R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance...

48
R MOS GB 0418-1 411482 FIGHTER 360P INSTALLATION AND MAINTENANCE INSTRUCTION FIGHTER 360P LEK +2 0 -2

Transcript of R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance...

Page 1: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

R

MOS GB 0418-1 411482FIGHTER 360P

INSTALLATION AND MAINTENANCE INSTRUCTION

FIGHTER 360P

LEK

+20-2

A B A B A BI II III I II I II

Page 2: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i
Page 3: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Contents 1

FIGHTER 360P

For Home Owners

General information for the installerTransport and storage .......................................... 11Handling .............................................................. 11Erecting the heat pump ........................................ 11Maximum boiler and radiator volumes ................ 11Inspection of the installation ................................ 11Electric boiler mode .............................................. 11

Pipe connectionsGeneral ................................................................ 12Docking ................................................................ 12Tap water connection .......................................... 12Draining the heating system ................................ 12Emptying the water heater .................................. 12Pump and pressure drop diagrams........................13

Ventilation connectionVentilation flow .................................................... 14Exhaust air duct .................................................. 14Adjustment .......................................................... 14Duct installation .................................................... 14Fan diagram ........................................................ 14

Electrical connectionsConnection .......................................................... 15Power rating as set at the factory ........................ 15Resetting the temperature limiter ........................ 15Max phase current .............................................. 16Connecting the outside sensor ............................ 16Access to the lower electrical connections .......... 16Centralised load control and load monitor .......... 17External contacts ................................................ 18Alarm/alarm outputs ............................................ 19

Commissioning and adjustingPreparations ........................................................ 20Filling the water heater and the heating system .... 20Venting the heating system .................................. 20Starting ................................................................ 20Setting the ventilation .......................................... 21Readjustment ...................................................... 21Setting the fan capacity ...................................... 21Opening the front panel ........................................ 22

Setting the automatic heating controlsystem

Offset heating curve -2 ........................................ 23Offset heating curve 0 .......................................... 23Offset heating curve +2 ........................................ 23Setting with diagrams .......................................... 23

ControlMenu system ........................................................ 24Main menus .......................................................... 26Sub-menus .......................................................... 27

Dealing with malfunctionsLow temperature or a lack of hot water ................ 34Low or a lack of ventilation .................................. 34Low room temperature ........................................ 34High room temperature ........................................ 34Switch position “ ” .......................................... 34Alarm indications on the display .......................... 35Resetting the temperature limiter ........................ 36Resetting the high pressure switch ...................... 36Resetting the miniature circuit breakers .............. 36High extract air temperature ................................ 36

ServiceHelping the circulation pump to start .................... 37Cleaning the circulation pump .............................. 37

Component positionsComponent locations .......................................... 38

List of componentsList of components .............................................. 39

Circuit diagramCircuit diagram .................................................... 40

Sensor connectionTemperature sensor data .................................... 41

DimensionsDimensions and setting-out coordinates .............. 42Measuring principle .............................................. 42

Technical dataTechnical specifications ...................................... 43Enclosed kit .......................................................... 43

AccessoriesAccessories .......................................................... 44

GeneralConcise product description ................................ 2Setting table ........................................................ 2

System descriptionPrinciple of operation .......................................... 3System diagram .................................................. 3

Front panelLayout .................................................................. 4Explanation .......................................................... 4

Room temperatureAutomatic heating control system ........................ 6

Default setting ...................................................... 6Changing the room temperature .......................... 6Basic values for the automatic heating control system ...................................................... 7

Maintenance routinesCleaning the air filter ............................................ 8Cleaning the fan .................................................... 8Cleaning the ventilation devices .......................... 9Checking the safety valves .................................. 9Pressure gauge .................................................. 9Extract air temperature ........................................ 9

For the Installer

Page 4: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

General

FIGHTER 360P

2

Installation date

Installer

The serial number (103), should always be stated with all

correspondence with NIBE.

089_ _ _ _ _ _ _ _ _ _ _

Chosen output, immersion heater

Pre-pressure in the expansion tank (0.5 bar on delivery)

Circulation pump setting

Selected fan curve, normal speed

Selected fan curve, speed I

Selected fan curve, speed II

Setting Heating curve selection

Setting Offset heating curve

To be filled in when the heat pump has beeninstalled

In order to get the ultimate benefit from your heatpump FIGHTER 360P you should read through thisInstallation and Maintenance Instruction.

FIGHTER 360P is an exhaust air heat pump. Thismeans that it collects the energy in the ventilation air and uses it for hot water and roomheating.

Microprocessors ensure that the heat pump alwaysworks efficiently.

FIGHTER 360P is a Swedish-made quality productwhich will last a long time and run reliably without unpleasant surprises.

For Home Owners

Page 5: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

System description 3For Home Owners

FIGHTER 360P

FIGHTER 360P comprises an electric boiler with acopper lined water heater and a heat pump whichrecovers energy from the ventilation air. The recov-ered energy is supplied to the heat pump. The heatpump must be installed in a ventilation system intend-ed for mechanical exhaust air.

The output of the immersion heater is max 13.5 kW(Supplied output of 7.5 kW).

When the exhaust air at room temperature passesthrough the evaporator, the refrigerant evaporatesbecause of its low boiling point. In this way the heat inthe room air is transferred to the refrigerant.

The refrigerant is then compressed in a compressor,causing the temperature to rise considerably.

The warm refrigerant is fed to the condenser, which isin the boiler water. Here the refrigerant gives off itsheat to the boiler water, so that its temperature dropsand the refrigerant changes state from gas to liquid.

The refrigerant then goes via filters to the expansionvalve, where the pressure and temperature are furtherreduced.

The refrigerant has now completed its circulation andreturns to the evaporator.

FrånluftAvluft

Förångare

Expansionsventil

Kompressor

Frånluftsfläkt

Kondensor

Elpatron

LEK

When the room air haspassed through the heatpump it is discharged. Thetemperature of the air hasbeen significantly reducedas the heat pump hasextracted the energy in theroom air.

The air from thekitchen fan goesdirectly out into aseparate duct.

The warm roomair is fed toFIGHTER 360P

FIGHTER 360P suppliesthe house with both hotwater and room heating.

Outdoor air is drawninto the house.

The warm room air isdrawn into the air ductsystem.

Air is transportedfrom rooms withoutdoor air devices torooms with exhaustair devices.

Principle of operation

System diagram

Extract air

Evaporator

Expansion valve

Exhaust air

Compressor

Immersionheater

Exhaust air fan

Condenser

Page 6: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Front panel

FIGHTER 360P

For Home Owners

4

Pressure gauge The radiator circuit pressure is displayed here.Gauge graduation is 0 - 4 bar. Normal pressureis 0.5 1.5 bar.

Display

2

1 bar 3

0 4

A B A B A BI II III I II I II

54.1°CVarmvattentemp.

1.0 13.43

SwitchPressure gauge

A

B

C

Left keypad Heating

curve offset

Switchwith three positions 1 - 0 -1 Normal mode. All control functions connect-

ed. 0 Heat pump off.

Standby. This position is used in the eventof operating disturbances.

Display First row:

Layout

Explanation

A CB

D E

Right keypad

F

I II III

A B

I II

I II

Compressor symbol.

Indicates when the compressor is opera-tional.

The switch must not be turned to 1 or “ ” before filling the boiler with water.

Supplement symbol

Displayed when supplementary energy isconnected, usually the immersion heater.The line indicates which powerstep/steps are currently connected.

I 3 kW supplementary power is con-nected

II 6 kW supplementary power is con-nected

III 4,5 kW supplementary power is con-nected

Hot water symbol.

Indicates when the Extra hot water func-tion is activated. A is shown when tempo-rary selected temperature increase is acti-vated and B when periodic temperatureincrease is activated.

Fan symbol.

Indicates when the fan is operational.Normal speed is indicated by just the fansymbol. When one line is visible fanspeed I is activated and when two linesare visible fan speed II is activated.

Heating system symbol.

Indicates when the house is being heat-ed, i.e. the circulation pump is opera-tional. When the heat pump is connectedto two heating systems, I is shown for cir-culation pump 1 and II for circulationpump 2.

Defrosting symbol

Indicates when evaporator defrosting is inprogress.

Value of the current parameter.Second row:

Description of current display parame-ter. Normally shows the Hot watertemperature

Third row:

Page 7: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Front panel 5For Home Owners

FIGHTER 360P

Show the current menu number.Fourth row:

Left keypad

Right keypad

Offset heating curveE

D

F

Operating modeThis button is used to set the requiredoperating mode with regard to permit-ting/blocking the circulation pump andsupplementary energy.

The different operating modes are:

Winter mode:The circulation pump is operational.Operation of the immersion heater is permitted whenthere is a need.

Summer mode: The circulation pump and immersionheater are blocked. However, when Extra hot water isactivated the immersion heater is connected. The cir-culation pump is automatically exercised twice a day.

Spring/Autumn mode:The circulation pump is opera-tional. The immersion heater is disabled. However,when Extra hot water is activated the immersionheater is connected.

The current operating mode is shown on the displaywhen the button is pressed and the mode changeswhen you continue to press the button. The displayreturns to the normal display mode once the enter but-ton is pressed.

Extra hot water The Extra hot water function is activatedusing this button.

24 hours: Means that the hot water tem-perature is increased to 60 °C during 24 hours. Thetemperature then returns to the normal value.

Periodic: Means that the hot water temperature isincreased to 60°C at regular intervals. The interval isset in the menu 1.1, Interval per. XHW. The value isadjustable from 1 to 90 days.

