I. INTRODUCTION J. A. Freitag Environmental Affairs
II. REGULATIONS AFFECTING WASTE OIL DISPOSAL J. A. Freitag Environmental Affairs
A. Special Wastes/Hazardous Wastes
B. Problems with Mixtures of Waste Oil And Chlorinated Solvents
III. WASTE OIL MANAGEMENT PROCEDURES F. M. Nemes Environmental Affairs
A. Segregating Waste Oil and Chlorinated Solvents
B. Disposal of Waste Oil with Greater Than 1000 ppm Chlorine
C. Disposal of Waste Oil with Less Than 1000 ppm Chlorine
IV. CLOR-D-TECT DEMONSTRATION F. M. NemesEnvironmental AffairsH. Brooks/ Wm. E. Phillips, Inc. and Dexsil Corp.
V. ADJOURN
Reprinted with permission of Commonwealth Edison Chicago, ILL. 60690-0767J. A. Freitag, Environmental Affairs, F. M. Nemes, Environmental Affairs
R E G U L ATIONS AND MANAGEMENT PROCEDURES FOR WASTE OIL DISPOSALCommonwealth Edison, Chicago, Ill.
DTR-09-01 1
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
WASTE OIL SEMINAR AND CLOR-D-TECT DEMONSTRAT I O N
June 7, 1989
D. H. Richardson (G.O. Ext. 4438)
Zion
Byron
Briadwood
Dresden
LaSalle
Quad Cities
F. M. Nemes (G.O. Ext. 4441)S. Pulido (G.O. Ext. 4453)
State Line
Joliet 9
Joliet 29
Kincaid
Collins
Powerton
Waukegan
Will County
Crawford
Fisk
Western Division
Northern Division
Production Training Center
Rock River Division
Chicago North
Chicago South
Sangamon Garage
Edison Building
Villa Park Garage
Southern Division
J. A. Freitag (G.O. Ext. 3016)
Technical Center
General Warehouse
DTR-09-01 2
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
ATTACHMENT 1
Environmental Affairs Contact Personnel
SOLID WASTE AND TOXICS GROUPDisposal Area Contact: J. A. Freitag (G.O. Ext. 3016)
Individual Facility Contacts:
DTR-09-01 3
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
DTR-09-01 4
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
DTR-09-01 5
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
DTR-09-01 6
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
Waste oil which has had chlorinated solvent inadver-tently mixed with it is considered a hazardous wasteby definition. Waste oil recyclers will not collect oilthat is contaminated with 1000 ppm or greateramounts of chlorinated solvents. This concentration isequivalent to about cup of solvent* in a 55-gallondrum. However, certain waste oil vendors will takewaste oil with up to 5% (by weight) (50,000 ppm)chlorine when they are provided with specific conta-mination documentation. The revenue received by theCompany from this oil with the higher chlorine con-centration is approximately one half the revenuereceived from non-contaminated waste oil. Waste oilwith greater than 50,000 ppm of chlorine contamina-
tion must be disposed of by incineration. Collectionand disposal fees that Edison must pay for incinera-tion of such waste oil are quite high and currentlyrange from $1.70 to $2.00 per gallon.
The attached procedure, which is based firstly on reg-ulatory concerns and secondarily on economic incen-tives, is to be used as a guideline for managing wasteoil and solvent mixtures.
* P a rtial list of chlorinated solvents: 1,1,1-t r i c h l o roethane, dichloroethylene, chloro o c t a d e c a n e ,t r i c h l o robenzene, methylene chloride, per-o c h l o roethylene, freon 113, monochloro b e n z e n e ,PCB, and barc o t h a n e .
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
DTR-09-01 7
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
This procedure is for the following CommonwealthEdison locations:
Collins Station LaSalle County Station
Crawford Station Quad Cities Station
Fisk Station Zion Station
Joliet 9 Station Bloom Peaker
Joliet 29 Station Dixon-Hydro
Kincaid Station Sabrooke Peaker
Powerton Station Electric Junction Peaker
State Line Station Lombard Peaker
Waukegan Station Calumet Peaker
Will County Station General Warehouse
Braidwood Station Technical Center Shops
Byron Station Havana Coal Dock
All Division General Office Production Locations Training Center
1. Provide a designated drum(s) for collection of sol-vent only. Labels which read “Waste Solvents Only”can be obtained from Environmental Affairs.
2. Do not mix waste solvents in the designated wasteoil drums or the waste oil storage tank. Labelswhich read “Waste Oil Only” can be obtained fromEnvironmental Affairs.
