Design, Installation & Testing Instruction

R-410A Heat Pump 60Hz

RXYQ96MTJU RXYQ192MTJU

SiUS39-504

Desig

n, In

stallation

& T

esting

Instru

ction

R-410A

Heat P

um

p 60H

zS

iUS

39-504

1645 Wallace Drive, Suite 110Carrollton, TX75006

[email protected]

This book is made of recycled paper.SiUS39-504Printed in U.S.A. 10/2005 AK

Page 2: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Preface

This system is a modular zone controllable air conditioning system of great sophistication which is capable of assembly in a variety of different configurations. It would, however, be no exaggeration to say that the full potential of the systems functions can only be achieved in combination with the skills of those involved in the design of the equipment itself and those responsible for the installation work.

As the move towards intelligent buildings has gathered momentum, so we have also been seeing ever more a growing demand for a wider range of independently controllable building related functions.

Against this background there have also quite naturally been calls for the development of more distributed types of air conditioning systems while at the same time taking full account of the need to use energy economically by demand matching in view of the huge annual increases in the demand for electric power seen in recent years.

We have therefore prepared this installation manual to enable installation work to be handled confidently on the basis of a clear understanding of the special features of this system. We have paid particular attention to points of difference in installation procedure between this system and the more traditional package and room air conditioning system.

The manual is designed specifically to cater for those supervising installation work and concentrates on those products which are currently on the market. Essential points which need to be taken into consideration when designing an appropriate configuration for the system and in each of the separate installation processes have also been included.

We have also added a section covering problems which have arisen in connection with installation work undertaken to date in an attempt to prevent the recurrence of the same problems.

Please be sure to read this manual thoroughly before starting installation work in order to ensure that all such work is carried out with maximum efficiency and to maximum effect.

The following technical documents are also available from Daikin. Please use these documents together with this manual to conduct efficient servicing.

Service Manual VRVII R-410A Heat Pump 60Hz Series SiUS39-502 Sept., 2005.Sept., 2005

After Sales Service Division

Page 3: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

R-410A SeriesR-410A SeriesR-410A SeriesR-410A Series

Part 1 General Information ..............................................................11. Product Outline ...........................................................................................2

1.1 Model Names of Indoor/Outdoor Units ....................................................... 21.2 External Appearance.................................................................................. 31.3 Model Selection .......................................................................................... 4

2. Points to Bear in Mind at the System Design..............................................52.1 Points Relating to the Performance of the Air Conditioning Units .............. 52.2 The Installation is of Vital Importance......................................................... 72.3 Striking a Balance between System Installation and

General Construction Work (Comprehensive Flow Chart) ......................... 82.4 Points to Bear in Mind when Preparing the Contract Drawings.................. 9

3. Installation .................................................................................................123.1 Step by Step Installation Procedure ......................................................... 123.2 Work Involved in Individual Operations and

Points to be Borne in Mind ....................................................................... 13

4. Test Operation ..........................................................................................664.1 Procedure and Outline.............................................................................. 664.2 Operation When Power is Turned On ...................................................... 694.3 Outdoor Unit PC Board Layout................................................................. 704.4 Field Setting.............................................................................................. 71

5. Caution for Refrigerant Leaks .................................................................1055.1 Caution for Refrigerant Leaks................................................................. 105

6. Hand Over to Customer ..........................................................................1076.1 Operational Steps................................................................................... 107

7. Appendix .................................................................................................1087.1 Operating Noise of Indoor Units ............................................................. 1087.2 Allowable Piping Length ......................................................................... 1107.3 Refrigerant Branch Kit Selection ............................................................ 1137.4 Pipe Size Selection................................................................................. 1157.5 How to Calculate the Additional Refrigerant to be Charged................... 1167.6 REFNET Pipe Connections for VRVII R-410A Series ............................ 1187.7 VRV Inspection Sheet ............................................................................ 1217.8 Piping System Diagrams ........................................................................ 1257.9 Wiring Diagrams..................................................................................... 1277.10 Bad Examples and Good Examples in Installation................................. 130

Table of Contents i

Page 4: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

Part 2 Installation Manual Outdoor Unit ..................................... 1391. Introduction .............................................................................................144

1.1 Combination ........................................................................................... 1441.2 Standard Operation Limit........................................................................ 1441.3 Standard Supplied Accessories.............................................................. 1451.4 Option Accessory ................................................................................... 1451.5 Technical Specifications ......................................................................... 1461.6 Electrical Specifications.......................................................................... 146

2. Main Components ...................................................................................1473. Selection of Location...............................................................................1484. Inspecting and Handling the Unit ............................................................1505. Unpacking and Placing the Unit ..............................................................1516. Refrigerant Piping ...................................................................................152

6.1 Selection of Piping Material .................................................................... 1526.2 Connecting the Refrigerant Piping.......................................................... 1526.3 Example of Connection .......................................................................... 1576.4 Leak Test and Vacuum Drying ............................................................... 1596.5 Pipe Insulation ........................................................................................ 1616.6 Additional Refrigerant Charge ................................................................ 162

7. Field Wiring .............................................................................................1647.1 Optional Parts Cool/Heat Selector.......................................................... 1647.2 Power Circuit and Cable Requirements ................................................. 1647.3 General................................................................................................... 1657.4 Examples................................................................................................ 165

8. Before Operation.....................................................................................1718.1 Checks before Initial Start-up ................................................................. 1718.2 Test Run................................................................................................. 171

9. Caution for Refrigerant Leaks .................................................................174

Part 3 Operation Manual Outdoor Unit ........................................1771. Safety Considerations .............................................................................1792. What to do before Operation...................................................................1823. Remote Controller and Changeover Switch: Name and

Function of Each Switch and Display......................................................1834. Operation Range.....................................................................................1855. Operation Procedure...............................................................................186

5.1 Cooling, Heating, and Fan Only Operation............................................. 1865.2 Program Dry Operation .......................................................................... 1885.3 Adjusting the Air Flow Direction.............................................................. 1895.4 Programming Start and Stop of the System with Timer ......................... 1915.5 Setting the Master Remote Controller .................................................... 1925.6 Precautions for Group Control System or

Two Remote Controller Control System................................................. 193

6. Optimum Operation.................................................................................194

ii Table of Contents

Page 5: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

7. Following Symptoms are not Air Conditioner Troubles ...........................1957.1 The System does not Operate................................................................ 1957.2 Cool/Heat Cannot be Changed Over...................................................... 1957.3 Fan Operation is Possible, but Cooling and Heating do not Work ......... 1957.4 The Fan Strength does not Correspond to the Setting........................... 1957.5 The Fan Direction does not Correspond to the Setting .......................... 1957.6 White Mist comes out of a Unit............................................................... 1967.7 Noise of Air Conditioners........................................................................ 1967.8 Dust comes out of the Unit ..................................................................... 1967.9 The Units can Give off Odours ............................................................... 1967.10 The Outdoor Unit Fan does not Spin...................................................... 1967.11 The Display Shows "88" ......................................................................... 1977.12 The Compressor in the Outdoor Unit does not Stop after a Short

Heating Operation .................................................................................. 1977.13 The Inside of an Outdoor Unit is Warm Even

When the Unit has Stopped.................................................................... 197

8. Trouble Shooting.....................................................................................198

Part 4 Precautions for New Refrigerant (R-410A) .......................2011. Precautions for New Refrigerant (R-410A) .............................................202

1.1 Outline .................................................................................................... 2021.2 Service Tools.......................................................................................... 203

Index ................................................................................................ i

Drawings & Flow Charts .................................................................. iii

Table of Contents iii

Page 6: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

iv Table of Contents

Page 7: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

General Information 1

Part 1Part 1Part 1Part 1General InformationGeneral InformationGeneral InformationGeneral Information

1. Product Outline ...........................................................................................21.1 Model Names of Indoor/Outdoor Units......................................................... 21.2 External Appearance.................................................................................... 31.3 Model Selection............................................................................................ 4

2. Points to Bear in Mind at the System Design..............................................52.1 Points Relating to the Performance of the Air Conditioning Units ................ 52.2 The Installation is of Vital Importance .......................................................... 72.3 Striking a Balance between System Installation and

General Construction Work (Comprehensive Flow Chart) ........................... 82.4 Points to Bear in Mind when Preparing the Contract Drawings ................... 9

3. Installation .................................................................................................123.1 Step by Step Installation Procedure ........................................................... 123.2 Work Involved in Individual Operations and

Points to be Borne in Mind ......................................................................... 13

4. Test Operation ..........................................................................................664.1 Procedure and Outline ............................................................................... 664.2 Operation When Power is Turned On ........................................................ 694.3 Outdoor Unit PC Board Layout................................................................... 704.4 Field Setting ............................................................................................... 71

5. Caution for Refrigerant Leaks .................................................................1055.1 Caution for Refrigerant Leaks .................................................................. 105

6. Hand Over to Customer ..........................................................................1076.1 Operational Steps..................................................................................... 107

7. Appendix .................................................................................................1087.1 Operating Noise of Indoor Units ............................................................... 1087.2 Allowable Piping Length ........................................................................... 1107.3 Refrigerant Branch Kit Selection .............................................................. 1137.4 Pipe Size Selection .................................................................................. 1157.5 How to Calculate the Additional Refrigerant to be Charged..................... 1167.6 REFNET Pipe Connections for VRVII R-410A Series.............................. 1187.7 VRV Inspection Sheet .............................................................................. 1217.8 Piping System Diagrams .......................................................................... 1257.9 Wiring Diagrams....................................................................................... 1277.10 Bad Examples and Good Examples in Installation................................... 130

Page 8: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Product Outline SiUS39-504

1. Product Outline1.1 Model Names of Indoor/Outdoor Units

Indoor Units

Outdoor Units (Inverter Series)

Type Model Name Power Supply

Ceiling Mounted Cassette Type(Multi Flow)

FXFQ 12M 18M 24M 30M 36M —

VJU

Ceiling Mounted Built-In Type FXSQ 12M 18M 24M 30M 36M 48M

Ceiling Mounted Duct Type FXMQ — — — 30M 36M 48M

Ceiling Suspended Type FXHQ 12M — 24M — 36M —

Wall Mounted Type FXAQ 12M 18M 24M — — —

Floor Standing Type FXLQ 12M 18M 24M — — —

Concealed Floor Standing Type FXNQ 12M 18M 24M — — —

Series Model Name Power Supply

Inverter Heat Pump RXYQ 96M 192M TJU

VJU: 1φ, 208~230V, 60HzTJU: 3φ, 208~230V, 60Hz

2 General Information

Page 9: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Product Outline

1.2 External Appearance1.2.1 Indoor Units

1.2.2 Outdoor Units

Ceiling mounted cassette type (Multi flow)

FXFQ12MVJUFXFQ18MVJUFXFQ24MVJUFXFQ30MVJUFXFQ36MVJU

Wall mounted type

FXAQ12MVJUFXAQ18MVJUFXAQ24MVJU

Ceiling mounted built-in type

FXSQ12MVJUFXSQ18MVJUFXSQ24MVJUFXSQ30MVJUFXSQ36MVJUFXSQ48MVJU

Floor standing type

FXLQ12MVJUFXLQ18MVJUFXLQ24MVJU

Ceiling mounted duct type

FXMQ30MVJUFXMQ36MVJUFXMQ48MVJU

Concealed floor standing type

FXNQ12MVJUFXNQ18MVJUFXNQ24MVJU

Ceiling suspended type

FXHQ12MVJUFXHQ24MVJUFXHQ36MVJU

RXYQ96MTJU RXYQ192MTJU

General Information 3

Page 10: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Product Outline SiUS39-504

1.3 Model SelectionVRV II Heat Pump Series

Connectable Indoor Units Number and Capacity

Connectable Indoor Unit

Indoor Unit Capacity

Use the above tables to determine the capacities of indoor units to be connected. Make sure the total capacity of indoor units connected to each outdoor unit is within the specified value (Btu/h).

The total capacity of connected indoor units must be within a range of 50 to 130% of the rated capacity of the outdoor unit.In some models, it is not possible to connect the maximum number of connectable indoor units. Select models so the total capacity of connected indoor units conforms to the specification.

Ton 8 ton 16 ton

System name RXYQ96M RXYQ192M

Outdoor unit 1 RXYQ96M RXYQ96M

Outdoor unit 2 — RXYQ96M

Total number of connectable indoor units 10 20

Total capacity of connectable indoor units (MBtu/h) 48~120 96~240

Type Model Name Power SupplyCeiling mounted cassette type (Multi flow) FXFQ 12M 18M 24M 30M 36M —

VJU

Ceiling mounted built-in type FXSQ 12M 18M 24M 30M 36M 48M

Ceiling mounted duct type FXMQ — — — 30M 36M 48M

Ceiling suspended Type FXHQ 12M — 24M — 36M —

Wall mounted type FXAQ 12M 18M 24M — — —

Floor standing type FXLQ 12M 18M 24M — — —

Concealed Floor standing type FXNQ 12M 18M 24M — — —

New refrigerant model code 12 type 18 type 24 type 30 type 36 type 48 type

Selecting model capacity 12,000Btu/h

18,000Btu/h

24,000Btu/h

30,000Btu/h

36,000Btu/h

48,000Btu/h

Equivalent output 1 ton 1.5 ton 2 ton 2.5 ton 3 ton 4 ton

4 General Information

Page 11: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Points to Bear in Mind at the System Design

2. Points to Bear in Mind at the System Design2.1 Points Relating to the Performance of the Air Conditioning

UnitsA number of points need to be borne in mind at the system design stage in order to ensure the mechanical efficiency of the air conditioning units.1. Path of refrigerant piping between outdoor and indoor units, height difference and pipe length.

Path of refrigerant piping should be determined such that length of piping is kept to a minimum.Piping should be kept within permissible limits in terms of length and height difference.

2. Positioning of outdoor unitPosition such that maintenance and repairs can be carried out. (leave room for servicing)Avoid reduction of airflow and short circuiting

Avoid reduction of airflow and short circuiting

General Information 5

Page 12: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Points to Bear in Mind at the System Design SiUS39-504

3. Positioning of indoor unitPosition such that maintenance and repairs can be carried out. (inspection port positions and size check)Avoid short circuitingEnsure sufficient drain pipe gradient (need for drain-up kit etc.)In the case of a ceiling mounted type make sure ceiling depth is sufficient (need for high performance filter, etc.)

6 General Information

Page 13: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Points to Bear in Mind at the System Design

2.2 The Installation is of Vital Importance

The analysis of major installation problems experienced is shown below;

How these installation problems affect an equipment are shown below:

General Information 7

Page 14: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Points to Bear in Mind at the System Design SiUS39-504

2.3 Striking a Balance between System Installation and General Construction Work (Comprehensive Flow Chart)

Note: 1. The division of the work should be thoroughly clarified. (This applies particularly to work relating to the connection of control wiring, fitting of remote controller and central control panel, boundary work on areas such as connection of drain piping and humidification supply piping, inspection and foundation)

2. Keep a constant check on the progress of the construction work to avoid deviations from the air conditioning work schedule.

3. For sleeve and insert work the positions of ceiling girders should be confirmed and sleeve and insert requirement, hole diameters, positioning and numbers decided. This is particularly important in the case of sleeves for drain piping.

8 General Information

Page 15: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Points to Bear in Mind at the System Design

2.4 Points to Bear in Mind when Preparing the Contract Drawings

The following points should be borne in mind when preparing the contract drawings from the original drawings and the execution drawings.The contract drawings for the air conditioning system are blueprints for the performance of the necessary work which are drawn up on the basis of the original drawings in such a way that a working balance is achieved between the specific requirements of each individual aspect of the work.

Contract Drawing Objectives include:The drawings should be easily comprehensible to those carrying out the work.The contents of the drawings should not be subject to subsequent alteration.

The following is a list of the main points to be considered when preparing contract drawings for the II System and should be used as a reference during this stage of the work:

2.4.1 At the Contract Drawing Stage the Following Points are Critical!!

Check points

Arrangement of units 1. Have you left the access passages clear and allowed sufficient room for servicing?2. Have you taken full account of the possibility of short circuits? (Both indoor and outdoor units)3. Can the air filters be replaced easily?4. Have you indicated the size and location of the ceiling inspection ports? (Make sure there no other installations in the

area above)5. Have you taken into account the depth of the installation area? (In case of ceiling built-in type)6. Have you specified the position of the indoor unit clearly? (Have you taken full account of relevant features of the local

ventilation, humidity and lighting?)

Refrigerant piping 1. Is the piping system correctly connected?2. Are the rise and fall pipes correctly connected?3. Are the lengths and height differences of the pipes within the

recommended limits?

Operational control 1. Are the interconnections between the piping and wiring of the indoor and outdoor units clearly shown?

2. Are the numbers of the local setting switches clearly shown? (Group No. and Unit No.)

3. Are the wiring connections between the remote controller and the centralized and remote controls clearly shown?Refer to the notes relating to the preparation of the control wiring system diagrams (see next page)

4. Are the different types of wires clearly marked?5. Are the any problems with the way the power supply cables and

control wiring have been separated or bound together?6. Are the inter-floor connections of the control wiring correct?7. Is the position of the remote controller clearly marked?

Miscellaneous 1. Have you checked the gradient of the drain piping? (Must be at least 1/100)

General Information 9

Page 16: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Points to Bear in Mind at the System Design SiUS39-504

2.4.2 Main Considerations in Preparation of Control Circuit DiagramsIn addition to the design of the appropriate this system configuration it is also essential that the control system be made amply clear. If the system is designed and installed without a clear, comprehensive plan then problems are inevitably going to occur during the test run.Servicing too will become much more time consuming than necessary. However, if control circuit diagrams are prepared along with the contract drawings in order to make the total system clearly visible then the essential points relating to the electrical connections will be easily understood, the test run will go off without a hitch and the whole system will be rendered fully effective.

Step 1: Compiling a System List

1. Mark each outdoor unit with a code.2. Add field settings and data for outdoor units, and outdoor unit No. if using sequential start.3. Add the model number of each indoor unit connected to each refrigerant circuit.4. Assign each indoor unit a code.5. Fill in the location of each indoor unit.6. Group indoor units controlled by one or two remote controllers. (group or individual control).7. Assign central group Nos. if using centralized control.8. Add field settings and optional equipment for indoor units.9. Add unit No. if making separate field settings for each indoor unit under group control.

Note: With the VRV II R-410A Heat Pump Series, unit No. is determined through automatic addressing, therefore readout unit Nos. after activating the power.

For details on field settings and centralized control group No., refer to the installation manual and system reference materials.

Example: System listOutdoor Unit Indoor Unit

Model Name (code) Field Settings Model Name System Name Location

Remote Controller

Group

Centralized Control Group

No.Unit No.

Optional equipment, field

settings, etc.

RXYQ96M (PAC1)

Cool/Heat selector: Indoor unitLow noise operation (L.N.O.P): Individual control Sequential start: ON Defrost: Earlier Sequential start No.

FXFQ12M 2F01 2nd floor office A 1–00

FXSQ18M 2F02 2nd floor office A (1–00)

FXFQ18M 2F03 2nd floor office A (1–00)

FXMQ30M 2F04 2nd floor office B 1–01

FXFQ12M 2F05 2nd floor office B (1–01)

RXYQ96M (PAC2)

Cool/Heat selector: Indoor unit Low noise operation (L.N.O.P): Individual control Sequential start: ON Defrost: Earlier

FXSQ24M 3F01 3rd floor office C 1–02

FXFQ24M 3F02 3rd floor office C (1–02)

FXSQ24M 3F03 3nd floor office C (1–02)

FXFQ24M 3F04 3rd floor office D 1–03

10 General Information

Page 17: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Points to Bear in Mind at the System Design

Step 2: Preparation of the Control Circuit Diagrams

The following sequence should be followed in order to prepare control circuit diagrams in accordance with the system list which has already been completed: Diagrams should be prepared for each individual outdoor unit. The outdoor unit model number should be

inserted into the diagram. (RXYQ96M) Insert name of refrigerant system. (PAC1, PAC2) Insert name of indoor unit. (FXFQ12M→FQ12M) Insert system name of indoor unit. Insert installation position. (Do this when demarcation is possible) Insert remote controller control wiring. (Group) Indicated by solid line. ........Solid line. Insert centralized control wiring. ........Dotted line Insert Group No. (G No. for each indoor unit with U No. 0)The control circuit diagrams are now complete.

Example: Control circuit diagram

General Information 11

Page 18: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

3. Installation3.1 Step by Step Installation Procedure

The above list indicates the order in which the individual work operations are normally carried out but this order may be varied where local conditions warrant such a change

12 General Information

Page 19: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

3.2 Work Involved in Individual Operations and Points to be Borne in Mind

3.2.1 Sleeve and Insert WorkOperational steps

Positioning of the Pipe Holes

a) The through holes for the drain piping should be positioned such that the pipes have a downward gradient. (The gradient must be at least 1/100. The thickness of the insulating materials must also be taken into consideration.)

b) The diameter of the through holes for the refrigerant piping should include an allowance for the thickness of the heat insulation materials. (It is a good idea to think of the liquid and gas pipes as pairs.)

c) Attention should be paid to the construction of the beam themselves since there are sometimes parts of the beam which cannot be used to accommodate through holes.

Example: Through holes in a reinforced concrete beam

Preliminary talks withconstruction company

Determineposition, size and number of units required

Carry out work Check work

(V0957)

General Information 13

Page 20: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Positioning the Insert

a) An insert is a metal tool which is inserted into a floor or a beam before the concrete is set such that fittings such as ducts, pipes or suspension bolts for hanging units can be fitted into place later. The positions of the inserts must be decided early.

Example: Steel insert

Important point:1. The weight of the fitting to be suspended must be taken into account when choosing the insert.

3.2.2 Installation of Indoor UnitOperational steps

Determine installationposition

Fit indoor unitMark installationposition

Fit suspensionbolts

(V0960)

14 General Information

Page 21: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

Positioning 3 essential points when installing an indoor unit

1. Height: Take care to account for final ceiling facing surface level2. Level: Level fitting is essential. (within ±1 degree of horizontal)3. Direction: The unit must be fitted in line with the ultimately visible ceiling joints

Important points1. The suspension bolts must be strong enough to support the weight of the indoor unit.2. Optional features must be added to the indoor unit prior to installation.3. The model name should be checked prior to installation.4. Take care to align the main unit correctly. (Bearing in mind piping layout and direction of blow out)5. Leave sufficient space for servicing to be carried out.6. Make inspection holes for model which need them.7. Fit the unit to ensure proper drainage.

General Information 15

Page 22: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Service Space for Indoor Units

Note: Above figure means minimum value. Please keep these value at least.

Note: Above figure means minimum value. Please keep these value at least.

Unit (Inch)FXFQ-M type

(length: in.)

Model HFXFQ12 · 18 · 24MVJU 9 7/16 or moreFXFQ30 · 36MVJU 11 3/4 or more

HH

*59or more

*59or more

*59or more

*59or more

Air discharge

Air discharge

39 3

/8 o

r mor

e

Air inlet

Air inlet

Air discharge

Air discharge

NOTE) Leave 7 7/8 or more space where marked with the *, on sides where the air outlet is closed.

Unit (Inch)

FXSQ-M type

For

inst

alla

tion

in h

igh

plac

es98

3/8

" or

mor

e

13/16"13/16"

16 General Information

Page 23: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

Note: Above figure means minimum value. Please keep these value at least.

Note: Above figure means minimum value. Please keep these value at least.

Unit (Inch)

FXMQ30, 36, 48M type

Unit (Inch)

FXHQ12, 24, 36M type

12 o

r mor

e

Air inlet

Air outlet

ObstructionFloor

Required service space

(Length : in.)

1 3/16 or more 1 3/16 or more∗∗

General Information 17

Page 24: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Note: Above figure means minimum value. Please keep these value at least.

Note: Above figure means minimum value. Please keep these value at least.

Unit (Inch)

FXAQ-M type

≥ 2 ≥ 2

[ Space required for installation (in.) ]

≥3

1/2

≥1

1/4

Floor

Obstruction

≤ 4 3/4

≥ 100 (from floor)For installation in high places.

Unit (Inch)

FXLQ-M, FXNQ-M type

Base

FXLQ

Window

4 or more(FXLQ)

6 or more(FXNQ)

4 or more(FXLQ)

3/4

or

mor

e

40 or more

70 or more

Air flow direction

Air inlet direction

Front side

(length : in.)

FXNQ

Maintenance area

3 1/

8 or

m

ore

A or moreB or more

24 5

/8

(length :in.)

(IMPORTANT) Leave sufficient clearance for air inlet and maintenance.

Model A (in.) B (in.)

FXNQ12MVJU 28 46

FXNQ18 · 24MVJU 39 57

18 General Information

Page 25: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

3.2.3 Refrigerant Pipe WorkOperational steps

The 3 Principles of Refrigerant Piping

The "3 principles of refrigerant piping" must be strictly observed.

Fit pipes provisionally

Install indoor unit

Solder Flushing Air tight test Vacuum drying

Cut pipes to size Replace nitrogen

(V0963)

The 3 principles of refrigerant piping

Dry Clean Air tight

Make sure there is no moisture inside the pipes

Make sure there is no dirt inside the pipe

Make sure the refrigerant does not leak out

Actoin to avoid problemCause of problem

l Rainwater, work water, etc. gets into pipes from outside

l Moisture generated inside pipes due to condensation

l Formation of oxides inside pipes during soldering

l Dirt, dust or other extraneous material gets into pipes from outside

l Leak from soldered area

l Leak from flared area

l Leak from flange area

Pipe covering Flushing

Replace nitrogen

Pipe covering

Air tight test

Flushing

Vacuum drying

Use the proper materials (copper pipe,

solder, etc.)

Adhere strictly to standard soldering

work practice

Adhere strictly to standard flaring work

practice

Adhere strictly to standard flange

connection work parctice

Cle

anD

ryA

ir tig

ht

(V0964)

General Information 19

Page 26: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Method for Replacing Nitrogen (Brazing)

If brazing work is carried out without passing nitrogen gas through the pipes which are being brazed then this allows the formation of oxidation bubbles on the inside surface of the pipes. These oxidation bubbles are then carried along inside the pipes to cause damage to various members of the system such as valves or compressors and the system ceases to function properly.

In order to avoid this problem nitrogen is passed through the pipes while the soldering work is being carried out. This operation is known as nitrogen replacement. (Air is replaced by nitrogen)

This is standard work practice for all brazing work.

Important points:1. The gas used must be nitrogen (oxygen, carbon dioxide and flon should not be used.)2. A pressure regulator must be used.

20 General Information

Page 27: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

Covering of Refrigerant Pipes

Covering is an extremely important operation as it prevents water, dirt or dust from getting inside the pipes. Moisture inside the pipes was a constant source of trouble in the past. The utmost care is required to nip this problem in the bud.

The end of each pieces of pipe must be covered. "Pinching" is the most effective method but "taping" is an simple alternative which may be used according to the work area and term of work.

1. Pinching methodThe end of the copper pipe is squeezed together and the gap brazed.

2. Taping methodThe end of the copper pipe is covered with PVC tape (vinyl tape).

<Taping method>

Particular care should be taken during the following operations:When passing copper pipe through a penetration hole (Dirt easily gets into the pipe).When copper pipe is located outside (Rainwater gets in)(Special care is needed when the pipes are standing vertically outside)

Location Term of Work Covering Method

Outdoors 1 months or more Pinching

Less than 1 months Pinching or taping

Indoors Irrelevant Pinching or taping

General Information 21

Page 28: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Refrigerant Pipe Flushing

[3 major effects]1. Removal of oxidation bubbles formed inside copper pipes when "nitrogen replacement is insufficient" during

soldering work2. Removal of extraneous material and moisture from pipes when covering has been insufficient3. Checks connections in pipes linking outdoor and indoor units (Both liquid and gas pipes)

[Example of procedure]1. Set pressure regulator on nitrogen cylinder.

∗The gas used must be nitrogen.(There is a danger of condensation if fleon or carbon dioxide are used and oxygen carries the risk of explosions.)

2. Connect the charge hose from the pressure regulator to the service port on the liquid pipe side of the outdoor unit.

3. Fit blanking plugs to all indoor units (B) other than unit A.

4. Open the main valve on the nitrogen cylinder and set the pressure regulator to 72psi.

5. Check that the nitrogen is passing through the unit A liquid pipe.

Flushing is a method of cleaning extraneous matter out of pipes using pressurized gas.

22 General Information

Page 29: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

6. Flushing.Block the end of the pipe with the insulation of your hand.

↓When the gas pressure becomes too great to contain remove insulation quickly. (First flush)

↓Block the end of the pipe with insulation again.

↓(Carry out second flushing)

(The nature and amount of the extraneous material inside the pipe can be checked during flushing by placing a rag lightly over the end of the pipe. In the unlikely case that even a small quantity of moisture is found then the inside of the pipe should be dried out thoroughly.)Action:1. Flush the inside of the pipe with nitrogen gas. (Until such time as the moisture disappears.)2. Carry out a thorough vacuum drying operation. (See page 35)

Close the main valve on the nitrogen cylinder. Repeat the above operation for unit B. When the liquid pipe operations have been completed then do the same with the gas pipes.

Choice of Materials for Refrigerant Piping

a) Refrigerant pipingThe piping used must meet the requirements of the JIS standard or equivalent. (Size, material, thickness, etc.) Specification: Oxidized phosphorous seamless copper pipeLong pipe lengths or coiled pipe (copper pipe with heat insulation coating) should be used to avoid the necessity for frequent brazing.(* Make sure the thickness and material shall be selected in accordance with following table.)

Size of Refrigerant Piping

*The thickness and material shall be selected in accordance with local code.

b) Brazed joints and special branches1. General use (L bend joint, socket joint, T joint, etc.)

Joints must meet the requirements of the relevant JIS standard. (Size, materials, thickness, etc.)2. Special branches

The Daikin outdoor unit multi connection kit, REFNET joint, REFNET header or Reducing socket should be used.

Outside Diameter in. (mm) Material

φ1/4 (φ6.4) 0

φ3/8 (φ9.5) 0

φ1/2 (φ12.7) 0

φ5/8 (φ15.9) 0

φ3/4 (φ19.1) 1/2H

φ7/8 (φ22.2) 1/2H

General Information 23

Page 30: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Example: R-410A RXYQ-M Series

Refer detail of DAIKIN REFNET joint and REFNET header on page 118.

c) BrazingThe Multi-System requires only copper/copper jointing and the jointing method is explained below.

The use of "hard solder" is essential.

The R-410A Heat Pump RXYQ-M Series uses a wide range of piping sizes. You should therefore be careful when selecting the nozzle tip.

Table 1: Correlation of nozzle tip and size of refrigeration piping

Note: The values in the table above are for type B torch (French).

BCup-2 reacts easily with sulfur to form a fragile water-soluble compound and should not therefore be used where the environment is not suitable.

φ1/4 (6.4)

φ3/8 (9.5)

φ1/2 (12.7)

φ5/8 (15.9)

φ1/2 (19.1)

φ7/8 (22.2)

Nozzle tip No.

1.6 2.4

(V0977)

in. (mm)

Pip

ing

size

# 200 # 225 # 250 # 315

Brazing rod diameter φ

24 General Information

Page 31: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

Brazing a) Brazing work should be carried out such that the final result is directed either downwards or sideways. An upward direction should be avoided wherever possible. (to prevent leakage)

b) Liquid and gas pipe branches should always be dealt with in the specified way with attention being paid to the direction of the fitting and its angle. (to prevent oil return or drift) For example see page 134.

c) It is standard working practice to use the nitrogen replacement method when brazing.

Important points1. Every effort must be made to avoid fire. (Clean area where brazing is to be performed and make sure that

fire fighting equipment and water are ready to hand.)2. Be careful of burns.3. Make sure that the gap between the pipe and the joint is correct. (To prevent leaks)4. Is the pipe adequately supported?

As a rule the gaps between supports for horizontal piping (copper pipe) are as follows:

The copper pipe should not be secured directly by metal brackets.

Copper pipe support spacing (From HASS 107-1977)

Nominal diameter φ1/2 or less φ7/8

Maximum gap (Inch) 40 60

General Information 25

Page 32: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Flare Connection (a) Stiffened pipe must always be annealed at least once prior to the flaring work.(b) A pipe cutter must be used to cut the pipe. (A large pipe cutter must be used where the pipe has a large

diameter. When cutting a pipe which is too big for the pipe cutter a metal saw may be used but care must be taken to ensure that the debris from sawing does not get into the pipe.)

(c) Set the flaring tool to make sure the flare size remains within the prescribed limits.

New Rank Compatible Flare ToolCompared to previous refrigerants, the components of a HFC refrigerant is small. R-410A also has a higher pressure than other refrigerants. Therefore, in order to strengthen the intensity of the form and size of the flare section used for R-410A (class 2) apparatus, unlike the specification of the conventional refrigerants, it was set up with different standards.When carrying out flare processing, use a new rank compatible flare tool or a conventional flare tool.

Flare Gauge (Adapter Corresponding to the New Rank)When using the later, use a flare gauge to take out the pipe from the gauge bar, adjust it, and then carry out the flare processing.

Size from the dice surface to the copper tip (in mm)

(d) Coat the inner and outer surface of the flare with refrigerator oil (Ester or ether oil). (this ensures that the flare nut passes smoothly, preventing the pipe from twisting.)Do not use SUNISO-4GS oil.

Nominal diameter External diameter of pipe d (mm)

Pipe widening dimensions A (mm)

1/4" 6.35 9.1

3/8" 9.52 13.2

1/2" 12.7 16.6

5/8" 15.88 19.7

NameOuter

diametermm

Wall thickness

mm

Previous refrigerant (R22, R407C etc.) R-410AThe conventional flare tool The conventional flare tool

Clutch type Clutch type1/4" 6.35 0.8 0~0.5 1.0~1.53/8" 9.52 0.8 0~0.5 1.0~1.51/2" 12.70 0.8 0~0.5 1.0~1.55/8" 15.88 1.0 0~0.5 1.0~1.5

12mm×72mm1.0×0.5mm Each

Flare gauge

Size

Thickness

26 General Information

Page 33: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

Important points1. Burrs should be carefully removed.2. 2 spanners should be used to grip the flare nuts.3. The flare nut must be inserted before starting the flaring operation.4. The appropriate amount of torque should be used to tighten the flare nut.

5. Check that there is no superficial damage to the surface of the flare.

Standard torques for tightening flare nut ±10%

SizeTorque

ft. lbf (kgf-cm) (N-cm)1/4(6.4φ) 10.4~12.7 144~176 1420~17203/8(9.5φ) 24.1~29.4 333~407 3270~39901/2(12.7φ) 36.5~44.5 504~616 4950~60305/8(15.9φ) 45.6~55.6 630~770 6180~7540

General Information 27

Page 34: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Flaring Procedure

28 General Information

Page 35: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

Not Recommendable But in Case of Emergency

You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may follow the installation method mentioned below.

After the work is finished, make sure to check that is no gas leak.

When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque suddenly increases. From that position, further tighten the flare nut the angle shown below:

Pipe size in. (mm) Further tightening angle Recommended arm length of tool

φ1/4" (6.4) 60 to 90 degrees Approx. 6" (150mm)

φ3/8" (9.5) 60 to 90 degrees Approx. 8" (200mm)

φ1/2" (12.7) 30 to 60 degrees Approx. 10" (250mm)

φ5/8" (15.9) 30 to 60 degrees Approx. 12" (300mm)

General Information 29

Page 36: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Flange Connection

a) The flange sheet surface should be clean and undamaged. (Clean any dirt away with a cloth and check that there has been no damage.)

b) Coat the flange sheet surface with refrigeration oil (Ester or ether oil) and then insert the packing. (Do not use SUNISO oil.)

c) Tighten the bolts in opposite corners first to ensure that the connection is true.

