RESTRICTED - Ncsarena.com.ng...RESTRICTED - Ncsarena.com.ng ... RESTRICTED
Restricted Earth Fault Protections
-
Upload
fatima-mir -
Category
Documents
-
view
217 -
download
0
Transcript of Restricted Earth Fault Protections
![Page 1: Restricted Earth Fault Protections](https://reader036.fdocuments.us/reader036/viewer/2022081810/577cd8d01a28ab9e78a20b85/html5/thumbnails/1.jpg)
7/29/2019 Restricted Earth Fault Protections
http://slidepdf.com/reader/full/restricted-earth-fault-protections 1/6
9/12/13 Restricted Earth Fault Protection
1/6myelectrical.com/notes/entryid/150/restricted-earth-fault-protection
YOU ARE HERE: Notes
Restricted Earth Fault Operation
ANSI Designat ion
Often 87N or 64REF are used to
denote restricted earth fault
protection. The intent is that both
mean the same thing.
Which is the correct or better to
use may be open to interpretation.
To me, 87N is more appropriate as
REF is a differential type protection
(ANSI 87 – differential protection
relay). I think 64 is strictly more
relevant to detecting earth/ground
faults due to breakdown of
insulation.
This was a question asked below
(in the discussion). If anyone has
any views, please join that thread.
Filed in [Power Systems] By Steven on March 25 th, 2012
Restricted Earth Fault Protection
The windings of many medium and small sized transformers are protected by restricted earth fault
(REF) systems. The illustration shows the principal of REF protection.
Basic Operation
Under normal conditions and by application of
Kirchhoff’s laws the sum of currents in both
current transformers (CTs) equals zero. If there is
an earth fault between the CTs then some current
will bypass the CT's and the sum of currents will
not be zero. By measuring this current imbalance
faults between the CTs can be easily identified
and quickly cleared.
Fault detection is confined to the zone between
the two CTs hence the name 'Restricted Earth
Fault'.
REF protection is fast and can isolate winding
faults extremely quickly, thereby limiting damage
and consequent repair costs. If CTs are located
on the transformer terminals only the winding is
protected. However, quite often the secondary CT
is placed in the distribution switchboard, thereby
extending the protection zone to include the main
cable.
Without REF, faults in the transformer star secondary winding need to be detected on the primary
of the transformer by the reflected current. As the winding fault position moves towards the
neutral, the magnitude of the current seen on the primary rapidly decreases and could potentially
not be detected (limiting the amount of winding which can be protected). As the magnitude of the
currents remain relatively large on the secondary (particularly if solidly earthed), nearly the entire
winding can be protected using REF.
It should be remembered that the protection as
illustrated covers only the secondary of the transformer.Sometimes REF protection is added to the primary as
well (although if primary protection is required I would
prefer to consider full differential protection).
As it is essential that the current in the CTs be balanced
during normal conditions (and through faults),
historically REF has been implemented using High
Impedance Relays. CT's have also been specified as
matched pairs and the impedance of leads/wires and
interconnecting cables has had a large influence on the
functioning of the relay. Measurement errors associated
with these issues have been responsible for nuisance
tripping and the system can be difficult to commission.
This may be the reason some people avoid the use of
REF. Recent advances in numerical relay technologyhave all but eliminated these issues, making the
implementation of REF relatively easy, ensuring no
nuisance tripping and simplifying commissioning.
In the diagram 87N is the ANSI Device Number for
restricted earth fault.
Latest Questions:
1. Meaning of "mult.symb" in motor
specifications
2. Recloser
3. Voltage Reduction and Energy Saving
4. Unbalanced Three Phase Load
5. PMAC machine in regenerative braking
mode6. LCI starting
7. Motor Voltage Drop at Starting time
8. Surge Suppressor
more questions...
Most Popular Notes:
Three Phase Current - Simple
Calculation
Switchboard - Forms of Internal
Separation
Motor Starting - Star Delta
Network Theory – Introduction andReview
Standard Cable & Wire Sizes
Restricted Earth Fault Protection
Motor Starting - Direct On Line
Motor Starting - Auto-Transformer
more notes...
Register Login
Home Notes Questions Tools Community News
Our website uses cookies so that we
can provide a better experience.
ContinueContinueContinue
To learn more about what cookies are andhow to manage them visit AboutCookies.org
![Page 2: Restricted Earth Fault Protections](https://reader036.fdocuments.us/reader036/viewer/2022081810/577cd8d01a28ab9e78a20b85/html5/thumbnails/2.jpg)
7/29/2019 Restricted Earth Fault Protections
http://slidepdf.com/reader/full/restricted-earth-fault-protections 2/6
9/12/13 Restricted Earth Fault Protection
2/6myelectrical.com/notes/entryid/150/restricted-earth-fault-protection
► Electrical ► Protection ► Transformer ► Relay
Comments
You need to log in to comment.
