers and vendors of door parts and accessories have emerged as an equally important segment of the industry. Weatherstripping, springs, hardware, windows, electrical operators and many other related products have grown proportionately with the demand for commercial doors. More variations, styles, applications and designs are continually

expanding. This study guide will focus on the rolling door segment of the commercial market.

The Importance of Fire Walls and Fire Doors

One of the basic principles of firefighting is confinement. By establishing compartments, the damage caused by a fire can be minimized but to do this, the entire building must be taken into account. Containment begins with the walls, ceilings and floors surrounding the space where a fire starts. Building codes specify the degree of fire protection required by these building components in accordance with the degree of hazard represented by the occupancy, the type of building construction, and the function served. Standard fire tests were developed for judging the fire resistance of various building materials, combinations of building materials and structural assemblies. Based on these tests, the concept of a firewall was born. But when was the last time that you saw a wall or an entire building without any openings in it? What good is the wall if there are unprotected openings that will allow the easy passage of fire and hot gasses? This led to the next level of containment – the protection of openings. While firewalls and fire doors serve several functions, the primary function is to act as a fire barrier and to protect openings and enclosures against the spread of fire and hot gasses within buildings or from an external source. This is accomplished by using specific products that have been designed, tested and manufactured for this primary reason. As a result, standard fire tests were developed in order to rate and examine products to ensure that they 1) prevent the passage of heat, flame,

Page 6: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

6

hot gasses and burning projectiles: 2) maintain their ability to support anticipated loads; 3) resist temperature transmission through the assembly (applies to firewalls only); and 4) to withstand the impact and erosion effects of debris. Firewalls and fire doors are found in all types of industrial, commercial and institutional applications. Additionally, fire doors can be utilized in certain residential applications, such as in row housing developments. They are an integral component in the overall fire protection plan of a facility. They are used to separate buildings into smaller compartments which help control the spread of fire and limit the fire area. They are counted on to act as a physical barrier and prevent the total destruction of facilities and loss of life when all other means of fire protection are not operational. In addition to serving as fire barriers, fire doors allow for vehicular, conveyor and foot traffic through wall openings that are not a required means of egress. The ability of a fire door to function as a fire barrier is highly dependent on their reliability to close automatically upon activation of a detection device. The effectiveness of the entire assembly could be compromised if any component is omitted, improperly installed, improperly maintained or replaced by one of substandard quality. Fire doors are an important item in the fire protection plan of a facility. When properly installed, maintained and regularly tested, they have demonstrated significantly improved performance compared to fire doors that have not received this attention. This plays a critical role in their ability to function properly in order to protect lives and property in fire situations.

Industry Organizations

The door and operator industry can be segmented into a number of distinct entities. The major groups are described below. Door & Access Systems Manufacturers’ Association (DASMA) is North America’s leading trade association of manufacturers of garage doors, rolling doors, high performance doors, garage door operators, vehicular gate operators and access control products. Formed in 1996, DASMA member companies manufacture products sold in the United States, Canada and more than 70 other countries worldwide. DASMA members produce more than 95 percent of the U. S. market for the door and access systems industry.

www.dasma.com

International Door Association (IDA), the industry’s authoritative voice to dealers, was formed in 1995 with the consolidation of the Door & Operator Dealers Association and the Far West Garage Door Association. IDA is the industry network for professional door and operator dealers and installers, along with their suppliers. While IDA represents the entire door and operator industry by promoting the use of professional dealers and installers, it is a membership driven association, relying on the input and feedback of its members to create and deliver programs of value.

www.doors.org

Page 7: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

7

Page 8: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

8

IDA Affiliate Organizations IDA maintains an alliance with other door systems industry organizations, known as IDA Affiliates. These organizations are independent associations involved in a variety of educational, training and social activities. Many companies maintain membership in more than one of these associations, as well as with IDA. Each group has its own board of directors and annual activities plan. The IDA Affiliates are: Australian Garage Door Association California Operator and Door Association Canadian Door Institute Central States Door Dealers Association (U. S. Midwest) Garage Door Association of Arizona Michigan Door and Operator Dealers Association Northeast Garage Door Association Northwest Door & Operator Association (Pacific Northwest) Professional Door Association of New England

Institute of Door Dealer Education and Accreditation (IDEA): A non-profit educational foundation established by ARDI, DASMA and IDA to provide professional door, gate and operator dealers with the knowledge and skills required to be competitive in today’s rapidly changing business environment. IDEA’s goals are to provide educational resources necessary to develop and maintain a successful business, and to validate and accredit those door and operator dealers whose standards meet IDEA’s demanding criteria of business excellence. ARDI and DASMA have since merged, leaving IDA and DASMA as the sponsoring organizations.

Institute of Door Dealer Education and Accreditation P.O. Box 236 West Milton, OH 45383 Tel: (937) 698-1027 www.dooreducation.com

American Fence Association (AFA): A trade association representing the fence, deck and railing industries in the United States and Canada. Founded in 1962, AFA, with its 31-member chapters, offer educational and certification programs, along with networking opportunities. AFA played the major role in developing the curriculum on which the IDEA Automated Gate Operator Installer Certification program is based and continues to play a role in the maintenance and periodic updates of the curriculum. AFA and its chapters also host certification testing opportunities for automated gate operator installers. American National Standards Institute (ANSI): A private, non-profit organization that oversees the development of voluntary consensus standards for products, services, processes, systems and personnel in the United States. ANSI also coordinates U. S. standards with international standards so that American products can be used worldwide. The organization facilitates the development of American National Standards by accrediting the procedures for organizations who work cooperatively to develop voluntary national consensus standards. Occupational Safety and Health Administration (OSHA): Created by the Occupational Safety and Health Act of 1970, OSHA promulgates and enforces safety and health standards in the workplace and provides consultative services to businesses. OSHA regulations impact virtually every job site in America.

Page 9: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

9

Underwriters Laboratories ® (UL): An independent product safety certification organization, UL tests products and writes standards for safety. UL tests more than 19,000 types of products, components, materials and systems each year. UL is an important organization to the door and access systems industry, due to UL 325 – Standard for Door, Drapery, Gate, Louvre, and Window Operator Systems, which sets forth safety performance requirements for door and gate operator systems. National Fire Protection Association (NFPA): A non-profit organization founded in 1896, NFPA’s mission is to reduce the worldwide burden of fire and other hazards on the quality of life, by providing and advocating consensus codes and standards, research, training and education. NFPA is the world’s leading advocate for fire prevention and an authoritative source on public safety. This organization is important to the fire door industry due to NFPA-80, Standard for Fire Doors and Other Opening Protectives. NFPA-80 regulates the installation and maintenance of door systems used to protect openings in walls, floors and ceilings against the spread of fire and smoke. Consumer Product Safety Commission (CPSC): A federal agency charged with protecting the public from unreasonable risks of serious injury or death from thousands of types of consumer products under the agency’s jurisdiction. The CPSC is committed to protecting consumers from products that pose a fire, electrical, chemical or mechanical hazard or can injure children. The CPSC’s work to ensure the safety of consumer products includes door and access systems.

FM Approvals: An enterprise of FM Global, provides independent third-party certification of products for manufacturers. FM Approvals tests property loss prevention products and certifies those that meet rigorous loss prevention standards. International Building Code (IBC): A model building code developed by the International Code Council (ICC), the International Building Code has been adopted throughout most of the United States. A large portion of the IBC deals with fire prevention. It addresses fire prevention regarding construction and design and fire prevention in regard to the operation of a completed and occupied building. The IBC applies to all structures in areas where it has been adopted, except in one and two-family dwellings. Canadian Standards Association (CSA): A not-for-profit membership-based association serving business, industry, government and consumers. The organization develops standards that address needs such as enhancing public safety and health, advancing the quality of life, helping to preserve the environment and facilitating trade. CSA functions as a neutral third party in testing products and developing consensus standards. Underwriters Laboratories of Canada (ULC): An independent product safety testing, certification and inspection organization. ULC supports governmental product safety regulations and complements federal, provincial and municipal public safety initiatives. ULC also works with other government and international safety systems to help further international trade. ULC is now merged with UL.

Page 10: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

10

Warnock Hersey: A division of Intertek, provides independent third-party certification of product safety and performance for building and construction products. Warnock Hersey tests and certifies products to indicate compliance to relevant building codes, association criteria, and product safety and performance standards. Warnock-Hersey is a common listing agency for Fire Doors and Fire Rated Countertops. Texas Department of Insurance (TDI): An agency which regulates the state of Texas insurance industry and issues product evaluations for wind load performance for use in the state of Texas.

Florida Building Commission (FBC): A government agency which issues State-Wide Product Approvals for windload and other products for the state of Florida indicating compliance to provisions of the Florida Building Code. Miami-Dade County Product Control Division: An internationally recognized government agency which provides product approvals through the issuance of a Notice of Acceptance (NOA) indicating building code compliance for windload and other products used in Miami-Dade and surrounding counties of Florida. United States Environmental Protection Agency (EPA): A US federal government agency created for the purpose of protecting human health and the environment. Most noted in the garage door industry for its regulations for Lead Renovation, Repair and Painting (RPP).

Page 11: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

11

Section Two

Understanding Codes and Standards

There are basic aspects associated with rolling doors that require installers to understand codes and standards. Compliance with existing standards is essential to professional installation but having the ability to explain codes and standards to customers is evidence of a high level of experience and grants additional credibility to the professional and the company.

Published Standards There are a number of standards applicable to rolling doors and operators, some of which dictate methods of testing. Prominent standards development organizations include Underwriters Laboratories (UL), American Standards for Testing Materials (ASTM), and the National Fire Protection Association (NFPA). Two applicable standards UL publishes include UL 10B, a fire test standard, and UL 1784, a smoke test standard. Three applicable standards NFPA publishes includes include NFPA 80, a standard for fire doors and windows, NFPA 252, fire test methods for door assemblies, and NFPA 105, a standard for installation of smoke control door assemblies. In addition, DASMA is an approved standards development organization accredited by the American National Standards Institute (ANSI). DASMA has published voluntary standards relating to rolling doors and operators. Various DASMA standards are approved and still others are undergoing the ANSI recognition process and will be published with the ANSI/DASMA designation upon final ANSI approval.

Building Codes Published standards applicable to rolling doors are referenced in various codes. Usually, these codes also contain additional applicable provisions. Historically, there have been a number of “model” business codes and code agencies throughout the United States. These model building codes may be adopted at the state level with or without state amendments and may even be adopted at the municipal level with or without local amendments. Larger cities and counties may even write their own building codes. The two most prominent “model” building codes are the International Building Code (IBC), issued by the International Code Council (ICC), and NFPA 5000, Building Construction and Safety Code, issued by NFPA. The ICC model codes are those predominantly adopted throughout the U.S. The ICC represents – as of January 1, 2000 – a merging of three code agencies:

• Building Officials & Code Administrators (BOCA), historically a Northeastern United States influence, which formerly published the National Building Code (NBC).

• Southern Building Code Congress International (SBCCI), historically a Southeastern United States influence, which formerly published the Standard Building Code (SBC).

• International Conference of Building Officials (ICBO), historically a Western United States influence, which formerly published the Uniform Building Code (UBC).

These three former model codes are no longer enforced.

Page 12: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

12

One of the best things a professional door technician can do is verify the code that is in place in the community where the door is being installed. Remember that even neighboring communities may have differing codes. Local building codes and officials are only one example of entities which may impose requirements on Rolling Doors. Often, architects, commercial building insurance underwriters, risk management individuals and companies, etc. can impose requirements above and beyond those required by the local building codes. It is imperative to determine these requirements well in advance of ordering the door to ensure the door meets the performance specifications.

Licensing Some states and local areas may require a specific license to install or service rolling doors and/or some portions of a door system. Many regions do not allow contractors to perform work without becoming licensed. To become licensed, it is typically required for a business to apply, demonstrate a number of years of experience, and to pass a series of exams which can range in topics such as construction, business, law, contracts, and contractor level information. These exams are rarely particular to rolling doors, but rather usually over general construction practices and business operation. It is often required by law to advertise your license number and list it on contracts and quotations. Violating licensing laws in areas which require them can result in penalties of fines, forfeiture, and imprisonment. Research the licensing requirements in the areas where you do work to ensure your company is compliant.

NEMA Standards Many architectural specifications refer to NEMA (National Electrical Manufacturers Association) standards. These standards comprise many

volumes and are far too detailed to summarize in this text. However, the volume that is most frequently referenced in door operator specifications is the one specifying standards for Enclosures of Electrical Equipment. These requirements will be covered in the operator section of this manual.

Seismic Qualification Rolling door installations in public safety and/or earthquake prone applications may encounter requirements for Seismic Qualification. This means the door requires certificates and/or calculations from the manufacturer showing the ability of the door system to endure the loads anticipated from an earthquake. An example specification for this is “Metal coiling doors shall withstand the effects of earthquake motions determined according to ASCE 7.” Withstand means the rolling door will remain in place without separation of any parts from the door when subjected to the seismic forces specified. Doors meeting this specification may require larger or more frequent wall attachment fasteners, larger shafts, heavier guides, etc. The dealer will have to supply the manufacturer information from the Architect’s plans in order for the manufacturer to engineer the door properly. Examples of information needed are building height, site class (A, B, C or D), occupancy category (I, II, III or IV), building code reference, seismic design category, component importance factor, spectral response-Ss, spectral response-S1, and jamb configuration. When installing a door subject to these requirements, the installer should verify that the components provided match that indicated on the seismic qualification documentation and are installed in accordance with the manufacturer’s instructions.

Page 13: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

13

Wind Load Requirements

Wind is the organized translation of large amounts of air at one time. It can shape landforms, transport dirt and debris miles away, uproot trees, and damage buildings. From a windy day, to thunderstorm microburst, tornadoes and hurricanes, Mother Nature can produce unexpected high winds virtually anywhere in the world. This section aims to give a technician a general understanding of wind loads and garage doors.

Studies of damage to buildings because of hurricanes and other high wind events found that one common cause of catastrophic building failure was a pressure buildup within the building. Much like inflating a balloon until it pops. Researchers found that the cause of this pressure buildup was a breech somewhere in the exterior envelope of the building which allowed high winds to enter. With nowhere to exit, these high winds cause an increase in pressure that eventually can blow out windows, walls, or even blow off roofs. A rolling door is significant in a building’s ability to withstand high winds because it often closes the largest opening(s) on a building. An open door, or one which fails during high winds, can create a very large breech in the outer envelope. This opening can allow large amounts of wind to enter at once and rapidly increase the internal pressure until the building fails. This is just one reason why it is important for doors to carry the wind load rating for the location it will be installed.

Winds are often measured by their speeds. Meteorologists use a measuring instrument called an anemometer to measure the wind speed and often report the speed of the peak gusts during a given wind event. The smoother the terrain, the faster the wind speeds can become. Similarly, the more obstructions the wind encounters, the less speed can develop. Required wind load ratings are typically higher in areas near the coast of a large body of water, where there are no obstructions, than in urban areas where numerous closely spaced obstructions are present.

In terms of wind speed, it is important to understand the units of wind are different whether you talk to a meteorologist or an engineer. The unit of wind speed used by the media to discuss weather (especially when identifying Hurricane Categories) is the one-minute sustained wind speed, vs. the building codes, that use 3-second peak gust. The difference is that the building code units are approximately 15mph higher for the three second-peak gusts. In building design, it is helpful to gauge wind in terms of the load it exerts on objects it encounters, such as rolling

Page 14: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

14

doors. Because of this, required wind load ratings are often specified in psf, or pounds per square foot. This is the amount of force exerted by the wind in each square foot of exposed area. Conversion of wind speed to psf can be a complex calculation and different methods are used from one building code to the next. DASMA has published a series of Technical Data Sheets (TDSs) which help to clarify the conversion of wind speed to psf as well as the wind load requirements of various building codes. Winds can impart forces on a rolling door, and building, in two different directions. The first is called Positive wind load. In the positive direction, winds hit the door directly and attempt to blow the door into the building, similar to the sail on a sailboat. The second direction is called Negative wind load. Typically caused by crosswinds on the side of the building and turbulent suction on the trailing end of the building. Negative wind loading attempts to suck the door outward. Both loading directions must be accounted for in the door design to ensure proper performance. Another wind load related performance requirement in some areas is for Impact resistance. High wind events can involve flying debris which can crash into a garage door. These impacts can cause damage to the door which lessens its wind load resistance, particularly if windows are involved. Impact

rated doors have undergone special testing to ensure the wind load performance is maintained after several impacts. The testing involves firing a 2x4 out of a cannon at 34 miles per hour and impacting numerous key areas of the door. To pass this testing, the impact cannot result in a hole in the door exceeding the allowable limits. In addition, the door must then endure prescribed cyclic wind load testing to ensure the wind load resistance has not been compromised.

Impact rating is most commonly required in hurricane prone regions near the coast but can be required outside of this region. According to the International Building Code, the

wind-borne debris region is where glazing is required to be impact rated. Increasing requirements for impact resistance have most recently been driven in part by the insurance industry in an effort to reduce the amount of water damage caused by impact penetration of the outside envelope of the building. There are typically two classifications for rolling doors with respect to wind protection. The first is wind load rated products that are designed to meet a specific pressure rating. These doors have pressure ratings in both the positive and negative direction. The second, in addition to an assembly being rated for pressure, it is design evaluated to meet the enhanced

Page 15: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

15

protection standards that require the complete door assembly to have been evaluated for impact-resistance, including the glazing if the door has glass. For most of the US, the doors must be designed in accordance with the International Building Code, but for some parts of the U.S. it is required that the doors have approvals from certain approval agencies. Examples of these include: Florida Product Approval - required for all doors installed in Florida, Miami-Dade Notice of Acceptance - required for Dade and Broward counties in Florida, and Texas Department of Insurance Wind Storm Inspection - required for areas along the Texas coast that need wind storm inspections. No matter which level of protection that the job requires, it is critical that only the components listed on the wind load design drawing are utilized and no components are being substituted unless obtaining approval from the manufacturer. When ordering a door, it is critical to check with the building specifications, as well as the local authority having jurisdiction, to ensure that a product is ordered that will comply with the wind load requirements. DASMA has published Technical Data Sheets (TDSs) that can help determine the required wind load ratings in your area. Specification of higher wind loads for rolling doors can result in many product changes which may not be obvious to the untrained eye. It is important to understand the implications of specifying higher wind loads because these changes can increase the cost of the door. First, special engineering is required to ensure all components can handle the higher loads generated. Guide angle and windbar thicknesses may increase in order to handle higher loads from windlocks. Similarly, guide assembly fastener sizes and quantities may increase. In some cases, Larger guides can even cause the barrel and bracket sizes to change in order to ensure proper transition of the curtain into the guides. If the additional wind load exceeds the pull limits of alternating windlocks, then continuous and/or special

windlocks could be required. It’s also possible the higher wind load may require a thicker gauge curtain. Many of these items of course cause the balance weight to go up which could result in requiring bigger springs. It may not be possible to convert a door to handle higher wind loads in the field if the door was not ordered with the proper rating.

Understanding Loads Exerted by Rolling Doors

(Excerpts from DASMA TDS #251)

Rolling doors can impart significant loads on the buildings to which they are attached. There are two different types of loads a rolling door will exert on a building called dead loads and live loads. Dead loading would include the weight of the curtain, counterbalance, hood, operator, etc., that is supported by the wall above the opening. Live loading would result from wind loads that act on the door curtain. On doors without windlocks, the only wind load force that the curtain exerts on the guides is normal to the opening. On doors with windlocks, there is an additional load that is parallel to the opening. This load is the catenary tension that results when the curtain deflects sufficiently to allow the windlocks to engage the windbar in the guide. This force acts to pull the guides toward the center of the opening. The door is exposed to a positive load by wind on the outside of the building. A negative load on the door comes from inside of the building. The following four site conditions are to be avoided:

• Building designed with roll-formed “C” jambs that cannot handle the normal and parallel forces exerted by the door guide assemblies. The “C” jambs will rotate under wind load and the door curtain can be blown out of the guides. Openings on

Page 16: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

16

the steel buildings must have jambs designed for rolling door loads.

• Wall above the opening not designed to handle the total hanging dead load. Face of wall mounted doors may extend above the opening for 12 to 30 inches. The door guide wall angles must be mounted to the wall above the opening to support the door. When the door has a hood to cover the coiled curtain and counter-balance, some provision must be made to fasten the top of the hood and hood supports to the wall.

• Concrete masonry unit wall without concrete and rebar reinforced jambs cannot handle the forces imposed by the door. The design of a steel reinforced CMU jamb should have at least a 2500 psi concrete rating. A rebar free location for installation of expansion anchors is preferred.

• Building designed with tilt-up concrete panel walls that include steel jambs not securely attached to the concrete panels. Thus, the jambs cannot handle the forces imposed by the door. The steel jambs must be securely fastened to the wall along the full height of the opening.

Rolling Door Operation under Wind Load Conditions

(DASMA TDS #279)

Under either no wind or minimal wind conditions, rolling door assemblies perform with minimal contact between the curtain and the guides, as shown in figures 1 and 3. When subjected to high winds, the curtain will deflect and press against the guide angles, as shown in figures 2 and 4, and the resulting friction may hinder the door operation. The amount of wind required to create this friction varies tremendously from door to door depending on many factors such as door width and slat design (material type, gauge, and shape). The maximum wind load at which a door is still able to operate is called the operational wind load of the door.

It is important to distinguish operational wind load, as defined above, from design wind load. In accordance with ASCE 7, the recognized standard for determining loads on buildings, design wind load is the wind pressure a fully closed door is designed to withstand while remaining intact and safely operable after the wind ceases. When the wind force exceeds the design load for the door, the door can be blown out of the guides by being pushed into the building (under positive wind load) or sucked out of the opening (under negative wind load.) The design wind load is usually much higher than the operational wind load. Some doors require curtain-mounted windlocks to withstand the specified design wind load. When these doors are subjected to high winds, the windlocks engage the guide-mounted windbars, resulting in extreme friction that usually prevents vertical movement and may cause the door components to wear faster. If continued effort to open or close the door is exerted, damage to the curtain or other component parts may result. An electrically operated door subjected to wind load may need to have the door controls wired for constant contact for both opening and closing the door. This means that the door will move while the open or close button is depressed, and the door will stop when the button is released. If the controls are wired for momentary contact on open and close buttons, damage to the door may occur when the windlocks engage during opening or closing operation during high winds.

Page 17: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

17

The deflection of the curtain under load can exert a considerable force on objects in the path of the deflecting curtain. The potential inward or outward movement of the curtain under wind load can be very significant, and should be marked on the floor as a precaution to prevent damage to objects adjacent to the curtain. The door manufacturer can provide an estimate of the maximum deflection of the curtain under wind load. Warn customers against interfering with this deflection during high wind events. Placing large items, such as a fork lift, in the area of deflection of the door can hinder the proper wind resistance performance of the door. The door manufacturer should be contacted if a door will be operated under windy conditions, or if a door is installed on a building with controlled internal pressure.

Rolling Doors and Hurricanes or High Wind Events (DASMA TDS #282 and #291)

Rolling doors are typically in the largest openings associated with building structures. There are several items that should be kept in mind regarding a rolling door’s wind load performance in hurricanes or other high wind events accounted for in building codes. NOAA’s National Weather Service defines High Wind as follows: “Sustained wind speeds of 40 mph or greater lasting for 1 hour or longer, or winds of 58 mph or greater for any duration.”

1. A rolling door is subject to either being

blown into the building or pulled out of the opening. Therefore, backing a vehicle, or placing any other object, against a rolling door is not recommended. Further, this may damage the vehicle or other items used. The appropriate protection is provided with a rolling door that is wind resistant to local requirements.

2. A rolling door should be closed prior to a hurricane or high wind event. The door should be wind resistant to local requirements, and the door rating is only valid for a fully closed door. Keeping a rolling door open during a hurricane or high wind event leaves the interior walls, ceilings and roof structure vulnerable to structural damage and possible collapse of the structure.

3. DASMA does not recommend the operation of rolling doors during hurricanes or high wind events. The increased operational force needed to manually open or close the door, especially if windlocks are present in the door installation, may result in property damage and/or personnel injury.

4. Adding any non-manufacturer specified reinforcement to a rolling door can create a dangerous situation that may result in property damage and/or personal injury. Owners should avoid adding reinforcement to a rolling door

Page 18: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

18

themselves. A rolling door is not operational with any type of permanently attached exterior reinforcement. Even if such reinforcement were to be attached only when the door is in the fully closed position, altering the door to accommodate the attachments may compromise the door's operational capabilities.

5. There are some coastal areas that are subject to storm surges where it is more important that the door “break away” from the structure rather than resist wind load. Contact your local building department if the structure in question may be included in this requirement.

If you question your rolling door's ability to resist high wind events or hurricane force winds, contact a design professional to evaluate both the door and the surrounding frame of the opening. Keep in mind that the attachments of both the door guides and the door jambs to the structure are just as critical as the strength of the door itself. Fire Rating There are multiple agencies that are capable of testing and evaluating rolling steel fire doors in order to label and list door fire ratings. Such agencies include UL (and its Canadian counterpart ULC), FM Approvals, and Intertek Testing Services (ITS), the parent company of Warnock-Hersey (W-H). Keep in mind that these agencies are not responsible for final approval of a particular product utilized in a particular application. Rolling steel fire doors are assigned an hourly designation indicating the duration of the fire test exposure. This designation is known as the fire protection rating. For rolling steel fire doors, the most common ratings are three hours, one and one-half hours, one hour and three-quarter hours. A few manufacturers do have four-hour rated door assemblies, but this rating is not

specified or required by the major model building codes. Although somewhat outdated, ratings are sometimes referred to as Class A, B, C, D or E openings:

• Class A labels are three-hour rated doors for openings in three or four-hour rated firewalls and in walls that divide a single building into distinct fire areas.

• Class B labels are intended for one and one-half hour rated doors for openings in two-hour rated partitions.

• Class C labels are intended for three-quarter hour rated doors for openings in walls or partitions between rooms and corridors having a fire resistance rating of one hour.

• Class D labels are intended for openings in exterior walls subject to a severed fire exposure from outside the building. Such doors are generally rated at least three hours.

• Class E labels are for openings in exterior walls subject to a moderate or light fire exposure from outside the building. Such doors generally are rated at one and one-half hours.

Fire door listings can be broken down into three types; Label Size, Oversize, and Oversize Construction Certificate. Label size fire doors represent door sizes up to and including the size door tested as indicated in the listing agency file. These doors are constructed exactly the same as the tested door and have a label affixed to the bottom bar indicating Label Size Rolling Fire Door along with listing information, fire rating, and serial number.

Page 19: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

19

Oversize fire doors represent doors larger in height or width or both than the size door tested as indicated in the listing agency file. These doors have modified construction extrapolated from the tested door. They often require larger components and have a label affixed to the bottom bar indicating Oversize Rolling Fire Door along with listing information, fire rating, and serial number.

Oversize Construction Certificate applies to doors larger in height or width or both or otherwise modified from that approved for the manufacturer for Oversize Fire Doors. These doors often require field inspection and drop test by representatives of the listing agency. Upon approval, the listing agency will issue an Oversized Construction Certificate indicating the approval of the door along with the listing information, fire rating, and serial number. There will not be a label on the bottom bar. Often the manufacturer can utilize the oversize construction certificate to expand their Oversize approvals. Because of this, oversize construction certificates have become much less common than previous years.

Smoke Control Any of the three types of rolling fire doors can offer a varying degree of smoke protection. Without specific testing for smoke infiltration, listed brush seals can be installed around the perimeter of an opening to reduce the amount of smoke that can pass through an opening when the door is closed and the opening is

sealed. In this case, the listing of the brush seals assures that the application of the seals will not affect the fire rating of the doors, but it does not indicate that the door is tested and listed for smoke protection or air leakage.

When required to meet local building code smoke protection requirements or to ensure smoke protection performance, provide a door that is labeled for smoke and draft control, which means it has undergone the UL 1784 test for air leakage and conforms to the requirements of NFPA 105, Standard for the Installation of Smoke Door Assemblies.

For rolling door products, it is typical for smoke rated units to also be fire rated. These type units will bear two independent labels, one for a fire rating and the other for air leakage, typically referred to as an S label. Per NFPA 105, Chapter 2 guidelines, air leakage rated assemblies must incorporate an automatic closing device and be signaled to close by activation of local smoke detectors or a central alarm system. To provide effective smoke protection, these type units must close long before local temperatures are high enough to melt fusible links.

Rated smoke protection is typically achieved with the addition of UL listed guide and lintel brush seal as well as high temperature silicone sealant. The sealant is applied to all guide assembly points, as well as to the entire

Page 20: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

20

perimeter of the opposite coil side of the guides, fascia (if applicable), all brush seal retainers, and any other areas where metal is in contact with the wall or header. It is important to follow the manufacturer’s instructions closely to maintain the smoke rating of the door. Whether the door is smoke rated or not, it is important to always drop test a fire door to ensure proper operation after any ancillary seals are installed. This is to ensure any resistance from the additional seals does not prevent complete closing of the door.

