R case 2

6
Rcase condensing units with Copeland scroll compressors www.refra.eu

description

R case 2 katalogas

Transcript of R case 2

Page 1: R case 2

R c a s e c o n d e n s i n g u n i t s w i t h C o p e l a n d s c r o l l c o m p r e s s o r s

w w w . r e f r a . e u

Page 2: R case 2

w w w . r e f r a . e u

J S C “ R E F R A “D a r i a u s & G i r e n o s t r . 1 7 3

L T - 0 2 1 8 9 , V i l n i u s L i t h u a n u i a

Page 3: R case 2

R407cR410aR404aR407cR410aR404a

2

R c a s e c o n d e n s i n g u n i t s w i t h C o p e l a n d s c r o l l c o m p r e s s o r s

S o m e e x a m p l e s w h e r e R c a s e u n i t s c o u l d b e u s e d

Scroll Reciprocating

Page 4: R case 2

R c a s e c o n d e n s i n g u n i t s w i t h C o p e l a n d s c r o l l c o m p r e s s o r s

STANDARD SET OF PARTS:

» Galvanized body with extra-coated poly-meric coating » Air cooled condenser with Axial fans» Compressor » Liquid receiver » Filter drier and contol sight glass » Shut off valves with service valves on liq-uide and suction lines » High and low pressure relay » Solenoid valve » Electrical terminal connectors

ADDITIONAL OPTIONS:

» Fan speed controller (FSC) or » High pressure relay (HP); » Pump down control LP switch (LP); » Sound jacket for compressor (SJ); » Control board (P).

*1 Colculations are made according condensing temperature +45°C, evaporating temperature -10°C, liquid subcooling 0K, suction gas temperature 20°C, Ambient T + 30°C, refrigerant – R404A *2 Sound pressure level indicated in 10 meters

Technical data Rcase 19 Rcase 21 Rcase 30 Rcase 38 Rcase 45

Cooling capacity *1 kW 4,2 5 6,9 8,5 10,1Nominal power input *1 kW 2,1 2,5 3,3 4,2 4,8COP - 2,00 2,00 2,09 2,02 2,10Sound level*2 (dbA) dBa 44 45 45 46 46Compressor Type Scroll Copeland

Quantity Nr 1 1 1 1 1Max. operating current A 6,5 7,2 10,3 12,8 13,1Tubes connection (suc/liq) mm 22/12 22/12 22/12 22/12 22/12Liquid receiver dmi 2.0 2.0 2,8 5,6 5,6Fans

Quantity Nr 1 1 1 2 2Diameter mm 450 450 500 450 450Power input W 160 160 220 160 x 2 160 x 2Operating current A 1,1 1,1 1,1 0,8 x 2 0,8 x 2

Standard Voltage V/ph/Hz 380/3/50

FEATURES:

» Compact unitary structure » Low level of noise and vibration » Provided with a cover box protecting from a harmful environmental influence » All the components of the refrigeration unit, including an air cooled cond. unit, are installed within the housing » Light weight and compact design allow installation of this type of refrigeration units indoor and outdoor as well as on the roofs of buildings » Provided with all the necessary and re-quired documents, and certificats of European Union » Modern and sophisticated components are used in wiring and the control system » A wide option of the unit models, set of parts and accessories.

3

Page 5: R case 2

Technical data Rcase 19 Rcase 21 Rcase 30 Rcase 38 Rcase 45

Cooling capacity *1 kW 4,2 5 6,9 8,5 10,1Nominal power input *1 kW 2,1 2,5 3,3 4,2 4,8COP - 2,00 2,00 2,09 2,02 2,10Sound level*2 (dbA) dBa 44 45 45 46 46Compressor Type Scroll Copeland

Quantity Nr 1 1 1 1 1Max. operating current A 6,5 7,2 10,3 12,8 13,1Tubes connection (suc/liq) mm 22/12 22/12 22/12 22/12 22/12Liquid receiver dmi 2.0 2.0 2,8 5,6 5,6Fans

Quantity Nr 1 1 1 2 2Diameter mm 450 450 500 450 450Power input W 160 160 220 160 x 2 160 x 2Operating current A 1,1 1,1 1,1 0,8 x 2 0,8 x 2

Standard Voltage V/ph/Hz 380/3/50

GROSS Prices and accesories Rcase 19 Rcase 21 Rcase 30 Rcase 38 Rcase 45

Unit price, EXW Vilnius EUR 2505 2790 3170 3400 3630Ad

ditio

nal

optio

ns, E

XW

Viln

ius

FSC EUR 110 110 110 110 110HP EUR 65 65 65 65 65LP EUR 65 65 65 65 65SJ EUR 188 188 188 188 188P EUR 505 505 505 505 505

Weight and dimentions Rcase 19 Rcase 21 Rcase 30 Rcase 38 Rcase 45

Distance between legs m/n mm 710/540 710/540 710/540 710/540 710/540A – Heigh mm 650 650 800 1250 1250B – Length mm 1150 1150 1150 1150 1150C – Width mm 570 570 570 570 570

Weight kg 85 90 100 115 138

THE UNITS CONFORM TO THE FOLLOWING DIRECTIVES: » EC Machines Directive 98/37/EC » EC Low Voltage Directive 73/27/EEC » EC Pressure Equipment Directive 97/23 (PED) » EMC Directive 89/336/EEC » The refrigeration units have been designed and manufactured in conformity to European Standards EN349, EN378, EN12263, EN60204-1 and other normative requirements. » The refrigeration units are certified and conform to all the requirements of the European Union.

4

R c a s e c o n d e n s i n g u n i t s w i t h C o p e l a n d s c r o l l c o m p r e s s o r s