Reactive Power Control in Electrical Power Transmission System

download Reactive Power Control in Electrical Power Transmission System

of 31

Transcript of Reactive Power Control in Electrical Power Transmission System

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    1/31

    Sub: APS-1

    Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    2/31

    A simple system analysis can be performed to

    develop a basic understanding of the effect of

    Shunt & Series Compensation on Power

    transmission Capacity.

    Sub: APS-1

    Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    3/31

    It is desirable both economically and technically

    to operate the electric power systems at near unity

    power factor (u.p.f).

    Usually power factor correction means to generate

    reactive power as close as

    possible to the load which it requires rather than

    generating it at a distance and transmit it to

    the load, as it results in not only need of

    a large sized conductor but also increased losses

    thereby reducing transmission efficiency.

    Sub: APS-1

    Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    4/31

    Artificial injection of reactive power at

    the loads may relieve the transmission

    network from reactive power flow and

    improves both transmission efficiency andoperating power factor where as artificial

    injection of negative reactance in the

    lines may relieve the lines from excessive

    voltage drop and improves the voltageregulation.

    Sub: APS-1

    Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    5/31

    The methods available for the injection of

    both are static compensation and

    synchronous compensation. Static

    compensation involves capacitors andreactors where as synchronous

    compensation involves synchronous phase

    modifier.

    Sub: APS-1

    Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    6/31

    In all cases it is not required to satisfy

    both the objectives of:

    increasing the power level at which the voltage

    profile is flat; and decreasing electrical length in order to improve

    power transfer level

    Sub: APS-1

    Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    7/31

    Short lines may require voltage support, i.e.,

    increase natural load

    This may be achieved by shunt capacitors, provided does not become excessive as a result

    Lines longer than 500 km cannot be loaded up

    to natural load because of excessive In such cases, reduction of is the first priority

    Sub: APS-1

    Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    8/31

    To control voltage and/or improve maximumpower transfer capability

    Achieved by modifying effective lineparameters:

    -characteristic impedance,

    -electrical length, = l

    The voltage profile is determined by ZC

    The maximum power that can be transmitteddepends on ZC as well as .

    C

    LZ

    C

    Sub: APS-1

    Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    9/31

    Used to compensate the undesirable

    voltage effects associated with line

    capacitance

    limit voltage rise on open circuit or light loadShunt compensation with reactors:

    increases effective ZC reduces the effective natural load , i.e., voltage

    at which flat voltage profile is achieved

    Sub: APS-1 Topic:

    Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    10/31

    They are connected either:

    directly to the lines at the ends, or

    to transformer tertiary windings; conveniently

    switched as var requirements varyLine reactors assist in limiting switching

    surges

    In very long lines, at least some reactors

    are required to be connected to lines

    Sub: APS-1 Topic:Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    11/31

    Used in transmission systems to

    compensate for I 2X losses

    Connected either directly to H.V. bus or

    to tertiary winding of transformersNormally distributed throughout the

    system so as to minimize losses and

    voltage drops

    Usually switched: a convenient means of

    controlling voltage

    Sub: APS-1 Topic:Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    12/31

    Shunt capacitor compensation of transmission

    lines in effect

    decreases ZC increases , i.e., electrical length

    Advantages: low cost and flexibility of

    installation and operating

    Disadvantages: Q output is proportional to

    square of the voltage; hence Q output reduced

    at low voltages

    Shunt capacitors are used extensively indistribution systems for power factor correction

    and feeder voltage control

    Sub: APS-1 Topic:Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    13/31

    Connected in series with the line

    Used to reduce effective inductive reactance of

    line

    increases maximum power reduces I 2X loss

    Series capacitive compensation in effect

    reduces both:

    characteristic impedance ZC, and

    electrical length

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    14/31

    Reactive power produced increases with increasing

    power transfer

    Self regulating

    Typical applications

    improve power transfer compatibility

    alter load division among parallel lines voltage regulation

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    15/31

    (a) Power transfer as a function of transmission angle

    (b) Midpoint voltage as a function of power transfer

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    16/31

    With shunt capacitor compensation (chosen to

    keep midpoint voltage at 1.0 pu when P = 1.4

    Po

    )

