RF Surge Protection - tcom.azureedge.net/media/files/tcom/... · RF Surge Protection Over forty...

24
RF Surge Protection

Transcript of RF Surge Protection - tcom.azureedge.net/media/files/tcom/... · RF Surge Protection Over forty...

RF Surge Protection

PolyPhaser leads the market with its patented RF protection solutions, specifically supporting communications systems. Based on its extensive experience with multi-stage surge protection, PolyPhaser continues to expand its product offering to support the needs of advanced network applications with technologies such as DC Block, DC Pass and Ultra Low PIM.

Smiths Power is a leading supplier of power distribution, conditioning, protection and monitoring solutions for data centers, wireless communications and other critical or high-value electrical systems.

As a family of brands, PDI, Onyx, PolyPhaser, Transtector, DOWIN, LEA and RO Associates unite under one umbrella to Transform, Distribute, Monitor and Protect™ power in global networks and systems. Our companies provide expertise in consulting, design and manufacturing of power transformers and distribu-tion systems, static switching, power monitoring, RF, AC, DC, data signal and EMP protectors as well as power quality engineering services.

Alongside Smiths Connectors and Smiths Microwave, Smiths Power is part of the Smiths Interconnect divi-sion of Smiths Group (www.smiths.com), a global leader in applying advanced technologies for markets in threat and contraband detection, energy, medical devices, communications and engineered components. Smiths Group employs around 23,000 people in more than 50 countries.

RF Surge Protection

Over forty years ago, PolyPhaser pionieered the market with its patented protection solutions for ever-evolving telecommunication systems. Our proven designs have stood the test of time and set forth the foundation for new deployments. Whether your coaxial application is at the tower top, GPS or in the base station, PolyPhaser RF products have set the standard for the industry. Technical innovation and a solution driven mindset continue to guide the development and extension of our comprehensive portfolio of radio frequency products.

5

TSX-DFF

• PIM < -155 dBc• Bidirectional broadband filter• Bulkhead mount• Tri-M3™ plating over brass

Features

• IEC 60529 IP 67• IEC 61000-4-5• Belcore #TA-NWT-000487• Procedure 4.11, Wind Driven (120 MPH)• RoHS compliant• CE

Standards and CertificatesTSXDC-DFM

Humidity <95% non-condensingOperating Temperature -50 C to 85 C

TSXDC-DFM

High performance, ultra low PIM RF protectors for 698 MHz to 2.5 HGz available in DC block and DC pass configurations.

TSX Series

Environmental

TUSX-DFM

RF Surge Protection

7RF Surge Protection

Frequency Range RF Power Insertion Loss VSWR Operating Voltage Max Surge Current Turn on Voltage Throughput Energy Surge Side Connector

Protected Side Connector

TSXDC-DFM 698 MHz to 2.5 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.2:1 over frequency range ± 60 Vdc

20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike

+150 Vdc + 20% < 25 mJ 2kA IEC 61000-4-5 8/20 µs waveform DIN Female DIN Male TSXDC-DFM

TSXDC-DFF 698 MHz to 2.7 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.2:1 over frequency range ± 60 Vdc

20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike

+150 Vdc + 20% < 25 mJ 2kA IEC 61000-4-5 8/20 µs waveform DIN Female DIN Female TSXDC-DFF

TSX-DFF 698 MHz to 2.7 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A

20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike

N/A < 5 nJ for 3kA 8/20 µs waveform DIN Female DIN Female TSX-DFF

TSX-DFM 698 MHz to 2.7 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A

20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike

N/A < 5 nJ for 3kA 8/20 µs waveform DIN Female DIN Male TSX-DFM

TUSX-DFF 300 MHz to 1.2 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A

30 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 40 kA per IEC 61000-4-5 8/20 µs waveform for one strike

N/A < 5 nJ for 3kA 8/20 µs waveform DIN Female DIN Female TUSX-DFF

TUSX-DFM 300 MHz to 1.2 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A

30 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 40 kA per IEC 61000-4-5 8/20 µs waveform for one strike

N/A < 5 nJ for 3kA 8/20 µs waveform DIN Female DIN Male TUSX-DFM

TUSX-NFF 300 MHz to 1.2 GHz 1 kW @ 920 MHz2.5 kW @ 400 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A

30 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 40 kA per IEC 61000-4-5 8/20 µs waveform for one strike

N/A < 7.5 nJ for 3kA 8/20 µs waveform N Female N Female TUSX-NFF

TUSX-NFM 300 MHz to 1.2 GHz 1 kW @ 920 MHz2.5 kW @ 400 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A

30 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 40 kA per IEC 61000-4-5 8/20 µs waveform for one strike

N/A < 7.5 nJ for 3kA 8/20 µs waveform N Female N Male TUSX-NFM

9RF Surge Protection

• Ultra low PIM <-155 dBc 2 x 20 W• Weather proof when installed • 50 Ω impedance

Features

• IEC 60529 IP67• IEC 61000-4-5• Belcore #TA-NWT-000487• Procedure 4.11, Wind Driven (120 MPH)• AISG compliant• RoHS compliant• CE (DGXJ-P-DFMT30, DGXJ-P-DFMS30)

Standards and Certificates

DAS-P-DFM30

DAS-P Series

Environmental

DAS-P-DMF30

DAS-P-DFF30

The DAS-P series is a dual band DC pass RF protector that offers outstanding throughput energy of <50v, while providing ultra PIM protection in a 30V unit.

