REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION OF PROPOSED 33/11 KV SUB STATION AT JAUN SAMANA, MARIPAT, GREATER NOIDA IN UTTAR PRADESH CLIENT M/S NOIDA POWER COMPANY LTD. GREATER NOIDA FEBRUARY-2018 PREPARED BY SANGUINE CONSULTANTS RZ-456/13, TUGLAKABAD EXTENSION NEW DELHI-110019. PH:26052881, 9810166713.

Transcript of REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater...

Page 1: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater

REPORT ON

SOIL INVESTIGATION FOR CONSTRUCTION OF PROPOSED

33/11 KV SUB STATION AT

JAUN SAMANA, MARIPAT, GREATER NOIDA IN UTTAR PRADESH

CLIENT

M/S NOIDA POWER COMPANY LTD. GREATER NOIDA

FEBRUARY-2018

PREPARED BY

SANGUINE CONSULTANTS RZ-456/13, TUGLAKABAD EXTENSION

NEW DELHI-110019. PH:26052881, 9810166713.

Page 2: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater

LIST OF CONTENTS

SL.NO. PARTICULARS PAGE NO.

1. INTRODUCTION 01 2. SCOPE OF WORK 02

3. FIELD INVESTIGATION METHODOLOGY 04 4. LABORATORY TESTING 05 5. LITHOLOGY 06 6. FOUNDATION ANALYSIS 06 & DISCUSSIONS 7. CONCLUSIONS & RECOMMENDATIONS 10 8. LAB.TEST RESULTS 11

(TABLE-01 TO TABLE-02) 9. ERT DATA 13

(TABLE-03 TO TABLE-04) 10. SIEVE ANALYSIS CURVE 15 (FIG.- 01 TO FIG.-02) 11. SHEAR CURVES 17

(FIG.-03 TO FIG-04)

12. SITE PLAN 19 (FIG.-05 )

Page 3: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater

1.0 INTRODUCTION

M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV

Sub-station at Jaun Samana, Maripat, Greater Noida in Uttar

Pradesh. For a detailed design & engineering of proposed tower,

the work of sub-soil investigation has been awarded to M/s

Sanguine Consultants, New Delhi.

The report presents the compiled data of test results of geotechnical

investigation. The observed data of field investigations and

laboratory tests are presented and uses to access the nature of

subsoil strata and to evaluate the soil parameters required for the

detailed design and engineering of proposed structure.

THE SITE

The site is located at Jaun Samana, Maripat, Greater Noida in

Uttar Pradesh. The site is developed, leveled and drained. The

informations & recommendations are given with respect to existing

ground level at particular points rather than the reference level.

Page 4: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater

2. SCOPE OF WORK

In order to establish the sub-soil characteristics of the area marked

for construction of proposed sub-station, the entire investigation

programme has been divided into field and laboratory tests leading

to preparation of comprehensive report on the recommendations for

foundation types and the corresponding design bearing capacity

values for the foundations of proposed structure at the site.

As mentioned within the framework of this job contract, the field

investigations comprised of the following :-

a) Boring of two (02) boreholes of 150mm dia. up to the

depth of 10m or refusal whichever encountered earlier.

b) Collection of representative disturbed and undisturbed soil

samples, 100mm in diameter, from the exploratory bore

holes for detailed laboratory analysis.

c) Carrying out standard penetration tests as per IS:2131 –

1981 in each bore hole and subsequently preparation of

penetration charts depth-wise for each bore hole.

d) Conducting two (02) no. of Electrical Resistivity Tests at

site as per marked in drawing.

Page 5: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater

The laboratory tests part of this job contract comprised of the

following:-

i) Grain size analysis

a) Sieve analysis

b) Hydrometer analysis

ii) Liquid limit & plastic limit.

iii) Specific gravity

iv) Natural moisture content

v) Bulk density & dry density

vi) Direct shear tests on granular soil samples

vii) Unconsolidated undrained triaxial shear test

viii) Consolidation test

Page 6: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater

3.0 FIELD INVESTIGATION METHODOLOGY 3.1 DRILLING OF BOREHOLE

Boreholes of 150mm diameter has been conducted by using shell

and auger method up to the depth of 10.0m as per IS:1892 at

proposed site location. The details of the soil type, type of sample

collected and SPT ‘N’-value are shown in Table-01 to Table-02.

