PC57.13.3 IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases

Transcript of I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation...

Page 1: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

PC57.13.3

IEEE Guide for Grounding of Instrument Transformer Secondary

Circuits and Cases

Page 2: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

OUTLINE

ScopeReferencesNeed for grounding; WarningDefinition of Instrument transformersGrounding secondary circuitsGrounding at a single locationConductor size for connecting to ground

Page 3: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Scope

The scope of the guide includes the grounding practices presently used and the practices that were not previously reported. Specifically, the issue of the grounding of cases of electronic transducers is addressed.

Page 4: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Covers

The practices described in this standard apply to all instrument transformers, including capacitive voltage transformers and linear couplers, irrespective of primary voltage or whether the primary windings are connected to, or are in, power circuits or are connected in the secondary circuits of other transformers as auxiliary cts or vts.

Page 5: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Does not cover

This guide does not discuss the grounding of some applications. For example, grounding of gas insulated substations and metal clad switchgear is not discussed in this guide; the reader will find these topics addressed in reference [9] listed in clause 2. The grounding of circuits of core-balance CTs is also not discussed in this guide. The reader can find this information also in reference [9] listed in clause 2. Another issue that is not discussed in this guide is the practice of using separate safety and control grounds. For discussion on this topic, the reader is directed to reference [12] listed in clause 2.

Page 6: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

References

[1] NFPA 70-2002, National Electricity Code® (NESC®)[2] ANSI C2-2002, National Electrical Safety Code® (NESC®)[3] C37.103™-2004, IEEE Guide for Differential and Polarizing Relay Circuit Testing[4] C57.13.1™-1981 (Reaffirmed 1999), IEEE Guide for Field Testing of Relaying Current Transformers[5] C37.92™-2004, IEEE Trial Use Standard for Low Energy Analog Signal Inputs to Protective Relaying

Page 7: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

References

[6] C62.92™-2000, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems[7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding[8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems[9] Std. 242™*2001, IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems[10] Std. 518™-1982 (R1996), IEEE Guide for the Installation of Electrical Equipment to Minimize Electrical Noise Inputs to Controllers from External Sources

Page 8: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

References

[11] Std. 525™-1992, IEEE Guide for the Design and Installation of Cable Systems in Substations[12] Std. 665-1995, IEEE Guide for Generating Station Grounding[13] Std. 1050-1996, IEEE Guide for Instrumentation and Control Equipment Grounding in Generating Stations[14] Std. 1100™-1999, IEEE Recommended Practice for Powering and Grounding Electronic Equipment[15] Std. 1143™-1994 (Reaffirmed 1999), IEEE Guide on Shielding Practice for Low Voltage Cables

Page 9: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Need for Grounding Secondary Circuits

To protect equipment connected to the circuitsTo Protect personnel who might come into contact with the equipmentHow the problem manifestsWhen secondary circuit is not groundedWhen a case is not groundedVoltage due to charge accumulation on an

ungrounded secondary circuit or case

Page 10: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Warning

Grounding of secondary circuits is an issue of safety of personnel and equipment connected to the secondary circuits. The reader is urged to consider it seriously and follow the stipulations of relevant standards and ensure that the stipulations of the National Electrical Code [1] and the National Electric Safety Code [2] are always adhered to.

Page 11: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Warning

Article 90.2 (A) of National Electrical Code [1] lists the installations that are covered by the Code [1] and Article 90.2 (B) lists the installations that are not covered by the Code. For immediate reference of the readers, Article 90.2 of National Electrical Code [1] is reproduced in Annex C.

