RADIO TRANSMISSION MODULESM7
USER’S MANUAL
�
�
1. APPLICATION ................................................................................ 5
2. SET OF THE SM7 MODULE .......................................................... 6
3. INSTALLATION ............................................................................. 6 3.1. ModuleMounting.................................................................... 7 3.2. SM7ElectricalConnections................................................... 8 3.3. WayofConnectionwithDevices.......................................... 10 3.4. RequirementsforOutletConnections...................................11 3.5. ExamplesofLUMEL-Heat,LUMEL-Energy andLUMEL3000ConfigurationstoCo-operate withSM7Module...................................................................11
4. MODULE PRINCIPLE OF OPERATION ...................................... 12 4.1. FirstStartoftheSM7ModuleandPCComputer................. 14 4.1.1. InstallationoftheConfigurationProgramonPC....... 14 4.1.2. ConfigurationProcedureoftheSM7Module............ 14 5. TECHNICAL DATA ....................................................................... 20
6. SM7 ORDER CODES ................................................................... 22
7. MAINTENANCE AND WARRANTY ............................................. 22
CONTENTS
RADIO TRANSMISSION MODULESM7
USER’S MANUAL
December2006-KZ1285/06
�
�
1.APPLICATIONTheSM7radiotransmissionmoduleisadevicedestinedfordatatransmissionbyradiointhenon-licensed433MHzor868MHzbandwithoutputpowerfrom-20to10dBminoneoftenaccessibleradiochannels.Thedatabaudrateintheradiochannelchangesintherange:4800.....76800bit/s,howeverintheserialport,itispossibletosetupthebaudrateintherange:4800.....115200bits/s.ThesechangesarecarriedoutbymeansoftheannexedSM7Config.execonfigu-rationprogram.Theofferedmodule isbecomecompletedwithastubantennaequippedwithaconnectorofSMAtype,SMA/SMAangleadapterandaconcentriccabledestinedtolocatetheantennainanyplace.TheSM7radiotransmissionmodulefindsapplicationamongotherthingsinpowerengineering,automatics-formonitoringdataofthemanufacturingprocessandinmanyotherapplicationsrequiringdatatransmission.TheSM7moduleenablesthedatareadoutfromdevicesequippedwithserialin-terfaces(RS-485orRS-232).Thedataexchangewiththemasterdeviceiscarriedoutintheradiocircuitwith433MHzor868MHzfrequency.TheSM7moduleenablestheworkinoneoftenradiochannels,intwodifferenttypesofdataencoding,ManchesterorNRZ.Theaddressingradiocircuithasbeenappliedinthemodule,whatgivesthepossibilityofgroupingmodulesworkingonthesameradiochannel.ExemplaryapplicationsoftheSM7modulearepresentedonthefig.1.
Fig.1. Exemplary monitoring of temperature, humidity and pressure
�
2. SET of the SM7 MODULE
Thesetofthedataacquisitionmoduleiscomposedof:SM7module.................................................................................. 1pc,stubantenna.................................................................................. 1pc,SMA/SMAangleadapter............................................................... 1pc,antennacable................................................................................ 1pc,plugwithscrewterminalsofBU1005type...................................2pcs,plugwithscrewterminalsofBU0204type...................................2pcs,SM7user’smanual........................................................................ 1pc,warrantycard................................................................................. 1pc,miniCDwithsoftware................................................................... 1pc.
Whenunpackingtheinstrument,pleasecheckwhetherthetypeandexecutioncodeonthedataplatecorrespondtotheorder.
3. INSTALLATION and SAFETY REQUIREMENTS
Symbolslocatedinthisservicemanualmean:WARNING!Warningofpotential,hazardoussituations.Especiallyimportant.Onemustacquaintwiththisbeforeconnectingtheinstrument.Thenon-observanceofnoticesmarkedbythesesymbolscan occasion severe injuries of the personnel and the damage of the instrument!
