RAY MAGIC NKInstallation manual
2
3
Ray Magic NK is a high performance hydronic radiant panel. It instals on the ceiling (and walls) and it is covered with ⅝" regular drywall, to create unobstructed radiant surfaces.
Ray Magic NK comes in 2'x8' size and can be cut down in two 2'x4' panels to fit smaller spaces.
Ray Magic “NaKed”
Cut sheets
4
96"
24"
48"
48"
= = = =3 ¾"
24"
23 ⅜"
22"
1 ½"
⅞"
1⅜"
1"1½"
Possiblecuts
Panel piping layout
RM 3-way fitting
8 mm radiant PEX pipe
16 mm backbone PEX pipe
2x4 panel pipes connection
Full panel (2'x8')
Half panel (2'x8')
5
What is in the box
2x1x 5x10x 10x
96 ¼"
12 ¼"
7 ¾"
RM cap Pre-insulated 16 mm PEX straight pipe (7 ½ ft)
(PEX1675I)
3-way fitting lock rings
Ray Magic NK(2x8 ft)
RM coupling
Weight: 40 lbDimension: 96 ¼” x 12 ¼” x 7 ¾”
6
Panel details
Alluminum transfer plate
Pre-cut EPS edge
RM 3-wayfitting
16 mm PEX backbone pipes
RM cap
RM coupling
Panel cap off
panel conections(2x4 panel only)
Connection between panels
7
FJ901604 16mm ELBOW push-fit, tvwist & lock plastic fitting for PEX piping
FJCP1604 16mm COUPLER push-fit, twist & lock plastic fitting for PEX piping
FJTE1604 16mm TEE push-fit, twist & lock plastic fitting for PEX piping
FJEC1604 16mm END CAP push-fit plastic fitting for PEX piping
PEX1630I Pre-insulated 16mm x 1.5 PEX pipe with 1/2” insulation 100ft coil
PEX1675I Pre-insulated 16mm x 1.5 PEX pipe with 1/2” insulation 7.5ft straight
CPRMNN32
NN indicates the number of loops from 02 to 12 loops (ex: CPRM0632)
NN-loop plastic 1-1/4” modular manifold with insulation.NPT female inlet. Temp gauges, air bleed valves, balancing valves and flow meters. Unassembled.
Required installation tools
Pipe cutter tool(PCUTPEX)
Helmet Long blade cutterGlovesOuter reamer tool for PEX 16x1.5(PORTPEX)
Recommended parts
8
Installation
9
This installation manual describes how to hang the Ray Magic NK panels to the ceiling and gives some basic layout guidance.
To properly size the radiant surface to cover heating and cooling loads consult with a mechanical engineering firm in your area.
When in doubt call (855) RAY-MAGIC
Furring layout(24" O.C. additional framing)
Ceiling joists
Framing
⅝ Dry wall
Requiredaddtionalframing
Ceiling joists
24" O.C.
Two hanging options
A
10
Framing layout(installation between 24" O.C. ceiling joists)
Ceiling joists
Ceiling joists
Required additional blocking for back support
Additionalblocking
⅝ Dry wall
24" O.C.
24"O
.C.
B
11
Furring layout
24’’ O.C.
24" O.C.
1½"
1½"
23½"
1¼"
1½
Wood strip channel (24 “ O.C.)
Galvanized stell hat furring channel (23 ½“ O.C.)
fasten poits per side6
Flat wire staple
Flat head nail
Flat head metal screw
A
A.1
A.2
23 ½" works better
12
Remove the edges before hanging
& tear out A.1 A.2
1½" 1½"
Remove the pre-cut EPS edge by applying pressure with your hands
13
Framing layout
24’’ O.C.
24’’ O.C.
24’’ O.C.
24 O.C. blocking
24"
24 " O.C.
Solid wood sistem (24 " O.C.)
Wood I joists (TJI) system (24 “ O.C.)
3" 3"
1½"
1 12"
1½"
2"
1½"
1½"
1 12"
1½"
2"
1½"
1½"
B
B.1
B.2
fasten poits per side6
Flat wire staple
Flat head nail
14
Remove the edges before hanging
Tear out
1½" blade cut
1 ½" 1 ½"
3" 3" Cut off no more than 1 ½"
Remove the pre-cut EPS edge by applying pressure with your hands
B.1
B.2
1½" 1½"
2" 2"
15
How to cut the 2x8 panel to make two 2x4 panels
Remove the tape around the panel
Separate the panels
Must use the proper pipe cutter tool (PCUTPEX) to cut the backbone pipe.
