NUMBER STP I-16C REVISION 1 DATE 3/22/82 PAGE 1 OF 29 XP(2 ~M3E Pacific Gas and Electric Company DEPARTMENT OF NUCLEAR PLANT OPERATIONS DIABLO CANYON POWER PLANT UNIT NO(S) 1 AND 2 SURVEILLANCE TEST PROCEDURE TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUAL INITIATION AND BLOCKING REACTOR PROTECTION AND ENGINEERED SAFEGUARQ5 APPROVED: PLANT MANAGER DATE RESPONSIBILITY 1. Instrument Supervisor (Test Director), for performing the test, analysis of data, and reporting of results. 2. Shift Foreman, for obtaining the proper clearance and maintaining safe operating conditions during the test period. Also, the SFM is responsible to supply personnel to perform verification. FREQUENCY The test may only be performed during plant shutdown (modes 5 or 6) when the rod control motor-generators are not operating and the reactor trip breakers are available for test. The Technical Specifications, Tables 4.3-1 and 4.3-2 require that the functional test be performed on a normal refueling outage basis. SCOPE I The purpose of the routine test is to determine that the manually operated switches for initiating and blocking reactor protection and engineered safeguards functions are operative and will perform the actions for which they were designed. These functions are as follows: 1. Manual Reactor Trip 2. Containment Isolation Phase B 3. Safety Injection 4. Containment Isolation Phase A, Actuate Trains A&B 5. Pressurizer SI Reset-Block 83i 228042i '3i 220 ' " ."PDR ADOCK" 05000275" I 'I'P '...'PDR ' DCOOA8 1III

Transcript of Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker...

Page 1: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

NUMBER STP I-16C

REVISION 1

DATE 3/22/82PAGE 1 OF 29

XP(2 ~M3E Pacific Gas and Electric Company

DEPARTMENT OF NUCLEAR PLANT OPERATIONS

DIABLO CANYON POWER PLANT UNIT NO(S) 1 AND 2

SURVEILLANCE TEST PROCEDURE

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUAL

INITIATION AND BLOCKING REACTOR PROTECTION

AND ENGINEERED SAFEGUARQ5

APPROVED:PLANT MANAGER DATE

RESPONSIBILITY

1. Instrument Supervisor (Test Director), for performing the test,analysis of data, and reporting of results.

2. Shift Foreman, for obtaining the proper clearance and maintaining safeoperating conditions during the test period. Also, the SFM isresponsible to supply personnel to perform verification.

FREQUENCY

The test may only be performed during plant shutdown (modes 5 or 6) when

the rod control motor-generators are not operating and the reactor tripbreakers are available for test. The Technical Specifications, Tables4.3-1 and 4.3-2 require that the functional test be performed on a normalrefueling outage basis.

SCOPE

I The purpose of the routine test is to determine that the manually operatedswitches for initiating and blocking reactor protection and engineeredsafeguards functions are operative and will perform the actions for whichthey were designed. These functions are as follows:

1. Manual Reactor Trip

2. Containment Isolation Phase B

3. Safety Injection

4. Containment Isolation Phase A, Actuate Trains A&B

5. Pressurizer SI Reset-Block

83i228042i '3i220 ' "."PDR ADOCK" 05000275" I 'I'P'...'PDR '

DCOOA8 1III

Page 2: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

1

i lt

S.,I )wL

Page 3: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S) 1 AND 2

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATIONAND BLOCKING REACTOR PROTECTIONAND ENGINEERED AF

NUMBER STP IREVISION

3/22/82PAGE 2 OF 2g

6. Steamline SI Reset-Block

7. Source Range Reset-Block

8. Intermediate Range Block

9. Power Range Block

10. Feedwater .Isolation Reset

DISCUSSION

The manually operated switches involved in the initiating, blocking and/orresetting of protection and safeguards functions work in any or all of fourways. These are: 1) contacts directly in the circuitry of the equipment,2) contacts directly to the master relays in the SSPS, 3) contacts to theelectronic logic circuitry in the SSPS and 4) contacts directly to theunlatching coils of the slave relays, as follows:

1. The correct functioning gf the contacts directly in the circuitry ofequipment is determined by observing the actual operation of theequipment.

2. The correct functioning'of the contacts that are directly involved inmaster relay operation is determined in the following manner. Thereare two ways that a slave relay can be activated. One is through themaster relay with which it is associated and the other a parallelcircuit through the Safeguards Test Cabinet. As the slave relays areactually energized during the use of the Safeguards Test Cabinet, itis therefore only necessary to prove the manual switch circuitrythrough the master relay to or beyond the common points of the twoparallel circuits. This is done by monitoring the bottom coil(terminal 2) of the slave relays in question with the output relaycabinet in the "TEST" mode and the master relay selector in the "OFF"position.

3. The correct functioning of the contacts that introduce a signal to theelectronic logic is verified by manually introducing a signal from thecontrol room switches and determining that the proper potential isreceived at the logic input. Operation of the logic is tested usingthe semi-automatic tester in the SSPS (STP I-16A or I-16D) whichapplies the same input signals to the logic as the control roomswitches.

DCOOAB 2III

Page 4: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 5: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

(.DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I-16CREVISIONDATE 3/22/82PAGE 3 OF 29

.i

4. The correct functioning of the contacts that unlatch the slave relaysis verified by observing that the proper unlatching potential isapplied across the unlatching coil. 'The physical unlatching of thecoils is demonstrated during individual slave relay testing throughthe Safeguards Test Cabinet, or other testing.

As this test involves only the two basic logic conditions of "True orFalse" it is not necessary to use calibrated voltmeters. The values givenin the procedure are referenced to the logic state rather than to precisevoltages.

DOCUMENTATION AND REPORTING

1. Sumary Sheet

A summary sheet is provided which is intended to serve as a "shopfollower" for the test. This sheet shall be filled out each time thetest is performed, and shall be filed with the data sheet package forthe test. The sumary sheet has several basic functions:

a. To allow the technician and inspector (if any) to documentcertain important findings and/or the completion of certainimportant steps in the procedure. In particular, provision ismade on the form to document the completion of the importantsteps in the removal from service and reinstatement.

At the bottom of the form is a section entitled "Summary of MajorFindings." This should be filled out by the technician, and isintended to be a brief summary of important, unusual orunexpected items, such as breaker contact remains closed, switchreplaced, Plant Problem Report filed, etc. This is intended onlyto be a convenient summary to aid the reviewer of the test. Itis not intended to be a comprehensive test report. More detailedinformation would be found on the test data sheets, maintenancehistory cards, Plant Problem Reports or in other special reportsprepared for the test.

b. To assist the reviewer(s) of the test results by directing theirattention to the important findings. The tests are ordinarilyreviewed shortly after completion by a cognizant supervisor whoapproves the data sheets and maintenance cards.

2. Data Sheets

a. The verification of each required check will be entered on theprovided data sheets (Form 69-9439). Other items which should beincluded, as appropriate, are:

DCOOAB 3III

Page 6: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

0,

Page 7: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUAL

INITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP IREVISIONDATE 3/22/82PAGE 4 OF 29

. 1) Logic functions which do not operate properly should becircled in red to assist the reviewer.

