    GMK

    OSM AUTOMATIC

    CIRCUIT RECLOSER

    15kV 27kV & 38kV MOdELS

    GROUND MOUNT KIOSK

    PRODUCT GUIDE

  • 7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure

    2/8

    Introduction

    Cable Entry, Main Earth Bar & High VoltageTerminations

    1. Earth Switch Viewing Window

    2. Cable Termination

    3. Main Earth Bar

    4. Gland Plate

    The GMK Ground Mount Kiosk is designed for the

    connection and protection of underground cables

    for voltage classes up to 38kV.

    The kiosk houses an OSM automatic circuit

    recloser, an RC controller, an interlocked isolation

    and earthing mechanism and cable connection

    compartment.

    The OSM automatic circuit recloser has been

    extensively type tested by independent laboratories

    to ensure long life and reliability under the harshest

    environmental conditions. It is the only solid di-electric insulated recloser to provide controlled

    arc fault venting and independent testing provides

    verification of this important safety feature.

    The RC controller provides all the protection, data

    logging and communications functions. An operator

    panel is used to operate the device locally.

    A two phase VT located in the main compartment

    provides low voltage AC auxiliary supply to the RC

    controller.

    A manual trip mechanism is located above the

    RC controller, and is used to manually open and

    isolate the OSM. The mechanism is then rotated

    using a lever to connect earth switches to the

    Load side of the OSM.

    Underground cables enter the kiosk through a

    metal plate provided in the base of the cable

    GMK Ground Mount Kiosk

    INTRODUCTION

    connection compartment. Six DIN 400 or ANSI

    Taper aromatic epoxy bushings are provided to

    terminate the cables onto the Load and Source

    side of the OSM automatic circuit recloser. An

    earth bar is also located in this compartment for

    earth bond connections.

    1. Product Guide GMK Ground Mount Kiosk

  • 7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure

    3/8

    Introduction 1.2.

    The OSM automatic circuit reclosers incorporatevacuum interrupters insie a soli ielectricpolymer housing enclose insie an arc ventestainless steel tan. This ensures the maximum inlife an reliability with a fully insulate arrangementinsie the long life housing.

    Voltage is measure on all six (6) bushings usingcapacitively couple screens. Current is measureon all three (3) phases using current transformers.

    The recloser mechanism is operate by three (3)

    separate magnetic actuators, one per phase. Thesemagnetic actuators are mechanically interloceto guarantee correct three (3) phase operation.The evice is latche in the close position bymagnetic latching. Each magnetic actuator usesa single coil.

    The open an close position of the evice isinicate by a green 0 to inicate the evice isopen an a re I to inicate the evice is close,this can be viewe through the winow next to thecontrol cubicle.

    The status of the recloser is also reflecte by amicroswitch connecte to the control electronics.The electronic circuit boar where the microswitchis fitte has no active elements which ramaticallyimproves impulse immunity.

    The main circuit bushings are manufacture fromUV stable polymer an have a silicone rubber

    OVERVIEW

    bushing boot to provie the require creepageistance.

    The magnetic actuators are operate from storeenergy charge capacitors locate in the RCcontrol cubicle. There is a rating plate locatein the base of the tan that provies tan ratingetails in accorance with the requirements ofANSI C37.60.

    The cross sectional iagram below etails theOSM tan configuration an main components.

    1. Bushing Connector2. Silicone Rubber Bushing Boot3. Polymer Bushing4. Current Transformers5. Capacitively Couple Voltage Sensor6. Stainless Steel Tan7. Magnetic Actuator8. Opening Spring9. Auxiliary Switches10. Insulate drive Ro11 . Polycarbonate Housing

    12. Vacuum Interrupter13. Ceramic Breather14. Mechanical trip Ring

    Product Guide GMk Groun Mount kios

    OSM Automatic Circuit Recloser

  • 7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure

    4/8

    Introduction

    The RC10 control an communications cubicle isa microprocessor base controller that provies airectional overcurrent, earth fault an sensitiveearth fault relay, auto reclosing relay, instantaneousmetering, event log, eman logger an remoteterminal unit (RTU) for remote control in a singlepacage.

