Robert McCabe
Director, Health Care Solutions
HTS Chicago
Improved Air Quality and Energy Efficiency
through Air Handler Filtration System Upgrade
Biography
Robert McCabe has been involved in commercial building HVAC and infrastructure for
22 years. As Director of Health Care Solutions for HTS Chicago, Robert is dedicated to
the education of the health care marketplace with regards to critical airflow control.
Robert has Bachelor of Science degrees in Biology from the University of Wisconsin-
Madison and in Electrical Engineering from Marquette University, and an MBA from the
Kellogg Graduate School of Management at Northwestern University.
HTS Chicago is a proven provider of custom HVAC solutions for critical Health Care
and Laboratory environments. HTS Chicago attributes its success in the region to
integrity, industry focus and the longevity of partnerships with premier system
manufacturers.
Presentation: Improved Indoor Air Quality and Increased Efficiency through
Air Filtration System Upgrade
Theme
Building owners and occupants expect more from their buildings today – including both
better indoor air quality (IAQ) and less energy consumption. However, maintaining
optimum IAQ often seems to be in conflict with minimizing operating and energy costs.
This need not be the case.
Goal
The goal of the presentation is to provide participants with knowledge of an alternative to
standard air filtration technologies that will reduce energy consumption, reduce
maintenance labor and material costs, eliminate most odors, and contribute to LEED and
Green initiatives.
Key Topic Areas
Standard air cleaning technologies, pros and cons
Polarized filtration, pros and cons
Key Take Away Points
Standard air cleaning filtration consumes energy and requires frequent maintenance
Polarized filtration saves energy and has 1/3 the life cycle cost of standard filtration
![Page 2: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/2.jpg)
Health Care Indoor Environments Air Filtration Options
Robert McCabe
![Page 3: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/3.jpg)
Objective
Evaluate available technologies for reducing airborne contaminants,
principally particulate, in Health Care environments
![Page 4: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/4.jpg)
Overview
Contaminant levels must be controlled for the people and processes in any building, especially a health care facility
Contaminants impact: Building occupants Infection Rates Computers/ Electronics Medical Equipment
Filtration Different methods Different efficiencies Different costs
![Page 5: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/5.jpg)
The Problem
Buildings generate and concentrate pollutants
EPA: Indoor air can be 7 to 10 times more polluted
than outdoor air. AMA: Respiratory problems are the 3rd largest
cause of death in the US ASHRAE Control the contaminants in the building
![Page 6: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/6.jpg)
What’s in the air?
Particulate: Smoke, vehicle exhaust, dust, man-made mineral
fibers, etc
Biological: Molds, viruses, bacteria
Gas Phase: CO2, CO, Volatile Organic Compounds
![Page 7: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/7.jpg)
Typical Atmospheric Dust Sample
3.0µm
5.0µm
0.5µm
Weight/ volume Count
0.18%
11% 0.25%
6.0% 1.07%
6.78%
80%
91.72% 1.0%
2.0% 1.0µm
![Page 8: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/8.jpg)
Ultrafine Particles
• Smaller than 0.1 micron • Dominate particle number concentrations and
surface area • Capable of carrying large concentrations of
adsorbed or condensed toxic air pollutants oxidant gases organic compounds transition metals
• Major source for introducing cardiovascular and pulmonary stressors into the body
• Deposit on electronic components and lead to premature failure
![Page 9: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/9.jpg)
FILTRATION
![Page 10: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/10.jpg)
Filter Efficiency Ratings: ASHRAE 52.1, 52.2 MERV: Minimum Efficiency Reporting Value
Efficiency MERV Rating
Typical Application
30% 7 - 8 Prefilters
65% 11 Mid filters
90-95% 14 Final Filters
HEPA 99.97% 16+ OR, Iso
Rooms
![Page 11: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/11.jpg)
Filter Effective Ranges
3.0µm
0.3µm