Important points1. Only clean refrigeration/oil should be used to coat the flange. (i.e. free from dirt or water)2. The correct amount of torque should be applied when tightening the flange bolts.

Standard torques for tightening screws and bolts

ISO hexagonal bolt

[Example]

Order:A→C→B→D The bolts should be tightened little by little in the above order such that the same degree of torque is applied evenly to each corner.

Class 5.8(5T) 10.9(10T)

Size ft. lbf kgf-cm ±15% N-m ±15% ft. lbf kgf-cm ±15% N-m ±15%

M8 9.0 125 1230 21.8 302 2960

M10 18.6 257 2520 44.9 620 6080

M12 31.6 436 4280 76.0 1,050 10,300

M16 74.6 1,030 10,100 179.7 2,480 24,300

M20 148.5 2,050 20,100 358.7 4,950 48,500

30 General Information

Page 37: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

3.2.4 Thermal Insulation Work (Refrigerant Piping)Operational steps

Materials The thermal insulation materials which are used must be well able to withstand the heat from the pipes.Example:Heat pump type: Heat resistant polyethylene foam (heat resistance of at least 120°C)Cooling only: Polyethylene foam (heat resistance of 100°C or more)

Essential Points of Thermal Insulation

The insulation of jointed areas such as the soldered, flared or flanged sections should only be carried out after the successful completion of the air tight test.Attention should be paid to the unit model and its operating conditions since there are occasions when the gas and liquid pipes also need to be thermally insulated.

Important points1. The thickness of the thermal insulation material must be determined in the light of the pipe sizes.

2. It will be necessary to increase the values in the above table for top floors or where conditions are hot and humid. (Refer to Installation manual "6-5 Pipe insulation" for more detail)

3. Where a customer supplies his own specifications then these must be adhered to.4. Where it is anticipated that the air conditioning unit will be operated at external air temperatures of 10°C or

less then thermal insulation will also be required for the liquid pipes.

Refrigerant pipe work

Insulation(jointed areas)

Insulation (with the exception of the jointed areas)

Air tight test

(V0985)

Pipe size in. (mm) Thickness of insulation material

φ1/4~φ1 (6.4mm~25.4mm) φ1/2 or more (12.5mm or more)

General Information 31

Page 38: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

3.2.5 Air Tight TestOperational steps

Essential Points of Testing (Maintaining Pressure Over a Period)

The key to successful testing is strict adherence to the following procedure:a) The liquid and gas piping in each refrigerant system should be pressurized in turn in accordance with the

following steps. (Nitrogen gas must be used.)

∗Increasing the system pressure to 551psi does not guarantee the identification of minor leaks if pressure is maintained for only a short time. It is therefore recommended that the system remain pressurized in accordance with Step 3 above for at least 24 hours.

Note: The pressure must on no account be increased beyond 551psi.

Complete refrigerant pipe installation work

Pressurize Check for pressure drop Success

Locate and repair leaks(V0987)

Step 1: increase pressure to 13.05psi for 3 minutes or more

Indicates existence of major leaksStep 2: increase pressure to 217psi for 5 minutes or more

Indicates existence of minor leaksStep 3: increase pressure to 551psi for approx. 24 hours

32 General Information

Page 39: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

b) Check for pressure dropIf there is no drop in pressure then the test is deemed a success.If the pressure drops then the leak must be located. See following page.However, if there is a change in the ambient temperature between the pressurizing stage and the time when you check for a drop in pressure then you will have to adjust your calculations accordingly since a change of 1°F can account for a pressure change of approximately 0.80psi.Compensating adjustment value:(temperature at time of pressurizing – temperature at time of checking) × 0.80Example:Time of pressurizing: 551psi 77°F24 hours later: 543psi 68°FThe pressure drop in such a case is deemed to be zero (successful test).

Checking for Leaks

[Check 1] (Where pressure falls while carrying out Steps 1 to 3 described on previous page)Check by ear......Listen for the sound of a major leak.Check by hand......Check for leak by feeling around jointed sections with hand.Soap and water check (∗Snoop)......Bubbles will reveal the presence of a leak.

[Check 2] (When searching for a minor leak or when there has been a fall in pressure while the system has been fully pressurized but the source of the leak cannot be traced.)1. Release the nitrogen until the pressure reaches 13.05psi.2. Increase pressure to 217psi using gaseous flon gas (R-410A). (Nitrogen and flon gas mixed)3. Search for the source of the leak using a leak detector.4. If the source of the leak still cannot be traced then repressurize with nitrogen up to 3.80MPa and check

again. (The pressure must not be increased to more than 551psi.)

Setup of Air-light TestAs for the air-tight test, the setup of devices shown in the following figure is recommended with considerations given to "vacuum drying and refrigerant additional charging", which are operation steps following the air-tightness test.

550

psi

500

450

400

350

300

250

200

150

100

50

0

13.05psi

217psi

551psi

General Information 33

Page 40: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

In order to conduct the air-tight test, with stop valves of 8.Gas side, 10.liquid side and those of the refrigerant and vacuum pump all closed, then open the nitrogen gas stop valve, 7.Valve A, while adjusting the nitrogen gas pressure regulating valve, thus increasing the pressure.

1.Pressure reducing valve2.Nitrogen3.Refrigerant cylinder4.Siphon system5.Measuring instrument6.Vacuum pump7.Valve A8.Gas side9.Outdoor unit10.Liquid side11.Indoor unit12.Shutoff valve service port13.Charge hose17.Dotted lines represent onsite piping

Important points1. Where the lengths of piping involved are particularly long then the air tight test should be carried out block

by block.Example:1. Indoor side2. Indoor side + vertical pipes3. Indoor side + vertical pipes + outdoor side

1

2

3

4

5 6

7

8

9

10 11

12

17

13

34 General Information

Page 41: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

3.2.6 Vacuum Drying

What is Vacuum Drying?

Vacuum drying is:"The use of a vacuum pump to vaporize (gasify) the moisture (liquid) inside the pipes and expel it leaving the pipes completely dry inside."At 1 atm (760 mmHg) the boiling point (evaporating temperature) of water is 212°F (100°C) but if a vacuum is created inside the pipes using a vacuum pump then the boiling point is rapidly reduced as the degree of the vacuum is increased. If the boiling point is reduced to a level below that of the ambient temperature then the moisture in the pipes will evaporate.

The evacuation of air conditioner piping provides the following effects.1. Vacuum drying2. Removes air and nitrogen (used in air-tightness test) from the inside of pipes.Therefore, it is necessary to ensure that the both purposes have been achieved in the vacuum drying operation.

<Example>When outside temperature is 44.9°F (7.2°C)As shown in the table on the right, the degree of vacuum must be lowered below –752mmHg.

Boiling point of water °F (°C)

Pressure

∗mmHg Pa Torr psi

104 (40) –705 7333 55 –13.69

86 (30) –724 4800 36 –14.0

80 (26.7) –735 3333 25 –14.2

75.9 (24.4) –738 3066 22 –14.28

71.9 (22.2) –740 2666 20 –14.31

69.0 (20.6) –742 2400 18 –14.35

64.0 (17.8) –745 2000 15 –14.41

59.0 (15.0) –747 1733 13 –14.45

53.0 (11.7) –750 1333 10 –14.51

→ 44.9 (7.2) –752 1066 8 –14.55

32 (0) –755 667 5 –14.61

Above figures (mmHg) are gauge pressure readings.

General Information 35

Page 42: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Choosing a Vacuum Pump

GeneralRefrigerant piping content volume of the VRVII R-410A Series is larger than the VRV Inverter Series, and consequently takes more time for vacuum drying. If you have time to spare, you may use the same vacuum pump, but if you want to save time, you will have to use a pump with higher exhaust velocity (exhaust volume).

The Necessity for Counter Flow PreventionAfter the vacuum process of the refrigerant cycle, the inside of the hose will be vacuumed after stopping the vacuum pump, and the vacuum pump oil may flow back. Moreover, if the vacuum pump stops during the operation by some reason, the same thing happens.In such cases, different oil mixes in the HFC system refrigerant apparatus cycle, and becomes the cause of a refrigerant circuit trouble. Therefore, in order to prevent the counter flow from the vacuum pump, a check valve is needed.

Vacuum pump with check valve or vacuum pump adapter

1. Vacuum pump performanceThe 2 most import things for determining vacuum pump performance are as follows: (1) Exhaust velocity(2) Degree of vacuum

(1) Exhaust velocityExhaust volume is usually expressed as l/min or m³/h. The larger the number, the faster vacuum id achieved.Generally speaking, the faster the exhaust velocity, the larger and heavier the vacuum pump itself is. Commercially available vacuum pumps (exhaust velocity of 20 - 30 l/min) usually take an extremely long time to achieve vacuum. (We recommend a vacuum pump of approx. 60 - 100 l/min.)

Key pointsLower the degree of vacuum to below –14.6psi (–755mmHg)

(V1216)

Vacuum pump adapterReverse flow preventive vacuum adapter

Vacuum pump with check valve

36 General Information

Page 43: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

(2) Degree of vacuumUltimate vacuum varies largely according to use of the vacuum pump. Vacuum pumps used for vacuum forming cannot be used for vacuum drying. (A vacuum pump with a high degree of vacuum is required.)

When selecting a vacuum, you should select one which is capable of achieving 0.2 Torr of ultimate vacuum.

Degree of vacuum is expressed in Torr, micron, mmHg, and Pascal (Pa). The units correlate as follows:

2. Vacuum pump maintenanceBecause of their nature, most vacuum pumps contain large amounts of oil which lubricates bearings, etc., and functions to enhance airtightness of pistons. When using a vacuum pump to discharge air from refrigerant piping, moisture in the air tends to get mixed in with the oil. You must therefore change oil periodically and make sure the proper oil level is maintained. (Perform periodic inspections in accordance with the operating instructions.)

3. Degree of vacuum measurementAn extremely accurate vacuum gauge is required to test degree of vacuum. You cannot accurately measure degree of vacuum with the compound gauge on the gauge manifold. A Pirani vacuum gauge is required to measure degree of vacuum accurately. Because Pirani gauges are very sensitive and require extreme care when using, they are not very suitable for use in the field. You should therefore use the Pirani gauge to calibrate the attached vacuum gauge on the gauge manifold and the degree of vacuum of the vacuum pump.

Unit Standard atmospheric pressure Perfect vacuum

Gauge Pressure kg/cm2 0 –1.033

Absolute Pressure kg/cm2 abs 1.033 0

Torr Torr 760 0

Micron Micron 760000 0

∗mmHg mmHg 0 760

Pa hPa 1013.33 0

psi psi 0 –14.7

Degree of vacuum must be within the range expressed by

0 Torr0 Micron

0 Pa760 mmHg–14.7 psi

Perfect vacuum

5 Torr5000 Micron

667 Pa755 mmHg–14.6 psi

Vacuum target value

760 Torr760000 Micron1013.33 hPa

0 mmHg0 psi

Standard atmospheric pressure

(V0992)

General Information 37

Page 44: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

4. Calibration method1. Connect a Pirani vacuum gauge and the gauge manifold vacuum gauge (0 - 760 mmHg) to the vacuum

pump at the same time, and run the pump for about 3 minutes. 2. Make sure the reading of the Pirani vacuum gauge is 5 Torr (667 Pa) or less. The reading of conventional

vacuum pumps lowers to about 0.2 Torr.If the reading is not 5 Torr or less, check the vacuum pump oil. (Oil is low in many cases.)

3. Check the attached gauge on the gauge manifold. Adjust the gauge if the reading is not exactly correct.4. Adjust the gauge manifold valve so that the Pirani vacuum gauge reads 5 Torr.5. Mark the position indicated by the gauge manifold gauge with an oil based ink pen.6. Use the mark of the gauge manifold as a target when vacuuming in the field.

(Reference) Types of vacuum pump with respective maximum degree of vacuum

TypeMaximum Degree of Vacuum Use

Expulsion Capacity Vacuum Drying Air Expulsion

Oil Rotary (Oil Using)

–14.66psi (0.02 mmHg)100 l/min Suitable Suitable

Oilless Rotary (No Need of Oil)

–14.5psi (10 mmHg)50 l/min Unsuitable Suitable

–14.66psi (0.02 mmHg)40 l/min Suitable Suitable ←Many handy

pumps fall into this category

38 General Information

Page 45: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

Vacuum Drying Procedure

There are two vacuum drying methods and the appropriate one should always be chosen to conform with individual local conditions.[Normal vacuum drying]........The standard method

[Operational steps]1. Vacuum drying (1st time): Connect a manifold gauge to the service port of the liquid or gas pipe and

operate the vacuum pump for at least 2 hours.(The degree of vacuum produced should be in excess of –14.61psi (–755 mmHg))If after 2 hours the vacuum produced has not exceeded 5 mmHg then either there is moisture in the pipe or there is a leak. Operate the vacuum pump for a further hour.If, even after 3 hours, the vacuum has not reached –14.61 (–755 mmHg) then check the system for a leak.

2. Carry out maintained vacuum test.Produce a vacuum in excess of –14.61psi (–755 mmHg) and do not release it for an hour or more. Check the vacuum gauge to make sure that it has not risen. (If the gauge does rise then there is still moisture in the pipe or there is a leak somewhere.)

3. Additional charge of refrigerant.Connect the charging cylinder to the liquid pipe service port and charge with the required amount of refrigerant.

4. Open stop valve to the full.Open the stop valves on the liquid and the gas pipes to the full.

Note: Vacuums should be produced in both the liquid and the gas pipes.(Because there are a large number of functional components in the indoor unit which cut off the vacuum mid–way through)

7.25psi

0psi

–14.7psi

–14.6psi(–755mmHg)

General Information 39

Page 46: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Special vacuum drying

This vacuum drying method is selected when there is a suspicion that there may be moisture in the pipes.For example:

When moisture was discovered during the refrigerant pipe flushing operationWhen there is a risk of condensation forming inside the pipes during periods of heavy rainfallWhen there is a risk of condensation forming inside the pipes if this refrigeration pipe works takes long timeWhen there is a risk that rainwater may have entered the pipes during installation

The special vacuum drying method is the same as the standard method except that nitrogen is introduced into the pipes to break the vacuum on one or more occasions during the course of the operation.

[Operational steps]1. Vacuum drying (1st time): 2 hours2. Vacuum breaking (1st time): Use nitrogen to raise pressure to +7.25psi (+0.05MPa).

(Since the nitrogen gas used to break the vacuum is dry nitrogen this process serves only to enhance the overall drying effect of the vacuum drying operation itself. However, since the effectiveness of this process is severely impaired by a high moisture level inside the pipes, the utmost care is required during installation to see that water does not enter or form inside the refrigerant pipes.)

3. Vacuum drying (2nd time): Operate the vacuum pump for at least 1 hour.(Observations: Degree of vacuum has reached –14.61psi (–755 mmHg). If the degree of vacuum has not reached –14.61psi (–755 mmHg) after 2 hours or more then repeat the operations at 2 (vacuum breaking) and 3 (vacuum drying) above.)

4. Carry out maintained vacuum test: 1 hour5. Additional charge of refrigerant6. Open stop valve to the full

∗ The gas used for the vacuum breaking operation must be nitrogen.(The use of oxygen brings a serious risk of explosions)

40 General Information

Page 47: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

3.2.7 Additional Charge of Refrigerant at installation timeOperational steps

Important points1. The results of all calculations must be recorded. (Make a list.)2. The additional charging operation should be carried out by input of liquid from Service port at liquid stop

valve following completion of the vacuum drying operation.3. When the additional charging operation cannot be satisfactorily completed, use the action of the

compressor to complete the additional charging during the test run.

Refrigerant Charging Instructions

HFC401A are Quasi-azeotropic* refrigerants. Therefore, these refrigerants must be charged in the liquid state. When charging the refrigerant into equipment from the refrigerant cylinder, turn the refrigerant cylinder upside down.

Important: Make sure that the refrigerant (liquid) is taken out from the bottom part of the refrigerant cylinder. Do not take out the refrigerant (gas) at the upper part of the refrigerant cylinder for charging.

Use the length of the piping to calculate the amount of refrigerant required

Additional charge of refrigerant

(V0995)

General Information 41

Page 48: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Caution Since some refrigerant cylinders differ in the internal mechanism, it is necessary to examine the cylinder carefully. (Some cylinders have a siphon tube to eliminate the need for turning it upside down.)

Siphon tube

<*Non-azeotropic refrigerants or Quasi-azeotropic refrigerants>When a refrigerant is a mixture of two or more types with different evaporation temperature, it is called a non-azeotropic refrigerant. If all refrigerant components evaporate at the same temperature, the mixture is called an azeotropic refrigerant.If a non-azeotropic refrigerant is charged into equipment in the gaseous state, the refrigerant components that evaporate sooner than others enter the equipment, and the refrigerant that evaporate after others remain in the refrigerant cylinder.

*Quasi-azeotropic mixture refrigerant: mixture of two or more refrigerants having similar boiling points.

Caution itemsThe following devices designed for R-22 cannot be used to charge the new refrigerants. Be sure to use the devices specifically designed for the new refrigerants.1. Charging cylinder...(Pressure resisting specification is different.)2. Gauge manifold (including hose)...(same as above)

42 General Information

Page 49: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

3.2.8 Drain Pipe Work (Indoor)Operational steps

Drain Pipe Gradient and Support

a) The drain pipe must be fitted at a gradient of at least 1/100.The drain pipe should be as short as possible and free from airlocks.

b) Suspension bolts should be used to support long stretches of drain pipe in order to ensure that a gradient of 1/100 is maintained. (PVC pipes should not be bent)

Spacing of supports for horizontal piping

c) The length of pipe laid horizontally should be kept to a minimum.

Drain Trap Fit any indoor unit whose drain pipe connection is subjected to negative pressure, with a drain trap.(FXMQ30~48M only)

a) Rig the drain trap as shown in the drawing bellow.

b) Provide one trap per unit. A single trap for converging units will prove ineffective.

c) Rig the trap to allow for future cleaning.

Insulate drain pipeInstall indoor unit Connect drain pipeCheck for water

leaks

(V0999)

Class Nominal diameter Spacing

Rigid PVC pipe 1"~1 1/2" (25~40mm) 3.28~4.92 ft (1~1.5m)

General Information 43

Page 50: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Grouped Drain Piping

1. It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible.

2. The pipework should be kept as short as possible and the number of indoor units per group kept to a minimum.

Use of an Auxiliary Drain Hose (Flexible)

If a drain pan made of polystyrene foam is used then an auxiliary drain hose (flexible) is also essential. A flexible drain hose permits the drain socket and drain pipe to be connected without difficulty and prevents any undue strain being placed on the drain pan.

Important points1. The drain pipe should be at least equal in size to that of the indoor unit.2. The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe.3. The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has

been connected some water should be added to the drain pan and the drain pump checked to see that it is functioning correctly.

4. All connections should be secure. (Special care is needed with PVC pipe)The use of a colored adhesive with PVC pipes will help you to remember to connect them up.)

44 General Information

Page 51: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

Piping Diameter for Grouped Drain Pipes

Select piping diameter from the below table in accordance with the amount of condensation drained by all units with a common drain pipe.Consider 2 l/hr of drainage for every 1 HP. For example, drainage from 3 units running at 2 HP and 2 units running at 3 HP is calculated as follows. 2 (l/hr) × 2 (HP) × 3 (units) + 2 (l/hr) × 3 (HP) × 2 (units) = 24 l/hr

1. Relationship between horizontal pipe diameter and allowable drainage (for extended ventilation system)

Notes: Calculations have been made with water area inside the pipe as 10%.Allowable flow rate figures below the decimal have been discarded.Use VP30 or larger pipe after the convergence point.

2. Relationship between riser diameter and allowable drainage (for extended ventilation system)

Notes: Allowed flow rate figures below the decimal have been discarded.Use VP30 or larger pipe in risers.Use the same drain pipe for the humidifier as the indoor unit.

JIS nominal Vinyl chloride pipe diameter in. (mm)

Allowable flow rate (l/hr)Remarks

Piping gradient 1:50 Piping gradient 1:100

VP20 3/4" (20) 39 27 (Reference value) Cannot be used in grouped piping.VP25 1" (25) 70 50

VP30 1 1/4" (31) 125 88Can be used in grouped piping.VP40 1 1/2" (40) 247 175

VP50 2" (51) 473 334

JIS nominal Vinyl chloride pipe diameter in. (mm)

Allowable flow rate(l/hr) Remarks

VP20 3/4" (20) 220 (Reference value) Cannot be used in grouped piping.VP25 1" (25) 410

VP30 1 1/4" (31) 730

Can be used in grouped piping.

VP40 1 1/2" (40) 1440

VP50 2" (51) 2760

VP65 2 1/2" (67) 5710

VP75 3" (77) 8280

General Information 45

Page 52: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Ceiling Mounted Cassette Type (FXFQ-M Multi-flow)

1. Rig drain piping

Note:

Lay pipes so as to ensure that drainage can occur with no problems. Employ a pipe with either the same diameter or with the diameter larger (excluding the raising section) than

that of the connecting pipe (PVC pipe, nominal diameter 25 mm, outside diameter 32 mm). Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets from

forming. If the drain hose cannot be sufficiently set on a slope, execute the drain raising piping. To keep the drain hose from sagging, space hanging wires every 40 to 60 inches.

1/100 gradient or more3.28~4.92 ft

Fig. 18

GOOD

Hanger bracket

Fig. 19

WRONG

n n

n

n n

n

• •

n •

n

n n Use the attached drain hose (1) and clamp (2).

Insert the drain hose into the drain socket up to the base, and tighten the clamp securely within the portion of a white tape of the hose-inserted tip. Tighten the clamp until the screw head is less than 3/16" from the hose.

Wrap the attached sealing pad (10) over the clamp and drain hose to insulate.Make sure that heat insulation work is executed on the following 2 spots to prevent any possible water leak-age due to dew condensation. Indoor drain pipe Drain socket

<PRECAUTIONS FOR DRAIN RAISING PIPING>Install the drain raising pipes at a height of less than 21 5/8".

n Install the drain raising pipes at a right angle to the indoor unit and no more than 11 13/16" from the unit.

Clamp (2)

Tape (White)

Drain hose (1)

Fig. 20

Clamp (2) Large sealing pad (10)

(attached) (attached)

≤ 3/16"Fig. 21

Ceiling slab

Clamp (attached) (2)

Drain raising pipe

Raising section

Drain hose (attached) (1)

≤ 29

1/2"

Hanger bracketAdjustable (≤ 21 5/8")

3.28~4.92 ft≤ 11 13/16"

7 7/8"

Fig. 22

To ensure no excessive pressure is applied to the included drain hose (1), do not bend or twist when install-ing. (This may cause leakage.)

If converging multiple drain pipes, install according to the procedure shown below.

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.

≥ 3

15/1

6"

T-joint converging drain pipes

Slope downwards at a gradient of at least 1/100

Fig. 23

n

n

46 General Information

Page 53: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

2. After piping work is finished, check if drainage flows smoothly.

Caution:

Add approximately 67oz (2000 cc) of water slowly from the air outlet and check drainage flow.

WHEN ELECTRIC WIRING WORK IS FINISHED Check drainage flow during COOL running, explained under ‘‘TEST OPERATION’’.

WHEN ELECTRIC WIRING WORK IS NOT FINISHED Remove the terminal box lid connect a power supply and remote controller to the terminals.

(Refer to the Installation Manual)

Next, press the inspection/test operation button “ ” on the remote controller. The unit will engage the

test operation mode. Press the operation mode selector button “ ” until selecting FAN OPERATION

“ ”. Then, press the ON/OFF button “ ”. The indoor unit fan and drain pump will start up. Check

that the water has brained from the unit. Press “ ” to go back to the first mode. Note that the fan also starts rotating. Attach the terminal box lid as before.

TEST

TEST

n

n

n

n n

The water inlet lidDrain pipe

Portable pump

Inspection opening

Service condensate outlet (with rubber plug)(Use this outlet to condensate water from the drain pan)

Bucket(Adding water from inspection opening)

Plastic watering can(Tube should be about 3 15/16" long.)

3 15/16" or more

⟨Adding water through air discharge outlet⟩

[Method of adding water]

208V–230VSingle phasepower supply

Power supply terminal block

Indoor unit PC board

Electric parts box lid (1)

Electric parts box lid (2)

Power supply terminal block

Drain piping connectionsDo not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sew-age might enter the indoor unit through the drain pipes and corrode the heat exchanger.

General Information 47

Page 54: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Ceiling Mounted Built-in Type (FXSQ-M)

Drain PipingRig the drain pipe as shown below and take measures against condensation. Improperly rigged piping could lead to leaks and eventually wet furniture and belongings.

(1) Rig drain piping• The diameter of the drain pipe should be greater than or equal to the diameter of

the connecting pipe (vinyl tube; pipe size: 1" ; outer dimension: 1 1/4").• Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent

air pockets from forming.• If the drain hose cannot be sufficiently set on a slope, execute the drain raising

piping.• To keep the drain hose from sagging, space hanging wires every 40 to 60".

Caution Setting the unit at an angle opposite to the drain piping might cause leaks.

• Use the attached drain hose and clamp metal. Tighten the clamp firmly. Insert the drain hose into the drain socket, up to the white tape. Tighten the clamp until the screw head is less than 3/16" from the hose.

• Wrap the attached sealing pad over the clamp and drain hose to insulate.

• Insulate the drain hose inside the building.

⟨ ⟨ ⟨ ⟨ PRECAUTIONS FOR DRAIN RAISING PIPING ⟩⟩⟩⟩

⟨ ⟨ ⟨ ⟨ HOW TO INSTALL PIPING ⟩⟩⟩⟩(1) Connect the drain hose to the drain raising pipes, and insulate them.(2) Connect the drain hose to the drain outlet on the indoor unit, and tighten it with the clamp.

No Good Good

≤3/16"

Large sealing padClamp metal

(attached) (attached)Clamp metal

Drain hoseTape (White)

48 General Information

Page 55: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

(3) Insulate both metal clamp and drain hose with the attached sealing pad.

• If converging multiple drain pipes, install according to the procedure shown below.

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.

(2) After piping work is finished, check drainage flows smoothly.• Open the water inlet lid, add approximately

34 oz. (1000 cc) of water gradually and check drainage flow.

A

When canvas duct is installed

13 3/4~20 7/8"

When air inlet panel is directly installed

10 13/16"

A

Drain raising pipeClamp (Attached with unit)

Drain hose (Attached with unit)

Ceiling slab

11 13/16"or less

Hanging bar

Adjustable range(0 – 9 13/16 ")

Part to be procuredin the field

3.28~4.92 ft

T-joint converging drain pipes

≥3 1

5/16

"

3P086156-3A-9

Open

Water inlet

Portable pump

Water inlet lid

Refrigerant pipes Close

Bucket

Drain outlet for maintenance

(with rubber plug)

Note: Use this outlet to drain water from the drain pan.

Adding water frominspection opening

[ WHEN ELECTRIC WIRING WORK IS FINISHED ]• Check drainage flow during COOL running, explained under “TEST OPERATION.”

[ WHEN ELECTRIC WIRING WORK IS NOT FINISHED ] Remove the electric parts box lid, connect a power supply and

remote controller to the terminals. (Refer to the “Installation Manuals”)Next, press the inspection/test operation button “ ” on the remote controller. The unit will engage the test operation mode.

Press the operation mode selector button “ ” until selecting FAN

OPERATION “ ”. Then, press the ON/OFF button “ ”. The indoor unit fan and drain pump will start up. Check that the water

has drained from the unit. Press “ ” to go back to the first mode. You can check whether drainage is satisfactory or not by removing the access opening lid and checking the

water level of the drain pan through the access opening. Be careful when doing so because the fan is turning at the same time.

TEST

TEST

3P086156-3A-10

L2L1

Electric parts box208 – 230V single phase power supply.

Indoor PC board

L2L1

Power supplyterminal block

General Information 49

Page 56: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Ceiling Mounted Duct Type (FXMQ-M)

Note: If installing central drain piping, install according to the following right figure.(Install a drain trap for each indoor unit.)

• After piping work is finished, check drainage flows smoothly.

3P080156-2-8

<<Rig the drain pipe as shown below and take measures against condensation. Improperly rigged piping could lead to leaks and eventually wet furniture and belongings.>><<Insulate the drain hose inside the buildings>>(1) Install the drain pipes.

• Keep piping as short as possible and slope it downwards so that air may not remaine trapped inside the pipe.

• Keep pipe size equal to or greater than that of the connecting pipe (Vinyl pipe of 1" norminal diam. and 1 1/4" outer diam.).

• Use the attached drain hose and clamp.Tighten the clamp firmly.

• Insulate the clamp metal with the attached sealing pad.

• There is negative pressure inside the unit relative to atmospheric pressure when the unit is running, so be sure to provide drain frap on the drain outlet. (See the figure)

• In order to prevent foreign matter from building up inside the piping, you should avoid curves as much as possible, and arrange so the trap can be cleaned.

FXMQ30-48M

1 15/1

6"1 1

5/16"

1

50 General Information

Page 57: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

Ceiling Suspended Type (FXHQ-M)

(1) Carry out the drain piping.Make sure piping provides proper drainage.You can select whether to bring the drain piping out from the rear right or right. For rear right-facing and right-facing situations, refer to “6. REFRIGERANT PIPING WORK” on page 7.Make sure the pipe diameter is the same or bigger than the branch piping. (vinyl-chloride piping, nominal diameter 1 in., external diameter 1 1/4 in.)Make sure the piping is short, has at least a 1/100 slope, and can prevent air pockets from forming. (Refer to Fig. 21)Do not allow any slack to gather in the drain pipe inside the indoor unit.(Slack in the drain pipe can cause the suction grille to break.)

Caution Water accumulating in the drain piping can cause the drain to clog.

Be sure to use the drain pipe (1) and metal clamp (2).Also, insert the drain pipe completely into the drain socket, and securely attach the metal clamp bracket inside the gray tape area on the inserted tip of the drain pipe. (Refer to Fig. 22)Screw the screws on the metal clamp bracket until there is 5/32 in. left. (Pay attention to the direction of the attachment to prevent the metal clamp bracket from coming into contact with the suction grille.) (Refer to Fig. 23)

Insulate the metal clamp bracket and drain pipe from the bottom using the large sealing pad (8). (Refer to Fig. 23)Be sure to insulate all drain piping running indoors.

Tilt down

Do not lift Make sure there is no slack

Make sure it is not in the water

Good

Wrong

Fig. 21

Taping area (Gray) Drain pipe (1)

Metal clamp (2)

Fig. 22

Large sealing pad (8)

Metal clamp (2)< Facing rear right or right >

5/32 or less

Fig. 23 (Length : in.)

General Information 51

Page 58: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

NOTE To ensure no excessive pressure is applied to the drain pipe (1), do not bend or twist when installing. (This may cause leakage.)If converging multiple drain pipes, install according to the procedure shown below.

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.

(2) Check to make sure the water flows smoothly after piping is complete.Slowly pour 600ml of drain-checking water into the drain pan through the air outlet.

Caution Drain piping connections :Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.

3 7/

8 or

mor

e

T-joint converging drain pipesSlope downwards at a gradient of at least 1/100 (Length : in.)

Wrong

Fig. 24

Air outletPlastic container for pouring

Make sure not to splash the water.

Fig. 25

52 General Information

Page 59: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

Wall Mounted Type (FXAQ-M)

(1) Install the drain piping. (Refer to Fig. 16)The drain pipe should be short with a downward slope and should prevent air pockets from forming.Watch out for the points in the figure 16 when performing drain work.

When extending the drain hose, use a commercially available drain extension hose, and be sure to insulate the extended section of the drain hose which is indoors. (Refer to Fig. 17)

Make sure the diameter of the extension drain piping is the same as the indoor unit drain hose (hard vinyl chloride, I.D. 9/16”) or bigger.In case of converging multiple drain pipes, install them referring to Fig. 18.Select diameter of drain piping which adapts to the capacity of the unit connected.

(2) Make sure the drain works properly.After drain work is complete, perform a drain check by opening the front panel, removing the air filter, pouring water into the drain pan, and making sure water flows smoothly out of the drain hose. (Refer to Fig. 19)

Caution Drain piping connectionsDo not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.

Fig. 16

Make sure the drain hose is at a downward slope.

Make sure the tip does not go underwater even when water is added.

Drain hose Drain hose

(Downward slope)

Indoor unit drain hoseExtension drain piping (commercially available)

Insulating tube (commercially available) Insulating tape (accessory) (4)

( See “4.INDOOR UNIT INSTALLATION” ) Fig. 17

Fig. 18 (Slope of at least 1/100)

4 or

mor

e

Plastic container for pouring

Drain pan

Make sure not to splash the water.Fig. 19

General Information 53

Page 60: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Floor Standing Type (FXLQ-M) Concealed Floor Standing Type (FXNQ-M)

Rig the drain pipe as shown below and take measures against condensate. Improperly rigged piping could lead to leaks and eventually wet furniture and belongings.(1) Carry out the drain piping

Connect the drain hose (1) using the attached hose and parts, as shown in the right drawing.

If converging multiple drain pipes, install according to the procedure shown below.

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.

(2) After piping work is finished, check drainage flows smoothly.Add approximately 1 liter of water slowly from the air outlet and check drainage flow.

(3) Be sure to insulate all indoor pipes

Caution Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.

3/4 drain pipe

2 or more

Drip pan

Metal clamp (accessory) (2)

Drain hose (accessory) (1)

Cut to suitable length

(length : in.)

Piping process inside unit

Tilt

Slope downwards at a gradient of at least 1/100

54 General Information

Page 61: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

3.2.9 Electrical Work

Control Wiring 1. Compatible types of wireWiring Specifications

Notes: 1. Sheathed wire may be used for transmission wirings, but they do not comply with EMI (Electromagnetic lnterference) (EN55014). When using sheathed wire. EMI must conform to Japanese standards stipulated in the Electric Appliance Regulatory Act. (If using a sheathed wire, the grounding shown in the figure on the left is unnecessary.)

2. Problems arising from the use of unsuitable cable

a) When cable less than 0.75 mm² is usedWhere the control wiring is particularly long the transmission signals may, for example, become unstable and the terminal relay cease to function. (Reduced voltage) The control system may become unduly subject to noise interference.

b) When cable more than 1.25 mm² is usedWhen wiring indoor units together, the terminal block will not be able to accommodate 2 cables simultaneously if the cables are larger than 1.25 mm².

c) For multi-core cableThe greater play between wires, the more the transmitted wave is distorted and transmission destabilized.

Wiring Type Sheathed Wire (2 wire)

Size AWG18-16 (0.75~1.25 mm²)

General Information 55

Page 62: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

d) In the case of a remote controller with a three way selector for cooling, heating and ventilation, twin core cable should be used when the ventilation mode is not required and three core cable should be used when three way selection is required.

e) Since there is a considerable risk of mixing high (220 to 240V) and low voltage in the case of, for example, a PCB for remote control, multiple core cable must not be used. (Internal wiring regulations and dielectric strengths of cables are relevant here.)

f) Other important points1. The refrigerant circuit and the indoor/outdoor connecting cables must correspond exactly.2. A suitable gap must be left between the control cables and the power supply cables where these are laid

alongside each other. (See "Separation of control and power supply cables" on page 57)

Power Supply (Cabling of Main Power Supply)

1. Choosing a circuit breakerThe power supply work must conform to local regulations. In Japan, the relevant regulations are the MITI ordinance determining technical standards for electrical equipment, and the Internal Wining Provisions.

a) The indoor unit circuit breakersIn accordance with the provisions for internal wiring (JEAC8001-1986), power may be supplied by means of crossover lines between the indoor units in a single system branch circuit.