Final Approval Code administration, final code interpretation and final product approval all fall under the Authority Having Jurisdiction (AHJ). As defined in NFPA 80, the AHJ is the organization, office or individual responsible for approving equipment, an installation or a procedure. An AHJ may be a building code official, a fire marshal, a state or federal government official. Their approval is an indication that the product has been found to comply with applicable codes and standards adopted by the jurisdiction in question. General contractors, firefighters, and building owners are not AHJs.

Insulation Insulation is the ability of a material to retard the flow of energy. Energy will always flow from a high-energy source to a low-energy source, such as heat flowing to cold. Insulation can also be effective in retarding the transmission of sound. Heat flow through a material is measured in British Thermal Units (BTU’s). One BTU is the amount of heat required to raise the temperature of one pound of water one degree Fahrenheit.

R-Value R-Value is used to measure a material’s resistance to heat flow and is the most commonly used measure for determining the performance of an insulating product. A product’s R-Value is its ability to retard heat flow. R-Values are presented in numerical form with a high number indicative of good insulating performance and a low number indicative of poor insulating performance. Thus, a product with an R-Value of 4.00 is more efficient at retarding heat flow than a product with an R-Value of 2.00. See DASMA TDS-163 for further information.

K-Factor K-Factor is used to measure an insulation material’s thermal conductivity. Thermal conductivity is defined as the degree to which a material facilitates the flow (conduction) of heat. K-Factors are presented in numerical form (typically decimals) with a high decimal value indicative of high conduction, which is detrimental to insulating performance, and a low decimal value indicative of low conduction which is beneficial to insulating performance. K-Factor is calculated by dividing 1 by a product’s insulation R-Value. An example of this calculation is as follows: Material: 1.00# Density EPS with an R-Value of 3.85 per inch. K-Factor Calculation: 1 divided by 3.85 (R-Value) = .259 (K-Factor)

U-Factor U-Factor is used to measure the overall thermal conductivity of a wall system, or in this case, a rolling door, by taking into account the thermal conductivity of all of the components within the system. Much like a K-Factor, a door system’s U-Factor will typically be presented in

Page 21: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

21

decimal form with a low decimal value being more desirable than a high decimal value. The U-Factor of an assembly cannot be determined by dividing 1 by the R-Value of the curtain. See DASMA TDS-163 for further information.

Method of Determining Thermal Performance The thermal performance ratings (Curtain R-value, insulation K-factor, and assembly U-factor) can be determined either by calculations or by testing. Values derived by calculations are often based solely on the mean section profile and do not account for complexities such as section joints and building interfaces. Values derived by testing come directly from test results on a complete installed door system. It is important to recognize the method used to derive published thermal performance ratings when comparing two products because the two methods produce different results which are not comparable. See DASMA TDS-163 for further information on manufacturer’s published insulation values.

Flame Spread The numeric flame spread rating for any material is a relative comparison to the flame spread ratings of cement asbestos board (0) and red oak (100). Flame spread is tested and measured in the Steiner Tunnel Testing Machine. The Steiner test method involves placing the material to be tested in the ceiling of the tunnel where it will be exposed to flame and observed through a glass wall for burn characteristics.

A gas burner propagates flame at one end of the tunnel and the extent of flame propagation along the sample material suspended at the tunnel ceiling is measured and compared to that of cement asbestos board and red oak. Typical building codes require that the flame spread rating for materials used in commercial construction applications not exceed 75.

Smoke Developed The numeric smoke developed rating for any material is determined by a measuring device, which is installed in the outlet of the Steiner Tunnel Testing Machine. As material is burned by the Steiner Test method, smoke generated during the test is ducted out of the tunnel where its density is measured and recorded. Typical building codes require that the smoke developed rating for materials used in commercial construction applications not exceed 450.

Sound Transmission Noise reduction is measured with either STC (Sound Transmission Class) ratings for exterior applications or OITC (Outdoor-Indoor Transmission Class) ratings for interior applications and is roughly the measure of the decibel reduction in noise that occurs in a building partition, such as a rolling door. For example, if an 80-decibel sound on one side of a door is reduced to 50-decibels on the other side, that door is said to have an STC of 30.

Page 22: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

22

Section Three

Rolling Door ComponentsMaterials and Finishes

Rolling door products are normally comprised of four different materials; aluminum, steel, stainless steel, or wood. Due to the lower melting point of aluminum and the flammability of wood, aluminum and wood are not used for any critical fire door components. That leaves steel and stainless steel as the base material for rolling fire rated products.

Steel Sheet Metal Components Slats are galvanized with zinc coatings ranging from G40 to G90. In many cases slats are also finished with at least one layer of baked-on primer and polyester top coat. Hood coatings may match the curtain or at a minimum be painted steel. Other exposed ferrous non-galvanized components are supplied at minimum with a coat of primer, paint, or powder coating.

Steel Components Standard or available coatings are dependent on the manufacturer. Hot dip galvanizing – Hot liquid process applies a protective zinc coating in a metallic silver finish. Cold galvanizing – zinc rich spray on liquid coating or zinc rich powder coating is applied to metal components for enhanced protection against weather and corrosion. Powder coating – an electrostatic applied polymer is baked-on to steel components providing a durable finish in a wide array of color choices.

Stainless Steel Components Curtain slats and hoods are formed of rolled or formed sheet metal in varying gauges. Bottom bar and guides are built up from formed stainless steel plate or structural stainless steel angles. Because of its roll forming and welding capabilities, most stainless used for rolling product components is grade 304. Type 304 stainless - is the most versatile, and one of the most widely applied of the 300 Series stainless steels. It has excellent forming and welding characteristics. It is readily break or roll formed into a variety of other parts for application in the industrial, architectural, and transportation fields. Type 304 stainless has excellent corrosion resistant properties, exceeding that of Type 302 in a wide variety of corrosive media.

Most Common Stainless Steel Finishes #4 Polished Finish is produced by abrasive belt polishing of cold rolled stainless steel sheet, plate or strip. Since polished grain lines follow one direction, hand or machine polishing after fabrication can restore finish. In welded assemblies the weld beads are first ground smooth and then re-polished to blend with original finish. Polished finishes can be cleaned frequently without changing surface appearance. This general purpose polished finish finds wide application in restaurant equipment, dairy equipment, food processing, medical and chemical equipment, as well as various architectural products. 2B Finish is the basic general-purpose cold rolled finish. Its smooth gray surface finish varies depending upon stainless type and thickness, with thin sections usually brighter

Page 23: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

23

than thicker sections. It is used for an extremely wide variety of fabricated parts. Structural Stainless Primary Finish (Mill Finish) is produced after hot rolling when the heavier gauge plate and sheet products are annealed and pickled. Resultant surface is dull etched and some variation in appearance can be expected. This finish is generally used in industrial applications where surface smoothness and uniformity of appearance are not critical factors.

Aluminum Finishes Most aluminum components are constructed from aluminum extrusions which are preformed and cut to length for the door. Aluminum can also be rollformed into various shapes. Aluminum slats typically are available in 14 and 16-gauge material. Aluminum can be finished in a variety of ways. Most aluminum doors are mill finish, and for more corrosive environments or better appearance, anodized, primed and painted, or powder coated finishes are available. Aluminum is also commonly used on rolling grilles. Available in mill finish, anodized, or powder coated, grille curtains are often made using aluminum links and hollow or solid aluminum rods.

Page 24: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

24

Typical Rolling Door Components

Page 25: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

25

Curtains

The door curtain is the largest component on the door in terms of the area of the opening it covers. The curtain is the component of the door that travels up and down in the guides of the door. It is assembled by sliding interlocking slats together and secured by means of endlocks on alternating or every slat. The endlocks will prevent the curtain from sliding apart during use and prolong the life of the curtain. When assembled, the curtain is attached to the barrel of the door with barrel rings or directly to the barrel assembly with either fastening sections or a starter slat(s).

The curtain configuration varies based on the type of door. Solid curtain slats are made of stainless steel, prime painted steel, galvanized steel, aluminum (mill or anodized), or wood. Slats are produced in a curved or flat configuration in a variety of sizes. Insulated curtain slats have an added backer slat and foam is used to fill the gap between them. This insulation improves the door’s resistance to heat flow and sound transmission. The foam may be foamed-in-place during slat production or laid in place during curtain assembly. Insulated Rolling doors typically have an R value between 6 and 8 and an STC/OITC rating of around 20 decibels. Reference your specific manufacturer for exact ratings.

Many fire door manufacturers offer insulated fire doors. The insulated slats of fire doors are typically made using mineral wool insulation material because of its fire resistance properties. Mineral wool is produced by a special process of spinning molten rock through an air stream somewhat like the process used to make cotton candy. This process creates fine, intertwined fibers which have insulating and sound dampening properties as well as excellent fire resistance. Further processing turns these fibers into a workable insulation material that can be laid in between the front and backer slats of an insulated fire door. Insulated fire doors typically have an R value between 4 and 5 and an STC/OITC rating of around 20 decibels. Reference your specific manufacturer for exact ratings. Examples of typical slat profiles, from left to right, are; small curved slat, large curved slat, small flat slat, large flat slat, insulated slat, aluminum extruded slat, and wood slat:

Slats are normally provided in 24, 22, 20, and 18-gauge thickness with some large slats using 16 or even 14-gauge. The finish on the galvanized steel curtain can be left unpainted or phosphate treated for paint adhesion, prime painted, finish painted, powder coated and/or finished with a zinc rich coating to prevent corrosion. Except for secondary finishes such as powder coating, the prime paint and finish paint are applied prior to the roll-forming process. The finish on the stainless steel curtain is typically a #4 polished finish, however 2B finish is available from some manufacturers when the doors are in a corrosive environment and aesthetics is not an issue.

Page 26: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

26

Rolling door slats interlock together differently for a door mounted on the inside of a building vs. a door mounted on the outside of a building. The orientation of the slats is reversed to provide proper watershed and prevent water infiltration into the building. This orientation is such that the upper slat bead on the outdoors side of the door covers the slat joint preventing water from infiltrating the slat connection. If the slats were not properly oriented when assembled, water would collect inside the individual slat beads and ultimately penetrate into the building. It is important to specify interior vs. exterior mounting when the door is ordered to ensure the slats are assembled for proper watershed.

Perforated Slats Perforated slats are available with multiple small holes punched in the slats on a tightly repeated pattern. These slats allow air and light to flow through the door while still maintaining security and strength. The smaller holes of perforated slats can also prevent most insects from entering through the curtain.

Fenestrated Slats When greater air or light penetration is desired, fenestrated slats are available. These slats are similar to perforated slats but have larger rectangular cutouts instead of small holes which can improve the durability of the slat. Fenestrated slats can comprise the entire door, or just a few rows of slats depending on how much light and air penetration is desired.

Vision Slats Like fenestrated slats, vision slats utilize rectangular cutouts in the slats with clear coverings to create small windows in the door. They are typically grouped in rows of multiple slats at eye level of the door to provide visibility to the opposite side of the door. The clear coverings prevent bugs and weather from entering and allow light to pass through the curtain.

Page 27: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

27

Grille Curtains Grille Curtains are constructed from solid or hollow rods, links and spacers which are laced together to form a pattern. Available in aluminum, steel, and stainless steel, grille curtains are most commonly produced in straight and brick patterns of various pattern lengths. Straight Pattern:

Brick Pattern:

Endlocks/Windlocks

Endlocks are the component of the door curtain that prevents the slats of the curtain from sliding apart or shifting during the travel of the door. Rolling Door Endlocks typically are constructed of cast iron, stamped steel or nylon, and are usually riveted to both ends of alternating slats. Fire product endlocks are constructed of cast iron or stamped steel. They are typically riveted to both ends of each or alternating slats. Specifications sometimes call for endlocks on both ends of each slat, or continuous endlocks.

In certain applications, endlocks utilize a windlock design. Windlocks incorporate a locking tab to secure the curtain inside the guides, preventing the curtain from releasing in high wind environments or to meet specific windload requirements. When utilizing windlocks, guides must be adapted to incorporate a windbar. The windbar allows the windlocks to engage and hold the curtain in place under windload for the designed PSF rating. Specifications or windload requirements may sometimes call for windlocks on both ends of each slat, or continuous windlocks.

Guides

Guides retain the edges of the curtain within the opening. Guides are available in various materials. Steel guides can be powder coated, prime painted, galvanized, non-galvanized (bare), stainless steel or zinc rich coated to prevent corrosion. Aluminum extruded guides are also available for non-fire rated products in some of these finishes along with mill finish and anodized.

Page 28: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

28

Typically, the tops of the guides are flared (bellmouth), providing a smooth transition for the curtain to enter into the guides. Stops are installed at the tops of the guides to prevent the curtain from exiting the guides. Some designs combine the flare and the stops into one component. The inside of the guide opening may contain a windbar on windload rated or larger doors. A windbar is a channel or bar welded inside the guide opening which engages the windlocks under windload. This prevents the curtain from releasing from the guides when wind is present.

There are three issues that determine the design of the guides on rolling doors.

First, since the guide angles are fastened to the wall and provide the only supporting connection between the door and the wall they must be sized correctly to support the weight of the counterbalance assembly and curtain assembly. Guide construction and fastener type must be designed around the intended loads as well as any other loading requirements such as fire rating, wind loads or seismic loads.

Second, wall construction and building material clearances influence guide design. There are two primary designs for face of wall mounted guides with regards to wall fastening and both affect only the wall angle – the part of the guide that attaches to the wall. On steel jambs the wall angle can be bolted to the jamb or welded to the face of the jamb in accordance with the manufacturer’s listing. The toe of the wall angle is pointing toward the jamb opening. This type of guide configuration is also known as an “E” type guide. FM does not allow Fire Door guides to be welded to steel jambs. When mounting to wood, masonry or concrete, the mounting fasteners are moved away from the edge of the opening. This prevents the jamb corners from cracking. The distance from the edge should be at least 6 times the diameter of the fastener according to NFPA 80. In this case the toe of the wall angle is pointed away from the jamb opening. This type of configuration is also known as a “Z” type guide.

Third, the way in which a guide is attached to the jamb can also affect the guide design. There are times that because of head room and/or side room limitations the guide cannot mount on the face of the jamb. In these cases, the guide is

Between Jambs Guide

Page 29: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

29

mounted within the jamb opening or between jambs mounted. This application normally uses a four-angle guide design, as opposed to a standard three-angle design. The addition of the fourth angle provides clearance from the jamb to accommodate drive and tension side components of the door.

There are several ways in which to attach the guides to the jamb. On steel jambs, drill and tapping using machine bolts or welding in place. When welding guide angles to the face of steel jambs, strict adherence to the manufacturer’s requirements regarding number of welds and length of welds is required. On solid masonry jambs the use of expansion anchors is acceptable. Expansion anchors must be manufactured from zinc, cadmium coated steel or stainless steel. On hollow block walls the guides shall be attached by means of through-the-wall type bolts and crush plates. When attaching fire door guides to the jambs, it is important to follow the manufacturer’s directions for upward or downward expansion and be in accordance with NFPA 80, Standard for Fire Doors and Fire Windows. NOTE: The installer should only use manufacturer supplied fasteners and verify then against the installation manual. NFPA 80 does not approve the use of lead anchors for Fire Door installations. Do not use lead anchors to install any component of a Fire Door.

Fire Door Guide Expansion Clearance The fire door guides are exposed to a tremendous amount of heat in a fire event. Steel expands as temperatures increase, which causes the guide angles to grow in length. This guide expansion must be compensated for with the guide and door designs to prevent catastrophic failure in the event of a fire. One way this is done is by incorporating Expansion Clearance into the door design. Expansion clearance is an amount of space built into the door design to accommodate the length increase of the

guides during a fire. There are two types of expansion clearance. Upward expansion is when the expansion clearance is at the top of the door and the guides are designed to move upwards during a fire. Fasteners attaching the guides to the wall must be located at the tops of the wall mounting slots so that the guide angles can slide upwards during a fire. These fasteners typically use special galvanized or fiber washers to aid with this guide movement during a fire. It is critical to ensure proper clearance at the top of the door to maintain this upward expansion. Downward expansion is when the expansion clearance is at the bottom of the door and the guides are designed to move downward during a fire. This requires the guides to be shimmed an additional distance off the floor during installation to provide the required clearance. Wall mounting fasteners in downward expansion designs are required to be installed at the bottoms of the wall mounting slots such that the guide angles can slide downward in a fire. These fasteners also typically use special galvanized or fiber washers to aid with guide movement during a fire. In some cases, it may be necessary to install additional metal shielding at the bottom of the guides to cover gaps for expansion clearance and/or from shimming the guides level.

The requirements for upward and downward expansion vary from one manufacturer to another depending on their listing agency’s approval. The amount of expansion required is typically 1/8” per foot of height. It is crucial to

Page 30: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

30

the safe function of a fire door to strictly adhere to the manufacturer’s installation instructions for guide expansion at installation. Failure to follow these instructions could result in failed protection in the event of a fire.

Bottom Bars

The bottom bar is the part of the door curtain that rests on the floor or sill. It is constructed of structural or roll-formed steel or aluminum angles, tubes or aluminum extrusions. Typical construction is two angles mounted back-to-back with a half slat sandwiched between the angles. Some small door designs or doors used with conveyor systems might have only one angle as the bottom bar. The bottom bar is notched, or coped, at the ends so that the vertical portion of the angle can extend into the guide.

Bottom bars perform several functions, which are important to the design and security of the product. The bottom bar reinforces the curtain assembly and can greatly deter someone from lifting or prying them up to gain access under the door. The bottom bar provides a surface in which a lock can be mounted to secure the door. It can also be equipped with an astragal for weather protection or a sensing device for safety. On an electrically operated door equipped with the bottom bar sensing device, the door will stop and reverse when it detects an obstruction. The bottom bar prevents the

curtain from exiting the guides when the door is open. By contacting the stops, the door cannot proceed up into the hood mechanism causing damage to various door components. On fire rated products, the bottom bar also provides hanging weight required to initiate automatic fire door closing.

Bottom bars can be finished in a variety of ways. Steel bottom bars can be galvanized, painted, powder coated or left unfinished. Stainless steel bottom bars can be mill finish, 2B or #4 finish. Aluminum bottom bars are available in anodized, mill finishes, primed and painted or powder coated finishes.

Bottom bars typically have a label affixed which identifies the manufacturer and serial number of the door. Fire Door bottom bars have the Fire Door label, and smoke label if applicable, affixed which identifies the manufacturer, listing agency, fire and/or smoke rating, and serial number of the door. It is important that the information on bottom bar labels be retained for replacement parts and future service work. For Fire doors, replacement parts and bottom bars, if needed, may only be supplied by the original fire door manufacturer.

Barrel

The barrel is a cylindrical member, steel tubing or pipe, whose main function is to house the counterbalance spring(s) and related hardware. Pre-drilled holes in the barrel or barrel rings allow for attachment of the curtain to the barrel.

Page 31: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

31

The barrel must be large enough to house all the springs required to correctly balance the door. The industry practice indicates that the barrel pipe shall not deflect more than .03” per foot of width. One end of the barrel is the tension end and the opposite end is the drive end. If a door is designated as right hand operated, the drive end is located on the right side of the door. The tension end contains the counterbalance mechanism and the tension shaft is connected to the springs. Drive shafts consist of a short solid shaft with one or more round plates welded to the shaft and pipe called a plug end.

Counterbalance Mechanism The counterbalance mechanism consists of one or more helical torsion spring(s) and related hardware and is housed within the barrel. The springs are designed to compensate for the weight of the curtain and to facilitate the desired method of operation. The counterbalance mechanism will not balance the door at all intervals of the opening and closing cycle. The door, when balanced properly, should hold tight in the open position. In the closed position, the door should rest on the floor with minimal lift. On fire door designs, the counterbalance mechanism must be designed, manufactured and installed in such a way that allows the door

to drop from the open position upon activation from a signaling device. The signaling device can be a heat sensing fusible link, a smoke detector, or the building alarm system. This can be accomplished by several means. For conventional style systems, upon activation from the signaling device, a release arm or drop arm disengages the drive mechanism from the barrel and allows for a release of a portion of the spring tension from the counterbalance mechanism. Releasing the spring tension provides the energy to start rotating the barrel (and attached curtain) and gears resulting in the closure of the door. This counterbalance release should only be performed from the full open position as non-repairable damage to the release components and/or barrel counterbalance system may occur if released while the door is at the closed position. Other fire door systems utilize a counterbalance mechanism that is already underbalanced. A brake prevents the door from falling during normal operation and a governing device controls the closing speed of the door. Rate of closure upon release is outlined in NFPA 80: The door shall close not slower than 6 inches per second (152 mm per second) and not faster than 24 inches per second (610 mm per second).

Cycles A cycle is defined as one opening plus one closing of a door. The springs within the counterbalance mechanism of a rolling door are engineered to last a predetermined number of

Plug End

Page 32: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

32

operational cycles. Most rolling doors manufactured today are engineered with minimum 20,000 cycle springs. Higher cycle springs are available from manufacturers, and are typically specified as 25,000, 50,000 and 100,000 cycles. Selection of higher cycle springs should be based on the anticipated usage of the door in application. A door which is expected to be opened and closed many times throughout the course of a day would require higher cycle springs than a door which is only opened and closed once at the beginning and end of the day. It is important to assess the application’s anticipated duty cycle in advance of ordering the door such that the springs can be designed for sufficient cycle life. The result in specifying higher cycle springs is the use of larger diameter spring wire and longer springs. These larger springs are stronger and therefore last longer. In some cases, a process known as shot peening is used to extend the life of the springs. Shot peening corrects surface imperfections created in the manufacture of the spring by bombarding the surface of the spring with small pellet-like spheres. This extends the life of the spring providing additional operational cycles. Rolling doors with higher cycle springs specified often also utilize heavy duty support bracket bearings, as well as thrust bearings within the barrel, to provide longer life of components other than the springs. Refer to the manufacturer’s recommended maintenance schedule to help achieve the expected life of the door. Torsion springs are made in combinations of wire size and coil diameter to operate safely and efficiently. Springs are always kept within Index Ratio, or IR- parameters. The IR is the ratio of wire size to coil diameter.

Brackets

The brackets provide structural support for the barrel, counterbalance mechanism, curtain assembly, and hood. They are constructed of steel, stainless steel or aluminum and are usually square or rectangular in shape. The finish on a steel bracket can be galvanized or painted. The stainless steel bracket can be mill finish, 2B or #4 finish. The brackets will have pre-drilled holes for bolting to the top of the guide wall angles. They also provide support for attachment of gears, electric operators, chain hoists, automatic closing devices (release mechanism), governors, tension wheels, etc. and will house the bearing for the drive shaft. The bracket on the drive side is known as the drive bracket and the tension side bracket is known as the tension bracket.

Operating Mechanism For non-manually operated rolling doors, there are typically operating mechanisms mounted on the outboard side of the drive bracket. Depending on the type of operation, these mechanisms could be as simple as mounting a sprocket on the drive shaft, to complex compound reduction chain hoists and fire door drop out mechanisms. Operating mechanisms can vary tremendously from one manufacturer to the next and are far too complex in scope to cover them all in this text. Reference the manufacturer’s information for details on specific operating mechanisms. Some manufacturers factory assemble the operating

Page 33: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

33

mechanisms to the drive brackets to aid field assembly.

Tension Wheel Tension wheels are a component attached to the counterbalance assembly tension shaft, which controls the spring tension as it is applied and locked to the bracket. These typically mount on the outboard side of the tension side bracket and have outwardly radiating holes to receive winding bars for applying spring tension. A tension wheel can be connected to the tension shaft with keys and setscrews, pins, or with interfacing shaft and hub shapes such as a D or Hex shape. They are most commonly made of stamped steel, cast steel, or cast iron and range in size depending on the amount of spring tension for the door.

Inside Tension Device

An inside tension device is typically used on counter doors and between jambs applications where side room is limited. There are two types of inside tension devices, inside tension wheels and inside shaft holders. Inside tension devices create a more finished look on counter doors and may be required on between-jambs applications. As the name implies, inside tension wheels have the tension wheel mounted on the interior side of the tension bracket. A cradle is mounted to the tension bracket and the tension wheel is used to turn the tension shaft and

apply tension to the springs. Tension is applied while the curtain is in the closed position. The top most slats are typically shorter than the rest of the door to provide access to the tension wheel while the door is closed. On larger doors where extreme tension is required, a worm-gear or other winding mechanism may be mounted to the tension bracket so that tension can be applied while the door is in the opened position. When Inside tension holders are used, a cradle is mounted inside the bracket and the tension shaft is pinned through the cradle. The shaft may contain alternating holes for winding the shaft, or tension may be applied by pre-charging the barrel before assembling the curtain. The top most slats may also be shorter than the rest of the door to provide access to apply tension the shaft while the door is closed.

Compound Tension Device A compound tension device provides a gear reduction between the tension wheel and the tension shaft. This gear reduction reduces the amount of force the installer must exert in order to apply the initial tension to the springs. These are used on very large, heavy rolling doors where the required spring tension is high. A full revolution of the tension shaft will require multiple revolutions of the tension wheel. Therefore, spring turns must be counted from the tension shaft, rather than the tension wheel. It is important to follow the manufacturer’s installation instructions closely when utilizing compound tension devices to ensure the spring tension is safely contained.

Page 34: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

34

Inertia Brake A unit that is attached to the door shaft and bracket or wall which will stop the door from free falling should there be a catastrophic failure in the motor operator brake, roller chain drive or tension spring assembly. When the shaft is moving above a certain RPM, the unit will lock up the shaft, preventing it from moving until the door can be repaired. Inertia brakes are recommended for spring-less doors, very large doors with very large out of balance, and are sometimes specified. They are often chosen as a redundant failure device to prevent the door from freefalling in the event of spring or operator failure.

Hoods

A hood is a sheet metal housing that mounts horizontally between the brackets, serving as an enclosure for the coiled curtain and closing the space between the door coil and the lintel. The hood on a rolling door is constructed of steel or stainless steel and typically is the same material and finish as the door curtain. The hood can be round or square in shape to attach at the brackets and can be attached at various points along the wall above the opening. The top and bottom edges of the hood are bent or curled to add rigidity over the length of the hood. Some doors utilize door slats to make a hood, called a Slat Hood. These hoods are made by assembling a predetermined number curtain slats with end locks and fastening them such that the slats wrap around the bracket. These hoods typically match the material and finish of the door curtain and provide a hood

which looks the same as the inside of the door curtain. Slat hoods are less popular than sheet hoods because the complex shape of the slats can trap dirt and debris. The hood performs multiple functions. First it serves as a cover for the counterbalance assembly and the rolled curtain. This helps to prevent items such as dirt and debris from interfering with the coiling and un-coiling of the curtain as the door travels. The second function it serves is a stabilizer for the drive bracket and tension bracket. The hood is mounted between the two brackets and helps to prevent the brackets from shifting or bowing out. Wider doors will require multiple hood sections with intermediate hood support(s) or bracing. On fire rated products, the hood also serves as a barrier that prevents flames from making their way around the coil area. Some manufacturers and/or listing agencies may also require the use of a flame baffle that mounts on the inside of the hood. The flame baffle is an additional component that prevents the spread of flame around the barrel of the door, which prevents the flame from reaching the other side of the opening. The flame baffle will be held away from contact with the curtain during normal operation by the sash chain or cable and released to contact the coil in an activated state. Flame baffles are required on all doors utilizing a Factory Mutual (FM) label. Intermediate hood supports may be on the exterior side of the hood when a flame baffle is present.

Page 35: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

35

Longer hoods and wider doors utilizing multiple hood sections will require the use of intermediate hood support(s). An intermediate hood support is a rigid member which is contoured to the shape of the hood and mounted to the wall between the brackets. The hood is then attached to the support to give the hood rigidity. These may mount on the inside or the outside of the hood depending on if there is a baffle present. These support the middle of the hood to prevent sagging and provide an attachment point for multi section hood splices. When the door is mounted under a lintel, a secondary hood called a fascia (backhood) is provided. A fascia panel is a finished metal cover used to conceal the opening which remains when the door height is less than the height of the opening. They are most commonly used on doors that are installed on under lintel applications, to enclose the counterbalance and curtain assembly on the opposite coil side of the door.

The attachment of the hood or fascia to the wall or brackets only supports the weight of the hood itself. Hood mounting does not provide any structural support of the rest of the door. Weather protective doors will have hoods with internal hood baffles to minimize air infiltration. Typically made of plastic or rubber, an internal hood baffle is a flat sheet mounted inside the hood

designed to close the space between the hood and the door coil to restrict air infiltration. These hood baffles rely solely on the hood for support and may require special installation techniques if internal hood supports are required. Fire doors may utilize a flame baffle to prevent the passage of fire. A specialty hood option available from some manufacturers is a sloping hood. Sloping hoods are formed with a larger slope to the upper, flat portion of the hood. These are used for exterior door applications where heavy snow loads or watershed requirements are anticipated.

