Rockwell Automation - Drive Safety Design and Techniques
Transcript of Rockwell Automation - Drive Safety Design and Techniques
![Page 1: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/1.jpg)
PUBLIC
Copyright © 2017 Rockwell Automation, Inc. All Rights Reserved. 1
Rockwell Automation - Drive Safety Design and Techniques
![Page 2: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/2.jpg)
PUBLIC Copyright © 2017 Rockwell Automation, Inc. All Rights Reserved. 2
Why Safety?
Safety continues to emerge as core system function
Value of Functional Safety:
Increased productivity
Systematic MTTR reduction
Improved competitiveness
Reduced floor space and direct labor
Reduced costs
Global compliance
Common designs
Improved ergonomics
Reduced injuries
Rockwell Automation is committed to delivering world class safety products & solutions
![Page 3: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/3.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC
3
PowerFlex Series AC Drives Safety Solutions
What Makes a System Safe? • Duality (Also known as Redundancy)
– If one thing fails, there is another thing that can bring the system to a safe state
– In parallel for Inputs or in series for Outputs
• Diversity
– Protects against two things failing in exactly the same way at the same time
– Example: Using one NO and one NC set of contacts
– Example: Using both a high and a low input channel to a safety device
• Diagnostics
– Safety products spend much of their time performing self-diagnostics
– If a problem is detected, the system will go to its “safe state” and will not allow the system to be restarted until the problem is fixed
– Example: A safety PLC has a significantly higher degree of self-diagnostic versus a standard PLC (> 90% vs. ≈ 50%)
![Page 4: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/4.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC
Risk Assessment – The Foundation
Provides Safety Performance Level – Design Target
Creates the Foundation of the Safety System Functional
Requirements, System Design and Validation Protocol
Shows “Due Diligence” and Compliance to Global Standards
S1
S2
F2
F1
Performance
Level, PLr
a
b
P1
P2
e
c
d
P1
P2
P1
P2
P1
P2
F2
F1
S = Severity F = Frequency or Duration of Exposure P = Avoidance Probability
Task/Hazard
Contribution to
Risk Reduction
Low
High
![Page 5: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/5.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC
5
PowerFlex Series AC Drives Safety Solutions
Safety solutions to meet your needs
• IEC 61508 addresses the design and development of Electrical, Electronic and Programmable Electronic Safety Systems (E/E/PE Systems)
– Probabilistic methodology based on probability of failure of the system
– Also introduces a safety life cycle as part of the standard
– Classifies safety control systems into 4 Safety Integrity Levels (SILs)
• Focus is on the the whole life cycle including design, development, use and modification
• Answers the following question:
– What is the probability of failure for the E/E/PE safety system when a safety related demand is placed on that system (known as the “Probability of Failure on Demand”)
Safety integrity level
(SIL)
Average probability of failure
on demand
Probability of a dangerous
failure per hour
4 10-5 to 10-4 10-9 to 10-8
3 10-4 to 10-3 10-8 to 10-7
2 10-3 to 10-2 10-7 to 10-6
1 10-2 to 10-1 10-6 to 10-5
![Page 6: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/6.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC
6
Network
PowerFlex 527/755 SIL3 / PLe (Network)
Hardwired
PowerFlex 70/525/527
SIL2 / PLd
PowerFlex 527/755 SIL3 / PLe
External
PowerFlex Drives
PowerFlex Series AC Drives Safety Solutions
Safety solutions to meet your needs
![Page 7: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/7.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC INFORMATION
Powerflex 525 – Safety Relay
7
![Page 8: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/8.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC INFORMATION
Powerflex 525 Safety Relay
8
![Page 9: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/9.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC INFORMATION
Powerflex Safe Torque Off
9
![Page 10: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/10.jpg)
PUBLIC Copyright © 2017 Rockwell Automation, Inc. All Rights Reserved. 10
Designed for the PowerFlex 755 and 755T AC drives
Safely removes power from the gate firing circuits of the
drive’s output power devices (IGBT)
Provides networked Safe Torque Off over EtherNet/IP
TÜV Rheinland Approved for networked and hardwired STO
PLe, CAT 3 per ISO 62061
SIL3 per IEC EN 61800-5-2
Stop Category 0 per EN 61800-5-2
Networked Safe Torque Off Product Overview
![Page 11: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/11.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC INFORMATION
Powerflex 527 Network Solutions
11
![Page 12: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/12.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC
Integrated Safety on EtherNet/IP How it works
12
Capable of SIL 3 / PLe for Safe Torque Off
> Duality
> Diagnostics
> Diversity
Safety Message Safety Message
Time Stamp Section Data Section
CRC-B
Producer to Consumer
Time_Stamp CRC
Producer to Consumer
Data B
normal data
inverted data
Data A CRC-A Mode
Output B Output A
A B
STO STO
EtherNet/IP CIP Safety Packet provides Duality, Diagnostics and Diversity!
Change to one axis
![Page 13: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/13.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC INFORMATION
Powerflex 527 Safety Solutions
13
![Page 14: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/14.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC
Integrated Safety on EtherNet/IP
14
Integrated Safety Enhances Machine Performance and Flexibility
![Page 15: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/15.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC INFORMATION
Powerflex 520 Logix
15
![Page 16: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/16.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC INFORMATION
Powerflex 520 Application Technique
16
![Page 17: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/17.jpg)
PUBLIC Copyright © 2017 Rockwell Automation, Inc. All Rights Reserved. 17
Networked Safety SIL3/Ple (20-750-S3) Hardwired Safety SIL3/Ple (20-750-S)
Networked Safe Torque Off PowerFlex 755 AC Drives Safety Solutions Offerings
SensaGuard
Non-Contact
Interlocks
GuardLogix
Controller
Guardmaster
Safety Relay
Stratix Switch
PointGuard I/O GuardLogix
Controller
SensaGuard
Non-Contact
Interlocks
Stratix Switch
Eliminate field wiring
and safety relays
![Page 18: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/18.jpg)
PUBLIC Copyright © 2017 Rockwell Automation, Inc. All Rights Reserved. 18
PointGuard
I/OTM
GuardLogix® Integrated
Safety System Controller
PowerFlex 755 with
Networked
Safe Torque Off
Stratix 5700TM Industrial
Ethernet switch
Networked Safe Torque Off Setup Example for SIL3/PLe Cat. 3
![Page 19: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/19.jpg)
PUBLIC Copyright © 2017 Rockwell Automation, Inc. All Rights Reserved. 19
Networked Safety SIL3/PLe
Reduced
hardware & points
of failure
Reduced overall
panel footprint
One node for
safety & drive
Reduced
hardware, wiring
& labor costs
Flexible control
Field installable
Networked Safe Torque Off Product Benefits
![Page 20: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/20.jpg)
PUBLIC Copyright © 2017 Rockwell Automation, Inc. All Rights Reserved. 20
20-750-S3 PowerFlex 527 Kinetix 5500
Common configuration, programming and safety related tags
Networked Safe Torque Off Elements of Commonality Across Rockwell Portfolio
![Page 21: Rockwell Automation - Drive Safety Design and Techniques](https://reader031.fdocuments.us/reader031/viewer/2022012123/61ddf91eecdc5f3f323fbf52/html5/thumbnails/21.jpg)
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC
21
Safety EtherNet I/O Selections for Safety Logix Processors
Safety solutions to meet your needs
Point I/O
Armor Point I/O