Reactors - Eurolaite · design and manufacture of air core, dry type, power reactors for all...
Transcript of Reactors - Eurolaite · design and manufacture of air core, dry type, power reactors for all...
Reactors
Introduction
With 40 years of successful fieldexperience, Trench is therecognized world leader in the design and manufacture of air core,dry type, power reactors for all utility and industrial applications.The unique, custom design ap-proach, along with fully integratedengineering and manufacturingfacilities in both North Americaand Europe have enabled Trench to become the technicalleader for high voltage inductorsworldwide.
A deep commitment to the powerindustry, along with extensive investment in engineering, manufacturing and test capabilitygive Trench customers the utmost in high quality, reliableproducts which are individually designed for each application. Trench reactor applications havegrown from small, distributionclass, current limiting reactors tocomplex EHV applied reactors surpassing 300 MVA per coil. Reactors are manufactured in accordance with ISO 9001 qualitystandard. Trench's highly develo-ped research and developmentprogram constantly addresses newtechnologies and their potential ap-plication in reactor products.Trench welcomes challenges fornew applications for power reactors.
This brochure outlines the features,capabilities and applications of Trench reactors. Although air-core, dry type reactors
represent the majority of reactorproduction volume, Trenchalso produces a highly successfulline of iron core/iron shielded andoil type reactors for specific appli-cation (eg. Resonance Grounding/Petersen Coils). These reactors arealso described in detail in othersections of the Trench product catalogue.
Design Features of Air-Core Dry Type Reactors
• Epoxy impregnated, fibreglassencapsulated construction
• Aluminum construction through-out with all current carryingconnections welded
• Highest mechanical and shortcircuit strength
• Essentially zero radial voltagestress, with uniformly gradedaxial voltage distribution between terminals
• Low noise levels are maintainedthroughout the life of the reactor
• Weatherproof construction, withminimum maintenance require-ments
• Design service life in excess of30 years
• Designs available in compliancewith ANSI/IEEE, IEC and othermajor standards.
Reactors
Fig. 1Three-phase stacked
current limiting reactor2
Series Reactors
Reactors connected in series withthe line or feeder. Typical uses arefault current reduction, load balancing in parallel circuits, limi-ting inrush currents of capacitorbanks, etc.
Reactor Applications
Fig. 2Schematic diagram
Fig. 4Current limiting reactor
Fig. 3Single phase series reactors
Trench reactors are utilized on transmission anddistribution systems. Although it is not possible to listall reactor applications, some of the most common aredescribed below.
Current Limiting Reactors,reduce the short circuit current tolevels within the rating of theequipment on the load side of thereactor.
Applications of current limiting reactors range from the simpledistribution feeder reactor to largebus-tie and load balancing reactorson systems rated up to 765 kV/2100 kV BIL.
Capacitor Reactors are designedto be installed in series with ashunt connected capacitor bank tolimit inrush currents due to switching, to limit outrush currentsdue to close in faults and to controlthe resonant frequency of the system due to the addition of thecapacitor banks. Reactors can beinstalled on system voltagesthrough 765 kV/2100 kV BIL.
When specifying capacitor reactors,the requested continuous currentrating should account for harmoniccurrent content, tolerance on capacitors and allowable systemovervoltage.
3
Buffer Reactors forElectric Arc Furnaces (EAF).The most effective use of EAFs isachieved by operating the furnaceat low electrode current and longarc length. This requires the use ofa series reactor in the supply systemof the arc furnace transformer forstabilizing the arc.
Fig. 5Buffer reactor
for E.A.F.
Fig. 6Load flow control reactors
Duplex Reactors are current limiting reactors which consist oftwo half coils, wound in opposition.These reactors provide a desirablelow reactance under normal con-ditions and a high reactance underfault conditions.
Load Flow Control Reactors areseries connected on transmissionlines up to 800 kV.The reactors change the line impedance characteristic such thatload flow can be controlled, thusensuring maximum power transferover adjacent transmission lines.
4
Filter Reactors
Filter Reactors are used in conjuctionwith capacitor banks to form series tuned harmonic filter circuits,or in conjunction with capacitorbanks and resistors to form broad-band harmonic filter circuits.
When specifying filter reactors,the magnitudes of fundamentaland harmonic frequency currentshould be indicated. If inductanceadjustment for fine tuning is required, the required tapping rangeand tolerances must be specified.