2) Any apparent discrepancy which does not have an obviousexplanation should be explained under "Remarks" to assistthe reviewer.

b. Following completion of the test, the data sheets will bereviewed for conformity with requirements and signed by theInstrument Supervisor or other knowledgeable supervisor.

c. The data sheets are filed in the surveillance test file.

.

3. Additional Reporting and,Documentation Requirements

a. If there are no malfunctions, complete the data sheets and submitthe summary sheet, data sheets and the dated IBM schedule cardfor STP I-16C to the Instrument Supervisor. He, after approvingthe data sheets, will forward the IBM schedule card to the TestCoordinator to indicate completion of the test.

b. If at any time during the test any logic function fails toperform properly, notify the Instrument Supervisor immediatelyand do not continue with the test until approval has beenobtained from the Instrument Supervisor. The InstrumentSupervisor shall promptly notify the Shift Foreman that thechannel is inoperable. He shall also notify the Power PlantEngineer at the earliest convenience. Initiate a Plant ProblemReport.

PRECAUTIONS

Technical Specification 3.9.9 requires that the Containment Ventilationisolation system shall be operable while in refueling operations, duringCORE ALTERATIONS or movement of irradiated fuel within the containment.During this test the Containment Ventilation isolation system shall be made

inoperable to comply with the functional testing requirements of the manualinitiation per Tables 4.3-1 and 4.3-2. Therefore the action statement forspecification 3.9.9 shall be taken prior to performance of this test if inmode 6. That is:

With the Containment Ventilation isolation system inoperable, close each ofthe ventilation penetrations providing direct access from the containmentatmosphere to the outside atmosphere. The provision of Specification 3.0.3and 3.0.4 are not applicable.

DCOOAB 4III

Page 8: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 9: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I-16CREVISION ]DATE 3/22/82PAGE 5 OF 2g

PREREQUI SITES

All testing and/or maintenance must be performed under a validin-plant clearance. The clearance request should be submitted atleast 36 hours in advance to permit scheduling of related activities.NOTE: The clearance request should include prerequisite 2 and 3.

2.

3.

6.

As part of this procedure it is necessary to deactivate the slaverelays on both trains A and 8 for the duration of the test, therefore,the Shift Foreman should be aware of this such that the status of theplant will permit this condition. See precautions.

If in Mode 5, have the CRD MG set input breakers (52-13D-7 and52-13E-3) opened and MOL tags hung.

All reactor trip breakers are available for test.Have available the following test equipment:

Three voltmeters. No ca1ibration is required for these meters as theyare used to verify a logic state rather than a precise value.

Establish communications between the reactor trip breakers, thecontrol room and the train being tested for the duration of the test.NOTE: This test will require a minimum of 2 instrument technicians.One operator is required for testing of the reactor trip breakers.

PROCEDURE

Removal From Service

NOTE 1: All steps refer to the SSPS Train A unless otherwise noted.When testing Train B the variables in parenthesis, where appropriate,must be used.

NOTE 2: Verification of the satisfactory completion of specifiedsteps in the removal from service and reinstatement is to be recordedon the summary sheet for this test (Form 69-9439). The technicianperforming the test shall legibly initial the verified space providedon the summary sheet adjacent to the step just performed labeled I&C.The verifying operations person shall legibly initial the verifiedspace provided on the summary sheet for which verification isrequired. Verification spaces labeled N/A do not require operationsperson's verification.

DCOOAS 5III

Page 10: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 11: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)' AND 2

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED AFE A

NUMBER STP I 16CREVISIONDATE 3/22/82PAGE 6 OF 2g

,

a. Preliminary Check as Follows:

1) Verify that the proper clearances have been obtained fromthe Shift Foreman and record the clearance number on thesummary sheet.

2) Obtain the final OK to perform the test from the ShiftForeman and obtain the keys to the SSPS, Train A and B.Initial the summary sheet.

3) Notify the Control Operator that the SSPS is about to betested. Initial the summary sheet.

4) Verify that both control rod drive M.G. sets are cleared andnot running. Initial the summary sheet.

b. Removal as follows:

1) In Train A(B) place a fused jumpter (2 Amps) between TB507-2and TB508-4 (in Logic Cabinet). Initial the summary sheet.

NOTE: This will bypass both the manual switch and generalwarning inputs to the UV trip coils.

2) In Trains A 8' Output Relay Cabinets transfer the MODESELECTOR switches to the "TEST" position, and hang a CAUTIONtag. Initial the summary sheet.

3) In Train A and B Logic Cabinets, put the INPUT ERROR INHIBITswitch in the "INHIBIT" position, and hang a CAUTION tag.Initial the summary sheet.

4) Check that the MASTER RELAY SELECTOR switches in both Trainsare in the "OFF" position. Initial the summary sheet.

5) Check that the UV COIL VOLTAGE in the Logic Cabinet isapproximately 48 volts. Initial the summary sheet.

.DCOOA8 6III

Page 12: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

iI J

Page 13: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

</~op [[gl, +gpAgp~+g,pm ~~.ppt yEI

DIABLOCANYON POWER PLANT UNIT NQ(S) 1 AND

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUAL

INITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I 16CREVISIONDATE 3/22/82PAGE 7 OF 29

2. Manual Reactor Trip

a. REACTOR TRIP switch on the control console to the shunt tripcoils.

1) Have operator rack in the following breakers, in accordancewith OP B-6.

52/RTA (B) - Reactor Trip Train A(B).52/BYB (A) - Reactor Trip Bypass Train B(A).

2) Have operator close breakers 52/RTA (B) and 52/BYB (A).Record on the data sheet.

3) Verify an'nunciator "Reactor Protection Signals" (PK 04-12)is clear. Record on the data'sheet.

4) Continuously monitor that the UV COIL VOLTAGE remains at 48volts on Train A(B) while Step 2.a.5) is performed. Recordon the data sheet.

5) Turn the REACTOR TRIP switch on the control console to the"TRIP" position, verify that the "Reactor ProtectionSignals" annunciator (0412) is lit, then let the switchreturn to its neutral position. Record verification ofannunciator operation on the data sheet.

6) Verify that annunciator typewriter first printed out "ManualReactor Trip" in red then in black. Record on the datasheet.

7) Verify that the computer read out "Y00040 REAC MANUAL TRIPSW-1" first in red, then in black. Record on the datasheet.

8) Verify that breakers 52/RTA (B) and 52/BYB (A) are in thetripped position. Record on the data sheet.

9) Turn the REACTOR TRIP switch on the control console to the"RESET" position, then let it return to the neutralposition.

10) Verify that breaker 52/RTA (B) is closed. Record on thedata sheet.

,DCOOA8 7III

Page 14: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 15: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

;DIABLOCANYON POWER PLANT UNIT NO(S)

TRiP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I-16CREVISION 1DATE 3/22/82PAGE 8 OF 29

,

b. REACTOR TRIP switch on VB-2 to the shunt trip coils.

1) Have operator close breaker 52/BYB (A). Record on the datasheet.

2) Verify annunciator "Reactor Protection Signals" (PK 04-12)is clear. Record on the data ~ sheet.