Humidity <95% non-condensingOperating Temperature -55 C to + 85 C

11RF Surge Protection

Frequency Range RF Power Insertion Loss VSWR PIM Performance Max Continuous Operating Current Max Surge Current Surge Side Connector Protected Side Connector

DAS-P-DFF30

680 MHz to 1 GHz, 1.7 GHz to 2.3 GHz RF2.0 MHz to 2.5 MHz Telemetry(AISG)

1.5 kW @ 920 MHz

<0.1 dB @ 698 MHz to 1 GHz,<0.1 dB @ 1.7 GHz to 2.7 GHz<0.4 dB @ 2.176 MHz

>2.2dB @ 698 MHz to 1 GHz,>2.2dB @ 1.7 GHz to 2.7 GHz,>15dB @ 2.176 MHz

<-155 dBc 2 x 20 W 4 A

20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike

DIN Female DIN Female DAS-P-DFF30

DAS-P-DFM30

680 MHz to 1 GHz,1.7 GHz to 2.3 GHz RF2.0 MHz to 2.5 MHz Telemetry(AISG)

1.5 kW @ 920 MHz

<0.1 dB @ 698 MHz to 1 GHz,<0.1 dB @ 1.7 GHz to 2.7 GHz<0.4 dB @ 2.176 MHz

>2.2dB @ 698 MHz to 1 GHz,>2.2dB @ 1.7 GHz to 2.7 GHz,>15dB @ 2.176 MHz

<-155 dBc 2 x 20 W 4 A

20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike

DIN Female DIN Male DAS-P-DFM30

DAS-P-DMF30

680 MHz to 1 GHz,1.7 GHz to 2.3 GHz RF2.0 MHz to 2.5 MHz Telemetry(AISG)

1.5 kW @ 920 MHz

<0.1 dB @ 698 MHz to 1 GHz,<0.1 dB @ 1.7 GHz to 2.7 GHz<0.4 dB @ 2.176 MHz

>2.2dB @ 698 MHz to 1 GHz,>2.2dB @ 1.7 GHz to 2.7 GHz,>15dB @ 2.176 MHz

<-155 dBc 2 x 20 W 4 A

20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike

DIN Male DIN Female DAS-P-DMF30

DGXJ-P-DFMT30 680 MHz to 1 GHz,1.7 GHz to 2.3 GHz RF 1.5 kW @ 920 MHz

<0.1 dB @ 698 MHz to 1 GHz,<0.1 dB @ 1.7 GHz to 2.7 GHz

>2.2dB @ 698 MHz to 1 GHz,>2.2dB @ 1.7 GHz to 2.7 GHz <-155 dBc 2 x 20 W 4 A

20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike

DIN Female DIN Male DGXJ-P-DFMT30

DGXJ-P-DFMS30 680 MHz to 1 GHz,1.7 GHz to 2.7 GHz RF 1.5 kW @ 920 MHz

<0.1 dB @ 698 MHz to 1 GHz,<0.1 dB @ 1.7 GHz to 2.7 GHz

>2.2dB @ 698 MHz to 1 GHz,>2.2dB @ 1.7 GHz to 2.7 GHz <-155 dBc 2 x 20 W 4 A

20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike

DIN Female DIN Male DGXJ-P-DFMS30

13RF Surge Protection

IS-B50HN-C0

• Frequency range 1.5 - 1000 MHz • Insertion loss: 0.1dB • Ideal for HF, UHF, VHF radios • DC blocked gas tube design • No DC continuity between center pins• Multi-strike capability

Features

• IEC 61000-4-5 • RoHS compliant• CE

Standards and Certificates

IS-B50LN-C2

B50 Series

Environmental

DC blocked 50 ohm bulkhead mounted protector is ideal for two way radio and SCADA applications.

