Review of Parametric Studies for Optimizing Laboratory ... · 7 ANSI/ASHRAE Standard 110-2016...

36
Review of Parametric Studies for Optimizing Laboratory Ventilation HE Yueyang (Dr.), Department of Building, [email protected] Daniel HII Jun Chung (Dr.), School of Design & Environment, [email protected] WONG Nyuk Hien (Prof.), Department of Building, [email protected] PECK Thian Guan (Dr.), Office of Safety Health and Environment, [email protected] 22 October 2019

Transcript of Review of Parametric Studies for Optimizing Laboratory ... · 7 ANSI/ASHRAE Standard 110-2016...

  • Review of Parametric Studies for Optimizing Laboratory Ventilation

    HE Yueyang (Dr.), Department of Building, [email protected]

    Daniel HII Jun Chung (Dr.), School of Design & Environment, [email protected]

    WONG Nyuk Hien (Prof.), Department of Building, [email protected]

    PECK Thian Guan (Dr.), Office of Safety Health and Environment, [email protected]

    22 October 2019

    mailto:[email protected]:[email protected]:[email protected]:[email protected]

  • 2

    ◼ Introduce the background of our lab ventilation research project in NUS

    ◼ Review existing standards/parametric studies of air flow rates

    ◼ Review existing standards/parametric studies of air distributions

    ◼ Discuss lab design parameters to be tested in CFD simulations

    ◼ Objectives

  • Section 1

    Background: Lab Energy Performance

  • 0

    100

    200

    300

    400

    500A

    vera

    ge E

    ner

    gy U

    se In

    ten

    sity

    (kW

    h/m

    2yr

    )2013 2016 2017

    ◼ University energy consumptions in Singapore

    4Source: Building Construction Authority (BCA), 2018

  • ◼ BCA Green Mark for laboratories (GM Lab: 2017)

    5

    ◼ Background• Official launch: 13 June 2017

    • World’s 1st green certification scheme for laboratories design and

    operation

    ◼ Lab 2-1 Energy efficiency• Use more efficient air distribution system (baseline: 0.35 kW/ton)

    • Design for air recirculation within laboratory while meeting safety

    requirement

    • Adopt VAV lab air flow and variable flow exhaust controls

    ◼ Lab 2-2 energy effectiveness• Use occupancy sensor or sash position monitoring for fume hood/

    biosafety cabinet to reduce exhaust air ventilation

    • Use VAV fume hood/ biosafety cabinet with lower face velocity (Platinum:

    ≤ 0.5 m/s & Gold: ≤ 0.6 m/s for biological and chemical lab)

    • Link sash position/exhaust rate/face velocity monitoring to BMS

    Source: Building Construction Authority (BCA), 2017

  • ◼ Inaugural Platinum awards

    6

    ◼ Lab ACH Control Band:

    • Cornell’s Laboratory Ventilation Management Program: never go down to 2ACH, 3ACH is bare

    minimum (Source: https://sp.ehs.cornell.edu)

    • OSHA’s Lab Standard: 4-12 ACH: adequate general ventilation

    ◼ Inaugural Platinum awards

    • NUS Chemistry Lab – Tahir Foundation

    • Cambridge Centre for Advanced Research and Education (Cares)

    • Agency for Science, Technology and Research's (A*Star) Institute of Bioengineering and

    Nanotechnology - IBN Chemistry Lab

  • 7

    Tahir Foundation Building (MD1)

    Floor plan at level 17

    Single laboratoryequipped with 8 fume hoods

    (Area = 48.2 m2/ 518.8 ft2)

