Risk Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference 2pm Monday June 22 nd , 2015

Transcript of Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure...

Page 1: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Risk Mitigation of Aging

Electrical Infrastructure

Presented by Tim Murphy

Authored by Jeff M. Miller, PE, ENV SP

2015 MWEA Annual Conference 2pm Monday June 22nd, 2015

Page 2: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 2 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

5

About the Presenter

Jeff M. Miller, PE, ENV SP

Tim Murphy is a Business Development Manager for Schneider

Electric's Water Wastewater Competency Center. Tim has a BA in

Administration and Marketing. He has worked in the Water Market for 16

years in various roles from Variable Frequency Drive Product Marketing

to Drive Application Engineer. He has a range of experience supporting

many projects throughout the entire Water Market Value Chain over the

past 16 years. He is an active member of AWWA - WEA in multiple

states.

Page 3: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 3 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

●Who has electrical equipment

that is ….?

If you had

seats this

comfortable

you would just

fall asleep.

Page 4: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 4 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

●Who knows if their electrical

equipment has …?

How many

times do we

need to raise

our hands? I’m

getting tired.

… been Arc Flash Labeled?

… been opened for inspection?

… had the interior and exterior cleaned?

… had the connections tightened?

… had the grounds tested?

… had mechanical maintenance?

… had a Themographic Survey (IR)

Page 5: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 5 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

When is electrical distribution equipment

operating?

●When it is energized?

●When it is performing its

function?

●What equipment do you

know of that is turned

on for 20+ years without

being turned off?

Page 6: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 6 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Are You a Gambler?

● How much do you put

at risk?

● Do you know the rules?

● Do you know the odds?

● What would you do to

better the odds?

Page 7: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 7 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

3X

What are the main causes of equipment

breakdown?

Page 8: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 8 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

How Dangerous is Electrical Equipment?

●Load Power? Roughly 1A @ 480VAC = 1hp

●Feeder Power?

●Supply Power?

●Fault Energy?

Page 9: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 9 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

FORENSIC PHOTOGRAPHS

TELL A STORY

ELECTRICAL EQUIPMENT

Page 10: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 10 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Forensic Photographs Tell a Story

Page 11: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 11 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Forensic Photographs Tell a Story

Page 12: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 12 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Forensic Photographs Tell a Story

Page 13: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 13 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Forensic Photographs Tell a Story

Page 14: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 14 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Forensic Photographs Tell a Story

Page 15: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 15 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Forensic Photographs Tell a Story

Page 16: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 16 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Forensic Photographs Tell a Story

Page 17: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 17 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Forensic Photographs Tell a Story

Page 18: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 18 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Forensic Photographs Tell a Story

Page 19: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 19 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

THE GREY BOXES

ELECTRICAL EQUIPMENT

Page 20: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 20 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Electrical Distribution Equipment

• Active Components •Circuit Breakers

•Trip Units

•Relays

•PLC’s, TVSS

•Fuses

•Racking Mechanisms

•Monitoring Components

• Passive Components •Structure

•Bussing

•Lugs/Lug Pads

•Bracing

Page 21: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 21 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Electrical Distribution System Active Components

• Mechanical Components • Involve moving parts, therefore they must be

maintained in order to operate as intended

• Will wear out over time

• Some components require replacement upon

use

• Solid State Components • The rise in utilization of solid state

components gives rise to another mode of

failure that cannot be easily detected

• Typically cannot be maintained and must be

replaced upon failure

• Obsolescence is a key consideration

Page 22: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 22 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Electrical Distribution System Passive Components

• Structural Components • Require minimal maintenance (more monitoring)

• If properly cleaned and monitored in a controlled

environment, the passive components do not

wear over time, however:

•Dust, dirt and moisture build-up can affect the

insulation system

•Loose connections due to improper torque

and/or vibration over time can lead to

excessive heat and failure

• If well maintained, these components

substantially outlast the life span of the Active

Components in a piece of electrical distribution

equipment

Page 23: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 23 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

WHAT CAN I DO?

ELECTRICAL EQUIPMENT MAINTENANCE AND CARE

Page 24: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 24 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

ELECTRICAL EQUIPMENT

MAINTENANCE AND CARE

●Maintenance

●Corrective

●Preventative

●Predictive

●Inspections

●Visual

●Infrared Camera

●Assessments

●Testing

●Themographic Survey (IR)

●Forensic Analysis

●Report by a Specialist

Page 25: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 25 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Approaches to Maintenance

●Corrective Maintenance ●Repair work conducted after a

failure or breakdown.

●Preventive Maintenance ●A specified list of inspections,

cleaning, testing and part

replacement during a pre-

defined, time-based schedule.