    The operator control panel is provie with a largebaclit LCd isplay an eypa to provie localcontrol functions.

    The control cubicle has three (3) main moules:

    The operator panel moule which proviesthe man machine interface.

    The Switchgear Interface Moule (SIM) whichprovies the power supply battery chargeran incorporates the capacitors that proviethe tripping an closing energy to the OSMtan.

    The Relay moule which provies the mainmicroprocessor an dSP functionality.

    Temperature compensate float charging is

    provie to the seale lea aci batteries locatein the RC10 control cubicle.

    There is space provie insie the control cubicleto install any communications equipment to beconnecte to the inbuilt RTU or I/O moule.

    The equipment has been esigne for the RC10control cubicle to operate over a temperature rangeof -40 to +55C insie the IP65 seale enclosure.

    The cubicle is constructe out of power coatestainless steel for a long, maintenance free lifetime.The roof features a ceramic base insulating

    RC10 CONTROL &

    COMMUNICATIONS CUBICLE

    coating that provies a 16C reuction in internaltemperature when the cubicle is expose to 1.1Wof solar raiation.

    The entry point for the control cable is housewithin a vanal-proof enclosure an the cubicleoor has a three point hanle locing mechanismmaing it extremely ifficult to brea into.

    Control an Communications Cubicle

    3. Product Guide GMk Groun Mount kios

    Trip/Close Auxiliaryswitches

    3 Phase HV Line CVT CVT

    PhaseVacuum

    OSM

    Recloser

    Control Cable

    Power

    Data

    Control / Indicaton

    Relay

    I/O

    modules

    AC Power

    Supply

    PC with CMSsoftware

    RTU or

    Radio /

    modem

    RC10

    Cubicle

    SCADA

    Comms.

    USB

    RS485

    RS232PSM

    Panel

    UPS &

    Switchgear

    Control

    SIM

    RechargeableBattery

    3 x Inputs(Internaluse only)

  • 7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure

    5/8

    Introduction 4.Product Guide GMk Groun Mount kios

    4 Inepenent Protection Groups directional over current an earth fault protection Current Setting Range 10-1280A Setting Resolution 1A

    Inverse Time Protection Inepenent Curve Selection for Forwar

    & Reverse direction 4 x IEC255 Curves 8 x ANSI Curves User define Curves 42 x Custom Curves

    definite Time Protection 0-120 secons

    Time Resolution 0.01 secons High set Instantaneous element

    directional Sensitive Earth Fault Protection Current Setting Range 4-80A 1-80A option available Setting Resolution 1A definite Time 0-120 secons Time Resolution 0.01 secons

    Voltage Protection Element Phase unervoltage balance element

    (UV1) 3 phase loa sheing Multiplier setting range: 0.6-1 of system voltage Multiplier setting resolution: 0.01 Trip time range: 0-180 sec Trip time setting resolution: 0.01 sec

    Phase-to-Phase Unervoltage Element(UV2) Multiplier setting range: 0.6-1 of system voltage Multiplier setting resolution: 0.01 Trip time range: 0-180 sec Trip time setting resolution: 0.01 sec

    Loss of Supply (UV3) Trip time range: 0-180 sec

    Trip time setting resolution: 0.01 sec Reclose time: 0-180 sec Reclose time resolution: 0.01 sec

    Phase (OV1) & Line-to-Line (OV2) OverVoltage Trip time range: 0-180 sec Multiplier Setting Range: 1.00 -1.20

    Frequency Protection Element Uner Frequency (UF) Picup Range:

    46-50Hz (50Hz system), 55-60Hz(60Hz system)

    Over Frequency (OF) Picup Range: 50-55Hz (50Hz system), 60-65Hz (60Hz

    system) Frequency settings resolution: 0.01Hz Trip time range: 0-120 sec Trip time setting resolution: 0.01 sec

    Voltage reclose control with automatic bacfee restoration provies loop automationfunctionality.