    Source: NUS

    ◼ Compact laboratory design in NUS

  • ◼ Diagram for optimizing lab ventilation

    8

    Air Flow Rates (ACH) Air Distributions

    CFD Parametric Studies

    Review of Existing Standards and Researches

    Chemical Spill Experiments

    Potential ACH ReductionSafety Requirements

    Validation

    Evaluation

    Future Lab Designs

  • Section 2

    Review: Air Flow Rates

  • ◼ Reviewed lab ventilation standards and criteria

    10

    NO Standard Region

    1 OSHA Federal register 29 CFR part 1910 US

    2 ANSI/ASHRAE Standard 62.1-2016 Ventilation for acceptable indoor air quality US

    3 NFPA 45-2015 Standard on fire protection for laboratories using chemicals US

    4 ANSI/AIHA/ASSE Z9.5-2012 Laboratory ventilation US

    5 ASHRAE Handbook 2015 - HVAC Applications, Chapter 16: Laboratories US

    6 ACGIH 2016 Industrial ventilation: a manual of recommended practice for design US

    7 ANSI/ASHRAE Standard 110-2016 Method of testing performance of laboratory fume hoods US

    8 SEFA 1-2010 Laboratory fume hoods recommended practices US

    9 Cornell University’s laboratory ventilation management program (LVMP) US

    10 International Building Code 2012 ICC

    11 BS 7258-1994 Laboratory fume cupboards / BS EN 14175 -7 fume cupboards British

    12 DD 191-1990 Method for determination of the containment value of a laboratory fume cupboard British

    13 DIN 1946-7 Ventilation and air conditioning Germany

    14 VDI 2051 Air-conditioning - Laboratories Germany

    15 SS 553-2016 Code of practice for air-conditioning and mechanical ventilation in buildings Singapore

    16 SS 554-2016 Code of practice for indoor air quality for air-conditioned buildings Singapore

    17 SS 641-2019 Code of practice for fire safety for laboratories Singapore

    18 GM Lab: 2017 BCA Green Mark for laboratories Singapore

    19 SCDF Fire Code 2018 chapter 7 Air-conditioning and mechanical ventilation systems Singapore

    20 WSH guidelines – Laboratories handling chemicals 2014 Singapore

    21 WSH guidelines – Management of indoor air quality in air-conditioned workplaces 2016 Singapore

    22 Workplace safety and health act Singapore

  • ◼ Standards for fume hood

    11

    Document Standard Year

    Laboratory fume cupboards BS 7258-2 1994 U ≥ 0.3 m/s 1994

    SEFA1-2010 U = 0.3 – 0.5 m/s 2010

    ANSI/AIHA Z9.5

    U = 0.3 – 0.4 m/s (excellent containment characteristics)U = 0.4 – 0.5 m/s (most hoods)

    U = 0.5 – 0.6 m/s (most hoods with higher operating costs)U = 0.6 – 0.7 m/s (performance is not significantly better)

    2012

    BCA Green Mark for laboratories GM Lab: 2017

    U ≤ 0.5 m/s (Platinum)U ≤ 0.6 m/s (Gold)

    2017

  • ◼ Standards for air flow rates (ACH)

    12

    Document Standard Highlight Year

    OSHA 29 CFR, Part 1910 ACH = 4 – 12 1990

    NFPA 45-2004ACH ≥ 4 (unoccupied)

    ACH > 8 (occupied)2004

    NFPA 45-2015 N/A 2015

    ANSI/AIHA Z9.5 ACH = 4 – 10⚫ ACH cannot meet all conditions. Furthermore, ACH is not the

    appropriate concept for designing contaminant control systems.2012

    ASHRAE 62.1-2016 ACH ≥ 1.2 (9-foot ceiling) 2016

    ASHRAE handbook HVAC

    2007ACH = 6 – 10 (occupied) 2007

    ASHRAE handbook HVAC

    2015N/A

    ⚫Minimum ventilation rates should be established on a room-by-room basis …

    2015

    ACGIH 2016 N/A⚫ ‘ACH’ is a poor basis for ventilation criteria where environmental

    control of hazards, heat, and/or odors is required …2016

  • ◼ Standards for air flow rates (ACH)

    13

    Document Standard Highlight Year

    Cornell University LVMPACH = 4 – 8 (normal)

    ACH = 3 – 6 (moderate)

    ⚫ Low ventilation: less than “moderate” rates, determined by review of operations in lab.

    ⚫ Lab-specific ventilation: determined by specific review of non-chemical hazards in lab.