Not selected: Pressing the button again deactivatesthe Extra hot water function.

The current function is shown on the display when thebutton is pressed and the mode changes when youcontinue to press the button. The display returns tothe normal display mode once the enter button ispressed.

Fan speed:This button is used to change the fanspeed. Return to normal speed occursautomatically (Does not apply howeverin the Off position).

Plus buttonThis button is used to scroll through themenu system (forwards) or increase thevalue of the selected parameter.

See the section, Control Menu system.

Minus buttonThis button is used to scroll through themenu system (backwards) or lower thevalue of the selected parameter.

See the section, Control Menu system.

Enter buttonThis button is used to select a lowermenu in the menu system, to activate aparameter change as well as confirm aparameter change.

See the section, Control Menu system.

This knob is used to change the heatingcurve's parallel offset and in doing sothe room temperature. Turning clock-wise increases the room temperature.When the knob is turned menu 2.0 isshown on the display screen and the

value for the calculated supply temperature changes.

Speed II: A choice is made during installation whetherthis should be a reducing or forced mode. A return tonormal speed occurs after a specific time. This time isset under the menu 7.11, Return-time speed II. Thetime can be set from 1 to 10 hours.

Off: Means that the fan stops and hence no ventilationis obtained. Note that the compressor is then blockedtoo, which means no recovery is obtained. NOTE! Inthe Off position there is no automatic return to normalspeed.

Speed I You can choose whether this should be areducing or forced mode during installation. A return tonormal speed occurs after a specific time. This time isadjustable under menu 7.12, Return-time speed I. Thetime can be set from 1 to 10 hours or 1 to 16 days.

Normal: Normal fan speed.

The current function is shown on the display when thebutton is pressed and the mode changes when youcontinue to press the button. The display returns tothe normal display mode once the enter button ispressed.

A key lock can be activated in the mainmenus by simultaneously pressing thePlus and the Minus buttons. The keysymbol will then be shown on the display.The same procedure is used to deactivatethe key lock.

Page 8: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Room temperature

FIGHTER 360P

For Home Owners

6

Automatic heating control systemThe indoor temperature depends on several factors.During the hot season, solar radiation and heat givenoff by people and equipment are sufficient to keep thehouse warm. When it gets colder outside, the heatingsystem must be started. The colder its gets, the hotterthe radiators must be.

This adjustment is made automatically, however thebasic settings must first be made on the boiler, see thesection Room temperature — Default setting.

The basic heating is set using menu 2.4 and with theOffset heating curve knob.

If you do not know the correct settings use the basicdata from the map opposite.

If the required room temperature is not obtained, read-justment may be necessary.

NOTE! Wait one day between settings so that the tem-peratures have time to stabilise.

Readjustment of basic settings.

Cold weather conditionsWhen the room temperature is too low, the heatingcurve value is increased in menu 2.1 by one incre-ment.

When the room temperature is too high, the heatingcurve value is decreased in menu 2.1 by one incre-ment.

Warm weather conditionsIf the room temperature is low, increase the offsetheating curve setting by one step.

If the room temperature is high, reduce the offsetheating curve setting by one step.

Changing the room temperature manually.

If you want to temporarily or permanently lower orraise the indoor temperature relative to the previouslyset temperature, turn the Offset heating curve knobanticlockwise or clockwise. One to three lines approxi-mately represents a 1 degree change in room tempera-ture.

NOTE! An increase in the room temperature may beinhibited by the radiator or floor heating thermostats, ifso these must be turned up.

Basic setting

Changing the room temperature

A B A B A BI II III I II I II

54.1°CVarmvattentemp.

1.0 13.43

Page 9: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Room temperature 7For Home Owners

FIGHTER 360P

Skellefteå

Umeå

Örnsköldsvik

Sundsvall

Hudiksvall

Gävle

Stockholm

Visby

Luleå

JönköpingGöteborg

Borås

HalmstadMarkaryd

Helsingborg

Malmö

VäxjöKalmar

LinköpingNorrköping

Karlskrona

YstadSimrishamn

Örebro

Karlstad

Hässleholm

Uppsala

Västerås

Söderhamn

11 (5)

10 (5)

9 (5)

9 (4)

8 (4)

8 (4)

9 (4)

Gällivare

Östersund

Kiruna

Falun

9 (5)

11 (5)

12 (6)

Example:

Examples of basic data selection:1. House with low temperature* radiator systems

Markaryd = Area 10 (5). Set the heating curve val-ue to 10 in menu 2.1 and the “Heating curve offset”knob to -2.

2. House with floor heating** installed in a concrete floor structure

Markaryd = Area 10 (5). Set the heating curve val-ue to 5 in menu 2.1 and the “Heating curve offset”knob to -1”.

3. House with floor heating** installed in a timberfloor structure

Markaryd = Area 10 (5). Set the heating curve val-ue to 8 (10-2=8) in menu 2.1 and the “Heatingcurve offset” knob to -1”.

* A low temperature radiator systems refers to asystem where the flow temperature needs to be55 °C on the coldest day.

** Floor heating can be dimensioned very differently.Examples 2 and 3 above refer to a system wherethe flow temperature needs to be approximately35 - 40 °C resp 45 - 50 °C on the coldest day.

The values stated on the map apply for the “Heatingcurve selection”.

The first value applies for low temperature * radiatorsystems. “Heating curve offset” is set to -2.

The value in brackets refers to floor heating systems**installed in concrete floor structures. When the systemis Installed in a timber floor structure you can use thenumber before the brackets, but this value must bereduced by two units. In these cases the “Heatingcurve offset” is set to -1.

The map values are usually a good starting point andconcern an approximate room temperature of 20°C.The values can be adjusted later if necessary.

Basic values for the automatic heating control systemThe lower values in the north of Sweden are due tothe lower design outdoor temperature.

Page 10: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Maintenance routines

FIGHTER 360P

For Home Owners

8

Clean the fan every other year by taking it out of theheat pump and carefully brushing the vanes clean.

Set the switch to “0”.

Open the upper front cover by pulling it out by thelower edge, then lifting it up.

To open the inner cover, unscrew the screws inthe outer edges of the cover.

The fan is removed by unscrewing the four screwsas illustrated and disconnecting the fan cable con-nector.

After removing the fan check the condensationtray under the evaporator. At the same time,check that the condensation hose connection isnot blocked.

Assembly takes place in the reverse order.

The heat pump's air filter needs to be cleaned regular-ly (approximately 4 — 5 times per year). The intervalbetween cleaning operations varies and depends onthe amount of dust in the exhaust air.

Set the switch to “0”.

Open the upper front cover by pulling it out by thelower edge, then lifting it up.

Release the filter holder by turning the two blackknobs a quarter of a turn anticlockwise.

Pull out the holder, take out the filter and shake offany dirt. If the filter is very dirty, turn it upside-down and wash it carefully with water.

Check that the filter is not damaged. New originalfilters can be ordered from NIBE.

Assembly takes place in the reverse order.

Also see the section, Alarm indications in the display,FILTER MONITOR.

NOTE! Avoid distorting the fan blades as

this causes imbalance.

Do not use wateror detergents.

21 bar 3

0 4TG

LE

K

Cleaning the fan

FILTER

The heat pump and its ventilation ducting requiresome regular maintenance when the following pointsshould be checked.

The numbers in brackets refer to the section Compo-nent locations.

Cleaning the air filter

Page 11: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Maintenance routines 9For Home Owners

FIGHTER 360P

LEK

+20-2

A B A B A BI II III I II I II

LEK

+20-2

A B A B A BI II III I II I II

Check that the temperature of the extract air (menu4.2) is clearly lower than the room temperature whenthe compressor is operational, also see section Deal-ing with malfunctions — High extract air temperature.It is normal that the extract air temperature varies.

The working range of the heating system is normally0.5 — 1.5 (bar) Check this on the pressure gauge(42).

FIGHTER 360P has two safety valves, one for theheating system and one for the water heater.

The heating system’s safety valve (52) must be com-pletely tight, but the hot water safety valve (47) mayoccasionally release some water after hot water hasbeen used. This is because the cold water, whichenters the water heater to replace the hot water,expands when heated causing the pressure to riseand the safety valve to open.

Check both the pressure relief valves regularly. Check one valve at a time as follows:

Open the valve.

Check that water flows through the valve.

Close the valve. The heating system may need to be refilled after

checking the safety valve (52), see the sectionCommissioning and adjustment — Filling the heat-ing system.

Cleaning the ventilation devices Pressure gauge

Extract air temperature

Efterfyll värmesystemet vid beSe skötselanvisning.

2

1 bar 3

0 4

52

47

The building’s ventilation devices should be cleanedregularly with a small brush to keep the correct venti-lation.

The device settings must not be changed.

NOTE! If you take down more than one ventilationdevice for cleaning, do not mix them up.

Check that the ventilation opening (84), behind thelower front cover, is not blocked. Clean if necessary.

Checking the safety valves5 . 0 ° C

V e n t e d a i r t e m p .4 . 2

Page 12: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

FIGHTER 360P

For the Installer

10

LEK

011007

Art.nr. 611827

2

1 bar 3

0 4

LE

K

Page 13: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

General information for the installer 11

FIGHTER 360P

Current regulations require the heating installation tobe inspected before it is commissioned. The inspec-tion must be carried out by a suitably qualified person.The above applies to installations with a closedexpansion vessel. A new inspection must be madewhen changing the heat pump or the expansion ves-sel.