3) Continuously monitor that the UV COIL VOLTAGE remains at 48volts on Train A(B) while Step 2.b.4) is performed. Recordon the data sheet.

4) Turn the REACTOR TRIP control switch on the vertical boardVB-2 to the "TRIP" position, verify that the "ReactorProtection signals" annunciator (PK 04-12) is lit, then letthe switch return to its neutral position. Recordverification of annunciator operation on the data sheet.

5) Verify that annunciator typewriter first printed out "ManualReactor Trip" in red then in black. Record on the datasheet.

6) Verify that computer read out "Y0005D REAC MANUAL TRIP SW-2"first in red then in black. Record on the data sheet.

7) Verify that breakers 52/RTA (B) and 52/BYB (A) are in thetripped position. Record on the data sheet.

c ~ REACTOR TRIP switch on the control console to the UV coils.

1) In Train A(B) transfer the jumper from between TB507-2 andTBSOB-4 to between TB507-4 and TB508-4. Record on the datasheet.

2) Verify that the UV COIL VOLTAGE in Train A(B) isapproximately 48 volts. Record on the data sheet.

3) Turn the REACTOR TRIP switch on the control console to the"TRIP" position and hold it in the "TRIP" position.

4) Verify that the UV COIL VOLTAGE in Train A(B) isapproximately zero volts. Record on the data sheet.

5) Let the REACTOR TRIP switch on the control console return tothe neutral position.

DCOOAB 8III

Page 16: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

0

Page 17: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)NUMBER STP I-16CREVISION 1DATE 3/22/82PAGE 9 OP 29

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

6) Verify that the UV COIL VOLTAGE in Train A(B) returned toapproximately 48 volts. Record on the data sheet.

d. REACTOR TRIP switch on VB-2 to the UV coils.

1) Turn the REACTOR TRIP switch on the vertical board VB-2 tothe "TRIP" position and hold it in the "TRIP" position.

2) Verify that the UV COIL VOLTAGE in Train A(B) isapproximately zero volts. Record on the data sheet.

3) Let the REACTOR TRIP switch on the vertical board VB-2return to the neutral position.

4) Verify that the UV COIL VOLTAGE in Train A(B) returned toapproximately 48 volts. Record on the data sheet.

e. Verification of P-4 (Reactor trip breaker trip contact interlockto ESFAS)Verification of P-4's accomplished in STP I-16E.

3. Containment Isolation Phase B

a ~ CONTAINMENT ISOLATION PHASE B ACTUATE TRAINS A AND B SWITCHES

1) In Train A(B) connect the negative lead of a vol tmeter toone of the terminals on TB642 or 656 (these are the twobottom TB's on the left side of the output cabinet and allterminals are common).

2) Set the voltmeter on DC to monitor +15 volts and zero volts.

3) With the positive probe verify that there is +15 volts DC onthe lower right coil (terminal 2) on the following slaverelays.

K615K622K618K619K625K626K643K644K645

- Containment Ventilation Isolation- Containment Ventilation Isolation- Phase B Isolation- Phase B Isolation- Phase 8 Isolation- Phase B Isolation- Spray Actuation- Spray Actuation- Spray Actuation

Record on the data sheet.

DCOOAB 9III

Page 18: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 19: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

,DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I-16CREVISION ],DATE 3/22/82PAGE 1(PP 29

4) Turn both CONTAINMENT ISOLATION PHASE B ACTUATE TRAINS A ANDB switches (VBl) to the "ACTUATE" position simultaneouslyand hold them in the "ACTUATE" position.

5) With the positive probe of the voltmeter verify that thereis zero volts DC on the lower coil (terminal 2) on the sameslave relays as in Step 3.a.3). That is:

K615K622K618K619K625K626K643K644K645

Record on the data sheet.

6) Release the two CONTAINMENT ISOLATION PHASE 8 ACTUATE TRAINA AND B switches.

7) Repeat Step 3.a.3) to verify the master relays havedeenergized. Record on the data sheet.

b. CONTAINMENT SPRAY TRAIN A(B) RESET pushbutton

1) In the Logic Cabinet turn the FUNCTION SELECTORS LOGIC Aswitch to position "23" and LOGIC B switch to position "18".(Hi-Hi Contain. Press., Spray Actuation and Phase B).

2) Simultaneously depress any two of the four MANUAL INPUTFUNCTION TEST pushbuttons and maintain them in the depressedposition through Step 3.c.7).

DCOOA8 10III

Page 20: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

~ i

Page 21: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUAL

INITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I-].6CREVISIONDATE 3/22/82PAGE 11 " 29

3) With the positive probe of the voltmeter verify that thereis zero volts DC on the lower coil (terminal 2) on thefollowing slave relays

K618K619K625K626K643K644K645

Record on the data sheet.

4) 'erify that the UV COIL VOLTAGE meter in Train A(B) readzero VDC. Record on the data sheet.

5) Depress the CONTAINMENT SPRAY TRAIN A(B) RESET pushbuttonand maintain it depressed while verifying the following witha voltmeter set to monitor 125 volts AC:

125 VAC across the reset (upper) coil (terminals 3 5 4) ofthe slave relays.

K643K644K645

Record the data sheet.

6) Release the CONTAINMENT SPRAY TRAIN A(B) RESET pushbuttonbut still maintain the two MANUAL INPUT FUNCTION TESTpushbuttons depressed.

7) Verify that the UV COIL VOLTAGE meter in Train A(B) reads+48VDC. Record on the data sheet.

8) In the Logic Cabinet turn the FUNCTION SELECTOR switch LOGICB to position "19".

9) Verify that the UV COIL VOLTAGE meter in Train A(B) readszero VDC. Record on the data sheet.

10) Depress the CONTAINMENT SPRAY TRAIN A(B) RESET pushbuttonand then release it, but still maintain the two MANUAL INPUTFUNCTION TEST pushbuttons depressed.

DCOOAB 11III

Page 22: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 23: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

liQhiI GV" ~L

DIABLOCANYON POWER PLANT UNIT NO(S) 1 AND 2 NUMBER STP I 16CREVISIONDATE 3/22/82PAGE 120F 29

TITLE: TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

c ~

11) Verify that the UV COIL VOLTAGE meter in Train A(B) reads+48VDC. Record on the data sheet.

CONTAINMENT ISOLATION PHASE B TRAIN A(B) RESET pushbutton

1) In the Logic Cabinet turn the FUNCTION SELECTOR switch LOGICB to position "21".

2) Verify that the UV COIL VOLTAGE meter in Train A(B) readszero VDC. Record on the data sheet.

3) Depress the CONTAINMENT ISOLATION PHASE B TRAIN A(B) RESETpushbutton and maintain it depressed while verifying thefollowing with a voltmeter set to monitor 125 volts AC.

125 VAC across the reset (upper) coil (terminals 3 8 4) ofthe slave relays.

K618K619K625K626

Record on the data sheet.r

4) Release the CONTAINMENT ISOLATION PHASE B TRAIN A(B) RESETpushbutton but still maintain the two MANUAL INPUT FUNCTIONTEST pushbuttons depressed.

5) Verify that the UV COIL VOLTAGE meter in Train A(B) reads+48VDC. Record on the data sheet.

6) Depress the CONTAINMENT SPRAY TRAIN A(B) RESET pushbutton.