CAUTION!Designatesageneralusefulnote.Ifyouobserveit,handlingofthemeterismadeeasier.Onemusttakenoteofthis,whentheinstrumentisworkinginconsistentlytotheexpectations.Possible consequences if disregarded !
InthesecurityscopetheinstrumentmeetstherequirementsoftheEN61010-1standard.
Remarks concerning the operator safety: 1. GeneralTheinstrumentisdestinedtobemountedona35mmrailacc.tothefig.2.Non-authorizedremovaloftherequiredhousing,inappropriateuse,incorrect installationoroperationcreatetheriskofinjurytopersonnelordamageto
�
equipment.Formoredetailedinformation,pleasestudythepresentuser’s manual.Alloperationsconcerningtransport,installation,andcommissioningaswell asmaintenancemustbecarriedoutbyqualified,skilledpersonneland nationalregulationsforthepreventionofaccidentsmustbeobserved.Accordingtothisbasicsafetyinformation,qualified,skilledpersonnelare personswhoarefamiliarwiththeinstallation,assembly,commissioning,and operationoftheproductandwhohavequalificationsnecessaryfortheir occupation.
2. Transport, storagePleaseobservethenotesontransport,storageandappropriatehandling.ObservetheclimaticconditionsgiveninTechnicalData.
3. InstallationThemetermustbeinstalledaccordingtotheregulationandinstructionsgiven inthisuser’smanual.Ensureproperhandlingandavoidmechanicalstress.Donotbendanycomponentsanddonotchangeanyinsulationdistances.Donottouchanyelectroniccomponentsandcontacts.Instrumentsmaycontainelectrostaticallysensitivecomponents,whichcan easilybedamagedbyinappropriatehandling.Donotdamageordestroyanyelectricalcomponentssincethismight endangeryourhealth!
4. Electrical connectionBeforeswitchingtheinstrumenton,onemustcheckthecorrectnessof connectiontothenetwork.Incaseoftheprotectionterminalconnectionwithaseparateleadonemust remembertoconnectitbeforetheconnectionoftheinstrumenttothemains.Whenworkingonliveinstruments,theapplicablenationalregulationsforthe preventionofaccidentsmustbeobserved.Theelectricalinstallationmustbecarriedoutaccordingtotheappropriate regulations(cablecross-sections,fuses,PEconnection).Additional informationcanbeobtainedfromtheuser’smanual.Thedocumentationcontainsinformationaboutinstallationincompliancewith EMC(shielding,grounding,filtersandcables).Thesenotesmustbeobserved forallCE-markedproducts.Themanufacturerofthemeasuringsystemorinstalleddevicesisresponsible forthecompliancewiththerequiredlimitvaluesdemandedbytheEMC legislation.
�
5. OperationMeasuringsystemsincludingSM7modulesmustbeequippedwithprotection devicesaccordingtothecorrespondingstandardandregulationsfor preventionofaccidents.Aftertheinstrumenthasbeendisconnectedfromthesupplyvoltage,live componentsandpowerconnectionsmustnotbetouchedimmediately becausecapacitorscanbecharged.Thehousingmustbeclosedduringoperation.
6. Maintenance and servicingPleaseobservethemanufacturer’sdocumentation.Readallproduct-specificsafetyandapplicationnotesinthisuser’smanual.Beforetakingthemeterhousingout,onemustturnthesupplyoff.Theremovaloftheinstrumenthousingduringthewarrantycontractperiod maycauseitscancellation.