    2013

    International Mechanical

    Code (IMC) 2009ACH ≥ 1.2 (9-foot ceiling) 2009

    DIN 1946-7:2009-7 ACH ≥ 9.1 (9-foot ceiling supply) 2009

    VDI 2051 Air-conditioning

    - LaboratoriesACH ≥ 9.1 (9-foot ceiling supply) 2018

    Singapore Civil Defence

    Force (SCDF) fire code

    2018

    ACH = 4 – 8 (Chemical/hazardous materials warehouses)

    ACH ≥ 20 (rooms involving use of flammable and explosive substances)

    2018

    SS 641-2019 Code of

    practice for fire safety for

    laboratories using

    chemicals

    ACH = 8 – 12 (prescribed value)ACH = 4 – 8 (further reduction based

    on risk assessment)

    ⚫ For energy conservation purposes, the air change rate for occupied laboratories can be reduced via the Risk Assessment Flow Chart

    2019

  • ◼ Parametric study of ACH

    14

    ACH (-) Floor area (m2)

    Method References2 4 6 8 10 12 14 16 18 20 22 24 26 28 30

    55.0 CFD Liu et al., 2017

    22.5 CFD Barbosa & Brum, 2017

    21.0 CFD Morcos et al., 2014

    70.0 Measurement Stuart et al., 2014

    N/A Measurement Sweet & Stuart, 2013

    21.0 Measurement Jin et al., 2012

    65.0 Measurement Klein et al., 2010

    65.0 Measurement Klein et al., 2009

    73.0 Measurement Smith & Smith, 2009

    N/A CFD Schuyler, 2009

    60.0 CFD Memarzadeh, 2009

    60.0 CFD Memarzadeh, 2007

    N/A N/A Sandru & Ouyang, 2005

  • ◼ Summary of ACH as a design parameter

    15

    ◼ Existing standards prefer a case-by-case criteria to a common criteria of ACH

    ◼ Existing studies mainly focus on the ACH ranged from 6 to 12

    ◼ ACH is not a appropriate basis for ventilation criteria

    ◼ Minimum ventilation rates should be established on a room-by-room basis considering the hazard level

  • 16

    ◼ SS 641-2019 Code of practice for fire safety for laboratories using chemicals

  • Section 3

    Review: Air Distributions

  • ◼ Standards for air flow distribution

    18

    Document Category Highlight Year

    ANSI/AIHA Z9.5

    Supply location,Exhaust location

    ⚫ Supply air diffusers close to the personnel corridor and entry door to the lab

    and far from the major exhaust devices.

    ⚫ Hoods and exhaust devices away from entry doors and exit corridors2012

    CFD solutions ⚫ Additional design information can be obtained using CFD

    ASHRAE handbook

    HVAC 2015

    ACH,Supply-exhaust location,

    supply type, pollutant source location, pollutant release rate, heat source

    position, room layout

    ⚫ Airflow patterns, temperature, and particle distribution … depend on several

    interrelated factors

    ⚫ The success of a mixed air distribution system depends primarily on supply

    diffuser location.

    2015

    CFD solutions

    ⚫ Physical testing and measurements … are time consuming and labor

    intensive, … analysis of various realistic scenarios through CFD simulations

    becomes an attractive alternative.

  • ◼ Standards for air flow distribution

    19

    Document Category Highlight Year

    DIN 1946-7:2009-7 Supply-exhaust location

    ⚫ The flow of air within the lab is primarily determined by the position and construction of supply air openings.

    ⚫ Supply air openings shall be constructed and arranged in such a way that they will not interfere with the extract air equipment.

    2009

    VDI 2051 Air-

    conditioning -

    Laboratories

    ACH, room space, room layout

    ⚫ Air flow patterns in lab areas depend on the intended use and the associated air volume flow rates and cooling loads. Further items to consider include the space required for the ventilation equipment and the arrangement of the components and devices.

    2018

    Workplace safety

    and health

    guidelines–

    laboratories

    handling chemicals

    Pollutant-exhaust location,Local exhaust location

    ⚫ Air exhaust points should be located as near as possible to expected contaminant sources

    ⚫ Fume cupboards should be located away from doors and high traffic areas2014

  • ◼ Parametric studies at lab scales

    20

    Authors Supply positionSupply

    propertyExhaust/return

    positionExhaust/ return

    property Spill position

    Chemical property

    Methods

    Liu et al., 2017

    • Wall-mount supply 1• Wall-mount supply 2• Wall-mount supply 3• Ceiling supply 1• Ceiling supply 2• Ceiling supply 3• Ceiling supply 4