7) Release the two MANUAL INPUT FUNCTION TEST pushbuttons.

8) Return the LOGIC A switch to the "OFF" position and theLOGIC B switch to position "24".

DCOOA8 12III

Page 24: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

0

Page 25: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I-16CREVISION 1DATE 3/22/82PAGE 133F 29

9) With the position probe of the voltmeter verify that thereis 15 volts DC on the lower coil (terminal 2) on thefollowing slave relays.

K615K622K618K619K625K626K643K644K645

Record on the data sheet.

10) With a voltmeter set to monitor 125 volts AC verify thatthere is zero volts AC across the reset (upper) coil(terminal 3 8 4) of the slave relays.

K618K619K625K626K643K644K645

Record on the data sheet.

4. Safety Injection

a. SAFETY INJECTION ACTUATE TRAINS A and B MSI-1 switch

1) If not already done connect the negative lead of a voltmeterto one of the terminals on TB-642 or 656 (these are the twobottom TB's on the left side of the output cabinet and allterminals are common).

2) Set the voltmeter on DC to monitor +15 volts and zero volts.

DCOOAB 13III

Page 26: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

0

Page 27: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

'DIABLOCANYON POWER PLANT UNIT NO(S)

TITLE: TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUAL

INITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I 16CREVISION 1DATE 3/22/82PAGE IPP 29

3) With the positive probe verify that there is +15 volts DC onthe lower coil (terminal 2) on the following slave relays.

K601 - Safety InjectionK602 - Safety InjectionK603 - Safety InjectionK604 - Safety InjectionK605 - Phase A IsolationK606 - Phase A IsolationK607 - Phase A IsolationK608 - Safety InjectionK609 - Safety InjectionK610 - Safety InjectionK611 - Safety InjectionK612 - Phase A IsolationK613 - Phase A IsolationK614 - Phase A IsolationK615 - Containment Ventilation IsolationK617 - Safety InjectionK620 - Closes Feedwater ValvesK621 - Trip Turbine & Main Feedwater PumpsK622 - Containment Ventilation Isolation

Record on the data sheet.

NOTE: If zero volts is obtained for any of the above,notify the Instrument Supervisor in charge beforecontinuing.

4) Have operator rack in the following breakers i.f it has notalready been done, in accordance with Operating ProcedureB-6:

52/RTA (8) - Reactor Trip Train A (8).52/BYB (A) - Reactor Trip Bypass Train B (A).

5) Have operator close the following breakers.

52/RTA (8) - Reactor Trip Train A (8).52/BYB (A) - Reactor Trip Bypass Train 8 (A).

Record on the data sheet.

6) Verify annunciator "Safety Injection Initiate (PK 02-02)clear. Record on the data sheet.

DCOOAB 14III

Page 28: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

0

Page 29: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S) 1, AND 2

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP IREVISIONDATE 3/22/82PAGE 190F 29

7) Turn the SAFETY INJECTION ACTUATE TRAINS A and B - MSI-1switch on the vertical board (VBl) to the "ACTUATE" positionand hold it in the "ACTUATE" position.

8) With the positive probe of the voltmeter verify that thereis zero volts DC on the lower coil (terminal 2) on the sameslave relays as in Step 3.2.3). That is:

K601K602K603K604K605K606K607K608K609K610K611K612K613K614K615K617K620K621K622

Record on the data sheet.

9) Verify annunciator "Safety Injection Initiate (PK 02-02) islit and that typewriter prints out "MANUAL S.I." in red.Record on the data sheet.

10) Verify computer readout "Y0920D SIS MANUAL SW-1 PROT It SITRIP". Record on the data sheet.

b. CONTAINMENT VENTILATION ISOLATION TRAIN A(B) RESET pushbutton

1) Still holding the SI actuate switch in the "ACTUATE"position momentarily depress the CONTAINMENT VENTILATIONISOLATION TRAIN A(B) RESET pushbutton.

DCOOAB 15III

Page 30: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 31: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I-16CREVISION 1DATE 3/22/82PAGE 16OF 29

2) With the positive probe of the voltmeter verify that thereis 15 volts DC on the lower coil (terminal 2) on thefollowing slave relays:

K615K622

Record on the data sheet.

c. CONTAINMENT ISOLATION PHASE A TRAIN A(B) RESET pushbutton

i

2)

Still holding the SI actuate switch in the "ACTUATE"position, momentarily depress the CONTAINMENT ISOLATIONPHASE A TRAIN A(B) RESET pushbutton.

I

With the positive probe of the voltmeter verify that thereis 15 volts DC on the lower coil (terminal 2) on thefollowing slave relays:

K605K606K607K612K613K614

Record on the data sheet.

3) Release the SAFETY INJECTION ACTUATE TRAINS A 8 B - MSI-1 onthe vertical board.

4) Verify computer clears "Y0920D SIS MANUAL SW-1 PROT 8 SITRIP". Record on the data sheet.

5) Verify annunciator "Safety Injection Initiate (PK 02-02) isclear and that typewriter prints out "MANUAL S. I." in black.Record on the data sheet.

DCOOA8 16III

Page 32: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 33: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I„16CREVISIONDATE 3/22/82PAGE 18 29

6) With the positive probe verify that there is 15 volts DC onthe lower coil (terminal 2) on the following slave relays.

K601K602K603K604K605

~ K606

K607K608K609K610K611K612

K613K614K615K617K620K621K622

7) Verify that the following breakers are tripped.

52/RTA (B) - Reactor Trip Train A (B).52/BYB (A) - Reactor Trip Bypass Train 8 (A).

Record on the data sheet.

8) Repeat Steps 4.a.5) through 4.c.7) using the SAFETYINJECTION ACTUATE TRAINS A and B MSI-2 switch on the controlconsole instead of the MSI-1 switch on the vertical board.

d. SAFETY INJECTION TRAIN A(B) RESET pushbuttonTesting of the switch is covered in STP I-16B.

5. Containment Isolation Phase A Actuate Trains A & B

a ~ CONTAINMENT ISOLATION PHASE A ACTUATE TRAINS A & B switch on VB1

1) If not already done, connect the negative lead of avoltmeter to one of the terminals on TB642 or 656.(these arethe two bottom TB's on the left side of the output cabinetand all terminals are comon).

2) Set the voltmeter on DC to monitor +15 volts DC and zerovolts.

DCOOAB 17III

Page 34: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

0

Page 35: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

iiFQP ([(P'QP}eI P ~~P~jp,p ",, p,r,n v~pt

DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I 16CREVISIONDATE 3/22/82PAGE 1$ P 29

3) With the positive probe verify that there is +15 volts DC onthe lower coil (terminal 2) on the following slave relays:

K605K606K607K612K613K614K615K622

Record on the data sheet.

NOTE: If zero volts is obtained for any of the above,not>fy the Instrument Supervisor in charge beforecontinuing.

4) Turn the CONTAINMENT ISOLATION PHASE A ACTUATE TRAINS A 8 B

switch on VB1 to the actuate position and hold it in the"ACTUATE" position.

5) With the positive probe of the voltmeter verify that thereis zero volts DC on the lower coil (terminal 2) on the samerelays as in Step 5.a.3). That is

K605K606K607K612K613K614K615K622

Record on the data sheet.