The heat pump should preferably be erected with itsback about 10 mm from an outside wall in a utilityroom or similar, to minimise noise nuisance. If this isnot possible, a wall that backs on to a bedroom orsome other room where noise would be a problemshould be avoided. Irrespective of the placement thewall should be sound insulated. NOTE! The distancebetween the heat pump and the wall should be atleast 10 mm.

Route pipes so they are not fixed to an internal wallthat backs on to a bedroom or living room.

FIGHTER 360P should be transported and stored ver-tically in the dry. The FIGHTER 360P may however becarefully laid on its back when being moved into abuilding.

The heat pump contains highly inflam-mable refrigerant. Special care shouldbe exercised during handling, installa-tion, service, cleaning and scrapping toavoid damage to the refrigerant systemand in doing so reduce the risk of leak-age.

Transport and storage

Electric boiler mode

Handling

Installation

Inspection of the installation

The volume of the expansion vessel (85) is 12 litresand it is pressurised as standard to 0.5 bar (5 mvp).As a result, the maximum permitted height H betweenthe vessel and the highest radiator is 5 metres; seefigure. If the standard initial pressure in the pressurevessel is not high enough it can be increased byadding air via the valve in the expansion vessel. Theinitial pressure of the expansion vessel must be statedin the inspection document. Any change in the initialpressure affects the ability of the expansion vessel tohandle the expansion of the water. The maximum sys-tem volume excluding the boiler is 285 litres at theabove initial pressure.

Maximum boiler and radiator volumes

H

For the Installer

NOTE!Work on the refrigerant system mustbe done by authorised personnel in

accordance with the relevantlegislation on refrigerants, sup-

plemented by additional requirementsfor flammable gas, for example,

product knowledge as well as serviceinstruction on gas systems with

flammable gases.

The unit can be used exclusively as an electric boiler,to produce heat and hot water, for example before thecollector installation is complete.

Three different operating modes are possible.

Option 1. Electric boiler mode with ventilationSelect menu 8.31 Electric boiler. Activate Yes.Option 2. Electric boiler mode without ventilationSelect menu 8.31 Electric boiler. Activate Yes.Activate fan Off using the Fan speed push button.Option 3. Standby mode “ ”

This mode is used when an outdoor sensor is not con-nected. The heat pump's compressor and electroniccontrol are disabled in the “ ” position.

The fan is operational (speed I) and the immersionheater is controlled by a separate thermostat.

The numerical display is off. The automatic heatingcontrol system is not operational, so manual shuntoperation is required. This is performed by pressing inthe shunt motor knob and then turning it to the pre-ferred position.

NOTE! When returning to normal mode do

not forget to reset the shunt knob to itsoriginal position by turning the knob

until it “jumps out”.

Page 14: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Pipe connections

FIGHTER 360P

12

Pipe installation must be carried out in accordancewith current norms and directives.

The system requires a low-temperature design of theradiator circuit. At DUT, the highest recommendedtemperatures are 55 °C on the supply line and 45 °Con the return line.

When the circulation pump is running, the flow in theradiator circuit must not be completely stopped. In oth-er words, in a system where the radiator flow mightstop because all thermostat valves are closed, theremust be a bypass valve to protect the circulationpump.

The total volume is 240 litres, with 170 litres in thewater heater and 70 litres in the double-jacket space.

The pressure vessel in the FIGHTER 360P isapproved for max 9.0 bar (0.9 MPa) in the waterheater and 2.5 bar (0.25 MPa) in the double jacketspace.

Overflow water from the evaporator collection tray andsafety valves goes via non-pressurised collectingpipes to a drain so that hot water splashes cannotcause injury.

Other heat sources can be docked to the FIGHTER360P Accessories are needed. Contact NIBE AB forinformation.

General Docking

NOTE!The pipe work must be flushed

before the heat pump is connected,so that any contaminants do notdamage the component parts.

For the Installer

To empty the water heater proceed as follows:

Disconnect the overflow pipe from the drain con-nection (79) and connect a hose to a drainingpump instead. Where no draining pump is avail-able, the water can be released into the overflowfunnel (99).

Open the safety valve (47).

Open a hot water tap to let air into the system. Ifthis is not enough, undo a pipe coupling (74) onthe hot water side and pull out the pipe.

The hot water can be drained off through drain valve(51) using an R15 (1/2") hose coupling. Remove thecover (80) from the valve. Now screw on the hosecoupling and open valve (51).

Open safety valve (52) to let air into the system.

Draining the heating systemEmptying the water heater

Hot and cold water are connected to pos (74) (hotwater) and (73) (cold water).

The heat pump should be supplemented with an elec-tric water heater if a bubble pool or other significantconsumer of hot water is installed.

Tap water connection

KV VV

Water heaterCOMPACT

Heat pumpFIGHTER 360P

Page 15: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Pipe connections 13For the Installer

FIGHTER 310

Pump and pressure drop diagrams

Flöde

Till

gäng

ligt t

ryck

, kP

akPa

l/h

10

2000

0

20

400

30

600

40

800

50

1000

60

1200

70

1400 1600 1800 2000

l/s0,50,40,30,20,10

Max flöde: 1700 l/hMax flow: 1700 l/h

Flow

l/hl/s

kPaA

vaila

ble

pres

sure

, kP

a

Page 16: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Ventilation connection

FIGHTER 360

For the Installer

14

FIGHTER 360P is connected so that all ventilation airexcept the kitchen fan passes the evaporator (62) inthe heat pump. The lowest ventilation flow accordingto current standards is 0.35 l/s per m2 floor area. Foroptimum heat pump performance the ventilation flowshould not be less than 110 m3/h. (31 l/s).

The heat pump's installation area should be ventilatedby at least 36 m3/h (10 l/s).

FIGHTER 360P is equipped with a ventilationopening in the base. As a result, an air flow of about 5m3/h (1,4 l/s) is taken directly from the room where theheat pump is installed.

Changing the ventilation capacity is described underElectrical connection - Setting the fan capacity. Seealso Circuit diagram. The numbering of the curvesrefers to the numbering on the fan terminal block (22).

To obtain the necessary air exchange in every room ofthe house, the exhaust air devices must be correctlypositioned and adjusted. A defective ventilation instal-lation may lead to reduced heat pump efficiency andthus poorer operating economy, and may result indamage to the house.

NOTE!A duct in a masonry chimney stack

must not be used for extract air.

To prevent fan noise being transferred to the exhaustair devices, it may be a good idea to install a silencerin the duct. This is especially important if there areexhaust air devices in bedrooms.

As the heat pump contains a flammable refrigerant inthe form of propane (R290), the air ducting systemmust be earthed. This is done by making a soundelectrical connection to the exhaust air and vented airducts with the two earthing cables supplied. Thecables must then be connected to the earthing studson top of the top cover.

Connections should be made via flexible hoses, whichmust be installed so that they are easy to replace. Theextract air duct must be provided with diffusion-tightinsulation over its entire length. Provision must bemade for inspection of the duct. Make sure that thereare no reductions of cross-sectional area in the formof creases, tight bends etc, since this will reduce theventilation capacity. All joins in the ducting must besealed and pop-riveted to prevent leakage.

The air duct system should, at a minimum, be of airtightness class B.

The diagram below shows the available ventilation capacity.

Fan diagram

Ventilation flow Duct installation

Adjustment

400

350

300

250

200

150

100

50

00 100 200 300 400

Luftflöde

Till

gän

glig

t st

atis

kt t

ryck

1 2 3 4 5 6 7 8 9 10

m3/h0 25 50 75 100 l/s

Pammvp

40

30

10

20

The kitchen flue must not be connected to FIGHTER360P.

Exhaust air duct

mmhp Pa

Ava

ilab

le s

tati

c p

ress

ure

Air flowm3/h

l/s

Page 17: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Electrical connection 15For the Installer

FIGHTER 360

FIGHTER 360P must be installed via an isolatorswitch. Other electrical equipment, except the outdoorsensor and the current sensors, are connected at thefactory.

Disconnect the heat pump before insulation testingthe house wiring.

The two immersion heaters have a total maximum out-put of 13.5 kW The power rating as set at the factory is7.5 kW, which corresponds to position C on the knob(101) on the load monitor card (2).

Connection Output as set at the factory

NOTE!Reset the temperature limiter,

it may have tripped during transport.

NOTE! The switch (8) must not be moved

from 1 or “ ” until the boiler hasbeen filled with water. Otherwise the

temperature limiter, thermostat,compressor and the immersion heater

can be damaged.

The automatic heating control system, circulationpump (16) and its cabling, are internally fuse protectedwith a miniature circuit breaker (7).

NOTE! Electrical installation and service mustbe carried out under the supervision of

a qualified electrician. Electricalinstallation and wiring must be carriedout in accordance with the stipulations

in force.

The supply to the heat pump is connected to termi-nal (9) via a strain relief. Connection must not be car-ried out without the permission of the electricity suppli-er and under the supervision of a qualified electrician.The cable entry conduit is dimensioned for cable witha max Ø 19 mm.

The power is controlled via a contactor which is oper-ated by a microprocessor.

The temperature limiter (6) cuts off the supply to theimmersion heater if the temperature rises to between90 and 100 °C; it can be manually reset by pressingthe button on the temperature limiter.

8

The temperature limiter (6) is accessible from behindthe centre front cover and is positioned under theinner protective cover.The temperature limiter is reset by firmly pressing inits button. The button can be accessed from theunderside of the distribution box. The cover on the dis-tribution box does not need to be removed whenresetting.