3. Keep waste solvents segregated from the waste oil.
4. To schedule a pickup of your waste oil, contact theInvestment Recovery Department at the GeneralWarehouse at Extension 303.
MANAGEMENT OF WASTE OIL AND WASTE OIL SUSPECTED OF BEINGCONTAMINATED WITH CHLORINATED (HALOGENATED) SOLVENTSEnvironmental/Regulatory Concerns
ATTACHMENT
PROCEDURE FOR MANAGEMENT OF WASTE OIL AND WASTE OIL SUSPECTED OF BEING CONTAMINATED WITH CHLORINATED SOLVENTS
5. To arrange for disposal of your waste solvent,contact Environmental Affairs and follow the pro-c e d u re for “Disposal of Drummed Chlorinatedand Non-Chlorinated Solvent Waste” datedDecember 18, 1987.
6. If waste solvents are inadvertently mixed with yourwaste oil, you must run a “screening” test prior toarranging a waste oil pickup. The waste oil vendorwill return any waste oil which has been contami-nated to greater than 1000 ppm with chlorine.
SCREENING TEST INSTRUCTIONS:
A.Take a representative sample of your waste oil.Waste oil and solvents will tend to separate intolayers. Be sure to collect oil through the entirevertical column of the storage container asdescribed in more detail in the attached sam-pling procedure (Appendix I).
B. Use the CLOR-D-TECT field screening test kitto perf o rm the analysis. These kits are avail-able as a Stores Item No. 134145. Follow thed i rections provided with the kit. The re s u l t sf rom this screening test will indicate whetheryour sample contains more or less than 1000ppm chlorine.
7. If your screening test shows that the waste oil hasless than 1000 ppm chlorine, then you may pro-ceed with arranging a waste oil pickup through theInvestment Recovery Department as previouslydescribed in Item 4 of this attachment.
8. If your screening test shows that the waste oil hasgreater than 1000 ppm chlorine, then contact yourEnvironmental Affairs representative listed inAppendix II for guidance on determining an appro-priate disposal method.
9 . E n v i ronmental Affairs will provide assistance inmaking arrangements for disposal of waste oil cont-aminated with chlorine. Your facility will be re s p o n-sible for perf o rming the following, as necessary :
•Obtain a representative sample
•Arrange for delivery of sample to appropriatelaboratory for analysis, as determined byEnvironmental Affairs
• Provide a function number or small purchaseorder for payment of laboratory fees
• Provide security for the waste
• Provide weekly visual inspections of the waste to assure that there are no leaks.
DTR-09-01 8
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
The Clor-D-Tect 1000 kit was developed by DexsilCorporation in response to the EPA decision to regu-late the chlorine content in waste oils. Research waspartially sponsored by EPA Region II.
The result of this program is a simple, reliable anddefinitive kit that can be used in the field by non-technical personnel.
The kit is designed to permit collectors of used orwaste oil for reprocessing or disposal to test for conta-mination in a generator’s oil before picking up theload. The kit can also be used by enforcement author-ities to spot-check suspected materials as they arebeing generated, transported or sold.
In an EPA study it was reported: “The kit (Clor-D-Tect1000) can probably be used as a screening kitthroughout the used oil industry, from the generatorto the recycler to the transporter and burner. There
are few false positives and negatives and minimalmatrix effects. The kit is simple to use. One does notneed to understand the chemical reactions that occurto obtain accurate results. A complete test requiresapproximately 15 minutes to complete. The greatestutilities for their regulation are the portability andaffordability of the kit”.1
1 A. Gaskill, Jr., E.D. Estes, D.L. Hardison, Evaluationof Methods for Determining Chlorine in Used Oils.Final Report, EPA Contract No. 68-01-7075, WorkAssignment No. 51, US EPA, Office of Solid Waste,August 1986
*CLOR-D-TECT Kit information from DexsilCorporation product brochure.
**For Kit users, CLOR-D-TECT color literature isavailable by contacting the Environmental AffairsDepartment.
DTR-09-01 9
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
APPENDIX I
CLOR-D-TECT KIT SAMPLING METHOD* AND OTHER GENERAL INFORMATION ABOUT THE KIT**
INTRODUCTION
ABOUT THE KIT
STEP #1
Assemble capillary-syringe sam-
pler by inserting glass capillary
about 1⁄ 8" into the plastic tub-
ing at end of syringe. Insert
bottom of glass capillary into
oil sample.
STEP #2
Using the syringe, slowly draw
oil up the glass capillary until it
reaches the flexible tubing.
Wipe off glass capillary with
the supplied tissue.
STEP #3
Unscrew white dispenser cap
and put capillary inside tube.