6) Release the CONTAINMENT ISOLATION PHASE A ACTUATE TRAINS A 8

8 switch on the vertical board.

DCOOAB 18III

Page 36: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 37: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I-16CREVISION 1DATE 3/22/82PAGE 19DF 29

7) With the positive probe verify that there is 15 volts DC onthe lower coil (terminal 2) on the following slave relays:

K605K606K607K612K613K614K615K622

Record on the data sheet.

b. CONTAINMENT ISOLATION PHASE A ACTUATE TRAINS A & 8 switch on thecontrol console.

Repeat Steps 5.a.4) through Step 5.a.7) using the CONTAINMENTISOLATION PHASE A, ACTUATE TRAINS A 8 B switch on the controlconsole instead of the one on the vertical board.

Co CONTAINMENT ISOLATION PHASE A TRAIN A(B) RESET pushbutton

1) Depress the CONTAINMENT ISOLATION PHASE A TRAIN A(B) RESETpushbutton (VB1) and maintain it depressed.

2) With a voltmeter set to monitor 125 volts AC, verify 125volts AC across the reset (upper) coil (terminals 3 5 4) ofslave relays.

K605K606k607K612K613K614

Record on the data sheet.

3) Release the CONTAINMENT ISOLATION PHASE A TRAIN A(B) RESETpushbutton.

d. CONTAINMENT VENTILATION ISOLATION TRAIN A(B) RESET pushbutton

1) Depress the CONTAINMENT VENTILATION ISOLATION TRAIN A(B)RESET pushbutton (VB1) and maintain it depressed.

DCOOAB 19III

Page 38: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 39: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)NUMBER STP I 16CREVISIONDATE 3/22/82PAGE 2(PF 29

TITLE: TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

2) With a voltmeter set to monitor 125 volts AC, verify 125volts AC across the reset (upper) coil (terminals 3 5 4) ofslave relays.

K615K622

Record on the data sheet.

3) Release the CONTAINMENT VENTILATION ISOLATION TRAIN A(B)RESET pushbutton.

4) With a voltmeter set to monitor 125 volts AC, verify zerovolts AC across the reset (upper) coil (terminals 3 5 4) ofslave relays.

K605K606K607K612K613K614K615K622

Record on the data sheet.

5) Remove the negative lead of the voltmeter that was connectedto one of the terminals on TB642 or 656. Record on the datasheet.

I 6. Reset Block Switches (Pressurizer SI, Steamline SI, and Source Range)

a ~ PRESSURIZER SI RESET-BLOCK TRAIN A(B) switch on CC2

1) Set a voltmeter on DC to monitor +48VDC and make thefollowing connections to monitor the block function forpressurizer SI:

VOLTMETER

Neg. Lead

Pos. Lead

PRESSURIZERSI

TB509-1

TB509-2

STEAMLINESI

TB509-7

TB509-8

SOURCERANGE

TB506-11

TB506-10

DCOOA8 20III

Page 40: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

L

'1

Page 41: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

iFOP< [Nl"=CPM'-"'limni'." Of'«"" Y"

DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUAL

INITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I-16CREVISION 1DATE 3/22/82PAGE 2 1OF 29

2) Verify that there is a +48VDC reading on the voltmeter.Record on the data sheet.

3) Turn the PRESSURIZER SI RESET-BLOCK TRAIN A(B) switch to the"BLOCK" position and verify that there is a 0 VDC reading onthe voltmeter with the switch maintained in the "BLOCK"

position. Record on the data sheet.

4) Release the PRESSURIZER SI RESET-BLOCK TRAIN A(B) switch andverify that there is a +48VDC reading on the voltmeter.Record on the data sheet.

5) Remove the voltmeter from the points in Step 6.a.1) and makethe following connections to monitor the reset function forpressurizer SI.

i

VOLTMETER

Neg. Lead

Pos. Lead

PRESSURIZERSI

..TB509-4

TB509-5

STEAMLINESI

TB509-10

TB509-11

SOURCERANGE

TB506-8

TB506-7

6) Verify that there is a 0 VDC reading on the voltmeter.Record on the data sheet.

7) Turn the PRESSURIZER SI RESET-BLOCK TRAIN A(B) switch to the"RESET" position and verify that there is a +48VDC readingon the voltmeter with the switch maintained in the "RESET"

position. Record on the data sheet.

8) Release the PRESSURIZER SI RESET-BLOCK TRAIN A(B) switch andverify that there is a 0 VDC reading on the voltmeter.Record on the data sheet.

9) Remove the voltmeter from the points in Step 6.a.5).

b. STEAMLINE SI RESET-BLOCK TRAIN A(B) switch on CC2

Repeat steps 6.a. 1) through 6.a.9) for the STEAMLINE SIRESET-BLOCK TRAIN A(B) switch using the meter connections asspecified in the tables for this switch.

DCOOAB 21III

Page 42: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 43: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)

TITLE: TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I-16CREVISION 1

DATE 3/22/82PAGE 22OF 29

c. SOURCE RANGE RESET-BLOCK TRAIN A(B) switch on CC1

Repeat steps 6.a. 1) through 6.a.9) for both SOURCE RANGERESET-BLOCK TRAIN A8B switches using the meter connections asspecified in the tables for this switch.

NOTE: Both switches must be pushed at the same time.

7. Block Switches ( Intermediate Range and Power Range)

INTERMEDIATE RANGE BLOCK TRAIN A(B) switch on CC1

1) Set a voltmeter on DC to monitor +48VDC and make thefollowing connections to monitor the block function for theintermediate range.

VOLTMETERINTERM.RANGE

POWER

RANGE

iNeg. Lead TB507-8 TB507-11

Pos. Lead TB507-7 TB507-10

2) Verify that there is a +48VDC reading on the voltmeter.Record on the data sheet.

3) Turn the INTERMEDIATE RANGE BLOCK TRAIN A(B) switch to the"BLOCK" position and verify that there is a 0 VDC reading onthe voltmeter with the switch maintained in the "BLOCK"position. Record on the data sheet.

4) Release the INTERMEDIATE RANGE BLOCK TRAIN A(B) switch andverify that there is a +48VDC reading on the voltmeter.Record on the data sheet.

5) Remove the voltmeter from the points in Step 7.a. 1).

b. POWER RANGE BLOCK TRAIN A(B) switch on CC1

Repeat steps 7.a. 1) through 7.a.5) for the POWER RANGE BLOCKTRAIN A(B) switch using the meter connections as specified in thetable for this switch.