Resetting the temperature limiter

6

Page 18: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Electrical connection

FIGHTER 310

For the Installer

16

Max phase current

1 2 3 4 5 6 7 8

15

149 10 11 12 13 14 15 16 17

Connecting the outside sensor

The setting of the different max outputs is done usingthe knob (101) on the load monitor card (2).

Install the outside sensor in the shade on a wall facingnorth or north-west, so it is unaffected by the morningsun. The sensor is connected with two-wire cable toterminal block (14) positions 1 and 2, on the load mon-itor card (2).

If a conduit is used it must be sealed to prevent con-densation in the sensor capsule. The minimum cable

cross section should be 0.4 mm2 up to lengths of 50metres, for example, EKKX or LiYY.

7,5 C 15,8

10,5 E 20,2

3,0 A 9,3

Immersion heater, output (kW)Knob positionMax load phase (A)

6,0 B 13,7

9,0 D 18,0

13,5 F 24,5

101

2

Access to the lower electrical connections

Open the centre front cover by removing the fourscrews. The load monitor card (2), microprocessorcard (34), etc are now accessible on the left-handside. Remove the protection plate by loosening thefour screws to gain access to the right-hand side.

011007

10

10

VANADIUM

No.7

CHROME

Åter-ledningradiatorerk.v.

Åter-ledningradiatorer

Blaha blahaoch annat

trams

NOTE! Electrical installation and service

must be carried out under thesupervision of a qualified electrician.

Electrical installation and wiring mustbe carried out in accordance with the

stipulations in force.

Page 19: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Electrical connection 17

FIGHTER 360P

For the Installer

Centralised load control/TariffIn those cases centralised load control or tariff controlis used this can be connected to the terminal block(14) on the load monitor card (2), which is positionedbehind the centre front cover.

When parts of the electrical output (how much is deter-mined by the max output) are to be disconnected, apotential free contact function is connected between 5and 7 on terminal block (14).

When the complete electrical output is to be discon-nected, a potential free contact function is connectedbetween 6 and 7 on terminal block (14).

Load monitorFIGHTER 360P is equipped with an internal load mon-itor.

When the load monitor senses an overcurrent on oneof the phases, the immersion heater will step down theoutput until it can be connected again.

The control system must be set for the installation’smain fuse so that the load monitor can work correctly.This is done using the knob (100), marked fuse on theload monitor card (2), which is positioned behind thecentre front cover. The supplied current sensor is con-nected to the terminal block’s (14) terminals marked 8to 11. Terminal 11 is the common conductor for thethree current sensors.

Cable type: unscreened LiYY, screened LiYCY. Cable cross section, at least 2 x 0.25 for cable lengths up to

50 m.

Centralised load control and load monitor

1 2 3 4 5 6 7 814

9 10 11 12 13 14 15 16 17

1 2 3 4 5 6 7 814

9 10 11 12 13 14 15 16 17

14

100

Page 20: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Electrical connection

FIGHTER 360P

18For the Installer

Contact for changing the room tempera-tureAn external contact function can be connected toFIGHTER 360P to change the supply temperature andin doing so change the room temperature, for example,a room thermostat or a timer. The contact should bepotential free and is connected between terminals 3 and4 on terminal block (14) on the load monitor card (2).When the contact is made the supply temperature ishigher or lower than the selected curve slope. The val-ue for the change is set on menu 2.6, Compensation.The value is adjustable between 25 and +25. One stepcorresponds to one degree of the calculated supplytemperature.

Contact for activation of Extra hot waterAn external contact function can be connected to FIGHT-ER 360P for activation of the Temporary Extra hot waterfunction. The contact should be potential free and non-locking and is connected via the edge board connectorbetween positions 1 and 2 down on the lower part of theleft connection row on the load monitor card (2).When the contact makes for at least one second theTemporary Extra hot water function is activated. An auto-matic return to the previously set function occurs after 24hours. This connection requires the accessory XTS 20.

Contact for activation of Fan speed IIAn external contact function can be connected toFIGHTER 360P for activation of fan speed II. The con-tact should be potential free and non-locking and isconnected via the edge board connector between posi-tions 3 and 4 down on the lower part of the left connec-tion row on the load monitor card (2). When the contactmakes for at least one second Fan speed II is activat-ed. The return to normal speed occurs according to thetime set in menu 7.11, Return-time speed II. This con-nection requires the accessory XTS 20.

External contacts

1 2 3 4 5 6 7 814

9 10 11 12 13 14 15 16 17

4X4.1

X6.1

4X4.1

X6.1

Page 21: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Electrical connection 19

FIGHTER 360P

For the Installer

Low priority alarmsThe following give a low priority alarm:Filter monitor, the air filter needs to be cleaned threetimes a year. This is indicated as a low priority alarmand the operation of FIGHTER 360P is not generallydisturbed by this.Sensor alarm, fault on the low priority sensor gives alow priority alarm and the operating mode is switchedto winter and any automatic operations are disabled.Low priority sensors are as follows:Outdoor sensor-Evaporation sensor-Return sensor-Extract air sensor-Exhaust air sensor.

High priority alarmsThe following give a high priority alarm:High pressure switch (HP) has tripped. Indicated asHP-alarm. The compressor is blocked and FIGHTER360P switches to electric boiler mode.LP pressure switch (LP) has tripped. Indicated as LP-alarm. The compressor is blocked and FIGHTER 360Pswitches to electric boiler mode.Temperature limiter (TB) has tripped. Indicated as aTL-alarm. The compressor and the immersion heaterare blocked, any set automatic operations are disabledas the operating mode switches to spring/autumn.A supply sensor fault is indicated as a Sensor alarm.FIGHTER 360P is force-run solely for hot water charg-ing.

Alarm/alarm outputs

MatningMax 2A/250 VAC

UtgångHögprioriterat larm

MatningMax 2A/250 VAC

UtgångLågprioriterat larm

A compressor sensor fault is indicated as a Sensoralarm. The compressor is blocked and FIGHTER360P switches to electric boiler mode.An immersion heater sensor fault is indicated as aSensor alarm. Immersion heater operation is blocked,any set automatic operations are disabled as theoperating mode switches to spring/autumn.A hot water sensor fault is indicated as a Sensoralarm. FIGHTER 360P is force-run solely for hot watercharging and automatic mode is engagedExternal indication of alarms is possible through therelay function on the load monitor card (2).

In the event of an alarm the relay contact makes

Supplymax 2A/250 VAC

OutputHigh priority alarm

OutputLow priority alarm

Supplymax 2A/250 VAC

Page 22: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Commissioning and adjusting

FIGHTER 360P

20

LEK

46

44

44

98

50

101

6

97 Åter-ledningradiatorerk.v.v.v.

Blaha blahaoch annat

trams

Åter-ledningradiatorer

Blaha blahaoch annat

trams

49

Vent FIGHTER 360P through the safety valve (52)and the rest of the heating system through the rele-vant venting valves.

Keep topping up and venting until all air has beenremoved and the pressure is correct.

Check that the switch (8) is set to 0.

Check that valves (44) and (50) are fully open andthat the temperature limiter (6) has not tripped (pressthe button firmly).

Fill the condensation water hose (97) with a little waterto prevent it making a noise. This is done by looseningthe hose which is located on the waste water pipe (98)and pouring water in the end of the hose so a waterseal arises. Refit the hose.

Venting the heating system

Starting

Preparations

The water heater is filled by first opening a hot water tap and then opening the filling

valve (46) fully. This valve should then remain fully open. When water comes out of the hot water tap, it can be closed. Open the filling valve (49). The boiler part of the

heat pump and the radiator system are now filledwith water.

After a while the pressure gauge (42) will show ris-ing pressure. When the pressure reaches 2.5 (bar)(approx. 25 mvp) a mixture of air and water startsto emerge from the safety valve (52). The filling valve then closed (49).

Turn the safety valve (52) until the boiler pressurereaches the normal working range (0.5 - 1.5 bar).

Filling the water heater and the heating system

Set the switch (8) to 1. When the exhaust air tempera-ture drops below 16 °C the compressor does not start.The immersion heater is then used for heating. Whenthe exhaust air temperature exceeds 16 °C the com-pressor is permitted to start automatically.

For the Installer

NOTE!Heating curve in menu 2.1 and Max

supply temp. in menu 2.5 are adjustedaccording to the heating system in

question.

Page 23: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Commissioning and adjusting 21

FIGHTER 360P

For the Installer

Air is initially released from the hot water and ventingmay be necessary. If bubbling sounds can be heardfrom the heat pump, the entire system requires furtherventing. NOTE! Safety valve (52) also acts as a man-ual venting valve. Operate it with care, since it opensquickly. When the system is stable (correct pressureand all air eliminated) the automatic heating controlsystem can be set as required. See the section Roomtemperature - Setting the Automatic heating controlsystem and Front panel.

ReadjustmentThe ventilation flow and correct outlet on the fan termi-nal block (22) are set out on the ventilation drawing.

Change the fan capacity by moving the grey cableon the fan terminal block (22) if necessary. Use thelowest possible output to obtain the lowest noiselevels.

Make sure that all outdoor air devices are fully open.

Set correct ventilation flows on the exhaust airdevices.

Now move the white and brown cables to obtain therequired exhaust air flow for fan speeds I and II. Thewhite cable corresponds to position I and the brownposition II. Note however that the exhaust air flowmust never fall below 110 m3/h (31 l/s).