Governors

The governor is a speed control mechanism that controls the rate of descent of an automatic closing fire door. There are various types of governing devices. The most common governing devices are ratcheting (escapement), viscous and centrifugal governors. The ratcheting (escapement) type uses a mechanism that ratchets up and down or side to side in conjunction with a notched wheel. This provides mechanical resistance preventing the wheel from free spinning and slowing the fall of the door. These types of governors can be noisy during drop testing depending upon the method of mechanical resistance. The viscous governor uses liquids of varying density (determined by weight) housed in a notched wheel device. Rotation of the viscous governor forces the fluid through the notches and provides resistance to

Page 36: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

36

higher speeds of rotation. The faster the governor spins, the more fluid is forced through the notches causing greater resistance. Centrifugal governors are a speed activated braking device typically achieved using arrangements of spring loaded brake pads. The faster the governor spins, the greater the amount of centrifugal force causing greater resistance. These governors sometimes require additional sprocket and/or gear reductions to increase the rotational speed of the governor. Automatic closing fire doors shall close no slower than 6 inches per second (152 mm per second) and no faster than 24 inches per second (610 mm per second). A governing device is required on all units that require controlled automatic closing speed to meet the requirements as stated per NFPA 80.

Sills and Countertops All automatic closing rolling fire doors need to come to rest in full width contact with either the floor or a countertop to completely close off the opening to provide required fire protection. NFPA 80 states that the floor structure beneath rolling fire doors needs to be constructed of a noncombustible material and shall extend through the door opening. Special noncombustible sill material construction is required to extend through the opening if combustible floor material is located beneath the fire door opening. Service Counter Fire Doors in NFPA 80 covers interlocking slat type door curtains integrally mounted in a four-sided frame that forms a labeled door and frame assembly and counter fire doors that mount to noncombustible opening framing. When countertops are supplied separately from the balance of the

door assemblies, they shall be labeled and installed in accordance with their listing. When countertops are to be provided and installed with counter fire doors, both labeled plastic laminate and labeled stainless steel countertops are available from counter fire door manufacturers. Labeled countertops normally carry a 1.5 hour rating and are available in various shapes to fit both face of wall or between jamb mount installations. The countertops have minimum projection requirements beyond the centerline of the curtain and beyond the width of the guide assembly. Check with individual suppliers for specific configuration requirements and size limitations.

Countertops are generally supplied in 3 shapes; Rectangular, “T” shaped, and “H” shaped (sometimes referred to “I” shaped):

Page 37: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

37

The following guidelines apply to fire rated countertops:

• The countertop must be within the minimum and maximum dimensions allowed by the listing agency. See manufacturer’s data sheet and countertop shop drawing.

• Single piece countertops are provided for smaller opening widths and two-piece countertops with a center joint may be required for wider openings.

• Depending on the listing agency approval, it may be required for all surfaces of laminated countertops to be laminated, including those which are not visible.

• The listing agency label must be visible at all times after installation.

• The countertop cannot be modified in the field. This means there can be no holes drilled, no trimming, and no other modifications of any kind other than those prescribed in the manufacturer’s installation instructions. All other trades must work around the Architect’s prescribed fabrication dimensions to ensure the proper fit of the fire rated countertop.

• Not all laminates are approved for fire rated laminated countertops. Contact the manufacturer for a list of approved laminates.

• It is best to provide radius corners on the public/corridor side of the countertop when applicable to prevent injury to people walking by.

• Radius edges are recommended on the tenant side of the countertop.

• Adequate mounting support inside the fire rated wall must be provided by others to support the anticipated loads on the countertop.

• Face of Wall Mounting o The countertop must extend a

minimum of 6” into the room on the coil side of the door.

o The countertop must extend a minimum of 4” beyond each jamb on the sides of the door under the guides.

o For “T” shaped countertops, the countertop must extend through the opening at least to the face of the finish on the opposite coil side of the door.

o The fire rated wall at each jamb and below the countertop must align with one another.

• Between Jambs Mounting o The countertop must extend a

minimum of 6” beyond the centerline of the door curtain towards the coil side of the door.

• For “H” and “Offset H” shaped countertops, sometimes referred to as “I” shaped countertops, the overall width and height of the opening must allow for the installation of the countertop. The countertop must fit through the opening diagonally in order to be installed.

Options and Accessories

Locks There are various different types of locks available for different applications. Most types of locks are located on the bottom bar assembly to secure the door. The basic lock system is the slide lock which is mounted to the bottom bar and slides through a hole in the guide to secure the door. Cylinder locks use rods and guides to allow the lock rod to slide under an adjustable stop or through a hole in the guide assembly. Counter doors and gates may use a center lock at the middle of the bottom bar that locks to the floor or countertop. To prevent damage, doors with motor operators must be installed with an electrical interlock to prevent accidental operation while the door is locked.

Page 38: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

38

Weather Seals Weather seals are used to limit air infiltration around the perimeter of a rolling door. Typically, this is accomplished by utilizing a vinyl or a brush seal with a rigid retainer. These seals can be attached to the guides or to the jamb systems as required. Additionally, the bottom seal, or astragal, can be factory installed as part of the bottom bar assembly. For Fire Doors, contact the door manufacturer for guidance on the approval of auxiliary weather and smoke seals. Always drop test a fire door after adding any additional weather seals to ensure the seals do not interfere with the closing operation of the Fire Door.

Wearstrips Wearstrips are a component incorporated into the guide to reduce noise and wear from curtain rubbing during operation. These are made from smooth materials like plastic, felt, or wool pile and sometimes incorporate weather seals. They run the vertical length of the guides providing a barrier between the curtain and the guides anywhere the two come in contact. Wearstrips may be factory attached, clipped onto a guide as an accessory item in the field, or integrated into the guide profile itself.

Exterior Mounted Doors There are two primary differences between an interior and exterior mounted service door. The first is the slat orientation. With exterior mounted doors, the slats are oriented in a fashion to prevent water infiltration into the interior of the building. The second is that the operating mechanism and winding mechanisms are provided with a weather resistant enclosure to prevent damage from natural elements or are thru-wall mounted.

Fascia Panel A fascia panel is a finished metal cover used to conceal the opening which remains when the door height is less than the height of the opening. They are most commonly used on doors that are installed on under lintel applications, to cover the exposed side of the coil.

Brush Seal

Page 39: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

39

ANSI/DASMA 203 Standard for Non-Fire Rated Rolling DoorsAmong the primary activities of DASMA is the publication of standards for the Door and Access Systems industry. ANSI/DASMA 203 is a voluntary standard defining minimum design and performance requirements for non-fire rated rolling doors. This standard is outlined below to aid in understanding the performance requirements of rolling doors and related components. 1.0 Scope

1.1 This standard defines minimum design and performance specifications for non-fire rated rolling doors in commercial and industrial applications, consisting of assembled, interlocking slats of steel, stainless steel, or aluminum.

1.2 This standard for non-fire rated rolling door assemblies shall be intended to cover commercial and industrial type warehouses, factories and other facilities. Rolling doors intended for frequent use should be designed for high cycle operation. Refer to section 11.1.2.

1.3 This standard is not intended to cover doors such a rigid, folding or multi-leaf sectional type doors, fire-rated rolling doors, coiling doors without interlocking slats (sheet doors), perforated slat construction or special applications.

1.4 Without limitation, DASMA does not represent or imply that this standard relates to any component or system other than the rolling doors expressly identified and described herein.

1.5 See informational statements in Appendix A on important design and operation information.

2.0 Definitions – See Glossary of Terms at the back of this manual.

3.0 General 3.1 Windloads

3.1.1 Door system shall be designed to withstand a minimum wind load as required by the authority having jurisdiction over the geographic location where the door is to be installed. When required by the authority having jurisdiction, structural tests shall be in accordance with DASMA 206 or other accepted means required by the authority having jurisdiction.

3.1.2 Where resistance to windborne debris is required by the authority having jurisdiction over the geographic location where the door is to be installed, a door system shall meet the requirements of DASMA 205 or other accepted means as required by the authority having jurisdiction.

3.1.3 Exception: Counter shutter doors are not wind loaded.

4.0 Material Thickness 4.1 Metal gauge shall comply with

Figure 1. 5.0 Guide Assemblies

5.1 Guide assemblies shall contain the curtain edges throughout the door operation and under the required wind load.

5.2 Guide assembly design shall allow for installation variances in the distance between left and right guides of ±1/8 inch (3 mm) within the specified value provided by the door manufacturer.

5.3 Guide assemblies shall be constructed to support the total

Page 40: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

40

weight of the door and the wind loads transmitted by the curtain.

5.4 Guide assemblies shall include curtain stops on the guides to ensure the bottom bar stops at a designated position.

6.0 Curtains 6.1 Curtain slats shall interlock to allow

the full range of angular rotation required to wrap around the barrel assembly without binding or separation.

6.2 Curtains shall be designed to resist lateral motion.

6.3 Where windlocks are required, windlock construction, material and attachment to curtain shall be adequate to resist wind load.

6.4 When subjected to the provisions of Section 3.1, curtain performance shall be such that the door shall remain operable after removal of the wind load.

6.5 The attachment of the curtain to the barrel and curtain slats shall be designed to not pull apart when subjected to operating forces.

6.6 Steel slats shall conform to ASTM A653/A653M, G40 minimum zinc coating, with grade chosen by manufacturer to meet performance requirements set forth herein. Slats may be painted.

6.7 Stainless steel slats shall conform to ASTM A240 or equivalent.

6.8 Aluminum slats shall conform to ASTM B209, ASTM B221 or equivalent. Slats may be anodized.

6.9 Other materials and finishes contact manufacturer for availability.

6.10 Foam plastics used in insulated rolling doors shall meet requirements established by the authority having jurisdiction for flame spread and smoke development.

7.0 Bottom Bars 7.1 A bottom bar may incorporate an

astragal or sensing edge for motor operated doors.

7.2 A bottom bar shall be designed to incorporate locks that engage at one or both ends of the bottom bar. If a locking mechanism is incorporated on a motor operated door, one of the following shall be installed: 7.2.1 An interlock switch, or switches,

activated by the lock mechanism.

7.2.2 An operator with the ability to sense either torque or starting current to the motor.

8.0 Brackets 8.1 Brackets shall be designed to

support the weight of the barrel assembly and the total curtain assembly weight.

9.0 Hoods and Hood Baffles 9.1 Hoods, when specified, shall be

constructed with gauge thickness in accordance with figure 1.

9.2 A hood, or hood fasteners, shall not be in contact with the curtain during any position of the door.

9.3 A hood baffle (when required) shall maintain full-width contact with the curtain when the door is closed.

9.4 A hood baffle shall not hinder operation of the door.

10.0 Fascia 10.1 Metal Fascia, when specified, shall

be constructed with gauge thickness in accordance with Figure 1.

11.0 Barrel Assemblies 11.1 Torsion Springs

11.1.1 Helical wound spring wire shall comply with ASTM A229 or equivalent.

11.1.2 Springs shall be designed for a minimum of 10,000 cycles of operation. Higher cycle life may be specified.

11.1.3 The selection of wire size relative to coiled diameter shall be such that mean coil diameter is at least six times the wire diameter.

11.2 Spring Anchors

Page 41: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

41

11.2.1 Spring anchors, shall be designed to withstand the radial and lateral forces exerted by the torsion spring to properly retain the spring when fully wound or unwound and allow the application of torque.

11.3 Pipe Deflection 11.3.1 The deflection of the pipe,

with the weight of the curtain and counterbalance assemblies applied, shall not exceed .03 inches per foot of length while supported only on both ends.

12.0 Tension Wheels 12.1 Tension wheels and locking

mechanism shall be designed with sufficient strength to withstand the maximum torque from torsion springs, and/or winding devices.

13.0 Operation 13.1 A door normally operated by chain

hoist shall not require more than 35 pounds (156 N) of force to operate the door.

13.2 A door normally operated by using a crank shall not require more than 25 pounds (111 N) of force to operate the door.

13.3 A door normally operated by manually pushing up the door shall not require more than 30 pounds (134 N) of force to operate the door. Recommended maximum door size shall be 80 square feet (7.44 square meters), recommended maximum door width shall be 10 feet (3.05 m), and recommended maximum door height shall be 8 feet (2.44 m).

14.0 Installation and General Operation 14.1 The door manufacturer shall furnish

standard details and instructions for proper installation and general operation. Such instructions shall include warnings relative to the installation and general operation of the door.

15.0 Maintenance

15.1 The door manufacturer shall furnish a list of components requiring regular maintenance, with instructions on and frequencies for such maintenance.

16.0 Labels 16.1 Each door shall be labeled to identify

the name and address of the door manufacturer.

16.2 DASMA labels RDD-201 and RDD-202 shall be placed on the door as described in TDS-267 16.2.1 Labels in accordance with

the applicable provisions of ANSI-Z535.1, ANSI-Z535.3, ANSI-Z535.4, shall be placed on the door.

Appendix A: Informational Statements A.1 Most rolling doors with windlocks cannot be

operated when wind load engages the

windlocks, due to the sliding friction of the

curtain within the guides. Contact the

manufacturer for special requirements.

A.2 Loads are imposed onto the building structure

from two sources: Wind load and door weight.

Wind loading can produce substantial catenary

forces in rolling doors as a result of the

locking action of the curtain edges within the

guides. The jambs must be designed to

withstand these loads. These loads are in

addition to those created by the direct wind

pressure and weight of the door assembly. The

magnitude and direction of these loads should

be obtained from the manufacturer. DASMA

Technical Data Sheet TDS-251 may be used

to state these loads.

A.3 After being subjected to wind loading, rolling

doors may retain some curvature in the

curtain, particularly on narrow doors.

A.4 Calculations for overall performance and

pass/fail prediction of the door system are well

established. Detailed stresses in the curtain

slats under wind loads cannot be calculated

accurately since the large-deflection of these

parts invalidates the assumptions used to

derive common engineering formulae.

A.5 Manual operation of rolling doors (push up,

hand chain or crank to open) is generally

Page 42: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

42

heavy in the bottom half to two-thirds of door

travel and light for the top third. Refer to

DASMA Technical Data Sheet TDS-272 for

additional information.

Page 43: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

43

ANSI/DASMA 204 Standard for Fire Rated Rolling Door AssembliesAmong the primary activities of DASMA is the publication of standards for the Door and Access Systems industry. ANSI/DASMA 204 is a voluntary standard defining minimum design and performance requirements for fire rated rolling door assemblies. This standard is outlined below to aid in understanding the performance requirements of rolling fire doors. 1.0 Scope

1.1 This standard defines minimum design and performance specifications for fire rated rolling door assemblies in commercial and industrial applications, consisting of assembled, interlocking slats of steel or stainless steel. Refer to individual manufacturer’s listings.

1.2 This standard for fire rated rolling door assemblies is intended to cover commercial and industrial type warehouses, factories and other facilities where a service counter fire door, fire shutter or fire door is required to close an opening in a firewall during an emergency. Rolling fire doors intended for frequent use should be designed for high cycle operation. Refer to section 13.1.2.

1.3 This standard is not intended to cover doors used for egress passage, nor other types of doors such as rigid, folding or multi-leaf sectional type doors, coiling doors without interlocking slats (sheet doors), perforated slat construction or special applications.

1.4 Without limitation, DASMA does not represent or imply that this standard relates to any component or system

other than the rolling doors expressly identified and described herein.

2.0 Definitions – See Glossary of Terms at the back of this manual.

3.0 General 3.1 A rolling steel fire door assembly shall

retard the passage of fire through a wall opening and the assembly shall include a Fire Protection Rating, an Automatic Closing Device and a Governor.

3.2 Fire endurance testing shall be in accordance with NFPA 252 Fire Test of Fire Door Assemblies.

4.0 Labels 4.1 Fire door assemblies that have been

tested shall bear a label attached to the bottom bar, which indicates that the door has been fire tested, for the size opening in the wall in accordance with the listing agency requirements. Fire door assemblies over the size opening tested shall be provided with an oversize label or oversize certificate.

4.2 Oversize label may be attached to the bottom bar of a fire door, which indicates that the oversize door has not been fire tested, but the door has been manufactured in accordance with the listing agency requirements.

4.3 Oversize certificate document may be provided by a recognized listing agency, which indicates that the oversize fire door assembly has not been fire tested, but the door has been manufactured in accordance with the listing agencies requirements. The oversize certificate may be provided in lieu of an oversize label.

4.4 Each door shall be labeled to identify the name and address of the door manufacturer.

4.5 DASMA labels RDD-200, RDD-201, and RDD-202 referenced in DASMA TDS- 267, shall be placed on the door. 4.5.1 Warning labels in accordance

with the provisions of ANSI-Z535.1, ANSIZ535.3, ANSI-

Page 44: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

44

Z535.4, shall be placed on the door.

5.0 Material Thickness 5.1 Metal gauge shall comply with the

manufacturer’s Label Procedure and with Figure 1.

6.0 Automatic Closing 6.1 The fire door shall include an automatic

closing device. 6.2 In the event of fire, the fire door shall

descend automatically to the completely closed position.

6.3 The door descent shall be at a controlled rate, not less than 6 in/sec nor greater than 24 in/sec.

7.0 Guide Assemblies 7.1 Guide assemblies shall contain the

curtain edges throughout the door operation.

7.2 Guide assembly design shall allow for installation variances in the distance between left and right guides of ±1/8 inch (3 mm) within the specified value provided by the door manufacturer.

7.3 Guide assemblies and fastener location shall be designed to allow for thermal expansion.

7.4 The guide assemblies shall be constructed to support the total weight of the door and loads transmitted by the governor and motor (if supplied).

7.5 Guide assemblies shall include curtain stops on the guides to ensure the bottom bar stops at a designated position.

7.6 Crush plates shall be installed when fire doors are mounted to hollow concrete masonry units.

8.0 Curtains 8.1 Curtain slats shall interlock to allow the

full range of angular rotation required to wrap around the barrel assembly without binding or separation.

8.2 Curtain shall be designed to resist lateral motion.

8.3 The attachment of the curtain to the barrel and curtain slats shall be designed to not pull apart when subjected to operating forces.

8.4 Steel slats shall conform to ASTMA653/A653M, G40 minimum zinc coating, with grade chosen by manufacturer to meet performance requirements set forth herein. Slats may be painted.

8.5 Stainless steel slats shall conform to ASTM-A240 or equivalent.

8.6 The door manufacturer’s listing may be referred to for other materials and finishes.

9.0 Bottom Bars 9.1 The bottom bar may incorporate an

astragal or sensing edge for motor operated doors.

9.2 The bottom bar may be designed to incorporate a locking mechanism that engages at one or both ends of the bottom bar. If a locking mechanism is incorporated on a motor operated door, one of the following shall be installed: 9.2.1 An interlock switch, or switches,

activated by the lock mechanism. 9.2.2 An operator with the ability to

sense either torque or starting current to the motor.

9.3 The bottom bar may bear a (¾, 1½, 3, 4) hour fire protection-rating label, from a recognized listing agency, indicating that the door has been manufactured in accordance with the listing agency requirements.

10.0 Brackets 10.1 Brackets shall be designed to

support the weight of the barrel assembly and the total curtain assembly weight.

10.2 Brackets shall be designed to incorporate an automatic closing device.

11.0 Hoods and Hood Flame Baffles 11.1 A metal hood shall be designed to

enclose the coiled curtain. 11.2 A hood, or hood fasteners, shall

not be in contact with the curtain at any position of the door.

11.3 A hood flame baffle (when required) shall actuate through fusible links or other automatic means. These

Page 45: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

45

links may be independent of the links that deploy the automatic closing device. When deployed, the baffle shall maintain full-width contact with the curtain when the door is closed.

11.4 A hood flame baffle shall not hinder operation of the door.

12.0 Fascia 12.1 Fascia shall be designed to

enclose the exposed partial or no header in the back of the door coil. Standard for between jambs mounted doors.

13.0 Barrel Assemblies 13.1 Torsion Springs

13.1.1 Helical wound spring wire shall comply with ASTM-A229 or equivalent.

13.1.2 Springs shall be designed for a minimum of 10,000 cycles of operation. Higher cycle life may be specified.

13.1.3 The selection of wire size relative to coiled diameter shall be such that mean coil diameter is at least six times the wire diameter.

13.2 Spring Anchors 13.2.1 Spring anchors, shall be

designed to withstand the radial and lateral forces exerted by the torsion spring to properly retain the spring when fully wound or unwound and allow the application of torque.

13.3 Pipe Deflection 13.3.1 The deflection of the pipe, with

the weight of the curtain and counterbalance assemblies applied, shall not exceed .03 inches per foot of length while supported only on both ends.

14.0 Tension Wheels 14.1 Tension wheels and locking

mechanism shall be designed with sufficient strength to withstand the maximum torque from torsion springs, and/or winding devices, and impact load when applicable.

15.0 Operation 15.1 A door normally operated by

chain hoist shall not require more than 35 pounds (156 N) of force to operate the door.

15.2 A door normally operated by using a crank shall not require more than 25 pounds (111 N) of force to operate the door.

15.3 A door normally operated by manually pushing up the door shall not require more than 30 pounds (134 N) of force to operate the door. Recommended maximum door size shall be 80 square feet (7.44 square meters), recommended maximum door width shall be 10 feet (3.05 m), and recommended maximum door height shall be 8 feet (2.44 m).

16.0 Installation and General Operation 16.1 The door manufacturer shall

furnish standard details and instructions for proper installation and general operation. Such instructions shall include warnings relative to the installation, general operation testing and resetting of the automatic closing device of the door. A drop test form (see DASMA TDS-271) shall be provided to certify that door operates and been tested in accordance with the manufacturer installation.

16.2 Installation of door and accessories and fusible link routing shall be in accordance with NFPA 80, DASMA TDS-254 and DASMA TDS-255.

16.3 Installation of detectors shall be in accordance with NFPA 80, NFPA 72 and DASMA TDS-254.

17.0 Maintenance 17.1 The door manufacturer shall

furnish a list of components requiring regular maintenance, with instructions on and frequencies for such maintenance.

17.2 The door shall be tested at least annually per NFPA 80.

Page 46: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

46

Appendix A: Informational Statements

A.1 Manual operation of rolling doors (push up, hand chain or crank to open) is generally heavy in the bottom half to two-thirds of door travel and light for the top third. Refer to DASMA Technical Data Sheet TDS-272 for additional information.

Page 47: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

47

Section Four

Types of Rolling DoorsWhen referring to rolling door products, the term door is sometimes generically used to refer to any types of rolling products; such as rolling service doors, rolling counter doors and rolling grilles. This certification is not intended to cover specialty rolling doors such as sheet doors, high performance doors, etc. as explained in the specialty applications section. The primary purpose of a door is to provide access control to certain areas within and around buildings.

Rolling Service Door Rolling service doors generally consist of interlocking slats, a double angle bottom bar, guides, a barrel assembly with a counterbalance mechanism, support brackets, and a hood. These units can be designed to close small to very large openings. Rolling service doors can be used for both vehicular and pedestrian opening applications that are not a required means of egress.

Rolling Counter Door Rolling counter doors consist of the same components as rolling service doors but are generally of a smaller scale utilizing a smaller slat profile to make up the curtain and smaller guides normally configured of lighter material.

Rolling counter doors typically close on sill angles or countertops. They may also run full height of an opening and close on the floor.

Rolling Grilles A rolling grille is an upward acting, rolling gate, offering security while maximizing air circulation, light infiltration and visual access. They are widely used in shopping malls and parking areas. Grilles are made from galvanized steel, stainless steel or aluminum rods and links laced together to make the curtain. Rods can be solid or hollow and assembled with the links into various patterns and pattern sizes. They can have optional clear inserts laced into the curtain for added security. The other components to the rolling grille are similar to those used in other types of rolling service doors.

Types of Fire Rated Rolling Doors

Fire-Rated rolling doors have a specialized set of requirements and require a highly technical and specialized knowledge of fire-rated door specific information. It is important for a technician to recognize the difference between a non-fire-rated door and one which carries a fire rating.

Page 48: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

48

Rolling Fire Door A rolling fire door is a fire door assembly consisting of a curtain, bottom bar, barrel, guides, brackets, hood and an automatic closing device. These doors can be very similar to Rolling Service Doors but are designed to close automatically when a fire is detected. Specialty drop out mechanisms and automatic closing devices are added along with sash chains or cable routings to activate the closing motion of the door in the event of a fire. Fire rating and listing agency marks will be identified on the bottom bar of the door.

Rolling Counter Fire Door Rolling counter fire doors consist of the same components as rolling fire doors but are generally of a smaller scale utilizing a smaller slat profile to make up the curtain and smaller guides normally configured of lighter gauge bent steel shapes. The maximum size opening in a firewall these units protect is much smaller than rolling steel fire doors. The maximum width is about sixteen feet and the maximum height is about ten feet. Rolling steel counter fire doors may close on sill angles or other non-combustible sills or on factory built labeled countertops. They may also run full height of an opening and close on the floor. Installation is covered in NFPA 80, chapter 6. Rolling counter fire doors can also be used to close conveyor openings or pedestrian type openings that are not a required means of egress. Some manufacturers refer to counter fire doors as fire shutters. A fire shutter is defined in NFPA 80 as a labeled door assembly used for the protection of a window opening in an exterior wall. The construction of fire shutters is defined as fire doors without glass lights and

can be a swinging door, a horizontal or vertical sliding door or a rolling steel door. Installation is covered in NFPA 80, Chapter 10. Operation shall be in accordance with the requirements of rolling doors.

Service Counter Fire Door A labeled fire door assembly used for protection of openings in walls where the primary purpose of the opening is for non-pedestrian use, such as counter service for food, a pharmaceutical dispensary, packaging and baggage transfer, or observation ports. These doors can be very similar to Rolling Counter Doors but are designed to close automatically when a fire is detected. Like rolling fire doors, specialty drop out mechanisms and automatic closing devices are added along with sash chains or cable routings to activate the closing motion of the door in the event of a fire. Fire rating and listing agency marks will be identified on the bottom bar of the door.

Conveyor Openings In many instances, rolling fire products and smoke control products are used to close off fire rated wall openings that contain a conveyor system passing through the opening. Two very important issues need to be considered when supplying and installing conveyor opening fire rated products:

1) The rolling fire product must completely close off the opening.

2) Conveyor design provisions need to ensure that the curtain will fully close in a fire emergency and not get jammed on product moving through the opening.

Page 49: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

49

The best way to completely seal off a conveyor opening is to design the fire product to close to the floor in-between two separate conveyor belts. Depending on the size of materials that will be running on the conveyor belts, the size of the slot between the conveyor belts will be critical. Special bottom bar designs may be available from the rolling door manufacturer that will help minimize the required slot between the conveyors. This needs to be coordinated early in the project with the conveyor and fire door suppliers. It may also be acceptable to have fire rated walls built up to the height of the conveyor belt to close off the gaps at the sides of the conveyor and have the fire rated rolling door come to rest on top of the conveyor and built up side walls. This set up would need prior approval with the Authority Having Jurisdiction. Special planning is required to ensure that the curtain will fully close upon automatic closing. Some ways to accomplish this are:

• Utilize a fire door operator that is signaled to close by the conveyor system program logic. The fire alarm signal is detected by the conveyor system program logic, which will not activate the door to close until the conveyors run and clear the opening of any material.

• If the material running on the conveyor is consistent in size and spacing, more than one rolling fire door can be positioned within the opening to assure that at least one of the fire doors will clear the material and fully close to protect the opening.

No matter how fire doors are set up on conveyor openings, planning to accomplish full closure in a fire emergency is critical.

Specialty Applications

There are many specialty and custom design applications in the commercial rolling door industry. While some of these share some or all of their components in common with rolling

doors, many of them would require their own complete training manual. Fire-Rated Rolling Steel Doors, for example, already have a separate certification due to the complex nature of these products. Some of these specialty applications are outlined in this section. It is important for a certified technician to be aware of these specialty applications and seek the appropriate training when they are encountered.

Pass Door A pass door, sometimes called a wicket door, is a hollow metal pedestrian door integrated into the rolling door assembly. The frame is hinged at the jamb, so the door frame swings out of the opening. The leading edge of the pass door also incorporates a vertical section of guides which the rolling door lowers into. The pass door can be located at the right or left side of the opening and may swing in or out. This option should not be used in high wind environments and must incorporate an interlock on motorized doors so that the door is not lowered without the pass door frame locked into place.

Wood Rolling Doors These are typically used in counter door applications. The curtain, hood, and bottom bar are made of wood while the remaining parts are those of a standard counter door. Wood rolling doors are available in a variety of different wood species and finishes.

Page 50: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

50

Combination Doors Combination doors, sometimes called superimposed doors, utilize a dual track system that allows two doors to be used in the same opening. This type of system is used to combine two different door types. The most common example is the combination of a rolling grille and a rolling service door to allow air flow while maintaining security. Typically, the exterior door utilizes a solid slat construction, while the interior door is a fenestrated door or rolling grille.