Weight Count
0.18%
11% 0.25%
6.0% 1.07%
6.78%
80%
91.72% 1.0% 2.0%
30% Prefilters
65% Midfilters
10.0µm
95% Final filters 1.0µm
99.97% HEPA
Effective range
![Page 12: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/12.jpg)
Health Care Filtration Guidelines
IDPH: Requires 30% prefilters and 90% final filters
City of Chicago Follows IDPH
ASHRAE 170 MERV 7 (30%) prefilters MERV 14 (90%) final filters Protective Environments HEPA MERV 17 finals
![Page 13: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/13.jpg)
• Passive or Mechanical Filters
• Passive Electrostatic and Electrostatic Precipitators
• Polarized Media Air Cleaners
Most Common Air Cleaning Technologies
![Page 14: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/14.jpg)
Passive Filters
![Page 15: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/15.jpg)
Passive Filters
• Most widely used technology • Essentially sieves - the tighter the grid, the more
effective the filter • Rely solely on mechanical capture
no electrostatic attraction • Typical configurations:
1” to 4” panel filters with pleated media Bag filters Box and rigid filters HEPA filters Roll filters
![Page 16: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/16.jpg)
Mechanisms of Passive Filtration
Impingement Interception Diffusion Straining-larger particles
![Page 17: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/17.jpg)
Passive Filters
+ Low first cost + Widely available + Proven approach + Most particle sizes can be addressed
- No effect on Volatile Organic Compounds (VOCs)
- As filter effectiveness increases energy efficiency decreases
- Captured particles can shed
Operational Considerations
![Page 18: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/18.jpg)
Passive-Electrostatic Filters
![Page 19: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/19.jpg)
Passive-Electrostatic Filters
• Media fibers have one-time factory induced or applied electrostatic orientation
• Many particles in the air have net ambient charge and/or relative charge sites
• Charge on media gives it greater efficiency than comparable passive media by attracting charges particles
• Effect is short-lived as fibers become coated
• Often high pressure drop
+ _
_ +
![Page 20: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/20.jpg)
Electrostatic Precipitators (ESPs)
• 50+ year-old technology based on electrostatic attraction opposites attract
• Industrial applications stack cleaning welding
• Not widely used in general applications
![Page 21: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/21.jpg)
Mechanisms of Electrostatic Precipitators
• High DC Voltage applied to thin wires creates corona of positive ions
• As particles go through corona, ions attach themselves to particles- ionizing them
• Ionized particles are attracted to oppositely charged plates
+ + + + + +
+ + + + + +
Ionizing Section 12-20,00 vdc Oppositely charged collection cell
Grounded surface, e.g. ducts, walls, ceilings, people
+ + + +
+
+
+
+ +
+ + + +
+ + + + +
+ + +
![Page 22: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/22.jpg)
Electrostatic Precipitators
Operational Considerations • Collection grids can become coated quickly When collection cells fill, ions go elsewhere Frequent maintenance is mandatory, or effectiveness plummets
• Captured particles shed
![Page 23: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/23.jpg)
Typical Health Care Passive Filter Configuration
65% Mid Filter 30% Pre Filter
+ HEPAs in Critical User Spaces……
95% or HEPA Final Filter
![Page 24: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/24.jpg)
Typical HC Filtration Pressure Drop (Clean/Dirty)
95% or HEPA Final Filter 1.0” / 2.0”
65% Mid Filter .25” / 1.25”
30% Pre Filter .25” / 1.0”
HEPAs in critical user Space 1.0” / 2.0”
Typical Supply AH designed for 8” SP loss •Filtration is over 50% of the loss when dirty, by design
![Page 25: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/25.jpg)
Other Forms of Similar Resistance to Flow
![Page 26: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/26.jpg)
There are Costs to this Approach…
![Page 27: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/27.jpg)
Polarized Media Air Cleaner
![Page 28: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/28.jpg)