When using high static pressure indoor units the fan motors must have a large capacity. Single phase 220~240V branch circuits are therefore required for each indoor unit.

Example: Up to 10 × 2.5HP indoor units or 5 × 5HP indoor units can be wired together.

b) The outdoor unit circuit breakerA separate circuit breaker must be fitted for each unit.The motors incorporated into air conditioning system compressors are treated as special motors under the internal wiring provisions. The values which apply to normal motors are thus somewhat variance with those which apply to such compressor motors. You are recommended to adhere strictly to the procedures laid down in the technical materials included in, for example, the system design manuals.

Calculation of load (Refer to local regulation.)

Branch circuit facility (Internal wiring provisions 305-2)The motors must be set up with a dedicated branch circuit for each unit. However, where they correspond to any of the following situations, this limitation does not apply. When used in a 15A branch circuit of a 20A

circuit breaker branch circuitNote: It is recommended that the total rated capacity of the motors set up in a 15A branch circuit or a 20A circuit breaker branch circuit should be no more than 2.2kW.

56 General Information

Page 63: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

With respect to the calculation of load for motors with special applications such as elevator, air conditioner and refrigerator motors, not only must the rated current be shown on the name plate of the said motor or piece of apparatus but it must also included all special characteristics or applications.

Note: The rated current for package air conditioners which use special purpose built-in compressor motors in their compressors in 1.2 times the operating current shown on the name plate.

2. Cable sizeThe thickness of the cables in the circuits (branch circuits) providing the main power supply to each item of apparatus must satisfy the following conditions:1. To have a current tolerance of 40% or more of the rated current of the overcurrent circuit breaker (wiring

circuit breaker, etc.).2. To have a current tolerance of 125% or more of the rated current in cases where the rated current of the

apparatus is 50A or less.3. To have a current tolerance of 110% or more of the rated current in cases where the rated current of the

apparatus is more than 50A.4. To satisfy voltage drop standards.

3. Separation of control and power supply cablesIf control and power cables are run alongside each other then there is a strong likelihood of operational faults developing due to interference in the signal wiring caused by electrostatic and electromagnetic coupling.The table below indicates our recommendations as to the appropriate spacing of control and power cables where these are to be run side by side.

Notes: 1. The figures are based on an assumed length of parallel cabling up to 33’ (100m). For lengths in excess of 33’ (100m) the figures will have to be recalculated in direct proportion to the additional length of cable involved.

2. If the power supply waveform continues to exhibit some distortion the recommended spacing in the table should be increased.

If the cables are laid inside conduits then the following points must also be taken into account when grouping various cables together for introduction into the conduits.1. Power cables (including power supply to the air conditioner) and signal cables must not be laid inside the

same conduit. (Power cables and signal cables must each have their own individual conduits.)2. In the same way, when grouping the cables, power and signal cables should not be bunched together.

Important points1. Earthing

Have the indoor and outdoor units both been earthed?∗ If the apparatus is not properly earthed then there is always a risk of electric shocks. The earthing of the

apparatus must be carried out by a qualified person.

Current capacity of power cable Spacing (d)

100V or more

10A or less 12" (300mm)

50A 20" (500mm)

100A 40" (1000mm)

100A or more 60" (1500mm)

General Information 57

Page 64: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

3.2.10 Duct Work (Indoor)Operational steps

Taking Account of Noise and Vibration

a) Canvas joints must be used between the main unit and the air suction and discharge ducts. These fittings are designed to inhibit secondary noise resulting from the transmission of vibrations and operating noise from the main unit to the ducts or to the rest of the building.

b) The speed of the airflow should be taken into account when choosing air suction and distribution grills in order to keep wind noise to minimum.

Important points1. The air discharge duct must be thermally insulated.2. The canvas duct on the inlet side must be set in a metal framework.3. The air suction and distribution grills should be positioned to take into account the possibility of short

circuits.4. Static pressure should be checked to ensure that the airflow is within the specified range.5. The air filter must be easily detachable.

Install indoor unit Connect ducts Fit inlets and outlets

(V1040)

58 General Information

Page 65: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

3.2.11 Selection of LocationThis unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment. If installed as a household appliance it could cause electromagnetic interference.The VRV OUTDOOR units should be installed in a location that meets the following requirements:1. The foundation is strong enough to support the weight of the unit and the floor is flat to prevent

vibration and noise generation.2. The space around the unit is adequate for servicing and the minimum space for air inlet and air

outlet is available. (refer to figure 1 and choose one of both possibilities)

3. There is no danger of fire due to leakage of inflammable gas.4. Ensure that water cannot cause any damage to the location in case it drips out the unit (e.g. in

case of a blocked drain pipe).5. The piping length between the outdoor unit and the indoor unit may not exceed the allowable

piping length. (see "Example of connection")6. Select the location of the unit in such a way that neither the discharged air nor the sound

generated by the unit disturb anyone.7. Make sure that the air inlet and outlet of the unit are not positioned towards the main wind

direction. Frontal wind will disturb the operation of the unit. If necessary, use a windscreen to block the wind.

≥3/8 ≥3/8≥3/8≥3/4

≥3/4

≥7 7/8

≥2≥2

≥2

≥7 7/8 ≥15 3/4 ≥15 3/4

≥2

≥3/8

B1 B1

≥11 3/4

A A

AA

B2 B2

H1

H2

≥3 7/8≥3 7/8

≥11 3/4

< If installed as a single unit >(Pattern 1)

(Pattern 2)

(Pattern 3)

(Pattern 1)

(Pattern 2)

(Pattern 3)

< When installed in serial >

1

1

2

2

1 3

1

1

11 (in.)

A

B1

B2

H1≤59

H1=59+X

H2≤19 5/8

H2=19 5/8+Y

⇒ A≥19 5/8

⇒ A≥19 5/8+X/2

⇒ B1≥11 3/4

B2≥3 7/8

⇒ B1≥11 3/4+Y/2

B2≥3 7/8+Y/2

1. Front side2. No limit to wall height3. Suction side

General Information 59

Page 66: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Note: 1. An inverter air conditioner may cause electronic noise generated from AM broadcasting. Examine where to install the main air conditioner and electric wires, keeping proper distances away from stereo equipment, personal computers, etc.

If the electric wave of AM broadcasting is particularly weak, keep distances of 10ft. or more and use conduit tubes for power and transmission lines.

2. In heavy snowfall areas, select an installation site where snow will not affect operation of the unit.

Warning 1. The refrigerant R-410A itself is nontoxic, nonflammable and is safe. If the refrigerant should leak however, its concentration may exceed the allowable limit depending on room size. Due to this it could be necessary to take measures against leakage. Refer to the chapter "Caution for refrigerant leaks".

2. Do not install in the following locations.Locations such as kitchens which contain a lot of mineral oil or steam in the atmosphere or where oil may splatter on the unit.Resin parts may deteriorate, causing the unit to fall or leak.Locations where sulfurous acids and other corrosive gases may be present in the atmosphere.Copper piping and soldered joints may corrode, causing refrigerant to leak.Locations where equipment that produces electromagnetic waves is found.The electromagnetic waves may cause the control system to malfunction, preventing normal operation.Locations where flammable gases may leak, where thinner, gasoline, and other volatile substances are handled, or where carbon dust and other incendiary substances are found in the atmosphere.Leaked gas may accumulate around the unit, causing an explosion.

Service Space It is extremely important that enough space is left when installing the equipment to allow routine servicing and maintenance to be carried out without undue hindrance. It is particularly important to bear in mind the work which will be required if the compressor needs to be replaced. (The layout of the pipework can sometimes cause considerable difficulties if the compressor needs to be changed.)

≥60

5

3

1

42

2

(in.)

≥40

≥40

≥40

≥60

≥60

≥60

1. indoor unit2. Branch switch, overcurrent

breaker3. remote controller4. cool/heat selector5. personal computer or radio

60 General Information

Page 67: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

3.2.12 Inspecting and Handling the UnitAt delivery, the package should be checked and any damage should be reported immediately to the carrier claims agent.When handling the unit, take into account the following:1. Fragile, handle the unit with care.

Keep the unit upright in order to avoid compressor damage.2. Choose the path along which the unit is to be brought in ahead of time.3. If a forklift it to be used, pass the forklift arms through the large openings on the bottom of the

unit.4. Lift the unit preferably with a crane and 2 belts of at least 27ft. long.5. When lifting the unit with a crane, always use protectors to prevent belt damage and pay

attention to the position of the unit’s centre of gravity. 6. After installation, remove the transport clasps attached to the large openings.7. Bring the unit as close to its final installation position in its original package to prevent damage

during transport.

6

3

< 5 >

< 7 >

3

4

1

2

8

1. Packaging material2. Forklift3. Belt sling4. Wear plate5. Removal of shipping brackets6. Shipping bracket (Remove the

screws.)7. Removal of corrugated paper8. Corrugated paper

General Information 61

Page 68: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

3.2.13 Installation of Outdoor UnitOperational steps

Notes: 1. The proportions of cement : sand : gravel for the concrete shall be 1 : 2 : 4, and ten reinforcement bars that their diameter are 6/16"-7/16", (approx. 12" intervals) shall be placed.

2. The surface shall be finished with mortar. The corner edges shall be chamfered.3. When the foundation is built on a concrete floor, rubble is not necessary. However, the surface of

the section on which the foundation is built shall have rough finish.4. A drain ditch shall be made around the foundation to thoroughly drain water from the equipment

installation area.5. When installing the equipment on a roof, the floor strength shall be checked, and water-proofing

measures shall be taken.

Bolt pitch

Prepare foundation Install outdoor unit

(V1150)

3D042653A

RXYQ96MTJU

43 3/8 4-φ19/32" dia. holes

28 7

/16-

29"

62 General Information

Page 69: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

Caution in installation1. Execute the installation work by checking the foundation strength and levelness to avoid any occurrence of

vibration and noise.Fix the unit tightly with foundation bolts. (Prepare 4 sets of M12 foundation bolts with proper nuts and washers.)The proper length of the foundation bolts form the surface of the base is 13/16".

Caution Install the unit securely in case of earthquake an typhoon, cyclone, hurricane or other strong wind. The unit may topple or cause another accident if improperly set up.

Unpacking and Placing the Unit

Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise.Secure the unit to its base using foundation bolts. (Use four commercially available M12-type foundation bolts, nuts, and washers.)The foundation bolts should be inserted 13/16”.Make sure the base under the unit supports the unit over an area of at least the base leg widths (2-5/8”).The height of the base should be at least 5-7/8” from the floor.The unit must be installed on a solid longitudinal foundation (steelbeam frame or concrete) as indicated in the figure below.

DO NOT USE STANDS TO SUPPORT THE CORNERS

Caution 1. Prepare a water drainage channel around the foundation to condensate waste water from around the unit.

2. If the unit is to be installed on a roof, check the strength of the roof and its drainage facilities first.

3. If the unit is to be installed on a frame, install the waterproofing board within a distance of 5 14/16" under the unit in order to prevent infiltration of water coming from under the unit.

1. Foundation bolt point (φ9/16” dia. : 4 positions)2. Depth of product3. Shape of outdoor unit’s support leg and foundation

bolt positions4. Base leg width

Model A (in.) B (in.)

Q96 type 48 13/16 43 3/8

13/1

6”

(in.)

28 7

/16-

29

2 5/

8

2 5/

8

30 1

/8AB

2 5/

8 (

4 )

1

2

3

≥4 ≥4

12 2≥4

≥4≥4

≥4

1. Do not use stands to support four corners.

2. Center position of unit

General Information 63

Page 70: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Installation SiUS39-504

Note: When installing on a roof, make sure the roof floor is strong enough and be sure to water-proof all work.Make sure the area around the machine drains properly by setting up drainage grooves around the foundation.(Condensate water is sometimes discharged from the outdoor unit when it is running.)Block all gaps in the holes for passing out piping and wiring using sealing material (locally procured).(Small animals may enter the machine.)

Ex: passing piping out through the front

1

2 3

1. Plug the areas marked with " ". (When the piping is routed from the front panel.)

2. Gas side piping3. Liquid side piping

64 General Information

Page 71: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Installation

Caution Caution label

General Information 65

Page 72: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

4. Test Operation4.1 Procedure and Outline

Follow the following procedure to conduct the initial test operation after installation.

4.1.1 Check Work Prior to Turn Power Supply On

4.1.2 Turn Power On

Check on refrigerant piping

Check on amount of refrigerant charge

(V3055)

Check the below items.2Power wiring2Control transmission wiring

between units2Earth wire

¡ Is the wiring performed as specified?¡ Are the designated wires used?¡ Is the grounding work completed?

Use a 500V electrical insulation tester to measure the insulation.2 Do not use a electrical insulation tester for other circuits than 200V (or

240v) circuit.¡ Are the setscrews of wiring not loose?

¡ Is pipe size proper? (The design pressure of this product is 550 psi.)¡ Are pipe insulation materials installed securely?

Liquid and gas pipes need to be insulated. (Otherwise causes water leak.)¡ Are respective stop valves on liquid, gas and oil equalizing lines securely

open?

¡ Is refrigerant charged up to the specified amount?If insufficient, charge the refrigerant from the service port of stop valve on the liquid side with outdoor unit in stop mode after turning power on.

¡ Has the amount of refrigerant charge been recorded on “Record Chart of Additional Refrigerant Charge Amount”?

Turn outdoor unit power on.

Carry out field setting on outdoor PC board

Turn indoor unit power on.(V3056)

¡ Be sure to turn the power on 6 hours before starting operation to protect compressors. (to power on clankcase heater)

¡ For field settings, refer to “Field Settings” on and after P71.After the completion of field settings, set to “Setting mode 1”.

66 General Information

Page 73: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

4.1.3 Check Operation* During check operation, mount front panel to avoid the misjudging.* Check operation is mandatory for normal unit operation. (When the check operation is not executed, alarm code "U3" will be displayed.)

On completion of test operation, LED on outdoor unit PC board displays the following.H3P ON: Normal completionH2P and H3P ON: Abnormal completion →Check the indoor unit remote controller for

abnormal display and correct it.

In the case of multi-outdoor-unit system, make setting on the master unit PC board. (Setting with the slave unit is disabled.)[LED display in the case of multi-outdoor-unit system] (Same as that in emergency operation)

* Discriminate the operating status of the master unit/slave units through the following LED display.

Check on operation

(V3057)

Press and hold the TEST OPERATION button (BS4) on outdoor unit PC board for 5 seconds.

¡ The test operation is started automatically.The following judgements are conducted within 15 minutes.2“Check for wrong wiring” 2“Check refrigerant for over charge”2“Check stop valve for not open” 2Pipe length automatic judgement”

The following indications are conducted while in test operation.2LED lamp on outdoor unit PC board H2P flickers (test operation)2Remote controller Indicates “On Centralized Control” on upper

right.Indicates “Test Operation” on lower left

LED display (7:ON 77:OFF 99:Blink)H1P---H7P H8P

(Factory set)

Master:Slave :

777777777 7777 77777777 7777777 99

General Information 67

Page 74: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

Malfunction codeIn case of an alarm code displayed on remote controller:

4.1.4 Confirmation on Normal Operation• Conduct normal unit operation after the check operation has been completed.

(When outdoor air temperature is 75°F or higher, the unit can not be operated with heating mode. See the instruction manual attached.)Confirm that the indoor/outdoor units can be operated normally.(When an abnormal noise due to liquid compression by the compressor can be heard, stop the unit immediately, and turn on the crankcase heater to heat up it sufficiently, then start operation again.)

• Operate indoor unit one by one to check that the corresponding outdoor unit operates.• Confirm that the indoor unit discharges cold air (or warm air).• Operate the air direction control button and flow rate control button to check the function of the

devices.

Cause of trouble due to faulty installation work

Alarmcode

Countermeasure

Closed stop valve of outdoor unit E3E4F3UF

Liquid side stop valve : OpenGas side stop valve : OpenOil equalizing pipe stop valve : CloseLiquid side stop valve : OpenGas side stop valve : OpenOil equalizing pipe stop valve : Open

Reversed phase in power cable connection for outdoor unit

U1 Change connection of two wires among three for correct phasing.

Electric power for outdoor or indoor unit is not supplied. (Including open phase)

U4 Check that the power cable for outdoor unit is connected properly.

Incorrect wiring between units UF Check that the wiring between units corresponds correctly to refrigerant piping system.

Refrigerant overcharge E3F6UF

Compute again optimum amount of refrigerant to be added based on the piping length, then, collect the excessive amount by using refrigerant collector to make the refrigerant amount proper.

Insufficient refrigerant E4F3

- Check that additional charging has been carried out.- Compute again the refrigerant amount to be added based on the

piping length, and charge proper amount of refrigerant additionally.

68 General Information

Page 75: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

4.2 Operation When Power is Turned On4.2.1 When Turning On Power First Time

The unit cannot be run for up to 12 minutes to automatically set the master power and address (indoor-outdoor address, etc.).Status

4.2.2 When Turning On Power The Second Time and SubsequentTap the RESET button on the outdoor unit PC board. Operation becomes possible for about 2 minutes. If you do not push the RESET button, the unit cannot be run for up to 10 minutes to automatically set master power.Status

4.2.3 When an Indoor Unit or Outdoor unit Has Been Added, or Indoor or Outdoor Unit PC Board Has Been Changed

Be sure to push and hold the RESET button for 5 seconds. If not, the addition cannot be recognized. In this case, the unit cannot be run for up to 12 minutes to automatically set the address (indoor-outdoor address, etc.)Status

Outdoor unit Test lamp H2P .... Blinks

Can also be set during operation described above.

Indoor unit If ON button is pushed during operation described above, the "UH" malfunction indicator blinks.(Returns to normal when automatic setting is complete.)

Outdoor unit Test lamp H2P .... Blinks

Can also be set during operation described above.

Indoor unit If ON button is pushed during operation described above, the operation lamp lights but the compressor does not operate. (Returns to normal when automatic setting is complete.)

Outdoor unit Test lamp H2P .... ON

Can also be set during operation described above.

Indoor unit If ON button is pushed during operation described above, the "UH" or "U4" malfunction indicator blinks. (Returns to normal when automatic setting is complete.)

General Information 69

Page 76: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

4.3 Outdoor Unit PC Board Layout

Outdoor Unit PC Board

BS1

MODE SET RETURN TEST RESET

BS2 BS3 BS4 BS5

H1P H2P H3P H4P H5P H6P H7P H8P

1 2 3 4

12

1 2 3 4

A B C F1 F2 F1 F2 Q1 Q2Switch cool/heat

Indoor −Outdoor

Outdoor −Outdoor Multi outdoor

(2) Set mode display (LED)

(3) Mode setting switch

(1) Microcomputer normal monitor

(4) Local setting switch

Connection terminal for transmission use

DS1 DS2DS3

HAP

(V3054)

(1) Microcomputer normal monitorThis monitor blinks while in normal operation, and turns on or off when a malfunction occurs.

(2) Set mode display (LED)LEDs display mode according to the setting.

(3) Mode setting switchUsed to change mode.

(4) Local setting switchUsed to make local settings.

70 General Information

Page 77: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

4.4 Field Setting4.4.1 Field Setting from Remote Controller

Individual function of indoor unit can be changed from the remote controller. At the time of installation or after service inspection / repair, make the local setting in accordance with the following description.Wrong setting may cause malfunction.(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be required to change. Refer to information in the option handbook.)

4.4.1.1 Wired Remote Controller <BRC1C71>

1. When in the normal mode, push the button for 4 seconds or more, and operation then enters the "field set mode."2. Select the desired "mode No." with the button. 3. During group control and you want to set by each individual indoor unit (when mode No. 20, 21,

22, 23, 25 has been selected), push the time mode button and select the "indoor unit No." to be set.Note: This operation is not required when setting as a group.

4. Push the button and select the first code No. 5. Push the button and select the second code No. 6. Push the timer button one time and "define" the currently set contents. 7. Push the button to return to the normal mode.

(Example)When setting the filter sign time to "Filter Dirtiness-High" in all group unit setting, set the Mode No. to "10", Mode setting No. to "0" and setting position No. to "02".

General Information 71

Page 78: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

4.4.1.2 Wireless Remote Controller - Indoor UnitBRC7C812BRC4C82BRC7E818BRC7E83

1. When in the normal mode, push the button for 4 seconds or more, and operation then enters the “field set mode.”

2. Select the desired “mode No.” with the button. 3. Pushing the button, select the first code No. 4. Pushing the button, select the second code No. 5. Push the timer button and check the settings. 6. Push the button to return to the normal mode.

(Example)When setting the filter sign time to “Filter Dirtiness-High” in all group unit setting, set the Mode No. to “10”, Mode setting No. to “0” and setting position No. to “02”.

72 General Information

Page 79: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

4.4.1.3 Simplified Remote ControllerBRC2A71

Group No. setting by simplified remote controller.1. Remove the cover of remote controller.2. While in normal mode, press the [BS6] BUTTON (field set) to enter the FIELD SET MODE.3. Select the mode No. [00] with [BS2] BUTTON (temperature setting ) and [BS3] BUTTON

(temperature setting ).4. Select the group No. with [BS9] BUTTON (set A) and [BS10] BUTTON (set B). (Group Nos. increase

in the order of 1-00, 1-01......1-15, 2-00,.....4-15. However, the unified ON/OFF controller displays only group No. set within the range of control.)

5. Press [BS7] BUTTON (set/cancel) to set group No.6. Press [BS6] BUTTON (field set) to return to the NORMAL MODE.

General Information 73

Page 80: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

4.4.1.4 Setting Contents and Code No. – VRV Unit

Notes: 1. Settings are made simultaneously for the entire group, however, if you select the mode No. inside parentheses, you can also set by each individual unit. Setting changes however cannot be checked except in the individual mode for those in parentheses.

2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they cannot be set individually. Setting changes also cannot be checked.

3. Marked are factory set.4. Do not make settings other than those described above. Nothing is displayed for functions the

indoor unit is not equipped with. 5. "88" may be displayed to indicate the remote controller is resetting when returning to the normal mode. 6. If the setting mode to "Equipped", heat reclaim ventilation fan conducts the fan residual

operation by linking to indoor unit.

VRV system indoor unit settings

Mode No.

Note 2

Setting Switch

No.

Setting Contents Second Code No.(Note 3)

01 02 03 04

10(20) 0 Filter contamination heavy/light (Setting for display time to clean air filter)(Sets display time to clean air filter to half when there is heavy filter contamination.)

Super long life filter

Light Approx. 10,000

hrs.

Heavy Approx. 5,000 hrs.

— —

Long life filter

Approx. 2,500 hrs.

Approx. 1,250 hrs.

Standardfilter

Approx. 200 hrs.

Approx. 100 hrs.

1 Long life filter type Long life filter Super long life filter

— —

2 Thermostat sensor in remote controller Use No use —

3 Display time to clean air filter calculation (Set when filter sign is not to be displayed.)

Display No display —

12(22) 0 Optional accessories output selection (field selection of output for adaptor for wiring)

Indoor unit turned ON by thermostat

Operation output Malfunction output

1 ON/OFF input from outside (Set when ON/OFF is to be controlled from outside.)

Forced OFF ON/OFF control — —

2 Thermostat differential changeover(Set when remote sensor is to be used.)

2°F 1°F — —

3 OFF by thermostat fan speed LL Set fan speed — —

4 Automatic mode differential (automatic temperature differential setting for VRV system heat recovery series cool/heat)

01:0 02:1 03:2 04:3 05:4 06:5 07:6 08:7

5 Power failure automatic reset Not equipped Equipped — —

13(23) 3 Air flow direction adjustment (Set at installation of decoration panel.)

Equipped Not equipped —

4 Field set air flow position setting Draft prevention Standard Ceiling Soiling prevention

5 Field set fan speed selection(fan speed control by air discharge outlet for phase control)

Standard Optional accessory 1

Optional accessory 2

15(25) 1 Thermostat OFF excess humidity Not equipped Equipped — —

2 Direct duct connection (when the indoor unit and heat reclaim ventilation unit are connected by duct directly.) ∗Note 6

Not equipped Equipped — —

3 Drain pump humidifier interlock selection Not equipped Equipped — —

5 Field set selection for individual ventilation setting by remote controller

Not equipped Equipped — —

6 Field set selection for individual ventilation setting by remote controller

Not equipped Equipped — —

74 General Information

Page 81: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

4.4.1.5 Applicable Range of Field Setting

Ceiling mounted cassette type

Ceiling mounted built-in type

Ceiling mounted duct type

Ceiling suspended type

Wall mounted type

Floor standing type

Concealed Floor standing type

Multi flow

FXFQ FXSQ FXMQ FXHQ FXAQ FXLQ FXNQ

Filter sign

Ultra long life filter sign — — — — — —

Remote controller thermostat sensor

Set fan speed when thermostat OFF

Air flow adjustment Ceiling height — — — —

Air flow direction — — — — — —

Air flow direction adjustment (Down flow operation) — — — — — — —

Air flow direction adjustment range — — — — — —

Field set fan speed selection — — — — —

General Information 75

Page 82: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

4.4.1.6 Detailed Explanation of Setting Modes

Filter Sign SettingIf switching the filter sign ON time, set as given in the table below.Set Time

Ultra-Long-Life Filter Sign SettingWhen a Ultra-long-life filter is installed, the filter sign timer setting must be changed.

Setting Table

Fan Speed Changeover When Thermostat is OFFBy setting to "Set Fan Speed," you can switch the fan speed to the set fan speed when the heating thermostat is OFF.∗ Since there is concern about draft if using "fan speed up when thermostat is OFF," you should take the setup location into consideration.

Setting Table

Auto Restart after Power Failure ResetFor the air conditioners with no setting for the function (same as factory setting), the units will be left in the stop condition when the power supply is reset automatically after power failure reset or the main power supply is turned on again after once turned off. However, for the air conditioners with the setting, the units may start automatically after power failure reset or the main power supply turned on again (return to the same operation condition as that of before power failure).

For the above reasons, when the unit is set enabling to utilize "Auto restart function after power failure reset", utmost care should be paid for the occurrence of the following situation.

Filter Specs.Setting

Standard Long Life Ultra Long Life Filter

Contamination Light 200 hrs. 2,500 hrs. 10,000 hrs.

Contamination Heavy 100 hrs. 1,250 hrs. 5,000 hrs.

Mode No. Setting Switch No. Setting Position No. Setting

10 (20) 1 01 Long-Life Filter

02 Ultra-Long-Life Filter (1)

03 —

Mode No. First Code No. Second Code No. Setting

12(22) 3 01 LL Fan Speed

02 Set Fan Speed

Caution 1. The air conditioner starts operation suddenly after power failure reset or the main power supply turned on again. Consequently, the user might be surprised (with question for the reason why).

2. In the service work, for example, turning off the main power switch during the unit is in operation, and turning on the switch again after the work is completed start the unit operation (the fan rotates).

76 General Information

Page 83: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

Air Flow Adjustment - Ceiling heightMake the following setting according to the ceiling height. The setting position No. is set to “01” at the factory.

In the Case of FXAQ12~24, FXHQ12~36

In the Case of FXFQ12~36

Air Flow Direction SettingSet the air flow direction of indoor units as given in the table below. (Set when optional air outlet blocking pad has been installed.) The second code No. is factory set to “01.”

Setting Table

Setting of Air Flow Direction Adjustment RangeMake the following air flow direction setting according to the respective purpose.

Setting Table

Air flow rate switching at discharge grille for field air flow rate switchingWhen the optional parts (high performance filter, etc.) is installed, sets to change fan speed for securing air flow rate.Follow the instruction manual for the optional parts to enter the setting numbers.

Mode No. Setting Switch No.

Setting Position No. Setting

13(23) 0

01 Wall-mounted type: Standard

02 Wall-mounted type: Slight increase

03 Wall-mounted type: Normal increase

ModeNo.

FirstcodeNo.

Second code No.

SettingCeiling height

4-way Outlets 3-way Outlets 2-way Outlets

13 (23) 0

01 Standard (N) Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m

02 High Ceiling (H) Lower than 3.0 m Lower than 3.3 m Lower than 3.8 m

03 Higher Ceiling (S) Lower than 3.5 m Lower than 3.5 m —

Mode No. First Code No. Second Code No.

Setting

13 (23) 1 01 F : 4-direction air flow

02 T : 3-direction air flow

03 W : 2-direction air flow

Mode No. First Code No. Second Code No. Setting

13 (23) 4 01 Upward (Draft prevention)

02 Standard

03 Downward (Ceiling soiling prevention)

General Information 77

Page 84: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

4.4.1.7 Centralized Control Group No. Setting

BRC1C Type If carrying out centralized control by central remote controller or unified ON/OFF controller, group No. must be set for each group individually by remote controller. Group No. setting by remote controller for centralized control

1. When in the normal mode, push the button for 4 seconds or more, and operation then enters the "field setting mode."

2. Set mode No. "00" with the button. ∗3. Push the button to inspect the group No. display. 4. Set the group No. for each group with the button (The group No. increases in the manner

of 1-00, 1-01, ...,1-15, 2-00,...4-15. However, the unified ON/OFF controller displays only the group No. within the range selected by the switch for setting each address.)

5. Push the timer button to define the selected group No. 6. Push the button to return to the normal mode.

Even if not using a remote controller, connect the remote controller when setting the group No., set the group No. for centralized control, and disconnect after making the setting.Set the group No. after turning on the power supply for the central remote controller, unified ON/OFF controller, and indoor unit.

78 General Information

Page 85: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

BRC7C TypeBRC4C TypeBRC7E Type

Group No. setting by wireless remote controller for centralized control1. When in the normal mode, push button for 4 seconds or more, and operation then

enters the “field set mode.”2. Set mode No. “00” with button. 3. Set the group No. for each group with button (advance/backward).

4. Enter the selected group numbers by pushing button. 5. Push button and return to the normal mode.

General Information 79

Page 86: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

Group No. Setting Example

Caution When turning the power supply on, the unit may often not accept any operation while "88" is displaying after all indications were displayed once for about 1 minute on the liquid crystal display. This is not an operative fault.

Centoral RemoteController

F1 F2

F1 F2 F1 F2F1 F2

P1 P2

RC

RC

RC RC RC

F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2

F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2

No Remote Controller

Group Control by Remote Contoller(autmatic unit address)

1-03

1-001-01

Main Sub1-02

1-04

Indoor/Outdoor Outdoor/Outdoor

F1 F2 F1 F2

Indoor/Outdoor Outdoor/Outdoor

(V0917)

80 General Information

Page 87: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

4.4.1.6 Setting of Operation Control Mode from Remote Controller (Local Setting)The operation control mode is compatible with a variety of controls and operations by limiting the functions of the operation remote controller. Furthermore, operations such as remote controller ON/OFF can be limited in accordance with the combination conditions. (Refer to information in the table below.)Centralized controller is normally available for operations. (Except when centralized monitor is connected)

4.4.1.7 Contents of Control ModesTwenty modes consisting of combinations of the following five operation modes with temperature and operation mode setting by remote controller can be set and displayed by operation modes 0 through 19.

ON/OFF control impossible by remote controllerUsed when you want to turn on/off by central remote controller only.(Cannot be turned on/off by remote controller.)OFF control only possible by remote controllerUsed when you want to turn on by central remote controller only, and off by remote controller only.CentralizedUsed when you want to turn on by central remote controller only, and turn on/off freely by remote controller during set time.IndividualUsed when you want to turn on/off by both central remote controller and remote controller.Timer operation possible by remote controllerUsed when you want to turn on/off by remote controller during set time and you do not want to start operation by central remote controller when time of system start is programmed.

General Information 81

Page 88: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

How to Select Operation Mode

Whether operation by remote controller will be possible or not for turning on/off, controlling temperature or setting operation mode is selected and decided by the operation mode given on the right edge of the table below.

Do not select "timer operation possible by remote controller" if not using a remote controller. Operation by timer is impossible in this case.∗1. Factory setting

ON by remote controller(Unified ON by central remote controller)

OFF by remote controller(Unified OFF by central remote controller)

Temperature control by remote controller

Operation mode setting by remote controller

OFF by remote controller

Control mode is "1."

Example

↓Rejection

↓Rejection

↓Rejection

↓Acceptance

↓Acceptance (VL069)

Control mode Control by remote controller Control mode

Operation OFF Temperature control

Operation mode settingUnified operation,

individual operation by central remote controller, or operation controlled by timer

Unified OFF, individual stop by central remote controller, or timer stop

ON/OFF control impossible by remote controller

Rejection (Example) Rejection (Example) Rejection (Example)

Rejection Acceptance 0

Rejection 10

Acceptance (Example)

Acceptance (Example)

1(Example)

Rejection 11

OFF control only possible by remote controller

Acceptance Rejection Acceptance 2

Rejection 12

Acceptance Acceptance 3

Rejection 13

Centralized Acceptance Rejection Acceptance 4

Rejection 14

Acceptance Acceptance 5

Rejection 15

Individual Acceptance Rejection Acceptance 6

Rejection 16

Acceptance Acceptance 7 ∗1

Rejection 17

Timer operation possible by remote controller

Acceptance (During timer at ON position only)

Acceptance (During timer at ON position only)

Rejection Acceptance 8

Rejection 18

Acceptance Acceptance 9

Rejection 19

82 General Information

Page 89: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

4.4.2 Field Setting from Outdoor Unit4.4.2.1 Field Setting from Outdoor Unit

Setting by dip switchesThe following field settings are made by dip switches on PC board.

There are the following three setting modes. Setting mode 1 (H1P off)

Initial status (when normal) : Used to select the cool/heat setting. Also indicates during "abnormal", "low noise control" and "demand control".

Setting mode 2 (H1P on)Used to modify the operating status and to set program addresses, etc. Usually used in servicing the system.

Monitor mode (H1P blinks)Used to check the program made in Setting mode 2.

Mode changing procedure

DipswitchSetting item Description

No. Setting

DS1-1ON

Cool / Heat select Used to set cool / heat select by remote controller equipped with outdoor unit.OFF (Factory set)

DS1-2~DS1-4

ONNot used Do not change the factory settings.

OFF (Factory set)

DS2-1~4

ONNot used Do not change the factory settings.

OFF (Factory set)

DS3-1, 2ON

Not used Do not change the factory settings.OFF (Factory set)

BS1

MODE

BS2

SET

BS3

RETURN

BS4

TEST

BS5

RESET

(V2760)

Setting mode 1 Monitor mode

H1P

Push the BS1(MODE button) one time.

Blinking

MODE MODE

Off

H1P

Setting mode 2

MODE

On

H1P

Push and hold the BS1 (MODE button) for 5 seconds.

Push the BS1(MODE button) one time.

(Normal)

(V2761)

Using the MODE button, the modes can be changed as follows.

General Information 83

Page 90: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

Mode changing procedure

Check item selection (SET button)

Contents display

Monitor mode

Setting mode 1(Initial condition)

Press BS3 (RETURN button).

Press BS3 (RETURN button).

Setting item selection (SET button)

Setting mode 2

(Set): Select mode with BS2 (SET button) in each selection step.

Setting conditionselection (SET button)

Setting condition(Contents) display

Press BS3 (RETURN button).

Press BS3 (RETURN button).

Press BS3 (RETURN button). Press BS1

(MODE button).

Press BS1(MODE button).

Press BS1(MODE button).Press BS1 (MODE button) for more than 5 sec.

(V2762)

84 General Information

Page 91: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

∗ Setting No. 1, 5, 6 are the present status display only.