Operating Temperature -45 C to 50 CVibration 1G up to 100Hz

15RF Surge Protection

Frequency Range RF Power Insertion Loss VSWR Max Surge Current Turn on Voltage Turn on Time Throughput Energy Surge Side Connector

Protected Side Connector

IS-B50HN-C0 1.5 MHz to 700 MHz VHF 500 W, UHF 250 W, HF 3 kW ≤ 0.1 dB ≤ 1.1 to 1 over frequency range 50 kA per IEC 61000-4-5 8/20 µs waveform ±1200 Vdc ± 20 % 7 ns for 2 kV / ns < 20 mJ for 3kA,

8/20 µs waveform N Female N Female IS-B50HN-C0

IS-B50HN-C2 125 MHz to 1000 MHz VHF 500 W, UHF 250 W ≤ 0.1 dB ≤ 1.1 to 1 over frequency range 50 kA per IEC 61000-4-5 8/20 µs waveform ±1200 Vdc ± 20 % 7 ns for 2 kV / ns < 800 µJ for 3kA,

8/20 µs waveform N Female N Female IS-B50HN-C2

IS-B50HU-C0 1.5 MHz to 700 MHz HF 3 kW, VHF 500 W, UHF 250 W ≤ 0.1 dB ≤ 1.2 to 1 over frequency range 50 kA per IEC 61000-4-5 8/20 µs waveform ±1200 Vdc ± 20 % 7 ns for 2 kV / ns < 20 mJ for 3kA,

8/20 µs waveform UHF Female UHF Female IS-B50HU-C0

IS-B50LN-C0 1.5 MHz to 700 MHz HF 2 kW, VHF 375 W, UHF 125 W ≤ 0.1 dB ≤ 1.1 to 1 over frequency range 50 kA per IEC 61000-4-5 8/20 µs waveform ±600 Vdc ± 20 % 2.5 ns for 2 kV / ns < 10 mJ for 3 kA,

8/20 µs waveform N Female N Female IS-B50LN-C0

IS-B50LN-C2 125 MHz to 1 GHz VHF 375 W, UHF 125 to 50 W ≤ 0.1 dB ≤ 1.1 to 1 over frequency range 50 kA per IEC 61000-4-5 8/20 µs waveform 600 Vdc ± 20 % 2.5 ns for 2 kV / ns < 220 µJ for 3kA,

8/20 µs waveform N Female N Female IS-B50LN-C2

IS-B50LU-C0 1.5 MHz to 700 MHz HF 2 kW, VHF 375 W, UHF 125 W ≤ 0.1 dB ≤ 1.2 to 1 over frequency range 50 kA per IEC1000-4-5 8/20 µs waveform ±600 Vdc ± 20 % 2.5 ns for 2 kV / ns < 10 mJ for 3kA,

8/20 µs waveform UHF Female UHF Female IS-B50LU-C0

17RF Surge Protection

TSX-NFM

AL-LSXM

• High surge current capability• Low let-through voltage and throughput energy• High pass filter design, no DC continuity

between center pins• Ideal use for applications where DC is not

required on the coaxial cable• Fully weatherized housing• Elongated female connector allows for mounting

through a 1/4” bulkhead or grounding bar• Multi-strike capability

Features

• IEC 60529 IP65 (AL-LSXM, AL-LSXM-MA, LSXL, LSXL-ME, WSXM)

• IEC 60529 IP67 (TSX-NFF, TSX-NFF-P, TSX-NFM, TSX-NFM-P)

• IEC 61000-4-5• Bellcore # TA-NWT-00487• Procedure 4.11, Wind Driven (120 MPH)• RoHS compliant• CE

Standards and Certificates

TSX-NFF

SX Series

Environmental

19RF Surge Protection

Frequency Range VSWR RF Power Insertion Loss PIM Performance Max Surge Current Throughput Energy Surge Side Connector

Protected Side Connector

AL-LSXM 2.0 GHz to 6.0 GHz < 1.2 to 1 over frequency range 10 W < 0.1 dB Typical (< 0.2 dB Max) N/A 10 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female AL-LSXM

AL-LSXM-MA 2.0 GHz to 6.0 GHz < 1.2 to 1 over frequency range 10 W < 0.1 dB Typical (< 0.2 dB Max) N/A 10 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Male N Female AL-LSXM-MA

LSXL 1.8 GHz to 3.8 GHz 4.2 GHz to 6.0 GHz < 1.2 to 1 over frequency range 10 W < 0.2dB N/A 18 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female LSXL

LSXL-ME 1.8 GHz to 3.8 GHz 4.2 GHz to 6.0 GHz < 1.2 to 1 over frequency range 10 W < 0.2dB N/A 18 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Male LSXL-ME

TSX-NFF 698 MHz to 2.7 GHz < 1.1 to 1 over frequency range 500 W @ 920 MHz, 700 W @ 50º C < 0.1dB N/A

20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes40 kA per IEC 61000-4-5 8/20 µs waveform for one strike

< 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female TSX-NFF

TSX-NFF-P 698 MHz to 2.7 GHz < 1.1 to 1 over frequency range 500 W @ 920 MHz, 700 W @ 50º C < 0.1dB -110 dBm

20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes40 kA per IEC 61000-4-5 8/20 µs waveform for one strike

< 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female TSX-NFF-P

TSX-NFM 698 MHz to 2.7 GHz < 1.1 to 1 over frequency range 500 W @ 920 MHz, 700 W @ 50º C < 0.1dB N/A