Setting the ventilation

The ventilation capacity is selected by moving thebrown, grey and white cables to an appropriate outleton the terminal block (22). See the section, Ventilationconnection - Fan diagram to choose appropriate con-nections.

The grey cable corresponds to the fan speed in nor-mal mode. The white cable corresponds to speed I. The brown cable corresponds to speed II.Example:Normal: Lowest possible fan speed is chosen to

obtain the planned ventilation flow (greycable).

Speed II: Highest possible fan speed is chosen, (forced) however consider ventilation noise (brown

cable).Speed I Lowest possible fan speed is chosen (reducing) where the min flow is maintained (white

cable).

Outlet Voltage (V)1 1002 1103 1254 1405 1556 1707 1858 2009 21510 230

Setting the fan capacity

22

5 6 7 8 9 103 41 2

GråVit Brun

In those cases the cable for normal mode is connect-ed to terminal 10 on terminal block (22) a forced fanspeed cannot be obtained. Two different reducingmodes should then be chosen.

whi

te

grey

brow

n

Page 24: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Commissioning and adjusting

FIGHTER 360P

For the Installer

22

LE

K54

57

28

22

29

13

To lower the front panel, unscrew the two screws atthe top of the panel. The panel can then be loweredto the horizontal position (where it rests on stops oneither side of the front panel).

Opening the front panel

Page 25: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Setting the heating controls 23For the Installer

FIGHTER 360P

FIGHTER 360P is equipped with outdoor temperaturecontrolled automatic controls. This means the supplytemperature is regulated in relation to the current out-door temperature.

The diagram is based on the dimensioned outdoortemperature in the area and the dimensioned supplytemperature of the heating system. When these twovalues meet, the heating control’s curve slope can beread. This is set under menu 2.1, Heating curve.

A suitable value is set using the knob on the frontpanel, Offset heating curve (38). A suitable value forfloor heating is -1 and for radiator systems -2.

30

40

50

60

70°C

FR

AM

LE

DN

ING

ST

EM

PE

RA

TU

R

- 40 °C

UTETEMPERATUR

- 10010 - 20 - 30

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

KURVLUTNING

- 5

+ 5

PARALLELLFÖRFLYTTNING

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

- 40 °C

UTETEMPERATUR

- 10010

- 5

+ 5

30

40

50

60

70°C

FR

AM

LE

DN

ING

ST

EM

PE

RA

TU

R

- 20 - 30

PARALLELLFÖRFLYTTNING

KURVLUTNING

1514 13 12 11 108

7

6

5

4

3

2

1

- 40 °C

UTETEMPERATUR

- 10010

- 5

+ 5

30

40

50

60

70°C

FR

AM

LE

DN

ING

ST

EM

PE

RA

TU

R

- 20 - 30

PARALLELLFÖRFLYTTNING

9

KURVLUTNING

Offset heating curve 0

Offset heating curve -2Setting using diagrams

Offset heating curve +2

HEATING CURVE

HEATING CURVE

HEATING CURVE

OFFSET HEATING CURVE

OFFSET HEATING CURVE

SUPP

LY T

EMPE

RA

TUR

ESU

PPLY

TEM

PER

ATU

RE

SUPP

LY T

EMPE

RA

TUR

E

OUTSIDE TEMPERATURE

OUTSIDE TEMPERATURE

OUTSIDE TEMPERATUREOFFSET HEATING CURVE

Page 26: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

ControlFor the Installer

24

FIGHTER 360P

The display screen shows information about the statusof the heat pump. Menu 1.0 is normally shown on thedisplay screen.

The Plus and Minus buttons and the Enter button areused to scroll through the menu system as well as tochange the set value in some menus.

The Plus button is used to move forward to the nextmenu on the current menu level and to increase thevalue of the parameter in menus where this is possi-ble.

The Minus button is used to move back to the previousmenu on the current menu level and to decrease thevalue of the parameter in menus where this is possi-ble.

The Enter button is used to select submenus of thecurrent menu, to permit parameters to be changedand confirm any changes to parameters. When themenu number ends with a zero this indicates there is asubmenu.

Changing a parameter (value):

Access the required menu.

Press the Enter button, the numerical value starts toflash

Increase or decrease the value with the Plus/Minusbuttons.

Confirm by pressing the Enter button.

Menu 1.0 is automatically displayed again 30 sec-onds after pressing the last button.

The structure of the menu system is shown above.

Menu system

Hotwater-temperature1.0

Supplytemperature2.0

Intervalper. XHW1.1

Temperaturecompr sensor1.2

Temperatureel. heat sensor1.3

Heating curve2.1

Return1.4

Offset heatingcurve2.2

Returntemperature2.3

Min. supplytemperature2.4

Max. supplytemperature2.5

Compensation2.6

Return2.7

Outdoor temperature4.0

Evaporatingtemperature4.1

Vented airtemperature4.2

Exhaust airtemperature4.3

Return4.4

Page 27: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Control

FIGHTER 360P

Menu system

Fan settings7.10

Return-time speed II7.11

Return-time speed I7.12

Return7.13

Other settings7.0

Servicemenues8.0

Operating modesettings7.20

Auto Operatingmode7.21

Stop circula-tionspump7.22

Stop electric heater7.23

Return7.24

Other7.30

Showservicemenues7.31

Return7.32

Return7.4

Compressorsettings8.10

Quickstartcompressor8.11

Stoptime defrosting8.12

Compressorstarts8.13

Operationtimecompressor8.14

Return8.15

Electric heatersettings8.20

Quickstartelectric heater8.21

Time factorelectric heater8.22

Return8.23

Language8.5

Other8.60

Current phase 18.61

Current phase 28.62

Current phase 38.63

Ratio of trans-former EBV8.64

Return8.65

Return5050

8.7

Operationsettings8.30

Electric boiler8.31

Circulationpump8.32

Return8.34

LCD settings8.40

LCD contrast8.41

Backlight LCD8.42

Default backlight8.43

Return8.44

Visas endast då meny7.31 är aktiverad.

25

Page 28: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Control

FIGHTER 360P

Main menus

Meny 1.0 Hotwater temperatureThe current water temperature (83) in the outer jacketroughly level with the water heater’s lower end-plate isshown here. Note that the hot water temperature atthe top of the tank is usually higher.

Meny 2.0 Supply temperatureThe current supply temperature (89) for the heatingsystem is shown here with the calculated supply tem-perature in brackets.

Meny 4.0 Outdoor temperatureThe current outdoor temperature is shown here. Mea-sured via the outside sensor (15).

Meny 7.0 Other settingsTime settings for alternative fan modes and tempera-ture levels for the circulation pump and immersionheater regarding automatic operating modes.

Meny 8.0 ServicemenusNOTE! This menu and its sub-menus are only shownon the display screen when access has been selectedin menu 7.31.

Values can be read and various settings can be madefrom these submenus. NOTE! These settings shouldonly be made by persons with the necessary exper-tise.

26

5 4 . 1 ° CH o t w a t e r t e m p .1 . 0

4 5 . 0 ( 4 6 . 0 ) ° CS u p p l y t e m p e r a t u r e .2 . 0

- 1 4 . 2 ° CO u t d o o r t e m p .4 . 0

O t h e r s e t t i n g s7 . 0

S e r v i c e m e n u s9 . 0

Page 29: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Control

FIGHTER 360P

Meny 1.1 Interval periodical extra hotwaterThe menu shows how often the hot water temperatureis raised from the normal level to Extra hot water levelwhen the function Periodic extra hot water is activat-ed.

The value is adjustable between 1 and 90 days.

Meny 1.2 Temperature compressor sensorThe current temperature of the compressor sensor(94) is shown here.

Submenus

Meny 1.3 Temperature immersion heater sensorThe current temperature of the immersion heater sen-sor (88) is shown here.

Meny 1.4 ReturnPressing the Enter button returns you to menu 1.0.

Meny 2.1 Heating curveThe selected curve slope (heating curve) is shownhere. The value can be set between curve 1 and 15.

Meny 2.2 Offset heating curveThe selected offset heating curve is shown here. Thevalue is adjustable between 10 and +10. NOTE! Thevalue cannot be changed using the Plus and Minusbuttons only with the Offset heating curve knob.

Meny 2.3 Return temperatureThe current temperature of the return water (93) fromthe heating system is shown here.

Meny 2.4 Min. supply temperatureThe set minimum level for the supply temperature tothe heating system is shown here. The calculated sup-ply temperature never drops below this level irrespec-tive of the outdoor temperature, curve slope or offsetheating curve. The value is adjustable between 10and 65 °C.

Meny 2.5 Max. supply temperatureThe set maximum level for the supply temperature tothe heating system is shown here. The calculated sup-ply temperature never exceeds this level irrespectiveof the outdoor temperature, curve slope or offset heat-ing curve. The value is adjustable between 10 and 65°C

27

1 4 d a y sI n t e r v a l p e r . X H W1 . 1

5H e a t i n g c u r v e2 . 1

- 2O f f s e t h e a t i n g c u r v e2 . 2

4 0 . 5 ° CT e m p . c o m p . s e n s o r1 . 2

3 8 . 3 ° CR e t u r n t e m p2 . 3

1 5 ° CM i n . s u p p l y t e m p .2 . 4

5 5 ° CM a x . s u p p l y t e m p .2 . 5

4 4 ° CT e m p . e l . h e a t . s e n s o r1 . 3

R e t u r n1 . 4

Page 30: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

ControlFor the Installer

FIGHTER 360P

Submenus

Meny 4.1 Evaporationg temperatureThe current evaporation temperature is shown here.This is the temperature of the refrigerant when thishas passed the expansion valve. Measured by sensor(86).