Page 12: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Grounding of Instrument Transformer Secondary Circuits

Definition of a secondary circuit for the purposes of the guideIssuesGrounding at a single locationMinimum size of the grounding conductor

Page 13: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Issues

Grounding at a single locationVoltage at different locations of the physical

ground and circuits connected to ground is different when fault currents flow

Convenience of testing a secondary circuitProblem with forming a common neutral of

more than one instrument transformers and then grounding the neutral busIsolation of all secondary circuits from

ground

Page 14: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Issues

Recommended point of grounding switchboard or relay panel

Grounding unused secondary windingsGrounding examples

Page 15: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Grounding 3 4 Wire VT Circuits

Page 16: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

PA

PB

PC

PB

PC

OPENDELTA

WYE

PA

CONNECTIONS TOGROUND BUS ATSWITCHBOARD(#12 AWG CUMINIMUM)

NEUTRAL NOT BROUGHT

OUT

GROUND ISOLATINGCONNECTION

Grounding 3 3 Wire VT Circuits

Page 17: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Grounding unused CTs

Page 18: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

ISSUES

Minimum size of grounding conductor 12 AWG required by NESC©

Page 19: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

TYPICAL APPLICATIONS

VT circuitsVoltage provided from distribution transformers

Page 20: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Using Voltage from a Distribution Transformer

Page 21: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

GROUND ISOLATING CONNECTION

PG

PN

RTO RELAYS,OSCILLOGRAPH,ETC.

TO GENNEUTRAL

STATION GROUNDMAT

SWITCHBOARDGROUND

Generator Neutral Grounding Transformer

Page 22: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Generator Neutral Grounding Transformer

CENTER TAP GROUND SOMETIMESUSED SO THAT ACCIDENTAL GROUNDON PG WILL NOT COMPLETELY DISABLEGENERATOR GROUND PROTECTION

OPTIONALCONNECTION

PG

PN

R TO RELAYS,OSCILLOGRAPH,ETC.

TO GENNEUTRAL

STATION GROUNDMAT

Page 23: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Generator Neutral Grounding Transformer

Page 24: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Generator Grounding Transformer

R

GROUNDINGTRANSFORMER

TO RELAYS,OSCILLOGRAPH,ETC.

Page 25: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Basic Synchroscope Circuit

PB

PN

SCOPE

PN

PB2525

CKT. 2 CKT. 1

GROUNDING ISOLATIONCONNECTION

RUN INC

Page 26: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Synchroscope with Multiple Incoming Circuits

Page 27: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Synchroscope with Multiple Incoming and Running Circuits

PB

PN

SCOPE

PN

PB25-125-1

CKT. 3 CKT. 1

GROUNDING ISOLATIONCONNECTION

RUN INC

25-2 PB25-2

25-1

25-2 PN

CKT. 2

GROUNDS NOT NECESSARILYELECTRICALLY CLOSE

25-1

25-2PN

CKT. 4

PB

Page 28: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Synchroscope with Multiple Incoming and Running Circuits using Isolating Transformers

PB

PN

SCOPE

PN

PB25-125-1

CKT. 3 CKT. 1

GROUNDING ISOLATIONCONNECTION

RUN INC

25-2 PB25-2

PN

CKT. 2

PN

CKT. 4

PB

1 - 1 ISOLATINGTRANSFORMERS

Page 29: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Synchroscope with Synchronizing Lights

PB

PN

SCOPE ORSYNC-CHECKRELAY

PN

PB2525

CKT. 2 CKT. 1

GROUNDING ISOLATIONCONNECTION

RUN INC

GROUNDS SHOULD BEELECTRICALLYAS CLOSE AS PRACTICAL

THIS CONTACT PERMITS THE TWO VOLTAGECIRCUITS TO BE SEPARATELY GROUNDED

SYNCHRONIZING LIGHTS

25

Page 30: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Grounding Distribution Station with one used for Instrumentation

G(N)

PN

NOTE: BECAUSE OF THE TWO GROUNDSON G(N), IT SHOULD BE SUFFICIENTLYHEAVY SO THAT STATION GROUNDFAULTS WILL NOT CAUSE DAMAGE TOG(N)