3.2 COLLECTION OF UNDISTURBED SOIL SAMPLES

Undisturbed soil samples have been collected at 1.50m/3.0m

interval in thin wall sampling tubes of 45cm long with area ratio

less than of 10%. All undisturbed soil samples were collected by

open drive tube sampler as per IS:2132 and the tube so recovered

with samples, after removal of loose disturbed soil, were sealed by

wax from both end to protect against the loss of moisture. After

sealing, the sampling tubes were marked for testing of sample for

various parameters.

3.3 STANDARD PENETRATION TEST

Standard Penetration tests have been conducted as per IS:2131 in

the borehole at interval of 1.50m or at the change of strata,

wchichever encountered earlier. The penetration resistance (SPT)

is expressed as number of blows required for 30 cm. on a rigid steel

head and standard “A” rod attachment. The bottom of borehole

have been cleaned before commencement of test. Also seating

number of blows of 150mm were recorded before recording actual

SPT ‘N’ for 30 cm penetration. On removal of sampler, the soil

entrapped in the sampler is taken out and the representative

disturbed soil sample is preserved in polythene bags to avoid any

loss of fines and marked for identification.

Page 7: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater

4.0 LABORATORY TESTING

1. The laboratory test was carried out after all the samples have

reached the .

2. All samples brought from field, whether disturbed or

undisturbed was extracted/prepared and examined by

competent technical personnel, and the test was carried out

as per the procedures laid out in the latest edition of the

relevant I.S. Codes.

The following laboratory test has been carried out

i) Grain size analysis

a) Sieve analysis

b) Hydrometer analysis

ii) Liquid limit & plastic limit.

iii) Specific gravity

iv) Natural moisture content

v) Natural density

vi) Drained direct shear test.

vii) Unconsolidated undrained triaxial shear test

All the above tests were conducted as per the provisions laid down

in the relevant IS Code of practice. The test results for all the

samples tested have been tabulated in proper format as shown in

Table No.01 to Table-02.

Page 8: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater

5.0 LITHOLOGY

Two boreholes drilled down to a depth of 10.0m reveals that the

entirqe stratum consists of two Lithounits (layers), namely

Lithounit-X and Lithounit-Y.

LITHOUNIT-X

Lithounit-X is light brown sandy silt with gravels starting from

G.L. to 2.5m/2.50m depth of boreholes. Soil classification shows

that this lithounit is low-plastic of CL in nature. Standard

penetration test conducted in the boreholes indicate that the strata is

stiff to very stiff in nature. Specific gravity of soil particles is found

from 2.66 to 2.67.

LITHOUNIT-Y

Lithounit-Y is light brown silty sand starting from 2.0m/2.50m to

the depth of boreholes. Soil classification shows that this lithounit is

non-plastic of SM in nature. Standard penetration test conducted in

the boreholes indicate that the strata is medium dense in nature.

Specific gravity of soil particles is found from 2.62 to 2.63..

6.0 FOUNDATION ANALYSIS AND DISCUSSIONS Two boreholes drilled down to a depth of 10.0m and disturbed/

undisturbed soil samples have been collected for laboratory testing.

Standard Penetration Tests have been carried out as per I.S.

standard. On the field investigation data, it is found that soil is stiff

to very stiff to medium dense in nature. Open foundation is

suggested.

Page 9: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater

6.1 GENERAL

A suitable foundation for any structure should satisfy two basic

criteria. Firstly, the soils should have adequate shear strength to

support the superimposed loads so that there is an adequate safety

factors against the bearing capacity. Secondly, the settlement of the

soils including immediate elastic settlement and long terms

consolidations settlement should be within the tolerable limits for

the structure. The net allowable bearing pressure on the foundations

should be taken as the lower of the two values obtained from these

two criteria.

6.2 FOUNDATIONS TYPE

In general, light to medium loaded structure may bear an open

shallow footings. Heavily loaded structure may bear on raft

foundation.