DCOOA8 22III

Page 44: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 45: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUAL

INITIATION AND BLOCKING REACTOR PROTECTION,AND ENGINEERED SAFEGUARD

NUMBER STP I 16CREVISIONDATE 3/22/82PAGE 2$ )F 2g

8. Feedwater Isolation Reset (FEEDWATER ISOLATION TRAIN A(B) RESET switchon VB3).

a. On the Logic Test Panel place the FUNCTION SELECTORS IN THEfollowing positions:

1) Turn LOGIC A switch to position No. 23

2) Turn LOGIG B switch to position No. 24

3) Turn LOGIC C switch to position No. 20

b. Connect the negative lead of a voltmeter to one of the terminalson TB642 or 656 (these are the two bottom TB's on the left sideof the output cabinet and all terminals are comIIon).

c. Set the voltmeter on DC to monitor +15 volts DC and zero volts.

d. With the positive probe verify that there is +15 volts DC on thelower coil (terminal 2) on the following slave relays:

K636K637

Record on the data sheet.

e. On the Logic Test Panel depress CHANNEL I and CHANNEL II, MANUAL

INPUT FUNCTION TEST pushbuttons and maintain them in thedepressed position.

f. With the positive probe of the voltmeter verify that there iszero volts DC on the lower coil (terminal 2) on the same slaverelays as in Step 8.d. That is:

K636K637

Record on the data sheet.

g. Depress the FEEDWATER ISOLATION TRAIN A(B) RESET pushbutton andmaintain it in the depressed position.

DCOOAB 23III

Page 46: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

0 0

Page 47: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP IREVISIONDATE 3/22/82PAGE 2+F 29

h. With the positive probe of the voltmeter verify that there is +15volts DC on the lower coil (terminal 2) on the same slave relaysas in Step 8.f. That is:

K636K637

Record on the data sheet.

With a voltmeter set to monitor 125 volts AC verify 125 volts ACacross the reset (upper) coil (terminals 3 5 4) of slave relays:

K636K637

Record on the data sheet.

j. Release the FEEDWATER ISOLATION TRAIN A(B) RESET pushbutton.

k. With the positive probe of the voltmeter verify that there isstill +15 volts DC on the lower coil (terminal 2) on slaverelays:

K636K637

Record on the data sheet.

1. With a voltmeter set to monitor 125 volts AC verify zero volts ACacross the reset (upper) coil (terminals 3 8 4) of slave relays:

K636K637

Record on the data sheet.

m. Release the CHANNEL I and CHANNEL II, MANUAL INPUT FUNCTION TESTpushbuttons.

n. Return the LOGIC A switch to the "OFF" position and the LOGIC Band C switches to the position "24". Record on the data sheet.

o. Remove the negative lead of the voltmeter that was connected toone of the terminals of TB642 or 656. Record on the data sheet.

DCOOAB 24III

Page 48: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 49: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I-REVISION ],DATE 3/22/82PAGE 2g3F 29

9. Reinstatement of SSPS as follows:

NOTE: Due to both MODE SELECTOR switches (Train A 5 B) being in theTEST" position it will be necessary to reinstate Train A 8 B

simultaneously.

a ~

b.

Verify the INPUT ERROR INHIBIT switch for Train A and Train B isin the "INHIBIT" position. Initial the sumary sheet.

Verify the MULTIPLEXER TEST switch for Train A and Train B is inthe "NORMAL" position. Initial the summary sheet.

c. Verify that the switches on the Logic Test Panel for Train A andTrain B are set as follows:

1) LOGIC A at "OFF"

2) LOGIC B at "24"

3) LOGIC C at "24.".

4) LOGIC D at "24"

5) PERMISSIVES at "OFF"

6) MEMORIES at "OFF"

7) BLOCKING FUNCTION TEST at either position

8) MULTIPLEXER TEST switch in "NORMAL"

Initial the appropriate column on the summary sheet.

d. On the Output Relay Test Panel for Train A and Train B verifythat the MASTER RELAY SELECTOR is in the "OFF" position. Initialthe sumIary sheet.

e. Transfer the MODE SELECTOR switch in the Output Test Panel forTrain A and Train B to the "OPERATE" position and observe theirrespective green lights are lit. Initial the summary sheet.

NOTE: Manual Safeguards actuation induced by operation ofswitches is now possible. Automatic actuation on Safeguardschannels input is impossible as the inputs are inhibited.

'DCOOAB 25III

Page 50: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 51: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S) 1 AND 2 NUMBER STPREVISIONDATE 3/22/82PAGE 2 g3F 2 g

TITLE: TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

f. Actuate all manual block switches as shown below for the trainunder test at the Control Console to reinstate or reset thefollowing blocks and initial the summary sheet.

1) SOURCE RANGE RESET-BLOCK TRAIN ASOURCE RANGE RESET-BLOCK TRAIN B

"RESET""RESET"

NOTE: Both Source Range Switches must be turned at the sametime.

2) PRESSURIZER S. I. RESET-BLOCK, TRAINS A 8 B ~ "BLOCK"

3) STEANLINE S.I. RESET-BLOCK, TRAINS A B B ~ "BLOCK"

g. Verify the following annunciator status:

IO

ANNUN.

PK 08-20 SOURCE RNG TRIP BLOCKED

PK 08-16 PZR S. I. BLOCKED

PK 08-17 HI STM FLO S. I. BLOCKED

Initial the appropriate column on the summary sheet.

STATUS

OFF

ON

ON

h. Obtain the written permission from the Shift Foreman to leave theMODE SELECTOR in the "OPERATE" position if required to make thesystem operable. Otherwise place in the "TEST"* position.Initial the summary sheet.

NOTE: The preferred position during the Modes 5 and 6 when notmoving fuel, or core alterations is in "TEST". This makes theSSPS incapable of causing safeguards actuation.

*In in "TEST," hang a caution tag on the MODE SELECTOR switchstating that S. I. blocks must be reinstated before placing in"OPERATE." This may be done by performing Steps 1 thru 10 ofSTP-16D3.

CAUTION: If moving fuel or during core alterations theContainment Vent Isolation must be operable (Requires SSPSOPERABLE). Therefore the following conditions MUST be met:

DCOOA8 26III

Page 52: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 53: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

P gl."-C'q-~P,h 8;,-P~~,"- ~| "~.Pq P,P~«

li< ~li'Jd Mi'L'~k4u il I ~. ~'4

DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I„16CREVISIONDATE 3/22/82PAGE 2$ F 29

1) HI Containment pressure S.I. must NOT be active. Check thebistables in the Hagan ra'cks for at Teast 2/3 not tripped.

PC 936A -—Rack 8

PC 935A —- Rack 11

PC 934A -—Rack 16

2) HI Steamline Differential Pressure S. I. must NOT be active.Check the bistables in the Hagan racks for at~east 2/3 nottripped on each steamline.

LP1 PC 514A —- Rack 3

PC 515A —- Rack 7

PC 516C --- Rack 16

LP2 PC 5148 -—Rack 3

PC 525A.-'-- Rack 9

PC 526C -—Rack 11

LP3 PC 534A —- Rack 5

PC 515B —- Rack 7

PC 526D —- Rack 11

LP4 PC 5348 --- Rack 5

PC 525B —- Rack 9

PC 516D —- Rack '16

3) PZR S. I. BLOCKED.

4) HI STM FLO S. I. BLOCKED.

5) MODE SELECTOR SWITCH IN OPERATE.

DCOOA8 27III

Page 54: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 55: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

,DIABLOCANYON POWER PLANT UNIT NO(S)

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

NUMBER STP I I6CREVISIONDATE 3/22/82PAGE 2P" 29

i

k.

l.

m.

n.

0.

WARNING Do not perform this step unless:

I) Condition 9.h. 1) through 9.h.5) are met.

