Reactive Power Control in Electrical Power Transmission System
-
Upload
ajay-talajiya -
Category
Documents
-
view
224 -
download
0
Transcript of Reactive Power Control in Electrical Power Transmission System
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
1/31
Sub: APS-1
Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
2/31
A simple system analysis can be performed to
develop a basic understanding of the effect of
Shunt & Series Compensation on Power
transmission Capacity.
Sub: APS-1
Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
3/31
It is desirable both economically and technically
to operate the electric power systems at near unity
power factor (u.p.f).
Usually power factor correction means to generate
reactive power as close as
possible to the load which it requires rather than
generating it at a distance and transmit it to
the load, as it results in not only need of
a large sized conductor but also increased losses
thereby reducing transmission efficiency.
Sub: APS-1
Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
4/31
Artificial injection of reactive power at
the loads may relieve the transmission
network from reactive power flow and
improves both transmission efficiency andoperating power factor where as artificial
injection of negative reactance in the
lines may relieve the lines from excessive
voltage drop and improves the voltageregulation.
Sub: APS-1
Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
5/31
The methods available for the injection of
both are static compensation and
synchronous compensation. Static
compensation involves capacitors andreactors where as synchronous
compensation involves synchronous phase
modifier.
Sub: APS-1
Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
6/31
In all cases it is not required to satisfy
both the objectives of:
increasing the power level at which the voltage
profile is flat; and decreasing electrical length in order to improve
power transfer level
Sub: APS-1
Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
7/31
Short lines may require voltage support, i.e.,
increase natural load
This may be achieved by shunt capacitors, provided does not become excessive as a result
Lines longer than 500 km cannot be loaded up
to natural load because of excessive In such cases, reduction of is the first priority
Sub: APS-1
Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
8/31
To control voltage and/or improve maximumpower transfer capability
Achieved by modifying effective lineparameters:
-characteristic impedance,
-electrical length, = l
The voltage profile is determined by ZC
The maximum power that can be transmitteddepends on ZC as well as .
C
LZ
C
Sub: APS-1
Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
9/31
Used to compensate the undesirable
voltage effects associated with line
capacitance
limit voltage rise on open circuit or light loadShunt compensation with reactors:
increases effective ZC reduces the effective natural load , i.e., voltage
at which flat voltage profile is achieved
Sub: APS-1 Topic:
Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
10/31
They are connected either:
directly to the lines at the ends, or
to transformer tertiary windings; conveniently
switched as var requirements varyLine reactors assist in limiting switching
surges
In very long lines, at least some reactors
are required to be connected to lines
Sub: APS-1 Topic:Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
11/31
Used in transmission systems to
compensate for I 2X losses
Connected either directly to H.V. bus or
to tertiary winding of transformersNormally distributed throughout the
system so as to minimize losses and
voltage drops
Usually switched: a convenient means of
controlling voltage
Sub: APS-1 Topic:Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
12/31
Shunt capacitor compensation of transmission
lines in effect
decreases ZC increases , i.e., electrical length
Advantages: low cost and flexibility of
installation and operating
Disadvantages: Q output is proportional to
square of the voltage; hence Q output reduced
at low voltages
Shunt capacitors are used extensively indistribution systems for power factor correction
and feeder voltage control
Sub: APS-1 Topic:Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
13/31
Connected in series with the line
Used to reduce effective inductive reactance of
line
increases maximum power reduces I 2X loss
Series capacitive compensation in effect
reduces both:
characteristic impedance ZC, and
electrical length
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
14/31
Reactive power produced increases with increasing
power transfer
Self regulating
Typical applications
improve power transfer compatibility
alter load division among parallel lines voltage regulation
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
15/31
(a) Power transfer as a function of transmission angle
(b) Midpoint voltage as a function of power transfer
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
16/31
With shunt capacitor compensation (chosen to
keep midpoint voltage at 1.0 pu when P = 1.4
Po
)
maximum power transfer capability increased to 1.58 pu
of natural power (SIL); represents an increase of 0.16 pu
over the uncompensated case
voltage regulation is poor, i.e., the voltage magnitude is
very sensitive to variations in power transfer
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
17/31
With series capacitor compensation (chosen to keep
mid point voltage at 1.0 pu when P = 1.4 Po)
maximum power transfer capability increased to 2.65 pu
voltage regulation significantly improved
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
18/31
Alternating current transmission systemsincorporating power electronics-based and
other static controllers to enhance
controllability and increase power transfer
capability
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
19/31
Without fundamental research in this area, very
little use will be made with full confidence of the
real opportunities offered by FACTS devices. For the time being we only have limited examples,
entirely based on simulation, which demonstrate
that fast regulation of reactive compensation on a
transmission grid could be very useful in the future.
Because of this, there may exist an immediate
danger of uncoordinated system-wide fast
regulation via FACTS devices which could become
detrimental to system integrity under certain
operating conditions.
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
20/31
Dynamic: Transient and dynamic stability
Subsynchronous oscillations
Dynamic overvoltages and undervoltages Voltage collapse
Frequency collapse
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
21/31
Static: Uneven power flow
Excess reactive power flows
Voltage capability Thermal capability
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
22/31
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
23/31
Long-term Control
-Power Flow control
-FACTS scheduling
-Economics
Dynamic Control
-System oscillation damping
-
Voltage stability-FACTS ringing
Local Control
-Control target acquisition
-Power electronics topology
-Modulation strategies
time
Is there a
one-size-fits-all
controller?
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
24/31
UPFC
SSSC
TCSC
TCPAR
These devices can affect active power flow
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
25/31
Sensitivity analysis
Where is the change in power transfercapacity in response to an addition of tcompensation in line i-j with admittance bij+j gijand b and g are sensitivity parameters
t
t
gt
t
b ijg
ij
b
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
26/31
Optimization (optimal power flow) with genetic
algorithms to minimize some cost function
Generation costs
Congestion
Problem is nonlinear, non-smooth, and non-convex
Max-flow (graph theory) uses forward and backward
labeling from source to sink to dynamically determineline flows
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
27/31
Dynamic Coordination of FACTS settings Security
Economics
Droop
Hierarchical or local control of FACTS?
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
28/31
transient stability improvement
inter-area oscillation damping
voltage collapse avoidance
subsynchronous resonance mitigation
Each control objective will (possibly)
require a different FACTS placement
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
29/31
Most dynamic control development has
concentrated on SMIB or very small two-
area systems
How is control implemented in a largenonlinear interconnected dynamic
network?
FACTS-FACTS interaction
FACTS-generator interaction
Hardware/field verification limited
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
30/31
Unbalanced operation
Harmonics
Integration of Energy Storage (BESS,
SMES, flywheels)Power electronic topologies
Power electronics devices
Sub: APS-1 Topic: Effect on Power Transfer Capacity
-
7/28/2019 Reactive Power Control in Electrical Power Transmission System
31/31
A. Edris et al., Proposed Terms and
Definitions for Flexible AC Transmission
System (FACTS), IEEE Transactions on
Power Delivery, Vol. 12, No. 4, October1997, pp. 18481853.
R. Mohan Mathur and Rajiv K. Varma -
Thyristor-Based FACTS Controllers for
Electrical Transmission Systems
Sub: APS-1 Topic: Effect on Power Transfer Capacity