6.3 OPEN FOUNDATION

Isolated/Raft foundation are feasible foundation schemes. Bearing

capacity analysis for the shallow foundation is in accordance with

IS 6403-1981. Considering the presence of water level at 8.0m

depth, a water table correction factor has been taken into account. A

safety factor of 2.50 has been considered in the analysis as per IS

1904. Settlement analysis has been performed in accordance with

IS:8009 part I. For computation of foundation settlement in average

lower bound corrected N value has been used. A tolerable total

settlement of 50mm and 75mm for Isolated and Raft foundation has

been considered as per IS:1904.

Page 10: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater

6.3.1 SHEAR CONSIDERATION

As per IS:6403 –1981,the net ultimate bearing capacity can be

calculated as:

qu = 2/3CNc1 Scdc ic+ q (Nq1 –1) Sq dq iq + 0.5 Br Nr1 Sr dr ir W1

At 1.50m depth

C = 5.50T/M2, φ = 6o, φ1 = 4o, Nc1 = 6.22, Nq1 = 1.456, Nr1 = 0.36,

r = 1.72 T/M3, Sc=1.3, Sq=1.2, Sr=0.8, w=0.5, FOS = 2.5.

Qu = 2/3x5.50x6.22x1.3 + 1.72x1.5x0.456x1.2 + 0.5Bx1.72x0.36x0.8x0.5

= 31.06 + 0.124 B

for 1mx1m - qa = 12.47 T/M2

2mx2m - qa = 12.52 T/M2

3mx3m - qa = 12.57 T/M2

6mx6m - qa = 12.72 T/M2

At. 2.0m. Depth

Qu =31.53 + 0.124 B

for 1mx1m - qa = 12.66 T/M2

2mx2m - qa = 12.71 T/M2

3mx3m - qa = 12.76 T/M2

6mx6m - qa = 12.91 T/M2

Page 11: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater

6.3.2 SETTLEMENT CONSIDERATION

Net safe bearing capacity on settlement criteria is calculated as per

IS: 8009(PART-1) –1976. A tolerable total settlement of 50mm and

75mm for Isolated and Raft foundation has been considered as per

IS:1904.

At 1.50m Depth for size 2mx2m

Average corrected N value below base of footing = 15

Settlement from the Fig.9 of IS:8009 (Part-I)-1976 = 20mm under

net pressure intensity of 10 T/M2

Therefore, for a specified permissible settlement of 50mm, the net

safe bearing capacity = (10 x 50) /(20 x 2 ) = 12.50 T/M2.

At 2.0m Depth for size 2mx2m

Average corrected N value below base of footing = 16

Settlement from the Fig.9 of IS:8009 (Part-I)-1976 = 18 mm under

net pressure intensity of 10 T/M2.

Therefore, for a specified permissible settlement of 50mm, the net

safe bearing capacity = (10 x 50) /(18 x 2 ) = 13.89 T/M2.

Page 12: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater

7.0 CONCLUSIONS AND RECOMMENDATIONS

Based on field and laboratory investigations, following

recommendations can be made:

1. As per field data & lab. Results, the entire stratum consists of

two Lithounits (layers). Detail is shown in article 5.0.

2. Based upon SPT value & density, the soil strata is found stiff to

very stiff to medium dense in nature.

3. It is suggested that the net allowable bearing capacity for

Isolated footings may be taken as the table given below : NET ALLOWABLE BEARING CAPACITY IN T/M2

Depth (m)

from EGL

1Mx1M 2Mx2M 3Mx3M

1.50 m 10.00 10.00 10.00

2.00 m 11.00 11.00 11.00

4. Raft foundation may be designed as net allowable bearing

capacity of 11.0 T/M2 and 12.0 T/M2 at 1.50m and 2.0m depth

from EGL respectively.

5. Water level was encountered at 8.0m depth during the field

investigation which may rise/fall with climatic condition.

6. For resistivity of soil, refer Table-03 to Table-04.

For SANGUINE CONSULTANTS M.K.SINGH. (M.E., Geotech)

Page 13: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater
Page 14: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater
Page 15: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater
Page 16: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater
Page 17: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater
Page 18: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater
Page 19: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater
Page 20: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater
Page 21: REPORT ON SOIL INVESTIGATION FOR CONSTRUCTION ... Test...1.0 INTRODUCTION M/s N.P.C.L., Greater Noida is planning to costruct 33/11 KV Sub-station at Jaun Samana, Maripat, Greater