Display for malfunction/preparing/test-run

Display during low noise operation

Display during demand operation

No. Setting (displaying) itemLED display example

H1P H2P H3P H4P H5P H6P H7P

1 Display for malfunction / preparing / test run ∗ 7 7 8 7 7 7 7

2 C/H selector (individual) 7 7 8 7 7 7 7

3 C/H selector (Master) 7 7 7 8 7 7 7

4 C/H selector (Slave) 7 7 7 7 8 7 7

5 Low noise operation ∗ 7 7 7 7 7 7

6 Demand operation ∗ 7 7 7 7 7 7

Normal 7 7 8 7 7 7 7

Malfunction 7 8 8 7 7 7 7

Preparing/Test-run 7 9 8 7 7 7 7

Normal 7 7 8 7 7 7 7

During low noise operation 7 7 8 7 7 8 7

H3P to H5P LEDdisplay changesdepending onsetting No. 2, 3, 4.

Normal 7 7 8 7 7 7 7

During demand operation 7 7 8 7 7 7 8

H3P to H5P LEDdisplay changesdepending onsetting No. 2, 3, 4.

8 : ON

7 : OFF

9 : Blinking

a. “Setting mode 1”

<Selection of setting items>

Push the SET button (BS2) and set LED display to a setting item you want.

l Regarding setting item No. 1,5,6, only the present status is displayed. For the respective description, refer to the table shown on lower right.

l The cool/heat selection setting can be changed on setting item 2, 3, 4. → After setting, push the RETURN

button (BS3) and decide the item.

When the RETURN button (BS3) is pushed, the status becomes the initial status of “Setting mode 1”.

Normally, “Setting mode 1” is set. In case of other status, push MODE button (BS1) one time and set to “Setting mode 1”.

(V2763)

General Information 85

Page 92: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

No. Setting item Description

0 EMG (Emergency operation 1)

Operates by Standard compressor only when inverter compressor malfunctions. Temporary operation until the compressor is replaced. Since the comfortability is extremely deteriorated, immediately replace the compressor.

1 Cool/heat unified address Sets address for cool/heat unified operation.

2 Low noise/demand address Address for low noise/demand operation

5 Indoor unit forced fan H

Allows forced operation of indoor unit fan while unit is stopped. (H tap)

6 Indoor unit forced operation Allows forced operation of indoor unit.

8 Te setting Target evaporation temperature for cooling

9 Tc setting Target condensation temperature for heating

10 Defrost changeover setting

Changes the temperature condition for defrost and sets to quick defrost or slow defrost.

11 Sequential operation setting Sets sequential operation

12External low noise setting / Demand setting

Reception of external low noise or demand signal

13 AIRNET address Set address for AIRNET.

18 High static pressure setting

Make this setting in the case of operating in high static pressure mode with diffuser duct mounted.

19Emergency operation(STD compressor operation prohibited)

Used to operate system only with inverter compressor when STD compressor malfunctions. This is a temporary operation extremely impairing comfortable environment. Therefore, prompt replacement of the compressor is required.

20Additional refrigerant charge operation setting

Carries out additional refrigerant charge operation.

21Refrigerant recovery / vacuuming mode setting

Sets to refrigerant collection mode.

22 Night-time low noise setting

Sets automatic nighttime low noise operation in a simple way.The operating time is based on "Starting set" and "Ending set".

25 Low noise setting Sets low noise level when the low noise signal is input from outside.

26 Night-time low noise control starting setting

Sets starting time of nighttime low noise operation. (Nighttime low noise setting is also required.)

27 Night-time low noise control ending setting

Sets ending time of nighttime low noise operation. (Nighttime low noise setting is also required.)

28

Power transistor check mode∗Check after disconnection of compressor wires

Used for trouble diagnosis of DC compressor. Since the waveform of inverter is output without wiring to the compressor, it is convenient to probe whether the trouble comes from the compressor or PC board.

29 Capacity precedence setting

If the capacity control is required, the low noise control is automatically released by this setting during carrying out low noise operation and nighttime low noise operation.

30 Demand setting 1 Changes target value of power consumption when demand control 1 is input.

32 Normal demand setting

Normally enables demand control 1 without external input. (Effective to prevent a problem that circuit breaker of small capacity is shut down due to large load.

b. “Setting mode 2”

<Selection of setting items>

<Selection of setting conditions>

Push and hold the MODE button (BS1) for 5 seconds and set to “Setting mode 2”.

Push the SET button (BS2) and set the LED display to a setting item shown in the table on the right. ↓Push the RETURN button (BS3) and decide the item. (The present setting condition is blinked.)

Push the SET button (BS2) and set to the setting condition you want. ↓Push the RETURN button (BS3) and decide the condition.

Push the RETURN button (BS3) and set to the initial status of “Setting mode 2”.

∗ If you become unsure of how to proceed, push the MODE button (BS1) and return to setting mode 1.

(V2764)

86 General Information

Page 93: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

No.

Setting item display

Setting condition displaySetting item MODE

H1PTESTH2P

C/H selection Low noiseH6P

DemandH7PIND

H3PMasterH4P

SlaveH5P ∗ Factory set

0

EMG (emergency operation)INV compressor operation inhibited.

8 7 7 7 7 7 7Normal operation 8777778 ∗Emergency operation 8777787

1 Cool / HeatUnified address 8 7 7 7 7 7 8

Address 0 8777777 ∗Binary number 1 8777778(6 digits) ~

31 8788888

2 Low noise/demand address 8 7 7 7 7 8 7

Address 0 8777777 ∗Binary number 1 8777778(6 digits) ~

31 8788888

5 Indoor forced fan H 8 7 7 7 8 7 8Normal operation 8777778 ∗Indoor forced fan H 8777787

6 Indoor forced operation 8 7 7 7 8 8 7

Normal operation 8777778 ∗Indoor forced operation 8777787

8 Te setting 8 7 7 8 7 7 7

High 8777877Normal (factory setting) 8777787 ∗Low 8777778

9 Tc setting 8 7 7 8 7 7 8

High 8777877Normal (factory setting) 8777787 ∗Low 8777778

10 Defrost setting 8 7 7 8 7 8 7

Quick defrost 8777877Normal (factory setting) 8777787 ∗Slow defrost 8777778

11 Sequential operation setting 8 7 7 8 7 8 8

OFF 8777778ON 8777787 ∗

12 External low noise/demand setting 8 7 7 8 8 7 7

External low noise/demand: NO 8777778 ∗External low noise/demand: YES 8777787

13 Airnet address 8 7 7 8 8 7 8

Address 0 8777777 ∗Binary number 1 8777778(6 digits) ~

63 8888888

18 High static pressure setting 8 7 8 7 7 8 7

High static pressure setting: OFF 8777778 ∗High static pressure setting: ON 8777787

19Emergency operation (STD compressor is inhibited to operate.)

8 7 8 7 7 8 8

OFF 8777777 ∗STD 1, 2 operation: Inhibited 8777778STD 2 operation: Inhibited 8777787

20Additional refrigerant charge operation setting

8 7 8 7 8 7 7Refrigerant charging: OFF 8777778 ∗Refrigerant charging: ON 8777787

21Refrigerant recovery / vacuuming mode setting

8 7 8 7 8 7 8Refrigerant recovery / vacuuming: OFF 8777778 ∗Refrigerant recovery / vacuuming: ON 8777787

22 Night-time low noise setting 8 7 8 7 8 8 7

OFF 8777777 ∗Level 1 (outdoor fan with 8 step or lower) 8777778Level 2 (outdoor fan with 7 step or lower) 8777787Level 3 (outdoor fan with 6 step or lower) 8777788

General Information 87

Page 94: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

No.

Setting item display

Setting condition displaySetting item MODE

H1PTESTH2P

C/H selection LownoiseH6P

DemandH7PIND

H3PMasterH4P

SlaveH5P ∗ Factory set

25 Low noise setting 8 7 8 8 7 7 8

Level 1 (outdoor fan with 8 step or lower) 8777778Level 2 (outdoor fan with 7 step or lower) 8777787 ∗Level 3 (outdoor fan with 6 step or lower) ∗ 8777877

26Night-time low noise operation startsetting

8 7 8 8 7 8 7

About 20:00 8777778About 22:00 (factory setting) 8777787 ∗About 24:00 8777877

27Night-time low noise operation end setting

8 7 8 8 7 8 8

About 6:00 8777778About 7:00 8777787About 8:00 (factory setting) 8777877 ∗

28 Power transistor check mode 8 7 8 8 8 7 7

OFF 8777778 ∗ON 8777787

29 Capacity precedence setting 8 7 8 8 8 7 8

OFF 8777778 ∗ON 8777787

30 Demand setting 1 8 7 8 8 8 8 7

60 % demand 877777870 % demand 8777787 ∗80 % demand 8777877

32 Continuous demand setting 8 8 7 7 7 7 7

OFF 8777778 ∗ON 8777787

38

Emergency operation(Master unit with multi-outdoor-unit system is inhibited to operate.)

8 8 7 7 8 8 7OFF 8777778 ∗

Master unit operation: Inhibited 8777787

39

Emergency operation(Slave unit 1 with multi-outdoor-unit system is inhibited to operate.)

8 8 7 7 8 8 8OFF 8777778 ∗

Slave unit 1 operation: Inhibited 8777787

88 General Information

Page 95: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

Setting item 0 Display contents of "Number of units for sequential start, and others"

No. Setting itemLED display

Data displayH1P H2P H3P H4P H5P H6P H7P

0 Number of units for sequential starting, and others 9 7 7 7 7 7 7 See below

1 C/H unified address 9 7 7 7 7 7 8

Lower 6 digits

2 Low noise/demand address 9 7 7 7 7 8 7

3 Not used 9 7 7 7 7 8 8

4 Airnet address 9 7 7 7 8 7 7

5 Number of connected indoor units 9 7 7 7 8 7 8

6 Number of connected BS units 9 7 7 7 8 8 7

7 Number of connected zone units (excluding outdoor and BS unit) 9 7 7 7 8 8 8

8 Number of outdoor units 9 7 7 8 7 7 7

9 Number of connected BS units 9 7 7 8 7 7 8 Lower 4 digits: upper

10 Number of connected BS units 9 7 7 8 7 8 7 Lower 4 digits: lower

11 Number of zone units (excluding outdoor and BS unit) 9 7 7 8 7 8 8 Lower 6 digits

12 Number of terminal blocks 9 7 7 8 8 7 7 Lower 4 digits: upper

13 Number of terminal blocks 9 7 7 8 8 7 8 Lower 4 digits: lower

14 Contents of malfunction (the latest) 8 7 7 8 8 8 7 Malfunction code table

15Contents of malfunction(1 cycle before) 8 7 7 8 8 8 8

16 Contents of malfunction(2 cycle before) 8 7 8 7 7 7 7

20 Contents of retry (the latest) 8 7 8 7 8 7 7

21 Contents of retry (1 cycle before) 8 7 8 7 8 7 8

22 Contents of retry (2 cycle before) 8 7 8 7 8 8 7

Number of units for sequential start

1 unit 9 7 7 7 7 7 7

2 units 9 7 9 7 7 7 7

3 units 9 7 8 7 7 7 7

EMG operation /backup operation setting

ON 9 7 7 8 7 7 7

OFF 9 7 7 7 7 7 7

Defrost select setting Short 9 7 7 7 8 7 7

Medium 9 7 7 7 9 7 7

Long 9 7 7 7 7 7 7

Te setting H 9 7 7 7 7 8 7

M 9 7 7 7 7 9 7

L 9 7 7 7 7 7 7

Tc setting H 9 7 7 7 7 7 8

M 9 7 7 7 7 7 9

L 9 7 7 7 7 7 7

c. Monitor mode

<Selection of setting item>

<Confirmation on setting contents>

To enter the monitor mode, push the MODE button (BS1) when in “Setting mode 1”.

Push the SET button (BS2) and set the LED display to a setting item.

Push the RETURN button (BS3) to display different data of set items.

Push the RETURN button (BS3) and switches to the initial status of “Monitor mode”.

∗ Push the MODE button (BS1) and returns to “Setting mode 1”.

(V2765)

General Information 89

Page 96: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

Push the SET button and match with the LEDs No. 1 - 15, push the RETURN button, and enter the data for each setting.

Data such as addresses and number of units is expressed as binary numbers; the two ways of expressing are as follows:

The No. 1 cool/heat unified address is expressed as a binary number consisting of the lower 6 digits. (0 - 63)

In the address is 010110 (binary number), which translates to 16 + 4 + 2 = 22 (base 10 number). In other words, the address is 22.

The number of terminal blocks for No. 12 and 13 is expressed as an 8-digit binary number, which is the combination of four upper, and four lower digits for No. 12 and 13 respectively. (0 - 128)In the address for No. 12 is 0101, the address for No. 13 is 0110, and the combination of the two is 01010110 (binary number), which translates to 64 + 16 + 4 + 2 = 86 (base 10 number). In other words, the number of terminal block is 86.

See the preceding page for a list of data, etc. for No. 0 - 22.

9 797997 16 4 132 8 2

977 7979

64 16128 32No.12

977 7997

4 1No.13 8 2

90 General Information

Page 97: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

4.4.2.2 Cool / Heat Mode Switching

There are the following 4 cool/heat switching modes.Set cool/heat separately for each outdoor unit system by indoor unit remote controller.Set cool/heat separately for each outdoor unit system by cool/heat switching remote controller.Set cool/heat for more than one outdoor unit system simultaneously in accordance with unified master outdoor unit by indoor unit remote controller.Set cool/heat for more than one outdoor unit system simultaneously in accordance with unified master outdoor unit by cool/heat switching remote controller.

Set Cool/Heat Separately for Each Outdoor System by Indoor Unit Remote ControllerIt does not matter whether or not there is outdoor - outdoor unit wiring.Set outdoor unit PC board DS1-1 to "indoor" (factory set).Set cool/heat switching to "individual" for "Setting mode 1" (factory set).

General Information 91

Page 98: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

Set Cool / Heat Separately for Each Outdoor Unit System by Cool/Heat Switching Remote ControllerIt does not matter whether or not there is outdoor - outdoor unit wiring.Set outdoor unit PC board DS1-1 to “outdoor” (factory set).Set cool/heat switching to “individual” for “Setting mode 1” (factory set).

92 General Information

Page 99: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

Set Cool / Heat for More Than One Outdoor Unit System Simultaneously in Accordance with Unified Master Outdoor Unit by Indoor Unit Remote Controller

Install the external control adapter for outdoor unit on either the outdoor-outdoor, indoor-outdoor, or transmission line.Set outdoor unit PC board DS1-1 to “Indoor” (factory set).In setting mode 1, set the outdoor unit you want to give cool/heat selection permission to as the group master, and set the other outdoor units as group slave units.Set the external control adapter for outdoor unit SS1 to BOTH (factory set) or C/H, and SS2 to OFF (factory set).

Multi outdoor units connection

General Information 93

Page 100: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

Set Cool / Heat for More Than One Outdoor Unit System Simultaneously in Accordance with Unified Master Outdoor Unit by Cool/Heat Switching Remote Controller

Install cool/heat select remote controller on the group master outdoor unit.Install the external control adapter for outdoor unit on either the outdoor-outdoor, indoor-outdoor, or transmission line.Set group master outdoor unit PC board DS1-1 to “Outdoor” (factory set).In setting mode 1, set the outdoor unit you want to give cool/heat selection permission to as the group master, and set the other outdoor units as group slave units.Set the external control adapter for outdoor unit SS1 to BOTH (factory set) or C/H, and SS2 to OFF (factory set).

Multi outdoor units connection

94 General Information

Page 101: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

Supplementation on and .When switching cool/heat for each adapter PC board with the use of more than one adapter PC board, set the address of the adapter PC board DS1 and DS2 so that it matches the unified cool/heat address of outdoor unit PC board.

Address setting for and (Set lower 5 digits with binary number.) [No.0 to No.31]

Address No.

Outdoor unit PCB LEDSet with setting mode 2

Adapter PCB

No 0

No 1

No 2

No 3

No 4

No 30

No 31

DS2 DS1

87 77777

87 77778

87 77787

87 77788

87 77877

87 88887

87 88888

0

1

2

3

4

30

31

0

1

2

3

4

30

31

~ ~ ~

8ON 7OFFUpper position (ON) lower position (OFF)

(The shaded part shows knob)

(V2724)

General Information 95

Page 102: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

4.4.2.3 Setting of Low Noise Operation and Demand Operation

Setting of Low Noise OperationBy connecting the external contact input to the low noise input of the outdoor unit external control adapter (optional), you can lower operating noise by 2-3 dB.

A. When the low noise operation is carried out by external instructions (with the use of the external control adapter for outdoor unit)

1. Set "External low noise / Demand YES/NO setting" to "External low noise / Demand YES". (Set by Setting Mode 2)

2. Set "External low noise level setting" on the outdoor unit PC board, as the need arises.(Lower noise operation can be carried out by "Mode 2" than by "Mode 1", and by "Mode 3" than by "Mode 2".)

3. Set "Capacity precedence setting" on the outdoor unit PC board, as the need arises.(If set to "ON", when air conditioning load gets higher, the low noise instructions are neglected to switch to normal operation.) (Set by Setting Mode 2)

B. When the low noise operation is carried out automatically at night (The external control adapter for outdoor unit is not required)

1. Set "Night-time low noise setting" on the outdoor unit PC board. (Set by Setting Mode 2)(Lower noise operation can be carried out by "Mode 2" than by "Mode 1", and by "Mode 3" than by "Mode 2".)

2. Set "Night-time low noise start setting" on the outdoor unit PC board, as the need arises. (Set by Setting Mode 2) (Since the time is presumed in accordance with the outdoor temperature, the starting time is a target only.)

3. Set "Night-time low noise end setting" on the outdoor unit PC board, as the need arises. (Set by Setting Mode 2) (Since the time is presumed in accordance with the outdoor temperature, the ending time is a target only.)

4. Set "Capacity precedence setting" on the outdoor unit PC board, as the need arises. (Set by Setting Mode 2) (If set to "ON", when air conditioning load gets higher, the status is switched to normal operation even at night.)

96 General Information

Page 103: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

Image of operation in the case of A

Image of operation in the case of B

Image of operation in the case of A, B

General Information 97

Page 104: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

Setting of Demand OperationBy connecting the external contact input to the demand input of external control adapter for outdoor unit (optional), the power consumption of unit operation can be saved suppressing the compressor operating condition.

A. When the demand operation is carried out by external instructions (with the use of the external control adapter for outdoor unit).Set the "External low noise/Demand YES/NO setting" switch on the outdoor unit PCB to the "External low noise/Demand YES".(Set by Setting Mode 2)Set the "Demand 1 level setting" on the outdoor unit PCB, as the need arises.(During the demand level 1 instruction, the power consumption can be saved to 80 %, 70 % or 60 % of the rated value respectively.)

B. When the Normal demand operation is carried out. (Use of the external control adapter for outdoor unit is not required.)Set the "Normal demand setting" on the outdoor unit PCB.Set the "Demand 1 setting" on the outdoor unit PCB, as the need arises.(During the Normal demand setting operation, the power consumption can be saved to 80 %, 70 % or 60 % of the rated value respectively.)

98 General Information

Page 105: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

Image of operation in the case of A

Image of operation in the case of B

Image of operation in the case of A and B

(V3081)

Power consumption

Rated power consumption

80 % of rated power consumption70 % of rated power consumption60 % of rated power consumption

40 % of rated power consumption

Forced thermostat OFF(Fan operation)

Demand level 1 instructing

Power consumption set by "Demand 1 level setting".

Demand level 2 instructing Demand level 3 instructing

The power consumption during the demand level 1 instructing can be set with the "Demand 1 level setting".("70 % of rated power consumption" has been set at factory.)

(V3082)

The power consumption set with "Demand 1 level setting".

When the "Continuous demand setting" is set to ON ("OFF" has been set at factory.) , the power consumption can be set with the "Demand 1 level setting". ("70 % of rated power consumption" has been set at factory.)

Power consumption

Rated power consumption

80 % of rated power consumption70 % of rated power consumption60 % of rated power consumption40 % of rated power consumption

Forced thermostat OFF(Fan operation)

(V3083)

The power consumption set with "Demand 1 level setting".HDemand level 2 instructing HDemand level 3 instructing

The power consumption can be set with the "Demand 1 level setting". ("70 % of rated power consumption" has been set at factory.)

HDuring continuous demand operation, when the external demand instruction is received repeatedly, the instruction with higher demand level has the precedence.

Power consumption

Rated power consumption

80 % of rated power consumption70 % of rated power consumption60 % of rated power consumption

40 % of rated power consumption

Forced thermostat OFF(Fan operation)

General Information 99

Page 106: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

Detailed Setting Procedure of Low Noise Operation and Demand Control

1. Setting mode 1 (H1P off)In setting mode 2, push the BS1 (MODE button) one time. → Setting mode 2 is entered and H1P lights.During the setting mode 1 is displayed, "In low noise operation" and "In demand control" are displayed.

2. Setting mode 2 (H1P on)In setting 1, push and hold the BS1 (MODE button) for more than 5 seconds. → Setting mode 2 is entered and H1P lights.Push the BS2 (SET button) several times and match the LED display with the Setting No. you want.Push the BS3 (RETURN button) one time, and the present setting content is displayed.→ Push the BS2 (SET button) several times and match the LED display with the setting content (as shown below) you want.Push the BS3 (RETURN button) two times. → Returns to .Push the BS1 (MODE button) one time. → Returns to the setting mode 1 and turns H1P off.

100 General Information

Page 107: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

Setting No.

Setting contents

Setting No. indication Setting No. indication Setting contents

Setting contents indication (Initial setting)

H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P

12 External low noise / Demand setting

NO (Factory set) 9

YES 9

22 Night-time low noise setting

OFF (Factory setting)

Mode 1 9

Mode 2 9

Mode 3 9 9

25 External low noise setting

Mode 1 9

Mode 2(Factory setting)

9

Mode 3 9

26 Night-time low noise start setting

PM 8:00 9

PM 10:00 (Factory setting)

9

PM 0:00 9

27 Night-time low noise end setting

AM 6:00 9

AM 7:00 9

AM 8:00 (Factory setting)

9

29 Capacity precedence setting

Low noise precedence (Factory setting)

9

Capacity precedence 9

30 Demand setting 1

60 % of rated power consumption

9

70 % of rated power consumption (Factory setting)

9

80 % of rated power consumption

9

32 Continuous demand setting

OFF (Factory setting)

9

Continuous demand 1 fixed

9

Setting mode indication section Setting No. indication section Set contents indication section

General Information 101

Page 108: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

4.4.2.4 Setting of Refrigerant Additional Charging OperationWhen additional refrigerant is not charged all with outdoor unit in stop mode, operate the outdoor unit and charge the liquid refrigerant from the service port of liquid stop value. The additional charging operation is activated by pushbutton switch on the outdoor unit PC board.

[Additional refrigerant charge total flow]

Confirm LIQ & SUCTION and Oil equalizing Stop valve closed.

Is all refrigerant charged?

Is all refrigerant charged?

YES

NO

YES

NO

Turn off the power.

Charge through Service port of LIQ. Stop valve.

Open LIQ & SUCTION Stop valve.

Open LIQUID Stop valve.

Disconnect charge hose.

END of charge method.

STOP refrigerant charge model

STEP 1

Additional

charge

without

Compressor

operation

Open Gas Stop valve.(Liquid side stop valve : close)

Start additional refrigerant charge mode. (Setting Mode 2 : Refer operation procedure detail on next page.)

STEP 2

Additional

charge

with

Compressor

operation

(V2892)

102 General Information

Page 109: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Test Operation

[Operation procedure detail]After turning the respective power supply switch of indoor and outdoor units off and charging the refrigerant, turn on the power of indoor and outdoor units.Do not fail to turn the power off and charge the refrigerant with outdoor unit in stop mode before adding the refrigerant following this procedure, otherwise resulting in trouble.Fully open the stop valve on the gas side and oil equalizing valve for multi outdoor connection, and do not fail to fully close the stop valve on the liquid side. (If the stop valve on the liquid side is open, the refrigerant cannot be charged.)In Setting mode 2 (H1P : ON) with outdoor unit in stop mode, Set "Additional refrigerant charging operation" switch to ON to start the operation. (H2P turns to display TEST OPERATION (blinks), and "TEST OPERATION" and "UNDER CENTRALIZED CONTROL" are displayed on the remote controller.)When the refrigerant is charged up to the specified amount, press the RETURN button (BS3) to stop charging.The charging operation is automatically stopped after operating for a maximum of about 30 minutes.If the charging is not complete within 30 minutes, set the Additional refrigerant charging operation again to start charging. When the charging immediately stops even by restarting, the refrigerant is charged excessively. The refrigerant cannot be charged any more.Do not fail to fully open the stop valve on the liquid side as soon as disconnecting the refrigerant charging hose.(The piping may be burst due to the liquid sealing.)

[Operation state]• Compressor frequency : 210Hz• Y1S, Y2S, Y3S Solenoid valve : Open• Outdoor unit fan : High pressure control• Indoor unit expansion valve (All unit) : 1024 pulse• Indoor unit fan : H tap

4.4.2.5 Setting of Refrigerant Recovery ModeWhen carrying out the refrigerant collection on site, fully open the respective expansion valve of indoor and outdoor unitsAll indoor and outdoor unit’s operation are prohibited.

[Operation procedure]In setting mode 2 with units in stop mode, set "B Refrigerant Recovery / Vacuuming mode" to ON. The respective expansion valve of indoor and outdoor units are fully opened. (H2P turns to display "TEST OPERATION" (blinks), "TEST OPERATION" and "UNDER CENTRALIZED CONTROL" are displayed on the remote controller, and the all indoor and outdoor unit operation is prohibited.After setting, do not cancel "Setting Mode 2" until completion of refrigerant recovery operation.Collect the refrigerant using a refrigerant recovery unit. (See the instruction attached to the refrigerant recovery unit for more detail.)Press Mode button "BS1" once and reset "Setting Mode 2".

General Information 103

Page 110: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Test Operation SiUS39-504

4.4.2.6 Setting of Vacuuming ModeIn order to perform vacuuming operation at site, fully open the expansion valves of indoor and outdoor units and turn on some solenoid valves.

[Operating procedure]With Setting Mode 2 while the unit stops, set (B) Refrigerant recovery / Vacuuming mode to ON. The expansion valves of indoor and outdoor units fully open and some of solenoid valves open. (H2P blinks to indicate the test operation, and the remote controller displays "Test Operation" and "Under Centralized control", thus prohibiting operation.)After setting, do not cancel "Setting Mode 2" until completion of Vacuuming operation.Use the vacuum pump to perform vacuuming operation.Press Mode button "BS1" once and reset "Setting Mode 2".

4.4.2.7 Check OperationTo prevent any trouble in the period of installation at site, the system is provided with a test operation mode enabling check for incorrect wiring, stop valve left in closed, coming out (or misplacing with suction pipe thermistor) of discharge pipe thermistor and judgment of piping length, refrigerant overcharging, and learning for the minimum opening degree of motorized valve.

Unit stopping

Press the TEST button for 5 seconds.

10 sec to 10 minutes

LED display (H1P~H7P) (8:ON 9:BLINK 3:OFF)3383333

3933338Pressure equalizingStep 1

20 sec to 2 minutes

10 minutes

3 minutes

5 minutes

3933383Cooling start controlStep 2

3933388

3933888

3938333

Stability waiting operationStep 3

Pump down residual operationStep 7

5 minutes

Standby for restarting

Completion

Step 8

• Stop valve close check • Wrong wiring check• Refrigerant over change check• Piping length check

3933833

3933838

3933883

Judgement functionStep4~6

CHECK OPERATION FUNCTION

104 General Information

Page 111: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Caution for Refrigerant Leaks

5. Caution for Refrigerant Leaks5.1 Caution for Refrigerant Leaks

(Points to note in connection with refrigerant leaks)

5.1.1 IntroductionThe installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.The VRV System, like other air conditioning systems, uses R-410A as refrigerant. R-410A itself is an entirely safe non-toxic, non-combustible refrigerant. Nevertheless care must be taken to ensure that air conditioning facilities are installed in a room which is sufficiently large. This assures that the maximum concentration level of refrigerant gas is not exceeded, in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards.

5.1.2 Maximum concentration levelThe maximum charge of refrigerant and the calculation of the maximum concentration of refrigerant is directly related to the humanly occupied space in to which it could leak.The unit of measurement of the concentration is lb/ft3 (the weight in Ib. of the refrigerant gas in 1ft3 volume of the occupied space).Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required.

Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant is heavier than air.

5.1.3 Procedure for checking maximum concentration

Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply.

1. Calculate the amount of refrigerant (Ib.) charged to each system separately.

Notes: Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems then use the amount of refrigerant with which each separate system is charged.

2. Calculate the smallest room volume (ft3)Incase like the following, calculate the volume of (A), (B) as a single room or as the smallest room.

2

1

1. direction of the refrigerant flow2. room where refrigerant leak

has occurred (outflow of all the refrigerant from the system)

amount of refrigerant in a single unit system (amount of refrigerant with which the system is charged before leaving the factory)

+additional charging amount (amount of refrigerant added locally in accordance with the length or diameter of the refrigerant piping)

=total amount of refrigerant (Ib.) in the system

General Information 105

Page 112: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Caution for Refrigerant Leaks SiUS39-504

A.Where there are no smaller room divisions

B.Where there is a room division but there is an opening between the rooms sufficiently large to permit a free flow of air back and forth.

(Where there is an opening without a door or where there are openings above and below the door which are each equivalent in size to 0.15% or more of the floor area.)

3. Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above.

If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so until the result falls short of the maximum concentration.

4. Dealing with the situations where the result exceeds the maximum concentration level.Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise the system.Please consult your Daikin supplier.

total volume of refrigerant in the refrigerant system≤ maximum concentration level (Ib./ft3)

size (ft3) of smallest room in which there is an indoor unit installed

1

2

1. opening between rooms2. partition

106 General Information

Page 113: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Hand Over to Customer

6. Hand Over to Customer6.1 Operational Steps

Important Points a) The measurements taken during the test run should be recorded and kept on a test run inspection sheet.b) Do not forget to record the length of the refrigerant piping and the refrigerant additional charging

volume on the plate on the back of the outdoor unit external notice board, as this information will be required for servicing the system.

c) Explain to the customer how to operate the equipment and let him try it.d) Assemble all the relevant diagrams and other printed matter which is required to operate the system and

hand it all over to the customer (on the spot) and tell him to keep it.

e) Make the service contact address clear.

Complete test runMake final report (test run inspection sheet)

Explain how to operate equipment

Hand over relevant printed materials

(V1050)

General Information 107

Page 114: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

7. Appendix7.1 Operating Noise of Indoor Units7.1.1 Difference between Catalogue Data and Actual Noise

Operating noise differs depending on the place of measurement (room) because of the various degrees with which the room reverberates the sound. To determine the amount of reverberation under uniform conditions, the unit has been measured in a dead room with results having been compiled in the below table. The actual sound produced in unit operation can be determined from Table 1.

Sound pressure rise due to room reverberation (Higher than catalogue data)

Table 1

Classifications of indoor unit environments (reference data)Table 2

Notes: 1. Excluding bedrooms2. Reference values of faint noises in the place of usage

A B C

Room Interior Detection

Floor Mortar Linoleum tile Carpet

Walls Mortar Plaster Fiberglass + Saroncross finish

Ceiling Mortar mineral wool tile Fiberglass + Saroncross finish

Average Absorbed Sound (Room with Approx. 50 m² Floor Area)

0.05 0.12 0.25

Typical office

Estimated value to be added to catalogue value 11~12 8~8.5 5~6

Classification Environment Example Faint Noises (NOTE 2)

Recommended Operating Noise on Site

1 Non-active places requiring silence Reception rooms, libraries, sitting rooms, hospitals (examining rooms) (NOTE 1) ~35 ~40

2 Sedate business activities that do not disturb people even over time

Quiet offices, classrooms, small conference rooms, lobbies ~40 ~45

3Somewhat quiet settings that permit soft-spoken conversation, typical activities

Small offices, large conferences rooms, quiet stores, restaurants ~45 ~50

4 Somewhat loud settings that permit regular conversation, brisk activity Large offices, typical stores, cafeterias ~50 ~55

5Loud places that permit conversation in a loud voice, highly active place with many people

Loud large-side offices, large cafeterias, loud stores ~55 ~60

6 Rather loud settings Factories, gymnasiums, recreational places like pachinko parlors ~60 ~65

108 General Information

Page 115: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

7.1.2 Faint Noises and Correcting Operating Noise with Respect to Faint Noises

Faint noises are defined as peripheral sounds existing while the unit is not running, which are picked up when measuring operating noise. If these faint noises are 10 dB or more than the noise produced by the unit, the measured value can be taken as the operating noise of the unit. But, the difference must be corrected if less than 10 dB, because of the effect these noises have on the actual measured value. Also, when the sound meter remains unchanged even while the unit is stopped, we can determine the operational noise to be at least 10 dB less than the faint noises, but we cannot pinpoint the operating noise exactly.For example, if the faint noises are some 65 dB and the noise produced by the unit in operation is 70 dB, the indicated difference comes to 5 dB. Using Table 3, we recommend you correct the operating noise by about 2 dB to 68 dB.

7.1.3 Calculating Operating NoiseWhen two or more units are running at the same time, the amount of operating noise they produce rises. The total amount of noise produced can be obtained ahead of time with Chart 4.

Sample calculation 1L1 and L2 are given as compounded sounds of 50 and 49 dB respectively. Since L1 – L2 = 50 – 49 = 1, the corrective value is 2.5, therefore 50 + 2.5 = 52.5 dB.

Sample calculation 2When sounds of 40 dB, 38 dB, 37 dB and 40 dB are placed in order of magnitude, we obtain the following:

40 dB, 40 dB, 38 dB, 37 dB

To start, the difference between 40 dB and 40 dB is 0, therefore we take a corrective value of 3dB and obtain 40 + 3 = 43 dB. The compounded sound of 43 dB and 38 dB has a 5.0 dB difference, thus a corrective value of 1.2 dB, which gives us 44.2 dB from 43 + 1.2. In the same manner, the corrective value for 44.2 dB and 37 dB is approximately 0.7 dB, or in other words, 44.2 + 0.7 = 44.9 dB.

Table 3 Correcting the effect of faint noisesUnit: dB

Difference between when noise is produced and when not 1 2 3 4 5 6 7 8 9 10

Corrective Value –6.9 –4.4 –3.0 –2.3 –1.7 –1.25 –0.95 –0.75 –0.60 –0.45

General Information 109

Page 116: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

7.2 Allowable Piping Length7.2.1 Branch with Refnet Joint

(Connection of 8 indoor units Heat pump system)

* In case of multiple outdoor units installed, re-read to the first outdoor branch as seen from the indoor unit.

One outdoor unit installed

Branch with refnet joint

Multiple outdoorunits installed

aA B C D E F G

b c d e f g p

h i j k l m n1 2 3 4 5 6 7

8H2

Outdoor unit REFNET joint (A-G)

Indoor units (1-8)

H1

A B C D E F G

a b c d e f g

8H2

H1

H3

P

Indoor units ( - )

Outdoor unitREFNET joint ( - )

h i j k l m n1 2 3 4 5 6 7

First outdoor branch

A G

1 8

Maximum Allowable Length

Between outdoor and indoor units

• Actual pipe lengthPipe length between outdoor and indoor units ≤ 330ft.Example unit 8: a + b + c + d + e + f + g + p ≤ 330ft.

• Equivalent lengthEquivalent pipe length between outdoor and indoor units ≤ 390ft.(assume equivalent pipe length of refnet joint to be 1.6ft., that of refnet header to be 3.3ft., calculation purposes)

• Total extension lengthTotal piping length from outdoor unit* to all indoor units ≤ 950ft.

Between outdoor branch and indoor unit (Only for multiple outdoor units) • Actual pipe length

Piping length from outdoor branch to outdoor unit ≤ 33ft. Approximately length: max 43ft.