●Predictive Maintenance ●Scheduled based on diagnostic

evaluations. Also factors in

equipment age, environmental

stresses, criticality of

equipment, etc to decide on

schedule.

Page 26: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 26 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Inspections and Assessments Common Causes of Electrical Equipment Failure

●Thermal Stresses

●Mechanical Stresses

● Insulation Breakdown or Dielectric Deterioration

●Vibration (internal and external)

●Contamination (dust, dirt, foreign particles, animals, critters)

●Exposure to Chemicals (liquid or vapor)

● Inadvertent Contact

●Loose Connections

●Moisture and Water Damage

●Corrosion, Oxidation, Reduction

●Corona and Electron Tracking

●Protective Devices that do not Operate and Designed and Intended

●Lack of a Regular Scheduled Preventive Maintenance Program

Page 27: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 27 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Inspections and Assessments Common Causes of Electrical Equipment Failure

The vast majority of all

anomalies and dysfunctions of

power distribution system can be

directly related to

ineffective or deteriorated

bonding and grounding system.

Page 28: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 28 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Summary Themographic Survey

●A Themographic Survey employs

infrared imaging to only detect

”relative” heat rise or “hot spots” on

the surface of equipment and can

detect heat rise within the interior

of equipment.

●Hot spots are often an indication of

loose connections or overload

conditions.

●TS can be routinely performed

without power interruptions.

● In order to perform a TS proper

PPE must be employed,

maintained, and worn.

●A TS does NOT reveal all

abnormal conditions.

●A TS does NOT reveal all

deteriorate conditions.

●A TS should NOT be employed in

lieu of a regular PM Program.

Page 29: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 29 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

WHAT IF IT IS TOO LATE?

RISK PREVENTION AND MITIGATION

Page 30: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 30 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

RISK PREVENTION AND MITIGATION

●Maintain

●Replacement Assemblies

●Modernize / Upgrade

●New

Page 31: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 31 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Maintain Equipment vs. Modernize?

●Even properly maintained equipment is subject to

two key phenomena:

●Ultimately degrades and reaches the end of its useful life

●No longer sustainable solution due to technological

advances ● Factors to consider:

● Age of equipment

● Operating environment

● Availability of spare parts

● Reliability of system components

● Cost of ongoing maintenance

● Emerging technology

● Worker safety

Page 32: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 32 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

New Equipment vs. Modernize? ●Downtime Costs

●Reliability of System Components

●Risk Catastrophic Failure

●Parts Obsolete/Parts Availability

●Equipment Location

●Safety Issues

●Designs per ANSI and IEEE

standards

Page 33: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 33 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Modernization Solutions

●Cost-effective options

●Reconditioning

●Replacement

●Retrofill

●Benefits

●Reduced maintenance

and operating costs

●Improved reliability

●Increased capabilities

●Less downtime and cost

for installation vs. new

equipment

Page 34: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 34 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Circuit Breaker Options

●Reconditioning, Refurbishing, Retrofit-Conversions

●Direct Replacement Circuit Breakers

●LV and MV

●Retrofill Solutions

●LV and MV

●Replacement

Switchgear

●Custom

●Match-in-Line

●Standard Available for any manufacturer’s equipment.

Before After

Page 35: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 35 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Why Choose Reconditioning?

●Upon completion of reconditioning, the circuit breaker

performs to manufacturer’s original specifications or “like

new” condition

●The circuit breaker’s condition is extensively documented,

i.e., “As Found” and “As Left” inspection completed for each

unit

●Many companies offer warranties for parts and

workmanship

Page 36: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 36 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Direct Replacement Breakers (LV)

●15 – 30 minute circuit outage

required

●Modern technology – all new

electrical/mechanical parts

●No disruption to existing cables

●Lower installed cost when

compared to new switchgear

option

●Greatly reduced spare parts

inventory. One style of

replacement breaker will replace

many different existing equipment

designs: ITE, Westinghouse, GE,

FPE, Allis Chalmers, etc

800 AF MO Breaker

New cradle in OEM gear

Masterpact NT with new

door

Page 37: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 37 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Direct Replacement Breakers (LV)

●Reduced Maintenance

requirements

●Most parts from the complete

spectrum of replacement breakers

are interchangeable

●Can be used to reduce Arc Flash

incident energy levels within

system

800 AF MO Breaker

New cradle in OEM gear

Masterpact NT with new

door

Page 38: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 38 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

●A brief initial outage to confirm key dimensions shall be required

●The retrofill process consists of replacing the existing circuit breaker and it’s related components

●A pre-engineered “erector kit” is manufactured

●Typical applications would be the Main/Tie breakers along with switch-to-breaker upgrade

● Installation then requires an extended bus outage which may range from 8 – 16 hours