Many filter applications require aQ-factor which is very much lowerthan the natural Q of the reactor.This is often achieved by connectinga resistor in the circuit.An economical alternative is theaddition of a de Q'ing ring structureon a reactor. This can reduce theQ-factor of the reactor at tuningfrequency up to as much as onetenth without the necessity of in-stalling additional damping resi-stors. (see Fig. 9 below)
These rings, mounted on the reactorare simply coupled to the magnetic
Fig. 8Filter reactors
Fig. 9Filter reactors with
de Q’ing rings
Fig. 7Schematic diagram
Fig. 10Capacitor/filter protection relay
field of the reactor. This eliminatesthe concern of space, connectionand reliability of additional compo-nents such as resistors.
The Capacitor/Filter ProtectionRelay CPR 04 is a microprocessorbased protection relay speciallydesigned for optimized protectionof shunt banks and harmonic filtercircuits.
5
Static VAR Compensators are used on transmission systems to improve the overall reliability, correct forvoltage fluctuations and power factor as well as increasing the transmission capability and reducing losses.
Shunt Reactors
Shunt Reactors are used to compensate for capacitive VARsgenerated by lightly loaded trans-mission lines or underground cables. They are normally connectedto the transformer tertiary windingbut can also be directly connectedon systems up to 115 kV.
Fig. 11Schematic diagram
Fig. 14Thyristor controlled reactor
Fig. 12Tertiary connected
shunt reactors
Fig. 13Thyristor controlled shunt reactors and filter
reactors in a Static VAR Compensator
Thyristor Controlled Shunt Reactors are extensivelyused in static VAR systems, wherereactive VARs are adjusted by thyristor circuits. Static VAR compensator reactor applicationsnormally include:
• Thyristor controlled shunt reactors(TCR). The compensating poweris changed by controlling thecurrent through the reactor bymeans of the thyristor valves.
• Thyristor switched reactors (TSR)
• Thyristor switched capacitor reactors (TSC)
• Filter reactors (FR)
6
HVDC-Reactors
HVDC lines are used for long distance bulk power transmission
Fig. 15Schematic diagram
Fig. 17HVDC-Smoothing reactor
Fig. 16AC-Filters
a) AC - PLC b) AC - FR c) HVDC - SMR d) DC - FR e) DC - PLC
as well as back-to-back inter-connections between differenttransmission networks.HVDC Reactors normally include
Smooting Reactors, AC and DCHarmonic Filter Reactors as well as AC and DC PLC Noise Filter Reactors.
7
Smoothing Reactors
Smoothing reactors are used to reduce the magnitude of the ripplecurrent in a DC system. They areused in power electronics applications such as variable speeddrives and UPS systems. They arealso required on HVDC transmissionlines for system voltages up to500 kV. Several design and constructiontechniques are offered by Trench.
Fig. 18Schematic diagram
Fig. 19Iron core,
forced air cooled reactor
Fig. 20Air core,
encapsulated winding design
Fig. 21Iron core,
water cooled reactor
8
Test Lab Reactors
Test Lab Reactors are installed inhigh voltage and high power testlaboratories. Some typical applications include current limiting,synthetic testing of circuit breakers,inductive energy storage, artificiallines, etc.
Fig. 22Schematic diagram
Fig. 23Reactor bank for the
voltage circuit for synthetic testingof circuit breakers; 32 kA peak to peak,
0,318 mH to 353,6 mH, up to 1600 kV BIL
Fig. 25Short circuit test reactor
Fig. 24Adjustable
current limiting reactor
9
Neutral Grounding Reactors
Neutral Grounding Reactors limitthe line to ground fault current tospecified levels. Specificationshould also include unbalancedcondition continuous current andduration.
Fig. 26Schematic diagram
Fig. 27Arc suppression coil 110 kV
Fig. 28Standard arc suppression coil
Arc Suppression Coils
Single-phase neutral grounding(earthing) reactors (arc suppressioncoils) are intended to compensatefor the capacitive line-to-groundcurrent during to a single phaseground-fault.The arc suppression coil (ASC) represents the central element ofthe Trench earth fault protection system.
Since the electric system is subjectto changes, the inductance of theASC used for neutral earthingmust be variable.
The earth fault detection systemdeveloped by Trench utilizes theplunger core coil (moveable coredesign). Based on extensive experi-ence in design, construction andapplication of ASCs, Trenchproducts can meet the most strin-gent requirements for earth faultcompensating techniques.