Sloped Bottom Bar An optional bottom bar is available that is tapered to match the slope of the floor to help to seal when the sill of the opening is not level. Sloped bottom bars are made by inserting a tapered plate between the bottom bar angles. This tapered plate will hang into the opening on the low side when the door is opened unless the door height is increased, and the coil is raised to clear the opening.

Side Coiling Doors Side coiling doors have a unique application and can be used in tight overhead applications. Side coiling doors come in solid and grill design and allow for a combination of patterns not available in the coiling door. The doors are installed with an overhead track allowing for the door to free hang. These doors can be used as single sliding or bi-parting when needed for larger opening widths. In wider applications a side coiling door may use both a top and bottom track. These types of doors are typically motor operated and can include other options normally associated with other rolling door products.

Side Folding Grilles Side folding grilles are accordion style folding doors which slide into the sides of the opening and stack into a pocket in the wall. These are similar to rolling grilles, but the rods and links are turned sideways, and the curtain hangs on a track at the top of the opening. The track can be straight or curved to close most openings. These doors do not roll around a barrel when opened, but instead fold back and forth accordion stile until the opening is clear. These doors are popular in airports and office buildings where security is desired, but overhead space is not available for the coil of a rolling grille.

Integral Frame Doors Available in wood, steel, and stainless steel, integral frame doors incorporate the entire door and opening framing into one including sill,

Crane Door

Interior Elevat ion

Vent ilated Service Doors

Interior Elevat ion (Fenestrated Door)

Perforated Door

Page 51: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

51

jambs, header, fascia, and complete door assembly. Integral Frame Doors are factory assembled and are installed as the wall is built. These are most commonly used in food service counters.

Sheet Doors Sheet doors are vertically operating, coiling doors typically used in commercial, industrial or self-storage applications, with a curtain consisting of formed metal sheets seamed together into one continuous sheet curtain. The continuous sheet curtain is rolled up around an axle assembly when the door is open. Sheet doors are similar to rolling service doors but are typically more economical and are generally limited to smaller openings.

Horizontal Doors Horizontal doors are similar to normal rolling service doors, but they are turned so that the curtain covers openings in horizontal and inclined planes. These are often used to cover skylights and pit openings. The tracks can be straight or curved to match the contour of the opening.

High Performance Doors High Performance Doors are rolling, folding or sliding non-residential doors, generally characterized by higher cycles and/or higher speeds, typically made-to-order, and designed for higher or special types of durability. The most common of these are high speed rolling doors which are designed to travel faster than 30 inches per second. These doors utilize special designs which vary tremendously from one manufacturer to the next.

Crane-way Doors Another type of specialty door is a crane-way door. These doors get their name from their most common application, closing openings along bridge cranes. The lower portion of the curtain is a shorter length than the upper portion to fit between the structural beams of the crane. When open, these doors allow passage of a bridge crane from the inside to the outside of a building.

Mullions Mullions are a combined guide assembly joining two adjacent rolling doors. Mullions may be stationary or removable. Removable mullions may be mechanically or motor operated where the center guide is hinged to lift up and out of the way, or slide to the side of the

Page 52: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

52

opening, to expose a full opening width when all of the doors are open. Mullions are used in very wide applications where the width of the opening may be too large for a single door. Another application they are common in is airport hangar doors, where it may be desirable for the center opening to be taller than the outer openings.

Page 53: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

53

Section Five

Methods of OperationRolling doors can be operated many different ways. Specification of the type of operation must consider door size, head room, side room, how often the door will be operated, cost, available power supply, etc. – just to name a few. Proper specification of type of door operation can play a large role in pleasing the customer and should be addressed in advance of ordering the door. Rolling fire doors are designed to provide a rated degree of fire protection and possibly smoke control, but when desired, they can also be regularly used to provide opening access control, security or weather resistance, even though these functions are not the primary design intent. Rolling fire doors are required to have an automatic closing system. This means an emergency signaling device will cause the door to close, either mechanically or electrically. In addition to the automatic closing system, some fire products have some type of operation that allows for normal door use. Generally, the normal use and automatic closing system operators work independent of one another. For detailed information on available automatic closing devices, see the automatic closing devices section of this manual. This section will detail different methods of operation for rolling doors. The methods of operating rolling doors that will be addressed are:

1. Manual Push-up Operation 2. Manual Chain Hoist Operation 3. Manual Hand Crank Operation 4. Electric Operator

If the door is to be mechanically operated, it is also necessary to determine the hand of operation before ordering the door. That is, when facing the door from the coil side, should

the door be operated from the left or from the right? The hand of operation should be selected to avoid known field obstructions and be convenient to the building traffic pattern and end users. Depending on the environment, it may also be necessary to consider the overall appearance of the operating mechanism. Fire shutters sometimes require the operator to be concealed for improved appearance. Proper specification of hand of operation can reduce time and headaches during installation.

Manual Push-Up Operation Manual Push-Up Operation is the simplest method of operation which involves manually lifting the door from the closed position and pushing it up to the open position. Push-Up operation requires that the effort to operate the door at any point of travel will not exceed 30 lbs of force. The maximum size of a given door will vary based upon curtain weight and counterbalance design, but generally will not exceed 10-feet in width. Although a pull down/pushup pole or rope can be utilized for doors up to around 10-feet high, push-up operation is not normally recommended for doors over 7 foot 6 inches high due to the reach limitations of the average height person. Lift handles are usually attached to the bottom bar to provide a point of operation. Extra effort fine tuning spring tension at installation will help to ensure lower lift efforts. Manual push-up operation may be considered somewhat beyond the size limits listed above when a fire rated product is going to remain open and only close in the event of a fire emergency. For these applications, size limit will be determined based on manufacturer ability to counterbalance the door so that operating effort will not exceed 40 pounds of lifting force. This is an economical consideration to obtain fire protection on a

Page 54: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

54

given opening, for both upfront cost and for easier testing when compared with other manually operated doors. But, one must be cautioned of the possibility that the end user will want to close off the opening daily at some time in the future and has a door that is not safe to regularly operate!

Manual Chain Hoist Operation Manual Chain Hoist Operation is a low-cost alternative to operate larger, heavier doors. A mechanism is attached to the door and a hand chain hangs down next to the opening for people to use to operate the door. As a person pulls the hand chain, the barrel rotates and begins to move the door. With the use of reduction gearing, chain hoist operation can be used within, and well beyond the size limits of manual push-up operated doors. These provide a mechanical advantage that reduces the amount of force required to operate the door. The manufacturer will select a chain hoist mechanism with a reduction gearing ratio based on the spring torque imbalance of the specific door so that the operating force on the hand chain will not exceed 35 pounds. Chain hoists are typically used in applications that do not involve frequent operation. Chain Hoist operation can be split into three types:

Direct Drive Chain Hoists These hoists install directly to the door shaft or barrel assembly. The hand chain is mounted to a large diameter chain wheel. One revolution of the door requires one revolution of the hoist wheel. The size of the chain wheel affects the amount of force required, i.e., for a given door, a small diameter hoist wheel will require a greater force to open the door then a larger diameter wheel. Direct drive hoists are typically limited to smaller doors due to the small

mechanical advantage provided by the 1 to 1 ratio. Direct drive chain hoists are rarely used on Fire Doors because additional mechanisms are usually required to disengage the hoist for automatic closing of the door.

Reduced Drive Chain Hoists These are typically mounted to the support bracket and are connected to the door through gears or roller chain sprockets. The mechanical advantage is provided by sizing the gears or sprockets to provide a single reduction. Typical reductions are in the range of 4 to 1. This means that 1 revolution of the door barrel requires 4 revolutions of the hoist wheel. Reduced drive chain hoists can lift heavier doors then direct drive chain hoists, but this is achieved at a cost as these hoists take more pulls of the hand chain to open the door.

Compound Reduction Chain Hoists These hoist mechanisms are larger versions of the reduced drive chain hoists. These are used for very heavy doors and involve multiple gears and/or sprockets to provide increased reduction. These often require auxiliary bracket plates for mounting the extra gears/sprockets to the door. The most common compound reduction chain hoist is the double reduction hoist. In the double reduction hoist, the chain wheel is fixed to a small sprocket. Roller chain connects the small sprocket to a larger

Page 55: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

55

sprocket on an auxiliary hoist shaft. The larger sprocket is fixed to another small sprocket which is connected to a large sprocket on the door shaft using roller chain. The greater the difference in the number of teeth of the small sprockets vs. the large sprockets, the greater the total reduction. The larger the reduction, the slower the door will operate, and the more hoist revolutions required to open the door. Compound reduction hoists are only recommended for doors that are not operated on a regular basis.

Chain Hoist Mounting Locations Chain hoists can be mounted in a variety of locations to suit the installation conditions. Hand of Operation, Side Room, Head Room, and hand chain location must all be considered before the door is manufactured. The most common location for chain hoists is bracket mounted. In this mounting, the hoist is on the outboard side of the operator bracket. The hoist is usually attached to a dropout mechanism which disengages the chain hoist when a fire actuation closure occurs. This is the preferred hoist mounting location because it simplifies the connection to the door and does not rely on unknown field conditions for mounting. Chain hoists can also be wall mounted when side room is limited or if there are obstructions that would interfere with the standard bracket mounting location. Wall mounted chain hoists attach directly to the wall and are connected to the door dropout mechanism with roller chain and sprockets. When it is necessary for the chain hoist operation to be provided to the opposite coil side of the door, Thru-Wall mounted chain

hoists are used. Thru wall chain hoists have a wall mounted hoist on opposite coil side of the door and an idler bracket assembly on the coil side of the door. Roller chain is run from the hoist, through the wall to the idler bracket and then to a sprocket on the door dropout mechanism.

Manual Hand Crank Operation Another mechanism available for operating rolling doors is manual hand crank. Crank operation is most frequently used on counter doors but can be used on other types of rolling doors as well. Manual hand crank operation can be awning crank style (mounted directly to the door drop out mechanism), or wall mounted style. Awning cranks work using worm gearing connected to the drive mechanism at the bracket. Wall mounted cranks typically mount a crank box to the wall and connect to the door using roller chain sprockets. With the use of a reduction gearing crank box, manual hand crank operation can be used within and beyond the size limits of manual push-up operated doors. The manufacturer will select a crank box and a reduction ratio based on the spring torque imbalance of the specific door so that the operating force on the hand crank will not exceed 25 pounds. The larger the door and greater the reduction, the more you will have to rotate the crank to open the door. Crank operation is generally selected

Awning Crank

Wall Crank

Page 56: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

56

over chain operation when doors are installed in more finished applications or when access to the bottom bar prevents manual push-up operation, such as deep countertop units. Manual cranks provide large reductions, typically around 20 to 1, which make the door very easy to operate. Hand crank will not be desirable on larger size doors that will be used frequently due to the many rotations of the crank required to open the door. A crank rod can be suspended from the bracket, mounted to the wall, or be removable so it can be used to engage the crank mechanism but be stored away out of sight when not in use. The crank rod is designed to spin in your hand, similar to a car scissor jack, which makes the many rotations required to open the door more manageable. Use caution to remove any crank rods before drop testing a door.

Electric Operators For the purposes of this text, an automated door system consists of a rolling door, an electric door operator, control equipment to interface with the door operator, and safety equipment to protect people and property. A large variety of electric operators and controls are available for safe and convenient operation of any size rolling door. A rolling door is a large, heavy object that can be moved with the help of an electric motor. A moving door can cause serious injury or death. The safety and wellbeing of others depends on the design and installation of a safe system.

The door itself must be properly balanced, aligned, and work freely and smoothly by hand. The door operator is not intended to operate a poorly installed, improperly balanced, or worn-out door. The use of a door operator to attempt to compensate for any door defect can result in a dangerous situation. In many instances, electric motor operators also function as part of a fire door automatic closing device. Due to the safety and convenience of testing and resetting that fire door operators offer, multi-function fire door operators should be considered whenever an electric operator is utilized with a fire rated door. For detailed information on available fire door operators that provide automatic closing device features, see the automatic closing devices section of this manual.

Automatic Operators It is important to select the proper door operator type. Emergency manual door operation, which could make a difference between life and death in the event of an emergency, should be a consideration on every system. Smaller doors generally require small, light duty operators whereas larger doors require large, heavy duty operators with special features like friction brakes and delay start. This is reflected in the standard features of the operators designed for these doors. Remember, mismatch or improper selection between door and operator can result in a malfunctioning or dangerous system.

Operator Usage Both the door and the door operator must be designed to stand up to the intended use of the system. For example, a door that opens and closes 25 times an hour cannot use an operator designed for limited duty cycles. Generally speaking, operators that utilize worm gear reduction systems will stand up to high frequency usage better than belt-reduced

Removable

Crank Rod

Page 57: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

57

operators. Continuous duty motors will last longer than limited duty motors. In frequent use applications, always use three phase power, if available at the job site, since three phase motors generally out-perform single phase motors. Three phase operators also use fewer amps which can save on electric consumption.

Operator Size The available sizes of electric operators range in power from 1/4 horsepower mini-operators to industrial duty 5 horsepower or larger operators. Electric operators utilize high reduction gearboxes making them capable of lifting very large doors, while allowing average door operating speed of approximately 8 inches per second. Door size area charts can be used to aid in the proper selection of an operator. However, these charts are only estimates and can vary widely based on the door manufacturer’s door design. Always consult the door manufacturer for recommendations when issues arise with operator selection. The door size area charts can be used with caution to determine the required operator horsepower. A sensing device is recommended with all electrically operating units, but an approved monitored sensing device is required when activation is other than constant pressure to close. This includes any operator that utilizes momentary contact push buttons, keyless entry, phone entry system, or that can be remotely signaled to electrically close. The UL 325 Standard also requires that all moving operator components that create possible pinch points below 8 feet above floor level be covered. See Electric Operator Compliance with UL 325 section for complete details on these and other requirements. Operator selection also involves taking door speed into account. Door speed can be adjusted by changing the size of the sprockets driving the door. For example, a door with a 24-tooth sprocket on the drive shaft of the door

will go twice as fast as a door with a 48 tooth drive sprocket. Adjustments to door speed must be made with caution as they directly impact the amount of torque on the operator. Careless adjustment to door speed could result in premature operator failure, roller chain breakage, shaft failure, etc. Consult the manufacturers as needed to ensure the door and operator will support any desired speed modifications. Average door speed, in inches per second, can be estimated using the formula: Door Speed = (RPM x TT x MT) / (60 x DT x WR)

Where RPM is the revolutions per minute of the motor output shaft, TT is the total travel of the door in inches, MT is the number of teeth on the motor sprocket, DT is the number of teeth on the door sprocket, and WR is the working revolutions of the door, or the number of times the barrel turns while the door is being opened. Safe door speeds range from 6 to 12-inches per second. Over-sizing an operator for rolling doors can be dangerous. Startup torques for larger operators can be too much for a door to handle if it has not been designed to accommodate it. Selecting an operator that is too big can cause premature door failure, such as a twisted drive shaft, bent brackets, broken roller chain, broken gear teeth, etc. Consult the manufacturer for operator size recommendations for specific doors.

Operator Mounting Locations As with chain hoists, rolling door operators have a variety of installation locations available to suit the field conditions of the job. Operators can be bracket mounted vertical, top of hood mounted, bracket mounted horizontal, wall mounted, thru-wall mounted, and Tube Mounted. Other special operator mounting locations may be available for extraordinary

Page 58: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

58

field conditions. Consult the door manufacturer when these conditions arise. The most common operator mounting location is bracket mounted vertical, also known as Front-of-Hood Mounted. Bracket mounted vertical operators mount to an operator support plate that is bolted or welded directly to the door support bracket. The operator is oriented up and down with the operator output shaft parallel to the lintel. The operator support plate typically has slots for adjusting the roller chain tension by tilting the operator towards the door for less tension and away from the door for more tension. Bracket mounted operators are preferred because they take away the uncertainty of unknown field mounting conditions by providing a self-contained operator mounting arrangement with predetermined roller chain lengths.

Another common operator mounting location is Top-of-Hood Mounted. In this installation, the operator is turned horizontal and mounted directly to the door support bracket above the hood. Top-of-Hood mounted is typically used to reduce the projection of the door from the header in order to avoid obstructions. It’s also commonly used on shorter doors to lift the operator out of reach to improve safety and avoid tampering.

Bracket mounted horizontal operators, sometimes called Bench Mount, are used when head room and side room are limited. The operator is turned horizontal, perpendicular to the opening protruding out in front of the door. This mounting location typically requires an operator modification to relocate the control box and a special mounting plate with additional reinforcement to support the weight and operational loads of the cantilevered operator. Rolling door operators can be wall mounted when field conditions provide adequate side room. The operator either mounts directly to the wall, or mounts to a wall mounting support plate, above or below the door bracket. The optimum distance from the center of the motor shaft to the door drive shaft is 12 to 15 inches. Wall mounting provides additional flexibility for operator location in the field and is frequently used when obstructions would interfere with bracket mounted operator locations. For exterior mounted doors with electric operation, a typical operator mounting location is thru-wall mounted. Thru-wall mounted operators allow the operator to be installed on the wall opposite the coil side of the door. The operator is mounted directly to the wall or to a wall mounted operator support. The operator drive chain then goes through the wall to an auxiliary idler assembly, and then connects to the drive mechanism of the door.

Page 59: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

59

Thru-Wall mounting is usually used to keep the operator out of the outside elements when field conditions do not permit the door to be interior mounted. Another type of rolling door operator is a tube motor. Tube motors typically install inside the barrel assembly of the door. The motor head is bolted directly to the support bracket of the door when installed. The motor turns the barrel to cause the door to operate and may be used with, or without springs. Tube motors provide a clean looking installation without visibility of the operator. The down side to tube motors is that any servicing needed to the operator usually requires the door curtain and barrel to be uninstalled.

Emergency Egress Emergency egress is a special operator and door design most typically encountered on rolling grilles. Emergency egress provides an emergency release lever on the wall near the door that disconnects the door operator. The door is over-sprung at the floor so that when the operator is released, the door opens on its own. This provides quick opening of the door for people to escape in the event of an emergency. Early versions of these doors were designed to only open to around 36” off the floor. More recent versions are now designed to fully clear the opening on their own when activated. Many codes require that a minimum of one grille on every retail storefront have this modification. Operator selection is limited to those operators which are compatible with the Emergency Egress option. It is important to specify this requirement in advance of ordering the door so that the manufacturer can adjust the spring design to account for it. Attempting to achieve this modification in the field on a door not designed for it will result in an unsafe

condition and dramatic reduction in the cycle life of the door or premature spring failure. Care must be taken when servicing Emergency Egress doors because disconnection of the operator and/or roller chains can result in rapid upward acceleration of the door due to the over-balanced condition. The internal resistance of the operator acts as a break to prevent the door from moving while engaged. Always service Emergency Egress doors in the open position and with the curtain and bottom bar adequately restrained from movement.

Electric Operator Compliance with UL 325 ANSI/UL 325 Safety for Door, Drapery, Gate, Louver, and Window Operators and Systems is a standard which defines certain safety requirements pertaining to commercial rolling door electric operators. This is a voluntary standard, meaning there is no law requiring compliance; however, compliance with this standard IS required in order for an operator to bear the Mark of a labeling/listing agency. It should also be understood that while compliance is not mandated by law, it may be required by the Local Authority Having Jurisdiction and building codes. The 2010 revision to this standard requires that all labeled and listed commercial/industrial operators manufactured on or after August 29, 2010 must comply with the latest revision, UL 325-2010. The most noteworthy of which was revision to section 30, which now requires that all commercial/industrial door operators monitor an external entrapment protection device or otherwise function only in constant pressure to close. An external entrapment protection device is an apparatus intended to prevent persons from becoming caught or held under a closing door causing risk for injury. Common examples of these are photo-eyes and sensing edges. The requirement for these to be monitored

Page 60: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

60

essentially means the operator must verify these are working properly prior to closing the door. The monitored device must provide continuous status to the operator, which is designed to receive and monitor the status. In the event that the monitored device is not present or has a fault condition, the operator must either revert back to constant pressure to close or stop and reverse a closing door to the open position. Either monitored photo-eyes or monitored sensing edge devices are mandatory for momentary contact operation. In the case of fire doors, the automatic closing function takes precedence over normal operating of fire door operators. Thus, sensing devices can be overridden during any alarm activated closing. The operation of a fire door operator in an alarm condition is explicitly exempted from UL325 compliance. External entrapment devices can be separated into two types; Primary and Ancillary. Primary external entrapment devices are mandatory and must be monitored if momentary contact to close is required. This includes non-contact type sensors such as monitored photo-eyes or monitored electric edges. Ancillary external entrapment devices are optional and cannot be used in lieu of primary devices. Ancillary devices include, among others, non-monitored electric or pneumatic sensing edges. If photo-eyes are selected as the primary entrapment protection device, they must be mounted at a maximum height of six inches above the floor. Additional photo-eyes or other non-monitored sensing devices can be installed as ancillary entrapment protection if desired, but installations without a primary external entrapment device continue to require constant pressure to close regardless of any ancillary entrapment devices used. In a constant pressure to close condition, the operator must stop the door when constant pressure on a control is removed prior to the operator reaching its closed limit. In addition, the operator must limit a portable transmitter or automatic actuation device to function only to cause the operator to open the door. Constant

pressure to close is not allowed from a portable transmitter in lieu of primary monitored entrapment protection. Therefore, remote operation requires primary monitored entrapment protection. The UL 325 listing is dependent on the testing of each operator with each of the acceptable entrapment protection devices, so each device must be tested and approved for each operator. All door operator manufacturers or primary entrapment device manufacturers are required to state within their installation manuals and/or user’s guides which photo sensors and sensing edges are approved by UL for use with which operators as a primary external entrapment protection device. Included with this is to list the methods of installation, adjustment, and wiring of external controls or devices serving as required protection against entrapment. Additional requirements of UL 325-2010 pertaining to rolling door operators are:

• If a three-button station is provided at

least one button must be stop.

• Controls shall be far enough from the door

or positioned such that the user is

prevented from coming in contact with the

door while operating the controls.

• Exposed moving parts of an industrial

door operator that is intended to be

mounted more than 8 ft above the floor

are not required to be guarded or

enclosed if the operator is marked

indicating minimum acceptable installation

height. If an industrial door operator is

installed below 8 ft., the exposed moving

parts must be guarded or enclosed to

conceal pinch points.

Prior to this revision, external entrapment protection devices were required, but they were not required to be monitored. Operators manufactured prior to August 29, 2010 can still be repaired as needed, but the technician

Page 61: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

61

should use this opportunity to educate the consumer on the added safety features and benefits of labeled UL 325-2010 compliant operators.

Environmental Considerations and NEMA Standards Door operators are designed to be installed in normal commercial and industrial environments including truck bays, storage facilities, and vehicular service door areas and are subject to standards developed by the National Electrical Manufacturers Association (NEMA), a trade association representing the electro-industry manufacturers (see chart of NEMA standard descriptions which follows in this section). All electrical controls are enclosed in NEMA 1 enclosures. However, if a particularly dirty or dusty environment is anticipated, then a NEMA 12 Operator Modification should be considered. If there is a lot of moisture or water spray in the area, a NEMA 4 Operator Modification may be necessary. Hazardous areas such as those containing explosive gases or particles (as defined by NFPA, National Electric Code) require a NEMA 7/9 Operator Modification. A thermostatic heater can keep an operator functioning in cold temperatures, particularly in heavy duty machines with worm gear-in-oil bath reduction systems. Many architectural specifications refer to NEMA standards. These standards comprise many volumes far too lengthy to summarize here. However, the volume that is most frequently referred to in door operator specifications is the one specifying standards for Enclosures of Electrical Equipment. The following summary of enclosures by NEMA type may prove useful:

• NEMA 1 General Purpose: An enclosure designed to prevent accidental contact with live electric parts. It is not dust-tight or watertight.

• NEMA 3R Rainproof: Designed for outdoor use to protect equipment from rain. It does not necessarily have to be watertight from underneath.

• NEMA 4 Watertight: A sealed enclosure designed to exclude water spray from any direction. It may not necessarily be submersible.

• NEMA 4X Corrosion Resistant: Same as NEMA 4, but also corrosion resistant. The enclosure material is usually a polymer or stainless steel.

• NEMA 7 Hazardous Area: An enclosure designed to contain an explosion. For use in hazardous areas containing flammable vapors and gasses. These flammable substances are grouped into four classes (Class A, B, C, and D) according to volatility. Consult the NFPA National Electric Code for more details.

• NEMA 9 Hazardous Area: An enclosure designed to contain an explosion. For use in hazardous areas containing combustible dust particles. These substances are grouped into three classes (Class E, F, and G) according to volatility. Consult the NFPA National Electric Code for more details.

• NEMA 12 Dust-Tight: A sealed enclosure designed to exclude dust, lint, fibers, and oil.

Access Control Selection A wide variety of entry control devices are compatible with rolling door operators. All operators are supplied with a standard Open/Close/Stop three-button station, which allows for complete control of the door. However, in many cases this is not enough to satisfy the requirements of the job. Most entry control devices require a choice to be made between convenience and security. Push buttons are easy for just about anyone to use, but that is precisely why they may be undesirable in certain installations. Key control stations are a popular alternative, requiring the

Page 62: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

62

use of a key to open or close the door. Another commonly used device is the card reader, which is similar to key controls in that the user must possess a device to operate the door. However, card readers offer the added advantage of being able to issue many different cards to users. A somewhat different approach is achieved by using digital keypads, which offer a comparable degree of security and flexibility to card readers, but which do not require the user to carry anything. However, the user must remember an access code to operate the door. Doors are often operated by people in vehicles. When this is the case, overhead pull switch controls, floor loop detectors, or radio controls are desirable. The latter allows a transmitter to be located on the vehicle for the convenience of the driver. Automatic controls can be used when conditions allow. The most common of this type is the auto-close timer, which will cause the door to close automatically after a preset time interval. Another variety is the 365-day time clock which can be programmed to open and close the door automatically at different times of the day.

Control Wiring on the Operator After deciding on the type(s) of entry controls for the door system, a Control Wiring type for the door operator that will accept the controls must be selected. In some instances, where questions arise regarding the compatibility between the operator and control devices, the operator manufacturer should be contacted for guidance.

Door Operator Access Controls

Digital Keypads Convenience and security for basic access are key considerations in selecting control applications. Stand alone and computerized output models available in lighted and non-lighted housings. A digital keypad is a numerical entry station which operates the door when the proper access code is entered. A large number of access codes can be programmed into this type of system, providing the user with the ability to add or delete individual code numbers to limit access to the door system.

Stand-Alone Card Access These access control devices are available in swipe card type, touch plate type, and proximity type. Card readers can be used to provide vehicular access control, pedestrian access control and building entry control. Each card has a unique code that provides management full accountability and control of cards that have been issued. Card codes can be entered into time zones or completely deactivated as the need requires. A variety of touch plate and proximity card readers is available and can be connected to computers to monitor usage.

Door Receivers Radio receivers allow the use of transmitters for remote control operation of the door. The operating range of the receivers can be increased using a coaxial antenna.

Page 63: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

63

Radio Transmitters Push button transmitters send signals to activate a radio receiver to open, close, and/or stop door operation. These devices can control several openings at once. Standard transmitters can operate one to four doors depending on the number of channels used.

A Commercial/Industrial Multi-Channel Remote Access Control System is a remote control transmitter that can open, close, and stop up to 250 doors. In a typical installation the receiver is installed in the operator or inside a building, next to the doors or existing access controls. The hand-held transmitter is programmed to the same binary digital code as the receiver and typically uses rolling code technology to change the code on each use. A single receiver can store up to 250 transmitters.

Control Stations For all control stations, the open button is frequently used as an override. Pressing the open button while a door is closing will stop and reverse direction to open. Momentary-contact to close can only be used in conjunction with monitored external entrapment protection as required by UL325.

Three Button Station: Surface-mounted three-button control is used as standard equipment with all operators in general purpose applications and can open, close, and stop the door. Single Button Station: Single button control can either open, close, or reverse the door. Two Button Station: Two button controls can open, close, and reverse the door.

Lighted Three Button Station: Three button control Open/Close/Stop with red pilot light “on” buttons will activate the door. Key Access Three Button Station: Surface mounted three button controls with on/off key switch. Buttons will open, close, and stop door when key is in the on position. Key switch will render push-buttons inactive in the off position. Key is removable in both positions. Key Access Lighted Three Button Station: Three button control with pilot light and on/off key switch. Buttons will open, close, and stop the door when the key is in the on position. Key switch will render push buttons inactive in the off position. Key is removable in both positions. Spring Return Key Switch: Surface or flush mounted, key activated with spring return to center. This type of device is available under various NEMA options. Push Button Station Lockout: Push button control with open, close, and stop with lockable stainless steel housing, suitable for flush or surface mounting. Key-lock covers can be used to prevent the use of the door by unauthorized personnel.