20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes40 kA per IEC 61000-4-5 8/20 µs waveform for one strike

< 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Male TSX-NFM

TSX-NFM-P 698 MHz to 2.7 GHz < 1.1 to 1 over frequency range 500 W @ 920 MHz, 700 W @ 50º C < 0.1dB -110 dBm

20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes30 kA per IEC 61000-4-5 8/20 µs waveform for one strike

< 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Male TSX-NFM-P

WSXM 6.0 GHz to 10.0 GHz < 1.2 to 1 over frequency range 10 W < 0.1 dB N/A 10 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female WSXM

21RF Surge Protection

IS-50NX-C0

IS-50NX-C0-MA

• Multi-strike capability • Low throughput energy • Mount to bracket or flat single point

grounding panel • Flange and bulkhead mounting options

Features

• IEC 61000-4-5 (IS-50NX-C0-ME, IS-50NX-C2, IS-50NX-C2-MA, IS-50NX-C2-ME, IS-50UX-C0)

• RoHS compliant• CE

Standards and Certificates

IS-50 Series

Environmental

Operating Temperature -45 C to 50 CVibration 1G up to 100Hz

The IS-50 series is a DC block broadband HF/VHF/UHF coaxial protector that operates in the frequency range of 1.5 to 1000MHz.

23RF Surge Protection

Frequency Range RF Power Insertion Loss VSWR Max Surge Current Turn on Voltage Turn on Time Throughput Energy Surge Side Connector

Protected Side Connector

IS-50NX-C0 1.5 MHz to 700 MHz HF 2 kW, VHF 375 W, UHF 125 W ≤ 0.1 dB ≤1.1 to 1 for

1.5 to 700 MHz50 kA per IEC 61000-4-5 8/20 µs waveform 500 J 600 Vdc ± 20 % 2.5 ns for 2 kV/ns ≤ 10 mJ 6 kV / 3 kA,

8/20 µs waveform N Female N Female IS-50NX-C0

IS-50NX-C0-MA 1.5 MHz to 700 MHz HF 2 kW, VHF 375 W, UHF 125 W ≤ 0.1 dB ≤1.1 to 1 for

1.5 to 700 MHz50 kA per IEC 61000-4-5 8/20 µs waveform 500 J 600 Vdc ± 20 % 2.5 ns for 2 kV/ns ≤ 10 mJ 6 kV / 3 kA,

8/20 µs waveform N Male N Female IS-50NX-C0-MA

IS-50NX-C0-ME 1.5 MHz to 700 MHz HF 2 kW, VHF 375 W, UHF 125 W ≤ 0.1 dB ≤1.1 to 1 for

1.5 to 700 MHz50 kA per IEC 61000-4-5 8/20 µs waveform 500 J 600 Vdc ± 20 % 2.5 ns for 2 kV/ns ≤ 10 mJ 6 kV / 3 kA,

8/20 µs waveform N Female N Male IS-50NX-C0-ME

IS-50NX-C2 125 MHz to 1 GHz125 to 220 MHz @ 375 W, 220 to 700 MHz @ 125 W, 700 to 1000 MHz @ 50 W

≤ 0.1 dB ≤1.1 to 1 over frequency range

50 kA per IEC 61000-4-5 8/20 µs waveform 500 J 600 Vdc ± 20 % 2.5 ns for 2 kV/ns ≤ 220 µJ for 3 kA,

8/20 µs waveform N Female N Female IS-50NX-C2

IS-50NX-C2-MA 125 MHz to 1 GHz125 to 220 MHz @ 375 W, 220 to 700 MHz @ 125 W, 700 to 1000 MHz @ 50 W

≤ 0.1 dB ≤1.1 to 1 over frequency range

50 kA per IEC 61000-4-5 8/20 µs waveform 500 J 600 Vdc ± 20 % 2.5 ns for 2 kV/ns ≤ 220 µJ for 3 kA,

8/20 µs waveform N Male N Female IS-50NX-C2-MA

IS-50NX-C2-ME 125 MHz to 1 GHz125 to 220 MHz @ 375 W, 220 to 700 MHz @ 125 W, 700 to 1000 MHz @ 50 W

≤ 0.1 dB ≤1.1 to 1 over frequency range

50 kA per IEC 61000-4-5 8/20 µs waveform 500 J 600 Vdc ± 20 % 2.5 ns for 2 kV/ns ≤ 220 µJ for 3 kA,

8/20 µs waveform N Female N Male IS-50NX-C2-ME

IS-50UX-C0 1.5 MHz to 700 MHz HF 2 kW, VHF 375 W, UHF 125 W ≤ 0.1 dB ≤1.2 to 1 over

frequency range50 kA per IEC 61000-4-5 8/20 µs waveform 500 J 600 Vdc ± 20 % 2.5 ns for 2 kV/ns ≤ 10 mJ for 3 kA,

8/20 µs waveform UHF Female UHF Female IS-50UX-C0

25RF Surge Protection

IS-NEMP-C2-ME

• Low throughput energy • High surge current capability • Ultra fast response • VHF and UHF applications• Bulkhead mount

Features

• IEC 61000-4-5 (IS-NEMP-C0, IS-NEMP-C0-MA, IS-NEMP-C1-MA, IS-NEMP-C1-ME, IS-NEMP-C2, IS-NEMP-C2-MA )

• RoHS compliant• CE

Standards and Certificates

IS-NEMP-C0

NEMP Series

Environmental

Ultra fast NEMP protection for frequency range of 1.5 to 1000MHz used in emergency radio communications equipment.