Meny 4.2 Vented air temperatureThe current extract air temperature is shown here.This is the temperature of the ventilation air when ithas passed the heat pump. Measured by sensor (87).

Meny 4.3 Exhaust air temperatureThe current exhaust air temperature is shown here.This is the temperature of the ventilation air before itpasses the heat pump. Measured by sensor (92).

Meny 4.4 ReturnPressing the Enter button returns you to menu 4.0.

Meny 2.6 Compensation.Connecting an external contact, see Electrical con-nections - External contacts, for example, a room ther-mostat or a timer allows you to temporarily or periodi-cally raise or lower the supply temperature and withthat the room temperature. When the external contactis made the calculated supply temperature is changedby the number of degrees shown here. The value isadjustable between -25 and +25.

Meny 2.7 ReturnPressing the Enter button returns you to menu 2.0.

28

0 ° CC o m p e n s a t i o n2 . 6

4 . 4 ° CE v a p o r a t i o n g t e m p .4 . 1

5 . 0 ° CV e n t e d a i r t e m p .4 . 2

2 1 . 2 ° CE x h a u s t a i r t e m p .4 . 3

R e t u r n4 . 4

R e t u r n2 . 7

Page 31: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Control

FIGHTER 360P

Submenus

Meny 7.10 Fan settingsSettings can be made regarding the fan speed in thesubmenus to this menu.

Meny 7.11 Return-time speed IIHere you select the time that should apply for fanspeed II when activated using the Fan speed button, i.e. when the return to normal fan speed should takeplace. The value can be set from 1 to 10 hours.

Meny 7.12 Return-time speed IHere you select the time that should apply for fanspeed I when activated using the Fan speed button,i.e. when the return to normal fan speed should takeplace. The value can be set within the ranges 1 to 10hours or 1 to 16 days.

Meny 7.13 ReturnPressing the Enter button returns you to menu 7.10.

Meny 7.20 Operating mode settingsSettings are made in the submenus to this menu tostop and start the circulation pump and immersionheater.

Meny 7.21 Auto Operating modeHere you select whether blocking of the circulationpump and immersion heater should take place auto-matically as a function of the outdoor temperature(position Yes) or whether blocking should take placemanually via the operating mode button (position No).

Meny 7.22 Stop circulation pumpHere you select the outdoor temperature when the cir-culation pump shall automatically stop, i.e. the tem-perature when heat production should cease. Thefunction only comes into force when Yes is selected inmenu 7.21. The value is adjustable between 14 and25 °C.

Meny 7.23 Stop immersion heaterHere you select the outdoor temperature that auto-matically blocks the immersion heater, i.e. the temper-ature when supplementary energy is not used. Thefunction only comes into force when Yes is selected inmenu 7.21. The value is adjustable between 5 °C andthe set value for the circulation pump (14-25 °C) undermenu 7.22.

Meny 7.24 ReturnPressing the Enter button returns you to menu 7.20.

29

F a n s e t t i n g s7 . 1 0

O p e r a t i n g m o d e s e t t .7 . 2 0

N oA u t o O p e r a t i n g m o d e7 . 2 1

1 7 ° CS t o p c i r c . p u m p7 . 2 2

1 0 ° CS t o p e l . h e a t e r7 . 2 3

R e t u r n7 . 2 4

4 hR e t u r n - t i m e s p e e d I I7 . 1 1

4 hR e t u r n - t i m e s p e e d I7 . 1 2

R e t u r n7 . 1 3

Page 32: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Control

FIGHTER 360P

Meny 7.31 Show service menuesWhen the option Yes is selected the service menus(menu 8.0 and its submenus) become available.When the No option is selected the service menus arenot shown. An automatic return to No takes placeapproximately 30 minutes after the last button ispressed.

Meny 7.32 ReturnPressing the Enter button returns you to menu 7.30.

Meny 7.4 ReturnPressing the Enter button returns you to menu 7.0.

Meny 7.30 OtherUsing the submenus to this menu you can chosewhether the service menus (menu 8.0 and its sub-menus) are to be available or not.

Meny 8.10 Compressor settings.Values can be read and various settings can be madefor the compressor from these submenus.

Meny 8.11 Quickstart compressor.Pressing the Enter button, Plus button and then theEnter button again disables the pressure equalisationtime for the compressor.

Meny 8.12 Stoptime defrostningThe required defrosting time is set here, i.e. the timethat the compressor is at a standstill so that evapora-tor defrosting can take place when necessary. Thevalue is adjustable between 15 and 25 minutes.

Meny 8.13 Compressor startsThe number of times that the compressor has beenstarted since the first start up is shown here. The val-ue is saved in the microprocessor and thus is not reseteven when the heat pump is switched off using themain power switch.

Meny 8.14 Operationtime compressorThe number of hours that the compressor has been inoperation since the first start up is shown here. Thevalue is saved in the microprocessor and thus is notreset even when the heat pump is switched off usingthe main power switch.

Submenus

30

O t h e r7 . 3 0

C o m p r e s s o r s e t t i n g s8 . 1 0

N oQ u i c k s t a r t c o m p .8 . 1 1

1 5 m i nS t o p t i m e d e f r o s t i n g8 . 1 2

4 3 2C o m p r e s s o r s t a r t s8 . 1 3

7 3 0 hO p e r a t . t i m e c o m p r . 8 . 1 4

N oS h o w s e r v i c e m e n u e s7 . 3 1

R e t u r n7 . 3 2

R e t u r n7 . 4

Page 33: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Control

FIGHTER 360P

Submenus

Meny 8.15 ReturnPressing the Enter button returns you to menu 8.10.

Meny 8.20 Immersion heater settingsValues can be read and various settings can be madefor the immersion heater from these submenus.

Meny 8.21 Quickstart immersion heaterNormally the electrical output of the immersionheaters is limited to a maximum of 6 kW for the firsttwo hours after the heat pump has been started, i.e.after the main power switch has been set to 1.

Pressing the Enter button, Plus button and the Enterbutton again in this menu disables this two hour delay.

Meny 8.22 Time factor immersion heaterThe time factor of the immersion heater since firststart up is shown here. The value is saved in themicroprocessor and thus is not reset even when theheat pump is switched off using the main powerswitch.

Meny 8.23 ReturnPressing the Enter button returns you to menu 8.20.

Meny 8.30 Operating settingsForce control of the electric boiler and circulationpump can be activated in the submenus to this menu.

Meny 8.31 Electric boilerThe heat pump can be set in electric boiler mode fromhere. This mode means the compressor is blocked,but all other components function as normal. Thismode can be activated if a fault is discovered on thecompressor or any other component in the cooling cir-cuit. Note no energy savings are made in this mode.Once the fault has been rectified the heat pumpshould be switched to normal mode again. The elec-tric boiler mode is activated when Yes is shown on thedisplay screen, otherwise No is shown. When theelectric boiler mode is activated the immersion heaterrespective circulation pump cannot be blocked withthe operating mode button.

Meny 8.32 Circulation pumpThe operating mode of the circulation pump for theheating system can be force controlled from thismenu. When On is selected the circulation pump runsconstantly. When Off is selected the circulation pumpis blocked. Note however that a change in the operat-ing mode using the operating mode button disablesthe change made in this menu.

Meny 8.34 ReturnPressing the Enter button returns you to menu 8.30.

31For the Installer

R e t u r n8 . 1 5

O p e r a t i n g s e t t i n g s8 . 3 0

N oE l e c t r i c b o i l e r8 . 3 1

O nC i r c u l a t i o n p u m p8 . 3 2

R e t u r n8 . 3 2

E l . h e a t e r s e t t i n g s8 . 2 0

N oQ u i c k s t a r t e l . h e a t e r8 . 2 1

8 9T i m e f a c t o r e l . h e a t8 . 2 2

R e t u r n8 . 2 3

Page 34: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Control

FIGHTER 360P

Meny 8.40 LCD settingsSettings concerning the readability of the displayscreen are made from the submenus.

Meny 8.41 LCD contrastThe contrast of the LCD is set here. The value isadjustable between 0 and 31.

Meny 8.42 Backlight LCDHere you choose whether the display screen’s back-ground light should be activated (Yes) or not (No).

Meny 8.43 Default backlightNOTE! This menu is only shown when Yes has beenselected in menu 8.42.

When the OFF option has been selected the displayscreen is normally not lit but the backlight comes onwhen a button has been pressed. When Low intensityis chosen the backlight is normally on a low level.When a button is pressed the light strength increasesto normal.

The return to a non lit display and low lighting takesplace automatically after approximately 30 minutes.

Meny 8.44 ReturnPressing the Enter button returns you to menu 8.40.

Meny 8.5 LanguageHere you select the language to be used on the dis-play screen.

Meny 8.60 OtherSettings can be made regarding the current transform-ers for the load monitor in the submenus to this menu

Meny 8.61 Current phase 1When the current transformers are installed the powerconsumption for the incoming phase 1 is shown here.LOW is shown when the current transformers are notinstalled or when the phase current is low.

Meny 8.62 Current phase 2When the current transformers are installed the powerconsumption for the incoming phase 2 is shown here.LOW is shown when the current transformers are notinstalled or when the phase current is low.

Meny 8.63 Current phase 3When the current transformers are installed the powerconsumption for the incoming phase 3 is shown here.LOW is shown when the current transformers are notinstalled or when the phase current is low.