    Zone Sequence Co-orination Col Loa Picup Col loa time ramp up: 1-400 min Col loa time ramp own: 0-60 min Col loa time resolution: 1 min Col loa multiplier: 1-5 times picup current Col loa multiplier resolution: 0.1

    Inrush Restraint

    Inrush time: 0.01-10 sec Inrush time resolution: 0.01 sec Inrush multiplier: 1-20 Inrush multiplier resolution: 0.1

    Temporary Time Aition

    Provies a steppe time elay toautomatically isolate faulte sections ina feeer or correct graing of evices inseries.

    duty Cycle O-0.1sec-CO-1sec-CO-1sec-CO-60sec

    recovery time

    Reclosing Times 1st reclosing time range 0.1 - 180 secons 2n reclosing time range 1 - 180 secons 3r reclosing time range 1 - 180 secons Setting resolution 0.01 secons

    Auto Reclose User configurable 1-4 trips to locout,

    inepenently settable for overcurrentearth fault, sensitive earth fault an voltageprotection.

    Live Line Function & Hot Line Tag Function

    Local Control Panel

    PROTECTION

  • 7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure

    6/8

    Introduction5. Product Guide GMK Ground Mount Kiosk

    Voltage is measured on all six (6) bushings andcurrent is measured on all three (3) phases of theOSM recloser using capacitively coupled voltagesensors and current transformers.

    Phase to Earth Voltage:Range 0.3 - 22.0kV, Accuracy 1% or 0.1kV

    Phase to Phase Voltage:Range 0.5 - 38.0kV, Accuracy 2% or 0.1kV

    Phase Current:Range 0 - 630A, Accuracy 1% or 4A

    Residual Current:Range 0 - 100A, Accuracy 5% or 0.5A

    Active, Reactive and Total Power:Range 40 - 630A, 4.5 - 38kV, Accuracy 2%

    Single and Three Phase Active, Reactive andTotal Power:Range 0 - 30,000 kW/kVAR/kVA, Accuracy 2%

    Frequency:Range 46-55Hz, 55-65HzAccuracy at dF/dT < 0.2Hz/s: 0.025Hz

    Range 46-55Hz, 55-65HzAccuracy at dF/dT < 0.5Hz/s: 0.05Hz

    Power Factor:Range 0-1, Accuracy 0.02

    A USB front panel interface is provided to connect

    to a PC running CMS. This provides full settingsand data management facilities. An RS232 RTUinterface offering 300-19.2k & 3xUSB port baud,full and half duplex modes, is provided to connectto remote control systems. NOJA Power RecloserApp is available for IPhone and IPad.

    DNP3 communications protocol is provided inthe standard product combined with our abilityto engineer new protocols to meet specifiedcustomer requests.

    The control cubicle has space to mount a radioor modem. The onboard radio power supply is

    rated at 12V 20W continuous duty, 30 watts 50%duty cycle.

    I/O modules with eight (8) user configurableinputs and eight (8) user configurable outputs canbe ordered as options in the RC10 control. Upto two I/O modules can be fitted extending thisto sixteen inputs and sixteen outputs. Three (3)user configurable sanitated inputs are included asstandard.

    MEASUREMENT

    EVENT LOG

    LOAD PROFILE LOG

    REMOTE CONTROL

    The RC10 control provides two method to accessthe event logs time and date stamped to a 0.01sec resolution.

    The first is method is from the RC LCD display, itprovides critical operations data for the linesmanand includes close/open operations, fault types,

    phase and peak level of fault current.

    The second is method is by PC upload usingCMS. It provides a full log of all operational historyincluding setting changes, operations and faulthistory.

    The fault history logs include 50 cycles of pre-triphistory to allow analysis of the fault propagation.

    The Load Profile is logged with a user configuredintegration period of either 1, 5, 10, 15, 30, 60 and120 minutes.

    The following parameters are logged separately forboth positive and negative power flow.

    Up to 10000 events can be stored in the memorywhich corresponds to a 417 day, 60 minute,integration period.

    CMS can be used to upload and plot the data.