Operating Temperature -45 C to 50 CVibration 1G @5Hz to 100Hz

27RF Surge Protection

Frequency Range RF Power Insertion Loss VSWR Max Surge Current Turn on Voltage Turn on Time Throughput Energy Surge Side Connector

Protected Side Connector

IS-NEMP-C0 1.5 MHz to 700 MHz 500 W HF, 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 over frequency range 50 kA per IEC 61000-4-5 8/20 µs waveform 500 J 330 Vdc ± 20% 1.5 ns for 2 kV / ns < 1100 µJ for

8/20 µs waveform N Female N Female IS-NEMP-C0

IS-NEMP-C0-MA 1.5 MHz to 700 MHz 500 W HF, 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 over frequency range 50 kA per IEC 61000-4-5 8/20 µs waveform 500 J 330 Vdc ± 20% 1.5 ns for 2 kV / ns < 1100 µJ for

8/20 µs waveform N Male N Female IS-NEMP-C0-MA

IS-NEMP-C1-ME 50 MHz to 700 MHz 200 W VHF, 100 W UHF ≤ 0.1dB 1.2 to 1 @50-60 MHz 50 kA per IEC 61000-4-5 8/20 µs waveform 500 J 330 Vdc ± 20% 1.5 ns for 2 kV / ns < 313 µJ for

8/20 µs waveform N Female N Male IS-NEMP-C1-ME

IS-NEMP-C2 125 MHz to 1.0 GHz 200 W VHF, 100 W UHF, 50 W 800 MHz ≤ 0.1dB < 1.1 to 1 over frequency range 50 kA per IEC 61000-4-5 8/20 µs waveform 500 J 330 Vdc ± 20% 1.5 ns for 2 kV / ns < 250 µJ for

8/20 µs waveform N Female N Female IS-NEMP-C2

IS-NEMP-C2-MA 125 MHz to 1.0 GHz 200 W VHF, 100 W UHF, 50 W 800 MHz ≤ 0.1dB < 1.1 to 1 over frequency range 50 kA per IEC 61000-4-5 8/20 µs waveform 500 J 330 Vdc ± 20% 1.5 ns for 2 kV / ns < 250 µJ for

8/20 µs waveform N Male N Female IS-NEMP-C2-MA

IS-NEMP-C2-ME 125 MHz to 1.0 GHz 200 W VHF, 100 W UHF, 50 W 800 MHz ≤ 0.1dB < 1.1 to 1 over frequency range 50 kA per IEC 61000-4-5 8/20 µs waveform 500 J 330 Vdc ± 20% 1.5 ns for 2 kV / ns < 250 µJ for

8/20 µs waveform N Female N Male IS-NEMP-C2-ME

29RF Surge Protection

VHF50HD-MA

VHF50HN

• High surge current capability with filter design• Low let-through voltage and throughput energy• No DC continuity between center pins• Weatherized housing• Insertion loss 0.1 dB• High powered public safety, TETRA and

UHF/VHF radio application• Standard N, 7/16 DIN Connectors

Features

• IEC 60529 IP67• IEC 61000-4-5• Belcore #TA-NWT-000487• Procedure 4.11, Wind Driven (120 MPH)• RoHS compliant• CE

Standards and Certificates

HF Series

Environmental

Ultra fast NEMP protection for frequency range of 1.5 to 1000MHz used in emergency radio communications equipment.

Operating Temperature -45 C to 50 CVibration 1G @5Hz to 100Hz

31RF Surge Protection

Frequency Range RF Power Insertion Loss VSWR Max Surge Current Throughput Energy Surge Side Connector

Protected Side Connector

VHF50HD 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Female DIN Female VHF50HD

VHF50HD-MA 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Male DIN Female VHF50HD-MA

VHF50HN 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Female N Female VHF50HN

VHF50HN-MA 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Male N Female VHF50HN-MA

VHF50HN-ME 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Female N Male VHF50HN-ME

33RF Surge Protection

DGXZ+06DFDM-A

DGXZ+06DFDM-A

• Patented dual path RF and DC protection

• Multi-strike capacity • Weatherized housing • Low throughput energy • Wide bandwith

Features

• IEC 60529 IP67• IEC 61000-4-5• IEC 60950-1 Section 7.4.2

(DGXZ+06NFNF-A, DGXZ+06NMNF-U) • Bellcore #TA-NWT-00487• Procedure 4.11, Wind Driven (120 MPH)• RoHS compliant• CE

Standards and Certificates

DGXZ+06NFNF-A

GXZ Series

Environmental

The GX series radio frequency DC pass filter protectors are ideal for RF coaxial applications where DC is required. The GX series can be used on GPS and point to point radios as well as active tower mounted electronic equipment that operate in the range of 30 to 2,500MHz. the GX series is available in a multitude of connector configurations each exhibiting low return loss, insertion loss and let-through voltage.