    • 360 × 360 • 420 × 420

    • Wall return 1• Wall return 2• Wall return 3• Wall return 4• Ceiling return 1• Ceiling return 2

    • X 1

    • Bench-top 1• Bench-top 2• Bench-top 3• Bench-top 4

    • Benzene CFD

    Jin et al., 2012 • Ceiling supply • Square• Bench exhaust• Wall exhaust 1• Wall exhaust 2

    • X 1

    • On the desk • On the floor near

    an occupant • On the floor away

    from occupants

    • SF6 measurement

    Klein et al., 2009

    • Ceiling supply• 3 grilles • 6 grilles

    • Overhead exhaust grill

    • X 6• Floor level• Bench-top

    • Diethylether

    measurement

    Klein et al., 2010

    • Ceiling supply • 6 grilles• Overhead

    exhaust grill• X 6

    • Floor level• Bench-top

    • Ether• Acetone• Ethanol

    measurement

    Memarzadeh, 2009

    • Door gap and ceiling• Linear and

    square

    • Ceiling exhaust • Bench hood

    exhaust

    • X 1• X 2• X 4

    • Bench-top N/A CFD

    Morcos et al., 2014

    • Ceiling supply • Square• Bench exhaust• Wall exhaust 1• Wall exhaust 2

    • X 1

    • On the desk • On the floor near

    an occupant • On the floor away

    from occupants

    • SF6 CFD

  • ◼ Summary of the design parameters affecting lab ventilation

    21

    ◼ Existing standards provide some general recommendations for laboratory layouts

    ◼ Existing studies mainly focus on supply/exhaust/return/chemical emission positions and their properties

    ◼ CFD solution is recommended for additional design information

  • Section 4

    Parametric Studies

  • 23

    ScenarioRoom exhaust

    operationHood exhaust

    operationPollutant position Measuring variable

    1 OnOn

    (100% open sash)N/A

    Air/face velocity (U), air temperature (Tair) and surface temperature (Tsurface)

    2 On Off Bench-top

    VOC concentration (VOC)

    3 On Off Ground

    ◼ Spill experiments for CFD validation

  • ◼ Baseline laboratory configuration

    ScenarioP1: Fume hood

    operationP2: Supply response

    P3: Fume hood position

    P4: Supplyposition

    P5: Room exhaustposition

    Baseline Single Synchronous Aside Above-corridor Ceiling

    Pollutant source

    24

  • ◼ Testing design parameters

    BaselineP1: Fume hood operation

    MultipleP2: Supply response

    Asynchronous

    P4: Supply positionAbove-bench

    P5: Room exhaust position

    FloorP3: Fume hood position

    Central25

  • ◼ Testing design parameters

    BaselineSingle

    P1: Fume hood operationMultiple

    P2: Supply response

    Asynchronous

    P4: Supply positionAbove-bench

    P3: Fume hood positionCentral

    P5: Room exhaust position

    Floor26

  • ◼ Testing design parameters

    BaselineSynchronous

    P1: Fume hood operationMultiple

    P2: Supply response

    Asynchronous

    P4: Supply positionAbove-bench

    P3: Fume hood positionCentral

    P5: Room exhaust position

    Floor27

  • ◼ Testing design parameters

    BaselineAside

    P1: Fume hood operationMultiple

    P2: Supply response

    Asynchronous

    P4: Supply positionAbove-bench

    P3: Fume hood positionCentral

    P5: Room exhaust position

    Floor28

  • BaselineAbove-corridor

    P1: Fume hood operationMultiple

    P2: Supply response

    Asynchronous

    P4: Supply positionAbove-bench

    P5: Room exhaust position

    FloorP3: Fume hood position

    Central

    ◼ Testing design parameters

    29

  • ◼ Testing design parameters

    BaselineCeiling

    P1: Fume hood operationMultiple

    P2: Supply response

    Asynchronous

    P4: Supply positionAbove-bench

    P3: Fume hood positionCentral

    P5: Room exhaust position

    Floor (*dense gas)30

  • ◼ Matrix of testing design parameters (pending)