Fire & Postal Lock Boxes: Fire and Postal lock boxes permit emergency vehicle and postal service access. The lock boxes are designed for pad locks, or fire department and postal key operation. Lock box access can be used to automatically activate the door, or to obtain a secured access control device or key.

Page 64: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

64

Automated Access Control Electric Vehicle Treadle Switch: The treadle switch can open the door, close the door, or act as a safety to reverse. The switch is commonly positioned about 4’ away from the door. If the door is in its descent the vehicle tire passing over it will reverse the door. Loop Vehicle Detector: It can be tuned to detect passage or presence of vehicles. It can open the door, close the door, or act as a safety to reverse. The loop detector is a fully transistorized and self-contained electronic unit. This type is typically saw cut into the driveway. Preformed Loops: The preformed loop is commonly installed in new driveway applications. These are put in place and wired before the driveway is installed. This saves time and eliminates saw cutting. Microloop Probe: The microloop probe was primarily designed to be used for vehicle detection where driveways are electrically heated or existing conditions prevent the installation of loop wires. It can be suspended above the door, driveway ramp deck, ramp walls, or installed in driveways in lieu of loop wires. Approach Sensor: Approach safety sensor is a microwave motion detector designed to respond to motion approaching in one direction only. When used on automatic entrances with two-way traffic the sensor will allow the door to close sooner because it ignores departing traffic as it moves away from the entrance.

Visible Warning Devices: The visible warning device is typically a rotating beacon light or flasher that is in operation during the opening and closing cycles of the door. It can also be used to alert during an activated closing of a door. Audible Warning Devices: The audible warning device emits an alert when the door is in motion. It can also be used to alert during an activated closing of a fire door. Horn/Strobe: The horn/strobe is a combination audible and visible warning device. Traffic Signal: The traffic signal is a warning device that is constantly in operation. Two position red/green lights warn vehicles of door condition. Commonly, the red light on when door is in motion or in the closed position. The green light on when door is fully open. Interior Solenoid Locks: The electric solenoid lock automatically engages a lock for securing the door from being opened. Electric Interlock Switch: The electric interlock switch is typically used in conjunction with an interior side lock, pass door or dock leveler. The interlock switch will disengage the controls and preventing damage to the door and operator in case of accidental operation.

Page 65: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

65

Safety Accessories

Selection All modern electric operators accept safety accessories to protect people and equipment from motorized doors. Some control wiring types will accept more accessories than others. UL 325-2010 requires the use of a monitored sensing device on all motorized doors that do not function in constant pressure to close. Two of the most common safety accessories used are contact and non-contact sensing devices. The contact sensing device is commonly known as a sensing edge or sensing device. The edge mounts on the bottom leading edge of the door and is connected to the operator by hard wire or by use of a wireless device. If the door strikes an obstruction while closing, the sensing device will cause the door to stop and/or reverse. Check with the manufacturer of the operator and sensing device to verify UL 325 approval when considering any sensing device for use as monitored external entrapment protection. Non-contact sensing devices are those such as photo-eyes and motion sensors. These devices stop and/or reverse a door without coming into contact with a vehicle or person. Proper mounting of these devices is essential to their effectiveness and is determined by the job condition and type of traffic utilizing the door. When utilizing a monitored sensing edge as a primary entrapment protection device, an interface module may be required. This module translates the auxiliary device signal to interface with the operator. Reference the manufacturer’s instructions for specific details. All installations should have warning signs in place to alert pedestrians of the dangers of operating doors. These should be carefully placed according to the manufacturer’s instructions. Depending on the location and surrounding of the door, consider using

additional warning signs as necessary. These can be obtained through the manufacturer.

Sensing Devices Most sensing devices supplied for door industry type operators are compatible with rolling door operators. This includes pneumatic edges, electric edges, through beam photo eyes, and retro-reflective photo eyes. If the door does not have a bottom sensing edge or photo eyes, encourage the owner to purchase one. If not preinstalled by the door manufacturer, mount the sensing device on the door according to the instructions provided with the device. The sensing device may be electrically connected by coiled cord, take-up reel, or wireless devices. Note: Sensing devices with normally open output are not considered monitored. Therefore, the operator will require constant contact to close operation per UL325.

Electric Sensing Edge Electromechanical sensing edges reverse and/or stop a closing door when contact is made. Comprised of two metal contact strips enclosed in a hermetically sealed elastomeric extrusion. This sensing edge has a three-point contact. Even lateral pressure on these sensing edges makes absolute contact to reverse and/or stop operation.

Page 66: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

66

Air Wave Sensing Edge As the leading edge of a rolling door meets an obstruction, an air wave is created. This wave motion is then detected by an electrical switch which activates the door control panel and reverses and/or stops the door.

Pneumatic Sensing Edge When the door encounters an obstruction during its downward travel, the air switch is triggered, and an electric signal is sent to the operator via a coil cord, take up reel or wireless device. The electric signal causes the operator to reverse and/or stop the door.

Non-Contact Sensing Edge As the door closes this device creates an invisible beam near the leading edge of the door. Once this invisible beam detects an object or person, the door reverses to the open position without the door making any contact with the obstruction.

Optical Sensing Edge Optical sensing edges reverse and/or stop a door when contact is made. This type of edge consists of a photo eye installed in a weather seal profile on the leading edge of the door. The light beam is

interrupted when the seal profile contacts an obstruction, causing the operator to stop and/or reverse the door movement.

Photoelectric Sensors Photo-eyes can be used for multiple applications. Photo-eyes can be used as a safety device as well as to signal the operator to start a timer or other various functions. The most common is for use as a safety reversing device. Photo-eyes should be installed no more than 6” off the ground when used as entrapment protection. Some photo-eyes can have a range or working distance for up to 35-foot-wide doors. Additional photo-eyes can be added when coverage is desired for reasons other than entrapment protection. There are two common photo-eye devices used today.

1. Through-Beam Type Photo-Eyes, include one sending unit and one receiving unit. The photoelectric controls are positioned close to the door and project a modulated light beam across the doorway path. If the beam should be interrupted while the door is closing, it will cause the door to reverse and/or stop. Depending on the device, these may be monitored or non-monitored.

2. Retro-reflective Type Photo-Eyes, include one sending/receiving unit and a reflective component for the opposite side of the door. The photoelectric controls are positioned close to the door and project a modulated light beam across the doorway path. If the beam should be interrupted while the door is closing, it will cause the door to reverse and/or stop.

Page 67: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

67

Take-up Reel The take-up reel is one of two types typically used to connect a safety reversing device to the electric operator. The reel stores the electric cable in a housing preventing it from hanging down. Take-up reels are not recommended for monitored devices. The slip coupling device breaks contact as it spins and may cause nuisance reversals.

Coil Cord The coil cord is the second way of connecting the safety reversing device. The coil cord is connected to a junction box fastened to the wall approximately halfway up the door opening. The junction box is then hardwired to the operator from this point. The coils in the cord stretch and retract to reduce the sag of the wire during operation of the door.

Wireless Edge Transmitter

Provides a monitored or non-monitored wireless signal to commercial operators from the sensing edge. The transmitter mounts on the bottom of the door and the receiver is interfaced with the operator. These can be used to take the place of take-up reels and coil cords.

Page 68: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

68

Section Six

Automatic Closing DevicesThe single most important ability of the rolling steel fire door, beyond its construction to withstand the ravages of fire for a predetermined period of time, is its automatic closing feature. It is this feature that allows the door, without direct human intervention, to complete its primary mission, which is to close on alarm or in the event of a fire emergency. Designs vary among manufacturers but there are common methods of initiating the automatic closing.

Rolling Fire Door Release Theory

Push-Up Fire Doors

When a rolling fire door is in the charged mode, the dropout arm or release arm is held into place with a sash chain or cable. The fusible link connects two sections of the sash chain or cable. Upon the melting of the fusible link, the two sections of the sash chain or cable become separated and the release arm drops. The activation of the release arm causes a significant amount of spring tension to be released from the counterbalance assembly. Once the spring tension is released, there is no mechanism holding the door in the open position. Gravity takes over at this point and

the now “heavy” door moves to the closed position. A governing device controls the closing speed. These devices will be discussed later in the text.

Chain, Crank or Motor Operated Fire Doors

During normal operation, dropout arms are held in place by sash chains or cables which are connected with fusible links, or release holders when used with electronic smoke detectors or alarm panels. In the event of the melting of a fusible link or the discharge of the release holder, a chain of events is put into motion. At the drive end of the door, the drive mechanism must disengage, while at the tension end of the door, a drop arm falls, allowing the release of sufficient spring tension. This creates an out of balance condition in the door. The now “heavy” door closes, its speed restrained by a governor device.

Rolling Fire Door Resetting Theory

The following outlines typical procedures to reset a fire door after a closing activation. Not all fire doors are designed and manufactured the same. It is essential to follow manufacturer’s instructions for testing and resetting fire doors. These procedures are only intended to provide a general understanding of the procedures involved.

Push-Up Fire Doors Raise the door to the open position and attach a clamp in the guide to prevent the door from closing. Reapply tension according to the manufacturer’s instructions to the

Page 69: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

69

counterbalance mechanism until the door remains open. Raise the dropout or release arm and reconnect the two segments of the sash chain or cable. When the tension of the counterbalance mechanism is holding open the door, remove the clamp from the guide.

Chain, Crank or Motor Operated Fire Doors To reset the door, follow the manufacturer’s instructions. Generally, this will necessitate the following procedure. For motorized units, it is first necessary to run the motor to the fully closed position to synchronize the limit switch settings. Reopen the door and clamp it in the open position so it cannot close. This often requires re-engaging the operator and clamping the drop arm in position at the drive end, then using the operator to open the door. Next, at the tension end of the door, rewind the charge wheel, restoring the lost spring tension and clamp the drop arm in place. Now, replace the broken fuse link or clear the smoke detector (most smoke detectors reset by turning power off for a few seconds and then back on) or alarm panel so as to reset the release holder allowing the end link to be re-installed. Restore the sash chains or cables to their original configuration. Finally, remove all clamps and operate the door for two full cycles.

Automatic Closing

All fire doors must close automatically when a fire occurs. Conventional fusible link units activate from the ambient heat created by fire. A fuse link is two metal links held together by solder which melts at a prescribed temperature, typically 165°F for most fire door applications. However, a door connected to smoke detectors or alarm panels requires a door release holder to convert the electronic alarm signals into a mechanical movement for the door to close. The release holder may cause the door to close by gravity, like a fuse link, or close

motorized doors with the motor, as long as power is present (when power is not present, the door will mechanically release and be closed by gravity). Release holders must also be self-monitoring, closing the door as described above without the need for an outside power source after initially applying power.

Alarm systems may protect the entire building or specific areas within the building. Covering large areas requires the system to divide the

area into zones.

Non-Spring Release Fire Door Operators

Many fire door designs do not release spring tension as described above. This simplifies the resetting process by eliminating the need to rewind spring tension to reset the door and allows for more frequent testing of the fire door system to assure fire readiness of the automatic closing system. These systems are ideal for larger size fire doors that are under extreme spring tension, for fire doors in applications where the coil and bracket assembly is mounted concealed above a ceiling, or for any application where mechanical resetting is not practical or not desired. Non-spring release operators are available for both electric and manually operated systems. Typical with these style systems is an operator that does not disengage with the drive shaft assembly for automatic closing. In many instances, the operator also acts as the governor to control the automatic closing speed of the door. Many of these style governing systems are very effective in controlling automatic closing speed, both in consistency of speed for the entire closing of the door and by maintaining the average closing speed on the slower end of the allowable spectrum of not slower than 6 inches and not faster than 24 inches per second, adding an additional level of safety.

Page 70: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

70

Since spring tension is not released for automatic closing, the resetting procedure is much easier and safer. Some electric systems simply require opening the door by use of the open push button on the control station after the alarm signal is cleared and power is restored. Other systems may require re-engaging the drop bar at the release device. But no matter what style non-spring release system is selected, the dangers and inconvenience of rewinding spring tension to reset the door is eliminated. The installer should take special precautions when servicing non-spring release Fire Doors. These doors are designed to fall under their own weight from any point of travel. If the brake mechanism is disengaged or if the governing device is disengaged or defective, release of the door could result in a rapid freefall causing damage or injury. Never service the drive components of these doors without first securing the curtain from moving. It is also critical to maintain proper chain tension and sprocket alignment during installation to prevent the roller chain from coming off during operation. Although non-spring release systems tend to be more costly up front, their long-term cost can be significantly less than traditional style systems when comparing the costs and inconvenience associated with mechanically resetting fire doors. These style systems also add a higher level of reliability, both in design and because the closing system can be effectively tested as much as desired.

Floor-Level Disconnect Common with non-spring release fire doors is the use of a floor level disconnect. This is typically a wall or guide mounted release lever connected into the sash chain or cable routing of the door. Actuation of the Floor Level Disconnect slacks the sash chain or cable simulating the separation of a fusible link and initiating the automatic closure of the door.

Once the drop test is complete, following the manufacturer’s instructions to reset the lever returns the door to normal operation. Special care must be taken with sash chain or cable routing when floor-level disconnects are used. The floor-level disconnect should be mounted in an area easily accessible to users, but turnbuckles and other fittings should be mounted out of reach to avoid tampering. Use caution when using pulleys to route the floor-level disconnect sash chain or cable to ensure the proper slack is maintained when the disconnect is activated. Improper routing with pulleys could cut the disconnect lever stroke in half.

Floor-level disconnects allow for easy drop testing of the door. They are often intended to allow the end user to drop test the door more frequently, ensuring the safe working of the fire door and providing early warning when service is needed. The end user should be shown the proper way to perform a safe drop test and encouraged to secure the floor-level disconnect to avoid use by unauthorized personnel. This is also a good opportunity to inform the customer that NFPA 80 requires fire doors to be inspected and tested annually, and to maintain written documentation of such inspections.

Release Devices A key element to the automatic closure of a fire door is the release device. A release device is a component that senses an emergency condition in one way or another and mechanically or electrically activates the closing mechanism of the door. The following information outlines various common release devices, how they work, and their requirements. Refer to DASMA Technical Data Sheet #255 as part of this section and for additional information.

Page 71: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

71

Fusible Link The most common fire door release device is a fusible link. A fusible link is comprised of two pieces of metal held together by low-melting solder. They are used to connect two pieces of sash chain or cable on a fire door. Upon melting of the fusible link, the two pieces of sash chain or cable become separated causing the release arm or dropout arm to become activated thus initiating the automatic closure of the door. Listings for fusible links can be found in the UL Building Material Directory, Category JGIX or in the FM Approvals Guide for Building Materials. Links are commonly marked with information such as the manufacturer’s name, agency listing mark, temperature rating, pull rating and date. The pull rating is marked with a letter, “B” the 40-pound rating, being the most common. It is important not to exceed this rating when installing fuse links. Keep in mind that Factory Mutual fusible link requirements differ from UL requirements. Failure to utilize FM listed fusible links on an FM listed door could prevent approval of the door by the AHJ and/or void the FM fire rating. Links for fire door usage are typically rated at 165°F or in some special cases 212°F. It’s important to note that a 165°F rated fusible link has a recommended maximum ambient exposure temperature of 100°F. If ambient temperatures are expected to regularly see > 100°F, then 212°F rated links are recommended. It’s also important to ensure other fire systems within the building are compatible with the fuse link temperature rating. If used with temperature activated sprinkler systems, the fire door activation temperature must be less than the sprinkler activation temperature. Keep fusible links away from areas accessible to sprinkler heads or install shields to prevent spray on the fusible link.

Per NFPA 80, fusible links must be located 4” to 12” below the ceiling on both coil side, and opposite coil side of the door and near the door opening on coil side. NFPA 80 also requires a fuse link housing to keep the fuse link exposed to the heat of a potential fire if a drop, or false, ceiling is installed above the door opening. Fusible links should be interconnected such that separation of any one link will cause the door to close.

Fuse links should be connected to sash chain or cable using S-hooks. All fusible links should be at least 6” away from any fixed point such as pulleys, thru-wall pipe or raceway, etc. to avoid snags preventing dropout. Sash chain or cable routing should be planned to avoid sharp turns or < 90° bends and routed through eyebolts fastened to the wall. Turn buckles should be used to tension the sash chain or cable and should be located high enough that they are out of reach to avoid tampering. The routing must not hang up on ceiling construction and it may be necessary to use cable instead of sash chain here. The Authority Having Jurisdiction is ultimately responsible for approval of fuse link routing.

Page 72: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

72

Fusible links and routings should be inspected annually for evidence of corrosion, soldered joint cracks, paint residue, chemical residue, stress/strain or buildup of any other foreign material that will impair the performance of the link. Clean debris from fusible links and routings using air pressure. Replace links annually in severe conditions such as corrosive or greasy environments. Fusible links should never be painted or modified in any fashion. Fusible links should be replaced immediately if painted, sprayed with chemicals, or modified in any way. Some fusible link manufacturers recommend fuse links be replaced once a year. The Fusible alloy that is used in the manufacturing of the Fusible Links is subject to a phenomenon known as Creep or Cold flow. It is the continuous application of load versus time that will ultimately fracture the Link. NFPA 80 does not address the replacement frequency of the Fusible Links, however, it is stated that the Fusible Links shall be installed according to the manufacturer.

Sash Chain and Cable

For conventional fire doors, the fusible link or release device is connected to the dropout mechanism on the door by means of a sash chain or cable. Upon activation of the fusible link or release device, the sash chain or cable must travel smoothly through any eyelets or pulleys. The chain or cable must be free from any twists or kinks which would prevent the door from closing properly. On through wall applications, the chain or cable must travel freely through the raceway.

Twists or snagged cable and sash chain arrangements are frequently noted as a reason for failure of such systems to operate properly. According to DASMA Technical Data Sheet #254, the following recommendations are made to prevent operational failures and ensure proper operation:

• Wire rope or cable that incorporates an exterior plastic coating should not be used.

• Wire rope and cable should be a nominal 1/8-inch or 3/32-inch in diameter.

• A sash chain used in a rolling fire door release assembly must be provided by the original fire door manufacturer.

• For proper operation, do not locate the travel path of a fusible link close to an eyehook, wall penetration, or other obstruction.

• Sharp angles, i.e. angles less than 90 degrees, should be avoided.

Refer to the complete DASMA TDS #254 for more details.

Closing Speed

The standard for closing speed of rolling steel fire doors is recommended in the National Fire Prevention Association Bulletin 80, Standards for Fire Doors and Fire Windows that the closing speed must average not slower than 6 inches per second and be not faster than 24 inches per second. All manufacturers doors are designed to meet this standard and the installer must test the installation to demonstrate compliance for the AHJ’s approval.

Basic Electro-Mechanical Release Device This is a device that will initiate the release of the release arm or “dropout” arm. This type of release device receives an electrical message from a fire or smoke alarm. The device will also

Page 73: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

73

activate the release arm or “dropout” arm in the event of a power outage. A time delay between signal reception and release of the doors can be built into this type of release device to reduce the number of nuisance drops. The time delay is normally 10 seconds with some units having adjustable delays up to 60 seconds. It is important to determine if local codes will accept time delays longer than 10 seconds.

Electro-Mechanical Release Device with Battery Back-Up This type of unit operates in a similar fashion to the basic release device with some additional features.

• The unit can support auxiliary devices, such as smoke detectors, sounder alarms and strobe lights.

• The unit has “down limit” detection capability. The release mechanism will not release if the door is already in the closed position.

• The feature of the battery back-up will also prevent the door from closing in the event of a power outage for up to 72 hours.

The battery powers the release device only and will not power the motor operator.

Electro-Mechanical Release Device with Battery Back-Up and Motor Controller The addition of the motor controller on this unit provides the following added features:

• The fire door will close via the motor operator during an alarm situation, providing there is power to the operator.

• Most units have obstruction sensing logic built-in the unit. If the fire door closes electrically and encounters an obstruction,

the door will return to the open position then return to the closed position. The door will typically cycle three times prior to resting on the obstruction. If the obstruction is removed the door will continue to the fully closed position.

If power is not present at the fire door operator, the door will mechanically release and close.

Motor Controlled Release (Non-Spring Release) This unit does not have a separate release device but does have releasing logic built-in to the motor unit. This unit has the following features:

• The fire door will close via the motor operator during an alarm situation, providing there is power to the operator.

• Most units have obstruction sensing logic built-in the unit. If the fire door closes electrically and encounters an obstruction, the door will return to the open position then return to the closed position. The door will typically cycle three times prior to resting on the obstruction. If the obstruction is removed the door will continue to the fully closed position.

• The fire door will NOT mechanically release. If power is not present, the door will close upon the disengaging of an electric brake. Once power is restored, the door can be raised via the motor operator and is restored to fire mode.

Motor Controlled Release with Battery Back-Up (Non-Spring Release): This unit does not have a separate release device but does have releasing logic built-in to the motor unit. This unit has the following features:

Page 74: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

74

• The fire door will close via the motor operator during an alarm situation, providing there is power to the operator.

• Most units have obstruction sensing logic built-in the unit. If the fire door closes electrically and encounters an obstruction, the door will return to the open position then return to the closed position. The door will typically cycle three times prior to resting on the obstruction. If the obstruction is removed the door will continue to the fully closed position.

• This unit has a battery back-up system that will monitor the fire door’s alarm function for a period of 72 hours. If power is discontinued to the operator, the door will remain in the open position if the alarm system is not activated. Upon alarm activation or a low power warning in the battery the door will close via the releasing of the electric brake.

• The fire door will NOT mechanically release. If power is not present, the door will close upon the disengaging of an electric brake. Once power is restored, the door can be raised via the motor operator and is restored to fire mode.

It is critical to follow the manufacturer’s instructions for testing and resetting any release device and fire door.

Detectors

Detectors come in many types and typically detect heat or smoke.

Smoke Detectors

Smoke detectors fall into two groups, photoelectric and ionization. Photoelectric types measure the amount of light scattered by smoke. Its operation may be sensitive to smoke and heat not related to fire such as dense smoke areas or theatrical special effects. Some models available with heat detection.

Ionization types measure the density of visible and invisible combustion particles. Its operation may be sensitive to combustion particles not related to fire such as vehicle exhaust and vapors from chemical reactions. Some models available with heat detection. All smoke detectors must be designed to transmit a signal to activate the releasing system of the door. Detectors designed for release will have Form C contacts for such use. Form C contacts are the auxiliary relay contacts used to connect the smoke detector to the release holder. Smoke detectors are available with and without a heat sensor, depending on the specifications, and both types are acceptable for fire door use. Where multiple smoke detectors control a number of doors, they must be wired so that activation of any one detector will result in door closure.

Heat Detector Carbon Dioxide, rate of rise, and other specialty detectors may also be used in conjunction with smoke detectors in some applications.

End of Line Device

End of line devices are required by UL at the end of all smoke detector circuits. A 2-wire smoke detector uses and End of Line Resistor, and a 4 wire smoke detector uses and End of Line Relay Their purpose is to change from standby status to alarm mode in the event of power loss to the smoke detector. Without these relays, disabled smoke detectors would give no outward appearance of their non-functioning condition. End of line relays are critical to safe function of a Fire Door in smoke detector circuits but are often overlooked in the bidding stages of a job.

Page 75: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

75

Warning Devices

Typical smoke detectors used with rolling fire doors do not provide any type of warning. Some applications may require warning devices. Sounder devices, strobe lights and even verbal warnings are available with some models of release holders. Sounder-strobe devices are recommended with door release holder device applications having no other form of fire alarm warning device.

Location

Mounting location of smoke detectors is described in NFPA 80 and NFPA 72, the National Fire Alarm Code. The first guideline installers must follow is that smoke detectors should be installed in accordance with the manufacturer’s instructions. Detectors or fusible links shall be installed on both sides of the wall, interconnected so that the operation of any single detector or fusible link causes the door to close. An exception to this is that detectors are not required to be mounted to the exterior side of exterior walls.

Generally, smoke detectors shall be mounted on the ceiling at least four inches from a wall or on a wall with the top of the detector not less than four inches or more than 12 inches below the ceiling. An exception to this, according to the National Fire Alarm Code, is that when a mounting surface might become considerably warmer or cooler than the room – such as a poorly insulated ceiling below an unfinished attic, the detectors shall be mounted on an inside wall.

Smoke detectors at times are incorporated into the overall fire alarm system versus using local regions. This could activate all fire doors within the building envelope if activated by the system versus a regional activation.

For example, using the fire alarm system on a six-story building with multiple fire doors on each floor without localized regions will result in all fire doors on all floors closing at the same time each time there is an activation. By using a local region, the doors can be grouped into local regions causing much less hassle when there is an activation

Page 76: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

76

Section Seven

Obtaining and Installing the Correct DoorThe Bid Specifications The specification section is an area to become familiar with. During installation and testing, from time to time it will be necessary to review the specifications before the installation begins. Knowing how to read a specification and understanding the specifications of the product being installed will better enable an installer to perform the installation efficiently and professionally. Should you discover a questionable installation issue with regards to the specification, you should first discuss the issue with your company’s sales staff. This section will review the paragraphs of a specification. Not all architects follow the same format, but most will cover the following areas.

Rolling Door Specifications

Part 1.00 General

1.01 Material to be furnished. The paragraph will have a brief overview of what is to be supplied. i.e. rolling fire door, electrical operators, etc.

1.02 The rating of the door specified. What class and hour rating is required.

1.03 Opening preparation. Who is to prepare the opening? Ultimately, you will be responsible for the inspection of the prepared opening and insuring that it is adequate for installation of the type and rating of door specified.

Part 2.00 Product

2.01 Manufacturers. In this paragraph a list of acceptable manufacturers will be listed. Some architects will have an area and criteria for accepting manufacturers other than those listed. These are called an “or equal.” Here some will also list the model number of a specific door that they are looking for.

2.02 Materials 2.02.1 Curtain. Here the curtain design

and type will be called out. For example, 22 gauge with a 3 inch slat design.

2.02.2 Guides. Here the guides will be discussed. Type, thickness, finish, galvanizing, wind-bars, etc.

2.02.3 Counterbalance. The type of counterbalance desired, such as torsion spring or weight, amount of cycle springs required, etc.

2.02.4 Brackets. The type and thickness of the brackets and finish.

2.02.5 Hoods. The type of hood, gauge of steel, finish, baffles, etc.

2.02.6 Operation. Options include manual, chain hoist, crank, or motor operation. If an electric operator is desired this is where the type, size etc. will be specified.

2.02.7 Closing devices. This may be the most difficult area of the specification. With so many types and designs of closing devices available, it may be difficult to determine what the architect and the end user wants to accomplish other than just having the door close.

Page 77: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

77

2.03 Finishes 2.03.1 Galvanizing. The type of

galvanizing to be used. 2.03.2 Finish selection. Galvanized

unpainted, prime painted, or maybe a powder coat finish may be specified.

2.03.3 Stainless steel finish. The type and finish. Most typical is #4 finish.

Part 3.00 Execution

3.01 Installation 3.01.1 Typically this area calls for the

door to be installed according to the manufacturer’s instructions.

3.01.2 A requirement for the manufacturer’s dealer or certified installer with a certain number of years experience may be required.

3.02 Testing 3.02.1 Typically a requirement for a drop

test will be specified. This area may also request having an end user’s representative on hand to witness the drop test. Be sure that whenever drop testing any fire door that you use a drop test form that is signed off by the customer or AHJ and the technician performing the test.

3.03 Quality Assurance

3.03.1This area will specify certain quality assurance issues, not only with the installation but also with the drop test, including clean up at the job site, touching up the finish, and testing and lubricating the door after the installation is complete.

Ordering the Door

Ordering the door should be accomplished with care and foresight. An installer may be consulted in this process and should be knowledgeable about the product and its application. Rules governing the installation of rolling doors not only follow specifications, but also – in many cases – the law and local building codes. The proper action taken to ensure the correct door is ordered is an important step in the installation process, whether the project is small and simple or large and complex. Prior to ordering a door, shop drawings should be submitted to the construction manager, contractor, owner, and any other essential person involved in the project. Written approval should be obtained on the drawing from the proper authority on the job. This may be an architect, engineer, etc. When drawings are returned “approved as corrected” or other similar wording, the drawings should be reviewed with a high degree of scrutiny. Some changes may impact the originally quoted price for the installed door. When this occurs, the issue should be raised prior to ordering the door, and not after the installation is completed. If the drawings are not approved as submitted, new drawings should be submitted and approved. A professional installer also will perform a site survey to verify field dimensions against the approved shop drawings including opening size, side room, head room, etc. Taking the extra steps to ensure accuracy from the initial stages of the process will enhance the efficiency and profitability of the project. When ordering the door, drawings should be sent to the manufacturer along with the order. Errors or mistakes can be prevented through this additional review stage. In some cases, manufacturers may require copies of the shop drawings at the time of ordering. Adhering to this simple rule not only may help prevent mistakes but also may provide protection in the event of a dispute. In most cases the seller of the door will remain contractually bound in

Page 78: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

78

accordance with the plans and specifications for the project unless a specific request for an exception to these requirements is granted.