SWITCHBOARD TERMINALS

GROUND ISOLATIONCONNECTION

Page 31: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Grounding 1 CT Circuit

CP

CN

BURDEN

Page 32: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Grounding 1 CT Circuit

GROUND ISOLATIONCONNECTION

BURDEN

CP

CN

Page 33: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Grounding 3 CT Circuit

Page 34: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Grounding 3 CT Circuit

Page 35: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Grounding V Connected CT Circuit

Page 36: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Delta-Delta Connected CTs in a Differential Protection Relay

Page 37: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Delta-Wye Connected CTs in a Differential Protection Relay

SWITCHBOARDTERMINALS

GROUND ISOLATIONCONNECTION

DIFF.RELAYS

A B C ABC

CBA

CBB

CBA

CBB

CBC CBC

Page 38: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Percentage Bus Differential Scheme

SWITCHBOARDTERMINALS

GROUND ISOLATIONCONNECTION

CD1N

CD1A

CD1B

CD1C

CD2A

CD2B

CD2C

CD3A

CD3B

CD3C

CD2N

CD3N

CKT. 1

TO CTSON CKT. 2

TO CTSON CKT. 3

RESTRAINT

OPERATE

PHASE A

PHASE B

PHASE C

ABC

Page 39: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Ring Bus or Breaker and a Half Scheme

SWITCHBOARD TERMINALS(MAY BE SLIDING LINKTYPETO FACILITATE TESTING)

GROUNDISOLATINGCONNECTION

TERMINALSAT CT LOCATION

CONTROL HOUSEGROUND BUS

TO METERS,RELAYS, ETC.

TERMINALSAT CT LOCATION

Page 40: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Multiple use of CTs

51-

A 51-

A51-B

51-B

51-C

51-C

Page 41: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Grounding of Cases

Grounding metallic conductive casesInsulated cases with conductive internal partsUngrounded metallic cases or internal parts Protected by suitable barriers or elevated to

prevent contact if operating voltage exceeds 1,000 V

Page 42: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Exceptions to Grounding

If the primary windings of instrument transformer circuits are connected to circuits of less than 1000 V with no live parts or wiring exposed or accessible to other than qualified persons, the circuits may not be grounded.

Page 43: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Exceptions to Grounding

For instrument transformer cases, the cases or frames of CTs may not be grounded if the primary windings are not over 150 V to ground and are used exclusively to supply current to meters.

Page 44: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Exceptions to Grounding

Cases of instruments, meters, and relays operating at less than 1000 V on switchboards having exposed live parts on the front of panels are not usually grounded. Mats of insulating rubber or other suitable floor insulation is provided where the voltage to ground exceeds 150 V.

Page 45: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Exceptions to Grounding

Instruments, meters, and relays, whose current-carrying parts operate at voltages to ground of 1000 V and over, are isolated by elevating them or protecting them by suitable barriers, grounded metal or insulating covers, or guards. In such situations, the cases are not usually grounded.

Page 46: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Grounding of Low-Energy Transducers

Page 47: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Grounding of Low-Energy Transducers

Page 48: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Grounding of Low-Energy Transducers

Page 49: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Annex A

Grounding of shielded cablesTo consider current carrying capacity of the

shieldCables with spiral design shields are grounded

at both endsCables with drain wires are grounded at one

end

Page 50: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Annex A

CTs installed over shielded cables

Page 51: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Annex B

IEEE Standards reviewed by the WG

Page 52: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

Annex C

Clause 90.2, Scope of National Electricity CodeType of installations covered by the CodeType of installations not covered bye the CodeSpecial permission

Page 53: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial

ANNEX D

Survey of Grounding PracticesApproximately one-third of the respondents do

not ground voltage transformers “at the first point of use” as described in the Guide. The Working Group is of the opinion that grounding “at the first point of use” is better than grounding at other locations.

Almost all respondents indicated that current transformers are grounded “at the first point of use” as described in the Guide.