16
How to prep the 16 mm pre-inseulated PEX pipe (PEX1675I or PEX1630I)
Chamfer both side
Insert the insulation again before using the pipe
Rotate the outer reamer tool until the pipe is smooth
Cut the pipe using the pipe cutter tool (PCUTPEX)
Insert the outer reamer tool (PORTPEX) on the pipe
Do not cut less than 3" to facilitate use of the reamer tool
1
2
3
4
17
16 mm pre-insulated PEX pipe connection into the panel (RM 3-way fitting only)
1 ½"
Chamfer each sides of the piece of pipe using the outer reamer tool (PORTPEX)
After plumbing completion, always pressure test the system at 100 psi following the Messana system pressure test and fill/purge procedure downloadable online
Insert pipe into the fitting all up to the pipe stop. If correctly inserted the mark will be aligned with the collar
1
Mark the pipe with a sharpie at 1 1/2” from the edge2
4
3
Make sure the mark is aligned with the fitting collar (pipe fully inserted)
You can use the RM Cap as a template to sign the pipe (1 1/2”)
18
16 mm pre-insulated PEX pipe connection into the 2x4 panel (pipe connections side only)
1 ¼"
Chamfer each sides of the piece of pipe using the outer reamer tool (PORTPEX)
Insert the pipes into the fitting up to the pipe stop (on both sides). If correctly inserted the mark will be aligned with the twist lock cap
Twist the screw cap until it touches the body flange to secure the pipe.
1
2
3
5
4
This locks the pipe into position and increases the O-ring seal around the pipe.
Make sure the mark is aligned with the fitting collar (pipe fully inserted)
After plumbing completion, always pressure test the system at 100 psi following the Messana system pressure test and fill/purge procedure downloadable online
Mark the pipe with a sharpie at 1 1/2” from the edge
19
How to disconnect a RM 3-way fitting
Pull easily out the pipe (or RM coupling, or RM cap)
Lift the RM 3-way fitting to access the twist collar and rotate 90 degrees (either CCW or CW)
1
2
Use this procedure to extract either a pipe, or a RM coupling, or a RM cap
Lock ring
EDPM triple o-ring
Funnel shaped twist collar
Circular stopping wedge
Ensure th system is decompressed
20
blablablbalbalbal
Insert in order the locking ring (new replacement), the wedge and the o-ring back into the fitting chamber
Cut the pipe right after the lock ring using the proper pipe cutter tool (PCUTPEX). Alternatively cut the lock ring using a cutting plier.
Put the colar back in to the fitting and rotate 90 degrees to lock the RM 3-way fitting (either CCW or CW)
3
5
4
6
Put the new lock ring in the right direction
21
Connections into the panel
2x8 panel
2x4 panel (2x4 panel pipes connection)
Never cap the half panel with the 16 mm END CAP. Move the 2x4 panel at the begining of the branch and cap the oppostite side on the RM 3-way fitting
22
How to connect panels to supply/return leader pipes
6"
6" Coil pipe
Strap pipes before bending
Never bend pipes connected to the RM 3-way fitting
Use a piece of the pre-insulated 16 mm PEX straight pipe (PEX1675I) for a direct connection
Use the RM coupling and 3" nipple PEX pipe to make a tight connection
3"
23
Clearence to the wall
6"
7"
2x4 panel as a header (7")
2x8 panel as a header (6")
5"
3"
5"
3"
7"
6"
Prepare two nipple pipes of 3" and 5" and ream the outer edges both side unising the reamer tool (PORTPEX)
Prepare two nipple pipes of 3" and 5" and ream the outer edges both side unising the reamer tool (PORTPEX)
24
2"
2 ¾"
2x4 panel as a header (2")
2x8 panel as a header (2¾")
Clearence to the wall (with attic space above)
SubfloorCeilingjoists Ray magic
NK 2x8
Subfloor
Ceilingjoists
Ray magic NK 2x4
25
How to join two panels
Make sure the panels are fully insert
Insert the RM coupling before connecting the panel
26
How to cap a panel
Make sure the cap is fully insert
27
Panels connections
28
Connect the half panel to the leader pipes
Never cap the half panel with the 16 mm END CAP. Move the 2x4 panel at the begining of the branch and cap the oppostite side on the RM 3-way fitting
29
Max 15 panels (2'x8') per manifold loop
3 6
2 5
1 4
6½
7½
8
9
10 13
11 14
12 15
To manifold loop
No more than 15 panels in a manifold loop
30
2
1
Keep a maximum 4 to 1 ratio rate on branches, alternately use an additional manifold loop
No more than 12 panels in a row
Balancing
Keep the braches balanced
Max 12 panels (2’x8’) in a branch
2 2
1 1
12 4 9
11
4:1 9:1