Allowable Height Length

Between outdoor and indoor units• Difference in height

Difference in height between outdoor and indoor units (H1) ≤ 164ft.(Max 130ft. if the outdoor unit is below)

Between indoor and indoor units• Difference in height

Difference in height between adjacent indoor units (H2) ≤ 49ft.Between outdoor and outdoor units • Difference in height

Difference in height between outdoor unit (main) and outdoor unit (sub) (H3) ≤ 16ft.

Allowable Length after the Branch

• Actual pipe lengthPipe length from first refrigerant branch kit (either refnet joint or refnet header) to indoor unit ≤ 130ft.Example unit 8: b + c + d + e + f + g + p ≤ 130ft.

r

t

Outdoor unit

r ≤ 33ft. (Approximately length: max 43ft.)t ≤ 33ft. (Approximately length: max 43ft.)

110 General Information

Page 117: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

7.2.2 Branch with Refnet Joint and Refnet Header(Connection of 8 indoor units Heat pump system)

* In case of multiple outdoor units installed, re-read to the first outdoor branch as seen from the indoor unit.

One outdoor unit installed

Branch with refnet joint and refnet header

Multiple outdoorunits installed

ai

b

c d e f g h1 2 3 4 5 6

Outdoor unit REFNET joint (B)

Indoor units (1-8)

Refnet headerk

j7 8

A B

H1

H2

H1

H2

ai

b

Outdoor unit

c d e f g h1 2 3 4 5 6

Indoor units ( - )

REFNET headerk

j7 8

H3REFNET joint ( • )

A B

1 8

A B

Maximum Allowable Length

Between outdoor and indoor units

• Actual pipe lengthPipe length between outdoor and indoor units ≤ 330ft.Example unit 6: a + b + h ≤ 330ft., unit 8: a + i + k ≤ 330ft.

• Equivalent lengthEquivalent pipe length between outdoor and indoor units ≤ 390ft.(assume equivalent pipe length of refnet joint to be 1.6ft., that of refnet header to be 3.3ft., calculation purposes)

• Total extension lengthTotal piping length from outdoor unit* to all indoor units ≤ 950ft.

Between outdoor branch and indoor unit (Only for multiple outdoor units) • Actual pipe length

Piping length from outdoor branch to outdoor unit ≤ 33ft. Approximately length: max 43ft.

Allowable Height Length

Between outdoor and indoor units• Difference in height

Difference in height between outdoor and indoor units (H1) ≤ 164ft.(Max 130ft. if the outdoor unit is below)

Between indoor and indoor units• Difference in height

Difference in height between adjacent indoor units (H2) ≤ 49ft.Between outdoor and outdoor units • Difference in height

Difference in height between outdoor unit (main) and outdoor unit (sub) (H3) ≤ 16ft.

Allowable Length after the Branch

• Actual pipe lengthPipe length from first refrigerant branch kit (either refnet joint or refnet header) to indoor unit ≤ 130ft.Example unit 6: b + h ≤ 130ft., unit 8: i + k ≤ 130ft.

r

t

Outdoor unit

r ≤ 33ft. (Approximately length: max 43ft.)t ≤ 33ft. (Approximately length: max 43ft.)

General Information 111

Page 118: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

7.2.3 Branch with Refnet Header(Connection of 8 indoor units Heat pump system)

* In case of multiple outdoor units installed, re-read to the first outdoor branch as seen from the indoor unit.

One outdoor unit installed

Branch with refnet header

Multiple outdoorunits installed

a

H1

H2

Outdoor unit Refnet header

Indoor units (1-8)

c d e f g hb1 2 3 4 5 6 7

8

H2 i8

H1

H3

a

Outdoor unitREFNET header

Indoor units ( - )

c d e f g hb1 2 3 4 5 6 7

1 8

Maximum Allowable Length

Between outdoor and indoor units

• Actual pipe lengthPipe length between outdoor and indoor units ≤ 330ft.Example unit 6: a + i ≤ 330ft.

• Equivalent lengthEquivalent pipe length between outdoor and indoor units ≤ 390ft.(assume equivalent pipe length of refnet joint to be 1.6ft., that of refnet header to be 3.3ft., calculation purposes)

• Total extension lengthTotal piping length from outdoor unit* to all indoor units ≤ 950ft.

Between outdoor branch and indoor unit (Only for multiple outdoor units) • Actual pipe length

Piping length from outdoor branch to outdoor unit ≤ 33ft. Approximately length: max 43ft.

Allowable Height Length

Between outdoor and indoor units• Difference in height

Difference in height between outdoor and indoor units (H1) ≤ 164ft.(Max 130ft. if the outdoor unit is below)

Between indoor and indoor units• Difference in height

Difference in height between adjacent indoor units (H2) ≤ 49ft.Between outdoor and outdoor units • Difference in height

Difference in height between outdoor unit (main) and outdoor unit (sub) (H3) ≤ 16ft.Allowable Length after the Branch

• Actual pipe lengthPipe length from first refrigerant branch kit (either refnet joint or refnet header) to indoor unit ≤ 130ft.Example unit 8: i ≤ 130ft.

r

t

Outdoor unit

r ≤ 33ft. (Approximately length: max 43ft.)t ≤ 33ft. (Approximately length: max 43ft.)

112 General Information

Page 119: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

7.3 Refrigerant Branch Kit Selection

7.3.1 How to Select the Refnet JointWhen using refnet joints at the first branch counted from the outdoor unit side.

Choose from the following table in accordance with the capacity of the outdoor unit.

For refnet joints other than the first branch, select the proper branch kit model based on the total capacity index of downstream indoor units.

*Example of downstream indoor units1. example in case of refnet joint C; indoor units 3 + 4 + 5 + 6 + 7 + 8,

2. example in case of refnet joint B indoor units 7 + 8example in case of refnet joint header; indoor units 1 + 2 + 3 + 4 + 5 + 6

3. example in the case of refnet header; indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8

Refrigerant branch kits can only be used with R-410A.

Outdoor unit capacity type Refrigerant branch kit name

RXYQ 96M type KHRP26M33T

RXYQ192M KHRP26M72TU

Indoor capacity index Refrigerant branch kit name

< 72 KHRP26M22T

72 ≤ x < 111 KHRP26M33T

111 ≤ KHRP26M72TU

aA B C D E F G

b c d e f g

h i j k l m n1 2 3 4 5 6 7

8H2

Outdoor unit REFNET joint (C)

Indoor units (1-8)

H1

ai

b

c d e f g h1 2 3 4 5 6

Outdoor unit REFNET joint (B)

Indoor units (1-8)

Refnet headerk

j7 8

A B

H1

H2

a

H1

H2

Outdoor unit Refnet header

Indoor units (1-8)

c d e f g hb1 2 3 4 5 6 7

8

General Information 113

Page 120: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

7.3.2 How to Select the Refnet HeaderChoose from the following table in accordance with the total capacity of all the indoor units connected below the REFENT header.Note: 250 type cannot be connected below the REFENT header.

*Example of downstream indoor units1. example in case of refnet joint C; indoor units 3 + 4 + 5 + 6 + 7 + 8

2. example in case of refnet joint B indoor units 7 + 8,example in case of refnet header; indoor units 1 + 2 + 3 + 4 + 5 + 6

3. example in the case of refnet header; indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8

7.3.3 How to Choose an Outdoor Branch KitIn case of multiple outdoor units installed, use outdoor branch kit.

Indoor capacity index Refrigerant branch kit name

< 72 KHRP26M22H (Max.4 kit)

< 111 KHRP26M33H (Max. 8 kit)

111 ≤ KHRP26M72H (Max. 8 kit)

aA B C D E F G

b c d e f g

h i j k l m n1 2 3 4 5 6 7

8H2

Outdoor unit REFNET joint (C)

Indoor units (1-8)

ai

b

c d e f g h1 2 3 4 5 6

Outdoor unit REFNET joint (B)

Indoor units (1-8)

Refnet headerk

j7 8

A B

H1

H2

a

H1

H2

Outdoor unit Refnet header

Indoor units (1-8)

c d e f g hb1 2 3 4 5 6 7

8

Number of outdoor units Branch kit name

2 units BHFP22M90U

114 General Information

Page 121: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

7.4 Pipe Size Selection

Piping between outdoor unit and refrigerant branch kit (part A)Match to the size of the connection piping on the outdoor unit.Outdoor unit connection piping size

(Unit : in.)

Piping between refrigerant branch kitsChoose from the following table in accordance with the total capacity of all the indoor units connected below this.Do not let the connection piping exceed the refrigerant piping size chosen by general system model name.

(Unit : in.)

Between refrigerant branch kit and indoor unitPipe size for direct connection to indoor unit must be the same as the connection size of indoor unit.

(Unit : in.)

Piping between outdoor branch and outdoor unit (part B)(Unit : in.)

Oil-equalizing line (Only for multiple outdoor units installed) (part C)(Unit : in.)

Piping between outdoor branch and outdoor unit (part B)

Oil-equalizing line (part C)

Piping between outdoor units and refrigerant branch kit (part A)

CautionThe thickness and material shall be selected in accordance with local code.For an outdoor unit multi installation, make the settings in accordance with the following figure.

Outdoor unit capacity typePiping size (outer diameter)

Gas pipe Liquid pipeRXYQ 96M type ø7/8 ø3/8RXYQ192M ø1-1/8 ø5/8

Indoor capacity indexPiping size (outer diameter)

Gas pipe Liquid pipe< 72 ø5/8

ø3/872 ≤ x < 111 ø7/8

111 ≤ x < 156ø1-1/8

ø1/2

156 ≤ ø5/8

indoor capacity typePiping size (outer diameter)

Gas pipe Liquid pipe12, 18 type ø1/2 ø1/424, 30, 36, 48 type ø5/8 ø3/8

outdoor capacity typePiping size

Gas pipe Liquid pipeRXYQ96 ø7/8 ø3/8

Piping size ø1/4

General Information 115

Page 122: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

7.5 How to Calculate the Additional Refrigerant to be ChargedAdditional refrigerant to be charged R (lb.)R should be rounded off in units of 0.1lb..

Note: If a negative result is gotten for R from the formula at right, no refrigerant needs to be added.

Note: The amount of refrigerant to be added to the unit should be written on the included "Added Refrigerant" plate and attached to the rear side of the front cover. Refer next page.

Example for refrigerant branch using REFNET joint and REFNET header for RXYQ192

R= + + +

+ + _

Total length (ft.) of liquid piping size at φ7/8

×0.235Total length (ft.) of liquid piping size at φ3/4

×0.168Total length (ft.) of liquid piping size at φ5/8

×0.114Total length (ft.) of liquid piping size at φ1/2

×0.074

Total length (ft.) of liquid piping size at φ3/8

×0.036Total length (ft.) of liquid piping size at φ1/4

×0.015Model name

RXYQ96RXYQ192

0 lb.6.6 lb.

Amount of refrigerant

ai

b

c d e f g h1 2 3 4 5 6

Outdoor unit

Indoor units (1-8)

Refnet headerk

j7 8

A B

H1

H2

H3

a: φ3/4 × 100ft.b: φ5/8 × 30ft.c: φ3/8 × 30ft.

d: φ3/8 × 30ft.e: φ3/8 × 30ft.f : φ3/8 × 30ft.

g: φ1/4 × 30ft.h: φ1/4 × 70ft.i : φ1/2 × 30ft.

j : φ1/4 × 30ft.k: φ1/4 × 25ft.

If the outdoor unit is RXYQ192 units and the piping lengths are as atright

R= 100 0.168 + 30 0.014 + 30 0.074 + 120 0.036 + 155 0.015 - 6.6 =22.485

ba c+d+e+f g+h+j+ki 22.5

116 General Information

Page 123: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

3P124659A

General Information 117

Page 124: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

7.6 REFNET Pipe Connections for VRVII R-410A Series7.6.1 REFNET Joint (Unit: mm)

KHRP26M22T

KHRP26M33T

KHRP26M72TU

Gas Side

Insulation Insulation

(unit:mm)Liquid Side

D3K03622B

Gas SideInsulation Insulation

Liquid Side

D3K03623A

Liquid SideGas Side

Insulation Insulation

D3K04887

118 General Information

Page 125: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

7.6.2 REFNET Header (Unit: mm)KHRP26M22H

KHRP26M33H

KHRP26M72H

D3K03629B

Gas SideLiquid SideInsulation Insulation

(unit:mm)

D3K03630B

Gas Side Liquid SideInsulation Insulation

D3K03631B

Gas Side Liquid Side

Insulation

Insulation

General Information 119

Page 126: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

REFNET Joint and Header Installation

1. REFNET joint(Gas line and liquid line branch pipe)

If the selected building pipe differs form the branch pipe in size, cut the connection with a pipe cutter as shown below.

Install the branch pipe either vertically or horizontally.

Insulate the branch pipe as described in the kit installation manual.

2. REFNET header

If the selected field pipe differs from the branch pipe in size, cut the connection with a pipe cutter as shown below.

Fit a stop end on all open branch pipe connections not in use.

Install the branch pipe horizontally.

Insulate the branch pipe as described in the kit installation manual.

Note: Install the REFNET joint horizontally or vertically, keeping it within a 30 angle when installed horizontally.Install the REFNET header so that it branches horizontally.Do not used a T-joint for the branch pipe.

120 General Information

Page 127: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

7.7 VRV Inspection Sheet

Indoor units

No.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

Installation Model Unit No. Group No.

Field settings

C/H SELECT (setting mode 1)

Tc

IND

H M L

C/H SELECT setting (DS1-1)

Te

ON OFF

H M L

Low noise operation

Defrost SETTING

ON OFF

Sequential start

Refrigerant addition/replenishment

lb.

ON OFF

H M L

MASTER SLAVE

Company name Inspector

(V1091)

Outdoor unit system name

Outdoor unit 1

Outdoor unit 2

Inspection date:

Delivery date:

Transfer date:

Owner System name

Outdoor units

Installation location Model Unit No.

General Information 121

Page 128: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

Before turning on the power

(V1092)

Inspection item Inspection method Standard (guideline) Measurement values Decision

Breaker capacity Visual inspection Specified capacity G NG

Refrigerant piping system Gas detector No leaks G NG

Heat exchanger Visual inspection No clogging or damage G NG

Terminal connection section Screwdriver, etc. No looseness G NG

Fan motor electrical insulation 500-V megatester 1 MΩ or more MΩ

Compressor electrical insulation 500-V megatester 1 MΩ or more INV MΩ STD MΩ

Installation Visual inspection Short circuit, etc. G NG

Refrigerant piping system Gas detector No leaks G NG

Heat exchanger Visual inspection No clogging or damage G NG

Terminal connection section Screwdriver, etc. No looseness G NG

Fan motor electrical insulation 500-V electrical insulation tester 1 MΩ or more MΩ

Compressor electrical insulation 500-V electrical insulation tester 1 MΩ or more INV MΩ STD MΩ

Installation Visual inspection Short circuit, etc. G NG

Indoorunit

Refrigerant system Gas detector No leaks

Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NGRoom 5 G NG Room 6 G NG Room 7 G NG Room 8 G NGRoom 9 G NG Room 10 G NG Room 11 G NG Room 12 G NGRoom 13 G NG Room 14 G NG Room 15 G NG Room 16 G NGRoom 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG

Air filter Visual inspection

No clogging or damage

Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NGRoom 5 G NG Room 6 G NG Room 7 G NG Room 8 G NGRoom 9 G NG Room 10 G NG Room 11 G NG Room 12 G NGRoom 13 G NG Room 14 G NG Room 15 G NG Room 16 G NGRoom 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG

Heat exchanger Visual inspection

No clogging or damage

Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NGRoom 5 G NG Room 6 G NG Room 7 G NG Room 8 G NGRoom 9 G NG Room 10 G NG Room 11 G NG Room 12 G NGRoom 13 G NG Room 14 G NG Room 15 G NG Room 16 G NGRoom 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG

Fan motor electrical insulation

500-V electrical insulation tester 1 MΩΩΩΩ or more

Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NGRoom 5 G NG Room 6 G NG Room 7 G NG Room 8 G NGRoom 9 G NG Room 10 G NG Room 11 G NG Room 12 G NGRoom 13 G NG Room 14 G NG Room 15 G NG Room 16 G NGRoom 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG

Auxiliary heater electrical insulation

500-V electrical insulation tester 1 MΩΩΩΩ or more

Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NGRoom 5 G NG Room 6 G NG Room 7 G NG Room 8 G NGRoom 9 G NG Room 10 G NG Room 11 G NG Room 12 G NGRoom 13 G NG Room 14 G NG Room 15 G NG Room 16 G NGRoom 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG

Installation Visual inspection Short circuit, etc.

Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NGRoom 5 G NG Room 6 G NG Room 7 G NG Room 8 G NGRoom 9 G NG Room 10 G NG Room 11 G NG Room 12 G NGRoom 13 G NG Room 14 G NG Room 15 G NG Room 16 G NGRoom 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG

System nameO

utdo

or u

nit 1

Out

door

uni

t 2

122 General Information

Page 129: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

During operation

(V1093)

Inspection item Inspection method Standard (guideline) Measurement values Decision

Out

door

uni

t 1

Main power supply voltage Tester Rated voltage ±10% R-S V S-T V R-T V

Operation circuit voltage Tester Rated voltage ±10% V

Fan rotation direction Visual inspection Forward rotation G NG

Fan noise/vibration Listening No noise or vibration

Fan operation current Clamp meterRED WHITE BLACK A A A

Suction air temperature Thermometer Temperature differential16.2~19.8deg. when cooling, 3.6~6.3deg. when heating

°F

Discharge air temperature Thermometer °F

Compressor discharge pressure Pressure gauge Psi

Compressor suction pressure Pressure gauge Psi

Compressor operating current Clamp meter Phase differential within 1A

INV U( )A, V( )A, W( )A

STD R( )A, S( )A, T( )A

Compressor operating frequency Clamp meter INV Hz

Suction pipe temperature Thermometer 37.4~59°F

Discharge pipe temperature Thermometer 185~221°F

Clank case heater Touch Warm

Out

door

uni

t 2

Main power supply voltage Tester Rated voltage ±10% R-S V R-S V R-S V

Operation circuit voltage Tester Rated voltage ±10% V

Fan rotation direction Visual inspection Forward rotation G NG

Fan noise/vibration Listening No noise or vibration

Fan operation current Clamp meterRED WHITE BLACK A A A

Suction air temperature Thermometer Temperature differential9~11deg. when cooling, 2~3.5deg. when heating

°C

Discharge air temperature Thermometer °C

Compressor discharge pressure Pressure gauge MPa

Compressor suction pressure Pressure gauge MPa

Compressor operating current Clamp meter Phase differential within 1A

INV U( )A, V( )A, W( )A

STD R( )A, S( )A, T( )A

Compressor operating frequency Clamp meter INV Hz

Suction pipe temperature Thermometer 37.4~59°F

Discharge pipe temperature Thermometer 185~221°F

Clank case heater Touch Warm

System name

INV °F STD °F

INV G NG STD G NG

INV °F

INV G NG

INV °F

INV °F

STD °F

STD °F

STD °F

STD G NG

General Information 123

Page 130: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

During operation

(V1094)

Inspection item Inspection method

Standard (guideline) Measurement values Decision

Indo

or u

nit

Powerly supply voltage Tester Rated voltage

±10%

Room 1 V Room 2 V Room 3 V Room 4 V

Room 5 V Room 6 V Room 7 V Room 8 V

Room 9 V Room10 V Room11 V Room12 V

Room13 V Room14 V Room15 V Room16 V

Room17 V Room18 V Room19 V Room20 V

Suction air temperature

Thermometer

Thermometer differential

48.2~55.4 °F when cooling,59~68 °F when heating

Room 1 °C Room 2 °C Room 3 °C Room 4 °C

Room 5 °C Room 6 °C Room 7 °C Room 8 °C

Room 9 °C Room10 °C Room11 °C Room12 °C

Room13 °C Room14 °C Room15 °C Room16 °C

Room17 °C Room18 °C Room19 °C Room20 °C

Discharge air temperature

Room 1 °C Room 2 °C Room 3 °C Room 4 °C

Room 5 °C Room 6 °C Room 7 °C Room 8 °C

Room 9 °C Room10 °C Room11 °C Room12 °C

Room13 °C Room14 °C Room15 °C Room16 °C

Room17 °C Room18 °C Room19 °C Room20 °C

Fan rotation direction

Visual inspection Forward rotation

Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NG

Room 5 G NG Room 6 G NG Room 7 G NG Room 8 G NG

Room 9 G NG Room 10 G NG Room 11 G NG Room 12 G NG

Room 13 G NG Room 14 G NG Room 15 G NG Room 16 G NG

Room 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG

Fan noise/vibration Listening No noise or

vibration

Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NG

Room 5 G NG Room 6 G NG Room 7 G NG Room 8 G NG

Room 9 G NG Room 10 G NG Room 11 G NG Room 12 G NG

Room 13 G NG Room 14 G NG Room 15 G NG Room 16 G NG

Room 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG

Fan operating current Clamp meter

Room 1 A Room 2 A Room 3 A Room 4 A

Room 5 A Room 6 A Room 7 A Room 8 A

Room 9 A Room10 A Room11 A Room12 A

Room13 A Room14 A Room15 A Room16 A

Room17 A Room18 A Room19 A Room20 A

System name

124 General Information

Page 131: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

7.8 Piping System Diagrams7.8.1 Outdoor Unit

RXYQ96MTJU

General Information 125

Page 132: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

7.8.2 Indoor Unit

FXFQ 12M / 18M / 24M / 30M / 36MVJUFXSQ 12M / 18M / 24M / 30M / 36M / 48MVJUFXMQ 30M / 36M / 48MVJUFXHQ 12M / 24M / 36MVJUFXAQ 12M / 18M / 24MVJUFXLQ 12M / 18M / 24MVJUFXNQ 12M / 18M / 24MVJU

R1T : Thermistor for suction air temperatureR2T : Thermistor for liquid line temperatureR3T : Thermistor for gas line temperature

C: DU220-602J

Heat exchangerGas piping connection port

Liquid piping connection port

(Flare connection)

Flare connection : φ5/8 or lessAttached piping : Above φ3/4

Fan

R3T

R1T

Electronicexpansion valve

Filter Filter

R2T

(mm)

Capacity GAS Liquid

12 / 18M φ1/2 φ1/4

24 / 30 / 36 / 48M φ5/8 φ3/8

126 General Information

Page 133: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

7.9 Wiring Diagrams7.9.1 Outdoor Unit

RXYQ96MTJU

General Information 127

Page 134: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

7.9.2 Field Wiring

RXYQ96M

C:3

D04

2647

A

128 General Information

Page 135: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

RXYQ192MTJU

C:3

D05

0353

General Information 129

Page 136: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

7.10 Bad Examples and Good Examples in Installation7.10.1 Example 1: Signal interference due to use of multiple core cable (all

model)

Situation Although for the purposes of group control there are only 2 units per group there are transmission malfunctions between the indoor units and the remote controller and the remote controller’s address display is showing non-existent addresses such as 13 or 15.

Source of Problem and Remedial Action

Multiple core cable has been used for at least part of the interconnecting wiring between the remote controller and the indoor units.This has resulted in signal interference leading to a transmission malfunction.

The multiple core cable was replaced by twin core cable and the fault disappeared.

Main Points Although twin core cable had been run from each unit, multiple core cable was used on the way.In schools, etc., because remote controllers are often installed in a single first floor control room, it is easier to use a multi-core cable.Signal interference can result in non-existent addresses appearing on the display.

130 General Information

Page 137: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

7.10.2 Example 2: Mismatch between cables connecting indoor and outdoor units and corresponding piping. (all model)

Situation The remote controller is not showing any malfunction and the system is operating but there is no flow of warm air from the indoor unit (in heating mode).

Source of Problem and Remedial Action

The connecting cables and the corresponding piping were not correctly matched.Recabling was carried out and the fault disappeared.

Main Points Special care must be taken when the pipework and cabling are carried out by different people.Run each indoor unit in turn to check that the system is correctly matched.

General Information 131

Page 138: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

7.10.3 Example 3: Drain pipe trap shape defective

Situation Indoor unit was fitted with a drain trap but a leak occurred during subsequent operation.

Source of Problem and Remedial Action

The trap was not properly shaped thus preventing it from functioning effectively as a trap and resulting in drain leakage. The trap was reshaped and the fault disappeared.

Main Points Duct types (18~48) require a drain trap.Reason: There is resistance on the air inlet side caused by the heat exchanger and air filter and this in turn creates negative pressure in relation to the atmospheric pressure on the discharge side. If there is no drain trap then air will be drawn in from the drain pipe and the waste water splashed around giving rise to the risk of water overflowing from the drain pan. To avoid this problem it is therefore necessary to design a trap which takes account of the maximum negative pressure which is likely to be created on the suction side.

132 General Information

Page 139: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

7.10.4 Example 4: Pressure down despite absence of leaks during air tight test (all model)

Situation In order to carry out local air tight tests on the refrigerant piping the system was pressurized via the liquid pipe service port and after 24 hours the pressure was found to have fallen. The local refrigerant piping alone does not lose any pressure. Maybe the gas leak is supposed to be located in the indoor unit itself.

Source of Problem and Remedial Action

The system was pressurized from the liquid pipe side and the gas pipes were therefore not pressurized. The system was then left under pressure for 24 hours but during that time gas leaked through into the gas pipes due to internal leaks within electronic expansion valves and the gas pressure inside the liquid pipes consequently dropped.

Main Points When carrying out air tight tests on local pipework it is essential that the system be pressurized via both the liquid pipes and the gas pipes.

Heat exchanger

Fan

Electronicexpansion valveFilter Filter

Indoor unit

General Information 133

Page 140: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

7.10.5 Example 5: Excessive noise due to incorrect angling of REFNET joints

Situation The noise of the refrigerant flow during defrosting is excessive.

Source of Problem and Remedial Action

The angle of the fittings was incorrect and needed to be rectified as shown in the following figure.

1. REFNET jointsThe REFNET joints should be installed such that branches meet the main pipe either horizontally or vertically at an angle of exactly 90 degrees.

2. REFNET headerThe REFNET header is a lateral flow pipe and should be fitted so as to allow horizontal branch fittings. (Vertical or sloping fitting is not permissible.)

Main Points Reasons for using refrigerant branch kitFittings of REFNET joints or headers which are not carried out in strict accordance with the principles outlined here may result in complaints relating, for example, to "poor performance" of the system or "noisy refrigerant flow". (To prevent unbalance flow or oil shortage)

134 General Information

Page 141: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

7.10.6 Example 6: Cracks develop in field pipes due to thermal expansion and contraction

Situation Refrigerant piping has developed cracks in soldered points and is leaking gas.

Cause Both ends of the pipe have been tightly fixed in place.↓Starting and stopping the compressor has caused temperature to vary, thus the pipes have expanded and contracted which places stress on soldered parts.↓Cracks have formed because of repeated expansion and contraction.

Remedial Action Fit the pipe with a loop as shown in the below drawing.

Main Points Take thermal expansion and contraction along the spline into consideration when installing pipe supports.

For Your Reference

Expansion (m) = Full length × Coefficient of thermal expansion × Rise in temperatureCoefficient of thermal expansion for copper: 16.5 × 10-6

Example For a pipe length of 10m and a rise in temperature of 50°C, expansion reaches 8.2mm.

General Information 135

Page 142: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

7.10.7 Example 7: Transmission wiring between the cool/heat selector and the outdoor unit is too close to a high voltage wire.

Situation Heating is indicated despite having selected cooling with the cool/heat selector.

Cause and Remedial Action

The transmission wiring between the cool/heat selector and the outdoor unit is too close to a high voltage wire. An induced voltage is, therefore, being impressed on the transmission wiring which is causing a heating/cooling malfunction in the outdoor unit PC board.

Bypassing the transmission wiring will allow the unit to function normally.

Main Points Keep low and high voltage wiring away from each another.

7.10.8 Example 8: The centralized control group number cannot be set (Inverter K Series).

Situation An attempt was made to set the centralized control group number with the indoor unit remote controller, but "00" cannot be selected in the field setting mode.

Cause 1. The central remote controller or unified ON/OFF controller is OFF.2. The central remote controller or unified ON/OFF controller, or indoor unit is not wired to the centralized

control line (F1 & F2).

Remedial Action Supply power to either the central remote controller or unified ON/OFF controller. Wire the central remote controller or unified ON/OFF controller, or indoor unit to the centralized control line.

136 General Information

Page 143: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Appendix

Main Points When communications with the central remote controller are down, "00" cannot be selected in the field setting mode.Activate power to the central remote controller, unified ON/OFF controller and indoor unit before setting the centralized control group number.

7.10.9 Example 9: "88" cannot be cleared from the central remote controller.

Situation The display on the central remote controller does not change from its initial state after turning power ON.

Initial display of the central remote controller

Cause 1. None of the indoor units connected to the central remote controller have been given a group No.2. The connector for setting the master controller inside the central remote controller is disconnected.

Remedial Action Set a centralized control group No. for each indoor unit with the respective remote controllers.Connect the connector for setting the master controller in one of the central remote controller.

Main Points If the setting for master controller has been changed, reset the power to the unit at the ON/OFF switch or the forced reset switch of the controller.Activate power to the central remote controller, unified ON/OFF controller and indoor unit before setting the centralized control group No.For details on how to set the centralized control group number, refer to the installation manual.

General Information 137

Page 144: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Appendix SiUS39-504

138 General Information

Page 145: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

Installation Manual Outdoor Unit 139

Part 2Part 2Part 2Part 2Installation ManualInstallation ManualInstallation ManualInstallation Manual

Outdoor UnitOutdoor UnitOutdoor UnitOutdoor Unit1. Introduction .............................................................................................144

1.1 Combination ............................................................................................. 1441.2 Standard Operation Limit ......................................................................... 1441.3 Standard Supplied Accessories ............................................................... 1451.4 Option Accessory ..................................................................................... 1451.5 Technical Specifications........................................................................... 1461.6 Electrical Specifications............................................................................ 146

2. Main Components ...................................................................................1473. Selection of Location...............................................................................1484. Inspecting and Handling the Unit ............................................................1505. Unpacking and Placing the Unit ..............................................................1516. Refrigerant Piping ...................................................................................152

6.1 Selection of Piping Material...................................................................... 1526.2 Connecting the Refrigerant Piping ........................................................... 1526.3 Example of Connection ............................................................................ 1576.4 Leak Test and Vacuum Drying ................................................................. 1596.5 Pipe Insulation.......................................................................................... 1616.6 Additional Refrigerant Charge .................................................................. 162

7. Field Wiring .............................................................................................1647.1 Optional Parts Cool/Heat Selector ........................................................... 1647.2 Power Circuit and Cable Requirements ................................................... 1647.3 General..................................................................................................... 1657.4 Examples.................................................................................................. 165

8. Before Operation.....................................................................................1718.1 Checks before Initial Start-up ................................................................... 1718.2 Test Run................................................................................................... 171

9. Caution for Refrigerant Leaks .................................................................174

[Applicable model]RXYQ96MTJURXYQ192MTJU

3P114261-6D EM03A046

Page 146: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

Please read these "SAFETY CONSIDERATIONS" carefully before installing air conditioning equipment and be sure to install it correctly. After completing the installation, make sure that the unit operates properly during the start-up operation.Please instruct the customer on how to operate the unit and keep it maintained.Also, inform customers that they should store this installation manual along with the operation manual for future reference.This air conditioner comes under the term "appliances not accessible to the general public".

Meaning of warning, caution and note symbols.

Warning ....Indication a potentially hazardous situation which, if not avoided, could result in death or serious injury.

Caution .....Indication a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be sued to alert against unsafe practices.

Note...........Indication situation that may result in equipment or property-damage-only accidents.

140 Installation Manual Outdoor Unit

Page 147: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

Warning Ask your dealer or qualified personnel to carry out installation work. Do not try to install the machine by yourself.Improper installation may result in water leakage, electric shocks or fire.Perform installation work in accordance with this installation manual.Improper installation may result in water leakage, electric shocks or fire.When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage.Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency.Be sure to use only the specified accessories and parts for installation work.Failure to use the specified parts may result in water leakage, electric shocks, fire or the unit falling.Install the air conditioner on a foundation strong enough to withstand the weight of the unit.A foundation of insufficient strength may result in the equipment falling and causing injuries.Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.Improper installation work may result in the equipment falling and causing accidents.Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel according to local laws and regulations and this installation manual.An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.Make sure that all wiring is secured, the specified wires and used, and no external forces act on the terminal connections or wires.Improper connections or installation may result in fire.When wiring the power supply and connecting the remote controller wiring and transmission wiring, position the wires so that the electric parts box lid can be securely fastened.Improper positioning of the electric parts box lid may result in electric shocks, fire or the terminals overheating.If the refrigerant gas leaks during installation, ventilate the area immediately.Toxic gas may be produced if the refrigerant gas comes into contact with fire.After completing the installation work, check that the refrigerant gas does not leak.Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.Before touching electrical parts, turn off the unit.Ground the air conditioner. Do not connect the ground wire to gas or water pipes, lightning rod or a telephone ground wire.Incomplete grounding may result in electric shocks.Securely install the outdoor unit terminal cover (panel).If the terminal cover (panel) is not installed properly, dust or water may enter the outdoor unit and fire or electric shock may result. When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the specified refrigerant (R-410A), such as air.Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.Do not reconstruct or change the settings of the protection devices.If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by Daikin are used, fire or explosion may result.Do not touch the switch with wet fingers.Touching a switch with wet fingers can cause electric shock. Install an leak circuit breaker, as required. If an leak circuit breaker is not installed, electric shock may result.

Installation Manual Outdoor Unit 141

Page 148: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

Caution While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation.Improper drain piping may result in water leakage and property damage.Do not touch the heat exchanger fins.Improper handling may result in injury.Be very careful about product transportation.Safely dispose of the packing materials.Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.Tear apart and throw away plastic packaging bags so that children will not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.Do not touch the refrigerant pipes during and immediately after operation.During and immediately after operation, the refrigerant pipes are may be hot and may be cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.Do not turn off the power immediately after stopping operation. Always wait at least five minutes before turning off the power. Otherwise, water leakage and trouble may occur.Do not use a charging cylinder.Using a charging cylinder may cause the refrigerant to deteriorate.

Note Install the indoor and outdoor units, power supply wiring and connecting wires at least 3.5ft. away from televisions or radios in order to prevent image interference or noise.(Depending on the radio waves, a distance of 3.5ft. may not be sufficient enough to eliminate the noise.)This unit is a class A product.In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.Dismantling of the unit, treatment of the refrigerant, oil and eventual other parts, should be done in accordance with the relevant local and national regulations.Do not use the following tools that are used with conventional refrigerants. (Gauge manifold, charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment.)If the conventional refrigerant and refrigerator oil are mixed in the R-410A, the refrigerant may deteriorated.Never perform outdoor unit piping connection work when it is raining.

Caution The refrigerant R-410A requires strict cautions for keeping the system clean, dry and tight.A.Clean and dryForeign materials (including mineral oils such as SUNISO oil or moisture) should be prevented from getting mixed into the system.B.TightR-410A does not contain any chlorine, does not destroy the ozone layer, and does not reduce the earth’s protection against harmful ultraviolet radiation.R-410A can contribute slightly to the greenhouse effect if it is released. Therefore we should take special attention to check the tightness of the installation.Read the chapter "Refrigerant piping work" carefully and follow these procedures correctly.

142 Installation Manual Outdoor Unit

Page 149: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

Caution Since R-410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. (If the refrigerant is charged in a state of gas, its composition changes and the system will not work properly.)The indoor unit is for R-410A. See the catalog for indoor unit models which can be connected.(Normal operation is not possible when connected to other units.)

Caution Do not allow children to mount on the outdoor unit, or avoid placing any object on it. Falling or tumble may result in injury.⟨⟨⟨⟨Safety Precaution⟩⟩⟩⟩The PCI Data Station is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.