Receiving the Door Once the door has been ordered and shipped the next step is proper receiving of the material. Once a product is received, a proper counting and checking of the material before the truck has left the dock is required. In many cases, shipping miscues involving missing items or damage may delay the start of a project. An even worse scenario is to discover missing parts or specialty hardware once an installation project is well under way. When all is received and accounted for, storage and handling is the next step. The door should be stored indoors away from the outside elements. Be sure the door is stored inside, out of the weather. Careful attention must be given to storage of the curtain assembly. These are typically very heavy and can be easily damaged if dropped due to excessive weight. Some doors may have a special finish. In this event, the final product will be expected to appear as a finished product. Damaged parts can result in costly replacement expense and additional delays in the installation project.

Rolling Door Installation Instructions

The following is a basic installation guide for rolling doors. This section is intended only as a general reference guide, and not as actual installation instructions. After this section insert the manufacturer’s instructions that will be used in your company.

As noted elsewhere in this study guide, it is important to follow the manufacturer’s instructions when installing a rolling door. These products are well-designed, effective tools in the protection of

lives and property, but are intended to work under specific installation conditions. If at any time you experience a conflict between a manufacturer’s instructions and an installation circumstance, contact the manufacturer for guidance.

Getting Started

Prior to loading material, check that all paperwork is complete and correct. All crates and boxes must be accounted for and loaded. It is important to read all instructions carefully, checking shop drawings supplied for any special conditions. Open all crated materials and check with attached parts list prior to installation. All parts supplied should correspond with the type of door being installed. If special devices such as electrical releases, smoke or heat detectors are supplied, their individual instructions should be reviewed prior to installation.

Site Inspection

Once at the job site, check in with the appropriate person and review all paperwork and job requirements prior to proceeding. Review all conditions and area required for the installation. Be sure that other trades or persons will remain outside of the work area for safety reasons. In some situations, installing caution tape may be required.

Page 79: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

79

Assessing the opening

All jambs must be plumb, level and square. If removing an old door, all jambs must be clean of existing welds and debris from prior door mounting material. After the door is removed and jambs are cleaned and prepared, the jambs and attachments must be checked and repaired as necessary before the installation can proceed. Part of the installer’s responsibility is to be sure that the type of wall construction and jambs are those that meet the requirements of the door being installed. This requires verification the wall construction is appropriate for the door that was ordered as well as sufficient construction to support the weight of the door and any applicable fire, wind load or seismic jamb requirements. If the installer discovers a wall that is not adequate at the project site, it is their responsibility to bring the conflict to the attention of management. Proceeding with the installation can result in project delays and complications, along with increased liability to the installer and the company.

Sizing the opening

The opening dimensions and clearances must be verified and compared with the approved shop drawings and manufacturer installation instructions. Verify opening width and

height. In addition, the opening surfaces should be plumb, and the floors and lintels level. If they are not, compensation for these conditions must be addressed in the beginning. Adequate side room clearances must be available. With the use of drop out mechanisms, release arms, etc., more side room is usually required so that the door can move freely and unobstructed. If the proper room is not available, these conditions must be corrected before the installation can begin. Fire doors must be installed according to the manufacturer’s instructions.

Headroom Requirements

Here again, dimensions and clearances must be verified and compared with the approved shop drawings and manufacturer installation instructions. Addition of future conduit, duct work, telephone lines, and other potential obstructions should be addressed in advance of the installation with the contractor and building owner. It is important that the owner understand nothing should be attached to the door, and that objects should not be stored or installed in a manner that might obstruct the door. For fire doors, all cables and attachments must be installed in a clear and unobstructed environment so that they may release and move without obstruction. If ceilings will be installed after a fire door installation, it will be important to ensure that ceiling construction will not interfere with drop out arms and other

Page 80: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

80

automatic closing components and that access panels be provided for future resetting of the door closing mechanisms.

Job Site Organization

It is important that all material be organized to be sure that a safe and efficient installation process is achieved. Layout guides in adjacent area to the wall. Curtain, counterbalance shaft and support brackets should be placed clear of the opening to prevent tripping hazards during installation of the guides. Layout all hardware and fasteners to check for proper count and type. For fire rated products, hardware used must be that provided by the manufacturer. If the provided hardware cannot be used, substituted hardware must be approved by the manufacturer.

Tools and Equipment The following tools are typically used in the installation of rolling doors:

Tool List:

• claw hammer

• carpenter’s level

• water level

• pliers

• ratchet wrench and sockets (5/16” - 7/8”)

• impact sockets ( 3/8” - 9/16” )

• extensions for ratchets

• 2 - 10’ x ½” sling ropes

• measuring tape

• screwdrivers

• winding bars

• vice grips

• wrenches (5/16” - 7/8”)

• drill bits for steel (3/16”, 1/4”, 15/64”, 7/16”, 3/4”, 5/16”, 3/8”, 1/2”)

• drill bits for masonry (3/16”, 1/4”, 5/16” 3/8” 1/2”)

• tin snips

• adjustable wrench

• nut drivers (1/4” - 7/16”)

• Wall clamps

• cable cutters

• tool pouch

• pry bar

• Speed wrench

• Uni-bit

• Work gloves

• Welding gloves

• Safety glasses

Power Tools:

• 3/8” electric drill motor

• 1/2” electrical drill motor

• 1/2” masonry drill motor

• 1/2” rotary hammer

• Impact wrench

• Circular saw

• 4 1/2” grinder

• Reciprocating saw

• Extension cords

• Electrical gang box with ground fault interruption (GFI) circuit

Page 81: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

81

Truck Inventory:

• 8’ step ladders (2)

• 24’ extension ladders (2)

• 5/16” expansion anchors

• 3/8” expansion anchors

• 5/16” & 3/8” all-thread

• Assorted nuts and bolts

• Touch spray paint for welds & curtain

• Cleaner & rags

• Shovel

• Broom

• Oxygen & acetylene burning outfit

• Electric arc welder

• Generator

• Gas can

• Saw horses

• 4 wheel dollies

• Saw horses

• 1-Ton Come-A-Long (2)

• 1-Ton Chain hoist

• Angle iron cutter

• Fire extinguisher

• First aid kit

• Caution Tape

• Hard hats

Page 82: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

82

Guide Installation

Guides are typically shipped assembled from the factory. It may be necessary to disassemble the guides for proper installation. Refer to the manufacturer’s installation documents to determine the spacing of the guides. It is imperative that this spacing is adhered to within the manufacturer’s tolerances and that the guides are plumb. Particularly for wind load rated and fire doors, installing the guides at the proper spacing and with strict adherence to the manufacturer’s installation instructions is the most important element of a good installation. If the guides are not installed as shown on the drawings and as outlined in the instructions, the wind load and/or fire rating of the door will be void. Contact the manufacturer for guidance anytime field conditions deviate from the drawings and installation instructions. Measure the slope of the floor and shim as necessary to ensure that the brackets are level with one another. Guide wall angles must be level with one another to ensure the brackets are level so that the curtain will fall cleanly down the guides and coil properly when opened.

For Fire Doors, some manufacturers use downward guide expansion of fire doors which requires shimming both guides an additional amount off the floor to provide clearance. Reference installation instructions and/or shop drawings for specific expansion requirements. Determine the location of all guide mounting fasteners and install the guides to the manufacturer’s specifications. Ensure you use the fasteners supplied by or specified by the manufacturer and double check them against the installation instructions and shop drawings. Fasteners must be positioned in specific locations within the wall mounting slots for fire doors to ensure proper guide expansion in the event of a fire.

Warning! Guide assemblies can be extremely heavy. Take proper precautions to ensure safety when lifting or standing up the guide assemblies.

Wall Types and Mounting There are a variety of wall types on which rolling doors can be installed. The type of wall construction will determine, in part, the required guide construction and fasteners, and the fire rating of a fire door. This must be determined before the installation can begin. For example, according to the specifications or manufacturer’s details you are supposed to install a door on steel jambs. You arrive on the job and there are concrete block walls on which to install the door. Installing the guides in “E” type steel jamb configuration on concrete block could result in the block splitting out or voiding the fire rating of a fire door. At this point, it would be wise for the technician to contact the supervisor and discuss the situation. If not, you may end up removing the installed door to have the contractor change the wall conditions and then be required to re-install the door. This may have to be done at the expense of the door company, which may not be recoverable from the contractor or owner. It is the responsibility of a professional door installer to be aware of these conditions and considerations before the job is done. For an installer, recognizing the correct type of wall and door construction is an important step. This should take place at the time a door is ordered but should be confirmed prior to the installation. This type of training and forethought is an important attribute of a professional technician.

Concrete Walls Are typically poured walls and do not require any additional capping of the jamb. For mounting the rolling door guides, usually

Page 83: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

83

concrete expansion anchors are used, but through wall bolts can also be utilized. If the jamb is capped with a structural steel channel or a bent steel plate has been provided at the wall jamb, the door may be designed to mount to either the concrete wall with use of a “Z” type guide or to the steel member with use of an “E” type guide. If mounting to the steel member, refer to steel wall type below for wall mounting information.

Masonry Walls There are two types of configurations for this wall. The first is the unfilled or hollow block wall. Hollow block walls require special attention. Through bolts with crush plates should be used for this type of mounting application and are required by NFPA 80 for Fire Doors. Expansion anchors should never be used with hollow block walls as there’s nothing for them to expand into. The purpose of the crush plates is to prevent the bolt from pulling through the wall. The second type is filled concrete masonry block – also referred to as Concrete Masonry Units (CMU) – or brick. On these type walls, use of through bolts or an approved type of expansion anchors are acceptable fasteners.

Steel Steel jambs for a pre-engineered building or concrete walls capped with a steel member are typical applications. Guides installed to steel jambs may be bolted to the steel member with tap bolts, or if the mounting condition allows, using a bolt and nut on the back side of the steel member. Welding of the guides to the steel member may also be done provided the welds are in accordance with the manufacturer’s installation instructions. Before welding fire door guides to steel jambs, be sure to follow the manufacturer’s written

instructions as not all manufacturers have approval for welding of their fire doors and not all listing agencies (most notably FM Approvals) approve the use of welding to steel jambs. So, while you may find it easier to weld the guides to the jambs, it may violate fire door approvals and listings. Afterwards, the only fix is to remove the guides and install them correctly using the proper fasteners.

Stud-Mounted Drywall This is a common wall mounting application for counter doors and counter fire doors. Through bolt mounting is used on larger rolling doors and lag screws may be provided for smaller doors. Through bolts are required for fire doors unless the manufacturer has other specific mounting approvals included with their listing.

Wood Walls Rolling doors are occasionally mounted to wood walls. Wood wall installation requires the use of lag screws or through bolts and jamb construction should be verified to be adequate to support the loads of the door. This is probably the most uncommon wall type for a fire door. Although there can be some type of fire rating on this kind of material, it generally is not used. Wood wall installation would require the use of through bolts unless the manufacturers have other specific mounting approvals included with their listing. Fire rated products mounted to non-masonry walls must be provided as approved by the manufacturer’s listing agency and be mounted to the wall with the fasteners as provided by the manufacturer.

Tube Mounted Doors Another rolling door mounting method is the use of a tube mounted assembly placed in front

Page 84: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

84

of the opening. This mounting is most common for rolling Grilles and is helpful for situations where attaching bolts to the wall is difficult if not impossible. In these cases, base plates are secured to the floor or sill and continuous steel tubes are attached to the base plates. The top of the steel tube is secured to either structural steel at the ceiling construction or to the wall above the opening. The tubes may be supplied by the manufacturer or by others and should be verified to be adequately attached to the building framing members to support the loads of the door. When part of the manufacturer’s procedure, fire doors may also be mounted to tubes placed in front of the opening. The top of the steel tube is designed for expansion with an expansion tube sleeve assembly that is secured to either structural steel at the ceiling construction or to the wall above the opening. Not all manufacturers have a listing for this type of installation, so verify the manufacturer’s listing before using this type of door mounting installation. Regardless of jamb construction, doors must be installed with the hardware provided and/or specified by the manufacturer, unless otherwise dictated or approved by a local authority having jurisdiction for Fire Doors. In the event the hardware provided by the manufacturer does not appear to be appropriate for the installation, the manufacturer should be contacted for verification and direction.

Fire Door Jamb Construction Jamb construction is important to a Fire Door’s ability to impede a fire. The jambs must have an equal or greater fire rating than the door to achieve the rating of the door. While it is not necessary for an installer to know how to build all the different jamb types, one must be familiar with their construction, method of attachment, and proper guide orientation to ensure they are correct for the fire rating of the

door and sufficient to support the door loads. DASMA has provided a number of Technical Data Sheets (TDSs) providing guide mounting details and recommended jamb constructions to Architects. Reference the following DASMA Technical Data Sheets for specific details critical to Fire Door jamb construction: • DASMA TDS261 – Common Jamb

Construction for Rolling Fire Doors:

Masonry Construction – Bolted and

Welded Guides

• DASMA TDS262 – Common Jamb

Construction for Rolling Fire Doors: Non-

Masonry Construction – Bolted Guides

• DASMA TDS263 – Common Jamb

Construction for Rolling Counter Fire

Doors - Masonry Construction – Bolted

Guides

• DASMA TDS264 – Common Jamb

Construction for Rolling Counter Fire

Doors: Non-Masonry Bolted Guides

• DASMA TDS273 – Rolling Fire Doors

Bolted onto Steel Tubes, Set Against

Face of Fire-Rated Walls

Preparing the Barrel

The barrel will be identified by the manufacturer for hand of operation. Left or right is always taken as you face the coil side. Place the counterbalance shaft according to this designation at the base of the guides. If supplied, install the rings on the counterbalance shaft, which will have holes drilled and tapped for ring attachment studs. Verify the direction of the coil to insure installing the rings in the proper direction. Refer to manufacturer’s installation instructions for specific ring attachment drawings.

Page 85: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

85

Attaching Curtain to Barrel Assembly If door is to be mounted outside, slats are arranged differently than if the door is to be interior mounted. Refer to the figure and confirm that the door slats are properly oriented.

Lay out the curtain and barrel assembly near the opening. Orient the barrel with its right hand end on the right side of the opening. Center the top slat of the curtain with the barrel assembly and connect it to the barrel rings. If rings are not provided, attach the top slat to bare pipe. There are two main methods used for installing the curtain and barrel assemblies. For smaller doors, the curtain is usually installed to the barrel on the ground while for larger doors; the curtain is typically slung from the barrel. We will touch on each of these methods in this manual.

Curtain Rolled on Barrel on Floor Use lumber, PVC pipe, cardboard, or any other adequate material to protect the curtain finish and unroll the curtain on the ground with the coil side of the slat facing up. Place the barrel on top of the curtain and line up the barrel with the top slat. The barrel should be centered on the curtain. Install the curtain to the barrel using the fasteners provided. Roll the curtain up around the barrel. Be sure that the curtain roll is tight and straight and use ropes or strapping to

secure the curtain from unrolling. Carefully lift each end of the curtain and barrel assembly and slide each bracket plate onto the barrel shaft. Be sure that the drive end of the barrel gets the drive side bracket and the tension end gets the tension side bracket. Take precautions to prevent curtain damage while lifting and raise the curtain, barrel, and bracket plates up into location. Line up the bracket plate holes with the guide assembly holes and fasten using the manufacturer’s specified fasteners.

Slinging the Curtain For some larger rolling doors, the combined weight of the coil and barrel may be too heavy to lift into place as one item as treated above. This method below describes how to lift each one separately. Attach the drive side support bracket to the guides. Slide the tension side bracket onto the barrel’s tension shaft extension and lift the barrel assembly and tension bracket into place with slings. Feed the drive shaft through the drive bracket already attached and proceed to attach the adjusting bracket to the guides. The tensioning end of the barrel contains most of the spring and is generally the heavier end, so sling the barrel accordingly to best balance the load. Choose multiple equal lengths of strapping or safety rope. It is the installer’s responsibility to verify that the strapping or safety rope is of adequate strength to support the coil’s weight. Tie a large loop in the straps around each end of the barrel so as to cradle the coil. The coil and barrel should be separate by a minimum of 18” and the coil should be rolled to have the top attachment slats exposed.

Page 86: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

86

Begin to rotate the barrel in the direction to raise the curtain. The rope loops will consequently uncoil the curtain. When sufficient curtain has been uncoiled, attach the top slat to the barrel assembly. With the top slat attached, continue to completely unroll the curtain in a similar fashion. Some installers use spring tension and/or manual chain hoists to roll the coil around the barrel to make it easier to rotate the barrel. While restraining the coil from turning freely, feed the bottom bar into the top of the guides allowing the curtain to advance approximately 6 inches to 12 inches. Block the bottom bar so it cannot travel beyond this point. Proceed to attach the stops to the top of both guides.

Installing the Tension Wheel If not installed while rolling the curtain around the barrel, follow the manufacturer’s instructions for installing the tension wheel to the tension shaft and secure from falling.

Applying Tension The amount of initial revolutions of the spring, usually specified by the manufacturer, is the theoretical starting point for the required spring tension. In most cases this figure is correct, but due to variations in steel, springs, friction, etc., slight adjustments may be required. For

underbalanced fire doors, initial turns may be close to zero. Due to variations in steel, springs, friction, etc., slight field adjustment to the specified initial turns may be required to provide optimum balance and/or drop speed. Caution! Always wind tension when the door is in the up position. The springs are under the least amount of tension at this point. Reference the manufacturer’s installation instructions when special springing systems are utilized. By hand, rotate the tension wheel slightly in both directions to determine the neutral point of the tension shaft. Mark the hole on the tension wheel which is nearest to the retaining lug on the tension side bracket. Using sufficiently sized winding bars, insert the two winding rods securely into the holes in the tension wheel. Tension is applied in the direction as the door would turn as it coils upward. Apply the manufacturer’s initial revolutions counting from the mark on the tension wheel made earlier. The initial revolutions are the required number of turns of the spring to hold the curtain in the open position. While holding the winding bar firmly in one hand, insert the tension wheel pin with the other hand through the lug in the bracket and into the hole in the tension wheel to lock the spring tension at the desired number of revs. Remove the winding rods. Operate the door to ensure proper balance and adjust tension as needed. Important: Apply only enough tension to hold the door in the up position against the stops.

Page 87: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

87

This is the optimum setting. Too much tension can cause door damage or present a safety hazard. Note: It may be necessary to temporarily clamp fire door drop out mechanisms in place until sash chain or cable routing is complete.

Applying Tension: Inside Tension Holder/Wheel When side room is limited, an inside tension adjustment mechanism may be used. Follow the manufacturer’s installation instructions and safety precautions. The curtain must be unrolled down into the guides to access the tension shaft and/or tension wheel. The curtain is typically shortened at the barrel to provide access to apply tension. Using the proper winding bars, apply the total spring turns indicated by the manufacturer. The tension shaft is then typically pinned to an inside shaft holder to secure tension. Test and adjust as required for proper balance.

Applying Tension: Compound Tension Wheel On doors with large amounts of spring tension, a compound adjusting mechanism may be used. These mechanisms use mechanical reductions to decrease the force required by the installer to tension the door. Refer to the manufacturer’s installation instructions for installation of a compound tension wheel. Once installed, operate the door to ensure proper spring tension, and make adjustments as needed to provide a safe, well-operating door.

Operating Mechanism Assembly If the door is manual pushup operation, skip this step. Otherwise, it may be necessary to assemble the operating mechanisms to the

operator bracket prior to installing the hood to provide access for assembly fasteners. If the door is to be motor operated, reference the separate installation instructions for electric operators in this manual. Operating mechanisms can vary tremendously from one manufacturer to the next. Reference the manufacturer’s installation instructions for details on assembling specific operating mechanisms. Some manufacturers factory-assemble the operating mechanisms to the drive brackets to aid with field assembly.

Hood Installation If supplied, it may be necessary to install the lintel brush before installing the hood. If the hood requires intermediate hood support(s), use a chalk line to strike a level line across the lintel even with the top of the support brackets. Reference the manufacturer’s specifications to determine the mounting location of the hood supports. Install the top of the hood support to the lintel in line with the chalk line using the supplied fasteners. Lift the hood up into position and fasten to the brackets and/or supports. Fasten the top flange of the hood to the lintel using the fasteners supplied by the manufacturer. Follow the same procedure for installation of the fascia if provided. If the door is supplied with a baffle, check for proper baffle functionality.

Page 88: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

88

Final Assembly If applicable, install the tension and drive side covers with the supplied fasteners. Attachment of the guide and lintel seals, if supplied, is one of the final steps of installation prior to turning the door over to the owner or general contractor. Clean the entire door assembly including hoods and covers. Install all safety and warning labels. Clean all debris and trash created by the door installation and sweep clean. For fire doors, install release devices, chains, cables, etc. per manufacturer’s instructions and the guidelines set forth in this manual. There are many ways in which to run the fuse link assemblies. Once the release devices are installed, drop test the door to be sure that all devices release, cables and chains slide properly, and all adjustments have been made to ensure the door drops correctly. Once the door has passed the drop test, properly secure all release devices and set for operation. A second drop test is required to be performed and witnessed by a representative of the owner. Completely fill out the drop test form that may be supplied by the manufacturer or use the DASMA form available in TDS #271. Leave one copy with the appropriate person and retain the original copy for file.

Inspection and Drop Testing of Fire Doors A fire door requires drop testing both at initial installation, and at least on an annual basis per NFPA 80, Chapter 15, Section 15-2.4.3 and in accordance with the Authority Having Jurisdiction. Fire doors should also be drop tested anytime service is performed. This drop testing is essential to ensuring the safe closure and proper fire protection of the door in the event of a fire.

The first step in performing a safe drop test of a fire door is to perform a thorough visual inspection of the door. This visual inspection should be performed upon completion of any new installation and for any fire door being serviced or drop tested in the field. It is important to perform the visual inspection prior to performing a drop test to avoid a dangerous situation or damage to the door due to a malfunction. The following are items to look for during a visual inspection:

• Guide and wall fasteners are not missing or loose. There should be no gaps between the guide wall angles and the jambs. Welds and weld locations comply with the manufacturer’s installation instructions.

• Guide assemblies have the proper guide expansion clearance and fasteners are installed in the proper slot locations per the manufacturer’s instructions.

• Curtain, barrel, and guides are plumb and level.

• Release and /or drop arms are properly connected to the fusible link and /or release device.

• Fusible links and detectors function properly and are located in accordance with manufacturer’s instructions, the requirements of NFPA 80, and local code.

• Fusible links and sash chain or cables are not painted or coated with dust or grease, cable is not kinked or pinched, chain is flexible and not twisted, and raceways and eyelets are not obstructed.

• Smoke detectors and auxiliary devices have power.

• Door curtain slats are not bent, cracked or torn and endlocks are not missing, bent, broken or loose.

• Bottom bar should be straight with no loose bolts and should contact the floor, sill, or countertop for the full width of the opening in the closed position.

• Guides should be clear of any debris. They should not be pinched, bent or have any loose attachment points.

Page 89: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

89

• Hood, fascia, and/or Flame Baffle should be properly attached, not bent and not rubbing the curtain when the door is in motion.

• Brackets and operating mechanism should not show any signs of worn, missing or misaligned parts. Gears or sprockets should not be missing any teeth and shafts should not be bent.

• Release mechanism should not be tied-off preventing automatic closing.

• Nothing that is not a part of the fire door assembly is attached to any part of the fire door assembly.

• The opening is clear of any obstructions which may prevent the door from closing.

Any replacements parts must be manufactured by the original manufacturer of the fire door. In some instances, a door manufacturer might no longer be in business and original parts not available. In such cases, the technician should discuss the parts with the owner and consider replacing the door entirely. The next step in a drop test following the visual inspection is an operational inspection. The door should be operated through a complete cycle to verify smooth, proper operation. Excessive lift effort or hoist effort, or a struggling operator may be a sign of a broken spring. Any abnormal noises, damage, or other observations should be fully investigated and repaired if necessary, prior to performing a drop test. If the door has passed visual and operational inspections, operate the door to the full open position to prepare for the drop test. The area should be roped off to keep people away from the door while it is being tested. WARNING! Drop testing should only be performed from the full open position. This position is critical not only in measuring the success of the test, but also in avoiding permanent damage to the door and in safeguarding against potential injury to people in the vicinity of the door.

The drop test is required to confirm that the fire door will close automatically during a fire emergency and should test all aspects of proper operation of the release mechanism. This will ensure that the fire door will close in a fire emergency situation. It is imperative to use the manufacturer’s instructions for testing the release mechanism. If the door has multiple closing options, all options should be tested. Initiate the drop test by inducing slack into the sash chain or cable routing. This can be done a variety of ways depending on the type of door and requirements of the AHJ. One method used, which is occasionally required by the AHJ, is to melt and separate one of the fusible links. Activating a floor level disconnect or separating a turnbuckle are other common ways of initiating a drop test. Fire doors integrated into building smoke or fire alarm systems or using electro-mechanical release devices should also be tested utilizing those systems. For the drop test to be successful, the door must close completely from the full open position and be in full width contact with the floor, sill, or countertop. The drop speed of the door should be no slower than 6 inches per second and no faster than 24 inches per second as required by NFPA 80. Determine the drop speed by dividing the door height in inches by the time in seconds from release until the door contacts the floor, sill, or countertop. The drop test should be witnessed by the building owner, building owner agent, and/or the Authority Having Jurisdiction. A drop test form should be completed with a copy for the building owner and a copy for the installer’s records. Records should be maintained for future contact for scheduled annual drop test inspections. Upon completion of a successful drop test, reset the release device(s) according to the manufacturer’s instructions. After resetting the release device(s), close and raise the door

Page 90: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

90

using the operational method of the door. The door must be drop tested twice – once to verify proper operation and full closure, and a second time to verify that the automatic closing device was properly reset. Ultimate acceptance of a fire door is the decision of the authority having jurisdiction, as defined in NFPA 80. Refer to DASMA Technical Data Sheets #252, #271 and #276 for additional drop test information.

Miscellaneous Final Checklist

• Apply all warning labels in the appropriate locations before leaving the installation site.

• Check the area for any extra parts and be sure these were not omitted in the installation process.

• Have the customer or his representative sign off on the installation and exchange all documentation and keys to locks, etc., at this time. Be sure the customer receives a copy of this manual and of the installation drawing.

• If the customer is unfamiliar with the product, demonstrate the operation of the door and any optional equipment before leaving the job site.

• Don’t leave a mess. Clean up the area

and make sure the area is secure if you’re

the last one to leave.

Page 91: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

91

Section Eight

Installation Instructions for Electric OperatorsImportant Safety Precautions WARNING! To reduce the risk of injury or death, always read and follow all manufacturers’ instructions and safety precautions. UL 325-2010 requires the use of a monitored sensing device on all motorized doors that do not function in constant pressure to close. Check with the manufacturer of the operator and sensing device to verify UL 325 approval when considering any sensing device for use as monitored external entrapment protection. Door operators and associated control equipment should only be installed and serviced by qualified professionals. Professional installers should observe the following safe installation procedures. The installer should also follow all of the manufacturer’s installation instructions and safety precautions:

Before Installation:

1. Verify that the operator is proper for the type, size of door and frequency of use per the operator specifications.

2. Power should always be disconnected whenever installing, wiring, or servicing a door operator or automatic door system. Not only is the chance of electric shock thus eliminated, but the moving chains in most door operators can catch clothing or fingers and cause severe injury.

3. Installation and wiring must be in compliance with local building and electrical codes.

4. Additional safety devices must be installed to prevent entrapment anytime pedestrian traffic is expected near or

around the door. Examples of such devices are reversing edges, photo-eyes, etc.

5. Reversing devices appropriate to the application must be installed as part of the system.

6. Outdoor or easily accessible controls must be of the security type to prevent unauthorized use of the system.

7. Place controls far enough from the door so that a user cannot touch the door when operating the controls.

8. Controls should be placed so the user has full view of the door when operating.

9. Always set the limits on the operator, even if power has not been supplied.

10. Some manufacturers tape the cotter pin against the clutch pulley. Make sure you remove it and pin the adjusting nut as per the manufacturer’s recommendations.

11. Do not over tighten a clutch to compensate for a damaged door.

12. Test door and service monthly. If adjusting limit travel, retest the door opener. Failure to adjust the door may cause death or injury.

13. Keep doors properly balanced. An improperly balanced door could cause severe injury. Qualified service personnel should make repairs to the door if needed.

14. Use emergency operation mechanisms only when the operator has been electrically disconnected. If possible, use them only when the door is closed. Use caution when using emergency operation mechanisms with the door open. Weak or broken springs may cause the door to fall rapidly.

15. The installer is responsible for assuring that the owner of the door system understands its basic operation and safety. In particular, be sure the

Page 92: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

92

owner/end-user understands the location and operation of the emergency operation mechanism.

16. Point out to the owner/end-user of the door system that children or pets should not be allowed to play on or near the door or any part of the system, and that the safety instructions supplied with the operator are the responsibility of the owner/end-user.

17. Leave the installation and maintenance manual for the operator as well as any additional information supplied with the operator or any other components of the door system with the owner/end-user.