10
A Trench air core dry type reactorconsists of a number of parallelconnected, individually insulated, aluminum (copper onrequest) conductors. These conductors can be small wire orproprietary cables custom designedand manufactured.
The size and type of conductorused in each reactor is dependanton the reactor specification. Thevarious styles and sizes of conductors available ensure optimum performance at the mosteconomical cost. The windings aremechanically reinforced withepoxy resin impregnated fibreglass,which after a carefully definedoven cure cycle produces an encapsulated coil. A network ofhorizontal and vertical fibreglassties coupled with the encapsulationminimizes vibration in the reactorand achieves the highest availablemechanical strength.
The windings are terminated ateach end to a set of aluminum barscalled a spider. This constructionresults in a very rigid unit capableof withstanding the stresses developed under the most severeshort circuit conditions.
Exceptionally high levels of terminalpull, tensile strength, wind loadingand seismic withstand can be accommodated with the reactor.See Fig. 29 for details on construction.
This unique design can be installedin all types of climates and environments and still offer optimum performance.
Trench air core dry type reactors are installed in pollutedand corrosive areas supplyingtrouble free operation. In additionto the standard fixed reactancetype of coil, units can be suppliedwith taps for variable inductance.A number of methods are availableto vary inductance for fine tuningor to provide a range of larger inductance steps.
Trench utilizes various otherdesigns for reactors (eg. iron core,water cooled, etc.) which aredescribed in other sections of thiscatalogue.
Construction
Fig. 29Typical Trench air core dry type
reactor construction
11
It is the customer's responsibilityto consider these minimum clearances, especially if steel reinforcing in concrete foundationsor floors, or structural steel is involved in the building or stationdesign. It is important, even outsidethese minimum magnetic clearan-ces, to avoid closed electrical loopswith metallic parts.
Terminals/Magnetic Clearance
D
If required, non-magnetic extensionbrackets can be supplied by Trench to maintain the necessary magnetic clearancebelow the reactor. Trench canprovide additional details on spacerequirements and recommended reinforcing steel(rebar) design, if requested.
Magnetic Clearence
Minimum clearances to metallicparts, and between coils, must bemaintained as indicated by Figs. 32and 33. The values shown are onlyguidelines. Each specific reactordesign will specify magnetic clearance requirements.
Fig. 30Terminal orientation
Fig. 31Terminal details
Fig. 32Minimum magnetic clearance to other reactors and metallic parts
not forming closed loops (approximate values only)
Terminals
12
Generally, air core, dry type reactors can be installed in eitherside by side or vertically stackedconfigurations and are oftenadded to existing substations orlocations where space limitationsexist. With its highly developedcomputer design expertise,Trench can design reactors withoptimized dimensions, to suit limited space requirements. Themulti-spider construction allowsflexibility in terminal location,which minimizes connection problems (see Fig. 35).
Number of spider arms to be obtained from the actual quotationdesign.
Installation assembly is minimaland typically requires only thatbrackets and insulators be boltedto the main coil. Installation instructions are provided witheach reactor order.
Trench takes into consideration all aspects of the reactor installation. These includerequirements of ventilation, reactor supports, connections andbusbar arrangements.
Trench can also provide detailedinformation regarding:
• magnetic field distribution analysis for mounting pads andfoundations, grounding grids,fences and adjacent structures
• Force calculations on adjacentcoil installations, bus and cableconnections
Installation
• Seismic analysis on entire reactorassemblies, including support insulators and mounting pedestals,when furnished.
Fig. 33Three-phase
stacked arrangement
13
Testing
At Trench each reactormanufactured is subjected to a rigorous test and inspection program. In addition to the routinetesting required by ANSI/IEEE orIEC a number of in-process testsare performed on each unit duringproduction to ensure maximum in-service reliability. Each reactor issupplied with a certified test reportwith the results from all tests performed.
In addition to routine testing wehave the capability in our HighVoltage and Power labs to performmost of the design tests describedin the applicable standards. Designtests can be performed at an additional cost or test reports onsimilar units can be supplied uponrequest.
The materials used in the manufacture of the reactor arealso subject to a strict test program.Cooling duct spacers and the fibreglass epoxy resin compositeencapsulation are subject to routinemechanical strength and trackingresistance testing. Acceleratedthermal and multifactor aging studies are carried out which helpto verify performance of the reactor components over their fullservice life.
This testing coupled with our Quality Assurance program enablesus to ensure the continuous perfor-mance of our reactors throughoutthe design service life.