Humidity <95% non-condensingOperating Temperature -50 C to + 85 C

Vibration 1G @5Hz to 500Hz

35RF Surge Protection

Frequency Range RF Power Insertion Loss VSWR

Max Continuous Operating Voltage

Max Continuous Operating Current

Max Surge Current Turn on Voltage Turn on Time Throughput Energy Surge Side

Connector

Protected Side Connector

CGXZ+15NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB < 1.1 to 1 over frequency range +15 Vdc < 4.0 A 20 kA per IEC 61000-4-5

8/20 µs waveform +16.5 Vdc 4 ns for 2 kV/ns ≤ 500 µJ for 3 kA, 8/20 µs waveform N Female N Female CGXZ+15NFNF-A

CGXZ+36NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB < 1.1 to 1 over frequency range +36 Vdc < 4.0 A 20 kA per IEC 61000-4-5

8/20 µs waveform +40 Vdc 4 ns for 2 kV/ns ≤ 1500 µJ for 3 kA, 8/20 µs waveform N Female N Female CGXZ+36NFNF-A

DGXZ+06DFDF-A 800 MHz to 2500 MHz 300 W < 0.1 dB < 1.1 to 1 over frequency range + 6 Vdc < 4.0 A 20 kA per IEC 61000-4-5

8/20 µs waveform +6.5 Vdc 4 ns for 2 kV/ns ≤ 175 µJ for 3 kA, 8/20 µs waveform DIN Female DIN Female DGXZ+06DFDF-A

DGXZ+06NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB < 1.1 to 1 over frequency range + 6 Vdc < 4.0 A 20 kA per IEC 61000-4-5

8/20 µs waveform +6.5 Vdc 4 ns for 2 kV/ns ≤ 175 µJ for 3 kA, 8/20 µs waveform N Female N Female DGXZ+06NFNF-A

DGXZ+06NMNF-U 800 MHz to 2500 MHz 300 W < 0.1 dB < 1.1 to 1 over frequency range + 6 Vdc < 4.0 A 20 kA per IEC 61000-4-5

8/20 µs waveform +6.5 Vdc 4 ns for 2 kV/ns ≤ 175 µJ for 3 kA, 8/20 µs waveform N Male N Female DGXZ+06NMNF-U

DGXZ+06TFTF-A 800 MHz to 2500 MHz 300 W < 0.1 dB < 1.1 to 1 over frequency range + 6 Vdc < 4.0 A 20 kA per IEC 61000-4-5

8/20 µs waveform +6.5 Vdc 4 ns for 2 kV/ns ≤ 175 µJ for 3 kA, 8/20 µs waveform TNC Female TNC Female DGXZ+06TFTF-A

DGXZ+15NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB < 1.1 to 1 over frequency range +15 Vdc < 4.0 A 20 kA per IEC 61000-4-5

8/20 µs waveform +16.5 Vdc 4 ns for 2 kV/ns ≤ 500 µJ for 3 kA, 8/20 µs waveform N Female N Female DGXZ+15NFNF-A

DGXZ+15TFTF-A 800 MHz to 2500 MHz 300 W < 0.1 dB < 1.1 to 1 over frequency range +15 Vdc < 4.0 A 20 kA per IEC 61000-4-5

8/20 µs waveform +16.5 Vdc 4 ns for 2 kV/ns ≤ 500 µJ for 3 kA, 8/20 µs waveform TNC Female TNC Female DGXZ+15TFTF-A

DGXZ+36NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB < 1.1 to 1 over frequency range +36 Vdc < 4.0 A 20 kA per IEC 61000-4-5

8/20 µs waveform +40 Vdc 4 ns for 2 kV/ns ≤ 1.5 mJ for 3 kA, 8/20 µs waveform N Female N Female DGXZ+36NFNF-A

DGXZ-60NFNF-A 800 MHz to 2500 MHz 40 W < 0.1 dB < 1.1 to 1 over frequency range -60 Vdc < 4.0 A 20 kA per IEC 61000-4-5

8/20 µs waveform -66.5 Vdc 4 ns for 2 kV/ns ≤ 2.5 mJ for 3 kA, 8/20 µs waveform N Female N Female DGXZ-60NFNF-A