18. If you have any questions about the safety of the door operating system, do not install the operator.

Preliminary Precautions To reduce the risk of severe injury or death, read and follow all manufacturer’s safety warnings and installation instructions. Ensure that the door is properly installed and working freely in both directions. Do not install the operator until all door problems have been corrected. If necessary, oil all moving parts (chains, rollers, guides, etc.). Remove any old accessories (locks, bolts, etc.) before installing the door operator. Locate any pushbutton controls within sight of the door, at a minimum height of 5 feet (1.53m) so small children cannot reach them, and away from all moving parts of the door.

Mounting Operator Support Plate Bracket Mounted Operators: Bracket Mounted Operators: Operator Support Plates are sometimes shipped pre-assembled to the door brackets by the manufacturer. If the support plate is already installed to the bracket, skip this step. Locate the operator support plate. Referencing the manufacturer’s installation documents, determine the location of the mounting holes on the bracket and

necessary hardware to install the support plate. Align the support plate to the bracket and fasten using the hardware provided. Before tightening the fasteners, be sure to slide the support plate towards the bracket to provide maximum adjustment for tightening the roller chain. Wall Mounted Operators: Determine the best location for the operator. The operator should mount to the wall off to the side of the door with the operator output shaft in alignment with the door drive shaft. The mounting location should provide adequate structure for mounting the operator to the wall. Locate the operator as close to the door as reasonably possible to reduce the length of the roller chain; optimum location is 12 to 15 inches from operator shaft to the door shaft. Excessively long roller chain may require additional devices, such as idler sprockets and chain guides. If a wall mounted operator support plate was provided, lift the support to the predetermined location and fasten to the wall using the appropriate fasteners.

Mounting Operator Operator should be installed a minimum of 8 feet (2.4m) above the floor. Installations below 8 feet require the use of an operator cover to protect personnel from accidental contact with the unit’s sprockets. WARNING! Electric operators can be very heavy. Exercise extreme caution while performing this step to prevent and secure the operator from falling to avoid severe injury or death.

Page 93: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

93

Determine a safe way to securely hoist the electric operator up into position. Carefully align the operator to the support plate and install the operator to support fasteners. If the operator is to mount directly to the wall, use the appropriate operator to wall mounting hardware. Make certain that the operator mounting fully supports the entire weight of the operator before removing the lifting mechanism. Place the door sprocket on the drive shaft. Slide the sprocket as close to the bracket as the operator installation will allow while still maintaining alignment with the operator output shaft. Insert the key into the door shaft keyway. Using the correct size Allen wrench, tighten the set screws to lock the sprocket in place. Use an Allen wrench to loosen the set screws in the operator drive sprocket. Slide the sprocket out into alignment with the door drive shaft. If installation permits, use a straight edge to line up the outside faces of the two sprockets. Once the sprockets are aligned, verify that the operator drive sprocket key is in place and tighten the set screws to lock the sprocket to the operator drive shaft. Lay the roller chain provided on the sprockets to determine the appropriate chain length. Cut the roller chain to length using a chain breaker if needed. To shorten the chain, punch out the pin that will leave an inside link nearest to the desired length. Connect the roller chain around the sprockets and join the two ends of the chain together with the connecting link. In some cases, half links may be needed to achieve the appropriate length.

Loosen the operator mounting bolts enough to allow the operator to slide or pivot. Slide the operator away from the door shaft to tighten the drive chain and then firmly tighten the mounting bolts. Check the tension on the chain and the set screws on the sprockets. There should be no more than 1/4-inch slack when chain is depressed between sprockets. If an auxiliary chain hoist is supplied, run the hand chain through the pocket wheel and chain guide outside the frame; allow both ends to hang down towards the ground and cut hand chain, if necessary, so that both ends are approximately 2 feet (0.6m) from the floor. Connect the ends of the hand chain. Attach the release cable to the chain hoist engaging lever and route it to approximately 4 feet (1.2m) from the floor following the manufacturer’s instructions. If provided, mount the floor level disconnect lever to the wall to allow the cable to be slightly loose when the lever is in the engaged position (upwards). Locate and install the floor level chain keeper with the appropriate fasteners.

Manual Operation of Electric Operator If the electric operator is equipped with an emergency chain hoist, use the following instructions to manually operate the door. With door in the closed position, pull the disconnect cable downwards to the disengaged position. This will disengage the drive mechanism from electrical operation and transfer it to manual chain hoist drive. A switch disconnects the electrical controls to prevent injuries.

Page 94: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

94

Operate the door manually by pulling downward on one side of the chain. Pulling the other side will cause door to move in the opposite direction. To return to electrical operation merely release the disconnect upwards to the “engaged” position.

Setting the Limits There are two main types of limit adjustment; Electronic and mechanical.

Electronic Limit Adjustment Limits are adjusted electronically using the operator control board. Follow the manufacturer’s instructions for proper key sequence required to set the operator travel limits.

Mechanical Limit Adjustment Limits are adjusted mechanically using an external limit box. Follow the manufacturer’s instructions for proper adjustment of mechanical limits. Traditional mechanical limit adjustment is as follows: There are typically four limit switches. Two are used as end of travel, one is for radio control or one button operation and one is for reversing devices such as sensing edges.

• The open limit switch is the end of travel

in the open position. Adjust the cam so

that the door stops in the open position at

the desired location. Be sure to set the

limit so the door stops just before

contacting the bottom bar stops.

• The advanced open limit switch is used

for radio-control and for one-button

(open/close) devices. This limit switch is

set to be activated slightly before the open

limit switch when opening.

• The close limit switch is the end of travel

in the closed position. Adjust limit cam so

that the door stops in the closed position

at the desired location. The limit should be

set so that the door contacts and seals

with the floor but does not crush the

curtain downward.

• The advanced close limit switch is used in

the operation of the reversing edge or

other reversing devices. This limit switch

deactivates any reversing devices slightly

before the door reaches its closed

position to prevent the door from

reversing on the floor.

Control Wiring

Wiring Type Refer to the wiring diagram located on the inside cover of the electrical box to determine the type of control wiring. Prior to 2010, standard operators were typically shipped from the factory set for C2 wiring, which required constant pressure to close the door. If momentary contact to close was desired, B2 wiring, the operator was either rewired or an adjustment on the control board was required to achieve this wiring type.

Page 95: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

95

1. Constant pressure on close (C2 wiring):

The operator requires constant pressure on the close control to keep the door moving in the close direction until it reaches the close limit.

2. Momentary contact to close (B2 wiring): The operator will require only momentary contact on the close control to close the door.

Since the 2010 revision to UL325, commercial operators are required to include an external monitored entrapment protection device if B2, momentary contact to close, is desired. The exception to this is when a Fire Door Operator is closing in an Alarm Condition. In this instance, the operator is allowed to ignore safety devices immediately or after a number of attempts and close with momentary contact or even if external monitored entrapment protection is not present, for the purpose of Fire Containment and Protection.

Special Control Wiring If the operator was shipped from the factory with non-standard control wiring or with optional accessories that require additional instructions, refer to the wiring diagram(s) indicated in the special control wiring data box. When a replacement wiring diagram is present, refer only to the replacement wiring diagram for all connections. If the wiring diagram is missing, or any uncertainties exist regarding the proper wiring type, contact the operator manufacturer before making any connections.

Locating the Control Station All operators are supplied with some type of control station. Generally, a three-button station (Open/Close/Stop) is provided. A two-position key switch or control station (Open/Close) may be added or substituted when requested at the time of order. The wall control(s) must be located so that the door is

within sight of the user and is far enough from the door or positioned such that the user is prevented from coming in contact with the door while operating the controls. The control station should be a minimum of five feet from the floor to prevent small children from reaching. An entrapment warning placard is required to be mounted on the wall adjacent to the wall control. The placard should be located such that it is visible when operating the door.

Clutch Adjustment If the electric operator is supplied with a clutch, it is necessary to adjust the clutch to ensure proper engagement. Failure to adjust the clutch specific to each door installation will result in an unsafe door system and potential for an accident, injury, or damage to the door. A clutch is not intended to be used as an alternative to proper entrapment protection, but rather an auxiliary device to protect the door from damage. Follow these procedures for properly adjusting the clutch. Refer to the manufacturer’s instructions for specific clutch type adjustment procedures.

Page 96: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

96

1. Move the door to the closed position 2. Remove the cotter pin or set screws from

the nut on the clutch shaft if needed. 3. Back off clutch adjustment until there is

very little tension on the clutch. 4. Tighten the clutch gradually until there is

just enough tension to permit the operator to move the door smoothly but to allow the clutch to slip if the door is obstructed. The clutch is not an automatic reversing device.

5. Once final adjustment to the clutch is made, reinstall cotter pin or set screws if previously removed. End users must be instructed in the safe operation and test procedures of the clutch assembly, as well as any other safety devices.

Brake Adjustment When the electric operator is supplied with a brake, the brake is factory set but may require adjustment after usage. To obtain optimal performance and maximum life, the brake must be adjusted for proper clearance between friction pads and brake tensioning. Reference the operator manufacturer’s installation instructions for detailed information on brake adjustment.

Test the System

1. Once power is supplied, test all controls and safety devices for proper operation. Make any necessary adjustments to the limit switches.

2. Do not leave the power on unless all safety and entrapment protection devices have been tested and are working properly.

3. Install all safety stickers and warning labels.

4. Conduct a thorough review of safe operating procedures with the owner or person(s) responsible for the operation of the door. Review safety instructions, the emergency manual operation of the door,

if provided, and explain how any safety devices operate and demonstrate how to test them.

All installations should include a thorough review to document the door system is working properly at its conclusion. As with any door system, rolling doors and operators may be damaged or modified by others following completion of the installation. Checklists, digital photographs, a form signed by the end-user are methods of documentation. In addition to providing documentation that may be important in the future, in the event of a malfunction, the post-installation process can reveal any undetected flaws or defects in the installation.

Page 97: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

97

Section Nine

Service and Operation of Rolling DoorsFire Door Repairs The correct repair and service of Rolling Doors is paramount to safe operation of the door, and correct operation of a fire door during a fire event. Fire doors have special requirements when service is needed. A fire door technician should be familiar with these requirements and handle repair and service properly. Following is a list of these requirements as outlined by DASMA TDS 257 and 275.

• Repairs shall be made and defects that could interfere with door operation shall be corrected without delay. Repair is defined as any action that restores the door to its original approved condition.

• All fire doors shall be repaired with parts obtained from the original manufacturer of the fire door needing repair. When parts are not available from the original manufacturer of the fire door needing repair, it is required that the complete fire door be replaced. As an alternative, a fire door operator, governor, and automatic closing device may be replaced with a labeled retrofit fire door operator when it is installed in accordance with its installation instructions and is acceptable to the Authority Having Jurisdiction. A retrofit operator may be provided by other than the original manufacturer of the fire door needing repair provided the retrofit operator listing allows it to be used on the manufacturer's door.

• Modifications of any fire door should be arranged with the door manufacturer, and with the Authority Having Jurisdiction. Field modifications can be made only after being submitted to and approved by the listing agency. A field inspection after the modifications are made may also be

required. Field modification is defined as a deviation from the product according to the approved procedure.

• All fire doors that are repaired shall be drop tested to ensure the repairs have been completed properly. Two successive successful drop tests are required – one to demonstrate proper operation and full closure, and a second to verify that the door was properly reset. The trained door systems technician’s company and building owner should retain a written record of the drop test results, including the names of witnesses.

UL provides special provisions for replacement of bottom bars.

A replacement bottom bar must be ordered from the original fire door manufacturer and produced in accordance with the specifications in the manufacturer’s UL follow-up service procedure. The order should include the manufacturer's serial number and, if available, the UL label affixed to the damaged bottom bar. The manufacturer will make the replacement bottom bar and attach a new UL replacement part label, including the hourly rating, or in some cases a new label for the entire door assembly. They will then ship the replacement bottom bar, along with instructions for installation and drop testing, to a qualified door company to complete the repair. The

Page 98: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

98

manufacturer is required to maintain a record of the original fire door factory order number and original UL label or certificate number along with the serial number on the UL replacement bottom bar label. This information must be available for a minimum of one year for review by UL representatives.

Modifications of any fire door are not subject solely to the authority of UL and/or FM approvals. Such modifications should be arranged with the door manufacturer, and with the AHJ. All modifications should result in a door and installation conforming to all requirements of NFPA 80 as well as any other required standards.

Servicing an Existing Rolling Door Although the information contained in this study guide is intended to cover a wide range of rolling doors, there are times when you will encounter doors that are not familiar to you. This may be doors that are very old or ones that have been modified with other manufacturer’s parts. In those cases, it is important that you follow the original manufacturer’s recommendations. If you do not have those recommendations, you will need to contact the manufacturer for this information or ask the building owner if they have a copy of the door manual on file. If none are available and the manufacturer cannot be contacted, you will need to assess the situation and make one of the following recommendations to the building owner. Do not perform service or fire door drop testing; and recommend that a door be replaced if:

• Servicing the door will result in an unsafe condition.

• The door is damaged or modified and cannot be repaired.

• The door is no longer manufactured, and the required repair parts are not available.

• A fire door is damaged or modified and cannot be repaired using parts from the original manufacturer.

• The original manufacturer of a fire door is out of business.

• The door has sustained un-repairable damage.

Do not perform service or fire door drop testing; and recommend that the owner obtain service from another qualified entity if:

• The door is not functioning correctly, and you do not have the information or manuals available to correct the situation.

• You do not have access to necessary parts for a fire door from an original manufacturer whom you know to be in business.

• You do not feel qualified to service the door properly.

Proceed with service and/or fire door drop testing if and only if:

• After reviewing the site, you determine that you have the expertise to proceed with the service call and complete the repair.

• The door is not damaged, only requires routine maintenance, or all repairs for a fire door can be done using parts from the original manufacturer.

Relocating an Existing Rolling Fire Door

Rolling fire doors have occasionally been removed from their original installation and then reinstalled on a different opening. The following information is a list of guidelines taken from DASMA TDS 285, which outlines items that manufacturers, dealers, code officials, design professionals, and building owners and managers should consider before such an existing door is relocated.

Page 99: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

99

• Locate the original fire door label from the approval agency on the bottom bar or the original oversize door certificate. If this information is not available, or is illegible, it may be difficult or impossible to get the door approved by the AHJ in its new location. Purchasing a new door may be a better option.

• Verify the other opening is the same size. A fire door is manufactured for a specific opening width and height. It cannot be field modified to fit either a larger or smaller opening. A larger door might be able to be installed covering a smaller opening without being modified if it can be properly mounted and attached.

• Verify the wall construction is the same. A fire door may have been manufactured for a specific wall construction and mounting condition. The wall construction where the new opening is located must be in accordance with the listing of the door. Some doors, especially older ones, were approved only for installation on masonry wall construction. The wall bolts used to reinstall the door must also be in accordance with the listing of the door.

• Verify the wall rating is the same. A fire door is manufactured with a specific hourly rating. It is not uncommon for a fire door rating to be less than the rating of the wall on which it is installed, but it must be as required by local codes and the Authority Having Jurisdiction. For example, a 1½ hour rated fire door is commonly allowed on 2 hour rated non-masonry wall construction if it is listed for such an installation. A fire door with a rating higher than that of the wall is normally acceptable.

• Verify the fire door is still code compliant: o The Authority Having Jurisdiction may

require the fusible link system to be set up so there are fusible links on both sides of the wall. If the existing system is not, additional fusible links and chain or cable will need to be purchased from the original

manufacturer of the door to set up the new release layout.

o If the original door is equipped with only fusible links to trigger the automatic closing, it must be evaluated for acceptability at the new location. Relocation of the door may require the door’s automatic closing to be triggered by the building’s alarm system with the fusible links being used only as a back up to this system. If this is the case, an approved electro-mechanical releasing device will need to be purchased to reinstall the door and connect it to the building’s alarm system. Additional fusible links and sash chain / cable may also need to be purchased to set up the release layout.

o If a fire door is being moved to an opening on a corridor or certain other locations, current building codes may require that the door also be leakage rated as an air leakage rated “smoke door” assembly. In most cases, an existing fire door cannot be field-labeled to comply. Even if the existing door can be field-labeled, purchasing a new door may be a better option.

• Inspect and consider the condition of the door. Depending on the age of a fire door, how well it operates, whether there is damage to be repaired, wear to the existing components, and other potential issues, it may not be worth moving. After the door is reinstalled, it must also be drop-tested successfully two times in accordance with the requirements of NFPA 80.

• The door must be re-installed at the new location per the original installation instructions and as originally required by its listing. Copies of the original installation drawings/instructions should be available to refer to for reinstallation of the doors. If not, the door manufacturer should be contacted for availability of such drawings. In most cases, the manufacturer will require the original job

Page 100: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

100

number in order to provide these documents. This may be on a nameplate somewhere on the door, most likely on the bottom bar, or it may be marked in an inconspicuous location such as inside the sheet metal hood, on the counterbalance shaft or inside one of the end plate brackets of the door. Check to see if this number is available before contacting the manufacturer for drawings.

• The following items are among those that must be verified: o Expansion clearance beneath the

guides or above the top of the coil o Size and type of wall mounting bolts o Bolt locations in the guide and wall

angle slots o Type of washers used on the mounting

and assembly bolts

• Consideration must be given to what will happen to the existing opening. o If the existing opening is part of a

building undergoing demolition, no further consideration is needed.

o If the existing opening is part of a building undergoing abandonment, consultation with a fire protection engineer and the Authority Having Jurisdiction may be needed as to whether the opening can be left open.

o If the existing opening is being replaced by another door with different specifications, the Authority Having Jurisdiction should be consulted.

o If the existing opening is being left open and the areas on both sides of the door are still under the same use, a fire protection engineer, and the Authority Having Jurisdiction should be involved.

• Consider if the relocated door will satisfy building codes and if documentation exists to demonstrate such. The Authority Having Jurisdiction has the final authority regarding approval. The manufacturer and/or the door listing agency will likely need to supply supporting information relating to the relocation.

In conclusion, it is very important to inspect, operate, and drop-test a fire door before committing to move it. It may also be necessary to consult with the door manufacturer to obtain any information that cannot be determined by a site inspection. As with any fire door installation, doors that are relocated must be installed per the provisions of NFPA 80 and meet the requirements of the AHJ.

Safe Operation of Rolling Doors Rolling doors are very large heavy moving objects. When operated safely and correctly, potential hazards can be mitigated. It is essential for the professional technician to be intimately familiar with the safe operation of these doors not only to follow these procedures on the job site, but to educate the end users. Some of these procedures may seem like common sense, but it is important not to take them for granted and lose sight of their importance. The following is a list of guidelines to follow for the safe operation of Rolling Doors:

• Visually inspect the door for physical

damage or defective components before

and during each operation.

• Release all locking devices prior to

operating the door. Attempting to operate

a door while locks are engaged can cause

damage to the lock and/or operating

mechanisms.

• Only operate the door when it is in full

view. User intervention can be much more

effective in avoiding dangerous situations

than relying upon any safety accessories

the door may have.

• Operate the door only when it is properly

adjusted and free of all obstructions.

• Always operate doors with smooth,

controlled movements. Jerking hand

chain, slamming doors open or closed,

Page 101: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

101

and start/stop operator movements can

cause damage and wear to the door

and/or operator components.

• For manually operated doors, lift the door

using lift handles or suitable gripping

points only.

• Never walk away from a closing door until

it has safely reached the closed position.

The door should be observed for the

duration of its movement to ensure safe

closing.

• Do not walk or drive under a moving door

regardless of if it is closing or opening.

• Keep people clear of the opening while

the door is moving.

• Do not operate a door that is jammed, has

a broken spring, or is damaged in any

other way. Attempting to operate a

damaged door could result in additional

damage or injuries.

• Avoid stopping the door at locations other

than open and closed.

• Secure all operator controls to prevent

use by unauthorized personnel.

• Keep controls away from children. Do not

allow children to play with, on, or around

the door or operator.

• Do not pull electric operator hand chain or

release lever during operation.

• Keep hands and other body parts away

from a moving door.

• Never operate a door under high wind or

air pressure differential environments.

Wind/pressure gusts can cause the door

to lockup or exit the guides resulting in

damage to the door.

• Should the door become difficult to

operate or completely inoperable, a

trained door system technician should

perform immediate repairs.

• Follow proper lock-out/tag-out procedures

to secure a malfunctioning or damaged

door from operation until repaired to

prevent safety risks to others.

Floor Level Disconnect Operation Many fire doors now provide floor level disconnects which afford convenient access to drop test and ease of resetting a fire door. With this added functionality comes added risk. It is imperative that the professional technician fully understand and explain these risks and appropriate procedures to the end users of the door. The following guidelines are provided as reference for understanding these risks and the proper procedure for using a floor level disconnect to drop test a fire door. Always follow the manufacturer’s instructions precisely when drop testing any fire door to ensure safety of surrounding personnel and to prevent damage to the door or its automatic closing function.

• Do not close the door by pulling the

release lever. The floor level disconnect

should be used for fire door drop testing

only.

• Never activate a floor level disconnect

during operation of the door.

• Follow the manufacturer’s instructions and

safety guidelines for drop test procedures.

• Do not

perform a

drop test

without

roping off

the

opening.

The door

descends rapidly during the test drop.

Rope off opening to keep persons from

entering area during a test.

• Secure hand chains and any other

moveable items before drop testing a

door.

Page 102: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

102

• Clear opening of all obstructions to ensure

clear path of travel to the closed position

prior to drop testing.

• Never activate a floor level disconnect on

a damaged door.

• Only operate floor level disconnects from

the full open position. Activating a fire

door closing mechanism from any position

other than fully open could result in

damage or injury.

• Never attempt to stop a moving door once

a drop test has been initiated.

• If the floor level disconnect is activated

and the door does not fall, immediately re-

engage the disconnect and secure the

door from falling. A trained door system

technician must properly repair, adjust,

and drop test the door to correct the

problem and restore operation.

• Always drop test a door twice

consecutively to ensure proper reset of

the floor level disconnect. Failure to verify

proper reset procedure could prevent the

door from closing in the event of a fire or

cause improper operation resulting in

severe damage or injury.

• Proper drop testing should verify the door

closes in full width contact with the sill and

travels no slower than 6 in/sec and no

faster than 24 in/sec.

• Always secure floor level disconnects to

prevent use by unauthorized personnel.

Page 103: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

103

Maintenance and Troubleshooting The following sections illustrate some common maintenance and troubleshooting techniques for doors and operators. These are not intended as actual procedural instructions, but as a template for general practices with which a professional technician should be familiar. Many operators include electronic error codes to aid in troubleshooting problems. Do not lubricate a motor. Motor bearings are rated for continuous operation. Do not lubricate a clutch or V-Belt. Inspect and service whenever a malfunction is observed or suspected. Always disconnect operator from power source before servicing. WARNING! Never adjust the operator clutch to compensate for an improperly balanced or damaged door. Repair all door defects prior to adjusting operator settings.

Door and Operator Maintenance Schedule Check at intervals listed in the following chart:

Item Procedure Monthly Every 3 Months

Every 6 Months

Every 12 Months

Drive Chain Check for excessive slack.

Check & adjust as required.

Lubricate.*

X

Sprockets Check set screw tightness

X

Clutch Check & adjust as required

X

Belt Check condition and tension

X

Fasteners Check & tighten as required

X

Manual Disconnect

Check & Operate X

Bearings & Shafts Check for wear & lubricate

X

Door Inspect for wear and damage

X

Operator Inspect for unusual noises

X

Operator Inspect for evidence of corrosion

X

PhotoCell/Sensing Edge Operation

Verify proper operation.

X

*Use SAE 30 Oil (Never use grease or silicone spray)

Page 104: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

104

Troubleshooting Rolling Doors The chart below is a list of possible problems with the operation of a door. The causes listed are the most common and are not meant to include all possibilities. With the variety of the product and the field conditions, other factors may be involved. If assistance beyond this troubleshooting chart is needed, please contact the supplier.

TROUBLE POSSIBLE CAUSE

REMEDY

Door is difficult to open; closes easily

Insufficient tension Increase spring tension

Door is difficult to close; raises easily

Too much tension Decrease spring tension

Door jumps up from floor

Too much tension Decrease spring tension

Curtain runs to one side

Broken endlocks Barrel not level Slat misalignment

Check and replace Check and level barrel Check and align

Door sticks when closing

Bent guide angle(s) Inspect for bent or kinked guides. Straighten guides and check opening measurement.

Door coil makes cracking sound

Bent slats Inspect, remove and straighten or replace

Door squeaks when operating

Tight guides Dirty guides

Check alignment and spacing. Inspect and clean inside of guide. Use light, weather proof lubrication.

Door is difficult to raise, will not stay open

Broken spring Remove barrel and replace spring.

Motor runs, door does not operate

Curtain jammed;

Inspect and remove obstruction.

Drop speed too fast. Insufficient tension. Governor Malfunction

Increase spring tension. Inspect/adjust governor

Drop speed too slow.

Too much tension. Governor Malfunction

Decrease spring tension. Inspect/adjust governor

Door does not drop when tested

Improper sash chain/cable routing Curtain bound

Check and adjust sash chain/cable routing. Check hood/flame baffle is not rubbing the curtain. Check curtain is not rubbing the guides.

Door does not operate

Release lever disengaged.

Check sash chain/cable routing

Page 105: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

105

Troubleshooting OperatorsOperators are tested and adjusted before shipping from manufacturer. If a problem arises, in most cases it is after installation and external devices are connected. If after connecting external devices you encounter problems, the trouble often lies in the external devices themselves or in the wiring leading to them. Verify all external wiring making certain that there are no wires pinched anywhere and that there are no voltages being sent into the control circuit. The operator functions only with dry contacts: all voltages necessary for proper functioning are generated by the operator transformer. The following troubleshooting guide will help you identify the source of the problem given a particular symptom.

Symptom Possible Cause Suggested Action

Door will not respond to open or close push buttons.

Motor has overworked, and the overload thermal protection has tripped.

Reset the overload protection: press reset button located on the side of the unit for a single-phase operator. For a three-phase operator, the switch is inside the motor, let the motor cool and restart operator. Is the door unbalanced? Is a larger operator needed?

Circuit breaker tripped. Reset circuit breaker.

Fuse is blown. Replace fuse. If control circuit fuse keeps blowing: Disconnect all external devices. Leave power terminals connected. (Remove power to terminals). Run the operator artificially by using jumpers and shorting out the appropriate terminals as indicated in the startup and testing guide. Then reconnect the various external devices one by one until you find the one causing the short to ground. Or, if you have an ohm-meter, use it to check all incoming wires for continuity to ground. The meter should read infinity in all instances. If there is conduction between and control circuit wire and ground, this indicates a leak to ground and this is why the control circuit fuse blows when power is applied. In some cases, the trouble is intermittent, i.e., the fuse only blows at certain times. This problem is difficult to detect, but again, disconnect all wires going to external devices and run the operator. If the fuse does not blow, this indicates the trouble lies in the external devices.

Transformer defective. Replace.

Defective Stop button. Replace.

Loose connection in one of the push buttons.

Verify, tighten, or replace.

Defective open or close push button.

Replace.

Door will not respond to open command but will respond to close command.

Defective Open push button. Replace.

Defective Open Limit Switch. Replace.

Loose wire on open push button, open limit switch, or coil of open contactor.

Verify, tighten, or replace.

Door will not respond to close command but will respond to open command.

Defective close button. Replace.

Defective close limit switch. Adjust.

Loose wire on close push button, close limit switch, or coil of close contactor.

Verify, tighten, or replace.

Page 106: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

106

Door moves in wrong direction with a three-phase motor.

Incorrect phasing. Interchange any two power leads.

Door closes by itself and operator does not shut-off at the end of closing travel.

Close contactor is defective. Verify and replace.

Door opens by itself and operator does not shut-off at end of opening travel.

Close limit switch defective. Verify and replace.

Open contactor is defective. Verify and replace.

Door coasts when stopped at any position.

Brake pad is worn out or requires adjustment.

Replace or adjust.

Sensing edge does not reverse door.

Pneumatic hose broken, electrical wiring not connected.

Replace or reconnect.

Reversing devices will open the door when the door is closed.

Advanced close limit switch is defective.

Replace.

The advanced close limit switch is not being engaged by traveling cam.

The advanced close limit switch needs adjusted slightly ahead of the close limit switch.

When door closes it reverses to fully open after it hits the floor.

The advanced close limit switch is defective.

Replace.

The advanced close limit switch is not being engaged by traveling cam.

The advanced close limit switch needs adjusted slightly ahead of close limit switch.

A close command is being given. Check close push button or any closing device for short-circuit.

Radio-control does not function or hesitates for 10 seconds before working.

It is normal for a radio receiver to take up to 10 seconds to warm up before being fully operational. Therefore, when applying power for the first time, the radio control will take 10 seconds before becoming operational.