Submenus

32

L C D s e t t i n g s8 . 4 0

R e t u r n8 . 4 4

E n g l i s hL a n g u a g e8 . 5

O t h e r8 . 6 0

L o wC u r r e n t p h a s e 18 . 6 1

L o wC u r r e n t p h a s e 28 . 6 2

L o wC u r r e n t p h a s e 38 . 6 3

0L C D c o n t r a s t8 . 4 1

Ye sB a c k l i g h t L C D 8 . 4 2

L o w i n t e n s .D e f a u l t b a c k l i g h t 8 . 4 3

Page 35: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

FIGHTER 360P

Submenus

For the Installer

Control

Meny 8.64 Ratio of transformer EBVThe transfer value must be defined depending on thecurrent transformers used for the load monitor card.This is done in this menu. The value is adjustablebetween 100 and 900 in increments of 10. The setting300 applies for the supplied current transformers.

Meny 8.65 ReturnPressing the Enter button returns you to menu 8.60.

Meny 8.7 ReturnPressing the Enter button returns you to menu 8.0.

33

3 0 0R a t i o o f t r a n s f . E B V8 . 6 4

R e t u r n8 . 6 5

R e t u r n8 . 7

Page 36: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Actions with operating disturbances

FIGHTER 360P

In the “ ” position the heat pump's compressor andelectronic control are disabled.

The fan is operational (speed I) and the immersionheater is controlled by a separate thermostat.

The numerical display is off The automatic heatingcontrol system is not operational, so manual shuntoperation is required. This is performed by pressing inthe shunt motor knob and then turning it to the pre-ferred position.

Switch position “ ”

If the operating disturbance cannot be rectified by means ofthe above an installation engineer should be called.

If necessary set the Switch to “ ” (manual shunt operation necessary).

Incorrect values for the parameters Max. supplytemp. (menu 2.5), Heating curve (menu 2.1) or Off-set heating curve (menu 2.2).

High room temperature

NOTE! The hot water capacity can be increased for24 hours by pressing in the button (18).

Large amounts of hot water were used. Circuit or main MCB tripped. Possible earth circuit-breaker tripped. Switch (8) set to 0. MCB (7) tripped. See the section Dealing with mal-

functions — Resetting the miniature circuit break-ers.

Tripped temperature limiter (6). (Contact service) Switch (25) not correctly set. Closed or throttled filler valve (46) on the water

heater.

Low temperature or a lack ofhot water

Circuit or main MCB tripped. Possible earth circuit-breaker tripped. MCB (7) tripped. See the section Dealing with mal-

functions — Resetting the miniature circuit break-ers.

Tripped temperature limiter (6). (Contact service). Incorrect values for the parameters Max. supply

temp. (menu 2.5), Heating curve (menu 2.1) or Off-set heating curve (menu 2.2).

Circulation pump (16) stopped. See the sectionDealing with malfunctions — Starting the pump.

Air in boiler or system. Close valves (44) and (50) in the radiator circuit.

Initial pressure in expansion vessel too low. This isindicated by low pressure on the pressure gauge(42). Contact the installer.

Filter (63) clogged (possibly replace). Exhaust air device blocked or throttled down too

much. Circuit or main MCB tripped. Possible earth circuit-breaker tripped. MCB (7) tripped. See the section Dealing with mal-

functions — Resetting the miniature circuit break-ers.

Fan speed reduced (position I and/or position II) or Off is activated.

Low room temperature

Low or a lack of ventilation

In the event of malfunctions or operating disturbances first check the points below:

NOTE! When returning to normal mode donot forget to reset the shunt knob toits original position by turning the

knob until it “jumps out”.

LEK

+20-2

A B A B A BI II III I II I II

34

Page 37: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Actions with operating disturbances

FIGHTER 360P

NOTE! The product’s serial number

should always be stated with allcorrespondence with NIBE.

089_ _ _ _ _ _ _ _ _ _ _

FILTER-ALARMThis information is shown every three months and is acall for the air filter to be cleaned, see the sectionMaintenance routines — Cleaning the air filter. Theinformation disappears when the filter has beencleaned and the main power switch is set to 1 again.

LP-ALARMThis information is shown when the low pressureswitch in the cooling circuit has tripped. This may becaused by a too low ventilation flow or too little refrig-erant. The information disappears when the pressureswitch resets (automatically) and the main powerswitch is set to 1 again.

SENSOR-ALARMThis information is shown when one of the tempera-ture sensor malfunctions, for example, a broken cableor a short circuit. The information disappears when thecause of the fault has been rectified and the mainpower switch is set to 1 again.

Alarm indications on the displayOther information can also be shown on the displaybesides the standard information. This applies withmalfunctions or for calls to take action. This type ofinformation is only shown in menu 1.0 (The displayalways automatically returns to menu 1.0 approxi-mately 30 minutes after the last button was pressed).This information alternates with menu 1.0’s standardinformation. At the same time the display’s back-ground lighting flashes.

The following information can be shown.

35

F I L T E R - A L A R M1 . 0

L P - A L A R M1 . 0

S E N S O R - A L A R M1 . 0

Page 38: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Actions with operating disturbances

When the extract air temperature (87) (read on menu4.2) is only insignificantly lower than the room temper-ature at the same time as the compressor is opera-tional, this indicates a probable fault in the refrigerantcircuit or its controller. Request a service. When thecompressor is not operational the extract air tempera-ture lies at about the same level as the room tempera-ture.

High extract air temperature

The MCB (7) is accessible behind the upper frontaccess panel and is located to the right of the panel.Normal mode of the MCB is 1 (up).

Resetting the miniature circuit breakers

Press the button on the top of the tripped high pressureswitch to reset it; see diagram. The pressure switch isaccessible by opening the filter cover.

High pressure pressostat

Resetting the high pressure switch

LEK

+20-2

A B A B A BI II III I II I II

HP-ALARMThis information is shown when the high pressureswitch in the cooling circuit has tripped. This maydepend on too high values being set in the menus 2.1Heating curve, 2.2 Offset heating curve, 3.1 Heatingcurve 2 and/or 3.2 Offset heating curve 2. The infor-mation disappears when the pressure switch resets ()and the main power switch is set to 1 again.

TL-ALARMThis information is shown when the temperature lim-iter for the immersion heater has tripped. The informa-tion disappears when this is done and the main powerswitch is set to 1 again.

The temperature limiter (6) is accessible from behindthe centre front cover and is positioned under theinner protective cover.The temperature limiter is reset by firmly pressing inits button. The button can be accessed from theunderside of the distribution box. The cover on the dis-tribution box does not need to be removed whenresetting.

Resetting the temperature limiter

6

36

FIGHTER 360P

T L - A L A R M1 . 0

H P - A L A R M1 . 0

2 0 . 0 ° CV e n t e d a i r t e m p .4 . 2

Page 39: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

Service

FIGHTER 360P

Shut down FIGHTER 360P by turning the switch(8) to 0.

Remove the lower front cover.

Loosen the air screw with a screwdriver. Hold acloth around the screwdriver blade as a certainamount of hot water may run out.

Insert a screwdriver and turn the pump rotor.

Screw in the air screw.

Start FIGHTER 360P and check whether the circu-lation pump runs.

It is usually easier to start the circulation pump withFIGHTER 360P running, switch (8) set to 1. If helpingthe circulation pump to start is performed with FIGHT-ER 360P running, be prepared for the screwdriver tojerk when the pump starts.

Helping the circulation pump to start

Venting screw

16

LE

K

GR

UN

DFO

SType

UP

S25 -

60

130

P/N

:59526447

230V

-

HE

JS

AN

PC

;0017N

IBD

K50H

z

IP 44

TF

110

Cla

ss H

Max. 1

0bar

2.5

uF

45

0.2

065

0.3

090

0.4

0

1m(A

)P,

(W)

For the Installer

Rotor unit

Drive sideA

LEK

GR

UN

DFO

STyp

eU

PS

25

- 6

01

30

P/N

:59

52

64

47

23

0V

-

HE

JS

AN

PC

;00

17

NIB

DK

50

Hz

IP

44

TF

1

10

Cla

ss

HM

ax. 1

0b

ar

2.5

uF

45

0.2

06

50

.30

90

0.4

0

1m(A

)P,

(W)

B

LEK

C

LEKD

Set the switch (8) to 0.

Close the shut-off valves before and after the cir-culation pump

Loosen the venting screw.

Remove the connection cover.

Loosen the power cable.

Remove the drive side from the pump housing byloosening the screws. Now dismantle the drive side(fig. A).

Remove the rotor unit (including pump housing) bycarefully pulling the pump rotor. If it sits firmly, itcan be loosened by knocking the rear of the shaft(fig. B).

Clean inside the stator can using a cleaning agent(fig. C).

Also clean the rotor unit using the cleaning agentand lubricate the O-ring with, for example, a soapsolution (fig. D).

Refit the rotor unit.

Re-assemble the drive side (the flat packing is bestplaced on the pump housing).

Connect the power cable.

Open the shut-off valves.

Set the switch (8) to 1.

Cleaning the circulation pump

37

Page 40: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Component placement

FIGHTER 360P

LEK

011007

Art.nr. 611827

2

1 bar 3

0 4

Åter-ledningradiatorerk.v.v.v.

Blaha blahaoch annat

trams

Åter-ledningradiatorer

Blaha blahaoch annat

trams

94

1

88

43

46

86

Fram-ledning

radiatorer

12

24

16

17

44

70

19

44

89

78

27

36

33

98

52

96

97

8

62

48

63

87

65

99

14

Åter-ledning

radiatorer

k.v.v.v.