Bend tubing to release capil-
lary. Crush capillary by squeez-
ing bottom of tube several
times, being careful not to
break reagent ampules.
STEP #4
Break the lower (colorless)
ampule in the tube by com-
pressing the sides of the tube.
Mix thoroughly by shaking the
tube vigorously for about 30
seconds. Break top (gray)
ampule in the tube and shake
thoroughly for about 20 sec-
onds. Allow reaction to proceed
for one minute, shaking intermit-
tently several times.
DTR-09-01 10
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
SAMPLING PROCEDURESTEP-BY-STEP DIRECTIONS
DTR-09-01 11
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
STEP #5
Remove the caps from both tubes
and pour the clear buffer solution
from Tube #2 (with yellow cap)
into Tube #1. Replace the white
cap tightly on Tube #1, and shake
vigorously for 10 seconds. Vent
the tube by partially unscrewing
the dispenser cap. Close securely
and shake well for an additional
10 seconds. Vent tube again, tight-
en cap and stand tube upside-
down on its cap. Allow the phases
to separate for two minutes.
STEP #6
After layers have separated, put
filtration funnel in Tube #2. Open
nozzle of white cap and dispense
5 ml of the buffer solution through
funnel and up to the line in the yel-
low capped tube. Replace cap
and then break lower (colorless)
ampule and shake for 10 seconds;
then break top (colored) ampule
and shake for 10 seconds and
observe color.
STEP #7
Observe color immediately. If the
solution appears purple, the oil
sample contains less than 1000
ppm chlorine. If it appears yellow
or colorless, the sample contains
more than 1000 ppm chlorine.
• Wear rubber gloves and safety glasses.
• When assembling capillary-syringesampler insert the glass capillaryapproximately 1⁄8" into plastic tub-ing, making for easy removal inStep 2A.
• When crushing glass ampules,press firmly in the center of theampule once. Never attempt torecrush broken glass in the testtube since glass may sever theplastic and cut fingers.
• In case of accidental breakage ontoskin or clothing wash with largeamounts of water. All the ampulesare poisonous and should not betaken internally.
• The kit works well on all types ofused and waste oils includingcrankcase, hydraulic, diesel, lubri-cating, fuel oils and kerosene.
• In step #6, observe the colorimmediately and compare to thechart. The purple color may fadeout over time.
• Perform the test in a warm, dryarea with adequate light. In coldweather, a truck cab is sufficient.
• The numbers assigned to the purplecolors are for approximation only.
• The test works on the principle ofchloride detection, therefore, cont-amination by salt (sodium chlo-ride), sea water, perspiration, etc.,may give a false positive result.
DTR-09-01 12
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
SUGGESTIONS FOR USING THE CLOR-D-TECT KIT
When crushing glass capillary, squeezeonly at the bottom of the tube whiletapping the glass down, being carefulnot to break the glass ampule.
DTR-09-01 13
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
• When taking oil samples with the syringesampler slowly draw the oil up to the rub-ber tubing then wipe off the capillary anddisconnect it into Tube #1.
• Be sure that your oil sample is uniform andrepresentative of the whole lot.
• The kit should be examined upon openingto see that all the components are presentand that all ampules (two in each tube) arein place and not leaking. The liquid in theyellow-capped tube should be approximate-ly 1⁄ 2"-inch above the 5 ml line inscribed onthe tube and the tube should not be leak-ing. The ampules are not supposed to becompletely full.
• The Clor-D-Tect test will not work on asample that contains more than 30% water.If, in step 2, the tube loses its gray color,the sample contains water and the testshould not be run.
• Dispose of kits properly.
• With samples that contain water, theremay be a small pre s s u re build-up in tube1; simply vent the tube by unscrewing thecap 1⁄ 2 t u rn .
• Freezing of the buffer solution does notdamage the kit, but the solution should becompletely melted before running the test.
• Remember that the kit is designed for useon many types of used oil. It may work onother fluids; contact Dexsil before using thekit in other applications.
Before using a kit, make sure that theexpiration date has not passed.
ENVIRONMENTAL/REGULATORY CONCERNS
Spent solvents, both chlorinated (such as 1,1,1-trichloroethane, barcothane, freon and non-chlorinat-ed* (mineral spirits), are considered hazardous waste.As such, disposal of these spent materials must meetthe following specific requirements:
1 . Mixing waste solvents with any liquid orsolid waste renders the entire mixture a haz-a rdous waste.
2. Landfilling of liquid hazardous waste is banned.
3.Drummed waste chlorinated solvents must bedisposed of by incineration.