OR

2) The MODE SELECTOR switch is in "TEST".

Return both Train A and Train B INPUT ERROR INHIBIT switches tothe "NORMAL" position. Remove CAUTION tag. Initial the summarysheet.

In Train A(B) remove the jumper from between TB507-4 and 508-4.Record removal of jumper. Initial the summary sheet.

In Train A(B) verify the UV Coil Voltage at 0 volts. Initial thesummary sheet.

Verify "GENERAL WARNING" lights are out on both Trains A&B if theMODE SELECTOR switches are returned to the "OPERATE" positions.Initial the sumary sheet.

Close and lock all'.SSPS cabinet doors. Initial the summarysheet.

Report OFF to Shift Foreman and have Operations reestablishnormal plant conditions relative to containment ventilationisolation and rack out the reactor trip breaker 52/RTA(B) andbypass breaker 52/BYB(A) in accordance with Operating ProcedureB-6.

Inform the Shift Foreman of the following SSPS switch positionsand return key for Solid State Protection. Initial the summarysheet.

I) MULTIPLEXER TEST switches - "NORMAL" (both trains)

2) INPUT ERROR INHIBIT switches - "NORMAL" (both trains)

3) MODE SELECTOR - as per his instruction (both trains)

Sign data sheets and turn them over to the Instrument Supervisorin charge for review and filing.

DCOOA8 28III

Page 56: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 57: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

DIABLOCANYON POWER PLANT UNIT NO(S) 1. AND 2

TRIP ACTUATING DEVICE OPERATIONAL TEST OF MANUALINITIATION AND BLOCKING REACTOR PROTECTIONAND ENGINEERED SAFEGUARDS

WUMBER STP I„16CREVISION ]DATE 3/22/82PAGE 2g3F 29

(INI

REFERENCES

1. Solid State Protection System by W (PGandE Record Print No.DC-663231-16)).

2. Solid State Protection System Interconnection Diagrams by W (PGandERecord Print Nos. DC-663231-18, 19 and 20).

3. PGandE Drawings Nos. 437841 and 437845

4. PGandE Drawing No. 437666

5. Technical Specifications Tables 4.3-1 and 4.3-2.

ATTACHMENTS

1. Form 69-9439, Summary/Data Sheet - Trip Actuating Device OperationalTest of Manual Initiation and Blocking of Reactor Protection andEngineer Safeguards. (3/82)

DCOOA8 29III

Page 58: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 59: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

Ee

69-9439 3/82 (20) Sheet 1 of 7PACIFIC GAS AND ELECTRIC COMPAN (

DEPARTMENT OF NUCLEAR PLANT OPERATIONS

DIABLO CANYON POWER PLANT UNIT NOS . 1 AND 2

SUMMARY SHEET - TRIP ACTUATION DEVICE OPERATIONAL TEST OF MANUAL INITIATION &

BLOCKING OF REACTOR PROTECTION & ENGINEERED SAFEGUARDS

UNIT TRAIN MODE

REASON FOR WORK

[ ] Routine Surv. Test

] Channel MalfunctionOther

Applicable Supporting Documents

Prob Rpt. L lf If 3 [ lf 3 [ lf 3 LP3[ 3[ 3L ][ ]Other

BASIC WORK INSTRUCTIONS

YES NO

[3 f3fl Ll18 Month Trip Actuating Device Operational Test

Maintenance Items (Suprvr. to indicate preplanned maintenance items)

By (I.S.)

EVERT DESCRIPTIONHOLD POINTS COMPLETION SIGNOFFS

W RK BY/0 TE INSP/DATE

i

[ 3 [ ] Other:

SUMt'.<RY OF MAJOR FINDINGS

FUNCTIONAL REPAIR/ FUNCTIONELEMENT REPLACE VERIFIED PROBLEM REPORT FILED YES NO

[ 3[ 3[ ] L 3[ 3 f 3[ 3 [P3[ 3[ 3[ ][ ]

REMARKS:

PERFORMED BY

REVIEWED BY/DATE

Ee

TIME/DATE

ACCEPTABLE YES [ 3 NO L 3

Page 60: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

)

Page 61: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

69-9439 3/82 (20) Sheet 2 of 7

SUMMARY SHEET - TRIP ACTUATION DEVICE OPERATIONAL TEST OF MANUAL INITIATION 8

BLOCKING OF REACTOR PROTECTION 5 ENGINEERED SAFEGUARDS

UNIT

STEP

TRAIN

DESCRIPTION

MODE

REMOVAL FROM SERVICE

OPSIKCVERIFIED

l.a.ll.a.2)I.a.3)l.a.4)1.b.1)1.b.2)1.b.3)1.b.4)1.b.5)

STEP

9.a.9.b.9.c.9.d.9.e.9.g.9.h.

9.i.9.j.9.k.9.1.9.m.

9.n.

REMARKS:

C earance No,

Final OK from SFM

Control Operator notifiedM.G. Sets cleared and not running

.Jumper installed (TB507-2 to TB508-4)

MODE SELECTOR in "TEST"

INPUT ERROR INHIBIT to "INHIBIT"

MASTER RELAY SELECTOR to "OFF"

UV COIL VOLTAGE &8VDC

REINSTATEMENT

DESCRIPTION

INPUT ERROR INHIBIT switch in "INHIBIT"

MULTIPLENER TEST switch to "NORMAL"

Logic Test Panel switches set for operationMASTER RELAY SELECTOR is "OFF"

MODE SELECTOR to "OPERATE"

Annunciator status correctMODE SELECTOR "AS LEFT" position

Approval to transfer to "OPERATE': SFM

INPUT ERROR INHIBIT switch to "NORMAL"

Jumper Removed

UV COIL VOLTAGE M VDC

"GENERAL WARNING" lamps "OFF"

SSPS doors closed and locked

Reported OFF and SFM informed of switch status

N A

N A

IhC OPS

N/A

VERIFIED

PERFORMED BY/DATE VERIFIED BY/DATE

Page 62: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 63: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

O

. 69-9439 3/62 (20) Sheet 3 of 7

DATA SHEET - TRIP ACTUATION DEVICE OPERATIONAL TEST OF MANUAL INITIATION 8

BLOCKING OF REACTOR PROTECTION 8 ENGINEERED SAFEGUARDS

STEP

2.a. 2

2.a. 4)2.a. 5)2.a. 6I2.a. 82.a. 10)

2.b. 1 )2.b.2)2.b.3)2. b,4

2.b.6I2 b.7)2.c. 1 )2.c.2)2.c.4)2.c.6)

d.2).d.4)

2. MANUAL REACTOR TRIP

R ATION

52/RT and 52/BY cl osedReactoar orotection Si~gna s annunciator clearNo loss of 48 volts during step 2,a.5).Reactor Protection signals annunciator functionedAnnunciator typewriter readout as specifiedComputer readout as specified52/RT and 52/BY tripped52/RT closed

52/BY closedReactor Protection Signals annunciator clear

-No loss of 48 volts during step 2.b.4).Reactor Protection Signals annunciator functionedAnnunciator typewriter readout as specifiedComputer readout as specified52/RT and 52/BY . trippedJumper removed and loggedUV coil voltage at 48 voltsUV coil voltage at zero voltsUV coil voltage at 48 voltsUV coil voltage at zero, voltsUV coil voltage at 48 volts