DGXE+30NMNF-A 650 MHz to 2700 MHz 400 Wrms average < 0.1 dB < 1.1 to 1 over frequency range +30 Vdc < 4.0 A 20 kA per IEC 61000-4-5

8/20 µs waveform+33 Vdc 4ns for 2 kV/ns 4 ns for 2 kV/ns ≤ 1.5 mJ for 3 kA,

8/20 µs waveform N Male N Female DGXE+30NMNF-A

37RF Surge Protection

DGXJ+24NFNF-A

• Coaxial RF protection with integrated Bias-T

• Patented technology• VSWR: ≤1.1:1 over frequency range • Multi-strike capability, high MTBF• Low throughput energy• Weatherized

Features

• IEC 61000-4-5 • IEC 60529 IP67• Bellcore #TA-NWT-00487• Procedure 4.11, Wind Driven (120 MPH) • RoHS compliant• CE

Standards and Certificates

GXJ Series

Environmental

Part Number CGXJ+36NFNF-A DGXJ+24NFNF-A DGXJ+24NFNM-A

Frequency Range 400 MHz to 1.2 GHz 800 MHz to 2.5 GHz 800 MHz to 2.5 GHz

RF Power 300 W average 300 W average 300 W average

Insertion Loss ≤ 0.1 dB over frequency range ≤ 0.1 dB over frequency range ≤ 0.1 dB over frequency range

VSWR ≤ 1.1:1 over frequency range ≤ 1.1:1 over frequency range ≤ 1.1:1 over frequency range

Max Continuous Operating Voltage +36 Vdc +24 Vdc +24 Vdc

Max Continuous Operating Current ≤ 4.0 A ≤ 4.0 A ≤ 4.0 A

Max Surge Current 20 kA per IEC 6100-4-5 8/20µs 20 kA per IEC 6100-4-5 8/20µs 20 kA per IEC 6100-4-5 8/20µs

Turn on Voltage +40 Vdc +26 Vdc +26 Vdc

Turn on Time 4 ns for 2 kV ns 4 ns for 2 kV ns 4 ns for 2 kV ns

Through-put Energy <25 µJ for 3 kA, 8/20 µs waveform

<25 µJ for 3 kA, 8/20 µs waveform

<25 µJ for 3 kA, 8/20 µs waveform

Surge Side Connector N Female N Female N Female

Protected Side Connector N Female N Female N Male

Integrated Bias-T, hybrid, multi-stage, multi-strike, fast response, high current capacity, DC pass coaxial lightning protection available with DIN and N connectors with frequency ranges of 400 MHz to 1.2 HGz and 800 MHz to 2.5 GHz.

Humidity <95% non-condensingOperating Temperature -50 C to + 85 C

Enclosure Rating IEC 60529, IP 67

39RF Surge Protection

DT-NFM

GT-TFF-AL

GT-NFSF-AL

• High surge current capability • High power configurations available • ±60 Vdc pass configurations available

(DT models) • Weatherized

Features

• IEC 61000-4-5• IEC 60529 IP67 (DT-NFF, DT-NFM)• Bellcore #TA-NWT-00487 (DT-NFF, DT-NFM)• Procedure 4.11, Wind Driven (120 MPH)

(DT-NFF, DT-NFM)• RoHS compliant (GT-NFF-AL, GT-NFM-AL,

GTH-NFF-AL, GTH-NFM-AL, GT-TFF-AL, GT-TFM-AL, DT-NFF, DT-NFM)

• CE (GT-NFF-AL, GT-NFM-AL, GTH-NFF-AL, GTH-NFM-AL, GT-TFF-AL, GT-TFM-AL)

Standards and Certificates

GT-NFF-AL

GT Series

Environmental

High performance gas tub coaxial protection for RF signals. Perform well in applications where a high voltage let-through is acceptable, yet good RF performance is essential.

Operating Temperature <95% non-condensingVibration -55 C to + 85 C

41RF Surge Protection

Frequency Range RF Power Insertion Loss VSWR Max Continuous Operating Current Max Surge Current Surge Side Connector Protected Side Connector

GT-NFF-AL DC to 7.0 GHz 90 W @ 30 MHz, 9 W @ 3 GHz

≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz

≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz

10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Female GT-NFF-AL

GT-NFSF-AL DC to 7.0 GHz 90 W @ 30 MHz, 9 W @ 3 GHz

≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz

≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz

10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Female GT-NFSF-AL

GT-NFM-AL DC to 7.0 GHz 90 W @ 30 MHz, 9 W @ 3 GHz

≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz

≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz

10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Male GT-NFM-AL

GTH-NFF-AL DC to 7.0 GHz 1 kW @ 30 MHz, 300 W @ 3 GHz

≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz

≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz

10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Female GTH-NFF-AL

GTH-NFM-AL DC to 7.0 GHz 1 kW @ 30 MHz, 300 W @ 3 GHz

≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz

≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz

10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Male GTH-NFM-AL

GT-TFF-AL DC to 7.0 GHz 1 kW @ 30 MHz, 300 W @ 3 GHz

≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 5.0 GHz, ≤0.5 dB @ 5.0 to 7.0 GHz