    ScenarioP1: Fume hood

    operationP2: Supply response

    P3: Fume hood position

    P4: Supplyposition

    P5: Room exhaustposition

    1 Single Synchronous Aside Above-corridor Ceiling2 Single Synchronous Aside Above-corridor Floor3 Single Synchronous Aside Above-bench Ceiling4 Single Synchronous Aside Above-bench Floor5 Single Synchronous Central Above-corridor Ceiling6 Single Synchronous Central Above-corridor Floor7 Single Synchronous Central Above-bench Ceiling8 Single Synchronous Central Above-bench Floor9 Single Asynchronous Aside Above-corridor Ceiling

    10 Single Asynchronous Aside Above-corridor Floor11 Single Asynchronous Aside Above-bench Ceiling12 Single Asynchronous Aside Above-bench Floor13 Single Asynchronous Central Above-corridor Ceiling14 Single Asynchronous Central Above-corridor Floor15 Single Asynchronous Central Above-bench Ceiling16 Single Asynchronous Central Above-bench Floor17 Multiple Asynchronous Aside Above-corridor Ceiling18 Multiple Asynchronous Aside Above-corridor Floor19 Multiple Asynchronous Aside Above-bench Ceiling20 Multiple Asynchronous Aside Above-bench Floor21 Multiple Asynchronous Central Above-corridor Ceiling22 Multiple Asynchronous Central Above-corridor Floor23 Multiple Asynchronous Central Above-bench Ceiling24 Multiple Asynchronous Central Above-bench Floor

    31

  • ◼ Evaluation of the design scenarios

    ◼ Pollutant source positions (focus on fugitive emission)

    ◼ Gas species

    • Acetone

    • Dimethyl Ether

    ◼ Minimum safety level

    • PEL?

    ◼ Evaluation zone (focus on breathing zone)

    Bench-topNear door

    Bench-topAway from door

    Evaluation zone

    32

  • ◼ Balance of ACH reductions and pollutant concentration

    ◼ ACH reductions (energy saving)

    Level 1 – Current ACH level

    Level 2 – Slight ACH reduction

    Level 3 – Moderate ACH reduction

    ◼ Pollutant concentration control (user safety)

    Steady simulations – Normalized mass fraction of pollutants (Cnormalized) and Local mean age of air (τzone)

    Transient simulations (selected scenarios) – Dilution time of pollutants (Tdilution)

    𝐶𝑛𝑜𝑟𝑚𝑎𝑙𝑖𝑧𝑒𝑑 =𝐶 − 𝐶𝑠𝑢𝑝𝑝𝑙𝑦

    𝐶𝑒𝑥ℎ𝑎𝑢𝑠𝑡 − 𝐶𝑠𝑢𝑝𝑝𝑙𝑦=

    𝐶

    𝐶𝑒𝑥ℎ𝑎𝑢𝑠𝑡

    𝑇𝑑𝑖𝑙𝑢𝑡𝑖𝑜𝑛 = 𝑇𝑖𝑛𝑖𝑡𝑖𝑎𝑙 - 𝑇𝑡ℎ𝑟𝑒sℎ𝑜𝑙𝑑

    τ𝑧𝑜𝑛𝑒 =𝑀

    𝑄

    (1)

    (2)

    (3)

    Source: Etheridge & Sandberg, 1996 33

  • Section 5

    Conclusion

  • ◼ Challenges and concerns in the future study

    ◼ Safety threshold:

    • Irregular risks associated with airborne chemicals in the laboratory

    • Safety versus energy saving

    ◼ Laboratory design:

    • Simplified models versus complicated lab environments

    • Selection/filter of key design parameters

    ◼ CFD simulations limitations:

    • Huge number of scenarios - super computer (HPC) required

    • Limitations of opportunities to validate CFD model with measurements

    • LES simulation method to capture the unsteady nature of flow – computationally expensive

    Source: Sweet & Stuart, 2013 35

  • HE Yueyang (Dr.), Department of Building, [email protected]

    Daniel HII Jun Chung (Dr.), School of Design & Environment, [email protected]

    WONG Nyuk Hien (Prof.), Department of Building, [email protected]

    PECK Thian Guan (Dr.), Office of Safety Health and Environment, [email protected]

    Thank you!

    Questions

    mailto:[email protected]:[email protected]:[email protected]:[email protected]