Radix Wire Cable - Champion Fiberglass
Transcript of Radix Wire Cable - Champion Fiberglass
Authorities Having Jurisdiction shouldbe consulted before installation.
System Overview:
RadixWire&Cablehasbeen2-hour,UL2196certifiedforuseinChampionFiberglassXW™phenolicsystemconduit.Thiscertificationwillallowforanon-metallicsolutionforalarmsystemapplicationswheretheuseofmetallicracewaysarenotdesired.ThisAddendumtotheDuraLife®IIFPLR/FPLR-CIInstallationGuidewillofferinformationastotheproperassemblyofthisuniquesystem,aswellasinformationastothesystemcomponentsthathavethe2-hourfirecertificationaslistedforuseinFHIT/FHIT728C.
UL 2196
ADDENDUMDuraLife®IIFPLRFAS90Shielded/UnshieldedFireResistiveCables
18AWG/2C,16AWG/2C,14AWG/2C,12AWG/2CPhenolicSystemGuidelines
FHIT/FHIT728C
Item No. CTUCTS
CAN/ULC S-139
September2019
DuraLife®IIFPLR/FAS90cableshavebeencertifiedtoUL2196for2-hourfirecomplianceinChampionFiberglassXW™phenolicconduitandsystemcomponents.Thecertifieditemnos.arelistedbelow:
System Certified Components
Straightsections;standardlengths ChampionFiberglassPartNos.
1.00”tradeI.D.(10ft.) 10EXW10S
1.25”tradeI.D.(20ft.) 12EXW10S
1.50”tradeI.D.(20ft.) 15EXW10S2.00”tradeI.D.(20ft.) 20FXW10S
A. Phenolic Conduit
Straightsections ChampionFiberglassPartNos.
1.00”tradeI.D. 10EXW42
1.25”tradeI.D. 12EXW42
1.50”tradeI.D. 15EXW422.00”tradeI.D. 20FXW42
B. Phenolic Conduit Couplers
90°sections;12”radius ChampionFiberglassPartNos.
1.00”tradeI.D. 10EXW90P
1.25”tradeI.D. 12EXW90P
1.50”tradeI.D. 15EXW90P2.00”tradeI.D. 20FXW90P
C. Phenolic Elbow Joints
Non-threaded;pinassembly;O-ring ChampionFiberglassPartNos.
1.00”tradeI.D. 10EXW30-2196
1.25”tradeI.D. 12EXW30-2196
1.50”tradeI.D. 15EXW30-21962.00”tradeI.D. 20FXW30-2196
D. Phenolic Box Fittings
DuraLife®IIFPLR/FAS90cablesareapprovedformultiplefillallowancesinChampionXWphenolicconduit.Seetablebelowformaximumcable-fill:
Phenolic Conduit Fill Allowances
Fill Allowances: Horizontal/VerticalConduit Size
Cable 1” 1.25” 1.5” 2”
18AWGUnshielded 3 6 9 X
18AWGShielded 3 5 7 X
16AWGUnshielded 2 4 6 10
16AWGShielded 2 4 6 10
14AWGUnshielded 2 3 4 10
14AWGShielded 1 3 4 10
12AWGUnshielded 2 3 4 9
DuraLife®IIFPLR/FAS90cables,bothshieldedandunshielded,canbemechanicallysplicedwhenusingapprovedNEMA1spliceboxes.Splicesareallowed(upto8conductors)inbothhorizontalandverticalinstallations.PleaserefertotheapprovedspliceprocedureforFHITSystem28C,andthecertifiedsplicecomponentsonpages7-9intheDuraLife®IIFPLR/FPLR-CIFAS90Dual-Rated Installation Instructions - Shielded and Unshielded,forbothapprovedsplicemethods.
Splice Allowance
• Onetotwocablescanusea8x8x4splicebox• Threeormorecablescanusea10x10x4splicebox• Verticalsplicingcanusea12x6x4splicebox
Requiredwallsupportmustbeamin12gauge,by1½in.wideor1-5/8in.wide,paintedorunpainted,slottedsteelchannelswithhemmedflangeedges.Channelbottomwithorwithoutholes.Lengthsofslottedsteelchannels5ft.andlessshallbesecuredtothewallorfloorwithaminoftwo¼in.diameter(orlarger)by2¼in.minlongconcretescrews,or¼in.diameter(orlarger)by1¾in.longminsteelmasonryanchors.Onescreworanchormustbelocatedateachendoftheslottedsteelchannel.Lengthsofslottedsteelchannelinexcessof5ft.requireaminofthreescrewsoranchors,oneateachendofthechannelandonecentrallylocatedwithinthelengthofthechannel.Forhorizontalcableinstallations,thesupportsshallbespacedatamaximumof5ft.OC.Forverticalcableinstallations,thesupportsshallbespacedamaximum6ft.OC.WheninstallingDuraLife® IIBrandcable(s)shieldedandunshieldedinverticalruns,themaximumverticalriseallowanceofcablewithinshallbe:
• 30ft.betweenterminatingpointsfor18AWG• 35ft.for16,14AWGand12AWG(unshieldedonly)
Phenolic System Support Requirements
Approvedphenolicconduitsupportclampsare:
PartNumber: ERICOER-CD2B(1”) ERICOER-CD3B(1.25”) ERICOER-CD4B(1.5”) ERICOER-CD5B(2”)
**NOTE-Duetothesystemassemblyrequirementofadhesiveforin-linecouplers,boxfittings,elbowjoints,asupportclampshouldbeusedwithin24”ofthelocationofthebondedjoint.Seeillustrationsbelow:
GeneralMethod:Thecomponentsofthephenolicsystemshouldbegluedbeforetheconduitisplacedonthewallsupports.Thismethodbelowwilldescribetheproperpracticetousetheepoxyadhesive:
• Thetwocomponentadhesivesystemwillbegintocurein3-7minutes,andrequiresapproximately30minutesofsettimebeforehandlingorpullingcables.Thetwocomponentsystemwillbesuppliedinadhesivetubeswithanaccompanyingmixertipthatwillmixthetwocomponentstogether.Theadhesivetubeshouldbeinsertedintotheapplicatordispenser(mustbepurchasedseparately).Themixertipshouldthenbeattachedtotheadhesivetubeanthentheadhesiveisreadytobeapplied.
PartNos.:ChampionFiberglassMixCM-2070• Epoxy---SuperFastGel#43558• Hardener---#43558• MixingTip---CM-MT-20• AdhesiveGun---CM-AG-20
• Theendsurfaceoftheconduit(approx.9”)shouldbelightlysandedtoremovethesheenfromthesurfacepriortoapplicationoftheadhesive(seeillustrationbelow).
• Whentheadhesiveapplicatortriggerisdepressed,theadhesivewillself-mixinthemixertip.Afewsquirtsofadhesiveshouldbeclearedfromthetubetogetthepropercomponentmixratio.Theadhesiveshouldbeliberallyspreadwithasteelspatulaleavinganapprox.10-15milthicknessoverthesandedsurfaceofconduitend.Theconduitendcanthenbeinsertedintothecorrespondingcoupling,orboxfitting,whileusingaslighttwistingmotion.Anyexcessadhesivecanbescrapedoffwiththesteelspatulaorwipedoffwitharag.Glovesandsafetyglassesarerecommendedwhenusingtheadhesive.
Adhesive Joint Application