4. Drummed nonchlorinated waste solvent may berecycled instead of incinerated depending on acase-by-case review performed byEnvironmental Affairs Department.
Based on these concerns, the attached procedures areprovided for handling waste solvents and mixtures ofwaste solvents.
DISTINCTION BETWEEN DRUMMED SOLVENTWASTE AND SAFETY-KLEEN SOLVENT WASTE
The attached instructions are for drummed chlorinat-ed/non-chlorinated solvent waste. They are not forsolvent waste accumulated in barrels integrally associ-ated with Safety-Kleen solvent parts washers.Instructions regarding disposal of the latter, whichinvolves only manifesting and/or recordkeeping, have
previously been sent to those Commonwealth Edisonlocations that use the Safety-Kleen parts washer ser-vice. If you require a copy, please contact your EADSolid Waste & Toxics Group Contact (Figure 2).
The principal reason that an additional solvent dis-posal method is required is that Safety-Kleen will onlyrecycle their own non-chlorinated solvent waste.Since a number of our facilities use a variety of chlori-nated solvent suppliers, there is a need to dispose ofthis waste separately from Safety-Kleen solvent.However, if an Edison facility decides to use only nonchlorinated solvents, it is advised that they considerthe Safety-Kleen solvent (or similar vendor) option toreduce disposal costs and associated liabilities associ-ated with chlorinated solvent waste disposal.
ECONOMIC CONSIDERATIONS
Disposal costs are continuing to increase. The chargefor incineration of one drum of non-chlorinated sol-vent waste is approximately $170 to $200 whereasthe charge for incineration of one drum of chlorinatedsolvent is approximately $275. Analytical, permittingand transportation costs are additional.
These costs are expensive. However, in choosing theincineration option, Commonwealth Edison’’ liabilityrisk in case the waste is mismanaged by some otherdisposal option is greatly reduced. In addition to theregulatory requirements listed above, the associatedliability concerns are economic incentives to managewaste solvent properly.
DTR-09-01 14
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
Revised 1/88Replaces Procedure Dated 9/23/85 and 1/28/86
DISPOSAL OF DRUMMED CHLORINATED AND/OR NON-CHLORINATED SOLVENT WASTE
*With flashpoint of less 140°F or 60°C (check your MSD sheet).
This procedure is for the following CommonwealthEdison locations:
Collins Station LaSalle County Station
Crawford Station Quad Cities Station
Fisk Station Zion Station
Joliet 9 Station Bloom Peaker
Joliet 29 Station Dixon-Hydro
Kincaid Station Seabrooke Peaker
Powerton Station Electric Junction Peaker
State Line Station Lombard Peaker
Waukegan Station Calumet Peaker
Will County Station General Warehouse
Braidwood Station Technical Center Shops
Byron Station Havana Coal Dock
All Division Locations General Office Production Training Center
1. Waste solvent liquids must not be mixed withwaste oil. Every effort must be made to preventaccidental mixing of solvents with waste oils.
2. Waste solvent liquids must not be contaminatedwith PCB oil, nor with any other liquid wasteincluding water.
3. Waste solvent must be placed into a non-leaking55 gallon drum, with either a non-removable orremovable lid. The lid must be equipped with abung hole for sampling purposes.
Generators of hazardous waste are allowed tos t o re wastes on-0site only for specified periods oftime, after which they must be removed. To storeor accumulate larger quantities of hazard o u swastes places the facility into a higher level of
re q u i red re c o rdkeeping. The following items (4t h rough 7) detail storage/accumulation re q u i re-ments in such a way as to minimize the impactof this additional regulation on each facility.
4.When one (1) 55-gallon drum is full, place ahazardous waste label on the drum side and fillin all of the information required on the labelexcept the Manifest Document Number. TheDate of Generation/Accumulation should befilled in with the date when the drum was com-pletely filled. Refer to Figure 1, Example of“Hazardous Waste Label.”
When subsequent drums are filled, label themexactly as above, using the actual date thosedrums were filled. Each drum must now beremoved off-site within 90 days from the datethat the drum became filled.
5. A reas where drums are stored must be inspect-ed weekly to assure that no drums are leaking.The IEPA re q u i res that a written re c o rd be keptto document these inspections. A “Hazard o u sWaste Container Inspection Weekly Check-OffLog” as provided in Figure 3 to re c o rd pert i-nent information and document these weeklyinspections. The re c o rds of your weeklyinspections must be readily accessible toE n v i ronmental Affairs and to the IEPA duringcompliance re v i e w s .