Check protocol code pins of the transmitter and receiver-they must be the same. Press on the transmitter and listen to the receiver-you should hear a faint click. The transmitter battery may be dead, or your receiver may need servicing. To test for radio-control function, short out momentarily terminals 7 and 8 on the terminal strip. Operator should function normally. Have the radio-control verified-the mini-relay inside the receiver may be defective.

Motor hums, starts when spun.

Capacitor defective. Replace.

Motor fails to shut off at fully closed or opened positions.

Defective limit switch. Operate limit switch manually while door is moving. If door does not stop, replace switch.

Limit cams are not adjusted. Verify and adjust.

Limit drive chain broken. Replace.

Loose sprocket on limit shaft. Tighten set screw.

Limit shaft does not rotate. Verify and replace.

Motor turns but door does not move.

Sprocket key is missing. Replace.

Drive chain is broken. Replace.

Clutch is slipping. Adjust clutch tension.

Motor hums or does not run.

Door locked or jammed. Verify manual operation of door.

Dead phase (three phase supply). Check power supply, fuses on each phase.

Brake does not release. Check wires to brake solenoid. Verify and adjust brake tension.

Limit switches do not hold their settings.

Loose drive or limit chain allows chain to jump sprocket teeth.

Adjust chain to proper tension.

Limit cam retainer not engaging slots in limit cams.

Be sure retainer is in slots of both cams.

Limit cams are binding on the shaft threads which allow them to jump position on retainer.

Lubricate shaft threads. Limit cams should turn freely.

Page 107: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

107

Radio control opens and reverses the door, but when the door is fully opened, will close door a little and bounce back to open position again. Door cannot be closed except by the close push button.

Advanced open limit switch is insufficiently advanced from the full open limit switch. When the door is fully opened, and a pulse is sent from the transmitter, the receiver maintains contact for 1.5 seconds. If the advanced open limit switch has returned to its normal state, the reversing relay will be activated, and the door bounces back to the open position.

Adjust the advanced open limit switch by bending the switch arm away from the open limit switch arm and more towards the traveling cam.

Electrical Procedures

• Disconnect operator from power source before opening the control box.

• Inspect the wiring compartment and remove any dirt from the control unit.

• Inspect all grounding wires and terminations for corrosion. Be particularly careful to check ground wires.

• Check the terminal strip to ensure that all screws are tight.

• Verify that the safety edge or other safety devices installed on the operator are fully operational.

• Verify the voltage at the input terminals while the operator is running. The voltage must not drop more than 10% during operation. If the voltage drop is excessive when running, the relays may chatter, the contact points will wear prematurely and may eventually weld.

• Inspect the power terminals for corrosion.

• Verify the current consumption of the unit with an amp-meter. The value of current should be consistent with the name-plate specifications.

• For three-phase operators, incorrect phasing of the power supply will cause the motor to rotate in the wrong direction. To correct this, interchange any two of the incoming three phase power lines.

Conclusion This section on service and maintenance should provide a solid background of basics with which to start. To become proficient, you must experience many different types of job situations and have the opportunity to work with seasoned door technicians. If you run into difficulty and do not have access to the manufacturer’s guidelines, you should always contact your supervisor or the manufacturer for the most effective and safest solution. You must always work with an attitude of safety when working in the repair of overhead doors because of the potential danger that exists in a malfunctioning door. Use common sense and think about the consequences of what you do during each step of the repair process. Also, point out any potential problems you see to the customer and make your recommendations in writing. Document everything that was done on a service call and have the customer sign and keep a copy of the paperwork. By taking these recommended steps, you will limit potential liability to you or your company in the event that anything should go wrong with the door after you have completed your work. Most building owners disregard their rolling door’s need for maintenance or service work until something goes wrong. Take a few minutes to explain routine maintenance procedures and attach rolling door safety literature to the service paperwork.

Page 108: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

108

Section Ten

Glossary of TermsReferences

Refer to the latest editions for the most current terms and definitions:

1. UL 325, Standard for Door Drapery, Gate, Louver, and Window Operators and Systems

2. DASMA TDS #277, Metal Coiling Slat Door Terminology

3. NFPA 70, National Electrical Code 4. DASMA Technical Data Sheet #160,

Sectional Garage Door Terminology

5. DASMA Standard #302, Garage Door Operator and Gate Operator Terminology

Access Panel: An opening in a ceiling for

access to tension adjusting wheel and to drive mechanism (motor, crank, chain hoist). Furnished by the ceiling subcontractor or general contractor and not by the door manufacturer.

Accessory: Any supplemental item or

device added to the basic gate or door system

Adjusting Wheel: See Tension Wheel. Adjustable Clutch: A friction device that is

designed to slip when torque exceeds a defined threshold

Air Infiltration: The leakage or passage of

air through a door system Approved: Acceptable to the Authority

Having Jurisdiction. Astragal: Neoprene or vinyl

weatherstripping added to the bottom bar to seal opening along the floor or

to protect a finished surface.

Authority Having Jurisdiction (AHJ):

The organization, office, or individual responsible for approving equipment, an installation or a procedure.

Automatic Closing Device:

A device, that causes the door or window to close when activated by a fusible link or other release device.

Automatic Fire Detectors:

Either individual devices or prescribed combinations of devices designed to detect flame, heat, smoke or combustion gases resulting from fire.

Backroom: Amount of clear

unobstructed space extending back from the face of the wall.

Barrel Assembly: A steel tube or pipe that

spans between the door brackets and contains the springs required to provide counterbalance and lifting capability. The curtain coils up around the barrel.

Barrel Ring: Stamping or casting,

attached to counterbalance pipe or barrel, which is used to increase the curtain wrap diameter and which is attached to the curtain top slat.

Page 109: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

109

Bar Stop: See Wind Bar. Base Plate: Optional steel plate

mounted on the floor to distribute weight from a framing system supporting the door.

Bellmouth: Flared upper portion of

guides to ease entry of curtain into the guides.

Between Jamb Mounted:

Type of mounting where the guides are positioned between the mounting surfaces and not on the face (interior or exterior) of the wall. Guides are generally "packed out" mounted to the inside of jamb and hood below lintel. Clear opening size will be reduced and may require "fascia" to close off back of hood.

Bottom Bar: A reinforcing member at

the bottom of a curtain; generally either two angles back-to-back forming an inverted "tee.” Serves to add lateral strength to door, to add weight to help curtain close, to act as an obstacle to stop door when fully open, as a stop plate, and to hold weather-stripping.

Brackets: End supporting plates for

the barrel counterbalancing assembly. One plate is the drive (chain hoist, crank or motor side) plate, the other is the tension (spring adjusting side)

plate. Each bracket is generally supported by the wall angle of the guide assembly.

Brush Seals: Term used to refer

generically to the use of brush filament material either in use as a weather-seal or when used as smoke seals for smoke and fire doors.

Brush Weatherstripping:

Weatherstripping for use on all configurations of doors to close the gaps at jambs and header. Brush material can be UL listed for "fire door" use.

Cable Sensor Edge:

An edge that uses two cables inside a standard neoprene loop astragal. Upon connection with motor operator, a sensing field is established between the two cables. Any disturbance to this field causes the motor and door to stop and reverse (or stop).

Ceiling: Top horizontal surface in

the interior of a garage or other building.

Chain Hoist: A mechanical device to

assist in raising and lowering the door by use of hand chain.

Charge Pin: A metal pin used to lock

tension wheel after proper spring tension is applied.

Charge Wheel: See Tension Wheel

Page 110: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

110

Closed Position: A position of the door curtain with the underside of the bottom bar, including an astragal or sensing edge, if provided, in contact with the sill along the entire width of the opening.

Closing Device: A means of closing a door

from the partially or fully opened position.

Counterbalance Assembly:

A system of springs or weights to provide the amount of force needed to raise the door and maintain it in the open position.

Crush Plates: Continuous steel-bearing

plates provided where doors are mounted on concrete masonry wall units with hollow cells to accommodate through-wall bolts to prevent crushing of the hollow concrete masonry unit.

Curtain: The part of the door that

actually rolls up and down, or slides side to side. It is manufactured of slats, endlocks, and/or windlocks.

Cycle: An action on the door from

the fully closed position, to the fully open position, and returned to the fully closed position.

Cylinder Lock: Key-operated locking

device located on the bottom bar.

Detectors: A device suitable for connection to a circuit that has a sensor that responds to a physical stimulus such as heat or smoke.

Double Throw Lock:

Center locking device that throws a locking bar into both guides, mounted on bottom bar.

Drive Gear: Large gear for chain- or

crank-operated units. It is directly fastened to the door shaft on the drive side bracket.

Drive Plug Assembly: See Plug End. Drive Shaft: The shaft in the barrel that

is securely attached to the barrel, through welding or pinning. When this shaft rotates the barrel should also rotate.

Door Frame: The frame into which the

door fits; consists of two door jambs and a door header

Door Header: The upper part of a door

frame, consisting of the head jamb, head casing, stop and trim molding

Door Jamb: The upright framing on

each side of the door opening

Door Opening: Dimensions taken

between the face of walls or jambs and from the floor to the header.

Page 111: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

111

Door Size: Door dimensions characterized by the width first and the height second

Drive Chain: A chain that connects to

the final drive mechanism Drive Plug Assembly: See Plug End. Drive Shaft: The shaft in the barrel that

is securely attached to the barrel through welding or pinning. When this shaft rotates the barrel should also rotate.

Dropout: Weighted mechanical

device for disengaging gearing or motor operator for rolling fire doors. Also used to activate closing device and to actuate governor in case of fire.

Drop Test: Test performed on a fire

door to ensure proper operation during emergency. Testing is required to be performed annually (see NFPA 80).

"E" Guides Common expression for

the shape that guides form when they are mounted to steel jamb supports or frames.

Electric Operator An electrically powered

device to assist the opening and closing of a door.

Electric Sensor Edge

See Sensing Edge. Electromechanical Release

A device which holds the auto close device until it is released by a signal from

a fire alarm or detection system. If power fails, the device also releases. There are a variety of types and manufacturers. Most have a time delay before release to prevent nuisance releases.

Emergency Electric Operation

Any rolling door with a motor operator and an Uninterruptible Power Supply (UPS) capable of opening and closing the door several times while facility line power is off.

Endlocks Steel stamping or

malleable iron castings which are riveted to curtain slat ends to prevent slats from shifting laterally, and to provide curtain wearing surface in guides. “Alternate endlocks” are at both ends of every other slat, commonly for service and rolling fire doors. “Continuous endlocks” are at both ends of every slat.

End Plates See Brackets. Entrapment The condition when an

object is caught or held in a position that increases the risk of injury

Entrapment Protection Device

Any device intended to prevent persons from becoming entrapped by a door system.

Exterior Hood Hood construction with a flat flange at the top of hood to accept field caulking.

Page 112: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

112

Exterior Mounted Condition where door is

mounted on exterior surface exposed to weather and wind load. Usually requires "exterior hood” and "gear covers".

External Entrapment Protection Device

A device located outside the door operator, intended to prevent persons from becoming entrapped by the door.

Face of Wall Door mounting condition

where guides mount directly to wall, and side clearance is allowed for tension wheel and drive mechanism.

Fascia Metal closure for back of

door housing. Required when there is only a partial or no header in place and back of door coil is exposed. Required when the wall above header is not full thickness of jamb (prefab building).

Fire Door A door that has a fire

protection rating and will close to the floor automatically in case of fire.

Fire Door Assembly

Any combination of a fire door, a frame, hardware, and other accessories that together provide a specific degree of fire protection to the opening.

Fire Protection Rating

The designation indicating the duration of the fire test

exposure to which a fire door assembly or fire window assembly was exposed and for which it successfully met all acceptance criteria as determined in accordance with NFPA 252, Standard Methods of Fire Tests of Door Assemblies, or NFPA 257, Standard for Fire Tests of Window Assemblies, respectively.

Fire Resistance Rating

The time, in minutes or hours, that materials or assemblies have withstood a fire exposure as established in accordance with the test procedures of NFPA 251, Standard Methods of Tests of Fire Endurance of Building Construction and Materials.

Fire Shutter A labeled door assembly

used for the protection of a window opening in an exterior wall.

Flame Baffle A hinged piece of sheet

metal within the hood that, when released, closes the space between the top of the curtain and the hood of a rolling door.

Fuse Link Housing

Box in which fusible links are sometimes furnished when rolling fire doors are mounted above ceiling to provide a finished exposure area in ceiling for link.

Page 113: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

113

Fusible Link Two metallic pieces that are joined together by a low temperature alloy. When the ambient temperature exceeds that of the alloy the connection melts and the pieces separate. These are used to release holding chains or cables that maintain a mechanical fire door release system. The most common temperature for a fire door is 165°F.

Gear Cover Metal cover protecting the

drive mechanism from weather and debris.

Governor Device on rolling fire door

drive brackets to control rate of descent of rolling fire door when released in the event of fire.

Guide Assembly Consists of two or more

angles or a roll-formed channel to create a groove in which the rolling curtain moves up and down.

Guide Standout The distance that face-

mounted guide assembly extends from wall face.

Gussets See Brackets. Half Slat Modified bottom slat used

to attach bottom bar angle(s) to bottom of curtain.

Hand of Operation The side on which the

door operation mechanism is placed, as viewed from the coil side of the door. It is either a RH or LH operation.

Header Seal Weather-stripping mounted to opening header to seal the opening between header and curtain, sometimes used where hood baffle is ineffective.

Headplates See Brackets. Headroom Amount of clear

unobstructed space above the door lintel or header.

Helical A term referring to the

spiral shape of torsion spring coils used in the spring counterbalance.

High Cycle Spring Counterbalance springs

with increased cycle life capability for high usage doors

Hood Metal cover that conceals

the door coil and is attached and supported by headplates and intermediate hood supports (if required).

Housing See Hood. Inch-Pounds English unit of

measurement of torque applied to a shaft.

Initial Charge See Initial Turns. Initial Tension See Initial Turns. Initial Turns Amount of turns of the

tension shaft to apply spring tension from zero with the door in the fully open position. These turns provide the minimum moment or force to hold door in the open position

Page 114: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

114

and/or establish the intended spring tension for underbalanced fire doors.

Inset See Setback. Installation Placing a door in position

for use Installer Technician placing the

door and access system in position for use

Insulated Door Door system that includes

door sections containing an insulating material

Insulation Material having the ability

to reduce heat or cold transmission.

Interlock, External An electrical switch to

prevent motor operation if locking device is not first disengaged.

Intermediate Hood Support

A rigid member which is contoured to the shape of the hood and mounted to the wall, between the headplates. The hood is then attached to the support to give the hood rigidity.

IPPT Acronym for Inch-Pounds

Per Turn; torque rate of a spring, indicating the number of inch-pounds of torque delivered to a shaft for each turn the spring is wound

Jamb The vertical member that

frames the side of an opening in the wall.

Jamb Angle See Wall Angle.

Jamb Load Force exerted on jamb by

guide assembly when curtain is subjected to wind load.

Key A square piece of steel

that slides into a key way to prevent the spinning on one object to another

Key Switch Control

Use of key to actuate a door operator in place of a push-button or transmitter

Key Way A groove, milled into an

object, which when used with a key will prevent an object from spinning on another subject

Keyed Shaft A shaft that has a built-in

key Keyed-Alike Two or more lock cylinders

of the same series K-Value Laboratory-determined

value of thermal conductance of a material; not normally used in conjunction with thermal transmittance through garage doors

Labeled Door The largest size of a fire

door or fire shutter assembly fire proven by test to meet a specific fire rating.

Labeled Equipment, materials or

services included in a list published by an organization that is acceptable to the Authority Having Jurisdiction and concerned with evaluation

Page 115: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

115

of products or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states that either the equipment, material, or service meets identified standards or has been tested and found suitable for a specified purpose.

Lift Handle A handle supplied on

manual push-up doors, to assist in raising and lowering the door.

Lintel A beam provided over an

opening to carry wall or roof loads over an opening.

Magnetic Release Device connected to a

smoke detector or alarm system, that on either an interruption of electrical power or applied signal will release the automatic closing device of a fire door or fire shutter.

Manual Override Means of operating a

motorized door by manual operation in case of power loss.

Master Keying Arrangement whereby

cylinder locks, although fitted with different keyed cylinders can be opened or locked by means of one "master" key.

Motor Cover Metal cover to protect the

motor from exterior weather, debris, or to meet

OSHA safety requirements.

NFPA 72, National Fire Alarm Code

Code deals with the application, installation, performance, and maintenance of fire alarm systems and their components.

NFPA 80, Standard for Fire Door and Fire Windows

Regulates the installation and maintenance of assemblies and devices used to protect openings in walls, floors, and ceilings against the spread of fire and smoke within, into, or out of buildings.

Offset Dimension between face

of header or jamb and center line of curtain. Required to reduce drag of curtain on bellmouth of guides when curtain is in a lowered position.

Opening Height The distance from the floor

to the top of the door opening

Opening Width The distance between

jambs of the door opening Operator A device used to control

the up and down motion of the door

Oversized Door A fire door or fire shutter

assembly that is larger than a labeled door size, that receives a label or a Certificate of Inspection implying that the door conforms to fire protection construction requirements.

Page 116: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

116

Packout Guide build-out to clear an obstruction or provide clearance for drive or tension mechanism when door is between-jamb mounted.

Pass Door Hollow-metal pedestrian

door integrated into the rolling door, the frame of which is hinged at the jamb, so door frame swings out of the opening.

Photoelectric A sensor that consists of a

light-emitting device and a light-receiving device. If the beam of light is blocked by an obstruction, the sensor signals the operator to stop and reverse.

Pipe Shaft See Barrel Assembly. Plug End Drive end of barrel

assembly driven by gear or sprocket for which the curtain is raised and lowered. Consists of assembly of short solid shaft and one or more round plates welded to the shaft and pipe which fit within the pipe.

Power-Operated Fire Doors

Doors that normally are opened and closed electronically, pneumatically, or mechanically.

Pre-turns See Initial Turns R-Value Thermal resistance value;

inverse of U-Value.

Rolling Steel Fire Door A fire door assembly consisting of a curtain, bottom bar, barrel, guides, brackets, hood and an automatic closing device.

S-Hook A type of hook used to

connect a cable to a pulley assembly.

Security Chain Box

Metal enclosure that encloses hand chain in a steel pad-lockable assembly attached to door guide.

Sensing Edge A device mounted on the

bottom bar of an electrically-operated door to stop or stop-and-reverse the closing door upon contact with an obstruction in the door opening.

Sensing Edge, Electric

An electrical bottom bar astragal enclosed with two parallel foils. When closing door bottom bar touches an obstruction, the foils close an electric circuit to cause the operator to stop or stop-and-reverse the door.

Sensing Edge, Infrared Type

Bottom bar astragal enclosing a tube with an infrared transmitter at one end and a detector at the other end. When IR source is obstructed the operator will stop or stop-and-reverse the door.

Page 117: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

117

Sensing Edge, Pneumatic An air hose installed inside the bottom bar astragal and connected to a diaphragm switch, to signal the motor operator to stop or stop-and-reverse the door.

Service Counter Fire Door

A labeled fire door assembly used for the protection of openings in walls where the primary purpose of the opening is for non-pedestrian use, such as counter service for food, a pharmaceutical dispensary, package and baggage transfer, or observation points.

Setback A standard space where

the guide is recessed from edge of the jamb at both sides of opening on a face of wall-mounted door.

Shutter A labeled door assembly

that is used for the protection of a window opening in an exterior wall.

Sideroom Required unobstructed

space on either side of the opening.

Sill The bottom part of an

opening onto which the door curtain and bottom bar come to rest when in the closed position.

Slat Cold rolled member of

door curtain. Slats are formed so as to interlock and form a water-shedding surface.

Slide Bolt Locking device on bottom bar which slides into guide or guide shoe and is equipped for padlocking. Mounted either inside, outside or both sides of the door.

Sloped Bottom Bar

Tapered bottom bar to match sloped sill of opening. Accomplished by inserting a tapered plate between bottom bar angles. This tapered plate will hang into opening on low side unless door height is increased and coil raised to have sloped bar clear opening when door is open.

Smoke Detector A device that senses

visible or invisible particles of combustion and/or heat.

Smoke Gasketing Brush seal used on fire

doors or fire shutters to reduce the passage of smoke and gases.

Sound Transmission Class

An integer rating of how well a building partition attenuates airborne sound.

Spot-Type Detector

A device with a detecting element concentrated at a particular location. Typical examples are bimetallic detectors, fusible alloy detectors, certain pneumatic rate of rise detectors, certain smoke detectors, and thermoelectric detectors.

Page 118: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

118

Spring Anchor A component in a counterbalance assembly, that holds a spring in place while it is under tension.

Spring Counterbalance

See Barrel Assembly. Spring Cycle Life Spring counterbalance is

designed for a fixed number of cycles.

Spring Release Device (Sliding Door, Vertical, Horizontal; Rolling Steel Door)

A device that, when activated, releases part of the spring counterbalancing force and causes the door to close.

Stand-out The distance that guide

assembly extends out from the wall on face-of-wall mounted doors.

Starter, Fire Door A mechanical device to

start the closing of door in the event of a fire and to do it independently of the hand chain, crank or motor operator normally used to close door.

Starter Slats Partial slats used to

connect curtain to barrel rings.

STC See Sound Transmission

Class. Stops Bars mounted at top of

guides to prevent bottom bar from traveling out of the guides when the curtain is fully raised.

Tapered Bottom Bar

See Sloped Bottom Bar.

Tension Wheel Casting or stamped steel assembly, either pinned or keyed to the spring inner shaft, with which the counterbalancing springs are initially tensioned or adjusted and is used in conjunction with a locking pawl or pin to lock adjustment.

Thru-Wall Fusible Link

Extending a fuse linkage to the opposite side of an opening, with respect to the side the door is mounted on. Required per NFPA 80 for all non-exterior wall mounted doors.

Thru-Wall Operation

A door driven by means of a hand chain, crank or motor operator located on the opposite side of the wall.

Thumb Turn Mortise Cylinder

Locking device, much like a cylinder lock but does not require a key to lock or unlock.

Torque The twisting force exerted

by the spring or motor Torsion Spring A helical wound spring,

commonly mounted inside a steel pipe, used to counterbalance curtain.

Tubular Operator A cylindrical operator that

mounts directly into the pipe and electrically drives the barrel assembly.

U.L. Underwriters Laboratories,

a non-profit, non-

Page 119: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

119

government organization that develops safety standards for devices, systems and materials, and labels and lists various products. The organization also operates laboratories for product testing

U – Value Thermal transmission

coefficient which, is a measurement of heat, in BTU’s, transmitted through out square foot of material (the door) in one hour at a temperature difference of 1 degree from one side to the other

Vision Lite A single cut-out of a slat

glazed with fire-rated glass.

Wall Angle An angle of the guide

assembly which attaches to the face of wall and supports the load of the door assembly.

Wicket Door See Pass Door. Wind Bar Channel or bar welded

inside guide groove which engage windlocks under wind load.

Windlocks Malleable iron castings

riveted at predetermined intervals to slat ends to prevent curtain from leaving guides under wind load, and which are used in conjunction with wind bars in guides which windlocks engage under wind load.

Working Turns The additional winding of

the springs as the barrel rotates and the curtain closes.

Page 120: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

120

Section Eleven

DASMA Standards and Technical Data SheetsAvailable Online

Door and Access Systems Manufacturers Association (DASMA) has produced many publications which can aid with both understanding the requirements of the product being installed and dealing with various common situations which arise in the field. These and other Standards and Technical Data Sheets relative to Rolling Doors, Operators, and Electronics can be found at DASMA’s website www.dasma.com in the Publications Section. A certified technician should be familiar with the documents listed below and their content.

DASMA Standards

• Test method for Thermal Transmittance and Air Infiltration of Garage Doors (ANSI/DASMA 105)

• Room Fire Test Standard for Garage Doors Using Foam Plastic Insulation (ANSI/DASMA 107)

• Standard Method for Testing Sectional

Garage Doors and Rolling Doors:

Determination of Structural Performance

Under Uniform Static Air Pressure

Difference (ANSI/DASMA 108)

• Standard Method for Testing Sectional Garage Doors and Rolling Doors: Determination of Structural Performance Under Missile Impact and Cyclic Wind Pressure (ANSI/DASMA 115)

• Standard for Non-Fire Rated Rolling Door Assemblies (ANSI/DASMA 203)

• Standard for Fire Rated Rolling Door Assemblies (ANSI/DASMA #204)

• Standard for Rolling Grilles (DASMA 208)

• Standard for Garage Door Operator and Gate Operator Terminology (DASMA 302)

• Performance Criteria for Accessible Communications Entry Systems (DASMA 303)

DASMA Technical Data Sheets –Operator & Electronics

• Door and Gate Operator Terminology

(TDS #350)

• Loop Systems and Depth in Road

Pavements (TDS #354)

• Access Controlled Egress Doors (TDS

#355)

• Vehicular Commercial Door and Gate

Operators, and OSHS Requirements

(TDS #358)

• Gate Operators, Commercial Door

Operators, and NEC Provisions (TDS

#359)

• Garage Doors Operated in Tandem (TDS

#361)

• Garage Door Operator Pre-Wiring

Diagram (TDS #362)

• Installation Height of Photoelectric

Sensors (TDS #364)

• Sensing Edges (TDS #368)

• Frequently Asked Questions Regarding

Automated Garage Door Systems (TDS

#369)

• Motor Operated Commercial Sectional Doors and Rolling Doors Electrical Service Installation Recommendations (TDS #375)

• Rolling Doors Operated by Roller Chains (TDS #381)

Page 121: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

121

DASMA Technical Data Sheets – Rolling Doors • Residential and Commercial Wind Load

Guides (TDS #155)

• Architects and Designers Should Understand Loads Exerted by Overhead Coiling Doors (TDS #251)

• Test Rolling Fire Doors in the Fully Open Position ONLY (TDS #252)

• Rolling Fire Doors: Installation of Hoods and Covers (TDS #253)

• Guidelines for Installation of Rolling Steel Fire Door Release Assembly (TDS #254)

• Guidelines for Fusible Links (TDS #255)

• Procedure for Repair of UL Classified Rolling Steel Type Fire Doors (TDS #257)

• Rolling Steel Fire Doors: Release Options (TDS #258)

• Metal Rolling Type Door Jamb Construction: Steel Reinforcement in Masonry Walls (TDS #259)

• Common Rolling Door Installation Problems (TDS #260)

• Common Jamb Construction for Rolling Steel Fire Doors: Masonry Construction – Bolted and Welded Guides (TDS #261)

• Common Jamb Construction for Rolling Steel Fire Doors: Non-Masonry Construction – Bolted Guides (TDS #262)

• Common Jamb Construction for Rolling Steel Counter Fire Doors: Masonry Construction – Bolted Guides (TDS #263)

• Common Jamb Construction for Rolling Steel Counter Fire Doors: Non-Masonry Construction – Bolted Guides (TDS #264)

• Standard Rolling Door Architectural Details (TDS #265)

• Rolling Steel Fire Door Protection for Fire Wall Openings (TDS #266)

• Rolling Door Labels (TDS #267)

• Rolling Doors Operated by Roller Chains

(TDS #268)

• Rolling Door Performance Evaluation

(TDS #269)

• Recommended Rolling Door

Maintenance Practices for Building

Maintenance Supervisors (TDS #270)

• Rolling Steel Fire Doors Drop Testing and Annual Follow-Up (TDS #271)

• Rolling Door Counterbalancing (TDS #272)

• Rolling Steel Fire Doors Mounted on Steel Tubes, Set Against Face of Fire-Rated Walls, Bolted Guides (TDS #273)

• Rolling Door Paint Wear (TDS #274)

• Procedure for Repair of Factory Mutual (FM) Approved Rolling Steel Type Fire Doors (TDS #275)

• Rolling Door “Red Zone” for Installations and Service (TDS #276)

• Metal coiling Slat Door Terminology (TDS #277)

• Rolling Steel Fire Doors and Balanced Fire Protection (TDS #278)

• Rolling Door Operation Under Wind Load

Conditions (TDS #279)

• Rolling Door Wind Load Determination –

Effective Wind Area (TDS #281)

• Rolling Doors and Hurricanes (TDS

#282)

• Rolling Door Winding Bars (TDS #284)

• Relocating an Existing Rolling Steel Fire Door (TDS #285)

• Rolling Door Component Substitution (TDS #287)

• Special Considerations for Rolling Fire Doors on Exterior Openings (TDS #288)

• Protecting Rolling Steel Fire Doors from Vehicular Traffic Related Damage (TDS #290)

• Rolling Doors and High Wind Events

(TDS #291)

• Vehicular Access Door Interface with Building Framing (TDS #292)

• Environmental Considerations for Exterior Doors (TDS #294)

Page 122: Rolling Steel Fire Door Considerations...4 Section One An Introduction to Rolling Doors This study guide has been created by the Institute of Door Dealer Education and Accreditation

122

To learn more about the Institute of Door Dealer Education and Accreditation, please visit the IDEA website:

www.dooreducation.com