Real-Time Compensation of Voltage Fluctuations in LV Networks

18
Real-Time Compensation of Voltage Fluctuations in LV Networks Online Workshop WG5: Data monitoring & analytics for better PV performance and grid integration" Dr. Ing. John Licari – University of Malta 12 January 2021

Transcript of Real-Time Compensation of Voltage Fluctuations in LV Networks

Page 1: Real-Time Compensation of Voltage Fluctuations in LV Networks

Real-Time Compensation of Voltage Fluctuations in LV NetworksOnline Workshop WG5: Data monitoring & analytics for

better PV performance and grid integration"

Dr. Ing. John Licari – University of Malta

12 January 2021

Page 2: Real-Time Compensation of Voltage Fluctuations in LV Networks

2

Overview

Introduction

Standard: EN50160

Mitigation options

Active voltage controller

Simulation results

Case study - Malta

Conclusion

2

Page 3: Real-Time Compensation of Voltage Fluctuations in LV Networks

3

Introduction

Conventional Grid Modern Grid

Page 4: Real-Time Compensation of Voltage Fluctuations in LV Networks

4

Standards

EN50160:

Voltage characteristics of electricity supplied by public electricity networks

The EN 50160 is one of the standards that describes the voltage tolerance limits in electrical networks in Europe.

The supply voltage variations1 should not exceed ± 10% of the rated voltage Un

Equipment can be unnecessarily stressed or damaged if operated with a voltage outside the tolerance limits

Inefficient operation of Machines, drives and lighting devices

1 during each period of one week 95 % of the 10 min mean r.m.s. values of the supply voltage shall be within the range of Un ± 10 %;

4

Page 5: Real-Time Compensation of Voltage Fluctuations in LV Networks

5

Conventional Grid Scenario

400V11kV

DV

Voltage distribution along the LV Feeder

Current flows from the grid to the loads

Voltage reduces along the LV feeder & Over-head line

Page 6: Real-Time Compensation of Voltage Fluctuations in LV Networks

6

Modern Grid Scenario - Challenges to the Grid operator

Voltage Drop along LV feeder

400V11kV

DV

Voltage distribution along the LV Feeder

Current

High PV penetration scenario – current flow from PV to the grid

Voltage increases along the LV feeder / Over-head line

Page 7: Real-Time Compensation of Voltage Fluctuations in LV Networks

7

Mitigation Options

(Consumer Side)

PV Power Curtailment

PV system does not operate at its peak generation but at a reduced output - Not attractive due to loss of energy

Reactive power compensation

Operating the PV Inverter at leading/lagging power factor - Not attractive due to loss of energy

Optimise local consumption

Load management (PV power generated is used locally with reduced export to the grid)

Electrical energy storage (Energy generated is stored and then used later when there is demand)

Battery Storage

Electrical Vehicle charging (an effective storage solution)

7

Page 8: Real-Time Compensation of Voltage Fluctuations in LV Networks

8

Mitigation Options

(Network Operator)

Distribution Transformer with On-load tap changer

Not good if different LV feeders need different adjustments

Reactive power compensation

Network Expansion – very expensive

Energy Storage – still very expensive

Centralised storage system at sub-station level

Other equipment such as Voltage Regulators

8

Page 9: Real-Time Compensation of Voltage Fluctuations in LV Networks

9

Active Voltage Controller (AVC)

Voltage distribution along the LV Feeder

400V11kV

DV

Current

AVC

230 Vac

+6%

-6%

Unom

Page 10: Real-Time Compensation of Voltage Fluctuations in LV Networks

10

AVC – Operation Logic

Voltage

Controller inactive

Setpoint

Tolerance band -

Tolerance band +

Step

Step

Controller active

Controller active

Page 11: Real-Time Compensation of Voltage Fluctuations in LV Networks

11

AVC - High Level Per Phase Topology

Step Transformer

1.5%

Transformer

4.5%

-6% -1.5% -4.5%

-4.5% 0% -4.5%

-3% +1.5% -4.5%

-1.5% -1.5% 0%

0% 0% 0%

+1.5% +1.5% 0%

+3% -1.5% +4.5%

+4.5% 0% +4.5%

+6% +1.5% +4.5%

Page 12: Real-Time Compensation of Voltage Fluctuations in LV Networks

12

AVC – Simulated Operation

Without Controller With Controller

Page 13: Real-Time Compensation of Voltage Fluctuations in LV Networks

13

Active Voltage

Controller –A Case Study

A project of a 30kWp PV system was proposed

In a rural (remote location) in Malta with a long LV feeder

Other consumers were connected on the same feeder

Load flow analysis showed a clear problem of overvoltage on the network if the PV system is installed

Together with the local Network operator a pilot project to test the performance of the active voltage controller was carried out.

13

Page 14: Real-Time Compensation of Voltage Fluctuations in LV Networks

14

AVC – Case Study

Equipment Active

Equipment Not Active

Upper limit Set to 248V in Controller

Page 15: Real-Time Compensation of Voltage Fluctuations in LV Networks

15

Active Voltage

Controller –Installation

Location

At sub-station level

At feeder level

At unit level

15

Page 16: Real-Time Compensation of Voltage Fluctuations in LV Networks

16

Active Voltage

Controller -Features

Reaction time in ms (<25ms)

Robust technology as it is based on Thyristors

High efficiency (99%)

Each phase can be compensated independently

AVC can be moved to other parts of the network easily if the voltage variation is reduced through other means.

No maintenance is needed as in the case of other equipment

16

Page 17: Real-Time Compensation of Voltage Fluctuations in LV Networks

17

Conclusion

The case study was done in collaboration with the manufacturer of the equipment and the Network Operator.

Its performance was analyzed both through simulations and through field testing

The successful performance of the Active Voltage Controller has been confirmed

17

Page 18: Real-Time Compensation of Voltage Fluctuations in LV Networks

18

Thank you for your attention!

Questions?