●Switch-to-breaker conversions require a mini-study for trip unit settings

Retrofill Breakers

New back

plate

New bus

“run-backs”

New

mounting

pan

New protection

Barrier frame

Retrofill cutaway

side view

Completed

Retrofill

installation:

front-view

Page 39: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 39 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Typical Retrofill Example

●Masterpact M/MP/MC breakers used in OEM

equipment

●Breaker is obsolete and parts limited availability

●Engineered solution to modernize the device

● Outage to obtain critical

dimensions

● Engineered to maintain

proper equipment ratings

● Improve reliability

● Outage to install

● Upgrade with

communications and

monitoring features

● Maintain existing asset

Page 40: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 40 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015 Rear View of bucket w/ stab assembly

Front View of MCC

●Solid-state overload

●Upgrade to an intelligent MCC with door mounted display

●Solid-State Starter (Soft-Start)

●Variable Frequency Drives Upgrade processes

Improve energy efficiency

Options for MCC Upgrade

Page 41: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 41 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Modernization Project Example

● LV direct replacement breakers and monitoring system install

● Each feeder/main breaker trip unit communicates data for energy analysis

● Enhanced safety features of upgrade and improved system reliability

● Existing asset upgraded at reduced cost/downtime compared to a new install

Before After (180° view)

Page 42: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 42 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

● Retrofill outdated MV switchgear with 19 circuit breakers and solid-state digital

relays

● New circuit breakers’ vacuum bottles prevent exposure to an arc

● More consistent trip unit reaction time

● Old elevator-type racking system was eliminated, reducing risks to electricians

● More reliable electrical distribution system

● Significant cost savings as opposed to a total switchgear replacement

Modernization Project Example

Did You Know? New switchgear is usually

smaller than the equipment it is designed to

replace. The existing conduit may need to be

moved and cabling replaced or spliced. Both

are expensive and time consuming tasks,

often costing more in labor and material than

the cost of the new equipment.

Before After

Page 43: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 43 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Non-Standard Dimension

Reduced height, depth, or width

Non-Standard Ratings

Interrupting Ratings

Continuous Current

Custom Footprints

Match existing cutouts

Match existing cable connection locations

Meet space restrictions

Add in Line

Exactly match existing cubicles

Doors, relays, wiring

Custom modifications and wiring

Third Party Integration

High Complexity, Compressed Lead Times

New Equipment and Custom

Switchgear and Integration

Page 44: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 44 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

ARC FLASH MITIGATION

UPGRADE SOLUTIONS

RISK PREVENTION AND MITIGATION

Page 45: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 45 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Remote Operation

●Switching – creates a

potential hazard

●Hard to avoid completely

●Do you have to do it “in the

line of fire”?

●Several remote options

available:

●Pendant

●Permanently-mounted remote

control panel

●SCADA system

●Remember, energy

drops roughly as 1/d2

Page 46: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 46 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Remote Racking

●Even more opportunity for

things to go wrong when

racking a breaker

●Many types of switchgear –

can rack with the door

closed

●Still requires worker to be in

close proximity

●Remote racking – similar

principle to Remote

Operation – remove worker

to outside the flash

protection boundary

Page 47: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 47 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Infrared Viewing Windows

●.

●Removes worker from danger zone

●Infrared scan cables and bus

connections without opening

equipment doors

●Helps Limit Arc Flash Injuries

●Available for new and retrofit

switchgear, switchboards, MCCs,

transformers, etc

Page 48: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 48 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Remote Voltage Indication

●Part of lockout/tagout

process is to verify

equipment dead ● Equipment considered energized

until verified dead

● Have to open up equipment to

verify!

●Can be problematic when

arc-flash levels are high

●Products on market now to

give remote indication

Page 49: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 49 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Time Delay Switches

●Fits into existing breaker

switch mounts

●No special wiring or relaying

●Local control of 10 sec

delay

●Can be programmed for

longer delays

●May not be suitable for all

applications

TIME DELAY CLOSE AND OPEN

Page 50: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 50 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Arc Flash Circuit Breakers

●Specifically designed to

limit high level arcing

fault currents.

●Provide protection

comparable to current

limiting fuses for high

level faults but provides

better protection than

fuses at lower current

levels.

Page 51: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 51 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Are You Willing to Roll the Dice?

The House Always Wins Eventually!

Page 52: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 52 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Questions?