3.1. Module mountingThemoduleisfixedona35mmrailacc.tothefig.2.
Fig.2. Overall dimensions and module fixing way
�
3.2. SM7 Electrical ConnectionsThe supply and external signals must be connected acc. to the fig. 3 and thetable1inwhichtheassignmentofparticularoutletsoftheSM7modulehasbeendescribed.
a)for85...253Va.c./d.c.and20...50Va.c./d.c.suppliesb)for7....35Vd.c.supply
Fig. 3. Description of SM7 outlets
�0
Description of SM7 outlets
Terminal No Terminal description
1 TxDRS-232line 2 RxDRS-232line 3 GNDRS-232line 4 (notused) 5 (notused) 6 (notused) 7 +5V25mAline 8 GNDRS-485line 9 ARS-485line 10 BRS-485line 11 Supplyline(+ford.c.currentsupply) 12 Supplyline(-ford.c.currentsupply) 13 Functionalgroundline(d.c.supplied) 14 (notused) 15 (notused) 16 (notused) 17 (notused) 18 (notused)
Table1
Description of SM7 module diodes Table2
Markings Description
RxD(red)
TxD(yellow)
RxRF(red)
TxRF(green)
Datareceiptfromtheserialport
Datatransmissiontotheserialport
Receiptofradiodata
Transmissionofradiodata
��
3.3. Way of Connection with DevicesThewayofSM7moduleconnectiontoRS-232orRS-485interfacesarepresentedonfig.4and5.
Fig.4 Connection way of SM7 module to the RS-232 bus
Fig.5 Connection way of SM7 module to the RS-485 bus
��
Caution:Considering electromagnetic interference, one must apply shielded wires to connect RS-485 interface signals. The shield must be con-nected to the earth terminal in a single point. The supply should be connected to the earth terminal in a single point. The supply should be connected by a two-wire cable, with an appropriate diameter of wires assuring its protection by means of an installation cut-out.
3.4. Requirements for Outlet ConnectionsPractically,differentinterferencesourcesoccurring,influenceonthemoduleinacontinuousorimpulsewayfromthesupplynetworkside(inconsequenceoftheotherdeviceoperations).Thelevelofthisinterferenceshouldbereducedtoavaluelowerthanthemoduleimmunitythreshold,firstofallthroughtheappropriatemoduleinstallationintheobject.In order to obtain a full immunity of the module against electromag-netic interference in an environment with an unknown interference level, it is recommended to observe following principles:Donotapplythemodulefromthenetworkintheproximityofdevices generatinghighimpulseinterference,Applynetworkfiltersforthegroupofmodulesservicingthesameobject,Applythegeneralprinciples,thatwires(groupofwires)leadingdifferent signalsshouldbeledfartherawaytooneanother(notlessthan50cm), andcrossingsofsuchgroupofwiresmadeatan90°Cangle.
3.5. Example of Lumel Heat, Lumel Energy and Lumel 3000 Confi-guration to Co-operate with the SM7 Module
LumelHeatandLumel3000systemscommunicatewithindustrialdevicesbymeansofCOMserialports.TheSM7moduledoesnotrequiretheinstallationofwhateverprogrammablelogiccontroller.Incasewhenthereisnotenoughofserialportsinthecomputer,onecanincreasethisnumberinstallingaPD10orPD12USBconverteronthebus,whatextendscomputerresourceswithadditionalCOMports.AfterinstallingadditionalCOMserialports,onecanrefertotheminsystemsofLumelseries.Then,onemustintroduceorchangesupervisorycallstotheaddedcommunicationports,inneworexistingapplicationsorsystemconfigurations.LumelEnergysoftwaresinolderversionthen2.5,servicemaximally4serialports,andtheymustbeinstalledasCOM1...4insuchsystems.