  • 7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure

    7/8

    Introduction

    COMPONENTS

    1. Earth Connection Viewing Winow2. Loa Sie Bushings3. Source Sie Bushings4. Earth Bar5. dIN 47636 series 400 630A Interface Bushing6. Earth Switch7. Phase To Phase VT8. Interloc Operator Shown In Normal Position8A. Interloc Operator Shown In Isolate Position9. Seale Lea Aci Battery10. Power Supply an driver Moules11. Main Processor Moule12. LV Mole Case Breaers an General Purpose Outlet13. Lifting Lugs14. Sling Guies15. Recloser Status Viewing Winow16. Removable Operating Arm Shown In Isolate But

    Not Earthe Position.16A.Removable Operating Arm Shown In Isolate an

    Earthe Position

    Top View B

    Front View Bac View

    Sie View

    Top View A

    6.Product Guide GMk Groun Mount kios

  • 7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure

    8/8

    OSM15-16-6303 x Current Transformers

    6 x Voltage ScreensRC 1015.5kV630A16kA40kA16kA30,00030,00020016kA/4 secs630A25A10A

    110kV110kV50kV50kV-40C to +55C0-100%3000M720kg

    Part NumberCurrent Sensing

    Voltage SensingControl TypeRated Maximum VoltageRated Continuous CurrentFault Make Capacity RMSFault Make Capacity PeakFault Break CapacityMechanical OperationsFull Load OperationsFault Break Capacity OperationsShort Time Current WithstandMainly Active Breaking CapacityCable Charging CurrentLine Charging Current

    Impulse Withstand Phase to Earth & Phase to PhaseImpulse Across the InterrupterPower Frequency Withstand Phase to Earth (Dry)

    Across the InterrupterAmbient TemperatureHumidity

    AltitudeWeight of the Tank

    OSM27-12-6303 x Current Transformers

    6 x Voltage ScreensRC 1027kV630A12.5kA31.5kA12.5kA30,00030,00020012.5kA/4 secs630A25A5A

    125kV (150kV option)125kV (150kV option)60kV60kV-40C to +55C0-100%3000M720kg

    OSM38-12-6303 x Current Transformers

    6 x Voltage ScreensRC 1038kV630A12.5kA31.5kA12.5kA30,00030,00020012.5kA/3 secs630A40A5A

    195kV170kV70kV70kV-40C to +55C0-100%3000M775kg

    Altitudes above 1000m should be derated in accordance with ANSI C37.60-2003

    NOJA-552-02

    NOJA Power is a registered trademarks of NOJA Power Switchgear Pty Ltd. This document is copyright and is intended for users and distributors of NOJA Power Switchgear product. It contains information that is the intellectual

    property of NOJA Power Switchgear and the document, or any part thereof, should not be copied or reproduced in any form without written permission from NOJA Power Switchgear.NOJA Power Switchgear applies a policy of continued fundamental research and development and reserves the right to change designs and specifications of this product without notice. NOJA Power Switchgear does not accept

    any responsibility for loss or damage incurred by anyone as a result of acting or refraining from action based on information in this Product Guide.

    Scan o v

    NOJA Po

    bs

    NOJA POwer AuStrAliACOrPOrAte OffiCe & fACtOry

    NOJA Po Schga P ld

    16 Archimedes Place, Murarrie

    Brisbane Qld 4172, Australia

    Phone: +61 (7) 3907 8777Fax: +61 (7) 3399 6777

    Email: [email protected]

    Web: www.nojapower.com.au

    NOJA POwer uKSAleS OffiCe

    NOJA Po lmd

    4 Stalyhill Drive, StalybridgeCheshire SK 15 2TR

    United Kingdon

    Phone: +44 (01865) 58 94 99Fax: +44 (01865) 58 9400

    Email: [email protected]

    Web: www.nojapower.co.uk

    NOJA POwer CHileSAleS OffiCe

    NOJA Po SpA

    Av 11 d spmb 1881, O 1415

    Povdnca, Sanago

    Ch

    Phone: +56 (2) 897 964 9Email: [email protected]

    Web: www.nojapower.cl

    NOJA POwer BrAZilOffiCe & fACtOry

    NOJA Po do Bas lda

    Avenida Pierre Simon de Laplace, 764Techno Park Campinas SPCEP 13069-301, Brasil

    Phone: +55 (19) 3283 0041

    Fax: +55 (19) 3283 0041Email: [email protected]

    Web: www.nojapower.com.br