VERIFIED

REMARKS:

PERFORMED BY/DATE

Page 64: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

j '

Page 65: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

t~ I

69-9439 3/82 (20) Sheet 4 of 7

DATA SHEET - TRIP ACTUATION DEVICE OPERATIONAL TEST OF MANUAL INITIATION 5B nrK WG OR REACTOR PROTECTION & ENGINEERED SAFEGUARDS

UNIT TRAIN

3. CONTAINMENT ISOLATION PHASE B

STEP

3.a.3)3.a.5)3.a.7)

3.b.3)3.b.4)3.b.5)3.b.73.b.93.b.ll)3.c.2)3.c.3).c.5),.c.9)

3.c.10)

OBSERVATION

+15 volts DC on the 9 specified slave relaysZero volts DC on the 9 specified slave relays.+15 volts DC on the 9 specified slave relays

Zero volts DC on the 7 specified slave relaysZero volts DC on the UV COIL VOLTAGE meter125 volts AC on the 3 specified unlatch coils48 volts DC on the UV COIL VOLTAGE meterZero volts DC on the UV COIL VOLTAGE meter48 volts DC on the UV COIL VOLTAGE meter

Zero volts DC on the UV COIL VOLTAGE meter125 volts AC on the 4 specified unlatch coils48 volts DC on the UV COIL VOLTAGE meter+15 volts DC on the 9 specified slave relaysZero volts AC on the 7 specified slave relays

VERIFIED

REMARKS:

PERFORMED BY/DATE

Page 66: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This
Page 67: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

59-'9439. 3/82 (20) Sheet 5 of 7

DATA SHEET - TRIP ACTUATION DEVICE OPERATIONAL TEST OF MANUAL INITIATION 8BLOCKING OR REACTOR PROTECTION 8 ENGINEERED SAFEGUARDS

STEP

4.a.3)4.a.5)4.a.6)4.a.84.a.9)4.a.lO)4 .b.2)4.c.2)4.c.4)4.c.5)4.c.6)4.c.7)4.c.8)4.c.8)

c.8)c.8

.c.8

(4.a.5)(4.a. 6)4.a.8)4 .a.9)4.a.lO)

4.c.8) (4.b.2)4.c.8) (4.c. 2)4.c.8) (4.c.4)4.c.8) (4.c.5)4.c.8 (4.c.6)4.c.8) (4.c.7)

UNIT TRAIN

4. SAFETY INJECTION

OBSERVATION

+15 volts DC on 19 specified slave relays52/RT and 52/BY closedSa'fety Insection Initiat>on annunciator clearZero volts DC on 19 specified slave relaysSI Initiation annunciator 8 typewriter verifiedComputer readout a's specified+15 volts DC on 2 specified slave relays+15 volts DC on 6 specified relaysComputer readout as specifiedSI Initiation annunciator 8 typewriter verified+15 volts DC on 19 specified relays52/RT and 52/BY tripped52/RT and '52/BY closedSafety~naection Initiat~on annunciator clearZero volts DC on 19 specified slave relaysSI Initiation annunciator 8 typewriter verifiedComputer readout as specified+15 volts DC on 2 specified slave relays+15 volts DC on 6 specified slave relaysComputer readout as specifiedSI Initiation annunciator 5 typewriter verified+15 volts DC on 19 specified slave relays52/RT and 52/BY tripped

VERIFIED

REMARKS:

RFORMED BY/DATE

Page 68: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

l a

0

Page 69: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

.69-9439 3/82 (20) Sheet 6 of 7

DATA SHEET - TRIP ACTUATION DEVICE OPERATIONAL TEST OF MANUAL INITIATION 8

BLOCKING OR REACTOR PROTECTION 5 ENGINEERED SAFEGUARDS

UNIT TRAIN

'TEP

5. CONTAINMENT ISOLATION PHASE A ACTUATE TRAINS A8B

OBSERVATION VERIFIED

5.a.3)5.a.5)5.a.7)5.b.(5.a.5)5.b.(5.a.7)5.c.2)5.d.2)5.d.4)5.d.5)

+15 volts DC on the 8 specified slave relaysZero volts DC on the 8 specified slave relays+15 volts DC on the 8 specified slave relaysZero volts DC on the 8 specified slave relays+15 volts DC on the 8 specified slave relays12S volts AC on the 6 specified slave relays125 volts AC on the 2 specified slave relaysZero volts. AC on the 8 specified slave relaysVoltmeter removed from specified terminals

6.a.2)6.a.3)

.a.4)

.a.6)6.a.7)6.a.8)6.b. (6.a.2)6.b. (6 a.3)6.b. (6 a.4)6.b. (6 a.6)6.b. (6 a.7)6.b. (6- a.8)6 ~ c. (6. a.2)6 .c.(6 a.3)6.c. (6. a.4)6.c. (6. a.6)6.c. 6. a.7)6.c. (5. a.8)

TerminalTerminalTerminalTerminalTerminalTerminal

TerminalTerminalTerminalTerminalTerminalTerminal

TerminalTerminalTerminalTerminalTerminalTerminal

6. RESET BLOCK SWITCHES

voltage at 48 voltsvoltage at zero voltsvoltage at 48 voltsvoltage at zero voltsvoltage at 48 voltsvoltage at zero voltsvoltage at 48 voltsvoltage at zero voltsvoltage at 48 voltsvoltage at zero voltsvoltage at 48 voltsvoltage at zero voltsvoltage at 48 voltsvoltage at zero voltsvoltage at 48 voltsvoltage at zero .voltsvoltage at 48 voltsvoltage at zero volts

REMARKS:

ERFORMED BY/DATE

Page 70: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

J ~

Page 71: Rev 1 to Procedure STP I-16C, 'Surveillance Test Procedure ... · unexpected items, such as breaker contact remains closed, switch replaced, Plant Problem Report filed, etc. This

99>9439 3/82 (20) Sheet 7 of 7

DATA SHEET - TRIP ACTUATION DEVICE OPERATIONAL TEST OF MANUAL INITIATION 8

BLOCKING OR REACTOR PROTECTION 8 ENGINEERED SAFEGUARDS

UNIT TRAIN

'TEP

7.a.2)7.a.3)7.a.47.b.(6.a.2)7.b.(6.a.3)7.b.(6.a.4

7. BLOCK SWITCHES

OBSERVATION

Terminal voltage at 48 voltsTerminal voltage at zero voltsTerminal voltage at 48 voltsTerminal voltage at 48 voltsTerminal voltage at zero voltsTerminal voltage at 48 volts

VERIFIED

STEP

8.d.S.f.S.h.8.i.

.k.

.1

.n.8.o

8. FEEDWATER ISOLATION RESET

OBSERVATION

+15 volts DC on the two specified slave relaysZero volts DC on the two specified slave relays+15 volts DC on the two specified slave relays125 volts AC on the two specified slave relays+15 volts DC on the two specified slave relaysZero volts AC on the two specified slave relaysLogic switches to positions specifiedNegative voltmeter lead removed

VERIFIED

REMARKS:

PERFORMED BY/DATE