Polarized Media Air Cleaner
• Combines characteristic of passive filters
and electrostatic precipitators
• Active electrostatic field constantly polarizes fibers of the media pad and particles passing through the field
• Polarized particles are drawn to the polarized fibers and to each other
![Page 29: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/29.jpg)
- +
Passive mechanisms: There is media, so there is passive collection
Polarization and electrostatic attraction:
polarized fibers charged center screen
Agglomeration: Natural process greatly accelerated by the field inside the air cleaner. Polarized particles attract each other and charged particles to form bigger clusters that are more easily captured
Grounded external screens
+7,000 vdc applied to center screen
Polarized media fibers
+ + + + + + +
+ + + + + + +
_ _ _ _ _ _ _
_ _ _ _ _ _ _
+ _
+
- +
+
_
- +
_ - +
Passive fiber
Loading Characteristics
Polarized fiber
Mechanisms of Polarized Media
![Page 30: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/30.jpg)
Impact of Polarization on Ultrafine Particles
• Ultra-fine particles adsorb and absorb gas phase contaminants
• Polarization agglomerate and captures ultrafine particles Reduce gas phase contaminants
• Removal rates stay constant
![Page 31: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/31.jpg)
Electrostatic vs Polarized Media Air Cleaners Important Distinctions
Electrostatic Polarized +
Ionize Particles X Polarize Particles X
Reorganize Surface Charges X
Eliminate Odors X Create Ozone X
Particles adhere to grounded surface X
Uneven media loading X
Low P Drop X Long Service
Interval X
+ + _ + _
![Page 32: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/32.jpg)
Polarized HC Filtration Pressure Drop (Clean/Dirty)
95% or HEPA Final Filter 1.0” / 2.0” .31” / .51
65% Mid Filter .25” / 1.25” 0” / 0”
30% Pre Filter .25” / 1.0” .13” / .27”
HEPAs in critical user Space 1.0” / 2.0”
Typical Supply AH designed for 8” SP loss • Polarized Filtration is < 10% of design loss, not 50%
![Page 33: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/33.jpg)
Performance Comparison
Measurement 30% 65% 95% HEPA Polarized MERV Rating 8 11 14 17 15+
Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51 Dust Cap Mid-Life (g) 170 300 300 300 2600 Media replacement
frequency (months) 3 12 12 12 48
![Page 34: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/34.jpg)
0
0.2
0.4
0.6
0.8
1
1.2
1.4
0 500 1000 1500 2000 2500 3000 3500 4000 4500
Pres
sure
Dro
p, in
ches
w.g
.
Dust Load, g
Filter Pressure Drop vs Dust Load SAE Fine Dust
Air Flow thru Face Area Of Filter Bank = 500fpm
![Page 35: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/35.jpg)
Local Case Study
Baseline Conditions
Post-Retrofit Conditions
Benefit
Measured Flow rate 33200 32500
Measured Voltage per leg 418 418
Measured Motor Amps 82 57.8 29%
•Baseline – 30% Prefilters, 65% bags •Retrofit – Polarized filter bank
Power savings 17.5 kw
Energy Savings 153,477 kwh
Energy $ Savings $15,348
Media Savings $1,135
Labor Savings $710
Total Annual Savings $17,193
![Page 36: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/36.jpg)
Other Air Cleaning Technologies
Activated Carbon and ad/absorbing media: Very effective against VOCs and other gas phase contaminants New configurations using honeycomb matrices have brought down the impediments for using carbon
![Page 37: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/37.jpg)
Germicidal UVC Properly applied can inactivate surface and airborne biologicals Care must be taken with exposure to equipment and personnel
Other Air Cleaning Technologies
![Page 38: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/38.jpg)
Ionizer Filter Enhancers Cause more problems than they solve Generate ions that adhere to particles so they will adhere to surfaces – air handlers, walls, people
Ozonators EPA – O3 has little potential to remove indoor contaminants O3 is a lung irritant
Other Air Cleaning Technologies
![Page 39: Robert McCabe Director, Health Care Solutions HTS Chicago€¦ · MERV Rating 8 11 14 17 15+ Static Pressure - Clean .25 .33 .6 1.5 .31 Static Pressure - Dirty 1.0 1.2 1.2 2.0 .51](https://reader033.fdocuments.us/reader033/viewer/2022050119/5f4fbc2157712b67c20c89a0/html5/thumbnails/39.jpg)
Questions Thank You