��
4. SM7 MODULES PRINCIPLE OF OPERATION
TheSM7radiotransmissionmoduleenablestheradiocommunicationofdevicesequippedwithanRS-232orRS-485serialport.Themaximalbaudrateintheradiochannelis76800bit/s.Thisratecanbechangedintherange:4800....76800bit/s.ThecommunicationwithRS-232orRS-485interfacescanbecarriedoutwithbaudratesfrom4800...115200bit/s.Theradiotransmissionisperformedmaximallyintheshapeof226bytepackages,fromwhich256bytesaredatareceivedfromtheserialport,andremainingareappliedfortheneedofpackageforming.Thedatatransmissioniscarriedout inthefollowingway:databitsarereceivedfromtheserialportandtheyareswitchedovertothesendingbuffer.Ifthesendingbufferwillbefilleduporifasuitabletimeiselapsed(„timeout”),dataareplacedinaframeautomaticallyprovidedwithanappropriateheadingandtransmittedbytheradiochannel.Theheadingisbuiltfromthesequenceofsixuniquebytes,allowingthereceivingdevicestoidentifystreamsofradiowavesasframeswithdata,Apartfromthecitedsequenceofbytes,thegroupaddressofthemoduletransmittingdataisencodedintheframeheading.Theinsertionofthisaddressintheframeincreasesthedatasafetyandallowstocre-ateseveralgroupsofmodulesworkingindependentlyonthesameradiochannel.The receptionof radiodata resolves itself into thedetectionof thecorrectdataframe.Afterreceivingthecorrectframe,thegroupedaddressencodedintheframeischecked.Iftheaddressisidenticalasthemoduleaddress,whichtheframehavereceived,thenreceiveddataaredirectedtotheserialport.Thecurrentoperatingconditionsofthemodulearesignalledbylightingdiodes:RedRxDdiodeandyellowTxDdiodesignalthedataflowthroughtheserialport,however the red RxRF and greenTxRF signal the data flow through the radiochannel.IfduringthetransmissionboththeredRxRFdiodeandthegreenTxRFdiodearelighted,thatmeansthatthereceptionbufferwasoverfilledbyatohighnumberofdatafromtheserialport(morethan256characters)andtheirtransmissionthroughtheradiolinewascancelled.RxRFandTxRFdiodesarealsolightedafterintroducingthemoduleintheconfigurationstate.ThetransmissionbetweenthemasterdeviceandthemodulecanrunfasterthanintheradiocircuitbecauseoftheRS-485portapplicationtocontrolthedataflow,the CTS signal which informs the master device if the module is ready to thedata reception,hasnotbeenapplied. In this connexion, for thecorrectmoduleoperation,itisrecommendedtoapplythesamebaudratesoftheserialportandtheradiocircuit.Themoduleisconfiguredbythemanufacturertoworkontheserialportwitha9600bit/sbaudrateinthe8N2mode,andontheradiocircuitwiththe9600bit/sbaudrate,
��
withtheManchesterencodingandthetransmitterpowerequal+10dBm,howeverallparameterscanbechangeddependingonrequirements.TheconfigurationiscarriedoutbymeansoftheSM7config.execonfigurationpro-gram.TheconfigurationprogramtakesadvantageoftheRS-232serialportandexchangesdatawiththeSM7moduleusingitsowncommunicationprotocol.Onemustremember,thatthemoduleconfigurationprogramworkswithfollowingserialportsettings:-baudrate:9600bit/s-transmissionmode:8N2ToswitchtheSM7moduleintotheconfigurationmode,onemustpressforthreesecondsduringthemoduleoperation,thebuttonbeingatthebottomofthehousing.Thebuttonlocationispresentedonthefig.6.Afterpressingthebutton,theSM7modulebreaksthenormaloperation,switchesovertotheconfigurationmodeandadaptsthesettingofitsserialporttosettingsoftheconfigurationprogram,i.e.9600,8N2Aftertheconfigurationchange,onemustturnthemodulesupplyoff,andnextswitchitonagain.Themodulewillstarttothenormalworkwithnewsettings.
Fig.6. Location of the configuration button
��
4.1. First Start of the SM7 ModuleAt the first start, the SM7 module requires settings of following indispensableinformation:groupaddress,radiochannel,transmitterpower,typeandradiobaudrate.Apartofthis,itisnecessarytosetparametersoftheserialport:baudrateandtransmittermode.The„SM7config.exe”)programaddedtotheset,allowstheusertoconfigureinaneasywaytheSM7modulesetting.