Your Email:
We respect y our email privacy
Raman says:
7/27/2012 12:14 PM
Thank you. You have explained it in simple terms. Can you also Please clarify the following :
For a radial transformer feeder provided with REF protection on LV side, does the operation of
REF relay be wired to trip the primary HV side or secondary LV side Breaker?
For parallel operation system, does operation of REF be connected to trip both primary and
secondary Breakers.?
It would be great if the breaker linkage is shown as part of the schematic.
Can you please clarify?
Thanks
Steven says:
7/27/2012 2:52 PM
REF is a fault in the winding and you need to isolate the transformer - trip the MV/HV side.
The REF is unit protection and restricted to one transformer. If you have two in parallel you
could isolate only the faulty transformer. Just make sure the other transformer can support
the full load.
I don't have access to my normal computer at the moment, but as soon as I do I will look at
updating the schematic.
Steven says:
1/26/2013 5:28 AM
Ugly's
Electrical
References,
2011Edition
$12.05
Black &
Decker The
Complete
Guide to ...$17.48
Hawkins
Electrical
Guide,
Number One ...
![Page 3: Restricted Earth Fault Protections](https://reader036.fdocuments.us/reader036/viewer/2022081810/577cd8d01a28ab9e78a20b85/html5/thumbnails/3.jpg)
7/29/2019 Restricted Earth Fault Protections
http://slidepdf.com/reader/full/restricted-earth-fault-protections 3/6
9/12/13 Restricted Earth Fault Protection
3/6myelectrical.com/notes/entryid/150/restricted-earth-fault-protection
Image now updated.
LYH says:
8/21/2012 2:10 AM
Further question: Is REF protection should be implemented on a small 6/0.4kV, 500kVA oil type
transformer?
Steven says:
8/24/2012 7:25 AM
There is a cost to REF and at some stage it becomes expensive in relation to the
transformer size. At 500 kVA, I would tend to think the cost may not be justified (unless the
transformer were particularly important).
It would be interesting if other site users have opinion on this and can add to the
discussion.
waji says:
9/26/2012 6:42 AM
Can you please explain how a transformer can detect an earth fault by using using phase CTs?
rajadurai says:
10/19/2012 11:33 AM
What class of cts used for REF and SEF protection of transformers
Amit says:
10/23/2012 4:52 AM
For REF protection, PS class CT are used for high accurecy and for SEF 5P10 type CTs
are used.
vishal says:
12/22/2012 6:25 AM
I want to just ask that how we can restrict the earth fault detection of a Particular Critical System
let us consider an alternator and what is the Logic Behind that?what are the things to keep in
mind and what is the difference between Overcurrent Earth Fault and REF ?How the CTs are
arranged in Differential Protection what is the logic behind the arrangement .
Daniel says:
1/5/2013 2:29 AM
Hi,
Is it a MUST that the knee point voltage, Vkp and excitation current, Imag of the Neutral CT and
phase CT to be the same?
if Vkp and Imag of both CT not the same, what will be the consequences on the Bias Differential
and REF protection?
Anybody can advise me on these? Thanks
![Page 4: Restricted Earth Fault Protections](https://reader036.fdocuments.us/reader036/viewer/2022081810/577cd8d01a28ab9e78a20b85/html5/thumbnails/4.jpg)
7/29/2019 Restricted Earth Fault Protections
http://slidepdf.com/reader/full/restricted-earth-fault-protections 4/6
9/12/13 Restricted Earth Fault Protection
4/6myelectrical.com/notes/entryid/150/restricted-earth-fault-protection
black mamba says:
4/4/2013 2:45 PM
what's the difference between ANSI 87N and ANSI 64REF?
Is the polarity of connection samefor both protection schemes?
Steven says:
4/7/2013 12:27 AM
I think the intent is that both mean the same thing. Which is the correct or better to use
may be open to interpretation.
To me, 87N is more appropriate as REF is a differential type protection (ANSI 87 –
differential protection relay). I think 64 is strictly more relevant to detecting earth/ground
faults due to breakdown of insulation.
Skara says:
5/21/2013 4:03 PM
goodday gents,
kindly please assaist with what is the difference between high impendance REF and low
impedance REF
Steven says:
5/22/2013 5:37 AM
The primary difference is in the type of relay used. High impedance relays have a high
input impedance and draw very little current under normal conditions. Low impedance
relays are the opposite.