6. When a facility re q u i res removal/disposal ofd rummed solvent waste, call your Enviro n m e n t a lA ffairs Department contact for assistance. A listof EAD Contracts is provided in Figure 2. Bep re p a red to state the number of drums involved,the location of the drums, and the contents, i.e.,chlorinated, non-chlorinated, or mixture of sol-vents in the drums. A Material Safety Data Sheet(MSDS) should also be pro v i d e d .
DTR-09-01 15
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
ATTACHMENT I
PROCEDURE FOR DISPOSAL OF DRUMMED CHLORINATED AND/OR NON-CHLORINATED SOLVENT WASTE
7. Environmental Affairs Department will contactthe waste broker on your behalf. EnvironmentalAffairs Department and the broker will consultregarding all regulatory matters, however, yourfacility will be invoiced for the various technicalservices performed. Services performed mayinclude the following, if necessary, if required bythe disposal contractor and at the direction ofEnvironmental Affairs:
Waste Sampling and Analysis
Waste inventory
Waste transfer from bad to good drums
Overpack of leaking drums
Preparation of regulatory and disposal site documentation
Preparation of manifest and additional labels
Pick-up of waste
Transportation of waste to disposal facility
8. Your facility will be responsible for performingthe following:
Provide vendor access to sample and inventory waste
Provide security for the waste
9. E n v i ronmental Affairs will inform your facility ofthe date when the waste is scheduled to be pickedup. The waste broker will present a completedmanifest which re q u i res your signature. Route themanifest according to the Pro c e d u re at right.
Manifest Routing Instructions (6 copies per manifest form)(1 form per shipment)
Copies 1 through 4 are given to the hauler.
Copy 5 (green) must be mailed by theCommonwealth Edison Facility to the IEPA(address is listed on the manifest) Withintwo working days.
Copy 6 (yellow) is to be retained on file byyour facility.
Copy 1 (white) should be returned to thefacility by the ultimate disposal site withinone month. If this does not happen, contactthe disposal facility and request that themanifest be sent to you. If Copy 1 has notbeen received within 45 days of the datewhen the waste was picked-up, then con-tact your Environmental Affairs representa-tive who must prepare a letter of explana-tion to the IEPA.
Copies 1 and 6 should be compared for dis-c repancies. Contact Environmental Affairs forassistance if there are discre p a n c i e s .
A photocopy should then be made of copy1 and sent to Environmental Affairs formaintenance in the manifest database. Yourfacility must keep copies 1 and 6 on file.This file must be readily accessible toEnvironmental Affairs and IEPA personnelfor inspection purposes.
DTR-09-01 16
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
Generators name – Provide station/facility name, i.e., LaSalle Station
Address – Provide mailing address of facility
Manifest Document Number – This number is obtained from actual manifest to be used toship this drum. That number is a red pre-printed number in the upper right hand portion of themanifest. Put that number on each drum(s) label to be shipped.
EPA ID# – Provide USEPA Generator ID # for your facility.
EPA/DOT Shipping Name – Provide proper EPA/DOT shipping name, i.e., Waste FlammableLiquid N.O.S., flammable liquid, UN1993
Date of Generation/Accumulation – Provide date when drum is filled and ready for disposal.
DTR-09-01 17
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]
FIGURE IHAZARDOUS WASTE LABEL
HAZARDOUS WASTE CONTAINER INSPECTION WEEKLY CHECK-OFF LOG
Hazardous Waste Container(s) Location ________________________
Week of ________________________ Through __________________
Date ___________________________ Name ____________________
For storage/accumulation of hazardous waste designated for off-site disposal.
1. Storage Area Location ________________________
2. Number of Solvent Containers at This Location ________________________
3. Waste Name _________________________
4. Volume of Container (gallons) _________________________
5. What Fraction of Container is Full _________________________
6. Container Labeled Hazardous Waste? Yes _________ No _________*
7. Accumulation Start Date Marked? Yes _________ No _________**
8. Container in Good Condition? Yes _________ No _________*
9. Container Leaking? Yes _________* No _________
10. Container Completely Closed? Yes _________ No _________*
11. Has the waste been stored for 75 days or more? Yes _________* No _________
*Report immediately to Regulatory Compliance Coordinator or appropriate individual.
**Put the date when the drum is completely filled.
NOTE: Containers must not be handled or stored in a manner which may ru p t u re the container or cause it to leak. Report any such occurring conditions to the RegulatoryCompliance Coord i n a t o r.
DTR-09-01 18
DEXSIL CORPORATION www.dexsil.comOne Hamden Park Drive • Hamden, Connecticut, 06517 • Phone 800.433.9745 • Fax 203.248.6523 • Email [email protected]