4.1.1. Installation of the Configuration on PC
Theinstallationconsistsincopyingofthe„SM7config.exe”programfromtheaddedCDdisktotheset,intothecatalogueassignedbytheuseronthecomputerharddisk.TheprogramcanbealsostarteddirectlyfromtheCDdisk.
4.1.2. Configuration Procedure of the SM7 Module
InordertoconfiguretheSM7module,onemustconnectittothecomputerserialport:RS-232(outletdescriptionaccordingtothefig.3.),next,turnthemodulesupplyon,pressthemoduleconfigurationbuttonandholditduringca1sec.Then,RxRFandTxRFdiodesarelightingtillthemomentofthesupplyturningoff.Afterstar-tingthe„SM7Config.exe”program,onecanchooseinthe„PortCOM:”field,thenumberoftheCOMportwhichtheSM7moduleisconnectedto.Afterpressingthe„Connect”button, theconfigurationprogramestablishestheconnectionwiththeSM7module,andthemessage:„Connectedwith theCOMport”appears in thecommunicationwindow.IncaseofaccesslacktotheCOMport,theinformationaboutthelackofconnec-tionwiththeCOMportwillbedisplayedinthemessagewindow.AfterthecorrectconnectionestablishedwiththeSM7module,theconfigurationprogramdisplaystheinformationaboutthecurrentmoduleconfiguration.Thechangeofthemoduleconfigurationconsistsinmakingthechoiceinappropriatefieldsintheprogramwindow.Followingoptionsareaccessible:-Optionsoftheserialport. -serialbaudrate(4800....115.200bit/s), -serialtransmissionmode(8N1,8N2,8E1,8O1,7E1,7O1).-Optionsoftheradioport: -settingoftheradiocircuit(groupaddress,radiochannelnumber), -transmissiontype(baudrate:4800....76800bit/sandencodingtype:NRZorManchester), -transmissionpower(from-20dBmto10dBm).
��
NOTE: One must remember that the optimal module work is reached at the setting of similar baud rate for both interfaces, i.e. the serial port and the radio circuit. For other settings, the occurrence of erroneous data transmission states is possible.
Thebutton„Restoremanufacturersettings”allowstosetupmanufacturersettingsinthemodule.EachchangeofsettingsisregisteredinthemessagewindowofSM7Config.exeprogramandtransmittedtotheSM7module.Incaseofcorrectlyorerroneouslycarriedoutoperationofthesettingchange,anappropriatemessagewillbedisplayedinthemessagewindowAftercarryingoutchanges,onemustdisconnect the transmissionchoosing the„Disconnect”button.ThedisconnectionofthetransmissionandthereleaseoftheCOMportbySM7Config.exewillfollow.Setparametersofthemoduleconfigurationwillbeoperativeafterturningthemodulesupplyoffforca3sec.anditrenewedturningon.
Fig. 7. View of the SM7Conf.exe configuration application
��
5. TECHNICAL DATA
Port 1:–RS-232interface
-dataformat 8N1,8N2,8E1,8O1,7E1,7O1-baudrate 2400...115200bit/s
Port 2:–RS-485interface
-formatdanych 8N1,8N2,8E1,8O1,7E1,7O1-prêdkoœætransmisji 4800...115200bit/s
Radio circuit:-carrierfrequency 433,868MHz-power -20,-15,-10,-5,0,5; (10dBmonlyfor433MHz)-receiversensivity -110dBm-baudrate 4800,9600,19200,38400,76800bit/s-encodingtype NRZ,Manchester-transmissionrangeindirectline 300m-numberofchannels 10-antennaoutput 50SMA
Time of availability obtainment since the supply connection 2s
Module input power 2.5VA
Rated operating conditions:-supplyvoltage 7...35Vd.c.;20...24...50Va.c./d.c. 85...230...253Va.c./d.c.-ambienttemperature 0...23...45°C-relativeairhumidity <95%(condensationinadmissible)-serviceposition any
Storage and handling conditions:-ambienttemperature -20...70°C-relativeairhumidity <95%(condensationinadmissible)
Ensured protection grade:-fromthehousingside IP20-fromtheterminalside IP20
Overall dimensions 45120100mm
Weight 0.5kg
��
Housing for35mmrailmounting, acc.EN60715
Electromagnetic compatibility:-noiseimmunity acc.EN61000-6-2-resistanceagainstsupplydecay acc.EN61000-6-2-noiseemissions acc.EN61000-6-4
Safety requirements acc. to EN 61010-1:-installationcategory III-pollutiongrade 2-maximalphase-to-earthworkvoltage:
-forsupplycircuit 50V-forothercircuits 50V
SM7 ORDER CODES
*Themanufacturerwillestablishthecodenumber.