There is a lot of debate on which to use and some theory. My view is that low impedance is
preferred. It's simpler, there is more flexibility in the CTs and inputs and coupled with all the
functions of a modern numerical relay it eliminates a lot of problems that exist in high
impedance systems.
There is also a technical comparison on the two types here which should help you:
https://www.selinc.com/WorkArea/DownloadAsset.aspx?id=5562
Freddie says:
5/30/2013 8:57 AM
What can cause 64REF to trip off a transformer during disturbances from the grid
Steven says:
6/2/2013 4:37 AM
It could be many things.
A common reason could be unbalanced/incorrectly selected CTs causing false residual
current and nuisance tripping. Similarly, if your CTs are becoming saturated they canbecome unbalanced and give problems.
You should also make sure that the CT ratios, phase shift, logic, etc. are programmed
correctly in to the relay and that your polarities/wiring are fine.
![Page 5: Restricted Earth Fault Protections](https://reader036.fdocuments.us/reader036/viewer/2022081810/577cd8d01a28ab9e78a20b85/html5/thumbnails/5.jpg)
7/29/2019 Restricted Earth Fault Protections
http://slidepdf.com/reader/full/restricted-earth-fault-protections 5/6
9/12/13 Restricted Earth Fault Protection
5/6myelectrical.com/notes/entryid/150/restricted-earth-fault-protection
Popular Tags
View All Tags
Have someknowledge toshare
If you have some expert
knowledge or experience,
why not consider sharing this with our
community.
By writing an electrical note, you will be
educating our users and at the same
time promoting your expertise within the
engineering community.
To get started and understand our
policy, you can read our How to Write an
.
circuits/issues logically until you can narrow it down. If you are also able to get a recording
of the voltages and currents during an incident this will help you a lot.
SYAM says:
9/3/2013 12:23 PM
Hi Steven,
"As the winding fault position moves towards the neutral, the magnitude of the current seen on
the primary rapidly decreases and could potentially not be detected (limiting the amount of
winding which can be protected)".
Can you please explain why..?
I have a few queries also (it may sound stupid).
Query 1. I am bit confused between the operation of REF and Standby earth fault relay. Can
you help me in understanding with some diagrams or any links to refer.?
Query 2. In our area we use separate CTs for REF and SEF+ OC protection. i.e 4 or 5 nos PS
class CTs (3 in Phases 2 in Neutral) along with 4 no 5P10 class CT ( 3 in Phases 1 in Neutral
for SEF+OC. We use separate relays for REF, SEF, & OC For SEF we use Induction (disc type)
relay. My query is that is it possible to use only one type of (PS Class) CT for all the
protections..? Is it possible to use a single relay(if the relay is capable of) to incorporate all the
protections.?
Query 3.Can I use Class PS CT for OC or SEF protection or for metering purpose.?
Query 4. When a fault occurs between one phase and the ground will the fault current travel
back from the ground through the neutral to the fault point..? (using the concept that current
flows only in a closed circuit)
For faults outside the Zone SEF will operate, REF will not operate.
For Faults inside the Zone the REF will operate When an earth fault happens inside the zonewill the CT provided for SEF sense the fault current. (i mean when a current flows in the primary
(neutral) a proportional current in the secondary)?
Please clarify my doubts.It may sound silly or stupid but I would like to know why and how.
Thanks in advance
Regards
SYAM
Automation Batteries Buildings Cables
Control Systems Education Electronics
Energy Equipment Equipment Data
Equipment Ratings Equipmen t Sizing
Fundamentals History IEC Standards
Motor Control Motor Starting MotorsmyElectrical Off-Topic
Power Systems Protection
Protective Devices Scientists Standards
Switchboards Testing Theory Voltage
Writing
![Page 6: Restricted Earth Fault Protections](https://reader036.fdocuments.us/reader036/viewer/2022081810/577cd8d01a28ab9e78a20b85/html5/thumbnails/6.jpg)
7/29/2019 Restricted Earth Fault Protections
http://slidepdf.com/reader/full/restricted-earth-fault-protections 6/6
9/12/13 Restricted Earth Fault Protection
6/6myelectrical.com/notes/entryid/150/restricted-earth-fault-protection
Terms Of UsePrivacy Statement AdvertiseContact UsCopyright (c) 2013 myElectrical
Click here to view the notes list in a
table format
Click here to view the notes indexed
by tag
Electrical Note.