Installation Manual Outdoor Unit 143

Page 150: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Introduction SiUS39-504

1. IntroductionThis installation manual concerns VRV inverters of the Daikin RXYQ-M series. These units are designed for outdoor installation and used for cooling and heatpump applications. The RXYQ-M units can be combined with Daikin VRV series indoor units for air conditioning purposes.The present installation manual describes the procedures for unpacking, installing and connecting the RXYQ-M units. Installation of the indoor units is not described in this manual. Always refer to the installation manual supplied with these units for their installation.

1.1 CombinationThe indoor units can be installed in the following range.

Always use appropriate indoor units compatible with R-410A.To lean which models of indoor units are compatible with R-410A, refer to the product catalogs.Total capacity/quantity of indoor units⟨Outdoor unit⟩ ⟨Total capacity of indoor units⟩ ⟨Total quantity of indoor units⟩RXYQ96MTJU ...................48 ~ 120 10 unitsRXYQ192MTJU .................96 ~ 240 20 units

1.2 Standard Operation LimitThe figures below assume following operating conditions for indoor and outdoor units:

Equivalent pipe length...........................................................25ft.Level difference.......................................................................0ft.

Cooling Heating

A Outdoor temperature (°FDB)B Indoor temperature (°FWB)C Outdoor temperature (°FWB)D Indoor temperature (°FDB)

Range for continuous operationRange for pull down operationRange for warming up operation

5

10

30

41

50

60

70

50 60 70 80 90

20

40

D

C

23

30

40

50

60

70

80

90

100

605750 70 77 80 90 B

110

A

40

144 Installation Manual Outdoor Unit

Page 151: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Introduction

1.3 Standard Supplied Accessories

1.4 Option AccessoryTo install the above outdoor units, the following optional parts are also required.

Refrigerant branching kit (For R-410A only: Always use an appropriate kit dedicated for your system.)

Outdoor unit multi connection piping kit (For R-410A only: Always use an appropriate kit dedicated for your system.)

∗ To select an optimum refrigerant branching kit, refer to "6. Refrigerant Piping".

Q96 type

Name Clamp (1) Clamp (2) Clamp (3)Gas line

piping attached to unit (1)

Quantity 9 pcs. 2 pcs. 1 pc. 1 pc.

Shape

Small Large

NameGas line

piping attached to unit (2)

Gas line piping attached to

unit (3)Vinyl tube Others

Quantity 1 pc. 1 pc. 1 pc. Operation manualInstallation manualAdditional refrigerant charge label

Shape

1

2

1. Operation manual Installation manual Clamp

2. Attached pipe

REFNET header KHRP26M22H KHRP26M33H KHRP26M72HREFNET joint KHRP26M22T KHRP26M33T KHRP26M72TU

Number of outdoor units connected 2 unitsKit name BHFP22M90U

Installation Manual Outdoor Unit 145

Page 152: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Introduction SiUS39-504

1.5 Technical Specifications

(1) Refer to the engineering data book for the complete list of specifications.(2) The nominal cooling capacity is based on: - indoor temperature: 80°FDB / 67°FWB

- outdoor temperature: 95°FDB- pipe length: 25ft.- level difference: 0ft.

(3) The nominal heating capacity is based on: - indoor temperature: 47°FDB- outdoor temperature: 70°FDB / 60°FWB- pipe length: 25ft.- level difference: 0ft.

(4) The nominal input includes total input of the unit: compressor, fan motor and control circuit.

1.6 Electrical Specifications

Model RXYQ96MTJU RXYQ192MTJUGeneralNominal cooling capacity (2) (MBh) 96.0 192.0Nominal heating capacity (3) (MBh) 108.0 216.0Nominal input cooling / heating (4) (kW) 8.67 / 9.19 17.34 / 18.38

Dimensions HWD (inch) 64 48-7/8 30-1/8 (64 48-7/8 30-1/8)+(64 48-7/8 30-1/8)

Mass (Ib.) 650 650 + 650Connectionsrefrigerant gas pipe (inch) 7/8 1-1/8refrigerant liquid pipe (inch) 3/8 5/8CompressorOil type Synthetic(ether)oilOil charge volume (I) 1.9+1.6 (1.9+1.6)+(1.9+1.6)Crankcase heater (W) 33+33 (33+33)+(33+33)Refrigerant type R-410ARefrigerant charge (Ib.) 25.1 25.1+25.1CondenserNominal air flow (m3/min) 7400 7400+7400Fan motor output (W) 750 750 2

Model RXYQ96MTJU RXYQ192MTJU

Power supply

Phase 3~ 3~Frequency (Hz) 60 60Voltage (V) 208-230 208-230Voltage torerance (%) ±10 ±10Recommended fuses (A) 70 70+70

Compressor

Phase 3~ 3~Frequency (Hz) 60 60Voltage (V) 208-230 208-230Nominal running current (A) 10.1+13.1 (10.1+13.1) 2

Control and fan motor

TypeVoltage (V) 208-230 208-230Nominal running current (A) 4.5 4.5 2

146 Installation Manual Outdoor Unit

Page 153: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Main Components

2. Main ComponentsFor main components and function of the main components, refer to the Engineering Data Book.

Installation Manual Outdoor Unit 147

Page 154: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Selection of Location SiUS39-504

3. Selection of LocationThis unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment. If installed as a household appliance it could cause electromagnetic interference.The VRV OUTDOOR units should be installed in a location that meets the following requirements:1. The foundation is strong enough to support the weight of the unit and the floor is flat to prevent

vibration and noise generation.2. The space around the unit is adequate for servicing and the minimum space for air inlet and air

outlet is available. (refer to figure 1 and choose one of both possibilities)

3. There is no danger of fire due to leakage of inflammable gas.4. Ensure that water cannot cause any damage to the location in case it drips out the unit (e.g. in

case of a blocked drain pipe).5. The piping length between the outdoor unit and the indoor unit may not exceed the allowable

piping length. (see "Example of connection")6. Select the location of the unit in such a way that neither the discharged air nor the sound

generated by the unit disturb anyone.7. Make sure that the air inlet and outlet of the unit are not positioned towards the main wind

direction. Frontal wind will disturb the operation of the unit. If necessary, use a windscreen to block the wind.

≥3/8 ≥3/8≥3/8≥3/4

≥3/4

≥7 7/8

≥2≥2

≥2

≥7 7/8 ≥15 3/4 ≥15 3/4

≥2

≥3/8

B1 B1

≥11 3/4

A A

AA

B2 B2

H1

H2

≥3 7/8≥3 7/8

≥11 3/4

< If installed as a single unit >

(Pattern 1)

(Pattern 2)

(Pattern 3)

(Pattern 1)

(Pattern 2)

(Pattern 3)

< When installed in serial >

1

1

2

2

1 3

1

1

11 (in.)

A

B1

B2

H1≤59

H1=59+X

H2≤19 5/8

H2=19 5/8+Y

⇒ A≥19 5/8

⇒ A≥19 5/8+X/2

⇒ B1≥11 3/4

B2≥3 7/8

⇒ B1≥11 3/4+Y/2

B2≥3 7/8+Y/2

1. Front side2. No limit to wall height3. Suction side

148 Installation Manual Outdoor Unit

Page 155: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Selection of Location

Note 1. An inverter air conditioner may cause electronic noise generated from AM broadcasting. Examine where to install the main air conditioner and electric wires, keeping proper distances away from stereo equipment, personal computers, etc.

If the electric wave of AM broadcasting is particularly weak, keep distances of 10ft. or more and use conduit tubes for power and transmission lines.

2. In heavy snowfall areas, select an installation site where snow will not affect operation of the unit.

Warning 1. The refrigerant R-410A itself is nontoxic, nonflammable and is safe. If the refrigerant should leak however, its concentration may exceed the allowable limit depending on room size. Due to this it could be necessary to take measures against leakage. Refer to the chapter "Caution for refrigerant leaks".

2. Do not install in the following locations.Locations such as kitchens which contain a lot of mineral oil or steam in the atmosphere or where oil may splatter on the unit.Resin parts may deteriorate, causing the unit to fall or leak.Locations where sulfurous acids and other corrosive gases may be present in the atmosphere.Copper piping and soldered joints may corrode, causing refrigerant to leak.Locations where equipment that produces electromagnetic waves is found.The electromagnetic waves may cause the control system to malfunction, preventing normal operation.Locations where flammable gases may leak, where thinner, gasoline, and other volatile substances are handled, or where carbon dust and other incendiary substances are found in the atmosphere.Leaked gas may accumulate around the unit, causing an explosion.

≥60

5

3

1

42

2

(in.)

≥40

≥40

≥40

≥60

≥60

≥60

1. indoor unit2. Branch switch, overcurrent

breaker3. remote controller4. cool/heat selector5. personal computer or radio

Installation Manual Outdoor Unit 149

Page 156: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Inspecting and Handling the Unit SiUS39-504

4. Inspecting and Handling the UnitAt delivery, the package should be checked and any damage should be reported immediately to the carrier claims agent.When handling the unit, take into account the following:1. Fragile, handle the unit with care.

Keep the unit upright in order to avoid compressor damage.2. Choose the path along which the unit is to be brought in ahead of time.3. If a forklift it to be used, pass the forklift arms through the large openings on the bottom of the

unit.4. Lift the unit preferably with a crane and 2 belts of at least 27ft. long.5. When lifting the unit with a crane, always use protectors to prevent belt damage and pay

attention to the position of the unit’s centre of gravity. 6. After installation, remove the transport clasps attached to the large openings.7. Bring the unit as close to its final installation position in its original package to prevent damage

during transport.

6

3

< 5 >

< 7 >

3

4

1

2

8

1. Packaging material2. Forklift3. Belt sling4. Wear plate5. Removal of shipping brackets6. Shipping bracket (Remove the

screws.)7. Removal of corrugated paper8. Corrugated paper

150 Installation Manual Outdoor Unit

Page 157: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Unpacking and Placing the Unit

5. Unpacking and Placing the UnitMake sure the unit is installed level on a sufficiently strong base to prevent vibration and noise.Secure the unit to its base using foundation bolts. (Use four commercially available M12-type foundation bolts, nuts, and washers.)The foundation bolts should be inserted 13/16".Make sure the base under the unit supports the unit over an area of at least the base leg widths (2-5/8”).The height of the base should be at least 5-7/8” from the floor.The unit must be installed on a solid longitudinal foundation (steelbeam frame or concrete) as indicated in the figure below.

DO NOT USE STANDS TO SUPPORT THE CORNERS

Note 1. Prepare a water drainage channel around the foundation to condensate waste water from around the unit.

2. If the unit is to be installed on a roof, check the strength of the roof and its drainage facilities first.

3. If the unit is to be installed on a frame, install the waterproofing board within a distance of 5-14/16" under the unit in order to prevent infiltration of water coming from under the unit.

Note When installing on a roof, make sure the roof floor is strong enough and be sure to water-proof all work.Make sure the area around the machine drains properly by setting up drainage grooves around the foundation.(Condensate water is sometimes discharged from the outdoor unit when it is running.)Block all gaps in the holes for passing out piping and wiring using sealing material (locally procured).(Small animals may enter the machine.)

Ex: passing piping out through the front

Model A (in.) B (in.)

Q96 type 48 13/16 43 3/8

13/1

6”

(in.)

28 7

/16-

29

2 5/

8

2 5/

8

30 1

/8

AB

2 5/

8 (

4 )

1

2

3

1. Foundation bolt point (φ9/16” dia. : 4 positions)

2. Depth of product3. Shape of outdoor unit’s support

leg and foundation bolt positions

4. Base leg width

≥4

2≥4

≥4

≥4

12

≥4≥4

1. Do not use stands to support for corners.

2. Center position of unit.

1

2 3

1. Plug the areas marked with " ". (When the piping is routed from the front panel.)

2. Gas side piping3. Liquid side piping

Installation Manual Outdoor Unit 151

Page 158: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Refrigerant Piping SiUS39-504

6. Refrigerant PipingNote After completing installation, be sure to open the valve.

(See 6.6 Additional refrigerant charge for details) (Operating the unit with the valve shut will break the compressor.)Use R-410A to add refrigerant. (The R-410A refrigerant cylinder has a pink stripe painted around it.)All field piping must be installed by a licensed refrigeration technician and must comply with relevant local and national regulations.CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPINGDo not use flux when brazing copper-to copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filter metal(BCuP) which does not require flux. (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil.)

Notes: Use R-410A only when adding refrigerant.Installation tools:Make sure to use installation tools (gauge manifold charge hose, etc.) that are exclusively used for R-410A installations to withstand the pressure and to prevent foreign materials (e.g. mineral oils such as SUNISO and moisture) from mixing into the system.(The screw specifications differ for R-410A.)Vacuum pump (use a 2-stage vacuum pump with a non-return valve):1.Make sure the pump oil does not flow oppositely into the system while the pump is not

working.2.Use a vacuum pump which can evacuate 14.6 psi.

6.1 Selection of Piping Material1. Foreign materials inside pipes (including oils for fabrication) must be 30mg/10m or less.2. Use the following material specification for refrigerant pipping:

construction material: Phosphoric acid deoxidized seamless copper for refrigerant.size: Determine the proper size referring to chapter "Example of connection".The wall thickness of the refrigerant piping should comply with relevant local and national regulations.

3. Make sure to use the particular branches of piping that have been selected referring to chapter "Example of connection".

4. Select the piping material to be used from the next table according to piping size.

6.2 Connecting the Refrigerant Piping1. The local branch piping can be connected either forward or to the sides (taken out of the

bottom) as shown in the figure.

Piping Size (O/D) Temper grade of Material

φ15.9 or less O

φ19.1 or more 1/2 H or H

1 2 3

1. Left-side connection2. Front connection3. Right-side connection

152 Installation Manual Outdoor Unit

Page 159: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Refrigerant Piping

[One outdoor unit installed]Front connection:Remove the shutoff valve cover to connect.

Side (bottom) connection:Remove the knock holes on the bottom frame and route the piping under the bottom frame.

[When multiple outdoor units installed]To connect the piping between outdoor units, an optional piping kit (multi connection piping kit) is always required. When installing the piping, follow the instructions in the installation manual that comes with the kit.

Front connection:Remove the stop valve cover to connect.

Side (bottom) connection:Remove the knockout holes on the bottom frame and route the piping under the bottom frame.

(1) 2 56

7

8

9

3

4 (1)(2)(3)

1. Front connection:2. Remove the shutoff valve cover to connect.3. Flange: 4. Gas side accessory pipe (1) (2) (3)5. Oil-equalizing piping shutoff valve6. No piping work is needed.7. Flare nut8. Brazing9. Liquid side piping (field supply)10.Side (bottom) connection:11.Remove the knock holes on the bottom frame and route the piping

under the bottom frame.12.Knockout hole13.Punch the knock holes.14.Liquid side piping (field supply)

3

4 (1)(3)(2)

9

14

(10) 11 56 7

12

138

( 1 ) 23 7

5

8

15

9

4 (1)(2)(3)

1. Front connection2. Remove the stop valve cover to connect.3. Flange 4. Gas side accessory pipe (1) (2) (3)5. Oil-equalizing piping stop valve6. No piping work is needed.7. Flare nut8. Brazing9. Liquid side piping (field supply)10.Side (bottom) connection11.Remove the knockout holes on the bottom frame and route the

piping under the bottom frame.12.Knockout hole13.Punch the knockout hole.14.Gas side piping (field supply)15.Oil-equalizing piping (field supply)

3

8

9

4 (1)(3)

( 10 ) 11 7

12

13

15

5

Installation Manual Outdoor Unit 153

Page 160: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Refrigerant Piping SiUS39-504

Note Be sure to use the attached pipe when carrying out piping work in the field.Be sure that the local piping does not touch other pipes, the bottom panel or side panel. Especially for the bottom and side connection, be sure to protect the local piping with the provided insulation, to prevent it from coming into contact with the casing.

Precautions when knocking out knock holesBe sure to avoid damaging the casingAfter knocking out the holes, we recommend you paint the edges and areas around the edges using the repair paint to prevent rusting.When passing electrical wiring through the knock holes, wrap the wiring with protective tape to prevent damage.Open knock holes around the 4 concave knock holes in the base frame, using a φ1/4"-bit drill.

2. Make sure to perform the piping installation within the range of the maximum allowable pipe length, allowable level difference and allowable length after branching as indicated in chapter "Example of connection"

3. For installation of the refrigerant branching kit, refer to the installation manual delivered with the kit.Mount the REFNET joint so that it branches either horizontally or vertically.

4. Pipe connectionOnly use the flare nuts included with the unit.Using different flare nuts may cause the refrigerant to leak.Be sure to perform a nitrogen blow when brazing.(Brazing without performing nitrogen replacement or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes, adversely affecting valves and compressors in the refrigerating system and preventing normal operation.)Do not use a flux when brazing the refrigerant pipe joints.Use phosphor copper brazing (BCup) which does not require flux.(Using a chlorine flux may cause the pipes to corrode, and if it contains fluoride it may cause the refrigerant lubricant to deteriorate, adversely affecting the refrigerant piping system.)

Notes: The pressure regulator for the nitrogen released when doing the brazing should be set to 2.9 psi or less.

1 2

3

1. Knock hole2. Drill3. Concave section

A1

A-arrow diagram

2

B3

B-arrow diagram

Mount the REFNET header so that it branches horizontally.

1. (Horizontal line)2. (Up to ±30° or vertically.)

3. (Horizontal line)

1 2 4 5 6

3

7

1. Refrigerant piping2. Location to be brazed3. Nitrogen4. Taping5. Manual valve6. Regulator7. Nitrogen

154 Installation Manual Outdoor Unit

Page 161: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Refrigerant Piping

5. Protection against contamination when installing pipesTake measures to prevent foreign materials like moisture and contamination from mixing into the system.

Great caution is needed when passing copper tubes through walls.

Precautions when selecting branch piping.If the piping between the outdoor units is 295ft. or longer, be sure to enlarge the main pipe in the liquid-side and gas-side branch piping.Depending on the length of the refrigerant piping, the power may drop, but even in such cases it is ok to enlarge the main pipe.

[Gas side]RXYQ96MTJU: ........................ φ7/8”→ φ1”RXYQ192MTJU: ...................... φ1-1/8”→ φ1-1/4”

[Liquid side]RXYQ96MTJU: ........................ φ3/8”→ φ1/2”RXYQ192MTJU: ...................... φ5/8”→ φ3/4”

Place Installation period Protection method

OutdoorMore than a month Pinch the pipeLess than a month

Pinch or tape the pipeIndoor Regardless of the period

1 2

4

53

1. Outdoor unit2. Main pipe3. Enlarge4. The first refrigerant

branching kit.5. Indoor unit

Installation Manual Outdoor Unit 155

Page 162: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Refrigerant Piping SiUS39-504

156 Installation Manual Outdoor Unit

Page 163: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Refrigerant Piping

Installation Manual Outdoor Unit 157

6.3 Example of Connection

One outdoor

unit installed

Branch with REFNET joint Branch with REFNET joint and REFNET header Branch with REFNET header

aA B C D E F G

A B C D E F G

b c d e f g

h i j k l m n1 2 3 4 5 6 7

8H2

H1P

Outdoor unit REFNET joint ( - )

Indoor units ( - )

H1

H1

H2

H2

a ai

b

ai

b

c d e f g h1 2 3 4 5 6

Outdoor unit

Outdoor unit

REFNET joint ( )

Indoor units ( - )

c d e f g h1 2 3 4 5 6

Indoor units ( - )

REFNET header

REFNET header

kj

7 8

kj

7 8

H1

H2

H2

Outdoor unit REFNET header

Indoor units ( - )

c d e f g hi

i

b1 2 3 4 5 6 7

8

8

a b c d e f g

8

H2

H1

H3 H3

P

Indoor units ( - )

Outdoor unitREFNET joint ( - )

REFNET joint ( )

h i j k l m n1 2 3 4 5 6 7

First outdoor

branch

H1

H3

a

Outdoor unitREFNET header

Indoor units ( - )

c d e f g hb1 2 3 4 5 6 7

Multiple outdoor

units installed

∗ In case of multiple outdoor units installed, re-read to

the first outdoor branch as seen from the indoor unit.

Maximumallowablelength

Between outdoorand indoor units

Between outdoor branch and indoor unit(Only for multiple outdoor units)

Between outdoor and indoor units

Between indoor and indoor units

Between outdoor and outdoor units

Actual pipe length

Actual pipe length

Actual pipe length

Difference in height

Difference in height

Difference in height

Equivalent length

Total extension length

Pipe length between outdoor and indoor units ≤ 330ft.

Example unit 8: a + b + c + d + e + f + g + p ≤ 330ft.

Example unit 8: b + c + d + e + f + g + p ≤ 130ft.

Equivalent pipe length between outdoor and indoor units ≤ 390ft. (assume equivalent pipe length of REFNET joint to be 1.6ft., that of REFNET header to be 3.3ft. calculation purposes)

Piping length from outdoor branch to outdoor unit ≤ 33ft. Approximately length: max 43ft.

Difference in height between outdoor and indoor units (H1) ≤ 164ft. (Max 130ft. if the outdoor unit is below)

Difference in height between adjacent indoor units (H2) ≤ 49ft.

Difference in height between outdoor unit (main) and outdoor unit (sub) (H3) ≤ 16ft.

Pipe length from first refrigerant branch kit (either REFNET joint or REFNET header ) to indoor unit ≤ 130ft.

Total piping length from outdoor unit* to all indoor units ≤ 950ft.

Allowableheightlength

Allowable length after the branch

Refrigerant branch kit selection

Pipe size selection

Example unit 8: a + i ≤ 330ft.Example unit 6: a + b + h ≤ 330ft., unit 8: a + i + k ≤ 330ft.

Example unit 8: i ≤ 130ft.Example unit 6: b + h ≤ 130ft., unit 8:i + k ≤ 130ft.

r

t

Outdoor unit

r ≤ 33ft. (Approximately length: max 43ft.)

t ≤ 33ft. (Approximately length: max 43ft.)

Refrigerant branch kits can only be

used with R-410A.

How to select the REFNET joint

When using REFNET joints at the first branch counted from the outdoor unit side, choose from the following table

in accordance with the capacity of the outdoor unit.

Piping between outdoor units and refrigerant branch kit (part A)

Match to the size of the connection piping on the outdoor unit.

Outdoor unit connection piping size

Piping between refrigerant branch kitsChoose from the following table in accordance with the total capacity of all theindoor units connected below this.

Do not let the connection piping exceed the refrigerant piping size chosen bygeneral system model name.

How to calculate the additional refrigerant

to be charged

If a negative result is gotten for R from the formula at right, no refrigerant

needs to be added.

Additional referigerant to be charged R (lb.)

R should be rounded off in units of 0.1 (lb.).

Piping between outdoor

branch and outdoor unit (part B)

Oil-equalizing line (part C)

Piping between outdoor units and refrigerant

branch kit (part A)

RXYQ96

RXYQ192

KHRP26M33T

KHRP26M72TU

For REFNET joints other than the first branch, select the proper branch kit model based on the total capacity

index.

< 72

72 ≤ x < 111

111 ≤

KHRP26M22T

KHRP26M33T

KHRP26M72TU

How to select the REFNET header

Choose from the following table in accordance with the total capacity of all the indoor units connected below the REFNET

header.

< 72

< 111

111 ≤

KHRP26M22H (Max. 4 kit)

KHRP26M33H (Max. 8 kit)

KHRP26M72H (Max. 8 kit)

In case of multiple outdoor units installed, use outdoor branch kit.

2 units BHFP22M90U

example in case of REFNET joint C; indoor units 3 + 4 + 5 + 6 + 7 + 8example in case of REFNET joint B indoor units 7 + 8,

example in case of REFNET header; indoor units 1 + 2 + 3 + 4 + 5 + 6example in case of REFNET header; indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8Example of downstream indoor units

RXYQ96

RXYQ192

φ7/8φ1-1/8

φ3/8φ5/8

Gas pipeindoor capacity index

Piping size

Liquid pipe

φ3/8

φ1/2φ5/8

< 72

72 ≤ x < 111

111 ≤ x < 156

156 ≤

φ5/8φ7/8

φ1-1/8

Between refrigerant branch kit and indoor unit

Pipe size for direct connection to indoor unit must be the same as the

connection size of indoor unit.

φ1/4φ3/8

12, 18 type

24, 30, 36, 48 type

φ1/2φ5/8

Piping between outdoor branch and outdoor unit (part B)

Gas pipeoutdoor capacity type

Piping size

Liquid pipe

φ3/8RXYQ96 φ7/8

a: φ3/4 × 100ft.

b: φ5/8 × 30ft.

c: φ3/8 × 30ft.

d: φ3/8 × 30ft.

e: φ3/8 × 30ft.

f : φ3/8 × 30ft.

g: φ1/4 × 30ft.

h: φ1/4 × 70ft.

i : φ1/2 × 30ft.

j : φ1/4 × 30ft.

k: φ1/4 × 25ft.

Oil-equalizing line (Only for multiple outdoor units installed) (part C)

φ1/4Piping size

(Unit: in.)

(Unit: in.)

(Unit: in.)

(Unit: in.)

(Unit: in.)

R= +

indoor capacity index Refrigerant branch kit name

Number of outdoor units Branch kit name

Outdoor unit capacity type Refrigerant branch kit name

indoor capacity index Refrigerant branch kit name

Gas pipeOutdoor unit capacity type

Piping size

Liquid pipe

Gas pipeindoor capacity type

Piping size

Liquid pipe

+ +

+ + _

If the outdoor unit isRXYQ192 units and thepiping lengths are as atright

R= 100 0.168 + 30 0.014 + 30 0.074 + 120 0.036 + 155 0.015 - 6.6 =22.485

ba c+d+e+f g+h+j+ki 22.5

NOTE:

Total length (ft.)of liquid pipingsize at φ7/8

×0.235

Total length (ft.)of liquid pipingsize at φ3/4

×0.168

Total length (ft.)of liquid pipingsize at φ5/8

×0.114

Total length (ft.)of liquid pipingsize at φ1/2

×0.074

Total length (ft.)of liquid pipingsize at φ3/8

×0.036

Total length (ft.)of liquid pipingsize at φ1/4

×0.015

Model name

RXYQ96

RXYQ192

0 lb.

6.6 lb.

Amount of refrigerant

Example for refrigerant branch using REFNET joint and REFNET header for RXYQ192

A B

A B

Caution

The thickness and material shall be selected in accordance with local code.

For an outdoor unit multi installation, make the settings in accordance with the

following figure.

A G

1 8 1 8

1 8

A B

A B

1 8

indoor unit

REFNET joint

REFNET header

1

A

A G

1 81 8

Page 164: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Refrigerant Piping SiUS39-504

158 Installation Manual Outdoor Unit

Page 165: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Refrigerant Piping

6.4 Leak Test and Vacuum DryingThe units were checked for leaks by the manufacturer.Confirm that the valves are firmly closed before pressure test or vacuuming.To prevent entry of any impurities and insure sufficient pressure resistance, always use the special tools dedicated for R-410A.

Air tight test and vacuum dryingAir tight test: Make sure to use nitrogen gas.(For the service port location, refer to the "Caution" label attached on the front panel [right] of the outdoor unit.)

Pressurize the liquid and gas pipes to 551 psi (do not pressurize more than 551 psi). If the pressure does not drop within 24 hours, the system passes the test. If the pressure drops, check where the nitrogen leaks from.Vacuum drying: Use a vacuum pump which can evacuate to –14.6 psi.1.Evacuate the system from the liquid and gas pipes by using a vacuum pump for more than 2

hours and bring the system to –14.6 psi. After keeping the system under that condition for more than 1 hour, check if the vacuum gauge rises or not. If it rises, the system may either contain moisture inside or have leaks.

2.Following should be executed if there is a possibility of moisture remaining inside the pipe (if piping work is carried out during the raining season or over a long period of time rainwater may enter the pipe during work).After evacuating the system for 2 hours, pressurize the system to 7.25psi (vacuum break) with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to –14.6 psi (vacuum drying). If the system cannot be evacuated to –14.6 psi within 2 hours, repeat the operation of vacuum break and vacuum drying.Then, after leaving the system in vacuum for 1 hour, confirm that the vacuum gauge does not rise.

Notes: Make sure to perform airtightness test and vacuum drying using the service ports of the shutoff valve shown in the table on the bellow.

Shutoff Valve Operation Procedure

IntroductionConfirm the sizes of the shutoff valves connected to the system referring to the table on the below.

Opening Shutoff Valve

1. Remove the cap and turn the valve counterclockwise with the hexagon wrench (JISB4648).2. Turn it until the shaft stops.

Do not apply excessive force to the shutoff valve. Doing so may break the valve body, as the valve is not a backseat type. Always use the special tool.

3. Make sure to tighten the cap securely.

1

3

2

1. [Service precautions]Label location

2. Electric box lid3. [Caution] Label

location

One outdoor unit installed: Liquid line stop valveGas line stop valve

Multiple outdoor units installed: Liquid line stop valveGas line stop valveOil-equalizing line stop valve

Q96 type

Liquid line shutoff valve φ 3/8"

Gas line shutoff valve φ 7/8"

Installation Manual Outdoor Unit 159

Page 166: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Refrigerant Piping SiUS39-504

Closing Shutoff Valve

1. Remove the cap and turn the valve clockwise with the hexagon wrench (JISB4648).2. Securely tighten the valve until the shaft contacts the main body seal.3. Make sure to tighten the cap securely.

∗ For the tightening torque, refer to the table on the bellow. Tightening torque

<Caution>Always use a charge hose for service port connection.After tightening the cap, check that no refrigerant leaks are present.When loosening a flare nut, always use two wrenches in combination. When connecting the piping, always use a spanner and torque wrench in combination to tighten the flare nut.When connecting a flare nut, coat the flare (inner and outer faces) with etheral oil or ester oil and hand-tighten the nut 3 to 4 turns as the initial tightening.

FLARE SHAPE and FLARENUT TIGHTENING TORQUE<<<<Precautions when connecting pipes>>>>

See the following table for flare part machining dimensions.When connecting the flare nuts, apply refrigerant oil to the inside and outside of the flares and turn them three or four times at first. (Use ester oil or ether oil.)See the following table for tightening torque.(Applying too much torque may cause the flares to crack.)After all the piping has been connected, use nitrogen to perform a gas leak check.

Shutoff valve size

Tightening torque ft.lbf (Turn clockwise to close)

Shaft (valve body) Cap (valve lid) Service port Flare nut

Gas line piping

attached to unit (1)

φ3/8" 3.98-4.87Hexagonal

wrench0.16 in.

9.96-12.17

84.8-102.5

24.1-29.4 _

φ7/8" 19.91-24.34Hexagonal

wrench0.39 in.

26.55-32.45 _ 162.3-206.5

1

2

3

4

5

1. Service port2. Cap3. Hexagon hole4. Shaft5. Seal

Torque wrench

Spanner

Piping unionFlare nut

160 Installation Manual Outdoor Unit

Page 167: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Refrigerant Piping

Not recommendable but in case of emergency.You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may follow the installation method mentioned below.

After the Work is Finished, Make Sure to Check that there is no Gas Leak.

When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque suddenly increases. From that position, further tighten the flare nut the angle shown below:

(in.)

Disposal Requirements

Dismantling of the unit, treatment of the refrigerant, oil and eventual other parts, should be done in accordance with the relevant local and national regulations.

6.5 Pipe InsulationAfter finishing the leak test and vacuum drying, the piping must be insulated. Take into account the following points:

Make sure to insulate the connection piping and refrigerant branch kits entirely. Be sure to insulate the liquid-side and gas-side piping for the inter-unit piping and the refrigerant branch kits and always use Q18-type or better insulation for the oil pressure equalizer.Not insulating them may cause leaking. (The gas piping can reach temperatures of 248°F. Be sure the insulation used can withstand such temperatures.)If you think the humidity around the cooling piping might exceed 86°F and RH80%, reinforce the insulation on the cooling piping (at least 13/16" thick). Condensation might form on the surface of the insulation.If there is a possibility that condensation on the shut-off valve might drip down into the indoor unit through gaps in the insulation and piping because the outdoor unit is located higher than the indoor unit, etc., this must be prevented by caulking the connections, etc.

Caution Be sure to insulate local pipes, as touching them can cause burns.

pipe size (in.) tighteningtorque (ft. lbf) A (in.) flare shape (in.)

φ3/8" 24.1 - 29.4 0.504 - 0.520

φ1/2" 36.5 - 44.5 0.638 - 0.654

φ5/8" 45.6 - 55.6 0.760 - 0.776R=0.016-0.031

45 ±2

90 ±2

A

Pipe size Further tightening angle Recommended arm length of tool

3/8" 60 to 90 degrees Approx. 7 7/8

1/2" 30 to 60 degrees Approx. 9 13/16

5/8" 30 to 60 degrees Approx. 11 13/16

1. Liquid line stop valve2. Gas line stop valve3. Outer-to-inner interconnecting

piping4. Calking treatment, etc.5. Heat insulator6. Oil-equalizing line stop valve

5

4

3

1

2

Multiple outdoor units installedOne outdoor unit installed

1

6

5

4

3

2

Installation Manual Outdoor Unit 161

Page 168: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Refrigerant Piping SiUS39-504

6.6 Additional Refrigerant Charge

Note Refrigerant cannot be charged until field wiring has been completed.Refrigerant may only be charged after performing the leak test and the vacuum drying (see above).When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid hammer.Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the appropriate refrigerant (R-410A) is charged.Refrigerant containers shall be opened slowly.Always use protective gloves and protect your eyes when charging refrigerant.

TO AVOID COMPRESSOR BREAKDOWN. DO NOT CHARGE THE REFRIGERANT MORE THAN THE SPECIFED AMOUNT TO RAISE THE CONDENSING PRESSURE.

This outdoor unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant.Charge the refrigerant to the liquid pipe in its liquid state. Since R-410A is a mixed refrigerant, its composition changes if charged in a state of gas and normal system operation would no longer be assured.Before filling, check whether the tank has a siphon attached or not.How to fill a tank with a siphon attached.

Other ways of filling the tank

Determine the amount of refrigerant to be added by referring to the table, write it down on the included "Added Refrigerant" plate and attach it to the rear side of the front cover.Note: refer to the example of connection for the amount to be added.After the vacuum drying is finished, charge the additional refrigerant in its liquid state through the liquid stop valve service port. Taking into account following instructions:1.Check that gas and liquid stop valves are closed.2.Stop the compressor and charge the specified weight of refrigerant.If the outdoor unit is not in operation and the total amount cannot be charged, follow the procedures for additional refrigerant charge shown below.Make sure to use installation tools you exclusively use on R-410A installations to withstand the pressure and to prevent foreign materials from mixing into the system.

There is a siphon tubeinside, so there is no needto turn the tank upside-down.

Fill with the tank upright.

Fill with the tank upside-down.

162 Installation Manual Outdoor Unit

Page 169: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Refrigerant Piping

Notes: Procedures for charging additional refrigerant.

[Additional refrigerant charge procedure]To learn the system settings for additional refrigerant charging, refer to the [Service Precaution] label attached on the back of the electric box lid in the outdoor unit.1. Fully open the gas line shutoff valve (liquid line shutoff valve and valve A above must be left fully

closed) and start the additional refrigerant charge operation.2. After the system is charged with a specified amount of refrigerant, press the confirmation button

(BS3) on the P-board (A1P) in the outdoor unit to stop the additional refrigerant charge operation.

3. Immediately restore the shutoff valve to the following status. (The test run cannot be performed properly if the shut-off valve is not correct.)

Note If the refrigerant cylinder is siphonal, set it upright while charging additional refrigerant.