Radio transmission module SM7 X X X
Supply voltage:85...230...253Va.c./d.c. ...........................................................120...24...50Va.c./d.c. ...............................................................27...35Vd.c. ..............................................................................3onorder* .................................................................................. X
Radio carrier frequency:433MHz ..........................................................................................1868MHz ..........................................................................................2
Acceptance tests:wthoutadditionaltests............................................................................ 8withanextraqualityinspectioncertificate.............................................. 7acc.touser’sagreement*........................................................................X
Coding example:TheSM7 1 2 7codenumbermeans:
SM7-Radiotransmissionmodule1-supplyvoltage:85...230...253Va.c./d.c.2-radiocarrierfrequency:868MHz7-withanextraqualityinspectioncertificate
��
7. MAINTENANCE AND WARRANTY
TheSM7moduldoesnotrequireanyperiodicalmaintenance.Incaseofsomeincorrectoperations:
1. After the dispatch date and within the period stated in the warranty cardOneshouldreturntheinstrumenttotheLUMEL’sQualityInspectionDept.Iftheinstrumenthasbeenusedincompliancewiththeuser’smanual,LUMELS.A.warrantstorepairitfreeofcharge.Thedisassemblingofthehousingcausesthecancellationofthegrantedwarranty.
2. After the warranty period:Oneshouldsendtheinstrumenttorepairitinaauthorizedserviceworkshop.Spa-repartsareavailablefortheperiodoffiveyearsfromthedateofpurchase.
LUMEL S.A. reserves the right to make changes in design and spe-cifications of any products as engineering advances or necessity
SALES PROGRAMDIGITALandBARGRAPHPANELMETERSMEASURINGTRANSDUCERSANALOGPANELMETERS(DININSTRUMENTS)ANALOGandDIGITALCLAMP-ONMETERS INDUSTRIALandHOUSEHOLDCONTROLLERSCHARTANDPAPERLESSRECORDERSPOWERCONTROLUNITSandINVERTERSLARGESIZENUMERICandALPHANUMERICDISPLAYSAUTOMOTIVEDASHBOARDINDICATORSACCESSORIESFORMEASURINGINSTRUMENTSMEASURINGSYSTEMS(ENERGY,HEAT,CONTROL)CUSTOM-MADEPRODUCTS
WE ALSO OFFER OUR SERVICES IN THE PRODUCTION OF:ALUMINIUMALLOYPRESSURECASTINGSPRECISIONENGINEERINGANDTHERMOPLASTICSPARTSPRESSURECASTINGDIESANDOTHERTOOLS
Lubuskie Zak³ady Aparatów Elektrycznych LUMEL S.A.ul.Sulechowska1,65-022Zielona Góra, Poland Tel.:(48-68)3295100(exchange)Fax:(48-68)3295101e-mail:[email protected]://www.lumel.com.pl
Export Department:Tel.:(48-68)3295302or5304Fax:(48-68)3254091e-mail:[email protected]
MEASUREMENTCONTROLRECORDING
QUALITY PROCEDURES: AccordingtoISO9001andISO14001internationalrequirements.AllourinstrumentshaveCEmark.Formoreinformation,pleasewritetoorphoneourExportDepartment