    maximum power transfer capability increased to 1.58 pu

    of natural power (SIL); represents an increase of 0.16 pu

    over the uncompensated case

    voltage regulation is poor, i.e., the voltage magnitude is

    very sensitive to variations in power transfer

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    17/31

    With series capacitor compensation (chosen to keep

    mid point voltage at 1.0 pu when P = 1.4 Po)

    maximum power transfer capability increased to 2.65 pu

    voltage regulation significantly improved

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    18/31

    Alternating current transmission systemsincorporating power electronics-based and

    other static controllers to enhance

    controllability and increase power transfer

    capability

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    19/31

    Without fundamental research in this area, very

    little use will be made with full confidence of the

    real opportunities offered by FACTS devices. For the time being we only have limited examples,

    entirely based on simulation, which demonstrate

    that fast regulation of reactive compensation on a

    transmission grid could be very useful in the future.

    Because of this, there may exist an immediate

    danger of uncoordinated system-wide fast

    regulation via FACTS devices which could become

    detrimental to system integrity under certain

    operating conditions.

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    20/31

    Dynamic: Transient and dynamic stability

    Subsynchronous oscillations

    Dynamic overvoltages and undervoltages Voltage collapse

    Frequency collapse

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    21/31

    Static: Uneven power flow

    Excess reactive power flows

    Voltage capability Thermal capability

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    22/31

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    23/31

    Long-term Control

    -Power Flow control

    -FACTS scheduling

    -Economics

    Dynamic Control

    -System oscillation damping

    -

    Voltage stability-FACTS ringing

    Local Control

    -Control target acquisition

    -Power electronics topology

    -Modulation strategies

    time

    Is there a

    one-size-fits-all

    controller?

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    24/31

    UPFC

    SSSC

    TCSC

    TCPAR

    These devices can affect active power flow

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    25/31

    Sensitivity analysis

    Where is the change in power transfercapacity in response to an addition of tcompensation in line i-j with admittance bij+j gijand b and g are sensitivity parameters

    t

    t

    gt

    t

    b ijg

    ij

    b

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    26/31

    Optimization (optimal power flow) with genetic

    algorithms to minimize some cost function

    Generation costs

    Congestion

    Problem is nonlinear, non-smooth, and non-convex

    Max-flow (graph theory) uses forward and backward

    labeling from source to sink to dynamically determineline flows

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    27/31

    Dynamic Coordination of FACTS settings Security

    Economics

    Droop

    Hierarchical or local control of FACTS?

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    28/31

    transient stability improvement

    inter-area oscillation damping

    voltage collapse avoidance

    subsynchronous resonance mitigation

    Each control objective will (possibly)

    require a different FACTS placement

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    29/31

    Most dynamic control development has

    concentrated on SMIB or very small two-

    area systems

    How is control implemented in a largenonlinear interconnected dynamic

    network?

    FACTS-FACTS interaction

    FACTS-generator interaction

    Hardware/field verification limited

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    30/31

    Unbalanced operation

    Harmonics

    Integration of Energy Storage (BESS,

    SMES, flywheels)Power electronic topologies

    Power electronics devices

    Sub: APS-1 Topic: Effect on Power Transfer Capacity

  • 7/28/2019 Reactive Power Control in Electrical Power Transmission System

    31/31

    A. Edris et al., Proposed Terms and

    Definitions for Flexible AC Transmission

    System (FACTS), IEEE Transactions on

    Power Delivery, Vol. 12, No. 4, October1997, pp. 18481853.

    R. Mohan Mathur and Rajiv K. Varma -

    Thyristor-Based FACTS Controllers for

    Electrical Transmission Systems

    Sub: APS-1 Topic: Effect on Power Transfer Capacity