Liquid line shutoff valve Gas line shutoff valve Oil-equalizing line shutoff valve

Open Open Close (Default status before delivery)

1

2

3

4

5 6

7

8

9

10 11

12

17

13

1

2

3

4

5

6

7

13

1214

98

910

15

17

16

One outdoor unit installed

Multiple outdoor units installed

1. Pressure reducing valve2. Nitrogen3. Tank4. Siphon system5. Measuring instrument6. Vacuum pump7. Valve A8. Gas side9. Outdoor unit10.Liquid side11.Indoor unit12.Shutoff valve service port13.Charge hose14.To indoor unit15.Oil-equalizing line16.Valve B17.Dotted lines represent onsite piping

Installation Manual Outdoor Unit 163

Page 170: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Refrigerant Piping SiUS39-504

7. Field WiringNote All field wiring and components must be installed by a licensed electrician and must comply with

relevant local and national regulations.The field wiring must be carried out in accordance with the wiring diagrams and the instructions given below.Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.This product’s reversed phase protection detector only works when the product started up.The reversed phase protection detector is designed to stop the product in the event of an abnormalities when the product is started up.Replace two of the three phases (L1, L2, and L3) during reverse-phase protection circuit operation.Reversed phase detection is not performed while the product is operating.If there exists the possibility of reversed phase after an momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.

7.1 Optional Parts Cool/Heat Selector S1S..............................Selector switch (fan, cool/heat)S2S..............................Selector switch (cool/heat)

Notes: Use copper conductors only.When using the adaptor for sequential start, refer to chapter "Examples".For connection wiring to outdoor-outdoor transmission F1-F2, outdoor-indoor transmission F1-F2, outdoor-multi transmission Q1-Q2, refer to chapter "Examples".For connection wiring to the central remote controller, refer to the installation manual of the central remote controller.Use insulated wire for the power cord.

7.2 Power Circuit and Cable RequirementsA power circuit (see table below) must be provided for connection of the unit. This circuit must be protected with the required safety devices, i.e. a main switch, a slow blow fuse on each phase and an earth leak detector.

When using residual current operated circuit breakers, be sure to use a high-speed type 200mA rated residual operating current.

Notes: Select the power supply cable in accordance with relevant local and national regulations.Wire size must comply with the applicable local and national code.Specifications for local wiring power cord and branch wiring are in compliance with local cord.

Phase andfrequency Voltage Recommended

fusesTransmissionline selection

RXYQ96MTJU φ 3, 60Hz 208-230V 70A AWG 18-16

RXYQ192MTJU φ 3, 60Hz 208-230V 70A + 70A AWG 18-16

164 Installation Manual Outdoor Unit

Page 171: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Refrigerant Piping

7.3 GeneralMake sure to connect the power source wire to the power source terminal block and to clamp it as shown in figure 14, chapter "Field line connection".As this unit is equipped with an inverter, installing a phase advancing capacitor not only will deteriorate power factor improvement effect, but also may cause capacitor abnormal heating accident due to high-frequency waves. Therefore, never install a phase advancing capacitor.Keep power imbalance within 2% of the supply rating.1.Large imbalance will shorten the life of the smoothing capacitor.2.As a protective measure, the product will stop operating and an error indication will be made,

when power imbalance exceeds 4% of the supply rating.Follow the "electrical wiring diagram" when carrying out any electrical wiring.Only proceed with wiring work after blocking off all power.Always ground wires. (In accordance with national regulations of the pertinent country.)Do not connect the ground wire to gas pipes, sewage pipes, lightning rods, or telephone ground wires.2Gas pipes: can explode or catch fire if there is a gas leak.2Sewage pipes: no grounding effect is possible if hard plastic piping is used.2Telephone ground wires and lightning rods: dangerous when struck by lightning due to

abnormal rise in electrical potential in the grounding.This unit uses an inverter, and therefore generates noise, which will have to be reduced to avoid interfering with other devices. The outer casing of the product may take on an electrical charge due to leaked electrical current, which will have to be discharged with the grounding.Be sure to install an earth leak detector. (One that can handle higher harmonics.)(This unit uses an inverter, which means that an earth leak detector capable handling high harmonics in order to prevent malfunctioning of the earth leak detector itself.)Earth leak detector which are especially for protecting ground-faults should be used in conjunction with main switch or fuse for use with wiring.This unit has a negative phase protection circuit. (If it operates, only operate the unit after correcting the wiring.)

7.4 Examples

System Example 1

2

3

4

5

6

3

4

1

2

1. Field power supply2. Main switch3. Earth leak detector4. Fuse5. Cool / heat selector6. Remote controller

power supply wiring (sheathed cable)transmission wiring (sheathed cable)

Installation Manual Outdoor Unit 165

Page 172: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Refrigerant Piping SiUS39-504

Field Line Connection

L1, L2, L3, phase of the power cord should be clamped to the safety catch using the included clamp material.The green and yellow striped wrapped wires should be used for grounding.

5

L1 L2 L3

1

324

67

14

1315

1617

8

910

11

12

1. Power supply(208~230 V, Three-phase)

2. Branch switch, overcurrent breaker3. Grounding wire4. Earth leakage breaker5. Section A6. Attach insulation sleeves.7. Power supply terminal block8. Grounding terminal9. Retain the ground wire along with the power supply

wiring using the accessory clamps (1).10.Retain the power supply wiring to the bracket using

the accessory clamps (1).11.Grounding wire12.When wiring, do not allow the ground wire to

contact the compressor lead wires. If the wire contacts each other, adverse effects may occur to other units.

13.When connecting two wires to one terminal, ensure that the crimp-style terminals face with each other back to back.Moreover, make sure that the wire of the smaller gauge is located above.

14.Terminal block15.Crimp-style terminal16.Wire gauge: Small17.Wire gauge: Large

5

7

10

8

1

4

6

9

23

1. Retain with accessory clamps (3).2. Electric wiring3. Wiring between units4. Retain to the electric parts box with

the accessory clamps (1).5. When routing the remote control cord

and inter-unit wiring, secure clearance of 5” or more from the power wiring. Ensure that the power wiring does not contact any heated sections ( ).

6. Retain to the back of the column support with the accessory clamps (2).

7. Inter-unit wirings8. Power/ground wires9. Grounding wire10.When wiring, exercise sufficient

caution not to detach the acoustic insulators from the compressor.

166 Installation Manual Outdoor Unit

Page 173: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Refrigerant Piping

Caution <<<<Precautions when laying power wiring>>>>Use round pressure terminals for connections to the power terminal block.When none are available, follow the instructions below.

Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring may cause abnormal heat.)When connecting wiring which is the same thickness, do as shown in the figure below.

For wiring, use the designated power wire and connect firmly, then secure to prevent outside pressure being exerted on the terminal board.Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will strip the head and make proper tightening impossible.Over-tightening the terminal screws may break them.See the table below for tightening torque for the terminal screws.

<<<<Precautions when connecting the ground>>>>When pulling the ground wire out, wire it so that it comes through the cut out section of the cup washer. (An improper ground connection may prevent a good ground from being achieved.)

Tightening torque (ft.Ibf)

M8 (Power terminal block)40.6-53.8

M8 (Ground)

M3 (Inter-unit wiring terminal block) 5.9-7.2

Connect same-thickness wiringto both sides.

Power wireRound pressure terminal

It is forbidden toconnect two toone side.

It is forbidden toconnect wiring ofdifferent thicknesses.

Round pressure terminal

Cup washer

Cut out section

Installation Manual Outdoor Unit 167

Page 174: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Refrigerant Piping SiUS39-504

Field Line Connection: Transmission Wiring and Cool/Heat Selection

[In case of one outdoor unit]

[In case of multiple outdoor unit]

Note Be sure to follow the limits below. If the unit-to-unit cables are beyond these limits, it may result in malfunction of transmission.Maximum wiring length: 3280ft.Total wiring length: 6560ft.Max branches No. of branches: 16Max. number of outdoor units connectable: 10 or lessUp to 16 branches are possible for unit-to unit cabling. No branching is allowed after branching.Max. number of outdoor units connectable: 10 or lessNever connect the power supply to unit-to-unit cabling terminal block. Otherwise the entire system may break down.

A B CA B C F1 F2 F1 F2 Q1 Q2

A B C F1 F1F2 F2 Q1 Q2

F1 F2 F1 F2 F1 F2

F1 F2 F1 F2 F1 F2

F1 F2 F1 F2 F1 F2

4

5

6

1 2

C/H SELECTOR TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT

A1P

3

1. Cool/heat selector2. Outdoor unit P.C. board

(A1P)3. Take care of the polarity4. Use the conductor of

sheathed wire (2 wire) (nopolarity)

5. Terminal board (field supply)6. Indoor unit

A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2

A1P

1

3

6

7

8

4 5 5

2 1. Unit A (Master unit)2. Unit B (Slave unit)3. TO IN/D UNIT4. TO OUT/D UNIT5. TO MULTI UNIT6. To COOL/HEAT selector7. To indoor unit8. To other systems

1. Branch2. Sub-branching

168 Installation Manual Outdoor Unit

Page 175: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Refrigerant Piping

Setting the Cool/Heat Operation (Heat Pump Unit Only)

1. Performing cool/heat setting with the remote controller connected to the indoor unit.Keep the cool/heat selector switch (DS1) on the outdoor unit PC board (A1P) at the factory setting position IN/D UNIT.

2. Performing cool/heat setting with the cool/heat selector.Connect the cool/heat selector remote controller (optional) to the A/B/C terminals and set the cool/heat selector switch (DS1) on the outdoor unit PC board (A1P) to OUT/D UNIT.

Note For low-noise operation, it is necessary to get the optional "External control adaptor for outdoor unit".For details, see the installation manual attached to the adaptor.

Picking Power Line and Transmission Line

Be sure to let the power line and the transmission line pass through a conduit hole.Pick the power line from the upper hole on the front position of the main unit.

TO IN/DUNIT

F1 F2DS1

1 2 3 4

OFF

ON

OUT

I N

F1 F2 P1 P2 P1 P2

1

1. 1 = Remote controller

A B C

A B C 1

DS1

1 2 3 4

OFF

ON

OUT

I N

1. 1 = Cool/heat selector

1

3

4

2

1. Electric wiring diagramPrinted on the back of the electric box lid.

2. Knockout hole3. Power line4. Transmission line

Installation Manual Outdoor Unit 169

Page 176: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Refrigerant Piping SiUS39-504

Precautions when Knocking Out Knock Holes

To punch a knock hole, hit on it with a hammer.Open an appropriate hole as needed.After knocking out the holes, we recommend you paint the edges and areas around the edges using the repair paint to prevent rusting.Power line: Open a knockout hole as shown at left and connect it using a conduit.Transmission line: Connect it using a conduit in the knockout hole on the right.

Caution Use a power wire pipe for the power wiring.Outside the unit, make sure the weak electric wiring (i.e. for the remote control, between units, etc.) and the strong electric wiring do not pass near each other, keeping them at least 50 mm apart. Proximity may cause electrical interference, malfunctions, and breakage.Be sure to connect the power wiring to the power wiring terminal block and secure it as described in 7-4 Field line connection.Inter-unit wiring should be secured as described in 7-4 Field line connection.2Secure the wiring with the accessory clamps so that it does not touch the piping.2Make sure the wiring and the electric box lid do not stick up above the structure, and close

the cover firmly.

Never connect 200 V to the terminal block of the interconnecting wiring. Doing so will break the entire system.

The wiring from the indoor units must be connected to the F1/F2 (In-Out) terminals on the PC board in the outdoor unit.

For the above wiring, always use vinyl cords with AWG 18-16 sheath or cables (2 core wires).(3 core wire cables are allowable for the cooler/heater changeover remote controller only.)

Note Be sure to keep the power line and transmission line apart from each other.Be careful about polarity of the transmission line.Make sure that the transmission line is clamped as shown in the figure in chapter "Field line connection".Check that wiring lines do not make contact with refrigerant piping.

If there are any possibilities that small animals enter the system through the knock holes, plug the holes with packing materials (to be prepared onsite).

Burr

Knockout hole

Left side Right sideLock nut

Conduit mounting plate

Conduit

Electric box(A1P)

Use the accessory clamps (1) to retain them to the electric box.

Vinyl tube(Accessory)

170 Installation Manual Outdoor Unit

Page 177: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Refrigerant Piping

8. Before Operation8.1 Checks before Initial Start-up

Warning Make sure that the circuit breaker on the power supply panel of the installation is switched off.Attach the power wire securely.

After the installation, check the following before switching on the circuit breaker:1. The position of the switches that require an initial setting

Make sure that switches are set according to your application needs before turning the power supply on.

2. Power supply wiring and transmission wiringUse a designated power supply and transmission wiring and make sure that it has been carried out according to the instructions described in this manual, according to the wiring diagrams and according to local and national regulations.

3. Pipe sizes and pipe insulationMake sure that correct pipe sizes are installed and that the insulation work is properly executed.

4. Additional refrigerant chargeThe amount of refrigerant to be added to the unit should be written on the included "Added Refrigerant" plate and attached to the rear side of the front cover.

5. Insulation test of the main power circuitUsing a megatester for 500V, check that the insulation resistance of 2MΩ or more is attained by applying a voltage of 500V DC between power terminals and earth. Never use the megatester for the transmission wiring.

6. Installation dateBe sure to keep record of the installation date on the sticker on the electric box lid according.

8.2 Test Run

Note After completing installation, be sure to open the valves. (Operating the unit with the valves shut will break the compressor.)

Power Supply Connection

When running the unit for the first time after installation, be sure to perform a test run following these steps for test run. (Not performing a test run when the unit is first installed may prevent the unit from operating properly.)

Installation Manual Outdoor Unit 171

Page 178: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Refrigerant Piping SiUS39-504

During the operation, monitor the outdoor unit operation status and check for any incorrect wiring.

<Cautions for check operation>If the system is started within about 12 minutes after the outdoor/indoor units are turned ON, the compressor will not run and H2P lights up. Before starting an operation, always verify that the LED display shows the contents of the table in "8-2 Test run 2.".The system may require up to 10 minutes until it can start the compressor after an operation start. This is a normal operation to equalize the refrigerant distribution.The check operation does not provide any means of checking the indoor units individually. For that purpose, perform normal operation using the remote controller after the check operation.

1. Turn ON the power to the outdoor units and indoor units.

3. • As necessary, configure the systemsettings onsite by using thedipswitch (DS1) on the outdoor unitPC board (A1P) and push buttonswitches (BS1 to 5).

Always perform configuration after turning ON the power. To learn the setting method, refer to the [Service Precautions] label attached at the position shown in the figure on the right (Electric box lid in outdoor unit). (Remember, the actual settings you have made must be recorded on the [Service Precautions] label.)

2. Check the LED on the PC board (A1P) in the outdoor unit to see if the data transmissionis performed normally.

Make sure to turn ON the power 6 hours before starting the operation. This is necessary to warm the crankcase preliminarily by the electric heater.

LED display: OFF ON Blinking

4. Check if the shutoff valves are in appropriate status and correct anywrong status. (Refer to the table in“6-6 Additional Refrigerant Charge”.)

5. Perform the check operation following the instructions printed on the [Service Precaution] label.

Do not leave any shutoff valve closed. Otherwise the compressor will fail.

The system operates for about 15 minutes (30 minutes at maximum) and automatically stops the test operation. The system can start a normal operation about 15 minutes after the test operation, only if the remote controller displays no error codes.

Caution

LED display (Default status before delivery)

One outdoor unit installed

When multiple outdoor unit installed (∗)

Master station

Microcomputer operation monitor

Page

HAP H1P H2P H3P H4P H5P H6P H7P H8P

Ready/Error

Cooler/heater changeover

IndividualBulk (parent)

Bulk (child)

Low noise Demand Multi

Sub station

(∗) The base (parent) unit is the outdoor unit to which the interconnecting wiring for theindoor units is connected. The other outdoor units are child units.

• When the system is in the multiple-outdoor unit configuration (Out Multi),perform the configuration on theparent unit. (Any settings made ona child unit will be ignored.)

1

2

3

1. Electric box lid2. Service lid3. [Service precautions] Label

location

172 Installation Manual Outdoor Unit

Page 179: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Refrigerant Piping

The check run cannot be performed in recovery or other modes.Before running a check on the unit, changing the indoor remote controller settings might cause the error code “UF” to be displayed and prevent a proper check to be run.

Remote Controller Displays an Error:

Temperature Adjustment Operation Confirmation

After the test run is over, operate the unit normally. (Heating is not possible if the outdoor temperature is 75°F or higher.)2Make sure the indoor and outdoor units are operating normally (If a knocking sound can be

heard in the liquid compression of the compressor, stop the unit immediately and then energize the heater for a sufficient length of time before restarting the operation.)

2Run each indoor unit one at a time and make sure the corresponding outdoor unit is also running.

2Check to see if cold (or hot) air is coming out of the indoor unit.2Press the fan direction and fan strength buttons on the indoor unit to see if they operate

properly.

Note <Cautions for normal operation check>Once stopping, the compressor will not restart in about 5 minutes even if the Run/Stop button of an indoor unit in the same system is pressed.When the system operation is stopped by the remote controller, the outdoor units may continue operating for further 5 minutes at maximum.If the system has not undergone any check operation by the test operation button since it was first installed, an error code "U3" is displayed. In this case, perform check operation referring to "8.2 Test Run".After the test run, when handing the unit over to the customer, make sure the electric box lid, the service lid, and the unit casing are all attached.

Installation error Malfunction code Solution

The stop valve of an outdoor unit is left closed.

E3E4F3UF

Check referring to the table in “6-6 Additional Refrigerant Charge”.

The phases of the power to the outdoor units are reversed.

U1 Exchange two of the three phases (L1, L2, L3) to make a positive phase connection.

No power is supplied to an outdoor or indoor unit (including phase interrup-tion).

U1U4

Check if the power wiring for the outdoor units are con-nected correctly.(If the power wire is not connected to L2 phase, no mal-function display will appear and the compressor will not work.)

Incorrect interconnections between units UF Check if the refrigerant line piping and the unit wiring are

consistent with each other.

Refrigerant overcharge

E3F6UF

Recalculate the required amount of refrigerant from the piping length and correct the refrigerant charge level by recovering any excessive refrigerant with a refrigerant recovery machine.

Insufficient refrigerant

E4F3

• Check if the additional refrigerant charge has been fin-ished correctly.

• Recalculate the required amount of refrigerant from the piping length and add an adequate amount of refriger-ant.

If an outdoor multi terminal is connected when there is one outdoor unit installed.

U7UF

Remove the line from the outdoor multi terminals (Q1 and Q2).

The operation mode on the remote controller was changed before the check run.

UFE4

Set the operating mode on all indoor unit remote control-lers to “cooling.”

The check operation has not been performed. U3 Perform the check operation.

Installation Manual Outdoor Unit 173

Page 180: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Refrigerant Piping SiUS39-504

9. Caution for Refrigerant Leaks(Points to note in connection with refrigerant leaks)IntroductionThe installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.The VRV System, like other air conditioning systems, uses R-410A as refrigerant. R-410A itself is an entirely safe non-toxic, non-combustible refrigerant. Nevertheless care must be taken to ensure that air conditioning facilities are installed in a room which is sufficiently large. This assures that the maximum concentration level of refrigerant gas is not exceeded, in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards.

Maximum Concentration Level

The maximum charge of refrigerant and the calculation of the maximum concentration of refrigerant is directly related to the humanly occupied space in to which it could leak.The unit of measurement of the concentration is kg/m3 (the weight in lb. of the refrigerant gas in 35.3ft3 volume of the occupied space).Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required.

Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant is heavier than air.

Procedure for checking maximum concentration

Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply.

1. Calculate the amount of refrigerant (Ib.) charged to each system separately.

Notes: Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems then use the amount of refrigerant with which each separate system is charged.

2. Calculate the smallest room volume (ft3)Incase like the following, calculate the volume of (A), (B) as a single room or as the smallest room.

A.Where there are no smaller room divisions

amount of refrigerant in a single unit system (amount of refrigerant with which the system is charged before leaving the factory)

+additional charging amount (amount of refrigerant added locally in accordance with the length or diameter of the refrigerant piping)

=total amount of refrigerant (Ib.) in the system

2

1

1. direction of the refrigerant flow2. room where refrigerant leak

has occurred (outflow of all the refrigerant from the system)

174 Installation Manual Outdoor Unit

Page 181: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Refrigerant Piping

B.Where there is a room division but there is an opening between the rooms sufficiently large to permit a free flow of air back and forth.

(Where there is an opening without a door or where there are openings above and below the door which are each equivalent in size to 0.15% or more of the floor area.)

3. Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above.

If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so until the result falls short of the maximum concentration.

4. Dealing with the situations where the result exceeds the maximum concentration level.Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise the system.Please consult your Daikin supplier.

total volume of refrigerant in the refrigerant system≤ maximum concentration level (lb./ft3)

size (ft3) of smallest room in which there is an indoor unit installed

1

2

1. opening between rooms2. partition

Installation Manual Outdoor Unit 175

Page 182: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Refrigerant Piping SiUS39-504

176 Installation Manual Outdoor Unit

Page 183: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

Part 3Part 3Part 3Part 3Operation ManualOperation ManualOperation ManualOperation Manual

Outdoor UnitOutdoor UnitOutdoor UnitOutdoor Unit

1. Safety Considerations .............................................................................1792. What to do before Operation...................................................................1823. Remote Controller and Changeover Switch:

Name and Function of Each Switch and Display ....................................1834. Operation Range.....................................................................................1855. Operation Procedure...............................................................................186

5.1 Cooling, Heating, and Fan Only Operation .............................................. 1865.2 Program Dry Operation ............................................................................ 1885.3 Adjusting the Air Flow Direction ............................................................... 1895.4 Programming Start and Stop of the System with Timer ........................... 1915.5 Setting the Master Remote Controller ...................................................... 1925.6 Precautions for Group Control System or

Two Remote Controller Control System................................................... 193

6. Optimum Operation.................................................................................1947. Following Symptoms are not Air Conditioner Troubles ...........................195

7.1 The System does not Operate ................................................................. 1957.2 Cool/Heat Cannot be Changed Over ....................................................... 1957.3 Fan Operation is Possible, but Cooling and Heating do not Work ........... 1957.4 The Fan Strength does not Correspond to the Setting............................. 1957.5 The Fan Direction does not Correspond to the Setting ............................ 1957.6 White Mist comes out of a Unit................................................................. 1967.7 Noise of Air Conditioners.......................................................................... 1967.8 Dust comes out of the Unit ....................................................................... 1967.9 The Units can Give off Odours ................................................................. 1967.10 The Outdoor Unit Fan does not Spin........................................................ 1967.11 The Display Shows "88" ........................................................................... 1977.12 The Compressor in the Outdoor Unit does not

Stop after a Short Heating Operation ....................................................... 1977.13 The Inside of an Outdoor Unit is Warm Even

When the Unit has Stopped ..................................................................... 197

8. Trouble Shooting.....................................................................................198

[Applicable model]RXYQ96MTJURXYQ192MTJU

3P114261-5R EM03A045A

Operation Manual Outdoor Unit 177

Page 184: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

Thank you for purchasing this Daikin air conditioner. Carefully read this operation manual before using the air conditioner. It will tell you how to use the unit properly and help you if any trouble occurs. After reading the manual, file it away for future reference.

178 Operation Manual Outdoor Unit

Page 185: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Safety Considerations

1. Safety ConsiderationsPlease read these "Safety Considerations" carefully before installing air conditioning equipment and be sure to install it correctly. After completing the installation, make sure that the unit operates properly during the start-up operation.Please instruct the customer on how to operate the unit and keep it maintained.Also, inform customers that they should store this operation manual along with the installation manual for future reference.This air conditioner comes under the term "appliances not accessible to the general public".Meaning of warning, caution and note symbols.

Warning ....Indication a potentially hazardous situation which, if not avoided, could result in death or serious injury.

Caution .....Indication a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be sued to alert against unsafe practices.

Note...........Indication situation that may result in equipment or property-damage-only accidents.

Keep these warning sheets handy so that you can refer to them if needed.Also, if this equipment is transferred to a new user, make sure to hand over this operation manual to the new user.

Warning It is not good for your health to expose your body to the air flow for a long time.In order to avoid electric shock, fire or injury, or if you detect any abnormality such as smell of fire, turn off power and call your dealer for instructions.Ask your dealer for installation of the air conditioner.Incomplete installation performed by yourself may result in a water leakage, electric shock, and fire.Ask your dealer for improvement, repair, and maintenance.Incomplete improvement, repair, and maintenance may result in a water leakage, electric shock, and fire.The refrigerant in the air conditioner is safe and normally does not leak. If the refrigerant leaks inside the room, the contact with a fire of a burner, a heater or a cooker may result in a harmful gas.Do not use the air conditioner until when a service person confirms to finish repairing the portion where the refrigerant leaks.For refrigerant leakage, consult your dealer.When the air conditioner is to be installed in a small room, it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the limiting concentration even when it leaks. If the refrigerant leaks exceeding the level of limiting concentration, an oxygen deficiency accident may happen.Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Be sure only to use accessories made by Daikin which are specifically designed for use with the equipment and have them installed by a professional.Ask your dealer to move and reinstall the air conditioner.Incomplete installation may result in a water leakage, electric shock, and fire.Never let the indoor unit or the remote controller get wet. It may cause an electric shock or a fire.Never use flammable spray such as hair spray, lacquer or paint near the unit.It may cause a fire.Never replace a fuse with that of wrong ampere ratings or other wires when a fuse blows out.Use of wire or copper wire may cause the unit to break down or cause a fire.Never remove the fan guard of the unit.A fan rotating at high speed without the fan guard is very dangerous.

Operation Manual Outdoor Unit 179

Page 186: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Safety Considerations SiUS39-504

Never inspect or service the unit by yourself.Ask a qualified service person to perform this work.To prevent refrigerant leak, contact your dealer.When the system is installed and run in a small room, it is required to keep the concentration of the refrigerant, if by and chance coming out, below the limit. Otherwise, oxygen in the room may be affected, resulting in a serious accident.Cut off all electric waves before maintenance.To avoid the risk of serious electrical shock, never sprinkle or spill water or liquids on the unit.Do not install the air conditioner at any place where flammable gas may leak out.If the gas leaks out and stays around the air conditioner, a fire may break out.Do not touch the switch with wet fingers.Touching a switch with wet fingers can cause electric shock.

Caution Do not use the air conditioner for other purposes.In order to avoid any quality deterioration, do not use the unit for cooling precision instruments, food, plants, animals or works of art.To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner is used together with the air conditioner.After a long use, check the unit stand and fitting for damage.If they are left in a damaged condition, the unit may fall and result in injury.Do not allow a child to mount on the unit or avoid placing any object on it.Falling or tumbling may result in injury.Do not let children play on and around the unit.If they touch the unit carelessly, it may result in injury.Do not place a flower vase and anything containing water.Water may enter the unit, causing an electric shock or fire.Never touch the internal parts of the controller.Do not remove the front panel. Some parts inside are dangerous to touch, and a machine trouble may happen. For checking and adjusting the internal parts, contact your dealer.Avoid placing the controller in a spot splashed with water.Water coming inside the machine may cause an electric leak or may damage the internal electronic parts.Do not operate the air conditioner when using a room fumigation - type insecticide.Failure to observe could cause the chemicals to become deposited in the unit, which could endanger the health of those who are hypersensitive to chemicals.Do not put a finger, a rod or other objects into the air inlet or outlet. As the fan is rotating at high speed, it will cause injury.Do not touch the heat exchanger fins. Improper handling may result in injury.Safely dispose of the packing materials.Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.Tear apart and throw away plastic packaging bags so that children will not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation. Do not turn off the power immediately after stopping operation. Always wait at least five minutes before turning off the power. Otherwise, water leakage and trouble may occur.The appliance is not intended for use by young children or infirm persons without supervision. The remote controller should be installed in such away that children cannot play with it.

Note Never touch the air outlet or the horizontal blades while the swing flap is in operation.Fingers may become caught or the unit may break down.

180 Operation Manual Outdoor Unit

Page 187: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Safety Considerations

Never press the button of the remote controller with a hard, pointed object.The remote controller may be damaged.Never pull or twist the electric wire of the remote controller.It may cause the unit to malfunction.Do not place appliances which produce open fire in places exposed to the air flow from the unit or under the indoor unit. It may cause incomplete combustion or deformation of the unit due to the heat.Arrange the drain hose to ensure smooth drainage. Incomplete drainage may cause wetting of the building, furniture etc.Do not place the controller exposed to direct sunlight.The LCD display may get discolored, failing to display the data.Do not wipe the controller operation panel with benzine, thinner, chemical dustcloth, etc.The panel may get discolored or the coating peeled off. If it is heavily dirty, soak a cloth in water-diluted neutral detergent, squeeze it well and wipe the panel clean. And wipe it with another dry cloth.Dismantling of the unit, treatment of the refrigerant, oil and eventual other parts, should be done in accordance with the relevant local and national regulations.

Operation Manual Outdoor Unit 181

Page 188: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

What to do before Operation SiUS39-504

2. What to do before OperationThis operation manual is for the following systems with standard control. Before initiating operation, contact your Daikin dealer for the operation that corresponds to your system type and mark.If your installation has a customized control system, ask your Daikin dealer for the operation that corresponds to your system.Outdoor units

Names and functions of parts

Cool/heat changeover remote control switch Operation modes

Inverter series

heat pumps RXYQ series yes no

1. Outdoor unit2. Indoor unit3. Remote controller4. Inlet air5. Outlet air6. Cool/heat changeover remote

control switch(figure 1 shows systems with changeover remote control switches)

182 Operation Manual Outdoor Unit

Page 189: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Remote Controller and Changeover Switch: Name and Function of Each Switch and Display

3. Remote Controller and Changeover Switch: Name and Function of Each Switch and Display

1. On/off buttonPress the button and the system will start. Press the button again and the system will stop.

2. Operation lamp (red)The lamp lights up during operation.

3. Display " " (changeover under control)It is impossible to changeover heat/cool with the remote controller when this icon is displayed.

4. Display " " (air flow flap)Refer to the chapter "Operation procedure - Adjusting the air flow direction".

5. Display " " (ventilation/air cleaning)This display shows that the total heat exchange and the air cleaning unit are in operation. (these are optional accessories)

6. Display " " (set temperature)This display shows the temperature you have set.

7. Display " " " " " " " " (operation mode)This display shows the current operation mode.

8. Display " " (programmed time)This display shows the programmed time of the system start or stop.

9. Display " " (inspection/test operation)When the inspection/test operation button is pressed, the display shows the mode in which the system actually is.

10.Display " " (under centralized control)When this display shows, the system is under centralized control. (This is not a standard specification.)

11.Display " " (fan speed)This display shows the fan speed you have selected.

12.Display " " (time to clean air filter)Refer to the indoor unit manual.

13.Display " " (defrost/hot start)Refer to the chapter "Operation procedure - Explanation of heating operation."

23

24

F

F

TEST

Operation Manual Outdoor Unit 183

Page 190: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Remote Controller and Changeover Switch: Name and Function of Each Switch and Display SiUS39-504

14.Timer mode start/stop buttonRefer to the chapter "Operation procedure - Programming start and stop of the system with timer."

15.Timer on/off buttonRefer to the chapter "Operation procedure - Programming start and stop of the system with timer."

16.Inspection/test operation buttonThis button is only used by qualified service persons for maintenance purposes.

17.Programming time buttonUse this button for programming start and/or stop time.

18.Temperature setting buttonUse this button for setting the desired temperature.

19.Filter sign reset buttonRefer to the indoor unit manual.

20.Fan speed control buttonPress this button to select the fan speed of your preference.

21.Operation mode selector buttonPress this button to select the operation mode of your preference.

22.Air flow direction adjust buttonRefer to the chapter "Operation procedure - Adjusting the air flow direction".

23.Fan only/air conditioning selector switchSet the switch to " " for fan only operation or to " " for heating or cooling operation.

24.Cool/heat changeover switchSet the switch to " " for cooling or to " " for heating operation.

Note In contradistinction to actual operating situations, the display on figure 1 shows all possible indications.If the filter sign lamp lights up, clean the air filter as explained in the indoor unit manual. After cleaning and reinstalling the air filter: press the filter sign reset button on the remote controller. The filter sign lamp on the display will go out.

184 Operation Manual Outdoor Unit

Page 191: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Operation Range

4. Operation RangeUse the system in the following temperature and humidity ranges for safe and effective operation.

*To avoid condensation and water dripping out the unit.If the temperature or the humidity is beyond these conditions, safety devices may work and the air conditioner may not operate.

COOLING HEATING

outdoor temperature 23°~110°FDB 5°~60°FWB

indoor temperature 57°~77°FWB 59°~80°FDB

indoor humidity ≤ 80%*

Operation Manual Outdoor Unit 185

Page 192: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Operation Procedure SiUS39-504

5. Operation ProcedureOperation procedure varies according to the combination of outdoor unit and remote controller. Read the chapter "What to do before operation".To protect the unit, turn on the main power switch 6 hours before operation.If the main power supply is turned off during operation, operation will restart automatically after the power turns back on again.

5.1 Cooling, Heating, and Fan Only OperationChangeover cannot be made with a remote controller whose display shows " " (changeover under control).When the display " " (changeover under control) flashes, refer to the chapter "Operation procedure - Setting the master remote controller".The fan may keep on running for about 1 minute after the heating operation stops.The air flow rate may adjust itself depending on the room temperature or the fan may stop immediately. This is not a malfunction.

FOR SYSTEMS WITHOUT COOL/HEAT CHANGEOVER REMOTE CONTROL SWITCH

Press the operation mode selector button several times and select the operation mode of your choice;" " Cooling operation" " Heating operation" " Fan only operationPress the on/off button.The operation lamp lights up and the system starts operation.

F

1

2

186 Operation Manual Outdoor Unit

Page 193: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Operation Procedure

FOR SYSTEMS WITH COOL/HEAT CHANGEOVER REMOTE CONTROL SWITCH

Select operation mode with the cool/heat changeover remote control switch as follows:" " " " Cooling operation (Refer to Cooling operation)" " " " Heating operation (Refer to Heating operation)" " " " Fan only operation (Refer to Fan only operation)Press the on/off button.The operation lamp lights up and the system starts operation.

Adjustment For programming temperature, fan speed and air flow direction follow the procedure shown below.Press the temperature setting button and program the desired temperature.

Each time this button is pressed, the temperature setting rises or lowers 1°F.

F

Cooling operation

F

Heating operation

F

Fan only operation

1

2

3

Operation Manual Outdoor Unit 187

Page 194: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Operation Procedure SiUS39-504

Note Set the temperature within the operation range.The temperature setting is impossible for fan only operation.

Press the fan speed control button and select the fan speed of your preference.Press air flow direction adjust button.Refer to the chapter "Adjusting the air flow direction" for details.

Stopping the system

Press the on/off button once again.The operation lamp goes off and the system stops operation.

Note Do not turn off power immediately after the unit stops, but wait for at least 5 minutes.

EXPLANATION OF HEATING OPERATION

Defrost operation In heating operation, freezing of the outdoor unit coil increases. Heating capability decreases and the system goes into defrost operation.The indoor unit fan stops and the remote controller displays " ".After maximum 10 minutes of defrost operation, the system returns to heating operation again.

Hot start In order to prevent cold air from blowing out of an indoor unit at the start of heating operation, the indoor fan is automatically stopped. The display of the remote controller shows " ".

5.2 Program Dry OperationThe function of this program is to decrease the humidity in your room with a minimum temperature decrease.The micro computer automatically determines temperature and fan speed.The system does not go into operation if the room temperature is low.

FOR SYSTEMS WITHOUT COOL/HEAT CHANGEOVER REMOTE CONTROL SWITCH

Press the operation mode selector button several times and select " " (program dry operation).