≤1.1:1 DC to 2.0 GHz, ≤1.2:1 2.0 to 3.0 GHz, ≤1.4:1 3.0 to 7.0 GHz

10 A 20 kA 8/20 µs per IEC 61000-4-5 TNC Female TNC Female GT-TFF-AL

GT-TFM-AL DC to 7.0 GHz 1 kW @ 30 MHz, 300 W @ 3 GHz

≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 5.0 GHz, ≤0.5 dB @ 5.0 to 7.0 GHz

≤1.1:1 DC to 2.0 GHz, ≤1.2:1 2.0 to 3.0 GHz, ≤1.4:1 3.0 to 7.0 GHz

10 A 20 kA 8/20 µs per IEC 61000-4-5 TNC Female TNC Male GT-TFM-AL

DT-NFF DC to 3.0 GHz 40 W @ 30 MHz ≤0.1 dB @ DC to 1.0 GHz, ≤0.25 dB @ 1.0 to 3.0 GHz ≤1.1:1 DC to 1.0 GHz 10 A 4 kA 8/20 µs per IEC 61000-4-5 N Female N Female DT-NFF

DT-NFM DC to 3.0 GHz 40 W @ 30 MHz ≤0.1 dB @ DC to 1.0 GHz, ≤0.25 dB @ 1.0 to 3.0 GHz

≤1.1:1 DC to 1.0 GHz, ≤1.15:1 DC to 3.0 GHz 10 A 4 kA 8/20 µs per IEC 61000-4-5 N Female N Male DT-NFM

43RF Surge Protection

• Engineered for RF and telemetry performance

• High surge current capacity

Features

• IEC 6100-4-5• RoHS compliant

Standards and Certificates

MDS

• 3 and 8 port earthed entrance panels• Building entry panels

Features

Grounding

Wall Thickness # of Ports Max. Cable Diameter3PEEP > 8” 3 3.13”8PB-M 10” 8 3.13”

8PEEP-M > 8” 8 3.13”

3PEEP-M

• RoHS

Standards

Flange mount, 75 ohm surge protection with telemetry and F female connector for satellite systems.

Input/Output Connector F female Enclosure Dimensions in (H x W x D ) 3.3 x 2.2 x 1.5

Enclosure Dimensions cm (H x W x D ) 8.4 x 5.5 x 3.7

Weight (max) lb, kg 0.5, 0.2

RF Frequency Range 300 MHz to 2.5 GHz

RF Power 50 WTelemetry Frequency Range 10 kHz to 150 kHz and 10 MHz to 100 MHzTelemetry Operating Voltage 24 Vdc

Max Surge Current 3 kA 8/20 µs, 3 kA 10/350 µs

Impedance 75 ohm

Mechanical

Environmental

Electrical

Part Name/Number MDS+24-F-F

Humidity 0 to 100% condensingOperating Temperature -50 C to + 85 C

Single point grounding is the most important part of any lightning protection system. PolyPhaser entry establishes a single point grounding solution. Whether you have a thick wall, thin wall, or multiple lines, PolyPhaser provides both panels and accessories to support all grounding requirements.

45RF Surge Protection

• Shield grounding kits• Copper grounding kits• Clamps• Copper straps• Adaptors

Options for Accessories Accessories

Grounding Clamp Product Description Application58R-112S Bonding Clamp Copper Strap Clamp

J-1 Transition Clamp for 0.5” to 1.33” diameter Wire/copper rod transition clamp

J-2 Transition Clamp for 1.5” to 2.25” diameter Wire/copper rod transition clamp

Grounding Kit Product Description ApplicationCCK Kit, Copper Cleaning Copper Cleaning KitCU-SPGP Copper Single Point Ground Panel Grounding Plate 16” on center

Device Ground Adaptor Product Description Application

GSA-KIT-N Kit, Ground Strap Adaptor N connector Ground Strap Adaptor SX Series

Copper Grounding Strap Width Length

CS112-25 1.5” 25’CS112-100 1.5” 100’CS3-25 3” 25’CS3-50 3” 50’CS3-100 3” 100’CS6-25 6” 25’CS6-50 6” 50’

CS6-100 6” 100’

Coaxial Shield Grounding Kit Shield Diameter Shield Material Grounding to

UNI-KIT-2CC 0.25” to 2.125” Copper or Brass Copper or BrassUNI-KIT-2CT 0.25” to 2.125” Copper or Brass Aluminum, Tin or Galvanized

PolyPhaser offers a full line of accessories needed to complete any professional single point grounding project.

Telephone: +1.208.772.8515 | Toll Free: +1.800.882.9110 | www.protectiongroup.com