Losses
The custom design approach usedby Trench allows optimum use ofmaterials to control reactor losses.If a loss evaluation is not indicated in the specification, thereactor will be designed to meetthe applicable standards at a mosteconomical initial cost.
All customers are aware of the advantages in minimizing systemlosses and are applying loss evaluation techniques for reactorpurchases. In the cases where lossevaluations are included in the reactor specifications, Trenchoptimizes the initial cost of thereactor plus the cost of operating losses, to ensure themost economical balance. Generally, a loss optimized reactorwill operate at a lower temperaturerise and will thus extend the reactoroverload capability.
Trench's ability to design andmanufacture low loss reactorsallow many electric power utilitiesto economically justify the replacement of older, inefficientreactor installations. The low lossreactors can usually be installed onexisting mounting pads.
Losses can also be influenced forother purposes. In some applicationsit is important to control the Q factor(X/R ratio) of the reactor. This maybe important at the fundamentalfrequency or at specific harmonicfrequencies where additional lossesare advantageous, for example capacitor switching reactors andcertain filter applications.
Testing/Losses
Fig. 34High voltage test laboratory
14
Trench designs and manufactures enclosures and support pedestals specifically forair core, dry type reactors.
Enclosures, depending on the requirement, are made of steel orfibreglass and can be designed forindoor or outdoor installations.Trench enclosure design minimizescirculating current loops and opti-mizes the size by defining ventila-tion area and acceptable tempe-rature rise. Enclosures have beenqualified as complete assemblies by short circuit testingof the enclosed reactor.
Trench can supply support pede-stals to elevate reactor live parts toa height commensurate with per-sonnel safety standards. Pedestalsalso provide proper magnetic clearance below the reactor. Various pedestal designs are available and include fibreglass,braced aluminum and non-magneticsteel designs.
Trench can recommend the mostpractical pedestal for each reactorapplication. Additional informationon enclosures and pedestals isavailable on request.
Sound shields can be provided toreduce the reactor noise level forspecial applications (HVDC).
Enclosures and Pedestals
Fig. 35Filter reactor with sound shield
Fig. 36Filter reactor with top-hat
and pedestal
15
Data required with order
• Reactor application
• Indoor or outdoor installation
• System voltage,impulse insulation level (BIL)
• Rated and maximumcontinuous current(fundamental and harmonics)
• Short circuit current leveland duration
• Rated inductance/impedance
• Mounting arrangement(side by side or vertical stack)
• Detailed accessoryrequirements (connectors,buswork, etc.)
• Location of installation andsite conditions
• Ambient temperature range
Änderungen vorbehalten04.09
E 600
Trench Austria GmbHPaschinger Straße 49AT-4060 Linz-Leonding/AustriaPhone +43.732.6793-0Fax +43.732.671341email [email protected]
Trench Brasil LTDA Via Expressa de Contagem, 2685CEP 32370-485Contagem, Minas Gerais/BrasilPhone +55.31.391-5959Fax +55.31.391-1828email [email protected]
Trench China Limited3658 Jiang Cheng RoadMinhang, Shanghai 200245 P.R. ChinaPhone +86.21.64630088Fax +86.21.64637828email [email protected]
Trench France S.A.16, rue du Général CassagnouB.P. 70FR-68302 St-Louis/FrancePhone +33.3.89 70 23 23Fax +33.3.89 67 26 63email [email protected]
Trench Germany GmbHNürnberger Straße 199DE-96050 Bamberg/GermanyPhone +49.951.1803-0Fax +49.951.1803-224email [email protected]
Trench Italia S.r.l.Strada Curagnata 37IT-17014 Cairo-Montenotte/ItalyPhone +39.019.5161.111Fax +39.019.5161.401email [email protected]
Trench Limited Coil Product Division71 Maybrook Drive, ScarboroughOntario, Canada M1V 4B6Phone +1.416.298-8108Fax +1.416.298-2209email [email protected]
Trench Limited Instrument Transformer Division390 Midwest Road, ScarboroughOntario, Canada M1P 3B5Phone +1.416.751-8570Fax +1.416.751-6952email [email protected]
Trench Switzerland AGLehenmattstraße 353CH-4052 Basel/SwitzerlandPhone +41.61.315 51 11Fax +41.61.315 59 00email [email protected]
Trench (UK) LimitedSouth DriveHebburnTyne & WearNE31 1UW, Great BritainPhone +44.191.483.4711Fax +44.191.430.0633email [email protected]
www.trenchgroup.com