Press the on/off buttonThe operation lamp lights up and the system starts operation.

Press the air flow direction adjust button. Refer to the chapter "Adjusting the air flow direction" for details.

Stopping the system

Press the on/off button once again.The operation lamp goes off and the system stops operation.

Note Do not turn off power immediately after the unit stops, but wait for at least 5 minutes.

4

5

6

1

2

3

4

188 Operation Manual Outdoor Unit

Page 195: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Operation Procedure

FOR SYSTEMS WITH COOL/HEAT CHANGEOVER REMOTE CONTROL SWITCH

Select cooling operation mode with the cool/heat changeover remote control switch.

Press the operation mode selector button several times and select program dry " ".

Press the on/off buttonThe operation lamp lights up and the system starts operation.

Press the air flow direction adjust button. Refer to the chapter "Adjusting the air flow direction" for details.

Stopping the system

Press the on/off button once again.The operation lamp goes off and the system stops operation.

Note Do not turn off power immediately after the unit stops, but wait for at least 5 minutes.

5.3 Adjusting the Air Flow Direction

Press the air flow direction button to select the air direction.The air flow flap display swings as shown below and the air flow direction continuously varies. (Automatic swing setting)

Press the air flow direction adjust button to select the air direction of your choice.

The air flow flap display stops swinging and the air flow direction is fixed.(Fixed air flow direction setting)

1

2

3

4

5

F

1

2

Operation Manual Outdoor Unit 189

Page 196: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Operation Procedure SiUS39-504

MOVEMENT OF THE AIR FLOW FLAP

For the following conditions, a micro computer controls the air flow direction which may be different from the display.

The air flow direction can be adjusted in one of the following ways.The air flow flap itself adjusts its position.The air flow direction can be fixed by the user.Automatic " " and desired position " ".

Note The movable limit of the flap is changeable. Contact your Daikin dealer for details.Avoid operating in the horizontal direction " ". It may cause dew or dust to settle on the ceiling.

COOLING HEATING

When starting operation.When the room temperature is higher than the set temperature.At defrost operation.

When operating continuously at horizontal air flow direction.When continuous operation with downward air flow is performed at the time of cooling with a ceiling-suspended or a wall-mounted unit, the microcomputer may control the flow direction, and then the remote control indication also will change.

Wall Mounted

Multi-flow

Ceiling Suspended

190 Operation Manual Outdoor Unit

Page 197: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Operation Procedure

5.4 Programming Start and Stop of the System with Timer

The timer is operated in the following two ways. Programming the stop time " ". The system stops operating after the set time has elapsed.Programming the start time " ". The system starts operating after the set time has elapsed.The timer can be programmed for a maximum of 72 hours.The start and the stop time can be simultaneously programmed.

Press the timer mode start/stop button several times and select the mode on the display.The display flashes.2For setting the timer stop " "2For setting the timer start " "Press the programming time button and set the time for stopping or starting the system.

Each time this button is pressed, the time advances or goes backward by 1 hour.

Press the timer on/off button.The timer setting procedure ends. The display " " or " " changes from flashing light to constant light.

Note When setting the timer off and on at the same time, repeat the above procedure (from " " to " ") once again.After the timer is programmed, the display shows the remaining time.Press the timer on/off button once again to cancel programming. The display vanishes.

For example:When the timer is programmed to stop the system after 3 hours and start the system after 4 hours, the system will stop after 3 hours and start 1 hour later.

F

1

2

3

1

3

Operation Manual Outdoor Unit 191

Page 198: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Operation Procedure SiUS39-504

5.5 Setting the Master Remote Controller

When the system is installed as shown in figure 14, it is necessary to designate one of the remote controllers as the master remote controller.

FOR RXYQ SERIES

When one outdoor unit is connected with several indoor units.Only the master remote controller can select heating, cooling operation.The displays of slave remote controllers show " " (changeover under control) and they automatically follow the operation mode directed by the master remote controller.

However, it is possible to changeover to program dry with slave remote controllers if the system is in cooling operation set by the master remote controller.

How to Designate the Master Remote Controller

Press the operation mode selector button of the current master remote controller for 4 seconds.The display showing " " (changeover under control) of all slave remote controllers connected to the same outdoor unit flashes.

Press the operation mode selector button of the controller that you wish to designate as the master remote controller. Then designation is completed. This remote controller is designated as the master remote controller and the display showing " " (changeover under control) vanishes.The displays of other remote controllers show " " (changeover under control).

F

1

2

192 Operation Manual Outdoor Unit

Page 199: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Operation Procedure

5.6 Precautions for Group Control System or Two Remote Controller Control System

This system provides two other control systems beside individual control (one remote controller controls one indoor unit) system. Confirm the following if your unit is of the following control system type.

Group control systemOne remote controller controls up to 16 indoor units. All indoor units are equally set.Two remote controller control systemTwo remote controllers control one indoor unit (in case of group control system, one group of indoor units). The unit is individually operated.

Note Contact your Daikin dealer in case of changing the combination or setting of group control and two remote controller control systems.

Operation Manual Outdoor Unit 193

Page 200: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Optimum Operation SiUS39-504

6. Optimum OperationObserve the following precautions to ensure the system operates properly.

Adjust the air outlet properly and avoid direct air flow to room inhabitants.Adjust the room temperature properly for a comfortable environment. Avoid excessive heating or cooling.Prevent direct sunlight from entering a room during cooling operation by using curtains or blinds.Ventilate often.Extended use requires special attention to ventilation.Keep doors and windows closed. If the doors and windows remain open, air will flow out of your room causing a decrease in the cooling or heating effect.Never place objects near the air inlet or the air outlet of the unit. It may cause deterioration in the effect or stop the operation.Turn off the main power supply switch to the unit when the unit is not used for longer periods of time. If the switch is on, it uses electricity. Before restarting the unit, turn on the main power supply switch 6 hours before operation to ensure smooth running. (Refer to the chapter "Maintenance" in the indoor unit manual.)When the display shows " " (time to clean the air filter), ask a qualified service person to clean the filters. (Refer to the chapter "Maintenance" in the indoor unit manual.)Keep the indoor unit and remote control at least 3.5ft. away from televisions, radios, stereos, and other similar equipment.Failing to do so may cause static or distorted pictures.Do not place items under the indoor unit which may be damaged by water.Condensation may form if the humidity is above 80% or if the drain outlet gets blocked.

194 Operation Manual Outdoor Unit

Page 201: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Following Symptoms are not Air Conditioner Troubles

7. Following Symptoms are not Air Conditioner Troubles

7.1 The System does not OperateThe air conditioner does not start immediately after the ON/OFF button on the remote controller is pushed.If the operation lamp lights, the system is in normal condition.To prevent overloading of the compressor motor, the air conditioner starts 5 minutes after it is turned ON again in case it was turned OFF just before. The same starting delay occurs after the operation mode selector button was used.If "Centralized Control" is displayed on the remote control and pressing the operation button causes the display to blink for a few seconds.This indicates that the central device is controlling the unit.The blinking display indicates that the remote control cannot be used.The system does not start immediately after the power supply is turned on.Wait one minute until the micro computer is prepared for operation.

7.2 Cool/Heat Cannot be Changed OverWhen the display shows " " (changeover under control), it shows that this is a slave remote controller.When the cool/heat changeover remote control switch is installed and the display shows " " (changeover under control).

This is because cool/heat changeover is controlled by the cool/heat changeover remote control switch. Ask your Daikin dealer where the remote control switch is installed.

7.3 Fan Operation is Possible, but Cooling and Heating do not Work

Immediately after the power is turned on.The micro computer is getting ready to operate.Wait 10 minutes.

7.4 The Fan Strength does not Correspond to the SettingThe fan strength does no change even if the fan strength adjustment button in pressed.During heating operation, when the room temperature reaches the set temperature, the outdoor unit goes off and the indoor unit changes to whisper fan strength.This is to prevent cold air blowing directly on occupants of the room.The fan strength will not change even if the button is changed, when another indoor unit is in heating operation.

7.5 The Fan Direction does not Correspond to the SettingThe fan direction does not correspond to the remote control display.The fan direction does not swing.This is because the unit is being controlled by the micro computer.

Operation Manual Outdoor Unit 195

Page 202: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Following Symptoms are not Air Conditioner Troubles SiUS39-504

7.6 White Mist comes out of a Unit

Indoor unit When humidity is high during cooling operation.If the interior of an indoor unit is extremely contaminated, the temperature distribution inside a room becomes uneven. It is necessary to clean the interior of the indoor unit. Ask your Daikin dealer for details on cleaning the unit. This operation requires a qualified service person.

Immediately after the cooling operation stops and if the room temperature and humidity are low.This is because warm refrigerant gas flows back into the indoor unit and generates steam.

Indoor Unit, Outdoor Unit

When the system is changed over to heating operation after defrost operation.Moisture generated by defrost becomes steam and is exhausted.

7.7 Noise of Air Conditioners

Indoor Unit A "zeen" sound is heard immediately after the power supply is turned on.The electronic expansion valve inside an indoor unit starts working and makes the noise. Its volume will reduce in about one minute.A continuous low "shah" sound is heard when the system is in cooling operation or at a stop.When the drain pump (optional accessories) is in operation, this noise is heard.A "pishi-pishi" squeaking sound is heard when the system stops after heating operation.Expansion and contraction of plastic parts caused by temperature change make this noise.A low "sah", "choro-choro" sound is heard while the indoor unit is stopped.When the other indoor unit is in operation, this noise is heard. In order to prevent oil and refrigerant from remaining in the system, a small amount of refrigerant is kept flowing.

Indoor Unit, Outdoor Unit

A continuous low hissing sound is heard when the system is in cooling or defrost operation.This is the sound of refrigerant gas flowing through both indoor and outdoor units.A hissing sound which is heard at the start or immediately after stopping operation or defrost operation.This is the noise of refrigerant caused by flow stop or flow change.

Outdoor Unit When the tone of operating noise changes.This noise is caused by the change of frequency.

7.8 Dust comes out of the UnitWhen the unit is used for the first time in a long time.This is because dust has gotten into the unit.

7.9 The Units can Give off OdoursThe unit can absorb the smell of rooms, furniture, cigarettes, etc., and then emit it again.

7.10 The Outdoor Unit Fan does not SpinDuring operation.The speed of the fan is controlled in order to optimize product operation.

196 Operation Manual Outdoor Unit

Page 203: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Following Symptoms are not Air Conditioner Troubles

7.11 The Display Shows "88"This is the case immediately after the main power supply switch is turned on and means that the remote controller is in normal condition. This continues for one minute.

7.12 The Compressor in the Outdoor Unit does not Stop after a Short Heating Operation

This is to prevent oil and refrigerant from remaining in the compressor. The unit will stop after 5 to 10 minutes.

7.13 The Inside of an Outdoor Unit is Warm Even When the Unit has Stopped

This is because the crankcase heater is warming the compressor so that the compressor can start smoothly.

Operation Manual Outdoor Unit 197

Page 204: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Trouble Shooting SiUS39-504

8. Trouble ShootingIf one of the following malfunctions occur, take the measures shown below and contact your Daikin dealer.The system must be repaired by a qualified service person.

If a safety device such as a fuse, a breaker or an earth leakage breaker frequently actuates, or the ON/OFF switch does not properly work;Measure: Turn off the main power switch.If water leaks from unit;Measure: Stop the operation.If the display " ", the unit number and the operation lamp flash and the malfunction code appears;

Measure: Notify your Daikin dealer and report the malfunction code.

If the system does not properly operate except for the above mentioned cases and none of the above mentioned malfunctions is evident, investigate the system according to the following procedures.

1. If the system does not operate at all;Check if there is no power failure.Wait until power is restored. If power failure occurs during operation, the system automatically restarts immediately after the power supply is recovered.Check if no fuse has blown or breaker has worked. Change the fuse or reset the breaker if necessary.

2. If the system goes into fan only operation, but as soon as it goes into heating or cooling operation, the system stops;Check if air inlet or outlet of outdoor or indoor unit is not blocked by obstacles.Remove any obstacle and make it well-ventilated.Check if the remote controller display shows " " (time to clean the air filter). (Refer to the chapter "Maintenance" in the indoor unit manual.)

3. The system operates but cooling or heating is insufficient;Check if air inlet or outlet of outdoor or indoor unit is not blocked by obstacles.Remove any obstacle and make it well-ventilated.Check if the air filter is not clogged. (Refer to the chapter "Maintenance" in the indoor unit manual.)Check the temperature setting.Check the fan speed setting on your remote controller.Check for open doors or windows. Shut doors and windows to prevent wind from coming in.Check if there are too many occupants in the room during cooling operation.

TEST

F

1. Inspection display2. Indoor unit number in which a

malfunction occurs3. Operation lamp4. Malfunction code

198 Operation Manual Outdoor Unit

Page 205: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Trouble Shooting

Check if the heat source of the room is excessive.Check if direct sunlight enters the room.Use curtains or blinds.Check if the air flow angle is not proper.

Operation Manual Outdoor Unit 199

Page 206: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Trouble Shooting SiUS39-504

200 Operation Manual Outdoor Unit

Page 207: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

Precautions for New Refrigerant (R-410A) 201

Part 4Part 4Part 4Part 4Precautions for NewPrecautions for NewPrecautions for NewPrecautions for NewRefrigerant (R-410A)Refrigerant (R-410A)Refrigerant (R-410A)Refrigerant (R-410A)

1. Precautions for New Refrigerant (R-410A) .............................................2021.1 Outline ...................................................................................................... 2021.2 Service Tools............................................................................................ 203

Page 208: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Precautions for New Refrigerant (R-410A) SiUS39-504

1. Precautions for New Refrigerant (R-410A)1.1 Outline1.1.1 About Refrigerant R-410A

Characteristics of new refrigerant, R-410A1. Performance

Almost the same performance as R-22 and R-407C2. Pressure

Working pressure is approx. 1.4 times more than R-22 and R-407C.3. Refrigerant composition

Few problems in composition control, since it is a Quasi-azeotropic mixture refrigerant.

1.Non-azeotropic mixture refrigerant : mixture of two or more refrigerants having different boiling points.

2.Quasi-azeotropic mixture refrigerant : mixture of two or more refrigerants having similar boiling points.

3.The design pressure is different at each product. Please refer to the installation manual for each product.(Reference) 1 MPa 145 psi

HFC units (Units using new refrigerants) HCFC units

Refrigerant name R-407C R-410A R-22

Composing substances

Non-azeotropic mixture of HFC32, HFC 125 and HFC134a (*1)

Quasi-azeotropic mixture of HFC32 and JFC125 (*1)

Single-component refrigerant

Design pressure 3.2MPa (gauge pressure) = 464 psi

3.80 MPa (gauge pressure)= 550 psi

2.75MPa (gauge pressure) = 406 psi

Refrigerant oil Synthetic oil (Ether) Mineral oil (Suniso)

Ozone destruction factor (ODP) 0 0 0.05

Combustibility None None None

Toxicity None None None

202 Precautions for New Refrigerant (R-410A)

Page 209: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Precautions for New Refrigerant (R-410A)

1.2 Service ToolsR-410A is used under higher working pressure, compared to previous refrigerants (R-22,R-407C). Furthermore, the refrigerating machine oil has been changed from Suniso oil to Ether oil, and if oil mixing is occurred, sludge results in the refrigerants and causes other problems. Therefore, gauge manifolds and charge hoses that are used with a previous refrigerant (R-22,R-407C) can not be used for products that use new refrigerants.Be sure to use dedicated tools and devices.

Tool compatibility

As for the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of charge hose.

Tool

Compatibility

Reasons for changeHFC HCFC

R-410A R-407C R-22

Gauge manifoldCharge hose

2Do not use the same tools for R-22 and R-410A.

2Thread specification differs for R-410A and R-407C.

Gas detector 2The same tool can be used for HFCs.

Vacuum pump(pump with reverse flow preventive function)

2To use existing pump for HFCs, vacuum pump adaptor must be installed.

Weighting instrument

Flaring tool (Clutch type) 2For R-410A, flare gauge is necessary.

Torque wrench 2Torque-up for 1/2 and 5/8

Pipe cutter

Pipe expander

Pipe bender

Pipe assembling oil 2Due to refrigerating machine oil

change. (No Suniso oil can be used.)

Refrigerant recovery device Check your recovery device.

Refrigerant piping See the chart below. 2Only φ19.1 is changed to 1/2H material while the previous material is "O".

Precautions for New Refrigerant (R-410A) 203

Page 210: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Precautions for New Refrigerant (R-410A) SiUS39-504

1. Flaring tool

Specifications2 Dimension A

Differences2 Change of dimension A

Conventional flaring tools can be used when the work process is changed. (change of work process) Previously, a pipe extension margin of 0 to 0.5mm was provided for flaring. For R-410A air conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5mm.(For clutch type only) Conventional tool with pipe extension margin adjustment can be used.

Flare gauge

Nominal size

1/4

3/8

1/2

5/8

3/4

Tube O.D.

Do

6.35

9.52

12.70

15.88

19.05

Class-2 (R-410A)

9.1

13.2

16.6

19.7

24.0

Class-1 (Conventional)

9.0

13.0

16.2

19.4

23.3

+0-0.4

Unit:mmA

Dimension A

For class-1: R-407CFor class-2: R-410A

204 Precautions for New Refrigerant (R-410A)

Page 211: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Precautions for New Refrigerant (R-410A)

2. Torque wrench

Specifications2 Dimension B Anytime

No change in tightening torqueNo change in pipes of other sizes

Differences2 Change of dimension B

Only 1/2", 5/8" are extended

3. Vacuum pump with check valve

Specifications2 Discharge speed Maximum degree of vacuum

50 l/min (50Hz) Select a vacuum pump which is able to keep60 l/min (60Hz) the vacuum degree of the system in excess of

2 Suction port UNF7/16-20 –14.6 psi (5 torr or 5000 micron or – 755 mmHg).(1/4 Flare)UNF1/2-20(5/16 Flare)with adapter

Nominal size Class-1 Class-2 Previous

1/2 24 26 24

5/8 27 29 27

Dimension B

For class-1: R-407CFor class-2: R-410A

Vacuum pump adapterReverse flow preventive vacuum adapter

Precautions for New Refrigerant (R-410A) 205

Page 212: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Precautions for New Refrigerant (R-410A) SiUS39-504

Differences2 Equipped with function to prevent reverse oil flow2 Previous vacuum pump can be used by installing adapter.

4. Leak tester

Specifications2 Hydrogen detecting type, etc.2 Applicable refrigerants

R-410A, R-407C, R-404A, R-507A, R-134a, etc.

Differences2 Previous testers detected chlorine. Since HFCs do not contain chlorine, new tester detects

hydrogen.

5. Refrigerant oil (Air compal)

Specifications2 Contains synthetic oil, therefore it can be used for piping work of every refrigerant cycle.2 Offers high rust resistance and stability over long period of time.

Differences2 Can be used for R-410A and R-22 units.

6. Gauge manifold for R-410A

206 Precautions for New Refrigerant (R-410A)

Page 213: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504 Precautions for New Refrigerant (R-410A)

Specifications2 High pressure gauge

- 0.1 to 5.3 MPa (-29.92 inHg to 738 psi)2 Low pressure gauge

- 0.1 to 3.8 MPa (-29.92 inHg to 530 psi)2 1/4" → 5/16" (2min → 2.5min)2 No oil is used in pressure test of gauges.

→ For prevention of contamination2 Temperature scale indicates the relationship between pressure and temperature in gas

saturated state.

Differences2 Change in pressure2 Change in service port diameter

7. Charge hose for R-410A

Specifications2 Working pressure 5.08 MPa (736 psi)2 Rupture pressure 25.4 MPa (3683 psi)2 Available with and without hand-operate valve that prevents refrigerant from outflow.

Differences2 Pressure proof hose2 Change in service port diameter2 Use of nylon coated material for HFC resistance

8. Weigher for refrigerant charge

Specifications2 High accuracy

TA101A (for 10-kg cylinder) = ± 2gTA101B (for 20-kg cylinder) = ± 5g

2 Equipped with pressure-resistant sight glass to check liquid refrigerant charging.2 A manifold with separate ports for HFCs and previous refrigerants is equipped as standard

accessories.

(Hose with ball valve)

Precautions for New Refrigerant (R-410A) 207

Page 214: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

Precautions for New Refrigerant (R-410A) SiUS39-504

Differences2 Measurement is based on weight to prevent change of mixing ratio during charging.

Regarding purchasing of service tools, please contact following address.Daikin U. S. Corporation (Dallas Office)1645 Wallace Dr, Ste 110 Carrollton, TX 75006“Tel : 1-972-245-1510 Fax : 1-972-245-1038”

208 Precautions for New Refrigerant (R-410A)

Page 215: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

IndexIndexIndexIndexSymbols“88” cannot be cleared from the central remote

controller .......................................................... 137

AAdditional Charge of Refrigerant............................... 41Additional Refrigerant Charge................................. 162Additional refrigerant charge operation setting ......... 87Air Flow Direction Setting.......................................... 77Air Tight Test............................................................. 32Airnet address ........................................................... 87Allowable Piping Length.......................................... 110Applicable range of Field setting ............................... 75

BBrazing ...................................................................... 25

CCapacity precedence setting..................................... 88Centralized Control Group No. Setting...................... 78Check Operation

Malfunction code ................................................ 68CHECK OPERATION FUNCTION.......................... 104Connectable Indoor Unit ............................................. 4Connectable Indoor Units Number and Capacity........ 4Connecting the Refrigerant Piping .......................... 152Continuous demand setting ...................................... 88Control Modes........................................................... 81Control Wiring ........................................................... 55Cool/Heat Mode Switching........................................ 91Cooling, Heating, and Fan Only Operation ............. 186Cracks develop in field pipes due to

thermal expansion and contraction .................. 135

DDefrost setting ........................................................... 87Demand setting ......................................................... 88dip switches............................................................... 83Drain Pipe Gradient and Support .............................. 43Drain pipe trap shape defective .............................. 132Drain Pipe Work (Indoor) .......................................... 43Drain Trap ................................................................. 43

EElectrical Specifications .......................................... 146Electrical Work .......................................................... 55Excessive noise due to incorrect angling of

REFNET joints ................................................. 134External Appearance................................................... 3External low noise/demand setting ........................... 87

FField Setting...............................................................71Field Setting from Outdoor Unit .................................83Flange Connection.....................................................30Flare Connection .......................................................26Flaring Procedure ......................................................28

GGrouped Drain Piping ................................................44

HHand Over to Customer...........................................107High static pressure setting .......................................87

IIndoor Unit Capacity ....................................................4Installation..................................................................12Installation of Indoor Unit ...........................................14Installation of Outdoor Unit ........................................62

LLeak Test and Vacuum Drying ................................159Local setting switch....................................................70Low Noise Operation and Demand Operation...........96Low noise setting .......................................................88

MMicrocomputer normal monitor ..................................70Mismatch between cables connecting indoor and

outdoor units and corresponding piping ...........131Mode setting switch ...................................................70Monitor mode.............................................................89

NNight-time low noise operation end setting................88Night-time low noise operation start setting...............88Night-time low noise setting.......................................87

OOperating Noise of Indoor Units ..............................108Operation Range .....................................................185Operation When Power is Turned On........................69Optional Parts ..........................................................164Outdoor Unit PC Board Layout ..................................70

Index i

Page 216: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

PPipe Insulation......................................................... 161Pipe size selection .................................................. 115Piping Diameter for Grouped Drain Pipes................. 45

Ceiling Mounted Built-in Type (FXSQ-M) ........... 48Ceiling Mounted Cassette Type

(FXFQ-M Multi-flow) .............................. 46Ceiling Mounted Duct Type (FXMQ-M) .............. 50

Piping System DiagramsIndoor Unit ........................................................ 126Outdoor Unit ..................................................... 125

Power Supply ............................................................ 56Precautions for New Refrigerant (R-410A) ............. 202Precautions when laying power wiring .................... 167Pressure down despite absence of

leaks during air tight test .................................. 133Program Dry Operation ........................................... 188Programming Start and Stop of

the System with Timer ..................................... 191

RR-410A.................................................................... 202REFNET Header ............................... 23, 119, 120, 134REFNET Joint ................................... 23, 118, 120, 134Refrigerant Additional Charging Operation ............. 102Refrigerant Leaks............................................ 105, 174Refrigerant Pipe Work............................................... 19Refrigerant Piping ................................................... 152Refrigerant recovery / vacuuming mode setting........ 87

SSelection of Location......................................... 59, 148Selection of Piping Material..................................... 152Sequential operation setting...................................... 87Service Space ........................................................... 60Service Tools .......................................................... 203Set mode display (LED) ............................................ 70Setting Contents and Code No. ................................ 74Setting mode 1 .......................................................... 85Setting mode 2 .......................................................... 86Setting Modes

Auto Restart after Power Failure Reset .............. 76Fan Speed Changeover When

Thermostat is OFF................................. 76Filter Sign Setting ............................................... 76Ultra-Long-Life Filter Sign Setting....................... 76

Setting of Operation Control Mode............................ 81Setting the Master Remote Controller..................... 192Signal interference due to use of

multiple core cable ........................................... 130Sleeve and Insert Work............................................. 13Step by Step Installation Procedure.......................... 12

TTechnical Specifications ..........................................146Test Operation

Procedure and Outline ........................................66Test Run ..................................................................171The centralized control group number

cannot be set ....................................................136Thermal Insulation Work............................................31Transmission wiring between the cool/

heat selector and the outdoor unit istoo close to a high voltage wire ........................136

VVacuum Drying ..........................................................35Vacuuming Mode.....................................................104VRV Inspection Sheet..............................................121

WWiring Diagram........................................................127

ii Index

Page 217: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

Drawings & Flow ChartsDrawings & Flow ChartsDrawings & Flow ChartsDrawings & Flow Charts

Symbols“88” cannot be cleared from the central remote

controller .......................................................... 137

Aa free flow of air back and forth.......................106, 175Additional Charge of Refrigerant

Operational steps ............................................... 41Refrigerant Charging Instructions....................... 41Siphon tube ........................................................ 42

Additional refrigerant charge total flow.................... 102Adjusting the Air Flow Direction .............................. 189Air Tight Test

Checking for Leaks............................................. 33Compensating adjustment value ........................ 33Operational steps ............................................... 32

Air tight test and vacuum drying.............................. 159Allowable Piping Length.......................................... 110Avoid reduction of airflow and short circuiting............. 5

BBranch with Refnet Header ..................................... 112Branch with Refnet Joint and Refnet Header.......... 111branches ................................................................. 168Brazing ...................................................................... 25BRC4C Type ............................................................. 79BRC7C Type ............................................................. 79BRC7E Type ............................................................. 79

CCalculate the Additional Refrigerant

to be Charged .................................................. 116Calculating Operating Noise ................................... 109Calibration method .................................................... 38Ceiling Mounted Built-in Type (FXSQ-M)

drain hose........................................................... 48Drain Piping ........................................................ 48DRAIN RAISING PIPING.................................... 48drainage flow ...................................................... 49ELECTRIC WIRING WORK ............................... 49multiple drain pipes............................................. 49

Ceiling Mounted Cassette Type (FXFQ-M Multi-flow)DRAIN RAISING PIPING.................................... 46Indoor drain pipe................................................. 46multiple drain pipes............................................. 46Rig drain piping................................................... 46Terminal box lid .................................................. 47

Ceiling Mounted Duct Type (FXMQ-M)..................... 50Centralized Control Group No. Setting

BRC1C Type ...................................................... 78Group No. Setting Example................................ 80

Change of dimension A ...........................................204Change of dimension B ...........................................205Check Operation........................................................67CHECK OPERATION FUNCTION ..........................104Check points ................................................................9Check Work Prior to Turn Power Supply on ..............66Choice of Materials for Refrigerant Piping .................23Coat the flange sheet surface with

refrigeration oil ....................................................30Coat the inner and outer surface of the flare with

refrigerator oil .....................................................26Connecting the Refrigerant Piping

Front connection ...............................................153local branch piping ............................................152Side (bottom) connection ..................................153

connecting wiring .....................................................167Contents of Control Modes

How to Select Operation Mode ...........................82Contract Drawing .........................................................9Control circuit diagram...............................................11Cool / Heat Mode Switching

Address setting ...................................................95Set Cool / Heat by Cool /

Heat Switching Remote Controller .........94Set Cool / Heat by Indoor Unit Remote

Controller................................................93Set Cool / Heat Separately by Cool /

Heat Switching Remote Controller .........92Set Cool/Heat Separately by Indoor Unit

Remote Controller ..................................91Cooling, Heating, and Fan Only Operation..............186Correlation of nozzle tip and size of

refrigeration piping..............................................24Covering of Refrigerant Pipes

Particular care .....................................................21Pinching method .................................................21Taping method ....................................................21

Cracks develop in field pipes due tothermal expansion and contraction...................135

DDegree of vacuum .....................................................37Drain pipe trap shape defective ...............................132Drain Pipe Work (Indoor)

Drain Pipe Gradient and Support ........................43Drain Trap ...........................................................43Grouped Drain Piping..........................................44Operational steps ................................................43Use of an Auxiliary Drain Hose (Flexible) ...........44

Duct Work (Indoor)Operational steps ................................................58

Drawings & Flow Charts iii

Page 218: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

Taking Account of Noise and Vibration .............. 58

EElectrical Work

a PCB for remote control, multiple core cable must not be used............................................ 56

Choosing a circuit breaker .................................. 56Earthing .............................................................. 57When cable more than 1.25 mm² is used........... 55

electronic noise .................................................60, 149example in case of refnet joint B .....................113, 114example in case of refnet joint C.....................113, 114example in the case of refnet header..............113, 114Example of Connection ........................................... 157Excessive noise due to incorrect angling of

REFNET joints ................................................. 134

FField line connection ............................................... 166

transmission wiring and cool/heat selection ..... 168Field Setting from Outdoor Unit

Mode changing procedure.................................. 84Setting by dip switches ....................................... 83

fill a tank with a siphon attached ............................. 162Flare Gauge .............................................................. 26flare shape .............................................................. 161Flaring Procedure...................................................... 28FOR RXYQ SERIES ............................................... 192FOR SYSTEMS WITH COOL/HEAT CHANGEOVER

REMOTE CONTROL SWITCH................187, 189

HHand Over to Customer

Important Points ............................................... 107Make the service contact address clear ........... 107Operational Steps............................................. 107

How these installation problems affect anequipment ............................................................ 7

How to choose an outdoor branch kit...................... 114How to select the refnet header .............................. 114How to select the refnet joint................................... 113

IInspecting and Handling the Unit ......................61, 150Installation of Indoor Unit

Operational steps ............................................... 14Positioning .......................................................... 15

Installation of Outdoor UnitBolt pitch............................................................. 62Operational steps ............................................... 62

Kknock holes ............................................................. 154

LLeak Test and Vacuum Drying................................ 159

MMaximum concentration level ......................... 105, 174Mismatch between cables connecting indoor and

outdoor units and corresponding piping ...........131Monitor mode.............................................................89Mount the REFNET header .....................................154Mount the REFNET joint..........................................154MOVEMENT OF THE AIR FLOW FLAP .................190

NNames and functions of parts ..................................182

OOil-equalizing line (Only for multiple outdoor units

installed) (part C) ..............................................115Other ways of filling the tank....................................162Outdoor Unit PC Board Layout ..................................70

PPicking power line and transmission line .................169Pipe Insulation .........................................................161Pipe size

Between refrigerant branch kit andindoor unit ............................................115

Piping between outdoor unit andrefrigerant branch kit ............................115

Piping between refrigerant branch kits ..............115Piping between outdoor branch and outdoor unit

(part B)..............................................................115Piping System Diagrams

FXFQ, FXSQ, FXMQ, FXHQ, FXAQ, FXLQ, FXNQ ...................................................126

Indoor Unit.........................................................126RXYQ96MTJU ..................................................125

Positioning of indoor unit .............................................6Positioning of outdoor unit ...........................................5Power supply connection.........................................171Precautions when connecting the ground................167Precautions when knocking out knock holes ...........170Precautions when selecting branch piping ..............155Pressure down despite absence of

leaks during air tight test...................................133pressure regulator for the nitrogen ..........................154Procedures for charging additional refrigerant.........163Program Dry Operation............................................188Programming Start and Stop of the

System with Timer ............................................191

RREFNET Header..................................... 119, 120, 134REFNET Joint......................................... 118, 120, 134Refrigerant Pipe Flushing

Fit blanking plugs ................................................22Flushing...............................................................23Open the main valve on the nitrogen cylinder and

set the pressure regulator to 72psi.........22Set pressure regulator on nitrogen cylinder ........22

iv Drawings & Flow Charts

Page 219: R-410A Heat Pump 60Hz - daikinac.com HP 96and192 HP_Design... · Design, Installation & Testing Instruction R-410A Heat Pump 60Hz RXYQ96MTJU RXYQ192MTJU SiUS39-504 Design, Installation

SiUS39-504

Refrigerant Pipe WorkAir tight ............................................................... 19Clean .................................................................. 19Dry ...................................................................... 19Operational steps ............................................... 19The 3 Principles of Refrigerant Piping ................ 19

Remote Controller and Changeover Switch............ 183

SSelection of Location.........................................59, 148Service Space ........................................................... 60Service Space for Indoor Units ................................. 16Set the flaring tool ..................................................... 26Setting mode 1 .......................................................... 85Setting mode 2 .......................................................... 86Setting of Air Flow Direction Adjustment Range ....... 77Setting of Demand Operation

Image of operation in the case of A.................... 99Image of operation in the case of A and B ......... 99Image of operation in the case of B.................... 99

Setting of Low Noise OperationImage of operation in the case of A.................... 97Image of operation in the case of A, B ............... 97Image of operation in the case of B.................... 97

Setting the cool/heat operationcool/heat setting with the cool/heat selector ..... 169cool/heat setting with the remote controller ...... 169

Setting the Master Remote Controller..................... 192setting the timer off and on...................................... 191Signal interference due to use of

multiple core cable ........................................... 130Simplified Remote Controller .................................... 73

BRC2A71............................................................ 73Sleeve and Insert Work

Operational steps ............................................... 13Steel insert.......................................................... 14Through holes in a reinforced

concrete beam....................................... 13Sound pressure rise due to room reverberation...... 108spanner and torque wrench .................................... 160Special vacuum drying .............................................. 40Standard Operation Limit ........................................ 144Standard Supplied Accessories .............................. 145standard work practice for all brazing work............... 20Step by Step Installation Procedure.......................... 12Striking a Balance between System Installation and

General Construction Work.................................. 8System example...................................................... 165

TTest Operation

Procedure and Outline........................................ 66The analysis of major installation problems

experienced ......................................................... 7The centralized control group number

cannot be set ................................................... 136The use of “hard solder” is essential ......................... 24

Thermal Insulation Work (Refrigerant Piping)Essential Points of Thermal Insulation ................31Operational steps ................................................31

Tighten the bolts in opposite corners first toensure that the connection is true ......................30

Transmission wiring between the cool/heat selector and the outdoor unit is tooclose to a high voltage wire ..............................136

Trouble Shooting .....................................................198Turn Power on ...........................................................66

UUnpacking and Placing the Unit........................ 63, 151

Caution label .......................................................65DO NOT USE STANDS TO SUPPORT THE

CORNERS .................................... 63, 151foundation bolts.................................................151passing piping out through the front........... 64, 151

VVacuum Drying ..........................................................35Vacuum Drying Procedure.........................................39VRV Inspection Sheet..............................................121

WWhere there are no smaller

room divisions.......................................... 106, 174Wired Remote Controller ...........................................71Wireless Remote Controller - Indoor Unit ..................72Wiring Diagrams

Field Wiring .......................................................128Outdoor Unit ......................................................127

wiring from the indoor units......................................170