41

3551807150497374 4779

84

95

85

53

42

61

103

92

83

100

101

2

93

3

6

10

67

69

9

11

7

18

30

38

25

32

68

102

34

20

66

38

Page 41: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

List of components

FIGHTER 360P

Connection Setting out dimensions

A B C70 Supply line, radiator circuit ............................................... Compression ring Ø 22 mm 100 . 465 ...... 9071 Return line, radiator circuit ............................................... Compression ring Ø 22 mm 130 .. 465 ...... 19073 Cold water connection ...................................................... Compression ring Ø 22 mm 260 .. 465 ...... 29074 Hot water outlet from water heater ................................... Compression ring Ø 22 mm 290 .. 465 ...... 34578 Filter cover79 Drain and overflow water connection, water heater ......... R 15 male (with compression ring not removed)80 Drain connection, heating system .................................... R 15 male83 Temperature sensor, hot water84 Ventilation opening85 Expansion vessel86 Temperature sensor, evaporator87 Temperature sensor, extract air (concealed)88 Temperature sensor, immersion heater operation89 Temperature sensor, supply line90 Ventilation connection exhaust air ................................... Ø 125 mm .................... 2095 ...... 295 ...... 16091 Ventilation connection extract air ..................................... Ø 125 mm .................... 2095 ...... 295 ...... 48592 Temperature sensor, exhaust air (hidden)93 Temperature sensor, return94 Temperature sensor, compressor operation95 Overflow pipe, safety valve water heater96 Overflow pipe, safety valve heating97 Condensation water outlet, fan box98 Overflow water discharge ................................................. PVC-pipe Ø 32 mm (outside diameter)99 Collection funnel, waste water

100 Knob, setting Fuse 101 Knob, setting Max electrical output102 No function103 Type plate

1 Immersion heater 9 kW2 Load monitor card3 Operating thermostat, backup heating6 Temperature limiter7 Miniature circuit-breaker8 Switch, position 1 - 0 - 9 Terminal block, power supply

10 Contactor, step 111 Terminal block, docking12 Terminal block, docking13 Terminal block, capacitor14 Terminal block15 Outside sensor16 Circulation pump17 Air screw, circulation pump18 Pushbutton, Extra hot water19 Shunt motor with handwheel20 Connector, fan22 Terminal block for fan speed24 Immersion heater 4.5 kW25 Push button, Operating mode26 Motor protection, compressor27 Compressor28 Operating capacitor, compressor 29 Relay card with power supply unit30 Push button, Fan speed32 Display unit33 High pressure pressostat

34 Central unit35 Capacity setting, circulation pump36 Fan, exhaust air38 Knob, Offset heating curve41 Low pressure pressostat42 Pressure gauge, boiler43 Shunt valve44 Shutoff valve, pump and supply radiator circuit46 Filler valve, water heater47 Safety valve, water heater48 Expansion valve49 Combined filling and non-return valve, heating

system50 Shutoff valve, return line radiator circuit51 Drain valve, heating system52 Safety valve, heating system53 Vacuum valve (hidden)54 Fan transformer57 Starter capacitor, exhaust air fan61 Docking connection, requires special pipe from

NIBE62 Evaporator63 Air filter (Filter type G2)65 Drying filter with tank66 Rating plate67 Contactor, step 268 Compressor heater69 Contactor, step 3

39

Page 42: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Circuit diagram

FIGHTER 360P

Re3

Re2

Re11

Re1

Re4

Re5

Re6

Re8

Re9

Re10

X29

X29NX29

1A

3A2A

4B

6B5B

R01

T

X20aX20b X29

X29

M

68

X29

9X22

X29

5X29

4

X29

7

6

5

4

3

2

7

8

9

10

1

X29

T

14

13

642

1 3 5

642

1 3 5

642

1 3 5

Svart4,5 kW Vit

3 kWBrun (Röd)

6 kW

X11

2

X11

3

6

7

8

16

10

67

69

43

3

54

57

28

35X29

34

X29

33

X29

31X29

32

X12

4

X12

6

1 1

X13

L 10

X13bX13a

N N

F2

F1

X12

5

X12

1

X29

30

X11

1

X12

3

X12

2

13

X29

12

X29

14

X29

17

X29

18 X29

19

X29

29

X11

5

X11

6

X11

4

X9N

X9L1

X9L2

X9L3

PE

X29

46

X29

20

X20X20 X29

2b 2a 1

X20bX20aX29

2 N N

36

X20aX20b

PE PE

X29

36

69

24

67

1

10

X29

45

26

C

S

R

27

22

X29

26

X29

27

X29

28

40

Page 43: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Sensors

FIGHTER 360P

15 Outside sensor33 High pressure pressostat41 Low pressure pressostat83 Temperature sensor, hot water86 Temperature sensor, evaporator87 Temperature sensor, extract air 88 Temperature sensor, immersion heater operation89 Temperature sensor, supply line92 Temperature sensor, exhaust air 93 Temperature sensor, return94 Temperature sensor, compressor operation

Temperature sensor dataSensor placement

-30 53,44 4,60

-20 29,20 4,31

-10 16,62 3,90

-40 102,35 4,78

Temperature (°C) Resistance (kΩ) Voltage (V)

-35 73,51 4,70

-25 39,29 4,47

-15 21,93 4,12

-5 12,71 3,65

0 9,81 3,38

5 7,62 3,09

10 5,97 2,80

15 4,71 2,50

20 3,75 2,22

25 3,00 1,95

30 2,42 1,70

35 1,96 1,47

40 1,60 1,27

45 1,31 1,09

50 1,08 0,94

4X4.1

X6.1

X11 5 10 15

X2 X3

83 93 89

X5.1

5

10

15

20

94

88

92

86

87

33

41

2

14

15

41

Page 44: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Dimensions

FIGHTER 360P

Dimensions and setting-out coordinates

Undvik rördragning inom streckmarkeratområde för att underlätta service

A15

Stä

llbar

15

– 40

250

45Min avstånd10 mm från vägg

Lucka på båda sidor

Erforderligt utrymme för demontering av övre frontlucka

77

B615

115

C 355

600

2095

70

35

40 20

35

70

A, B and C: See Connection in List of components.

Pipes must not be run from the floor in the areaindicated by dots.

A clear space of 500 mm isneeded in front of the heatpump for servicing.

Measuring principle

Klämring Cu-rör

Skyddsklenspänning Ø 16

Frånluft Ø 125Avluft Ø 125

Elektriskmatning Ø 25

Dockning Ø 16

91 90

440115

295

42

Space required to dismantle theupper service cover.

Min. distance 10 mmfrom the wall

Protective extra low voltage Ø 16

Exhaust air Ø 125Extract air Ø 125

Docking Ø 16

Mains supply Ø 25

Cover on both sides Compression ring Copper-pipe

Avoid routing pipes within the lined area tofacilitate servicing.

Adj

usta

ble

15 -

40

Page 45: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

For the Installer

Technical specifications 43

FIGHTER 360P

Enclosure class IP 21

Required ceiling height 2 185 mm

Depth 615 mm

Volume total 240 litres

Volume water heater 170 litres

Output immersion heater 13,5 kW (switchable)

Rated output exhaust air fan 170 W

Max pressure in double jacket volume 0,25 MPa (2.5 (bar)

Breaking value, low pressure pressostat 0,15 MPa (1.5 (bar)

Refrigerant volume 420 g

Sound power level* 44-48 dB(A)

RSK No. 625 01 08

IP 21

Height (excl. foot: 15 40 mm(mm) 2 095 mm

Width 600 mm

Weight 205 kg

Volume double jacket 70 litres

Supply voltage 400 V~ 3-phase + N

Rated output, circulation pump 100 W

Rated output, compressor 650 W

Max pressure in storage heater 0,9 MPa (9 (bar)

Breaking value, high pressure pressostat 2,45 MPa (24.5 (bar)

Design pressure in double jacket volume 0,25 MPa (2.5 (bar)

Refrigerant type R290 (propane)

Sound level in the boiler house** 40-44 dB(A)

* A-weighted sound power level (LwA). The value

varies with the selected fan curve.** A-weighted sound pressure level (LpA). The value

varies with the room’s damping capacity. Thesevalues apply with a damping of 4 dB.

Enclosed kit

LEK

NIBE AB

Utetemperatur givare

Outdoor temperature sensor

Aussentemperatur fühler

Artikel 018764

Outside sensorCurrent sensor

Earth cable

Feet

LEK

LEK

LEK

Page 46: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

FIGHTER 310

For the Installer

Accessories

Top cabinetTop cabinet high 332 mm.

Top cabinet low 242 mm.Low and high can be combined. Building height 332532 mm.

LEK

LEK

Docking kitsThere are docking kits available for connecting otherheat sources to the heat pump.

LEK

10

15 20

2530°C

Room thermostat RT 10

Extra shunt groupUsed when there is a need of two different supply tem-peratures. Installed externally, but controlled fromFIGHTER 360P- Circulation pump- Shunt motor- Shunt valve- Circuit card- Pipe fittings- Sensor and cabling

44

Cables for external electricboilers and outer alarm signal.

Cables XTS 20

Page 47: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i
Page 48: R FIGHTER 360P - nibeonline.com · r mos gb 0418-1 411482 fighter 360p installation and maintenance instruction fighter 360p lek +2 0-2 a bi i a b i

NIBE ABR

Box 14Järnvägsgatan 40SE-285 21MARKARYD,

SWEDEN