WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 1 Preparation for Wholesaler Presentation Select 8 Retrofit A1 Refrigerants 2019 Wholesale Conference Andreas Peselmann Application Engineering

Transcript of Retrofit A1 Refrigerants

Page 1: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 1

Preparation for Wholesaler Presentation Select 8

Retrofit A1 Refrigerants

2019 Wholesale Conference

Andreas Peselmann

Application Engineering

Page 2: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 2

Agenda

• Refrigerants Overview

• Conclusions For Retrofitting

• Retrofitting Existing R404A Systems, Scroll + Semihermetic

• Retrofitting ZB56-11 TW*, ZS56-11 TW*, ZF24-48 TW*

• Retrofitting Existing R134a Systems, Scroll + Semihermetic

Page 3: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 3

Refrigerant Options

R-410A

Like

Capacity

R404A &

R407/22

Like

R134a

Like

GWP Level

400-675

< 1500

~600HFO 1234yf

HFO 1234ze

R410A

R22

R407A

R407C

R407F, R452A

0 500 1000 1500 2000

Cooling Capacity

System Pressure

R32/HFC/HFO

Blends

R32/HFO

Blends

HFC/HFO

BlendsR134a

CO2

R404A

R507A

R290

NH3

A1 – Non Flammable

A2L – Lower Flammable

A3 – Higher Flammable

B2L – Toxic, Mildly Flam.Qualitative Chart –

Not To Scale

(3922)

R32/HFO

Blends R448A/R449A

R450A

R513A

<150 R455A (HDR110)

R454C (DR3)

R32 R452B (DR55)R454B

Page 4: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 4

Refrigerant safety classification, according to ISO 817 .

Refrigerant Classification

Flammability

A3 B3 Higher Flammable

A2 B2 Flammable

A2L B2L Lower Flammable

A1 B1 Non Flammable

ToxicityLow

Toxicity

High

Toxicity

Page 5: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 5

Refrigerant Classification

• refrigerant safety classification per ISO 817

Page 6: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 6

Refrigerant Classification

• overview refrigerant safety

classification EN378-1, Annex E

Page 7: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 7

Legislation and Safety

• system design safety devices and components depend on the refrigerant safety

class, like A1, A2L or A3

• A1 system design, safety and legislation is well known

• A2L and A3 system design have other requirements

- legislation (general, local) must be considered

- specific product norms, like for example EN60335-2-89 might work

- otherwise EN378 comes into place

- impact on system design, components selection, refrigerant filling, safety concept

- ped classification +1 for flammable refrigerants

Page 8: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 8

Refrigerant And System Classification

Conclusions:

• A2L and A3 refrigerants for new systems only. The system and safety architecture

must be adapted to be appropriate for A2L and A3

• systems designed for A1 refrigerant, could only be operated with A1 refrigerants

• retrofit of an existing A1 system with A2L or A3 refrigerant is NOT possible

Page 9: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 9

Retrofit Existing Systems With R404A

Page 10: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 10

Retrofit Existing R404A Systems

Official Emerson released R404A

replacements:

R448A, R449A, R407A, R407F

-> see Select software for compressor

– refrigerant combination

Page 11: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 11

Retrofit Existing R404A Systems, General Guidelines

Technical information for the refrigerant changeover from R404A

to R407A, R407F, R448A or R449A

• for Copeland compressors scroll + semi hermetic

• general advices

• changeover procedure

• pressure and temperature tables

Page 12: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 12

Retrofit Existing R404A Systems, General Guidelines

Technical Information considerations:

• ester oil

• capacity and efficiency values

• discharge temperatures

• MT and LT operation envelopes

• material compatibility (gaskets)

• density and mass flow (piping)

• suction and discharge pressures (adjusting valves)

Page 13: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 13

Retrofit Existing R404A Systems, General Guidelines

Technical information considerations:

• R407A, R407F, R448A and R449A are

blend refrigerants

-> temperature glide to be considered

Example: -10°C evaporating => 2,6 bar,g R448A

for the correct superheat measurement and calculation,

the dew point must be used.

-> eventually new expansion valve

-> expansion valve settings must be adapted

Warning: using the old R404A expansion valve without adapting, could damage the compressor!

Page 14: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 14

Retrofit Existing R404A Systems, Scroll

MT + LT applications scroll.

compressor envelope

-> check for possible restrictions in terms of

suction gas return temperature or

superheat

Page 15: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 15

Retrofit Existing R404A Systems, Scroll

MT + LT applications scroll

Capacity value comparison:

R404A vs replacement refr.

-> Select enables a direct comparison

of both refrigerants

-> replacement refrigerant might have

less cooling capacity

Page 16: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 16

Retrofit Existing R404A Systems, Scroll

MT applications scroll.

Envelope comparison: R404A vs replacement

refrigerant

-> Select enables a direct comparison of the possible

operation envelope

-> for MT applications usually the envelope of the

R404A replacement refrigerant fits quite good!

Page 17: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 17

Retrofit Existing R404A Systems, Scroll

LT applications scroll with liquid injection

Envelope comparison: R404A vs replacement

refrigerant

-> due to liquid injection technology, mostly the

envelope fits quite good!

Page 18: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 18

Retrofit Existing R404A Systems, Scroll

LT applications scroll with vapour injection

Envelope comparison: R404A vs replacement

refrigerant

-> care must be taken for the pure EVI envelope

-> operating area with wet injection required

Page 19: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 19

Retrofit Existing R404A Systems, Semih.

MT applications semihermetic.