Jeff M. Miller, PE, ENV SP

Solutions Architect

Water Wastewater Competency Center

8001 Knightdale Blvd.

Knightdale, NC 27545-9023

Office: 919.266.8360 | Mobile: 919.824.9114

[email protected]

www.schneider-electric.com

Tim Murphy Business Development Manager

Water Wastewater Competency Center

2525 E. Royalton Rd.

Broadview Heights, OH 44147

Mobile: 440-497-8023

[email protected]

www.schneider-electric.com

Page 53: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 53 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Schneider Electric Electrical Safety and Modernization Related Links

● Solutions for OSHA and NFPA 70E Compliance ● http://products.schneider-electric.us/products-services/services/electrical-distribution-services/arc-flash-safety/

● Modernization & Upgrade Solutions ● http://products.schneider-electric.us/products-services/services/electrical-distribution-services/modernization-and-upgrade-solutions/

● Electrical Safety for Contractors ● http://www2.schneider-electric.com/sites/corporate/en/customers/contractors/protection_electrical_risks/protection-electrical-risks.page

● Modernization for Safety ● http://products.schneider-electric.us/solutions/industrial-buildings/modernization-phase-solutions-to-enhance-your-facility-capacilities/

● Arc Protection Relays System ● http://www.schneider-electric.com/products/us/en/54700-medium-voltage-distribution-and-energy-automation/54740-protection-relays-by-range/62049-vamp-arc-

protection-relay-system/

● LV Arc Resistant Switchgear ● http://www.schneider-electric.com/products/us/en/53300-switchboards-and-switchgear/53320-switchgear/62141-power-zone-4-arc-resistant-low-voltage-switchgear-with-

arcblok-technology/

● LV Arc resistant MCC ● http://www.schneider-electric.com/products/us/en/54800-surge-protective-devices-spd/54820-retrofit/62142-model-6-arc-resistant-motor-control-center/

● MV Arc Resistant Switchgear ● http://www.schneider-electric.com/products/us/en/53300-switchboards-and-switchgear/53320-switchgear/60021-masterclad-medium-voltage-arc-resistant-metal-clad-

switchgear/

Page 54: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 54 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Short Presentation Abstract Modern day utilities depend on electrical power for operation of critical equipment. System reliability and personnel safety

are both negatively impacted by aging and poorly maintained electrical equipment. Many risks are unknown or

unidentified, so proper preventative maintenance and emergency contingency planning may not be in place. There are

many modernization alternatives to doing a complete "rip and replace" in order to mitigate these risks while satisfying

financial constrictions, improve personnel safety and ensure operational continuity. This presentation will discuss aging

electrical system threats, vulnerabilities, O&M methods, electrical modernization alternatives, and contingency planning

methods used to mitigate risk.

Page 55: Risk Mitigation of Aging Electrical Infrastructure Mitigation of Aging Electrical Infrastructure Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP 2015 MWEA Annual Conference

Schneider Electric 55 | Jeff M. Miller | Risk Mitigation of Aging Elect. Infrastructure | MWEA Annual Conference | Monday June 22nd, 2015

Long Presentation Abstract Modern day utilities depend on electrical power and related systems for operation of their critical equipment, processes,

and systems. System reliability and personnel safety are both negatively impacted by aging and poorly maintained

electrical equipment. Most utilities have a false sense of security when it comes to power distribution equipment and fail to

understand the substantial risks taken as well as the possible impacts to their operation. Recent studies indicate that

between five and ten arc flash explosions occur in electrical equipment every day in the United States in addition to other

non-explosive catastrophic electrical equipment failures. Although arc flash labeling and safety is important, it has recently

taken the attention away from many other important aspects of maintaining a reliability and safe power distribution system.

Many risks are obvious to the casual observer and can be prevented by proper maintenance and inspections, but others

may be unknown to utility staff, so proper planning and emergency contingencies may not be in place to minimize impacts

to the utility. Aging electrical infrastructure has the capacity to cause long term outages and severe personnel safety

incidents

Of course, this isn’t all due to old equipment, so rather than doing a complete "rip and replace" there are things that can be

done to mitigate these risks, improve personnel safety and ensure operational continuity.

This presentation will discuss aging electrical system threats, vulnerabilities, and risks using forensic investigation

examples of failed electrical equipment. Evidence is provided to show how proper maintenance, inspections, and

assessments can prolong the life of electrical equipment while ensuring reliability and safety throughout its life. When

equipment can no longer be maintained or enhanced safety and reliability is desired, the pros and cons of replacing verses

modernizing electrical equipment are compared. Various low cost modernization methods and options are presented as

an alternative to replace with new. In addition to the retrofit options, newer “retrofill” options will be presented as a method

to prevent unnecessary capital expenditures and system outages.

In addition, O&M methods, electrical architecture improvements, contingency planning, and new arc-resistant equipment

designs being used to mitigate risk. Various program and project implementation methods for making improvements will be

discussed. Real world project examples will be given highlighting the challenges and successes of these types of

improvements.