Envelope comparison: R404A vs replacement

refrigerant

-> Select enables a direct comparison of the possible

operation envelope

-> for MT applications usually the envelope of the

R404A replacement refrigerant fits quite good!

Page 20: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 20

Retrofit Existing R404A Systems, Semiherm.

LT applications semihermetic

Envelope comparison: R404A vs replacement

refrigerant

-> compare envelope with/without liquid injection

Demand Cooling DC

Page 21: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 21

New Service BOM 951

ZB56-11KE/ME, ZS56-11KE/ME, ZF24-48K4E/KVE

Retrofit Options

Page 22: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 22

New Service BOM951 ZB56-11KE/ME, ZS56KE/ME, ZF24-48K4E/KVE TW*

Old „Specter“ compressor families still remain in

production, but now sold with service BOM 951

Page 23: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 23

ZB56-11KE/ME, ZS56KE/ME, ZF24-48K4E/KVE TW*

• Compressor series for service

purposes only

• Technical data still available under

„previous generation“

• Old data shown for R404A, R22,

R134a...

• No new refrigerant qualification, such

as R448A/R449A, R407A, R407F.

-> no technical data in Select

Page 24: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 24

ZB56-11KE/ME, ZS56KE/ME, ZF24-48K4E/KVE TW*

• Estimation of capacity values,

application envelopes possible with

comparison to newer model range,

see Select software:

- select old compressor and new

compressor family based on R404A

- select similar/comparable

displacement

Page 25: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 25

ZB56-11KE/ME, ZS56KE/ME, ZF24-48K4E/KVE TW*

• Estimation of capacity values,

application envelopes possible with

comparison to newer model range,

see Select software:

- use new compressor family/model

as baseline for new refrigerant

calculation

Page 26: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 26

ZB56-11KE/ME, ZS56KE/ME, ZF24-48K4E/KVE TW*

• estimation of capacity values,

application envelopes possible with

comparison to newer model range,

see Select software:

- use new compressor family/model

envelope for estimation of possible

operation range

Page 27: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 27

ZF24-48 K4E TWD with liquid injection

ZF24-48 K4E TWD Specter family compressors with liquid injection

• Technical Information for the conversion of existing R404A systems

with capillary tube towards DTC valve liquid injection available

Page 28: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 28

Retrofit Existing R404A Systems, Semihermetic

Old „previous generation“ compressor families, new technical data

• Compressor model families, which have been identified as phase-out

or obsoleted products have not been qualified for new refrigerants, such

as R448A, R449A ect.

Examples: DWM Models D2S*, D3S*, D4S*, D6S* D8S*, D4D*, D6D*, D6T*

• Consequently, there are no technical data in Select available.

• Theoretical calculated data for specified operation points could be provided on request

• Valuation of the possible operation envelope: comparison with released Stream models

Example:

MT Old: D4DH 250X (70,8 m³/h) 4MH 25X (71,4 m³/h)

LT Old: D4DL 150X (70,8 m³/h) 4ML 15X (71,4 m³/h)

Page 29: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 29

Retrofit Existing Systems With R134a

Page 30: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 30

Retrofit Existing R134a Systems

Official Emerson released R134a replacements:

R450A, R513A

• R450A (N13), A1 safety class, GWP 605

composition R134a (42%), R1234ze (58%)

• R513A (XP10), A1 safety class, GWP 631

composition R134a (44%), R1234yf (56%)

Page 31: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 31

Retrofit Existing R134a Systems

R450A, R513A qualification

• refrigerant migration of liquid R450A/R513A

into the compressor crankcase could cause

low oil viscosity and compressor damage.

When using R450A and R513A with the

standard compressor versions, it is critical to

meet some application requirements.

For new systems/applications with R513A/R450A:

Emerson offers a new compressor family

ZR24-92 KRE + ZRD36-92 KRE

launch planned for Q1 2019

Page 32: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 32

Retrofit Existing R134a Systems

R450A, R513A retrofit scrolls in the field

Dedicated application recommendations:

• maintain adequate superheat settings

with a minimum superheat of 8-10K

• no liquid refrigerant migration into the compressor at any time, especially during standstill, during

or after defrost, or after reverse mode for example in heat pumps

• pumpdown is recommended

• the use of a crankcase heater is mandatory;

• for R450A and R513A refrigerants Emerson recommends to use suction accumulators, unless it

has been qualified that an accumulator is not needed (procedure described in the Application

Guidelines).

Page 33: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 33

Retrofit Existing R134a Systems, General Guidelines

Technical information for the refrigerant changeover from R134a

to R450A + R513A

• for Copeland compressors scroll + semi hermetic

• general advices

• changeover procedure

• pressure and temperature tables

Page 34: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 34

Retrofit Existing R134a Systems, General Guidelines

Technical Information considerations:

• ester oil

• capacity and efficiency values

• discharge temperatures

• MT and LT operation envelopes

• material compatibility (gaskets)

• density and mass flow (piping)

• suction and discharge pressures (adjusting valves)

Page 35: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 35

Retrofit Existing R134a Systems, Scroll

compressor envelopes R134a, R450A, R513A

-> compressor ebvelopes are quite comparable

Page 36: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 36

Retrofit Existing R134a Systems, Scroll

Capacity value comparison:

-> Select enables a direct

comparison between all three

refrigerants

Page 37: Retrofit A1 Refrigerants

WHS Workshop 2019, Retrofit A1 Refrigerants, Slide 37

Retrofit Existing R134a Systems, Semih.

compressor envelopes R134a, R450A, R513A

-> compressor envelopes are quite comparable